The 3500/45 Position Monitor is a 4-channel instrument that
accepts input from proximity transducers, Rotary Position
Transducers (RPTs), DC Linear Variable Differential
Transformers (DC LVDTs), AC Linear Variable Differential
Transformers (AC LVDTs), and rotary potentiometers. The
monitor conditions the input and compares the conditioned
signals with user-programmable alarms.
The type of measurement and transducer input
determine which I/O modules are required. See
Transducer Types for Position Measurements on
page10., See Figures and Graphs on page12., and See
I/O Modules for AC LVDTs and Rotary Potentimeters on
page14.
You can program each channel using the 3500 Rack
Configuration Software to perform the following functions:
141537 Rev. H
l Axial (thrust) Position
l Differential Expansion
l Standard Single Ramp Differential Expansion
l Non-standard Single Ramp Differential Expansion
l Dual Ramp Differential Expansion
l Complementary Differential Expansion
l Case Expansion
l Valve Position
The monitor channels are programmed in pairs and
can perform up to two of these functions at a time. For
example, Channels 1 and 2 can perform one function
while channels 3 and 4 may perform the same or a
different function.
Page 2
3500/45 Position Monitor
Datasheet141537 Rev. H
The primary purpose of the 3500/45 Position
Monitor is to provide the following:
l Machinery protection by continuously
comparing monitored parameters
against configured alarm setpoints to
drive alarms
l Essential machine information for
operations and maintenance personnel
Each channel, depending on configuration,
typically conditions its input signal to generate
various parameters called measured variables. You can establish alert setpoints for
each active measured variable and danger setpoints for any two of the active measured
variables.
2/19
Page 3
3500/45 Position Monitor
Datasheet141537 Rev. H
3.94 mV/V/mm (0.10 mV/V/mil)
Specifications
Inputs
SignalAccepts from 1 to 4 signal inputs
7.7 watts, typical, using Position
I/O,
or
Rotary
Potentiometer
Valve Position
Rotary Position
Transducer (RPT)
Valve Position
or
3.15 mV/V/mm (0.08 mV/V/mil)
41 mV/degree rotation
140 mV/deg rotation,
70 mV/deg rotation or
50 mV/deg rotation
Indicates when the 3500/45 Position
Monitor is operating properly.
Indicates when the 3500/45 Position
Monitor is communicating with other
modules in the 3500 rack.
Indicates when the 3500/45 Position
Monitor is in Bypass Mode.
Transducer Power Supply
Sensitivity
Thrust
Differential
Expansion
Ramp Differential
Expansion
Complementary
Input Differential
Expansion
DC LVDT Case
Expansion
AC LVDT Case
Expansion
AC LVDT Valve
Position
3.94 mV/μm (100 mV/mil) or
7.87 mV/μm (200 mV/mil)
0.394 mV/μm (10 mV/mil) or
0.787 mV/μm (20 mV/mil)
0.394 V/mm (10 mV/mil),
0.787 V/mm (20 mV/mil),
3.937 V/mm (100 mV/mil) or
7.874 V/mm (200 mV/mil)
0.394 V/mm (10 mV/mil),
0.787 V/mm (20 mV/mil) or
3.937 V/mm (100 mV/mil)
0.05 V/mm (1.25 V/in),
0.08 V/mm (1.90 V/in),
0.10 V/mm (2.50 V/in),
0.18 V/mm (4.50 V/in),
0.20 V/mm (5.00 V/in) or
0.22 V/mm (5.70 V/in)
28.74 mV/V/mm (0.73
mV/V/mil),
15.35 mV/V/mm (0.39 mV/V/mil)
or
9.45 mV/V/mm (0.24 mV/V/mil)
28.74 mV/V/mm (0.73
mV/V/mil)
15.35 mV/V/mm (0.39
mV/V/mil),
9.45 mV/V/mm (0.24 mV/V/mil),
10.24 mV/V/mm (0.26
mV/V/mil),
7.48 mV/V/mm (0.19 mV/V/mil),
5.51 mV/V/mm (0.14 mV/V/mil),
Proximitor or
RPT
DC LVDT+15 Vdc
AC LVDT2.3Vrms 3400Hz sine wave
Rotary
Potentiometer
Recorder
Voltage
Compliance
(current
output)
Resolution
-24 Vdc
-12.38 Vdc
+4 to +20 mA
Values are proportional to monitor
full-scale.
The monitor provides individual
recorder values for each channel
except Ramp and CIDE.
Monitor operation is unaffected by
short circuits on recorder outputs.
0 to +12 Vdc range across load
Load resistance is 0 to 600 Ω.
0.3662 µA per bit
±0.25% error at room temperature
±0.7% error over temperature range
Update rate 100 ms or less
3/19
Page 4
3500/45 Position Monitor
Datasheet141537 Rev. H
Signal Conditioning
Specified at +25 ºC (+77 ºF) unless
otherwise noted.
