This instruction manual provides information about the operation and installation of the BE1-50/51B-232
Overcurrent Relay. To accomplish this, the following information is provided:
General Information and Specifications
Controls and Indicators
Functional Description
Installation and Maintenance
Testing
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
the intention of this manual to cover all details and variations in equipment, nor does this manual
INFORMATION
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-50/51B-232 Introduction 9252000896 Rev B
Page 5
REVISION HISTORY
The following information provides a historical summary of the changes made to this instruction manual
(9252000896). Revisions are listed in reverse chronological order.
Manual
Revision and Date
B, 12/08
A, 03/08
―, 01/07
Updated Storage statement in Section 4.
Modified Figure 5-2, Target Operational Test Setup.
In Section 5, Testing, removed list of required tools and removed
steps about disconnecting and re-connecting relay terminal wires.
Modified Target Test so that TIME and INST targets can be verified
independently from each other.
Minor text edits throughout manual.
Updated front panel drawings to show new target reset button.
Initial release.
Change
9252000896 Rev B BE1-50/51B-232 Introduction iii
Page 6
This page intentionally left blank.
iv BE1-50/51B-232 Introduction 9252000896 Rev B
Page 7
CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
SECTION 2 CONTROLS AND INDICATORS........................................................................................ 2-1
Type Tests.......................................................................................................................................... 1-7
Table 1-1. GE IAC Relays Suitable for Direct Replacement..................................................................... 1-1
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)................................................. 1-3
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On).............................................. 1-3
9252000896 Rev B BE1-50/51B-232 General Information i
Page 10
This page intentionally left blank.
ii BE1-50/51B-232 General Information 9252000896 Rev B
Page 11
SECTION 1 GENERAL INFORMATION
INTRODUCTION
BE1-50/51B-232 protective relays are direct replacements for General Electric, IAC relays. BE1-50/51B232 protective relays are enclosed in an S1 case. The BE1-50/51B-232 has a 5 ampere current sensing
input. Compatible IAC model numbers are listed in Table 1-1.
Table 1-1. GE IAC Relays Suitable for Direct Replacement
Inverse
Inverse with Instantaneous
Very Inverse
Very Inverse with Instantaneous
Short Time
Short Time with Instantaneous
Long Time
Long Time with Instantaneous
Extremely Inverse
Extremely Inverse with Instantaneous
Any digit covering all pickup ranges except 50 Hz models.
Basler Electric BE1-50/51B-232 protective relays are self-powered, microprocessor-based, nondirectional phase or ground relays that monitor the magnitude of a single-phase ac current to provide
accurate instantaneous and time overcurrent protection for 60 Hz power systems. Each model covers 15
popular time characteristics, a wide range of pickup settings, and field selectable instantaneous or
integrating reset.
FEATURES
A wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-232 overcurrent relays have the following standard features.
Independent time and instantaneous elements
A secure method to manually trip the breaker at the relay front panel
Direct reading front panel controls
Minimum pickup setting for safety during installation
Time characteristics extend to a pickup multiple of 40
Rugged draw-out construction with steel case
Gravity latching targets retain indication without power
Built-in accuracy eliminates internal adjustments
Minimum transient overreach
Field selectable characteristic curve selection similar to either GE IAC or ABB type curves
Field selectable instantaneous or integrating reset
Field selectable 0.0, 0.1, 0.2, or 0.3 second, fixed, instantaneous delay
Internal switches provide for selecting instantaneous element delays of 0.0, 0.1, 0.2, or 0.3 second,
characteristic curve group selection for either GE IAC or ABB type curves, and instantaneous or
integrating reset characteristics. Switch location and description is provided in Section 2.
9252000896 Rev B BE1-50/51B-232 General Information 1-1
Page 12
Advantages
BE1-50/51B-232 overcurrent relays have many advantages over other overcurrent relays. The primary
advantages are:
Time characteristics are defined by equations and graphs
Field selectable time characteristics
Very low burden extends the linear range of the CTs
Self powered from the sensed current
Continuous automatic calibration
BE1-50/51B-232 overcurrent relays may be tested without removing the relay from the case. Shorting
contacts are provided for all current inputs when the connection plugs or relay chassis is removed from
the relay case.
SPECIFICATIONS
BE1-50/51B-232 electrical and physical specifications are listed in the following p aragraphs.
Current Sensing Input
Contin
uous Current: 14 Aac
One Second Rating: 400 Aac
Time Overcurrent (51) Element
Setting the T
state and may be used as a safety setting.
