Bently Nevada 1900/65A Specifications

Page 1
1900/65A General Purpose Equipment Monitor
Datasheet
Bently Nevada Machinery Condition Monitoring
Description
The 1900/65A General Purpose Equipment Monitor is designed to continuously monitor and protect equipment that is used in a variety of applications and industries. The monitor’s low cost makes it an ideal solution for general­purpose machines and processes that can benefit from continuous monitoring and protection.
Inputs
Outputs
The 1900/65A provides six relay outputs, four 4-20 mA recorder outputs, and a dedicated buffered output. The user can use the 1900 Configuration software to configure the relay contacts to open or close according to the OK, Alert and Danger statuses of any channel or combination of channels, and to provide data from any variable from any channel on any recorder output. The dedicated buffer output can provide the signal for each transducer input.
A Modbus Gateway option allows the monitor to provide static variables, statuses, event list, time and date information directly to any Modbus client, including Distributed Control Systems (DCSs), Supervisory Control and Data Acquisition (SCADA) systems, Programmable Logic Controllers (PLCs), or System 1 software. The monitor uses an internal counter and a Modbus client/master time reference to generate time and date information. Users can upgrade monitors without the Modbus Gateway by ordering the 1900/01 Communications Upgrade (see the Ordering Information section). The 1900/65A
Document : 173401
Rev. T
Page 2
1900/65A General Purpose Equipment Monitor Datasheet
supports Modbus communications via Ethernet and a software-configurable RS232/485 serial port.
Configuration
The user defines monitor operation and the Modbus Gateway register map by using software running on a laptop or PC to create a configuration file and download the file to the monitor through the built-in Ethernet connection. The 1900/65A permanently stores configuration information in non-volatile memory, and can upload this information to the PC for changes.
Display Module
The 1900/65A supports an optional display/keypad to view channel information or make minor configuration changes. This allows the 1900/65A to operate as a stand-alone package. If desired, the user can mount the display up to 75 metres (250 feet) from the Monitor Module.
2/22 173401 Rev. T
Page 3
1900/65A General Purpose Equipment Monitor Datasheet
processes up to four variables per channel.
Specifications

Inputs

Transducer Inputs
Users can configure Channels 1 through 4 to accept input from acceleration, velocity or displacement transducers.

Transducer Channel Types

Channel Types define the functionality for processing that will be applied to an input signal and the kind of variables or measurement values that will be derived from this input. Channel Types also define the kind of sensor that must be used. Transducer Channel Types include:
l Acceleration or Reciprocating
Acceleration l Velocity or Reciprocating Velocity l Radial Vibration (shaft vibration) l Thrust (shaft axial displacement) l Position l Speed
Vibration
Acceleration Enveloping
Bias Voltage
Up to three bandpass filtered amplitude measurements.
Users can apply the acceleration enveloping algorithm to one Acceleration or Reciprocating Acceleration Variable.
Users may assign the value of the transducer bias voltage to any of the variables.
Configuration Options
Each variable is independently configured with the following options.
Vibration Variables
Enveloped Variable
l Peak or RMS l Metric or English
l Filter corner
l Full scale range l Acceleration
l Filter corner
l Standard or
units
frequencies
integrated to velocity
frequencies
Enhanced demodulation
Acceleration and Reciprocating Acceleration Channel Types
The Acceleration Channel Type and Reciprocating Acceleration Channel Type support two- and three-wire acceleration sensors. The Reciprocating Acceleration channel type has timed OK channel defeat disabled.
Acceleration Variables and Reciprocating Acceleration Variables
Acceleration Variables and Reciprocating Acceleration Variables are filtered and processed measurements from raw transducer signals. The Acceleration Channel Type and Reciprocating Acceleration Channel Type continuously
Filters
Vibration Variable
Enveloping High-Pass
Enveloping Low-Pass
Enveloped Variable High­Pass
Enveloped Variable Low­Pass
Bias Filter 0.01 Hz 1-pole low-pass
OK Filter 2.4 kHz 1-pole low-pass
0.5 Hz – 25 kHz configurable 4-pole high­pass, 4-pole low-pass
25 Hz to 5 kHz, configurable 4-pole
125 Hz to 25 kHz, configurable 2-pole
0.1 Hz min., but greater than Enveloped Variable low-pass 2-pole
Greater than Enveloped Variable high-pass and less than Enveloping high-pass 4-pole
Full Scale Range
Vibration
20 to 500 m/s2 (2 to 50 g) peak
3/22 173401 Rev. T
Page 4
1900/65A General Purpose Equipment Monitor Datasheet
and RMS
Enveloped
Integrated
Bias Voltage -24 V
20 to 500 m/s2 (2 to 50 g) peak and RMS
10 to 100 mm/s (0.4 to 4 in/s) peak and RMS
Accuracy
Vibration Variables ±1% of full scale range
Input Impedance
3-wire Voltage Mode 10 kΩ

