Basler Electric BE3-47N User Manual

www.basler.com
info@basler.com
INTRODUCTION
SPECIFICATIONS
Inputs
All units are self powered. Nominal Voltage: 120 Vac, 240 Vac, 380 Vac, or
Overload Withstand: 1.25 times nominal continuously.
Frequency: 50, 60, or 400 Hz Burden: <2 VA
Setpoint
Range: Adjustable 5 to 15% (±5%) of
Repeatability: Greater than 0.5% of full span Undervoltage: Preset at 85% of nominal (BE3-
Time Delay: Adjustable 0 to 10 s Operating Time: 200 ms, typical
Outputs
Relay Type: D.P.D.T. AC Rating: 250 V, 5 A, non-resistive,
DC Rating: 125 V, 1 A, resistive, 120 W Mechanical Life: 5 million operations
Temperature
Operating Temperature: 0°C (32°F) to 60°C (140°F) Functional Temperature: –25°C (–13°F) to 70°C (158°F) Storage Temperature: –40°C (–40°F) to 70°C (158°F) Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity: 95% non-condensing
Publication
9320300990
+1 618.654.2341 (USA)
480 Vac
2 times nominal for 3 s.
nominal)
47N/27 only)
1200 VA
Revision
D
Instructions
Model
Physical
Mounting: DIN rail 1.38” by 0.29” (35 mm by
Case: Complies with IEC 529, DIN
Case Material: Complies with UL 94VO Weight: 0.88 lb (0.4 kg) Size: 2.17” wide (55 mm)
Agency
cULus listed to UL 508 and CSA C22.2 No. 14 CE compliant GOST-R certified per the relevant standards of Gosstandart
of Russia
BE3-47N and BE3-47N/27
7.5 mm)
40050, BS 5490
OPERATION
The BE3-47N and BE3-47N/27 phase balance relays have two external, user-adju sta ble c ontr ol s marked UNB AL and DELAY. The UNBAL control adjusts the relay trip point. The relay trips when the voltage becomes unbalanced by the percentage set by the UNBAL control. The trip point is adjustable from 5 to 15% (±5%) of nominal input. The DELAY control adjusts the time from when a fault is detected until the output contacts change state. The delay is adjustable from 0 to 10 seconds. The undervoltage feature of the BE3-47N/27 has no external adjustment and is fixed at 85% of the nominal input voltage. If all three phases remain balanced, but decrease below 85% of nominal voltage, the relay de-energizes.
Settings Example
A BE3-47N/27 relay with a nominal input rating of 120 Vac has the following settings:
UNBAL - 10%
DELAY - 5 s
The relay detects a phase unbalance when any one phase decreases to 108 Vac or increases to 132 Vac. The output relay trips five seconds after the phase unbalance is detected. The output relay also trips if all phases decrease to 85% of nominal, or 102 Vac.
INSTALLATION
BE3 phase balance relays are designed for mounting on standard DIN rails that comply to DIN-EN 50022. Mounting involves hooking the top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout containing the release clip is then pushed over the opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. BE3 relays should be installed in a dry, vibration-free location where the ambient temperature does not exceed the operating temperature range. Connections to the relay should be made using wire that meets applicable codes and is properly sized for the application. Figure 1 shows the terminal connections for the BE3-47N/27 relay. Connections for the BE3-47N relay are identical.
Date
04/14
Copyright
2014
CALIBRATION
The calibration marks on the faceplate have a maximum error of 10% and are provided only as guides. Proper calibration requires using an accurate voltmeter in parallel with the input signal. Use the following procedure to calibrate your relay.
Unbalance
1. Adjust the UNBAL control fully clockwise and the
DELAY control fully counterclockwise.
2. Apply three-phase, nominal input voltage with the
proper phase sequence to the relay. The output relay should energize.
3. Lower one phase of the applied voltage to the desired
trip level. Slowly adjust the UNBAL control counter c lockwise until the relay trips.
Delay
1. Set the DELAY control at the desired time setting.
2. Apply three-phase, nominal input voltage with the
proper phase sequence to the relay.
FIGURES
3. Step down one phase of the applied voltage below the
relay trip point. Using an appropriate timing device, measure the time from when the voltage is reduced until the relay trips.
4. Compare the measured time to the desired time delay
and adjust the DELAY control accordingly.
5. Repeat Steps 3 and 4 as required.
MAINTENANCE
BE3 relays are solid-state devices that requ ire no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland, IL, USA for return authorization.
ORDERING INFORMATION
Figure 2 shows the BE3 phase balance rel ay style chart.
BE3-47N - Phase Balance
BE3-47N/27 - Phase Balance/Undervoltage
Publication
9320300990
Figure 1. BE3-47N, BE3-47N/27 Phase Balance Relay Connections
Figure 2. BE3-47N, BE3-47N/27 Style Number Identification Chart
Revision
D
Instructions
Date
06/14
Page
2 of 2
Loading...