Bard FH085D36D, FH110D48D, FH110D60D, FLF085D36D, FLR085D36D Installation Instructions Manual

...
0 (0)
OIL FURNACE
INSTALLATION INSTRUCTIONS
MODELS
FH085D36D FH110D48D FH110D60D FLF085D36D FLR085D36D FLF110D48D FLR110D48D FLR140D60D FC085D36D
WARNING
READ ALL INSTRUCTIONS CAREFULL Y BEFORE BEGINNING THE INSTALLATION.
THIS INST ALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INST ALLATION LOCATION.
IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS.
F AILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPER TY DAMAGE, BODIL Y INJURY OR DEATH.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE V APORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
IMPORTANT NOTICE
THIS FURNACE IS NOT INTENDED FOR USE AS A CONSTRUCTION HEA TER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING PHASES OF A STRUCTURE IS CONSIDERED AS "OPERA TION IN A CORROSIVE A TMOSPHERE" AND "UNUSUAL, NEGLIGENT OR IMPROPER USE" AND AS SUCH ARE CONSIDERED EXCLUSIONS BY THE BARD MANUFACTURING COMPANY LIMITED W ARRANTY.
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual: 2100-392A Supersedes: File: VOL. I, TAB 3 Date: 12-17-01
Copyright 2001
CONTENTS
Getting Other Information and Publications Installation and Operating Instructions
Equpment Selection ...............................................2
Locating the Furnace..............................................2
Duct Work...............................................................6
Installing a Cooling Unit..........................................6
Wiring ...............................................................6
Oil Line Piping ........................................................8
Beckett AFG Oil Burner..........................................8
Beckett “CleanCut” Oil Pump .................................9
Beckett Solid State Igniter ......................................9
Beckett R7184B Primary Control............................9
Beckett R7184B Primary Operational Guide ........10
Burner Set up and Adjustments ........................... 11
Burner Nozzle and Electrode Adjustments...........14
Ventilation and Combustion Air ............................14
Louvers and Grilles...............................................18
Venting .............................................................18
Thermostat ...........................................................18
Fan & Limit Control...............................................18
T ABLES
Table 1 Minimum Clearances ............................. 2
Table 2 Dimensions Lo-Boy Models .................. 3
T able 3 Dimensions Hi-Boy Models .................... 4
T able 4 Dimensions Counterflow Models............ 5
Table 5 Electrical Data ........................................ 7
Table 6 Furnace Data ........................................11
Table 7 Correlation of % of CO
Reserve Air .......................................... 13
Table 8 No. 2 Fuel Oil Efficiency Chart ............. 13
T able 9 Recommended Start-Up Settings ........ 13
T able 10 Round Duct Sizing ............................... 14
Table 1 1 Sq.Ft. Required as
Unconfined Space................................ 15
Table 12 Minimum Ventilation Openings............. 16
Table 13 Temperature Rise Ranges, Limit
Control Settings, and
Heating Blower Speeds........................ 19
Table 14 Filter Sizes for Gas Furnaces............... 20
, O2 and
2
Filters
Hi-Boy Models – Filter Locations & Removal
and Replacement Procedures ..............................20
Counterflow Models – Filter Locations ...............21
Lo-Boy Models – Filter Locations .......................22
Maintenance
Lubrication ............................................................23
Inspect Air Filter....................................................23
Final Inspeciton and Test......................................23
Service Hints ........................................................23
Combination Combustion Chamber/Burner
Mounting System..................................................24
To Remove Burner Only .......................................24
To Remove Entire Combustion Chamber
Mounting System..................................................24
Common Causes of Trouble.................................26
Care of Finish .......................................................26
Cleaning of Furnace .............................................26
Blower System Resistance Curves ................ 27-30
Wiring Diagrams............................................. 31-33
FIGURES
Figure 1 Lo-Boy Models Dimensions ............... 3
Figure 2 Hi-Boy Models Dimensions................ 4
Figure 3 Counterflow Models Dimensions ....... 5
Figure 4 Typical Installation Requirement
Front Flue .......................................... 7
Figure 5 T ypical Single Inside
Tank Installation................................. 8
Figure 6 Pressure Gauge Connection to
Pressure Gauge Port....................... 12
Figure 7 Electrode Adjustments..................... 14
Figure 8 All Air From Inside Building.............. 15
Figure 9 All Air From Outdoors ...................... 16
Figure 10 All Air From Outdoors Through
Ventilated Attic................................. 17
Figure 11 All Air From Outdoors - Inlet Air
From Ventilated Crawl Space and
Outlet Air to Ventilated Attic............. 17
Figure 12 Typical Installation of 16x25x1
Filter Rack........................................ 20
Figure 13 Typical Installation of 20x25x1
Filter Rack........................................ 20
Figure 14 Filter Installation - Counterflow
Models ............................................. 21
Figure 15 Filter Installation - Lo-Boy Models ... 24
Figure 16A Removal of Burner Only .................. 20
Figure 16B Removal of Entire Combustion
Chamber Mounting System ............. 25
i
GETTING OTHER INFORMA TION and PUBLICATIONS
These publications can help you install the furnace. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Fuel Gas Code ........... ANSI Z223.1/NFPA54
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Standard for Chimneys, Fireplaces, Vents ... NFPA 211 and Solid Fuel Burning Appliances
Load Calculation for .......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACC A Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-392 Page 1
INST ALLATION and OPERATING INSTRUCTIONS
EQUIPMENT SELECTION
An accurate heating load calculation must be conducted using American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) or Air Conditioning Contractors of America (ACCA) manuals. Do not add a large safety factor above the calculated value. If the calculated heating load requirement exceeds the heating capacity rating of a given model, use only the next larger size available. Never increase by any more than absolutely necessary based upon available equipment heating capacities. Always select based upon heat capacity (output), never use input capacities.