Velocity and Reciprocating Velocity Channel Type

The Velocity Channel Type and Reciprocating Velocity Channel Type support two-wire and three-wire piezo­velocity sensors.
units
l Filter corner
frequencies l Full-scale range l Velocity integrated
to displacement
Filters
Vibration Variables
Bias Filter 0.09 Hz 1-pole low-pass
OK Filter: 2.4 kHz 1-pole low-pass
0.5 Hz to 5.5 kHz, configurable 8-pole high­pass, 4-pole low-pass
Full Scale Range
Vibration 10 to 50 mm/s (0.5 to 2 in/s) peak and RMS
Integrated 100 to 500 μm (5 to 20 mils) peak to peak
Bias Voltage -24 V
Accuracy
Vibration Variables ±1% of full scale range
Input Impedance
Velocity Variables and Reciprocating Velocity Variables
Velocity Variables and Reciprocating Velocity Variables are filtered and processed measurements from raw transducer signals. The Velocity Channel Type and Reciprocating Velocity Channel Type support up to four continuously calculated variables per channel.
Vibration
Bias Voltage
Up to three bandpass filtered amplitude measurements.
Users may assign the value of the transducer bias voltage to any of the variables.
Configurable Options
Each variable is independently configured with the following options.
Vibration Variables
l Peak or RMS l Metric or English
3-Wire Voltage Mode 10 kΩ

Radial Vibration Channel Type

The Radial Vibration Channel Type measures radial shaft motion using proximity sensors.
Radial Vibration Variables
Radial Vibration Variables are filtered and processed measurements from raw transducer sensors. The Radial Vibration Channel Type supports up to four continuously calculated variables per channel.
Direct
Gap Gap voltage
Vibration
Configurable Options
Up to three bandpass filtered amplitude measurements
Up to three bandpass filtered amplitude measurements
4/22 173401 Rev. T
Page 5
1900/65A General Purpose Equipment Monitor Datasheet
Each variable is independently configured with the following options.
Vibration Variables
l Metric or English
units
l Filter corner
frequencies
l Number of filter
poles
l Full-scale range
Filters
Direct Filter 1 4 to 4000 Hz (240 to 240,000 RPM)
Direct Filter 2
Direct Filter Characteristics
Gap Filter 0.09 Hz 1-pole low-pass
Vibration Variables
OK Filter 2.4 kHz 1-pole low-pass
1 to 600 Hz (60 to 36,000 RPM)
High-pass set by attack and decay, 1-pole low-pass
0.5 Hz to 4 kHz, configurable
1-, 2-, or 4-pole high-pass and low-pass, configurable
Full Scale Range
Direct 100 to 500 μm (3 to 20 mils) peak-to-peak
Gap -24 V
transducer signals.
Position Axial position of shaft
Gap Gap, voltage or position
Configurable Options
Each variable is independently configured with the following options.
Position Variables
Metric or English units
Full-scale range
Filters
Direct Filter: 1.2 Hz 1-pole low-pass
Gap Filter 0.41 Hz 1-pole low-pass
OK Filter: 2.4 kHz 1-pole low-pass
Full Scale Range
Position
Gap -24 V
1 to 4 mm (50 to 150 mils) span with adjustable zero position
Accuracy
Position Variables ±1% of full-scale range
Accuracy
Vibration Variables ±1% of full-scale range
Input Impedance
Non-configurable 10 kΩ

Thrust Channel Type

The Thrust Channel Type measures axial shaft motion using proximity sensors.
Thrust Variables
Thrust Variables are filtered and processed measurements from raw
Input Impedance
Non-configurable 10 kΩ

