Bently Nevada 3500/15 Data sheet

3500/15 AC and DC Power Supplies
Datasheet
Bently Nevada Machinery Condition Monitoring

Description

The 3500/15 AC and DC Power Supplies are half-height modules and must be installed in designated slots on the left side of the rack. The 3500 rack can contain one or two power supplies with any combinations of AC and DC. Either supply can power a full rack.
When two power supplies are installed in a rack, the one in the lower slot acts as the primary supply, and the other in the upper slot acts as the backup supply. If installed, the second supply is the backup for the primary one.
The 3500/15 AC and DC Power Supplies accepts a wide range of input voltages and converts them to voltages acceptable for use by other 3500 modules. The following power supplies are available with the 3500 Series Machinery Protection System:
l Universal AC Power
l High Voltage DC Power Supply
l Low Voltage DC Power Supply
141530 Rev. L
The Universal AC Power Supply and PIM (Power Input Module) are not compatible with the Legacy 3500 AC Power Supply, High Voltage AC PIM and Low Voltage AC PIM.
The High Voltage and Low Voltage DC Power Supplies and PIM(Power Input Module) are NOT compatible with the Legacy 3500 High Voltage and Low Voltage DC Power Supplies and PIMs.
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L

Specifications

Inputs
Voltage Options
Universal Voltage AC
Description This option uses the universal AC
Power Supply and universal AC Power Input Module (PIM).
Input Voltage
Input Frequency
High Voltage DC
110 to 220 Vac nominal 85 to 264 Vac rms 120 to 373 Vac pk
The universal AC Power Supply and Power Input Module are not compatible with the legacy High Voltage AC or Low Voltage AC units.
47 to 63 Hz
voltage AC
High voltage DC2.5 A (maximum)
Low voltage DC11.0 A (maximum)
Description This option uses the High Voltage
DC Power Supply and the High Voltage DC Power Input Module (PIM).
Input voltage 88 to 140 Vdc
Low Voltage DC
Description This option uses the Low Voltage
DC Power Supply and the Low Voltage DC Power Supply Input Module (PIM).
Input voltage 20 to 30 Vdc
Current Information
Out of Range Protection
Full Rack Current Draw
For all power supply options, an under-voltage does not harm the supply or the PIM. An over-voltage causes the fuse to open on the PIM.
Universal 2.8 A rms (maximum)
2/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L
Outputs
Front Panel LEDs
Supply OK LED
Indicates when the power supply is operating properly
Physical
Power Supply Module
Dimensions (Height x width x depth)
Weight 1.39 kg
Power Input Modules
Dimensions (Height x width x depth)
120.7 mm x 50.8 mm x 251.5 mm
4.75 in x 2.0 in x 9.9 in
3.06 lb
120.7 mm x 25.4 mm x 114.3 mm
4.75 in x 1.0 in x 4.5 in
Storage temperature
Humidity 95%, non-condensing
-40 °C to +85 °C
-40 °F to +185 °F
Weight 0.34 kg
0.75 lb
Rack Space Requirements
Power supply module
Power input module
Two half-height slots are located on the left side of the rack. Each slot accommodates one power supply. Both slots can hold a power supply at the same time, allowing for redundant power supplies.
Special half-height module located directly behind the associated power supply
Miscellaneous
Minimum loading
No minimum rack load is required.
Environmental Limits
Operating temperature
-30 °C to +65 °C
-22 °F to +150 °F
3/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L

Compliance and Certifications

FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
l This device may not cause harmful
interference.
l This device must accept any interference
received, including interference that may cause undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for Industrial
Environments
EN 61000-6-4 Emissions for Industrial
Environments
Electrical Safety
European Community Directive:
LV Directive 2014/35/EU
Standards:
EN 61010-1