IME PICKUP control at the minimum pickup setting places the relay in the most sensitive
Pickup
Setting Range: 0.5 to 15.9 Aac
Setting Increment: 0.1 Aac
Accuracy: ±2%, ±25 milliamperes at or above 0.5 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Timing Range
0.0 to 9.9 seconds in 0.1 second steps
Timing Accuracy
The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap
and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that
is the sum of ±2%, ±25 milliamperes.
Timing Accuracy Example
PU setting: 5 amperes
Current Applied: 6.5 amperes
+ Multiple Tolerance: 6.655 amperes
– Multiple Tolerance: 6.345 amperes
Time Curve: E
Time Dial: 5.0
Minimum time dial
using 6.655 amperes: 46.5470 seconds
Maximum time dial
using 6.345 amperes: 61.3968 seconds
Curve time using 6.5 amperes: 53.1800 seconds
Curve Characteristics
Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch.
Characteristic curves for the inverse and definite time functions are defined by the following equation.
Where: T
T
T
AD
N
KBD
CM
-
A, B, C, N, K =constants for the particular curve
=time to trip in seconds
T
D =time dial setting
M =multiple of pickup setting
1-2 BE1-50/51B-232 General Information 9252000896 Rev B
Page 13
Time characteristic curve constants are listed in Tables 1-2 and 1-3. Constants have been selected to
conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40.
Values of the constants are provided for use in computer relay setting software. Timing accuracy is 1
cycle, 2 percent of time to trip.
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)
Curve Type
BE1 Similar To
Figure
Number †
A B C N K R
Constants
S ABB CO-2 A-1 0.2663 0.03393 1.000 1.2969 0.028 0.500
L ABB CO-5 A-2 5.6143 2.18592 1.000 1.000 0.028 15.750
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.875
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.750
I ABB CO-8 A-5 8.9341 0.17966 1.000 2.0938 0.028 9.000
V ABB CO-9 A-6 5.4678 0.10814 1.000 2.0469 0.028 5.500
E ABB CO-11 A-7 7.7624 0.02758 1.000 2.0938 0.028 7.750
B BS142-B ‡ A-8 1.4638 0.00000 1.000 1.0469 0.028 3.250
C BS142-C ‡ A-9 8.2506 0.00000 1.000 2.0469 0.028 8.000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.000
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On)
Curve Type
BE1 Similar To
Figure
Number †
A B C N K R
Constants
S GE IAC 55 A-10 0.0286 0.0208 1.000 0.9844 0.028 0.0940
L GE IAC 66 A-11 2.3955 0.00002 1.000 0.3125 0.028 7.8001
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.8750
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I GE IAC 51 A-12 0.2747 0.1042 1.000 0.4375 0.028 0.8868
V GE IAC 53 A-13 4.4309 0.0991 1.000 1.9531 0.028 5.8231
E GE IAC 77 A-14 4.9883 0.0129 1.000 2.0469 0.028 4.7742
B BS142-B ‡ A-8 1.4636 0.00000 1.000 1.0469 0.028 3.2500
C BS142-C ‡ A-9 8.2506 0.00000 1.000 2.0469 0.028 8.0000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.0000
Notes for Tables 1-2 and 1-3
BE1 Curve Types: S: Short Inverse V: Very Inverse
L: Long Inverse E: Extremely Inverse
D: Definite Time B: BS142 Very Inverse
M: Moderately Inverse C: BS142 Extremely Inverse
I: Inverse F: Fixed Time Delay
† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves.
‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.
Integrating Reset
Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of
electromechanical relays. BE1-50/51B-232 relays provide the integrating reset function even when input
current falls to zero.
9252000896 Rev B BE1-50/51B-232 General Information 1-3
Page 14
Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation
constants are provided in Tables 1-2 or 1-3.
Integrating Reset Equation:
Where:
RD
T
R
2
1M
TR = Time to reset in seconds
R = Constant for the particular curve
D = TIME DIAL setting
M = Current in multiples of PICKUP setting during reset
100.0
P0046-11
10.0
xRD (Seconds)
1.0
0.0000.2000.4000.6000.8001.0001.200
Multiple of Pickup
Vertical axis xRD (Seconds) is applicable for all curves and is derived from
multiplying the constant R for the curve selected times D (the Time Dial setting).
NST PICKUP control to the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.
Pickup
Setting Range: 1 to 99 Aac
Setting Increment: 1 Aac
Accuracy: ±2%, ±25 milliamperes at or above 1.0 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Curve Characteristics
Instantaneous characteristic curves are similar to standard electromechanical instantaneous units.