NOTE: It is the personal responsibility and
obligation of the purchaser to contract a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.
LOCATING THE FURNACE
When installing the furnace be sure to provide adequate space for easy service and maintenance. Locate the furnace as close to the chimney as practical, giving consideration to the accessibility of the oil burner, controls, and blower for service. Allow a minimum of 24 inches at front of furnace for servicing oil burner. Allow adequate room for filter and blower maintenance. Clearance from combustible material as
stated on the furnace and repeated in Table 1 must be maintained. For damp basement installations, a raised
concrete pad is recommended. This will help keep the bottom of the furnace dry and reduce rusting.
An oil burner must have a generous supply of combustion air to operate properly. The flow of combustion and ventilating air must not be obstructed from reaching the furnace. See “Ventilation and Combustion Air” section.
The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.
This unit is not designed for mobile home or trailer installations. Always install furnace in a level position.
TABLE 1
MINIMUM CLEARANCES
sehcnI--secnaraelCnoitallatsnImuminiM
1
ledoM
D63D580HF D84D011HF D06D011HF
D84D011FLF D84D011RLF
D63D580CF
j
C
NC
*
**
4 4 4
D63D580FLF
6
D63D580RLF
6 6
6
D06D041RLF
6 6
For the first three (3) feet from plenum. After three (3) feet, no clearance required. Combustible flooring Noncombustible floor Maintained on one side or the other to achieve filter access and/or blower service. Floor must be noncombustible. For furnace only installation can be installed on combustible flooring only when installed on special base part no. CFB7 available from factory. When air conditioning coil cabinet DCB23-22 is used then use special base part no. CFB23.
1 1 1
0
81
0
81 81
1
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
tcuD
2 2 2
2 2 2
2 2 2
eulF epiProolFtnorFkcaBsediSpoTsediStnorFkcaBsediS
9 9 9
9 9 9
9 9 9
C C C
CN CN CN
CN CN
**
CN
ecivreSmuminiM
secnaraelCecanruFmunelP
42 42 42
42 42 42
42 42 42
---
---
---
42 42 42
42 42
---
---
---
---
*
81 81
*
81
*
81
*
81
*
---
Manual 2100-392 Page 2
TABLE 2
LO-BOY MODELS
DIMENSIONS (INCHES)
munelP
tenibaC
ledoM
rebmuN
D63D580FLF D63D580RLF
D84D011RLF D84D011RLF
D06D041RLF62050502x5261x52raeR68/5-34---1x52x021
j
Washable type filter 1 nom. thickness
A
32 32
32 32
B
htdiW
C
htpeD
4/1-74 4/1-74
4/1-74 4/1-74
thgieH
4/1-04 4/1-04
4/1-44 4/1-44
ExD
sgninepOnoitcennoCeulFsretliFriA
FxD
ylppuS
02x22 02x22
02x22 02x22
nruteRnoitacoL
61x22 61x22
61x22 61x22
G
tnorF
raeR
tnorF
raeR
HJ
.aiD
6 6
6 6
eziS
---
43
---
83
4/1-5
--­4/1-5
---
1
.oN desU
1x02x61
1
1x02x61
1
1x02x02
1
1x02x02
1
FIGURE 1
LO-BOY MODELS DIMENSIONS
MIS-1345
Manual 2100-392 Page 3
TABLE 3
HI-BOY MODELS
DIMENSION (INCHES)
tenibaCsgninepOmunelP
ledoM
rebmuN
D63D580HF D84D011HF D06D011HF
A
htdiW
32 32 32
j
Washable type filter
k
Left or right side return air option. Must be cut in by installer.
