Basler Electric BE1-50/51B-232 User Manual

Page 1
INSTRUCTION MANUAL
FOR
OVERCURRENT RELAY
BE1-50/51B-232
Publication: 9252000896 Revision: B 12/08
Page 2
Page 3

INTRODUCTION

General Information and Specifications
Controls and Indicators
Functional Description
Installation and Maintenance
Testing
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the relay is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.
9252000896 Rev B BE1-50/51B-232 Introduction i
Page 4
First Printing: January 2007
Printed in USA
© 2008 Basler Electric, Highland Illinois 62249 USA
All Rights Reserved
December 2008
CONFIDENTIAL
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
It is not provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Should further information be required, contact Basler Electric.
the intention of this manual to cover all details and variations in equipment, nor does this manual
INFORMATION
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-50/51B-232 Introduction 9252000896 Rev B
Page 5

REVISION HISTORY

The following information provides a historical summary of the changes made to this instruction manual (9252000896). Revisions are listed in reverse chronological order.
Manual
Revision and Date
B, 12/08
A, 03/08
, 01/07
 Updated Storage statement in Section 4. Modified Figure 5-2, Target Operational Test Setup. In Section 5, Testing, removed list of required tools and removed
steps about disconnecting and re-connecting relay terminal wires.
Modified Target Test so that TIME and INST targets can be verified
independently from each other.
Minor text edits throughout manual.
Updated front panel drawings to show new target reset button.
Initial release.
Change
9252000896 Rev B BE1-50/51B-232 Introduction iii
Page 6
This page intentionally left blank.
iv BE1-50/51B-232 Introduction 9252000896 Rev B
Page 7

CONTENTS

SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
SECTION 2 CONTROLS AND INDICATORS........................................................................................ 2-1
SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1
SECTION 4 INSTALLATION .................................................................................................................. 4-1
SECTION 5 TESTING ............................................................................................................................ 5-1
APPENDIX A TIME CHARACTERISTIC CURVES................................................................................ A-1
9252000896 Rev B BE1-50/51B-232 Introduction v
Page 8
This page intentionally left blank.
vi BE1-50/51B-232 Introduction 9252000896 Rev B
Page 9
SECTION 1 GENERAL INFORMATION
TABLE OF CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
INTRODUCTION....................................................................................................................................1-1
FEATURES............................................................................................................................................1-1
Advantages.........................................................................................................................................1-2
SPECIFICATIONS................................................................................................................................. 1-2
Current Sensing Input ........................................................................................................................ 1-2
Time Overcurrent (51) Element.......................................................................................................... 1-2
Instantaneous Overcurrent (50) Element...........................................................................................1-4
Burden................................................................................................................................................ 1-5
Frequency Response......................................................................................................................... 1-6
Transient Response........................................................................................................................... 1-6
Harmonic Response........................................................................................................................... 1-6
Target Indicators ................................................................................................................................1-7
Output Contacts .................................................................................................................................1-7
Type Tests.......................................................................................................................................... 1-7
Environment ....................................................................................................................................... 1-8
Agency Recognition ...........................................................................................................................1-8
Physical..............................................................................................................................................1-8
Figures
Figure 1-1. Integrating Reset Characteristic Curve...................................................................................1-4
Figure 1-2. Instantaneous Characteristic Curves......................................................................................1-5
Figure 1-3. Burden Characteristics............................................................................................................ 1-6
Figure 1-4. Harmonic Rejection................................................................................................................. 1-7
Tables
Table 1-1. GE IAC Relays Suitable for Direct Replacement..................................................................... 1-1
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)................................................. 1-3
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On).............................................. 1-3
9252000896 Rev B BE1-50/51B-232 General Information i
Page 10
This page intentionally left blank.
ii BE1-50/51B-232 General Information 9252000896 Rev B
Page 11
SECTION 1 GENERAL INFORMATION

INTRODUCTION

BE1-50/51B-232 protective relays are direct replacements for General Electric, IAC relays. BE1-50/51B­232 protective relays are enclosed in an S1 case. The BE1-50/51B-232 has a 5 ampere current sensing input. Compatible IAC model numbers are listed in Table 1-1.
Table 1-1. GE IAC Relays Suitable for Direct Replacement
IAC Model Number Curve Type
12IAC51AA 12IAC51BA 12IAC53AA 12IAC53BA 12IAC55AA 12IAC55BA 12IAC66AA 12IAC66BA 12IAC77AA 12IAC77BA
Inverse Inverse with Instantaneous Very Inverse Very Inverse with Instantaneous Short Time Short Time with Instantaneous Long Time Long Time with Instantaneous Extremely Inverse Extremely Inverse with Instantaneous
 Any digit covering all pickup ranges except 50 Hz models.
Basler Electric BE1-50/51B-232 protective relays are self-powered, microprocessor-based, non­directional phase or ground relays that monitor the magnitude of a single-phase ac current to provide accurate instantaneous and time overcurrent protection for 60 Hz power systems. Each model covers 15 popular time characteristics, a wide range of pickup settings, and field selectable instantaneous or integrating reset.