However, the time to trip for applications where the initial current through the relay is less than 0.4
ampere may be slightly longer. This may occur on a very lightly loaded circuit or when the relay is
providing ground protection and is connected to measure neutral current. Figure 1-2 shows the
instantaneous characteristic curves for maximum time to trip.
An additional fixed delay of 0.1, 0.2, or 0.3 second may be added with internal switches SW3-1 and
SW3-2. This delay applies to both phase and ground applications. Closing switch SW3-1 provides an
additional delay of 0.2 second. Closing switch SW3-2 provides an additional delay of 0.1 second. Closing
1-4 BE1-50/51B-232 General Information 9252000896 Rev B
Page 15
both SW3-1 and SW3-2 provides an additional delay of 0.3 second. Section 2 illustrates the location of
SW3.
The instantaneous element in BE1-50/51B-232 relays may be set lower than the instantaneous element
in ABB relays and still have the same reach. This is because the BE1-50/51B-232 instantaneous element
effectively eliminates the fault current transient overreach components. When calculating BE1-50/51B232 relay instantaneous element settings, calculate the symmetrical value without any adder for transient
overreach.
P0048-10
Figure 1-2. Instantaneous Characteristic Curves
Burden
Burden is non-linear. Figure 1-3 illustrates the devi
ce burden.
At 0.5 amperes: 4.8
At 5.0 amperes: 0.2
9252000896 Rev B BE1-50/51B-232 General Information 1-5
Page 16
P0048-11
Figure 1-3. Burden Characteristics
Frequency Response
A chang
e of ±5 Hz from the nominal 60 Hz current causes <0.5% change in the current required for
pickup.
Transient Response
<10% ove
rreach with system time constants up to 40 ms.
Harmonic Response
Figure 1-4 shows that a
relay set for 1 ampere pickup would pick up at 0.96 amperes with a current
containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be
evaluated in the same manner.
1-6 BE1-50/51B-232 General Information 9252000896 Rev B
Page 17
Figure 1-4. Harmonic Rejection
Target Indicators
Gravity latch
ed, manually reset targets indicate that current of 0.2 amperes or greater was present in the
trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See
Output Contacts for maximum current rating.
Output Contacts
Output co
ntacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc: Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows.
All circuits to ground: 2,828 Vdc or 2,000 Vac
Input to Output Circuits: 2,828 Vdc or 2,000 Vac
Surge Withstand Capability
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems.
Impulse
Qualified to IEC 255-5.
Radio Frequency Interference (RFI)
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical
planes.
9252000896 Rev B BE1-50/51B-232 General Information 1-7
Page 18
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a
total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Environment
ng Te
Operati
mperature: –40C to 70C (–40F to158F)
Storage Temperature: –50C to 70C (–58F to 158F).
Agency Recog
GOST-R Certification
nition
GOST-R certified per the relevant standards of Gosstandart of Russia.
Physical
Case Size:
S1 (Refer to Section 4, Installation for case dimensions.)
Weight: 6.1 lb (2.77 kg)
1-8 BE1-50/51B-232 General Information 9252000896 Rev B
Figure 2-1. Front Panel Controls and Indicators ....................................................................................... 2-1
Figure 2-2. Location of SW3......................................................................................................................2-2
Tables
Table 2-1. BE1-50/51B-231 Controls and Indicators (Refer to Figures 2-1 and 2-2)................................2-3
TROLS AND INDICATORS........................................................................................2-1
2-1
9252000896 Rev B BE1-50/51B-232 Controls and Indicators i
Page 20
This page intentionally left blank.
ii BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
Page 21
SECTION 2 CONTROLS AND INDICATORS
INTRODUCTION
Figure 2-1 illustrates the front panel controls and indicators of the BE1-50/51B-232. Figure 2-2 illustrates
the location of switch SW3. Both illustrations have lettered call-outs that correspond to the control and
indicator descriptions provided in Table 2-1.
Figure 2-1. Front Panel Controls and Indicators
9252000896 Rev B BE1-50/51B-232 Contr
ols and Indicators 2-1
Page 22
SW3
Figure 2-2. Location of SW3
2-2 BE1-50/51B-232 Controls and Indicators
P0053-50
9252000896 Rev B
Page 23
Table 2-1. BE1-50/51B-232 Controls and Indicators (Refer to Figures 2-1 and 2-2)
Locator Control or Indicator Function
A INST MANUAL TRIP
Test Points
B INST PICKUP
Selectors
C Targets
D TIME PICKUP
Selectors
E
F
CURVE Selector Ten position selector switch to select one of nine inverse functions
TIME DIAL Selectors Two selector switches (UNITS and TENTHS) to select the desired
G TIME MANUAL TRIP
Test Points
When shorted, the test points (jacks) provide a secure means to
manually trip the controlled breaker. Jacks accept a standard 0.08
inch diameter phone tip plug.