Position Channel Type

The Position Channel Type measures mechanical motion using proximity sensors.
Position Variables
Position Variables are filtered and processed measurements from raw transducer signals.
Position Mechanical position
Gap Gap, voltage or position
Configurable Options
5/22 173401 Rev. T
Page 6
1900/65A General Purpose Equipment Monitor Datasheet
Each variable is independently configured with the following options.
Position Variables
Metric or English units
Full- scale range
Filters
Direct Filter 1.2 Hz 1-pole low-pass
Gap Filter 0.41 Hz 1-pole low-pass
OK Filter 2.4 kHz 1-pole low-pass
Full Scale Range
Position
Gap -24 V
1 to 28 mm (50 to 1100 mils) span with adjustable zero position.
Accuracy
Position Variables ±1% of full scale range
Input Impedance
Non-configurable 10 kΩ
Speed 100 - 100,000 rpm
Events Per Revolution
EPR 0.001 to 1000
Accuracy
Speed Variables: ± 0.5 RPM + 0.015% of reading
Input Impedance
Non-configurable 10 kΩ

Temperature Inputs (Ch. 5 – 8)

Channels 5 through 8 support Type E, J, K, and T thermocouples, and 2- and 3-wire RTDs.
Temperature Variable
Temperature variables are processed measurements from raw transducer signals. The temperature channel type processes one temperature variable per channel.

Speed Channel Type

The Speed Channel Type measures speed using proximity sensors.
Speed Variables
Speed Variables are filtered and processed measurements from raw transducer signals.
Speed Up to 4 speed measurements
Gap Gap, voltage
Configurable Options
Each variable is independently configured with the following options:
Gap Filter 0.09 Hz 1-pole low-pass
OK Filter 2.4 kHz 1-pole low-pass
Full Scale Range
Configurable Options
Each Variable is independently configured with the following options.
Units °C or °F
Filters
Analog Filter 50 Hz 1-pole, low-pass
Digital Filter
Notch filter will attenuate the first 5 orders of 50 Hz and 60 Hz (49 Hz to 61 Hz) by a minimum of 100 dB.
Full Scale Range
Type E -200 to 1000 ºC (-328 to 1832 ºF)
Type J -210 to 1200 ºC (-346 to 2192 ºF
Type K -200 to 1370 ºC (-328 to 2498 ºF)
Type T -200 to 400 ºC (-328 to 752 ºF)
10 Ω Cu α=0.00427
-200 to 260 ºC (-328 to 500 ºF)
6/22 173401 Rev. T
Page 7
1900/65A General Purpose Equipment Monitor Datasheet
120 Ω Ni α=0.00672
100 Ω Pt α=0.00385:
100 Ω Pt α=0.00392:
-80 to 260 ºC (-112 to 500 ºF)
-200 to 850 ºC (-328 to 1562 ºF)
-200 to 700 ºC (-328 to 1292 ºF)
Accuracy
All Thermocouple Types
3-Wire RTD (except 10 Ω Cu)
3-Wire RTD 10 Ω Cu
2-wire RTD Types
±1 °C (±1.8 °F) typical @ 25 °C (77 °F)
±2.5 °C (±4.5 °F) maximum for thermocouple measurements over –100 °C (148 °F)
±5 °C (±9 °F) maximum for thermocouple measurements below –100 °C (-148 °F)
±1.5 °C (±2.7 °F) + 0.5 % full scale
±3 °C (±5.4 °F) + 0.5 % full scale
2-wire RTDs have additional errors due to field wire resistance and variations in the field wire resistance due to changes in ambient temperature.
Input Impedance
Thermocouple Inputs >1 MΩ
or close contacts according to user­defined logic statements. Logic statements use the OK, Alert and Danger statuses of any channel, or combination of channels as inputs.
Logical Operators
AND bypassed channels ignored
True AND bypassed channels included
OR
Logical Operands
Monitor Inhibit
Monitor Not OK
Monitor Danger
Monitor Alert
Channel Not OK
Channel Danger
Channel Alert
Variable Danger
Variable Alert

Alarm Status Time Delays

Position/ Vibration Inputs
Minimum 0.1 second
Maximum 60 seconds
Adjustment Resolution 0.1 second
Temperature / Speed Inputs
Minimum 1 second
Maximum 60 seconds
Adjustment Resolution 0.1 second

Relays

Relay Logic
The 1900/65A monitor has six relay outputs that users can program to open
Maximum Operands
50 per relay

Relay Configuration

The following configuration options are independent of the relay logic and can be configured for each relay:
l Latching or non-latching
independent of alarm status
l Normally energized or normally de-
energized
l Normally open and normally closed
via contacts