FEATURES

A wide range of pickup settings and front panel selectable time characteristics permit applications involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements. Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-232 overcurrent relays have the following standard features.
Independent time and instantaneous elements A secure method to manually trip the breaker at the relay front panel Direct reading front panel controls Minimum pickup setting for safety during installation Time characteristics extend to a pickup multiple of 40 Rugged draw-out construction with steel case Gravity latching targets retain indication without power Built-in accuracy eliminates internal adjustments Minimum transient overreach Field selectable characteristic curve selection similar to either GE IAC or ABB type curves Field selectable instantaneous or integrating reset Field selectable 0.0, 0.1, 0.2, or 0.3 second, fixed, instantaneous delay
Internal switches provide for selecting instantaneous element delays of 0.0, 0.1, 0.2, or 0.3 second, characteristic curve group selection for either GE IAC or ABB type curves, and instantaneous or integrating reset characteristics. Switch location and description is provided in Section 2.
9252000896 Rev B BE1-50/51B-232 General Information 1-1
Page 12

Advantages

BE1-50/51B-232 overcurrent relays have many advantages over other overcurrent relays. The primary advantages are:
Time characteristics are defined by equations and graphs Field selectable time characteristics Very low burden extends the linear range of the CTs Self powered from the sensed current Continuous automatic calibration
BE1-50/51B-232 overcurrent relays may be tested without removing the relay from the case. Shorting contacts are provided for all current inputs when the connection plugs or relay chassis is removed from the relay case.

SPECIFICATIONS

BE1-50/51B-232 electrical and physical specifications are listed in the following p aragraphs.

Current Sensing Input

Contin
uous Current: 14 Aac
One Second Rating: 400 Aac

Time Overcurrent (51) Element

Setting the T state and may be used as a safety setting.
IME PICKUP control at the minimum pickup setting places the relay in the most sensitive
Pickup
Setting Range: 0.5 to 15.9 Aac Setting Increment: 0.1 Aac Accuracy: ±2%, ±25 milliamperes at or above 0.5 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Timing Range
0.0 to 9.9 seconds in 0.1 second steps
Timing Accuracy
The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that is the sum of ±2%, ±25 milliamperes.
Timing Accuracy Example
PU setting: 5 amperes Current Applied: 6.5 amperes + Multiple Tolerance: 6.655 amperes – Multiple Tolerance: 6.345 amperes Time Curve: E Time Dial: 5.0 Minimum time dial using 6.655 amperes: 46.5470 seconds Maximum time dial using 6.345 amperes: 61.3968 seconds Curve time using 6.5 amperes: 53.1800 seconds
Curve Characteristics
Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch. Characteristic curves for the inverse and definite time functions are defined by the following equation.
Where: T
T
T
AD
N
KBD
CM
-
A, B, C, N, K = constants for the particular curve
= time to trip in seconds
T
D = time dial setting
M = multiple of pickup setting
1-2 BE1-50/51B-232 General Information 9252000896 Rev B
Page 13
Time characteristic curve constants are listed in Tables 1-2 and 1-3. Constants have been selected to conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40. Values of the constants are provided for use in computer relay setting software. Timing accuracy is 1 cycle, 2 percent of time to trip.
Table 1-2. Time Characteristic Curve Constants with SW3-3 Open (Off)
Curve Type
BE1 Similar To
Figure
Number
A B C N K R
Constants
S ABB CO-2 A-1 0.2663 0.03393 1.000 1.2969 0.028 0.500 L ABB CO-5 A-2 5.6143 2.18592 1.000 1.000 0.028 15.750 D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.875
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.750
I ABB CO-8 A-5 8.9341 0.17966 1.000 2.0938 0.028 9.000 V ABB CO-9 A-6 5.4678 0.10814 1.000 2.0469 0.028 5.500 E ABB CO-11 A-7 7.7624 0.02758 1.000 2.0938 0.028 7.750 B BS142-B A-8 1.4638 0.00000 1.000 1.0469 0.028 3.250
C BS142-C A-9 8.2506 0.00000 1.000 2.0469 0.028 8.000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.000
Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On)
Curve Type
BE1 Similar To
Figure
Number
A B C N K R
Constants
S GE IAC 55 A-10 0.0286 0.0208 1.000 0.9844 0.028 0.0940 L GE IAC 66 A-11 2.3955 0.00002 1.000 0.3125 0.028 7.8001
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.8750 M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I GE IAC 51 A-12 0.2747 0.1042 1.000 0.4375 0.028 0.8868 V GE IAC 53 A-13 4.4309 0.0991 1.000 1.9531 0.028 5.8231 E GE IAC 77 A-14 4.9883 0.0129 1.000 2.0469 0.028 4.7742 B BS142-B A-8 1.4636 0.00000 1.000 1.0469 0.028 3.2500
C BS142-C A-9 8.2506 0.00000 1.000 2.0469 0.028 8.0000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.0000
Notes for Tables 1-2 and 1-3 BE1 Curve Types: S: Short Inverse V: Very Inverse
L: Long Inverse E: Extremely Inverse D: Definite Time B: BS142 Very Inverse M: Moderately Inverse C: BS142 Extremely Inverse I: Inverse F: Fixed Time Delay
† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves. ‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.
Integrating Reset
Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of electromechanical relays. BE1-50/51B-232 relays provide the integrating reset function even when input current falls to zero.
9252000896 Rev B BE1-50/51B-232 General Information 1-3
Page 14
Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation constants are provided in Tables 1-2 or 1-3.
Integrating Reset Equation:
Where:
RD
T
R
2
1M
TR = Time to reset in seconds R = Constant for the particular curve D = TIME DIAL setting M = Current in multiples of PICKUP setting during reset
100.0
P0046-11
10.0
xRD (Seconds)
1.0
0.000 0.200 0.400 0.600 0.800 1.000 1.200
Multiple of Pickup
Vertical axis xRD (Seconds) is applicable for all curves and is derived from multiplying the constant R for the curve selected times D (the Time Dial setting).
Figure 1-1. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the I
NST PICKUP control to the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.
Pickup
Setting Range: 1 to 99 Aac Setting Increment: 1 Aac Accuracy: ±2%, ±25 milliamperes at or above 1.0 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Curve Characteristics
Instantaneous characteristic curves are similar to standard electromechanical instantaneous units. However, the time to trip for applications where the initial current through the relay is less than 0.4 ampere may be slightly longer. This may occur on a very lightly loaded circuit or when the relay is providing ground protection and is connected to measure neutral current. Figure 1-2 shows the instantaneous characteristic curves for maximum time to trip.
An additional fixed delay of 0.1, 0.2, or 0.3 second may be added with internal switches SW3-1 and SW3-2. This delay applies to both phase and ground applications. Closing switch SW3-1 provides an additional delay of 0.2 second. Closing switch SW3-2 provides an additional delay of 0.1 second. Closing
1-4 BE1-50/51B-232 General Information 9252000896 Rev B
Page 15
both SW3-1 and SW3-2 provides an additional delay of 0.3 second. Section 2 illustrates the location of SW3.
The instantaneous element in BE1-50/51B-232 relays may be set lower than the instantaneous element in ABB relays and still have the same reach. This is because the BE1-50/51B-232 instantaneous element effectively eliminates the fault current transient overreach components. When calculating BE1-50/51B­232 relay instantaneous element settings, calculate the symmetrical value without any adder for transient overreach.
P0048-10
Figure 1-2. Instantaneous Characteristic Curves