Two switches (TENS and UNITS) to select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.
Red target indicators latch when the trip circuit current is greater
than 0.2 amperes. One target each for TIME and INST.
Two switches (UNITS and TENTHS) t o select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.
or one fixed time function.
characteristic curve. A setting of 0.0 results in instantaneous
operation without any intentional delay. A setting of 9.9
corresponds to the typical time provided by an electromechanical
relay at its maximum dial setting.
When shorted, the test points provide a secure means to manually
trip the controlled breaker. Jacks accept a standard 0.08 inch
diameter phone tip plug.
H
I
SW3
ACTIVE/PICKUP LED Red LED indicates sensed current has ex ceeded the TIME
PICKUP setting. LED turns from red to green when sensed current
falls below 95% of pickup setting. When the LED is green, the
relay is active but has not picked up.
Target RESET Button Linkage extends through back of front cover to reset both gravity
latched target indicators.
SW3-1
SW3-1 provides an additional instantaneous delay of 0.2 second
when closed (ON). Closing both SW3-1 and SW3-2 provides an
additional instantaneous delay of 0.3 second.
SW3-2
SW3-2 provides an additional instantaneous delay of 0.1 second
when closed (ON). Closing both SW3-2 and SW3-1 provides an
additional instantaneous delay of 0.3 second.
SW3-3
SW3-3 provides selection of GE IAC type curves or ABB type
curves. Closing switch SW3-3 (ON) selects GE IAC type curves
(refer to Table 1-3). Opening switch SW3-3 (OFF) selects ABB
type curves (refer to Table 1-2).
SW3-4
SW3-4 provides selection of either instantaneous or integrating
reset characteristics. Closing S W3-4 (ON) selects integrating reset
characteristics. Opening SW3-4 (OFF) selects instantaneous reset
characteristics.
9252000896 Rev B BE1-50/51B-232 Controls and Indicators 2-3
Page 24
This page intentionally left blank.
2-4 BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
L DESCRIPTION........................................................................................... 3-1
3-1
3-1
3-1
3-1
3-1
3-2
9252000896 Rev B BE1-50/51B-232 Functional Description i
Page 26
This page intentionally left blank.
ii BE1-50/51B-232 Fun ctional Description 9252000896 Rev B
Page 27
SECTION 3 FUNCTIONAL DESCRIPTION
GENERAL
BE1-50/51B-232 Overcurrent Relays are microprocessor based non-directional relays that measure ac
current to provide secure and reliable instantaneous and time overcurrent protection for power sy stems.
FUNCTIONAL DESCRIPTION
Sensing Input
Single phase ac current from system current transformers (CT) is brought into the Overcurrent Relay at
terminals 5 and 6. Refer to Figure 3-1 to follow the functional description. The input current is applied to
internal power and signal CTs.
Power Supply
nt from the power CT is rectified, filtered, and supplied to all relay internal circuitry for operating
Curre
power. A precision +5 Vdc supply also serves as a reference for automatic calibration.
Instantaneous Signal
nt from the signal CT is rectified and applied to the instantaneous scaling resistors controlled by the
Curre
INST PICKUP selector switches. The analog voltage of the instantaneous input signal developed across
the scaling resistors is filtered and applied to the multiplexor (MUX).
Time Signal
nt from the signal CT is also rectified and applied to the time scaling resistors controlled by the TIME
Curre
PICKUP selector switches. The analog voltage of the time input signal is also filtered and applied to the
multiplexor.
Microprocessor
Operating po
microprocessor is active and executing code, the ACTIVE/PICKUP LED is green. When the input current
falls below an acceptable level, the supervisor circuit interrupts the microprocessor, halts further
operation, and turns OFF the ACTIVE/PICKUP LED. A microprocessor watchdog feature resets the
microprocessor program when the program flow is interrupted.
Information from the TIME DIAL selector switches, the TIME CURVE selector switch, INST DELAY
switches, and RESET CHAR switch is also applied to the microprocessor. The microprocessor uses
these inputs to set the operating parameters.
When the microprocessor is ready for analog information from the multiplexor, microprocessor control
signals cause the multiplexor to route the desired input through to the output. The output is converted
from an analog value to a digital value and applied to the microprocessor.