B
htpeD
2/1-13 2/1-13 2/1-13
C
thgieH
65 06 06
ExD
ylppuS
02x22 02x22 02x22
2
HxF
nruteR
41x32 41x32 41x32
G
.aiDeulF
6 6 6
1
eziSretliF
52x61 52x61 52x02
FIGURE 2
HI-BOY MODELS DIMENSIONS
Manual 2100-392 Page 4
MIS-1346
TABLE 4
COUNTERFLOW MODELS
DIMENSION (INCHES)
tenibaCsgninepOmunelP
ledoM
rebmuN
D63D580CF322/1-926502x2291x816
A
htdiW
j
Washable type filter
k
Left or right side return air option. Must be cut in by installer.
B
htpeD
C
thgieH
ExD
2
nruteR
HxF
ylppuS
G
.aiDeulF
FIGURE 3
COUNTERFLOW MODELS DIMENSIONS
1
eziSretliF
02x01 02x51
MIS-1344
Manual 2100-392 Page 5
DUCT WORK
The air distribution system should be designed and installed in conformance with manuals published by Air Conditioning Contractors of America (ACCA) as set forth in Manual D, or ASHRAE publications.
IMPORTANT
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace This is to prevent drawing possible hazardous combustion products into the circulated air.
INSTALLING A COOLING UNIT
When the furnace is used in connection with a cooling unit*, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit, unless the damper is in the full heat or cool position.
* A cooling unit is an air conditioning coil, heat
pump coil or chilled water coil.
When installing a cooling unit above an FH or FL (below on an FC) series furnace, the coil must be spaced far enough from the furnace outlet to assure proper operation of the furnace. Bard supplied coils, when used with Bard supplied coil cabinets, are automatically positioned.
For top discharge FH and FL models, when coils are installed without using Bard coil cabinets or coils of another brand are used, the coil drain pan should be located a minimum of two (2) inches above the top of the furnace cabinet. If a greater clearance is specified by the coil manufacturer then it would apply.
INADEQUATE SUPPLY AIR and/or RETURN AIR DUCT SYSTEMS
Short cycling because of limit control operation can be created by incorrectly designed or installed supply and/ or return air duct systems.
The duct systems must be designed using ASHRAE or ACCA design manuals and the equipment CFM and external static pressure ratings to insure proper air delivery capabilities.
On replacement installations, particularly if equipment is oversized, the duct systems can easily be undersized. Modifications may be required to assure that the equipment is operating within the approved
temperature rise range when under full rated input conditions, and that no short cycling on limit controls is
occurring.
INSTALLING THE FURNACE
A typical installation is shown in Figure 4. All parts of the furnace installation (furnace, oil tank and piping systems, combustion and ventilation air, venting, etc.) must comply with NFPA31, Installation of Oil Burning Equipment -- latest edition. This drawing shows the typical connecting parts needed to correctly install this furnace. Make sure that all parts of the heating system comply with the local codes.
Check the furnace and your load calculation to verify that the unit is properly sized. (Refer to Equipment Selection” section on Page 2.)
The correct size of unit needed may be substantially smaller than the unit being replaced due to home improvements and technology advancements since the initial installation.
WIRING
FACTORY WIRING
All units are fully factory wired. Multispeed blowers are factory wired on high speed for cooling/manual fan operation. Heating speeds are wired for the largest input and may need lower speed for field installed low input nozzle. If replacement wire is necessary, use 105 degrees C minimum. See electrical data, Table 5.
NOTE: If drain pan is anything other than a steel pan
particular attention must be given to the installation instructions for the coil to make sure it is acceptable for use with these oil furnaces having maximum outlet air temperature of 200° F.
See CFM versus static pressure tables on pages 23-26 for additional information.
Manual 2100-392 Page 6
FIELD WIRING
All wiring must conform to the National Electrical Code and all local codes. A separate fuse or breaker should be used for the furnace.
FIGURE 4
TYPICAL INSTALLATION REQUIREMENTS
FRONT FLUE LO-BOY MODEL SHOWN
NOTE: The chimney must be lined with a high temperature noncorrosive material that complies with the local
codes, or in their absence with Standard for Chimneys and Vents, NFPA211. Also see section on Venting in these instructions.