Burden

Burden is non-linear. Figure 1-3 illustrates the devi
ce burden.
At 0.5 amperes: 4.8 At 5.0 amperes: 0.2
9252000896 Rev B BE1-50/51B-232 General Information 1-5
Page 16
P0048-11
Figure 1-3. Burden Characteristics

Frequency Response

A chang
e of ±5 Hz from the nominal 60 Hz current causes <0.5% change in the current required for
pickup.

Transient Response

<10% ove
rreach with system time constants up to 40 ms.

Harmonic Response

Figure 1-4 shows that a
relay set for 1 ampere pickup would pick up at 0.96 amperes with a current containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be evaluated in the same manner.
1-6 BE1-50/51B-232 General Information 9252000896 Rev B
Page 17
Figure 1-4. Harmonic Rejection

Target Indicators

Gravity latch
ed, manually reset targets indicate that current of 0.2 amperes or greater was present in the trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See Output Contacts for maximum current rating.

Output Contacts

Output co
ntacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc: Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc: Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Type Tests

Isolation
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows. All circuits to ground: 2,828 Vdc or 2,000 Vac
Input to Output Circuits: 2,828 Vdc or 2,000 Vac
Surge Withstand Capability Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems. Impulse
Qualified to IEC 255-5.
Radio Frequency Interference (RFI)
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144 MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical planes.
9252000896 Rev B BE1-50/51B-232 General Information 1-7
Page 18
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.

Environment

ng Te
Operati
mperature: –40C to 70C (–40F to158F)
Storage Temperature: –50C to 70C (–58F to 158F).
Agency Recog
GOST-R Certification
nition
GOST-R certified per the relevant standards of Gosstandart of Russia.
Physical
Case Size:
S1 (Refer to Section 4, Installation for case dimensions.)
Weight: 6.1 lb (2.77 kg)
1-8 BE1-50/51B-232 General Information 9252000896 Rev B
Page 19
SECTION 2 CONTROLS AND INDICATORS
TABLE OF CONTENTS
SECTION 2 CON
INTRODUCTION....................................................................................................................................
Figures
Figure 2-1. Front Panel Controls and Indicators ....................................................................................... 2-1
Figure 2-2. Location of SW3......................................................................................................................2-2
Tables
Table 2-1. BE1-50/51B-231 Controls and Indicators (Refer to Figures 2-1 and 2-2)................................2-3
TROLS AND INDICATORS........................................................................................2-1
2-1
9252000896 Rev B BE1-50/51B-232 Controls and Indicators i
Page 20
This page intentionally left blank.
ii BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
Page 21
SECTION 2 CONTROLS AND INDICATORS