The microprocessor performs the program operations based on the inputs and the internal software
program. When the sensed current exceeds the TIME PICKUP setting, the ACTIVE/PICKUP LED turns
from green to red. The 50/51 contact is closed in accordance with the TIME characteristic equation or if
the sensed current exceeds the INST PICKUP setting.
Power-Off Sensing
r-off sensing circuits measure the voltage across a capacitor at power-down and at power-up.
Powe
These circuits determine how long power has been removed based on the difference voltage and the
circuit RC time constant. This provides information for the integrating reset function even when power has
been entirely removed.
wer from the power supply is applied to the microprocessor supervisor circuit. When the
9252000896 Rev B BE1-50/51B-232 Functional Description 3-1
Page 28
Outputs
Instantaneous and Timed
System circuit breakers controlled by the output contacts can be manually tripped by applying a short
across the TIME or INST MANUAL TRIP front panel test points. Current flow in the trip circuit is indicated
by the operation of the target. The targets will not operate without adequate operating power for the relay.
WARNING!
Trip circuit voltage is present at the front panel test points. When shorting the test
points, use insulated jumpers to avoid contact with these voltages.
Figure 3-1. Functional Block Diagram
3-2 BE1-50/51B-232 Functional Description 9252000896 Rev B
Figure 4-6. AC Input Connections............................................................................................................. 4-6
Figure 4-7. DC Control Connections......................................................................................................... 4-7
9252000896 Rev B BE1-50/51B-232 Installation i
Page 30
This page intentionally left blank.
ii BE1-50/51B-232 Installation 9252000896 Rev B
Page 31
SECTION 4 INSTALLATION
GENERAL
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,
Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5.
If the relay won't be installed immediately, store the relay in its original shipping carton in a moisture and
dust-free environment.
MOUNTING
Relay outline dimensions and panel drilling diagrams are shown in Figures 4-1 through 4-4. Dimensions
in parentheses are in millimeters.
D2750-29
Figure 4-1. Outline Dimensions for S1 Case, Semi-Flush Mounting
9252000896 Rev B BE1-50/51B-232 Installation 4-1
Page 32
Figure 4-2. Panel Drilling Diagram for S1 Case, Semi-Flush Mounting
4-2 BE1-50/51B-232 Installation 9252000896 Rev B
Page 33
Figure 4-3. Panel Drilling Diagram for S1 Case, Projection Mounting
9252000896 Rev B BE1-50/51B-232 Installation 4-3
Page 34
2.40
(62.48)
1.95
(49.53)
4.03
(102.4)
4.03
(102.4)
6.19
(157.2)
AA
.25
(6.4)
MOUNTING PANEL
5/16-18 STUD
2 PLACES
CASE
DETAIL A-A
SHOWING THE ADDITION OF WASHERS
OVER THE BOSS TO TIGHTEN THE
RELAY AGAINST THE PANEL.
MOUNTING PANEL
PANEL
10-32 SCREWS
.31
(7.9)
TERMINAL EXTENSION (TYP.)
FOR DETAILED INSTRUCTIONS.
SEE THE TERMINAL PROJECTION
.75
(19.1)
MOUNTING KIT SUPPLIED.
2.195
(55.75)
NOTE: PROJECTION MOUNT USES WASHERS OVER THE BOSSES AS SHOWN IN THIS ILLUSTRATION.
Figure 4-4. Panel Drilling Diagram for S1 Case, Side View, Projection Mounting
FACTORY SETTINGS
Factory settings for the internal switches of SW3 are as follows:
SW3-1 — OFF (0.0 additional fixed delay for the instantaneous element).
SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).
SW3-3 — ON (General Electric, IAC type characteristic curves).
SW3-4 — ON (Integrating reset characteristics).
D2750-25
12-17-99
APPLICATION COORDINATION
In a typical application coordination scheme, a BE1-50/51B-232 is being used to provide primary
protection for a radial distribution feeder. An electromechanical overcurrent relay with extremely inverse
timing provides protection for the transformer and bus. To improve coordination with the
electromechanical relay, the BE1 relay with integrating reset characteristic has the time characteristic
4-4 BE1-50/51B-232 Installation 9252000896 Rev B
Page 35
curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder
reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a permanent fault
occurs (magnitude ten times pickup), calculate the feeder breaker trip time for each of the three
operations. Refer to Section 1 for characteristic curve constants.
From the time characteristic curve equation.
T
Trip
AD
N
CM
KBD
.
