Basler Electric BE1-50/51B-232 User Manual

INSTRUCTION MANUAL
FOR
OVERCURRENT RELAY
BE1-50/51B-232
Publication: 9252000896 Revision: B 12/08

INTRODUCTION

General Information and Specifications
Controls and Indicators
Functional Description
Installation and Maintenance
Testing
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the relay is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.
9252000896 Rev B BE1-50/51B-232 Introduction i
First Printing: January 2007
Printed in USA
© 2008 Basler Electric, Highland Illinois 62249 USA
All Rights Reserved
December 2008
CONFIDENTIAL
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
It is not provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Should further information be required, contact Basler Electric.
the intention of this manual to cover all details and variations in equipment, nor does this manual
INFORMATION
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-50/51B-232 Introduction 9252000896 Rev B

REVISION HISTORY

The following information provides a historical summary of the changes made to this instruction manual (9252000896). Revisions are listed in reverse chronological order.
Manual
Revision and Date
B, 12/08
A, 03/08
, 01/07
 Updated Storage statement in Section 4. Modified Figure 5-2, Target Operational Test Setup. In Section 5, Testing, removed list of required tools and removed
steps about disconnecting and re-connecting relay terminal wires.
Modified Target Test so that TIME and INST targets can be verified
independently from each other.
Minor text edits throughout manual.
Updated front panel drawings to show new target reset button.
Initial release.
Change
9252000896 Rev B BE1-50/51B-232 Introduction iii
This page intentionally left blank.
iv BE1-50/51B-232 Introduction 9252000896 Rev B

CONTENTS

SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
SECTION 2 CONTROLS AND INDICATORS........................................................................................ 2-1
SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1
SECTION 4 INSTALLATION .................................................................................................................. 4-1
SECTION 5 TESTING ............................................................................................................................ 5-1
APPENDIX A TIME CHARACTERISTIC CURVES................................................................................ A-1
9252000896 Rev B BE1-50/51B-232 Introduction v
This page intentionally left blank.
vi BE1-50/51B-232 Introduction 9252000896 Rev B
SECTION 1 GENERAL INFORMATION
TABLE OF CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
INTRODUCTION....................................................................................................................................1-1
FEATURES............................................................................................................................................1-1
Advantages.........................................................................................................................................1-2
SPECIFICATIONS................................................................................................................................. 1-2
Current Sensing Input ........................................................................................................................ 1-2
Time Overcurrent (51) Element.......................................................................................................... 1-2
Instantaneous Overcurrent (50) Element...........................................................................................1-4
Burden................................................................................................................................................ 1-5
Frequency Response......................................................................................................................... 1-6
Transient Response........................................................................................................................... 1-6
Harmonic Response........................................................................................................................... 1-6
Target Indicators ................................................................................................................................1-7
Output Contacts .................................................................................................................................1-7
Type Tests.......................................................................................................................................... 1-7
Environment ....................................................................................................................................... 1-8
Agency Recognition ...........................................................................................................................1-8
Physical..............................................................................................................................................1-8
Figures
Figure 1-1. Integrating Reset Characteristic Curve...................................................................................1-4
Figure 1-2. Instantaneous Characteristic Curves......................................................................................1-5
Figure 1-3. Burden Characteristics............................................................................................................ 1-6
Figure 1-4. Harmonic Rejection................................................................................................................. 1-7
Tables
Table 1-1. GE IAC Relays Suitable for Direct Replacement..................................................................... 1-1
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)................................................. 1-3
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On).............................................. 1-3
9252000896 Rev B BE1-50/51B-232 General Information i
This page intentionally left blank.
ii BE1-50/51B-232 General Information 9252000896 Rev B
SECTION 1 GENERAL INFORMATION

INTRODUCTION

BE1-50/51B-232 protective relays are direct replacements for General Electric, IAC relays. BE1-50/51B­232 protective relays are enclosed in an S1 case. The BE1-50/51B-232 has a 5 ampere current sensing input. Compatible IAC model numbers are listed in Table 1-1.
Table 1-1. GE IAC Relays Suitable for Direct Replacement
IAC Model Number Curve Type
12IAC51AA 12IAC51BA 12IAC53AA 12IAC53BA 12IAC55AA 12IAC55BA 12IAC66AA 12IAC66BA 12IAC77AA 12IAC77BA
Inverse Inverse with Instantaneous Very Inverse Very Inverse with Instantaneous Short Time Short Time with Instantaneous Long Time Long Time with Instantaneous Extremely Inverse Extremely Inverse with Instantaneous
 Any digit covering all pickup ranges except 50 Hz models.
Basler Electric BE1-50/51B-232 protective relays are self-powered, microprocessor-based, non­directional phase or ground relays that monitor the magnitude of a single-phase ac current to provide accurate instantaneous and time overcurrent protection for 60 Hz power systems. Each model covers 15 popular time characteristics, a wide range of pickup settings, and field selectable instantaneous or integrating reset.