INTRODUCTION

Figure 2-1 illustrates the front panel controls and indicators of the BE1-50/51B-232. Figure 2-2 illustrates the location of switch SW3. Both illustrations have lettered call-outs that correspond to the control and indicator descriptions provided in Table 2-1.
Figure 2-1. Front Panel Controls and Indicators
9252000896 Rev B BE1-50/51B-232 Contr
ols and Indicators 2-1
Page 22
SW3
Figure 2-2. Location of SW3
2-2 BE1-50/51B-232 Controls and Indicators
P0053-50
9252000896 Rev B
Page 23
Table 2-1. BE1-50/51B-232 Controls and Indicators (Refer to Figures 2-1 and 2-2)
Locator Control or Indicator Function
A INST MANUAL TRIP
Test Points
B INST PICKUP
Selectors
C Targets
D TIME PICKUP
Selectors
E
F
CURVE Selector Ten position selector switch to select one of nine inverse functions
TIME DIAL Selectors Two selector switches (UNITS and TENTHS) to select the desired
G TIME MANUAL TRIP
Test Points
When shorted, the test points (jacks) provide a secure means to manually trip the controlled breaker. Jacks accept a standard 0.08 inch diameter phone tip plug.
Two switches (TENS and UNITS) to select pickup current in amperes. Changing switch selectors while the relay is in service may cause tripping.
Red target indicators latch when the trip circuit current is greater than 0.2 amperes. One target each for TIME and INST.
Two switches (UNITS and TENTHS) t o select pickup current in amperes. Changing switch selectors while the relay is in service may cause tripping.
or one fixed time function.
characteristic curve. A setting of 0.0 results in instantaneous operation without any intentional delay. A setting of 9.9 corresponds to the typical time provided by an electromechanical relay at its maximum dial setting.
When shorted, the test points provide a secure means to manually trip the controlled breaker. Jacks accept a standard 0.08 inch diameter phone tip plug.
H
I
SW3
ACTIVE/PICKUP LED Red LED indicates sensed current has ex ceeded the TIME
PICKUP setting. LED turns from red to green when sensed current falls below 95% of pickup setting. When the LED is green, the relay is active but has not picked up.
Target RESET Button Linkage extends through back of front cover to reset both gravity
latched target indicators.
SW3-1
SW3-1 provides an additional instantaneous delay of 0.2 second when closed (ON). Closing both SW3-1 and SW3-2 provides an additional instantaneous delay of 0.3 second.
SW3-2
SW3-2 provides an additional instantaneous delay of 0.1 second when closed (ON). Closing both SW3-2 and SW3-1 provides an additional instantaneous delay of 0.3 second.
SW3-3
SW3-3 provides selection of GE IAC type curves or ABB type curves. Closing switch SW3-3 (ON) selects GE IAC type curves (refer to Table 1-3). Opening switch SW3-3 (OFF) selects ABB type curves (refer to Table 1-2).
SW3-4
SW3-4 provides selection of either instantaneous or integrating reset characteristics. Closing S W3-4 (ON) selects integrating reset characteristics. Opening SW3-4 (OFF) selects instantaneous reset characteristics.
9252000896 Rev B BE1-50/51B-232 Controls and Indicators 2-3
Page 24
This page intentionally left blank.
2-4 BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
Page 25
SECTION 3 FUNCTIONAL DESCRIPTION
TABLE OF CONTENTS
SECTION 3 FUNCTIONA
GENERAL..............................................................................................................................................
FUNCTIONAL DESCRIPTION .............................................................................................................. 3-1
Sensing Input......................................................................................................................................
Power Supply.....................................................................................................................................
Instantaneous Signal.......................................................................................................................... 3-1
Time Signal.........................................................................................................................................
Microprocessor...................................................................................................................................
Power-Off Sensing............................................................................................................................. 3-1
Outputs...............................................................................................................................................
Figures
Figure 3-1. Functional Block Diagram....................................................................................................... 3-2
L DESCRIPTION........................................................................................... 3-1
3-1 3-1
3-1 3-1
3-1 3-2
9252000896 Rev B BE1-50/51B-232 Functional Description i
Page 26
This page intentionally left blank.
ii BE1-50/51B-232 Fun ctional Description 9252000896 Rev B
Page 27
SECTION 3 FUNCTIONAL DESCRIPTION

GENERAL

BE1-50/51B-232 Overcurrent Relays are microprocessor based non-directional relays that measure ac current to provide secure and reliable instantaneous and time overcurrent protection for power sy stems.

FUNCTIONAL DESCRIPTION

Sensing Input

Single phase ac current from system current transformers (CT) is brought into the Overcurrent Relay at terminals 5 and 6. Refer to Figure 3-1 to follow the functional description. The input current is applied to internal power and signal CTs.

Power Supply

nt from the power CT is rectified, filtered, and supplied to all relay internal circuitry for operating
Curre power. A precision +5 Vdc supply also serves as a reference for automatic calibration.

Instantaneous Signal

nt from the signal CT is rectified and applied to the instantaneous scaling resistors controlled by the
Curre INST PICKUP selector switches. The analog voltage of the instantaneous input signal developed across the scaling resistors is filtered and applied to the multiplexor (MUX).

Time Signal

nt from the signal CT is also rectified and applied to the time scaling resistors controlled by the TIME
Curre PICKUP selector switches. The analog voltage of the time input signal is also filtered and applied to the multiplexor.