276247
09382
.
524815
.
.
110
110806124
seconds 0.209
0280202758.0
.
028005516.0
.
From the reset characteristic curve equation.
RD
T
2
Reset
27.75
10
2
1M
seconds 15.5
M = 0 if current goes to zero.
Negative result indicates reset time.
Results: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.
In Figure 4-1,
T
T
T
= 0.209 seconds (relay was at reset).
A
= value < TA because rewind has not gone to zero.
B
= value < TA because rewind has not gone to zero.
C
Figure 4-5. Coordination Timing Diagram
9252000896 Rev B BE1-50/51B-232 Installation 4-5
Page 36
Equation for time to trip during rewind (before relay is reset).
Second Operation
T
Occurence This Trip
T
B
30.209
15.5
Time RewindTrip Full
Rewind Full
Third Operation
B
T
C
C
seconds 0.040T
15.5
seconds 0.161T
11.960.209
CONNECTIONS
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
Typical ac input and dc control connections are shown in Figures 4-6 and 4-7. Refer to the block diagram
in Section 3 for relay internal connections.
Figure 4-6. AC Input Connections
4-6 BE1-50/51B-232 Installation 9252000896 Rev B
Page 37
Figure 4-7. DC Control Connections
MAINTENANCE
BE1-50/51B-232 overcurrent relays require no preventive maintenance. However, periodic checks should
be performed according to scheduled practices. A recommended periodic test is provided in Section 5. If
the relay fails to function properly, contact the Technical Sales Support Department of Basler Electric.
STORAGE
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.
Figure 5-1. Pickup and Timing Test Setup................................................................................................ 5-2
Figure 5-2. Target Operational Test Setup................................................................................................ 5-2
9252000896 Rev B BE1-50/51B-232 Testing i
Page 40
This page intentionally left blank.
ii BE1-50/51B-232 Testing 9252000896 Rev B
Page 41
SECTION 5 TESTING
GENERAL
Dielectric testing, operational testing, and periodic testing are described in the following paragraphs.
DIELECTRIC TEST
In accordance with IEC 255-5 and IEEE C37.90-1989, one-minute dielectric (high potential) tests may be
performed as follows:
All circuits to ground: 2,828 Vdc or 2,000 Vac
Input to output circuits: 2,828 Vdc or 2,000 Vac
Output contacts are surge protected.
OPERATIONAL TEST PROCEDURE
The following procedures verify operation of relays BE1-50/51B-232. The test setup of Figures 5-1 and
5-2 are intended primarily as an illustration of the principles involved. Other test setups known to be
capable of testing with the stated and implied tolerances (including equipment specifically designed for
testing relays) may be used.
Test Equipment Required
Current source with a range from 0 to 20 Aac (sensing input current)
AC or DC voltage source (target operation)
Timer or counter
CAUTION
To ensure proper timing during testing, before each test, remove the current from
the unit for R times D seconds (refer to Section 1, Specifications, Time Reset for
R and D definitions).
9252000896 Rev B BE1-50/51B-232 Testing 5-1
Page 42
Figure 5-1. Pickup and Timing Test Setup
Figure 5-2. Target Operational Test Setup
5-2 BE1-50/51B-232 Testing 9252000896 Rev B
Page 43
NOTE
When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect
the calibration of the TIME functions. TIME PICKUP settings of 00 also affect
INST functions.
Test Procedure
The following tests are performed to verify functionality of the BE1-50/51B-232 overcurrent relay. The
TIME and INST output contact terminals are strapped together. Therefore it is necessary to disconnect
specific wires during the TIME and INST pickup tests. This verifies the proper functionality of the TIME
and INST elements.
NOTE
Observe all applicable electrostatic discharge (ESD) precautions when handling
the relay draw-out assembly.
TIME Pickup Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON and SW3-4 to
ON.
Set TIME DIAL to 0.0.
Set CURVE to S
Set TIME PICKUP to 0.5.
Set INST PICKUP to 90.
Step 1. Slowly increase current to terminals 5 and 6. PICKUP LED should turn RED at a maximum input
current of 0.550 ampere.
Step 2. Decrease input current until PICKUP LED turns GREEN then OFF.
Step 3. Set TIME PICKUP to 2.2.
Step 4. Slowly increase current to terminals 5 and 6. PICKUP LED should change from GREEN to RED
at an input current of 2.131 to 2.269 amperes.
Step 5. Decrease input current until PICKUP LED turns OFF.
INST Pickup Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
Set TIME DIAL to 0.0.