Hazardous Area Approvals

For the detailed listing of country and product specific approvals, refer to the
Quick Reference Guide
from Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D;
T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or
149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc Ex ec nC ic IIC T4/T5 Gc
T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or
149244.
(108M1756) available
Approvals
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships, Offshore Units, and High Speed and Light Craft
4/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L
Spares
Ordering Information
For the detailed listing of country and product specific approvals, refer to the
Quick Reference Guide
from Bently.com.
(108M1756) available
3500/15 Power Supply Module
3500/15 -AA-BB-CC
A: Power Supply Type (Top Slot)
03 Legacy High Voltage DC (88 to 140 Vdc)
04 Legacy Low Voltage DC (20 to 30 Vdc)
05 Universal AC Voltage (85 to 264 Vac rms)
06 High Voltage DC Supply
07 Low Voltage DC Supply
B: Power Supply Type (Bottom Slot)
00 No Supply (Used when no supply is required)
03 Legacy High Voltage DC (88 to 140 Vdc)
04 Legacy Low Voltage DC (20 to 30 Vdc)
05 Universal AC Voltage (85 to 264 Vac rms)
06 High Voltage DC Supply
07 Low Voltage DC Supply
C: Agency Approval
00 None
Approvals
Part Number Description
106M1079-01 Universal AC Power Supply Module
106M1081-01 Universal AC Power Input Module
129486-01 Legacy High Voltage DC Power
Supply Module
129478-01 Legacy High Voltage DC Power Input
Module
133292-01 Legacy Low Voltage DC Power
Supply Module
133300-01 Legacy Low Voltage DC Power Input
Module
114M5329-01 High Voltage DC Power Supply
115M7750-01 High Voltage DC PIM
114M5330-01 Low Voltage DC Power Supply
114M5335-01 Low Voltage DC PIM
01720025 Replacement Fuse (for both
AC Power Input Module and Legacy High Voltage DC Power Input Module)
01720045 Replacement Fuse (Low Voltage DC
Power Input Module and Legacy Low Voltage DC Power Input Module)
120M3877 Replacement Fuse
Fast blow rated at 5A/500 Vac Size 6.3 x 32 mm (Universal AC Power Input Module)
131150-01 Power Supply Blank Front Panel (qty
1, includes screws)
01 CSA / NRTL / C (Class 1, Division 2)
02 ATEX / IECEx / CSA (Class 1, Zone 2)
128085-01 Power Supply Rear Input Connector
Cover (qty 1) Order part 04310251 for screws.
04310251 Screw for Power Supply Input Cover
(qty 2)
129767 3500/15 Power Supply User Guide
118M0915-01 Replacement connector for Universal
AC Power Input Module
5/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L
Part Number Description
118M0915-02 Replacement connector for DC
Power Input Module
129M0198 Replacement fuse (High Voltage DC
Power PIM (Power input Module)
6/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L

Graphs and Figures

1. 3500/15 AC and DC Power Supplies OK LED
2. Legacy Low Voltage DC Power Input Module
3. Legacy High Voltage DC Power Input Module
4. Legacy High Voltage AC Power Input Module
5. Legacy Low Voltage AC Power Input Module
6. Universal AC Voltage Power Input Module
7. High Voltage DC Power Input Module
8. Low Voltage DC Power Input Module
Figure 1: 3500/15 Power Supply and PIMS
7/8
3500/15 AC and DC Power Supplies Datasheet 141530 Rev. L
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada and Orbit Logo are registered trademarks of Bently Nevada, a Baker Hughes Business, in the United States and other countries. The Baker Hughes logo is a trademark of Baker Hughes Company. All other product and company names are trademarks of their respective holders. Use of the trademarks does not imply any affiliation with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does not make any representation as to the accuracy or completeness of the information and makes no warranties of any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect, consequential or special damages, claims for lost profits, or third party claims arising from the use of the information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make changes in specifications and features shown herein, or discontinue the product described at any time without notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of Baker Hughes and its affiliates; and is subject to change without prior notice. It is being supplied as a service to our customers and may not be altered or its content repackaged without the express written consent of Baker Hughes. This product or associated products may be covered by one or more patents. See
Bently.com/legal.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 or 1.800.227.5514 (US only)
Bently.com
8/8
Loading...