Microprocessor

Operating po microprocessor is active and executing code, the ACTIVE/PICKUP LED is green. When the input current falls below an acceptable level, the supervisor circuit interrupts the microprocessor, halts further operation, and turns OFF the ACTIVE/PICKUP LED. A microprocessor watchdog feature resets the microprocessor program when the program flow is interrupted.
Information from the TIME DIAL selector switches, the TIME CURVE selector switch, INST DELAY switches, and RESET CHAR switch is also applied to the microprocessor. The microprocessor uses these inputs to set the operating parameters.
When the microprocessor is ready for analog information from the multiplexor, microprocessor control signals cause the multiplexor to route the desired input through to the output. The output is converted from an analog value to a digital value and applied to the microprocessor.
The microprocessor performs the program operations based on the inputs and the internal software program. When the sensed current exceeds the TIME PICKUP setting, the ACTIVE/PICKUP LED turns from green to red. The 50/51 contact is closed in accordance with the TIME characteristic equation or if the sensed current exceeds the INST PICKUP setting.

Power-Off Sensing

r-off sensing circuits measure the voltage across a capacitor at power-down and at power-up.
Powe These circuits determine how long power has been removed based on the difference voltage and the circuit RC time constant. This provides information for the integrating reset function even when power has been entirely removed.
wer from the power supply is applied to the microprocessor supervisor circuit. When the
9252000896 Rev B BE1-50/51B-232 Functional Description 3-1
Page 28

Outputs

Instantaneous and Timed
System circuit breakers controlled by the output contacts can be manually tripped by applying a short across the TIME or INST MANUAL TRIP front panel test points. Current flow in the trip circuit is indicated by the operation of the target. The targets will not operate without adequate operating power for the relay.
WARNING!
Trip circuit voltage is present at the front panel test points. When shorting the test points, use insulated jumpers to avoid contact with these voltages.
Figure 3-1. Functional Block Diagram
3-2 BE1-50/51B-232 Functional Description 9252000896 Rev B
Page 29
SECTION 4 INSTALLATION
TABLE OF CONTENTS
SECTION 4 INSTALLATION .................................................................................................................. 4-1
GENERAL..............................................................................................................................................4-1
MOUNTING............................................................................................................................................4-1
FACTORY SETTINGS...........................................................................................................................4-4
APPLICATION COORDINATION.......................................................................................................... 4-4
CONNECTIONS .................................................................................................................................... 4-6
MAINTENANCE.....................................................................................................................................4-7
STORAGE..............................................................................................................................................4-7
Figures
Figure 4-1. Outline Dimensions for S1 Case, Semi-Flush Mounting.........................................................4-1
Figure 4-2. Panel Drilling Diagram for S1 Case, Semi-Flush Mounting....................................................4-2
Figure 4-3. Panel Drilling Diagram for S1 Case, Projection Mounting...................................................... 4-3
Figure 4-4. Panel Drilling Diagram for S1 Case, Side View, Projection Mounting.................................... 4-4
Figure 4-5. Coordination Timing Diagram................................................................................................. 4-5
Figure 4-6. AC Input Connections............................................................................................................. 4-6
Figure 4-7. DC Control Connections......................................................................................................... 4-7
9252000896 Rev B BE1-50/51B-232 Installation i
Page 30
This page intentionally left blank.
ii BE1-50/51B-232 Installation 9252000896 Rev B
Page 31
SECTION 4 INSTALLATION

GENERAL

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to prevent damage during transit. Immediately upon receipt of a relay, check the model and part number against the requisition and packing list to see that they agree. Visually inspect the relay for damage that may have occurred during shipment. If there is evidence of damage, immediately file a claim with the carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric, Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5. If the relay won't be installed immediately, store the relay in its original shipping carton in a moisture and dust-free environment.

MOUNTING

Relay outline dimensions and panel drilling diagrams are shown in Figures 4-1 through 4-4. Dimensions in parentheses are in millimeters.
D2750-29
Figure 4-1. Outline Dimensions for S1 Case, Semi-Flush Mounting
9252000896 Rev B BE1-50/51B-232 Installation 4-1
Page 32
Figure 4-2. Panel Drilling Diagram for S1 Case, Semi-Flush Mounting
4-2 BE1-50/51B-232 Installation 9252000896 Rev B
Page 33
Figure 4-3. Panel Drilling Diagram for S1 Case, Projection Mounting
9252000896 Rev B BE1-50/51B-232 Installation 4-3
Page 34
2.40
(62.48)
1.95
(49.53)
4.03
(102.4)
4.03
(102.4)
6.19
(157.2)
AA
.25
(6.4)
MOUNTING PANEL
5/16-18 STUD 2 PLACES
CASE
DETAIL A-A
SHOWING THE ADDITION OF WASHERS
OVER THE BOSS TO TIGHTEN THE
RELAY AGAINST THE PANEL.
MOUNTING PANEL
PANEL
10-32 SCREWS
.31
(7.9)
TERMINAL EXTENSION (TYP.) FOR DETAILED INSTRUCTIONS. SEE THE TERMINAL PROJECTION
.75
(19.1)
MOUNTING KIT SUPPLIED.
2.195
(55.75)
NOTE: PROJECTION MOUNT USES WASHERS OVER THE BOSSES AS SHOWN IN THIS ILLUSTRATION.
Figure 4-4. Panel Drilling Diagram for S1 Case, Side View, Projection Mounting