Set CURVE to S
Set TIME PICKUP to 15.9.
Set INST PICKUP to 01.
Step 1. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
0.955 to 1.045 amperes.
Step 2. Decrease input current until INST output contacts open.
Step 3. Set INST PICKUP to 08.
Step 4. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
7.815 to 8.185 amperes.
Step 5. Decrease input current until INST output contacts open.
9252000896 Rev B BE1-50/51B-232 Testing 5-3
Page 44
Time Dial Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
Set TIME DIAL to 4.5.
Set CURVE to S
Set TIME PICKUP to 1.0.
Set INST PICKUP to 90.
Step 1. Prepare to apply 1.5 amperes input current to terminals 5 and 6 and record the elapsed time from
when current is applied until TIME output contacts close.
Step 2. Apply the current (step from 0 to 1.5 amperes) and record the elapsed time. Elapsed time should
be 0.345 to 0.424 seconds. (This tolerance is greater than ±2 % because it is the accumulation of
both pickup and timing tolerances.)
Step 3. Remove input current.
Target Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-2.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
Set TIME DIAL to 4.5.
Set CURVE to S
Set TIME PICKUP to 1.0.
Set INST PICKUP to 90.
Step 1. Set voltage source to provide a target current of 1.0 ampere.
Step 2. Apply 5 amperes input current to terminals 5 and 6. Check that the TIME target operates.
Step 3. Remove input current and reset target.
Step 4. Set TIME PICKUP to 15.9 and set INST PICKUP to 01.
Step 5. Set voltage source to provide a target current of 1.0 ampere.
Step 6. Apply 5 amperes input current to terminals 5 and 6. Check that the INST target operates.
Step 7. Remove input current and reset target.
Manual Trip Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-2.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
Set TIME DIAL to 4.5.
Set CURVE to S
Set TIME PICKUP to 1.0.
Set INST PICKUP to 01.
WARNING!
Trip circuit voltage is present at the front panel test points. When shorting the test
points, use insulated jumpers to avoid contact with these voltages.
Step 1.
Set voltage source to provide a target current of 1.0 ampere.
Step 2. Apply 0.9 ampere input current to terminals 5 and 6. (0.9 ampere provides input power but stays
below pickup.)
Step 3. Connect a jumper between TIME MANUAL TRIP test points. Check that TIME target operates.
5-4 BE1-50/51B-232 Testing 9252000896 Rev B
Page 45
Step 4. Connect a jumper between INST MANUAL TRIP test points. Check that INST target operates.
Step 5. Reset targets.
Integrating Reset Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.
Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.
Set TIME DIAL to 9.9.
Set CURVE to V.
Set TIME PICKUP to 1.0.
Set INST PICKUP to 90.
Step 1. Set voltage source to provide a target current of 1.0 ampere.
Step 2. Read all of Step 3 before beginning Step 3.
Step 3. Apply 4.0 amperes input current to terminals 5 and 6. After the unit trips, remove the input current
for 29 ±0.25 seconds, then reapply the 4.0 amperes input current. Record the elapsed time from
the re-application of input current to the output retrip.
Result: Elapsed time should be 2.08 ±0.4 seconds.
SETTING THE RELAY
Select the desired relay settings before putting the relay into service. Changing pickup current settings
while the relay is in service may cause tripping.
PERIODIC TESTS
General
All relays should be tested periodically to identify and correct any problems that are found.
Single phase relays such as the BE1-50/51B-232 are normally used in groups of four (three phase and
ground) on the protected circuit. This relay scheme allows each unit to be withdrawn one at a time for
testing purposes without losing protection. Only three are required at any one time to sense all types of
faults on a grounded wye system. Refer to Figures 5-1 and 5-2 for recommended test setups.
Periodic Test
Periodi
Step 1. Verify that the instantaneous pickup is within ±2% of the value set on the dials. Pickup occurs
Step 2. Verify that the time pickup is within ±2% of the value set on the dials. Pickup occurs when the
Step 3. Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as
Step 4. Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater
Step 5. Verify that the targets operate with one ac ampere of trip current in the trip circuits and that they
c testing should consist of the following procedures.
when the INST output contacts close.
LED turns GREEN then RED.
the time given on the characteristic curve. Refer to Section 1 for the characteristics curves.
than the time given on the instantaneous characteristic curve. Refer to Section 1 for the
instantaneous characteristic curve.
can be reset using the RESET BUTTON.
9252000896 Rev B BE1-50/51B-232 Testing 5-5
Page 46
This page intentionally left blank.