FEATURES

A wide range of pickup settings and front panel selectable time characteristics permit applications involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements. Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-232 overcurrent relays have the following standard features.
Independent time and instantaneous elements A secure method to manually trip the breaker at the relay front panel Direct reading front panel controls Minimum pickup setting for safety during installation Time characteristics extend to a pickup multiple of 40 Rugged draw-out construction with steel case Gravity latching targets retain indication without power Built-in accuracy eliminates internal adjustments Minimum transient overreach Field selectable characteristic curve selection similar to either GE IAC or ABB type curves Field selectable instantaneous or integrating reset Field selectable 0.0, 0.1, 0.2, or 0.3 second, fixed, instantaneous delay
Internal switches provide for selecting instantaneous element delays of 0.0, 0.1, 0.2, or 0.3 second, characteristic curve group selection for either GE IAC or ABB type curves, and instantaneous or integrating reset characteristics. Switch location and description is provided in Section 2.
9252000896 Rev B BE1-50/51B-232 General Information 1-1

Advantages

BE1-50/51B-232 overcurrent relays have many advantages over other overcurrent relays. The primary advantages are:
Time characteristics are defined by equations and graphs Field selectable time characteristics Very low burden extends the linear range of the CTs Self powered from the sensed current Continuous automatic calibration
BE1-50/51B-232 overcurrent relays may be tested without removing the relay from the case. Shorting contacts are provided for all current inputs when the connection plugs or relay chassis is removed from the relay case.

SPECIFICATIONS

BE1-50/51B-232 electrical and physical specifications are listed in the following p aragraphs.

Current Sensing Input

Contin
uous Current: 14 Aac
One Second Rating: 400 Aac

Time Overcurrent (51) Element

Setting the T state and may be used as a safety setting.
IME PICKUP control at the minimum pickup setting places the relay in the most sensitive
Pickup
Setting Range: 0.5 to 15.9 Aac Setting Increment: 0.1 Aac Accuracy: ±2%, ±25 milliamperes at or above 0.5 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Timing Range
0.0 to 9.9 seconds in 0.1 second steps
Timing Accuracy
The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that is the sum of ±2%, ±25 milliamperes.
Timing Accuracy Example
PU setting: 5 amperes Current Applied: 6.5 amperes + Multiple Tolerance: 6.655 amperes – Multiple Tolerance: 6.345 amperes Time Curve: E Time Dial: 5.0 Minimum time dial using 6.655 amperes: 46.5470 seconds Maximum time dial using 6.345 amperes: 61.3968 seconds Curve time using 6.5 amperes: 53.1800 seconds
Curve Characteristics
Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch. Characteristic curves for the inverse and definite time functions are defined by the following equation.
Where: T
T
T
AD
N
KBD
CM
-
A, B, C, N, K = constants for the particular curve
= time to trip in seconds
T
D = time dial setting
M = multiple of pickup setting
1-2 BE1-50/51B-232 General Information 9252000896 Rev B
Time characteristic curve constants are listed in Tables 1-2 and 1-3. Constants have been selected to conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40. Values of the constants are provided for use in computer relay setting software. Timing accuracy is 1 cycle, 2 percent of time to trip.
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)
Curve Type
BE1 Similar To
Figure
Number
A B C N K R
Constants
S ABB CO-2 A-1 0.2663 0.03393 1.000 1.2969 0.028 0.500 L ABB CO-5 A-2 5.6143 2.18592 1.000 1.000 0.028 15.750 D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.875
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.750
I ABB CO-8 A-5 8.9341 0.17966 1.000 2.0938 0.028 9.000 V ABB CO-9 A-6 5.4678 0.10814 1.000 2.0469 0.028 5.500 E ABB CO-11 A-7 7.7624 0.02758 1.000 2.0938 0.028 7.750 B BS142-B A-8 1.4638 0.00000 1.000 1.0469 0.028 3.250
C BS142-C A-9 8.2506 0.00000 1.000 2.0469 0.028 8.000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.000
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On)
Curve Type
BE1 Similar To
Figure
Number
A B C N K R
Constants
S GE IAC 55 A-10 0.0286 0.0208 1.000 0.9844 0.028 0.0940 L GE IAC 66 A-11 2.3955 0.00002 1.000 0.3125 0.028 7.8001
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.8750 M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I GE IAC 51 A-12 0.2747 0.1042 1.000 0.4375 0.028 0.8868 V GE IAC 53 A-13 4.4309 0.0991 1.000 1.9531 0.028 5.8231 E GE IAC 77 A-14 4.9883 0.0129 1.000 2.0469 0.028 4.7742 B BS142-B A-8 1.4636 0.00000 1.000 1.0469 0.028 3.2500
C BS142-C A-9 8.2506 0.00000 1.000 2.0469 0.028 8.0000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.0000
Notes for Tables 1-2 and 1-3 BE1 Curve Types: S: Short Inverse V: Very Inverse
L: Long Inverse E: Extremely Inverse D: Definite Time B: BS142 Very Inverse M: Moderately Inverse C: BS142 Extremely Inverse I: Inverse F: Fixed Time Delay
† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves. ‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.
Integrating Reset
Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of electromechanical relays. BE1-50/51B-232 relays provide the integrating reset function even when input current falls to zero.
9252000896 Rev B BE1-50/51B-232 General Information 1-3
Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation constants are provided in Tables 1-2 or 1-3.
Integrating Reset Equation:
Where:
RD
T
R
2
1M
TR = Time to reset in seconds R = Constant for the particular curve D = TIME DIAL setting M = Current in multiples of PICKUP setting during reset
100.0
P0046-11
10.0
xRD (Seconds)
1.0
0.000 0.200 0.400 0.600 0.800 1.000 1.200
Multiple of Pickup
Vertical axis xRD (Seconds) is applicable for all curves and is derived from multiplying the constant R for the curve selected times D (the Time Dial setting).
Figure 1-1. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the I
NST PICKUP control to the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.
Pickup
Setting Range: 1 to 99 Aac Setting Increment: 1 Aac Accuracy: ±2%, ±25 milliamperes at or above 1.0 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Curve Characteristics
Instantaneous characteristic curves are similar to standard electromechanical instantaneous units. However, the time to trip for applications where the initial current through the relay is less than 0.4 ampere may be slightly longer. This may occur on a very lightly loaded circuit or when the relay is providing ground protection and is connected to measure neutral current. Figure 1-2 shows the instantaneous characteristic curves for maximum time to trip.
An additional fixed delay of 0.1, 0.2, or 0.3 second may be added with internal switches SW3-1 and SW3-2. This delay applies to both phase and ground applications. Closing switch SW3-1 provides an additional delay of 0.2 second. Closing switch SW3-2 provides an additional delay of 0.1 second. Closing
1-4 BE1-50/51B-232 General Information 9252000896 Rev B
both SW3-1 and SW3-2 provides an additional delay of 0.3 second. Section 2 illustrates the location of SW3.
The instantaneous element in BE1-50/51B-232 relays may be set lower than the instantaneous element in ABB relays and still have the same reach. This is because the BE1-50/51B-232 instantaneous element effectively eliminates the fault current transient overreach components. When calculating BE1-50/51B­232 relay instantaneous element settings, calculate the symmetrical value without any adder for transient overreach.
P0048-10
Figure 1-2. Instantaneous Characteristic Curves

