BECKHOFF KL1002 User Manual

Data sheet for KL1002 and KL1012, Version 1.3
Two-channel, digital input terminals, 24 VDC
The KL1002 and KL1012 digital input terminals acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation unit. The KL1002 and KL1012 versions have input filters of different speeds. The Bus Terminals contain two channels that indicate their signal state by means of light emitting diodes.
Technical data KL1002/KS1002 KL1012/KS1012
Connection technology 4-wire Number of inputs 2 Rated voltage 24 VDC (-15%/+20%) Signal voltage “0” -3 V … +5 V Signal voltage “1” +15 V … +30 V Input filter 3 ms 0.2 ms Input current typically 5 mA Current consumption from K-bus typically 3 mA Electrical isolation 500 V (K-Bus/field potential) Bit width in process image 2 input bits Configuration no address-or configuration settings required Dimensions (W x H x D) 15mm x 100mm x 70mm (connected width: 12mm) Weight approx. 50 g Permissible ambient
temperature range
during operation -25°C ... +60°C
0°C ... +55°C (according to cULus, for Canada and USA) 0°C ... +55°C (according to ATEX, see special conditions)
during storage -40°C... +85°C Relative humidity 5% ... 95%, no condensation Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27 EMC resistance/emission conforms to EN 61000-6-2 / EN 61000-6-4
Beckhoff® and TwinCAT® are Beckhoff brands. Information is subject to change and are only binding if agreed contractually. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Data sheet for KL1002 and KL1012, Version 1.3
Technical data KL1002/KS1002 KL1012/KS1012
Protection class / Installation position IP20/ variable Approvals CE, cULus, ATEX, GL Pluggable wiring at all KSxxxx series terminals
ATEX - Special conditions
Observe the special conditions for the intended use of Beckhoff fieldbus components in potentially explosive areas (directive 94/9/EU)!
WARNING
The certified components are to be installed in a suitable housing that guarantees a protection class of at least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be taken into account!
If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured te mperature values!
Observe the permissible ambient temperature range of 0 - 55°C for the use of Beckhoff fieldbus components in potentially explosive areas!
Measures must be taken to protect against the rated operating voltage being exceeded by more than 40% due to short-term interference voltages!
The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
The fuses of the KL92xx power feed terminals may only be exchanged if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
Operation of the Bus Terminal System in potentially explosive areas (ATEX)!
Note
Pay also attention to the continuative documentation Notes about operation of the Bus Terminal System in potentially explosive areas (ATEX) that is available in the download area of the Beckhoff homepage http://www.beckhoff.com!
Beckhoff® and TwinCAT® are Beckhoff brands. Information is subject to change and are only binding if agreed contractually. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com