Thrust and Differential Expansion
Within ±0.33% of full-scale
Accuracy
Frequency Response
Direct filter-3 dB at 1.2 Hz
Gap filter-3 dB at 0.41 Hz
Ramp Differential Expansion
Accuracy
Frequency Response
Direct filter-3 dB at 1.2 Hz
Gap filter-3 dB at 0.41 Hz
typical
±1% maximum
See Ramp Differential Expansion
Accuracy on page11.
Valve Position
Within ±0.33% of full-scale
Accuracy
Frequency Response
Direct filter-3 dB at 1.2 Hz
Gap filter-3 dB at 0.41 Hz
typical
±1% maximum
Physical
Monitor Module (Main Board)
Dimensions
(Height x Width x
Depth)
Weight0.91 kg (2.0 lb)
I/O Modules
Dimensions
(Height x Width x
Depth)
Weight0.20 kg (0.44 lb)
241.3 mm x 24.4 mm x 241.8
mm
(9.50 in x 0.96 in x 9.52 in)
241.3 mm x 24.4 mm x 99.1
mm
(9.50 in x 0.96 in x 3.90 in)
Rack Space Requirements
Complimentary Input Differential
Expansion (CIDE)
Within ±0.33% of full-scale
Accuracy
Frequency Response
Direct filter-3 dB at 1.2 Hz
Gap filter-3 dB at 0.41 Hz
typical
±1% maximum
Case Expansion
Within ±0.33% of full-scale
Accuracy
Frequency Response
Direct filter-3 dB at 1.2 Hz
Gap filter-3 dB at 0.41 Hz
typical
±1% maximum
Monitor Module1 full-height front slot
I/O Modules1 full-height rear slot
Alarms
Use the 3500 Rack Configuration
Software to set alert and danger
levels for the direct values
measured by the monitor.
Alarm Setpoints
Accuracy of
alarm setpoints
Alarms are adjustable from 0 to
100% of full-scale for each
measured value. However, when
the full-scale range exceeds the
range of the transducer, the
range of the transducer will limit
the setpoint.
Within 0.13% of the desired value
4/19
Page 5
3500/45 Position Monitor
Datasheet141537 Rev. H
Alarm Time Delays
You can program alarm delays using
the 3500 Rack Configuration Software
from one to 60 seconds in one second
intervals.
Alert
Danger
From one to 60 seconds in one
second intervals
0.1 seconds or from one to 60
seconds in 0.1 second intervals
Measured Variables
Position measurements are used for
machine protection and condition
monitoring. The 3500/45 Position
Monitor returns values for the following
measured variables depending on
configuration.
Thrust Position
Differential
expansion
Ramp Differential
Expansion
CIDE
Case expansion
Value positionDirect and position
Direct
Gap
Direct
Gap
Composite
Direct
Gap
Composite
Direct
Gap
Composite
Direct and position
Environmental Limits
When used with Internal/External
Operating
Temperature
Storage
Temperature
Humidity
Termination I/O Module:
-30°C to +65°C
(-22°F to +150°F)
-40°C to +85°C
(-40°F to +185°F)
95%
Non-condensing
5/19
Page 6
3500/45 Position Monitor
Datasheet141537 Rev. H
Firmware and Software
Requirements
When adding the 3500/45 Position Monitor to
an existing 3500 system, the following firmware
and software versions or later are required:
l 3500/20 RIM Firmware rev. G
l 3500 Configuration Software 2.41
l 3500 Data Acquisition 2.20
l 3500 Operator Display 1.20
l 3500/93 Display Interface Module 135799-
01
l Firmware rev. G
l For Valve Position using RPT, you must
have 3500 Configuration Software 3.00 or
greater.
6/19
Page 7
3500/45 Position Monitor
Datasheet141537 Rev. H
Hazardous Area Approvals
Compliance and
Certifications
FCC
This device complies with part 15 of the
FCC Rules. Operation is subject to the
following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including
interference that may cause
undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for
Industrial Environments
EN 61000-6-4 Emissions for
Industrial Environments
Electrical Safety
For the detailed listing of country and product
specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4
Gc;
Class I, Zone 2: AEx/Ex ec nC ic IIC T4
Gc;
Class I, Division 2, Groups A, B, C,
and D;
T4 @ Ta= -20˚C to +65˚C (-4˚F to
+149˚F)
When installed per drawing 149243
or 149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc
Ex ec nC ic IIC T4/T5 Gc
T4 @ Ta= -20˚C to +65˚C
(-4˚F to +149˚F)
When installed per drawing 149243
or 149244.