FACTORY SETTINGS

Factory settings for the internal switches of SW3 are as follows:
SW3-1 — OFF (0.0 additional fixed delay for the instantaneous element). SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element). SW3-3 — ON (General Electric, IAC type characteristic curves). SW3-4 — ON (Integrating reset characteristics).
D2750-25
12-17-99

APPLICATION COORDINATION

In a typical application coordination scheme, a BE1-50/51B-232 is being used to provide primary protection for a radial distribution feeder. An electromechanical overcurrent relay with extremely inverse timing provides protection for the transformer and bus. To improve coordination with the electromechanical relay, the BE1 relay with integrating reset characteristic has the time characteristic
4-4 BE1-50/51B-232 Installation 9252000896 Rev B
Page 35
curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder
reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a permanent fault occurs (magnitude ten times pickup), calculate the feeder breaker trip time for each of the three operations. Refer to Section 1 for characteristic curve constants.
From the time characteristic curve equation.
T
Trip
AD
N
CM
KBD
.
276247
09382
.
524815
.
.

110
110806124
seconds 0.209
0280202758.0
.
028005516.0
.
From the reset characteristic curve equation.
RD
T
2
Reset
27.75
10
2
1M
seconds 15.5
M = 0 if current goes to zero. Negative result indicates reset time.
Results: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.
In Figure 4-1, T T T
= 0.209 seconds (relay was at reset).
A
= value < TA because rewind has not gone to zero.
B
= value < TA because rewind has not gone to zero.
C
Figure 4-5. Coordination Timing Diagram
9252000896 Rev B BE1-50/51B-232 Installation 4-5
Page 36
Equation for time to trip during rewind (before relay is reset).



Second Operation
T
Occurence This Trip
T
B
30.209
15.5
Time RewindTrip Full
Rewind Full
Third Operation
B
T
C
C
seconds 0.040T
15.5
seconds 0.161T
11.960.209

CONNECTIONS

NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the relay is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.
Typical ac input and dc control connections are shown in Figures 4-6 and 4-7. Refer to the block diagram in Section 3 for relay internal connections.
Figure 4-6. AC Input Connections
4-6 BE1-50/51B-232 Installation 9252000896 Rev B
Page 37
Figure 4-7. DC Control Connections

MAINTENANCE

BE1-50/51B-232 overcurrent relays require no preventive maintenance. However, periodic checks should be performed according to scheduled practices. A recommended periodic test is provided in Section 5. If the relay fails to function properly, contact the Technical Sales Support Department of Basler Electric.

STORAGE

This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once per year.
9252000896 Rev B BE1-50/51B-232 Installation 4-7
Page 38
This page intentionally left blank.
4-8 BE1-50/51B-232 Installation 9252000896 Rev B
Page 39
SECTION 5 TESTING
TABLE OF CONTENTS
SECTION 5 TESTING ............................................................................................................................ 5-1
GENERAL..............................................................................................................................................5-1
DIELECTRIC TEST ...............................................................................................................................5-1
OPERATIONAL TEST PROCEDURE................................................................................................... 5-1
Test Equipment Required...................................................................................................................5-1
Test Procedure................................................................................................................................... 5-3
SETTING THE RELAY ..........................................................................................................................5-5
PERIODIC TESTS................................................................................................................................. 5-5
General............................................................................................................................................... 5-5
Periodic Test.......................................................................................................................................5-5
Figures
Figure 5-1. Pickup and Timing Test Setup................................................................................................ 5-2
Figure 5-2. Target Operational Test Setup................................................................................................ 5-2
9252000896 Rev B BE1-50/51B-232 Testing i
Page 40
This page intentionally left blank.
ii BE1-50/51B-232 Testing 9252000896 Rev B
Page 41
SECTION 5 TESTING

GENERAL

Dielectric testing, operational testing, and periodic testing are described in the following paragraphs.

DIELECTRIC TEST

In accordance with IEC 255-5 and IEEE C37.90-1989, one-minute dielectric (high potential) tests may be performed as follows:
All circuits to ground: 2,828 Vdc or 2,000 Vac Input to output circuits: 2,828 Vdc or 2,000 Vac
Output contacts are surge protected.

OPERATIONAL TEST PROCEDURE

The following procedures verify operation of relays BE1-50/51B-232. The test setup of Figures 5-1 and 5-2 are intended primarily as an illustration of the principles involved. Other test setups known to be capable of testing with the stated and implied tolerances (including equipment specifically designed for testing relays) may be used.

Test Equipment Required

Current source with a range from 0 to 20 Aac (sensing input current)
  AC or DC voltage source (target operation) Timer or counter
CAUTION
To ensure proper timing during testing, before each test, remove the current from the unit for R times D seconds (refer to Section 1, Specifications, Time Reset for R and D definitions).
9252000896 Rev B BE1-50/51B-232 Testing 5-1
Page 42
Figure 5-1. Pickup and Timing Test Setup
Figure 5-2. Target Operational Test Setup
5-2 BE1-50/51B-232 Testing 9252000896 Rev B
Page 43
NOTE
When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect the calibration of the TIME functions. TIME PICKUP settings of 00 also affect INST functions.