Relay Specifications

Type
7/22 173401 Rev. T
Page 8
1900/65A General Purpose Equipment Monitor Datasheet
Single pole, double throw (SPDT)
Contact Ratings
Minimum Switched Current 12Vdc/100mA
DC specifications (resistive load)
Maximum Switched Current 5 A
Maximum Switched Power
Maximum SwitchedVoltage 60 Vdc
70W @ 24 Vdc
10W @ 48 Vdc
9W @ 60 Vdc
AC specifications (resistive load)
Maximum Switched Current 5 A
Maximum SwitchedPower 150 VA
Maximum SwitchedVoltage 30 Vac
 Refer to Hazardous Area Special Considerations Section for Relay specifications when used in hazardous area applications.
When configured for Trip Multiply short­circuiting the Inhibit/Trip Multiply contact to RTN will increase Alert and Danger set points.
When configured for Inhibit the Inhibit input will inhibit (bypass or inactivate) Alert and Danger statuses. Short circuiting the INHIBIT contact to INHIBIT RTN will:
l Set all Variable Danger Statuses to logic 0
l Set all Variable Alert Statuses to logic 0
l Set Bypass and Inhibit Statuses to logic 1
Monitor Alarm Inhibit switch, and Monitor Trip Multiply switch mapped in the Modbus Gateway will
remotely inhibit Alert and Danger statuses or activate Trip Multiply respectively. 
Electrical
Activate Inhibit 50 kΩ or less (shorted)
De-activate Inhibit 500 kΩ or greater (open)
Contact Life
100,000 cycles @ 5 A, 250 Vac
200,000 cycles @ 1 A, 24 Vdc
Sealing
Epoxy
Insulation Resistance
1000 MΩ minimum @ 500 Vdc

Inhibit, Reset, and Trip Multiply Inputs

Inhibit/Trip Multiply
Users can use software to configure the Inhibit/Trip Multiply input as either Inhibit or Trip Multiply.

Reset

Use the Reset input to reset all latched alarms and latched relays. If the condition driving the status no longer exists, short­circuiting the RESET contact to RESET RTN will:
l Reset all latched Alert statuses
l Reset all latched Danger statuses
l Reset all latched Not OK statuses
l Reset all latched relays
Writing a non-zero value to the Modbus register Reset Latched Statuses mapped in the Modbus Gateway will reset the monitor remotely. 
Electrical
Activate Reset 50 kΩ or less (shortened)
De-activate Reset 500 kΩ or greater (open)

Transducer Supplies

8/22 173401 Rev. T
Page 9
1900/65A General Purpose Equipment Monitor Datasheet
All outputs are short-circuit protected.
Two-Wire Current Mode
Current Source 3.3 mA ± 5%
Open Circuit Voltage 21 to 24 Vdc
Three-Wire Voltage Mode
Supply Voltage -24.02 Vdc to –23.47 Vdc
Maximum Rated Current 15 mA
Short Circuit Current 15.1 mA to 23.6 mA

4-20 mA Interface

Number of Outputs
Proportional Value
Loop Supply Voltage
Loop Resistance
Accuracy 2% over operating temperature range
Update Rate 100 mS
Resolution 10 mA
Clamp Current
Four outputs, any of which may be configured to provide data from any channel and any variable.
4 to 20 mA values are proportional to the channel full-scale.
18 to 36 Vdc
600 Ω maximum
2 mA ± 10% (configurable for Not OK and Bypass)

Buffered Outputs

Display Module
A single buffered output on the Display Module provides access to input Channels 1 through 4. The signal does not have gain, and is not scaled. This output is buffered to provide short circuit and EMI protection.
Output Impedance
Bandwidth
550 Ω
40 kHz minimum (Display Module attached directly to Monitor)
8 kHz minimum (75 m (250 ft.) of
cable)
Monitor Module
Each input for channels 1 through 4 has a dedicated buffered output. The signal does not have gain, and is not scaled. Each output is buffered to provided short circuit and EMI protection.
Output Impedance 550 Ω
Bandwidth 40 kHz minimum

Indicators

Monitor Module

Status LED

Indicates when the monitor is functioning properly.
Display Module
OK LED
Alert LED Indicates an Alert condition.
Danger LED Indicates a Danger condition.
Bypass LED
Trip Multiply LED
Channel LED Indicates channel is active.
Display Liquid Crystal Display (LCD) with backlight
Dimensions
Indicates when the monitor is functioning properly.
Indicates that the monitor is in Bypass mode.
Indicates that the monitor is in Trip Multiply mode.
68.6 mm (2.7 in) wide x 35.6 mm (1.4 in) high