TABLE 5
ELECTRICAL DATA
rotoMrewolBrotoMrenruB
latoT
ledoMHP-ZH-stloV
spmA
D63D580HF1-06-5112.93/15.77/17.15151
D84D011HF1-06-5112.212/15.017/17.16102
D06D011HF1-06-5112.414/35.217/17.19102
D63D580FLF1-06-5113.713/16.57/17.15151
D63D580RLF1-06-5113.713/16.57/17.15151
D84D011FLF1-06-5112.212/15.017/17.16102
D84D011RLF1-06-5112.212/15.017/17.16102
D06D041RLF1-06-5112.414/35.217/17.19102
D63D580CF1-06-5113.73/16.57/17.15151
PHALFPHALF
MIS-1335
emiT.xaM muminiM tiucriC
yticapmA
esuFyaleD
RCAHro
rekaerBtiucriC
Manual 2100-392 Page 7
OIL LINE PIPING
First determine whether the pipe system is to be a single line system or a two line system. All connections must be absolutely air tight or you will have a malfunction of the burner. When installing the piping, a good oil filter should be installed close to the burner. A single line system is recommended for gravity feed.
A typical single inside tank installations shown in Figure 5. For installation details for this and other tank configurations, refer to NFPA31 -- latest edition. All tank and pipe setups must comply with NFPA31.
BECKETT AFG OIL BURNER
This furnace is equipped with a high static Beckett AFG oil burner which is designed to produce adequate draft in nearly any vertically vented application. The burner employs the latest time tested controls of the highest quality. The controls consist of a high voltage Beckett solid state igniter, a Beckett “CleanCut” oil pump with an integral solenoid valve, and a Beckett R7184B primary control.
These controls were selected for their proven high quality, dependability, and serviceability. With proper maintenance this burner assembly will provide many years of reliable service.
All units are shipped with the oil burner installed, and with high rate oil nozzle installed designed for use with No. 1 or No. 2 fuel oil. Inspect firepot refractory
before firing to be sure it has not been jarred out of position in shipment. Burner air tube must not extend beyond inside surface of firepot. Burner head should be centered on the combustion chamber opening. See Figures 16A and 16B.
WARNING
Never attempt to use gasoline in your furnace. Gasoline is more combustible than fuel oil and could result in a serious explosion causing damage, injury or death.
FIGURE 5
TYPICAL SINGLE INSIDE TANK INSTALLATION
Manual 2100-392 Page 8
MIS-1340
The following is a detailed explanation of each control included in the Becket AFG Oil Burner, how each operates, how to set up the burner, and how to troubleshoot problems should they occur.
BECKETT “CLEANCUT” OIL PUMP
This oil pump is equipped with an oil solenoid valve installed in the pump housing. This feature provides quick cutoffs resulting in reduction in smoke after the burner shuts down. This is a time proven pump design and is capable of both one and two pipe systems. This pump requires a pre-purge style primary control such as the R7184B primary. All installation and set up instructions are outlined in the “Oil Pump Specification” section of the installation instructions manual.
As an improved service feature Bard Manufacturing has installed a brass tee fitting next to the oil line output of the pump for installing a pressure gauge to ensure the correct pump pressure. Refer to the “Burner Set Up and Adjustment” section in the manual.
BECKETT SOLID STATE IGNITER
This igniter differs from the traditional iron core transformer in that it produces a 14,000 volt spark instead of a 10,000 volt spark of the iron core
transformer. This hotter spark provides for cleaner, faster ignitions. Being solid state technology this igniter is less susceptible to problems caused by voltage variations. It also has a greater ability to ignite cold and/or inconsistent oil. The solid state igniter is wired to the primary control the same as a standard iron core transformer.
BECKETT R7184B PRIMARY CONTROL
The R7184B Interrupted Electronic Oil Primary is a line voltage, safety rated, interrupted ignition oil primary control for residential oil burners. The R7184B used with a cad cell flame sensor, operates the oil burner and oil valve. The primary controls fuel oil, senses flame, controls ignition spark and is designed to notify a remote alarm circuit before going into lockout when equipped with a flame monitoring system.
This primary control, though it possesses the latest technology, is a very simple control to operate and provides additional troubleshooting features to ease service and reduce down time. Once the features and operation of this control are understood the service person will find it a welcomed addition. In an effort to help in the transition to the R7184B primary control the operational guide is provided following on Page 10.
Manual 2100-392 Page 9
Loading...
+ 24 hidden pages