Test Procedure

The following tests are performed to verify functionality of the BE1-50/51B-232 overcurrent relay. The TIME and INST output contact terminals are strapped together. Therefore it is necessary to disconnect specific wires during the TIME and INST pickup tests. This verifies the proper functionality of the TIME and INST elements.
NOTE
Observe all applicable electrostatic discharge (ESD) precautions when handling the relay draw-out assembly.
TIME Pickup Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON and SW3-4 to
ON.
Set TIME DIAL to 0.0.  Set CURVE to S  Set TIME PICKUP to 0.5.  Set INST PICKUP to 90.
Step 1. Slowly increase current to terminals 5 and 6. PICKUP LED should turn RED at a maximum input
current of 0.550 ampere. Step 2. Decrease input current until PICKUP LED turns GREEN then OFF. Step 3. Set TIME PICKUP to 2.2. Step 4. Slowly increase current to terminals 5 and 6. PICKUP LED should change from GREEN to RED
at an input current of 2.131 to 2.269 amperes. Step 5. Decrease input current until PICKUP LED turns OFF.
INST Pickup Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.  Set TIME DIAL to 0.0.  Set CURVE to S  Set TIME PICKUP to 15.9.  Set INST PICKUP to 01.
Step 1. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
0.955 to 1.045 amperes. Step 2. Decrease input current until INST output contacts open. Step 3. Set INST PICKUP to 08. Step 4. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
7.815 to 8.185 amperes. Step 5. Decrease input current until INST output contacts open.
9252000896 Rev B BE1-50/51B-232 Testing 5-3
Page 44
Time Dial Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.  Set TIME DIAL to 4.5.  Set CURVE to S  Set TIME PICKUP to 1.0.  Set INST PICKUP to 90.
Step 1. Prepare to apply 1.5 amperes input current to terminals 5 and 6 and record the elapsed time from
when current is applied until TIME output contacts close.
Step 2. Apply the current (step from 0 to 1.5 amperes) and record the elapsed time. Elapsed time should
be 0.345 to 0.424 seconds. (This tolerance is greater than ±2 % because it is the accumulation of both pickup and timing tolerances.)
Step 3. Remove input current.
Target Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-2.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.  Set TIME DIAL to 4.5.  Set CURVE to S  Set TIME PICKUP to 1.0.  Set INST PICKUP to 90.
Step 1. Set voltage source to provide a target current of 1.0 ampere. Step 2. Apply 5 amperes input current to terminals 5 and 6. Check that the TIME target operates. Step 3. Remove input current and reset target. Step 4. Set TIME PICKUP to 15.9 and set INST PICKUP to 01. Step 5. Set voltage source to provide a target current of 1.0 ampere. Step 6. Apply 5 amperes input current to terminals 5 and 6. Check that the INST target operates. Step 7. Remove input current and reset target.
Manual Trip Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-2.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.  Set TIME DIAL to 4.5.  Set CURVE to S  Set TIME PICKUP to 1.0.  Set INST PICKUP to 01.
WARNING!
Trip circuit voltage is present at the front panel test points. When shorting the test points, use insulated jumpers to avoid contact with these voltages.
Step 1.
Set voltage source to provide a target current of 1.0 ampere.
Step 2. Apply 0.9 ampere input current to terminals 5 and 6. (0.9 ampere provides input power but stays
below pickup.)
Step 3. Connect a jumper between TIME MANUAL TRIP test points. Check that TIME target operates.
5-4 BE1-50/51B-232 Testing 9252000896 Rev B
Page 45
Step 4. Connect a jumper between INST MANUAL TRIP test points. Check that INST target operates. Step 5. Reset targets.
Integrating Reset Test
Perform preliminary setup:
Connect test setup as shown in Figure 5-1.  Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OFF, SW3-3 to ON, and SW3-4 ON.  Set TIME DIAL to 9.9.  Set CURVE to V.  Set TIME PICKUP to 1.0.  Set INST PICKUP to 90.
Step 1. Set voltage source to provide a target current of 1.0 ampere. Step 2. Read all of Step 3 before beginning Step 3. Step 3. Apply 4.0 amperes input current to terminals 5 and 6. After the unit trips, remove the input current
for 29 ±0.25 seconds, then reapply the 4.0 amperes input current. Record the elapsed time from the re-application of input current to the output retrip.
Result: Elapsed time should be 2.08 ±0.4 seconds.

SETTING THE RELAY

Select the desired relay settings before putting the relay into service. Changing pickup current settings while the relay is in service may cause tripping.

PERIODIC TESTS

General

All relays should be tested periodically to identify and correct any problems that are found. Single phase relays such as the BE1-50/51B-232 are normally used in groups of four (three phase and
ground) on the protected circuit. This relay scheme allows each unit to be withdrawn one at a time for testing purposes without losing protection. Only three are required at any one time to sense all types of faults on a grounded wye system. Refer to Figures 5-1 and 5-2 for recommended test setups.