European Community Directive:
LV Directive 2014/35/EU
Standards:
EN 61010-1
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships,
Offshore Units, and High Speed and Light
Craft
7/19
Page 8
3500/45 Position Monitor
Datasheet141537 Rev. H
Ordering Information
For the detailed listing of country and product
specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
Position Monitor
3500/45 - AA-BB
A: I/O Module Type
Position I/O Module with Internal Terminations
01
(Proximitor, RPT, DC LVDT)
Position I/O Module with External Terminations
02
(Proximitor, RPT, DC LVDT)
Discrete TMR Position I/O Module with External
03
Terminations (Proximitor or DC LVDT)
Bussed TMR Position I/O Module with External
04
Terminations (Proximitor)
AC LVDT Position I/O Module with Internal
05
Terminations
AC LVDT Position I/O Module with External
06
Terminations
Rotary Potentiometer Position I/O Module with
07
Internal Terminations
Rotary Potentiometer Position I/O Module with
You must order external termination blocks and
cables separately for each I/O module with
external termination.
When using the 3500/45 Position Monitor in a
TMR application, valve position measurement
are not available, and case expansion
measurements are only supported for Discrete
TMR.
Ramp angles 4 - 70
degrees
Less than 3 Vdc fullscale span
11/19
Page 12
3500/45 Position Monitor
Datasheet141537 Rev. H
Figures and Graphs
1. Front View of 3500/45 Position Monitor
2. Status LEDs
3. Buffered Transducer Outputs
4. Rear Views of I/O Modules with Proximitors, Rotary Position
Tranducers or DC LVDTs.
5. Position I/O Module, Internal Termination, for Use with
Proximitors, Rotary Position Transducers, or DC LVDTs
6. Position I/O Module, External Termination, for Use with
Proximitors, Rotary Position Transducers, or DC LVDTs
7. Position I/O Module, TMR Discrete, External Termination, for
Figure 1: Front and Rear Views of 3500/45 Position Monitor and I/O modules for use with
Proximitor, Rotary Position Transducer and DC LVDT I/Os
12/19
Page 13
3500/45 Position Monitor
Datasheet141537 Rev. H
Figure 2: Side View of I/O Modules
The I/O modules with internal or external terminations have the same jumpers.
13/19
Page 14
3500/45 Position Monitor
Datasheet141537 Rev. H
1. Rear Views of I/O Modules Used with AC LVDTs
2. Position I/O Module, Internal Termination, for Use with AC
LVDTs
3. Position I/O Module, External Termination, for Use with AC
LVDTs
4. Rear Views of I/O Modules Used with Rotary
Potentiometers
5. Position I/O Module, Internal Termination, for Use with
Rotary Potentiometers
6. Position I/O Module, External Termination, for Use with
Rotary Potentiometers
Figure 3: I/O Modules for AC LVDTs and Rotary Potentimeters
14/19
Page 15
3500/45 Position Monitor
Datasheet141537 Rev. H
Thrust and Valve Positions
Thrust Position
The following picture depicts the axial position of the rotor with respect to the thrust bearing or some
fixed reference:
Valve Position
The following picture depicts the relative measurement of the position of a process inlet valve stem
based on its full stroke, or the relative measurement of the rotational position of a cam shaft based on
its full rotation:
Differential Expansion
The following picture depicts shaft growth relative to the machine case:
15/19
Page 16
3500/45 Position Monitor
Datasheet141537 Rev. H
The following picture depicts standard single ramp differential expansion:
16/19
Page 17
3500/45 Position Monitor
Datasheet141537 Rev. H
The following picture depicts non-standard single ramp differential expansion:
The following picture depicts a dual ramp differential expansion:
The following image depicts a complementary input differential expansion (CIDE) which uses a
combination of two probes to increase the measurement range to twice the range of a single proble:
17/19
Page 18
3500/45 Position Monitor
Datasheet141537 Rev. H
Case Expansion
The following picture depicts a single case expansion which is the measurement of the machine casing
growth relative to its foundation:
The following picture depicts a dual case expansion:
18/19
Page 19
3500/45 Position Monitor
Datasheet141537 Rev. H
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada, Orbit Logo and Proximitor are registered trademarks of Bently Nevada, a Baker Hughes Business, in
the United States and other countries. The Baker Hughes logo is a trademark of Baker Hughes Company. All other
product and company names are trademarks of their respective holders. Use of the trademarks does not imply any
affiliation with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does
not make any representation as to the accuracy or completeness of the information and makes no warranties of
any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and
fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect,
consequential or special damages, claims for lost profits, or third party claims arising from the use of the
information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make
changes in specifications and features shown herein, or discontinue the product described at any time without
notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of BakerHughes and its affiliates; and is subject to
change without prior notice. It is being supplied as a service to our customers and may not be altered or its content
repackaged without the express written consent of Baker Hughes. This product or associated products may be
covered by one or more patents. See Bently.com/legal.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 or 1.800.227.5514 (US only)
Bently.com
19/19