Data sheet for KL1154 and KL1164, Version 1.0
Digital Input
Signal LED1
Signal LED2
Signal LED3 Signal LED4
Input 1
Input 2
+24 V
Power contact +24 V
0 V
Power contact 0 V
Input 3
Input 4
5
1
6
2
7
3
positive negative
8
4
2-wire
Contact assemblyTop view Connection
3-wire
KL1154, KL1164 | 4-channel digital input terminal 24 V DC,
switching to positive and negative potentials
The KL1154 and KL1164 digital input terminals acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation unit. The KL1154 and KL1164 versions have input fi lters of different speeds. Sensors that
switch to the positive potential or to 0 V (ground) can be connected to the KL1154 and KL1164 versions. The Bus Terminals contain four
channels that indicate their signal state by means of light emitting diodes.
Technical data KL1154 KL1164
Number of inputs 4
Nominal voltage 24 V DC (-15 % /+20 %)
“0” signal voltage 7.6 V … 17.4 V (at 24 V DC)
“1” signal voltage
Input fi lter
Input current typ. 5 mA
Current consump. from K-bus typ. 8 mA
Electrical isolation 500 V
Bit width in the process image
Confi guration no address or confi guration settings
Weight approx. 55 g
Operating /storage temperature
Relative humidity 95 %, no condensation
Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27/ 29
EMC resistance burst / ESD conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class / installation pos. IP 20 / variable
Beckhoff™ and TwinCAT™ are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the
terms of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Phone: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
0 V … 7 V and 18 V … 30 V (at 24 V DC)
3.0 ms 0.2 ms
(K-bus / fi eld potential)
rms
4 inputs
0 °C … +55 °C/-25 °C … + 85 °C