Periodic Test

Periodi Step 1. Verify that the instantaneous pickup is within ±2% of the value set on the dials. Pickup occurs
Step 2. Verify that the time pickup is within ±2% of the value set on the dials. Pickup occurs when the
Step 3. Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as
Step 4. Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater
Step 5. Verify that the targets operate with one ac ampere of trip current in the trip circuits and that they
c testing should consist of the following procedures.
when the INST output contacts close.
LED turns GREEN then RED.
the time given on the characteristic curve. Refer to Section 1 for the characteristics curves.
than the time given on the instantaneous characteristic curve. Refer to Section 1 for the instantaneous characteristic curve.
can be reset using the RESET BUTTON.
9252000896 Rev B BE1-50/51B-232 Testing 5-5
Page 46
This page intentionally left blank.
5-6 BE1-50/51B-232 Testing 9252000896 Rev B
Page 47
APPENDIX A TIME CHARACTERISTIC CURVES
TABLE OF CONTENTS
APPENDIX A TIME CHARACTERISTIC CURVES................................................................................A-1
TIME CHARACTERISTIC CURVES......................................................................................................A-1
Figures
Figure A-1. Time Characteristic Curve, S-Short Inverse (SW3-3 OFF, Similar to ABB CO-2).................A-1
Figure A-2. Time Characteristic Curve, L-Long Inverse (SW3-3 OFF, Similar to ABB CO-5)..................A-2
Figure A-3. Time Characteristic Curve, D-Definite Time (Similar to ABB CO-6) ......................................A-3
Figure A-4. Time Characteristic Curve, M-Moderately Inverse (Similar to ABB CO-7).............................A-4
Figure A-5. Time Characteristic Curve, I-Inverse (SW3-3 OFF, Similar to ABB CO-8) ...........................A-5
Figure A-6. Time Characteristic Curve, V-Very Inverse (SW3-3 OFF, Similar to ABB CO-9) .................A-6
Figure A-7. Time Characteristic Curve, E-Extremely Inverse (SW3-3 OFF, Similar to ABB CO-11)........A-7
Figure A-8. Time Characteristic Curve, BS142-B (BS142 Very Inverse)..................................................A-8
Figure A-9. Time Characteristic Curve, BS142-C (BS142 Extremely Inverse).........................................A-9
Figure A-10. Time Characteristic Curve, S2-Short Inverse (SW3-3 ON, Similar to GE IAC 55).............A-10
Figure A-11. Time Characteristic Curve, L2-Long Inverse (SW3-3 ON, Similar to GE IAC 66)..............A-11
Figure A-12. Time Characteristic Curve, I2-Inverse (SW3-3 ON, Similar to GE IAC 51)........................A-12
Figure A-13. Time Characteristic Curve, V2-Very Inverse (SW3-3 ON, Similar to GE IAC 53)..............A-13
Figure A-14. Time Characteristic Curve, E2-Extremely Inverse (SW3-3 ON, Similar to GE IAC 77).....A-14
9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves i
Page 48
This page intentionally left blank.
ii BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B
Page 49
APPENDIX A TIME CHARACTERISTIC CURVES

TIME CHARACTERISTIC CURVES

Figures A-1 through A-14 illustrate the time characteristic curves that are programmed into the nonvolatile memory of this relay.
Figure A-1. Time Characteristic Curve, S-Short Inverse
(SW3-3 OFF, Similar to ABB CO-2)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-1
Page 50
Figure A-2. Time Characteristic Curve, L-Long Inverse
(SW3-3 OFF, Similar to ABB CO-5)
A-2 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 51
Figure A-3. Time Characteristic Curve, D-Definite Time
(Similar to ABB CO-6)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-3
Page 52
Figure A-4. Time Characteristic Curve, M-Moderately Inverse
(Similar to ABB CO-7)
A-4 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 53
Figure A-5. Time Characteristic Curve, I-Inverse
(SW3-3 OFF, Similar to ABB CO-8)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-5
Page 54
Figure A-6. Time Characteristic Curve, V-Very Inverse
(SW3-3 OFF, Similar to ABB CO-9)
A-6 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 55
Figure A-7. Time Characteristic Curve, E-Extremely Inverse
(SW3-3 OFF, Similar to ABB CO-11)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-7
Page 56
Figure A-8. Time Characteristic Curve, BS142-B
(BS142 Very Inverse)
A-8 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 57
Figure A-9. Time Characteristic Curve, BS142-C
(BS142 Extremely Inverse)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-9
Page 58
Figure A-10. Time Characteristic Curve, S2-Short Inverse
(SW3-3 ON, Similar to GE IAC 55)
A-10 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 59
Figure A-11. Time Characteristic Curve, L2-Long Inverse
(SW3-3 ON, Similar to GE IAC 66)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-11
Page 60
Figure A-12. Time Characteristic Curve, I2-Inverse
(SW3-3 ON, Similar to GE IAC 51)
A-12 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 61
Figure A-13. Time Characteristic Curve, V2-Very Inverse
(SW3-3 ON, Similar to GE IAC 53)
9252000896 Rev B BE1-50/51B-232 Time Ch
aracteristic Curves A-13
Page 62
Figure A-14. Time Characteristic Curve, E2-Extremely Inverse
(SW3-3 ON, Similar to GE IAC 77)
A-14 BE1-50/51B-232 Time Characteris
tic Curves 9252000896 Rev B
Page 63
Page 64
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618-654-2341 FAX +1 618-654-2351
Loading...