5-6 BE1-50/51B-232 Testing 9252000896 Rev B
Page 47
APPENDIX A TIME CHARACTERISTIC CURVES
TABLE OF CONTENTS
APPENDIX A TIME CHARACTERISTIC CURVES................................................................................A-1
TIME CHARACTERISTIC CURVES......................................................................................................A-1
Figures
Figure A-1. Time Characteristic Curve, S-Short Inverse (SW3-3 OFF, Similar to ABB CO-2).................A-1
Figure A-2. Time Characteristic Curve, L-Long Inverse (SW3-3 OFF, Similar to ABB CO-5)..................A-2
Figure A-3. Time Characteristic Curve, D-Definite Time (Similar to ABB CO-6) ......................................A-3
Figure A-4. Time Characteristic Curve, M-Moderately Inverse (Similar to ABB CO-7).............................A-4
Figure A-5. Time Characteristic Curve, I-Inverse (SW3-3 OFF, Similar to ABB CO-8) ...........................A-5
Figure A-6. Time Characteristic Curve, V-Very Inverse (SW3-3 OFF, Similar to ABB CO-9) .................A-6
Figure A-7. Time Characteristic Curve, E-Extremely Inverse (SW3-3 OFF, Similar to ABB CO-11)........A-7
Figure A-8. Time Characteristic Curve, BS142-B (BS142 Very Inverse)..................................................A-8
Figure A-9. Time Characteristic Curve, BS142-C (BS142 Extremely Inverse).........................................A-9
Figure A-10. Time Characteristic Curve, S2-Short Inverse (SW3-3 ON, Similar to GE IAC 55).............A-10
Figure A-11. Time Characteristic Curve, L2-Long Inverse (SW3-3 ON, Similar to GE IAC 66)..............A-11
Figure A-12. Time Characteristic Curve, I2-Inverse (SW3-3 ON, Similar to GE IAC 51)........................A-12
Figure A-13. Time Characteristic Curve, V2-Very Inverse (SW3-3 ON, Similar to GE IAC 53)..............A-13
Figure A-14. Time Characteristic Curve, E2-Extremely Inverse (SW3-3 ON, Similar to GE IAC 77).....A-14
9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves i
Page 48
This page intentionally left blank.
ii BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B
Page 49
APPENDIX A TIME CHARACTERISTIC CURVES
TIME CHARACTERISTIC CURVES
Figures A-1 through A-14 illustrate the time characteristic curves that are programmed into the nonvolatile
memory of this relay.
Figure A-1. Time Characteristic Curve, S-Short Inverse
(SW3-3 OFF, Similar to ABB CO-2)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-1
Page 50
Figure A-2. Time Characteristic Curve, L-Long Inverse
(SW3-3 OFF, Similar to ABB CO-5)
A-2 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 51
Figure A-3. Time Characteristic Curve, D-Definite Time
(Similar to ABB CO-6)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-3
Page 52
Figure A-4. Time Characteristic Curve, M-Moderately Inverse
(Similar to ABB CO-7)
A-4 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 53
Figure A-5. Time Characteristic Curve, I-Inverse
(SW3-3 OFF, Similar to ABB CO-8)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-5
Page 54
Figure A-6. Time Characteristic Curve, V-Very Inverse
(SW3-3 OFF, Similar to ABB CO-9)
A-6 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 55
Figure A-7. Time Characteristic Curve, E-Extremely Inverse
(SW3-3 OFF, Similar to ABB CO-11)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-7
Page 56
Figure A-8. Time Characteristic Curve, BS142-B
(BS142 Very Inverse)
A-8 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 57
Figure A-9. Time Characteristic Curve, BS142-C
(BS142 Extremely Inverse)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-9
Page 58
Figure A-10. Time Characteristic Curve, S2-Short Inverse
(SW3-3 ON, Similar to GE IAC 55)
A-10 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 59
Figure A-11. Time Characteristic Curve, L2-Long Inverse
(SW3-3 ON, Similar to GE IAC 66)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-11
Page 60
Figure A-12. Time Characteristic Curve, I2-Inverse
(SW3-3 ON, Similar to GE IAC 51)
A-12 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 61
Figure A-13. Time Characteristic Curve, V2-Very Inverse
(SW3-3 ON, Similar to GE IAC 53)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-13
Page 62
Figure A-14. Time Characteristic Curve, E2-Extremely Inverse
(SW3-3 ON, Similar to GE IAC 77)
A-14 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 63
Page 64
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618-654-2341 FAX +1 618-654-2351
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.