Burden

Burden is non-linear. Figure 1-3 illustrates the devi
ce burden.
At 0.5 amperes: 4.8 At 5.0 amperes: 0.2
9252000896 Rev B BE1-50/51B-232 General Information 1-5
P0048-11
Figure 1-3. Burden Characteristics

Frequency Response

A chang
e of ±5 Hz from the nominal 60 Hz current causes <0.5% change in the current required for
pickup.

Transient Response

<10% ove
rreach with system time constants up to 40 ms.

Harmonic Response

Figure 1-4 shows that a
relay set for 1 ampere pickup would pick up at 0.96 amperes with a current containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be evaluated in the same manner.
1-6 BE1-50/51B-232 General Information 9252000896 Rev B
Figure 1-4. Harmonic Rejection

Target Indicators

Gravity latch
ed, manually reset targets indicate that current of 0.2 amperes or greater was present in the trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See Output Contacts for maximum current rating.

Output Contacts

Output co
ntacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc: Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Type Tests

Isolation
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows. All circuits to ground: 2,828 Vdc or 2,000 Vac
Input to Output Circuits: 2,828 Vdc or 2,000 Vac
Surge Withstand Capability Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems. Impulse
Qualified to IEC 255-5.
Radio Frequency Interference (RFI)
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144 MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical planes.
9252000896 Rev B BE1-50/51B-232 General Information 1-7
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.

Environment

ng Te
Operati
mperature: –40C to 70C (–40F to158F)
Storage Temperature: –50C to 70C (–58F to 158F).
Agency Recog
GOST-R Certification
nition
GOST-R certified per the relevant standards of Gosstandart of Russia.
Physical
Case Size:
S1 (Refer to Section 4, Installation for case dimensions.)
Weight: 6.1 lb (2.77 kg)
1-8 BE1-50/51B-232 General Information 9252000896 Rev B
SECTION 2 CONTROLS AND INDICATORS
TABLE OF CONTENTS
SECTION 2 CON
INTRODUCTION....................................................................................................................................
Figures
Figure 2-1. Front Panel Controls and Indicators ....................................................................................... 2-1
Figure 2-2. Location of SW3......................................................................................................................2-2
Tables
Table 2-1. BE1-50/51B-231 Controls and Indicators (Refer to Figures 2-1 and 2-2)................................2-3
TROLS AND INDICATORS........................................................................................2-1
2-1
9252000896 Rev B BE1-50/51B-232 Controls and Indicators i
This page intentionally left blank.
ii BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
Loading...
+ 44 hidden pages