Power Requirements

Input Voltage Range 18 to 36 Vdc
Operating Current 0.35 A typical, 1.0 A maximum
Operating Power 8.5 W typical, 14 W maximum
9/22 173401 Rev. T
Page 10
1900/65A General Purpose Equipment Monitor Datasheet

Physical

Monitor Module
Dimensions (L x W x H)
Weight 0.77 kg (1.70 lb)
196.9 mm x 149.4 mm x 74.4 mm (7.75 in x 5.88 in x 2.93 in)

Display Module

Dimensions (L x W x H)
Weight 0.40 kg (0.89 lb)
196.9 mm x 149.4 mm x 32.8 mm (7.75 in x 5.88 in x 1.29 in)

Mounting

DIN Rail Option
Bulkhead Option
Weatherproof Enclosure Option
35 mm DIN rail
Bulkhead mounting plate
NEMA 4X/IP66 Fiberglass Housing with window, 300.2 mm x 249.4 mm x 209.8 mm (11.82 in x 9.82 in x 8.26 in)

Configuration Software

The 1900 Configuration Software package contains everything necessary to install, configure, and maintain the 1900/65A monitor.
l Feature tools for installing and
troubleshooting l Simple display to help with configuration l Ability to browse network for 1900
monitors l Network configuration l Configuration for channels, variables,
setpoints, tag names, recorders and filters l Configuration for the optional Modbus
Gateway l Configuration for relays and relay voting
logic l Off-line configuration allowing use of
software when hardware is not available l Firmware upgrade function and
diagnostics
l Change bypass modes and setpoints on
the fly
l Display component for statuses and
variables
l Display Hardware Identification and
manufacturing information
l Context-specific help

Environmental

Temperature
Operating -20 to +70 ºC (-4 to +158 ºF)
Storage
-30 to +90 ºC (-22 to +194 ºF)
Humidity
Operating 95% non-condensing, maximum
Storage
95% non-condensing, maximum

Supported Transducers

Channel Type
Acceleration and Reciprocating Acceleration
Velocity and Reciprocating Velocity
Radial Vibration, Thrust, and Speed
Bently Nevada
Transducer
330400 Accelerometer
330425 Accelerometer
190501 Velomitor
330500 Velomitor
330525 Velomitor
330750 Velomitor
3300 5 & 8 mm Proximitor System
3300 XL 8mm Proximitor System
3300 XL 11mm Proximitor System
3300 XL NSv Proximitor System
7200 5 & 8mm Proximitor System
7200 11mm Proximitor System
7200 14 mm Proximitor System
10/22 173401 Rev. T
Page 11
1900/65A General Purpose Equipment Monitor Datasheet
3300 5 & 8 mm Proximitor System
3300 XL 8mm Proximitor System
3300 XL 11mm Proximitor System
3300 XL 25mm Proximitor System
Position
The 1900/65A provides default configuration settings for Bently Nevada transducers. The user can configure the 1900/65A to accept other transducers.
3300 XL 50mm Proximitor System
3300 XL NSv Proximitor System
7200 5 & 8mm Proximitor System
7200 11mm Proximitor System
7200 14 mm Proximitor System
11/22 173401 Rev. T
Page 12
1900/65A General Purpose Equipment Monitor Datasheet
Hazardous Area
Compliance and Certifications
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including interference that may cause undesired operation.
EMC
EN 61000-6-2: 2005
EN 61000-6-4: 2007 +A1:2001
EMC Directive 2014/30/EU

Electrical Safety

EN 61010-1: 2010
Approvals
For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from www.Bently.com.
This monitor is not certified for installation in Class 1 Div 1 locations, but it will support transducers installed in Div 1 locations via the use of galvanic isolators and barriers. If galvanic isolators are used, no change is necessary to the installation. A removable ground jumper allows the monitor to support zener barrier installations. Removing the jumper will disconnect circuit common from chassis at the monitor so that chassis can be connected at the barrier.

