BECKHOFF KL2612 User Manual

KL2612
2-Channel 125 V AC Relay Output Terminal Configuration Instructions
Version 1.1 2006-20-23
Datasheet for KL2612, Version 1.1
Top view
KL2612
3
7
Introduction KL2612
13
14
A B
C D
1
5
Signal ­LED2
LED display
Process data
OUT
OUT
power contact
IN
2 6
5
6
OUT
1
2
IN
3
7
OUT
PE
PE
4
8
PE
Functional Description
The KL2612 output terminal switches two relays, each having one changeover contact, under control of the automation device. The signal state of the bus terminal is indicated by an LED. If the LED is on, it means that the contact between 2 and 1 or, in the case of the second relay, between 6 and 5, is closed. The KL2612 Bus Terminal does not have a power contact, which means that a voltage that has been passed on through earlier terminals via the power contacts must be fed in again after a KL2612.
The signal LEDs indicate the operational state of the associated terminal channel.
On: Changeover between 2-1 (6-5) closed Off: Changeover between 2-3 (6-7) closed
Or: A watchdog timer overflow has occurred. If no process data is handled by the bus coupler for 100 ms, the green LED goes out and the outputs are set to 0.
The bit-width in the process image is 2 bits.
Beckhoff™ and TwinCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Phone: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Datasheet for KL2612, Version 1.1
Technical data
Technical data KL2612
Number of outputs
Contact material
Switched voltage max.
Switched current max.
Switched power max.
with resistive load
Minimum permitted load
(approximate)
Reaction times
at rated load
Electrical isolation
K-bus current consumption
Bit width in the process
image
Service life (operating
cycles) mechanical
Operating cycles electr.
(min.)
Permitted operating
frequency at maximum
contact load
Contact resistance max. (new)
2 x change-over Gold-clad silver alloy 125 V AC / 30 V DC 5 A
alternating voltage 0,5 A 125V AC direct voltage 2 A 30V DC
10 µA at 10mV Max. reaction time 4 ms
Max. release time 4 ms max. bounce time 4 ms
500 V 60 mA
2 A
108 cycles
105 resistive load switches at 30 V DC, 2 A or 125 V AC, 0,5 A
20 cycles / min
< 40 mOhm
(K-bus/mains voltage)
eff
Insulation resistance (min).
Test voltage between
open contacts
Configuration
Weight approx.
Operating temperature
Storage temperature
Relative humidity
Vibrations/Shock
resistance
EMC resistance burst / ESD
Installation position
Type of protection
100 MOhm at 500 V DC 750 V (1 min. between open contacts)
No address or configuration settings 80 g 0°C ... +55°C
-25°C ... +85°C 95% without dew formation according to IEC 68-2-6 / IEC 68-2-27
According to EN 50082 (ESD, burst) / EN 50081 any IP20
Beckhoff™ and TwinCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Phone: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149,
http://www.beckhoff.com
Datasheet for KL2612, Version 1.1
i
Note
Smooth operation
Notes on the Correct Use of Relay Terminals
It is extremely important to observe the technical specifications if fault-free operation is to be guaranteed. Any time that the stated parameters are exceeded, damage ranging from premature contact ageing up to fused contacts can result.
If relays are to be used in a control system the expected operating conditions must be analysed with great care.
Switching capacity, service life (operating cycles) and the number of switches per minute must be considered.
Appropriate protective circuits must be used to protect the relay contacts from excessive voltage peaks such as can occur when switching inductive loads (contactors, motors etc.). This allows switching frequencies nearly equal to those appropriate to resistive loads to be achieved. Arcing time when switching DC loads are significantly longer than those for comparable AC voltages (where there is a zero-voltage transition); melting of the material can result.
Warning!
Service life
If the terminal is used to change the direction of inductive loads, adequate dead-times during the switch-over must be provided, in order to avoid temporary short-circuits.
It is the maximum values that are to be expected that are critical to selection of the right terminal rather than the technical figures for normal operation!
Beckhoff™ and TwinCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Phone: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Loading...