CSA/NRTL/C

Ex/ AEx nA nC IIC Gc: Class I, Zone 2: Class I, Division 2, Groups A, B, C, and D T4 @ -20°C [Ta [+70°C Vn = 18 to 36 Vdc @ Imax = 1A per drawing 173089 
LV Directive 2014/35/EU

ATEX

EN 60079-0: 2012
EN 60079-15: 2010
ATEX Directive 2014/34/EU

RoHS

RoHS Directive 2011/65/EU

Maritime

ABS 2009 Steel Vessels Rules
1-1-4/7.7,4-8-3/1.11.1,4-9-7/13

ATEX/IECEx

II 3 G
Ex nAC IIC T4 Gc  T4 @ Ta = -20°C [Ta [+70°C
Special Considerations
l Hazardous area installations require
relay contact voltages below 30 Vac rms, or 30 Vdc to minimize hazard.
l Hazardous area installations require
relay contact amperages below 5 Amps DC, or AC to minimize hazard.
12/22 173401 Rev. T
Page 13
1900/65A General Purpose Equipment Monitor Datasheet
Ordering Information
For a detailed listing of country- and product­specific approvals, refer to the Approvals Quick Reference Guide (document 108M1756) available from www.bently.com.

1900/65A General Purpose Equipment Monitor

1900/65A-AA-BB-CC-DD-EE
A: Power Option
00 18 to 36 Vdc
00 110 to 220 Vac @ 50 to 60 Hz (external supply)
B: Display Option
00 No display
01 Attached display (no cable)
02 Display with 10’ PVC cable
03 Display with 10’ unassembled PVC cable
04 Display with 10’ TEF cable
05 Display with 10’ unassembled TEF cable
C: Mounting Option
00 None
01 DIN rail mount
02 Bulkhead Mount
Fiberglass NEMA 4X/IP66 WP housing with window
03
in door
1900/55 replacement kit (See "1900/65A General
04
Purpose Equipment Monitor" above)*
ProTIM Housing, Wiring and Mounting
07
HardwareSee "ProTIM Housing Dimensions" on
page21
* Uses existing 1900/55 weather-proof housing and requires power option A01 (110/220 Vac to 24 Vdc external power supply)
00 None
01 Modbus communicationsw
Figure 1: DIN Rail Mount
Figure 2: Bulkhead Mount
D: Approvals Options
00 None
01 Multiple approvals
See Hazardous Areas Approvals section for specific certifications. Maritime approvals included with all approval options.
E: Communications Option
13/22 173401 Rev. T
Page 14
1900/65A General Purpose Equipment Monitor Datasheet
Figure 3:  NEMA 4X/IP66 WP Housing

1900/01 – 1900/65A General Communications Monitor, Communications Upgrade

1900/01-AA-BB-CC-DD
A: Order Type Option
01 New order (CD, key, and binder)
98 Replacement licenses (key)
99 Configuration Software only (CD)
B: Communications Option
01 Modbus comm.
C: License Key Type Option
00 None
01 USB license key
D: License Key Type Option
XX Total Licenses (1 to 99)
Figure 4:  1900/55 Replacement Kit
14/22 173401 Rev. T
Page 15
1900/65A General Purpose Equipment Monitor Datasheet
Graphs and Figures
Note: All dimensions shown in millimeters (inches) except as noted.
Figure 1:  Monitor Module Dimensions
15/22 173401 Rev. T
Page 16
1900/65A General Purpose Equipment Monitor Datasheet
Figure 2:  Display Module Dimensions
16/22 173401 Rev. T
Page 17
1900/65A General Purpose Equipment Monitor Datasheet
Figure 3: Combined Dimensions
17/22 173401 Rev. T

Page 18
1900/65A General Purpose Equipment Monitor Datasheet
Figure 4: Weatherproof Housing Dimensions
18/22 173401 Rev. T
Page 19
1900/65A General Purpose Equipment Monitor Datasheet
Figure 5:  Weatherproof Door Drill Pattern
19/22 173401 Rev. T
Page 20
1900/65A General Purpose Equipment Monitor Datasheet
Figure 6: Weatherproof Door Dimensions
20/22 173401 Rev. T
Page 21
1900/65A General Purpose Equipment Monitor Datasheet
Figure 7: ProTIM Housing Dimensions
21/22 173401 Rev. T
Page 22
1900/65A General Purpose Equipment Monitor Datasheet
Copyright 2019 Baker Hughes, a GE company, LLC ("BHGE") All rights reserved.
Bently Nevada, Orbit Logo, Proximitor, Velomitor and System 1 are registered trademarks of BHGE in
the United States and other countries. All product and company names are trademarks of their
respective holders. Use of the trademarks does not imply any affiliation with or endorsement by the
respective holders. This product may be covered by one or more patents, please see Bently.com/legal
for current status. The information contained in this document is subject to change without prior
notice.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 Bently.com
22/22 173401 Rev. T
Loading...