Bard WA121 User Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
Model:
WA121
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914....Moving ahead just as planned.
Manual : 2100-234 Supersedes: 2100-234H File: Volume III Tab 16 Date: 08-01-07
© Copyright 2002
Manual 2100-234I Page 1 of 17
CONTENTS
Getting Other Informations and Publications 3
Wall Mount General Information
Air Conditioner Wall Mount Model Nomenclature ..... 4
Shipping Damage ..................................................... 6
General ..................................................................... 6
Duct Work ................................................................. 7
Filters ........................................................................ 7
Fresh Air Intake ........................................................ 7
Condensate Drain ..................................................... 7
Installation Instructions
Wall Mounting Information ........................................ 8
Mounting the Unit ..................................................... 8
Wiring – Main Power .............................................. 12
Wiring – Low Voltage Wiring .................................. 12
Figures
Figure 1 Unit Dimensions ...................................... 5
Figure 2 Blower Damper Assembly....................... 7
Figure 3 Mounting Instructions .............................. 9
Figure 4 Wall Mounting Instructions ................... 10
Figure 5 Wall Mounting Instructions ................... 10
Figure 6 Common Wall Mounting
Instructions ............................................ 11
Figure 7 Low Voltage Wiring ............................... 13
Figure 8 Fan Blade Setting Dimensions ............. 16
Start Up
Important Installer Note .......................................... 14
Service Hints .......................................................... 14
High Pressure Switch ............................................. 14
Sequence of Operation ........................................... 14
Compressor Control Module ................................... 14
Adjustments ............................................................ 15
Pressure Service Ports ........................................... 15
Troubleshooting
Fan Blade Setting Dimension ................................. 16
Refrigerant Charge ................................................. 16
Pressure Tables ...................................................... 17
Option Field Installed Accessories .......................... 17
Tables
Table 1 Electric Heat Table .................................. 4
Table 2 Electrical Specifications .......................... 6
Table 3 Thermostat Wire Size ........................... 12
Table 4 Wall Thermostats .................................. 12
Table 5 Fan Blade Dimensions .......................... 16
Table 6 Suction Line Temperatures ................... 16
Table 8 Recommended Operating Ranges ....... 16
Table 7 Indoor Blower Performance .................. 16
Table 9 Maximum ESP of Operation
Electric Heat Only ................................. 16
Table 10 Pressure Table - Cooling ...................... 17
Table 11 Optional Accessories ............................ 17
Manual 2100-234I Page 2 of 17
GETTING OTHER INFORMATION and PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of .......... ANSI/NFPA 90A
Air Conditioning and Ventilating Systems
Standard for Warm Air Heating ........ ANSI/NFPA 90B
and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for ................................. ACCA Manual D
Residential Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-355 Fax: (617) 984-7057
Manufactured under the following U.S. patent numbers:
5,485,878; and 5,301,744
Manual 2100-234I Page 3 of 17
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
MODEL NUMBER
CAPACITY
12 - 1 Ton
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 K - 115/60/1
WA 12 1 – A 00 X X X X X J
COLOR OPTIONS
KW
00 - No KW 02 - 2.2 KW 03 - 3.6 KW 05 - 5.0 KW
VENTILATION OPTIONS
X - Barometric Fresh Air
Damper (Standard) B - Blank-off Plate E - Economizer (Internal) - Fully
Modulating with Exhaust
TABLE 1
ELECTRIC HEAT TABLE
X - Beige 4 - Buckeye Gray
FILTER OPTIONS
X - One Inch Throwaway
(Standard)
P - Two Inch Pleated
CONTROL MODULES
E - Low Ambient Control J - Telecommunication
COIL OPTIONS
X - Standard Coils
OUTLET OPTIONS
X - Front
sledoMA-121AWK-121AWG-121AW
WKA1UTBA1UTBA1UTBA1UTBA1UTB
203.81589,70.01566,81.9003,7
300.51067,210.31507,90.51067,218.31008,01
508.02045,711.81572,31
1 dedulcnisttawrewolbhtiW
Manual 2100-234I Page 4 of 17
V042V802V021V042V022
FIGURE 1
UNIT DIMENSIONS
FACTORY BUILT AT 5 INCHES
Manual 2100-234I Page 5 of 17
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
TIUCRICELGNIS
3
stloVdetaR
dna
sledoM
00A-121AW 30A 50A
00K-121AW 20K
00G-121AW 20G 30G
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75° C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
esahP
1-802/032
1-511
1-05-022
dleiF.oN
rewoP
stiucriC
1 1 1
1 1
1 1 1
muminiM tiucriC
yticapmA
8
02 72
71 52
7
31 02
1
2
mumixaM
esuFlanretxE
tiucriCro
rekaerB
51 02 03
52 03
51 51 02
rewoPdleiF
eziSeriW
41 21 01
01 01
41 41 21
2
dnuorG
eziSeriW
41 21 01
01 01
41 41 21
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return air ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-234I Page 6 of 17
DUCT WORK
All duct work, supply and return must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 9 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. It is recommended that on this type of installation that a filter grille be located in the wall. Filters must be of sufficient size to allow a maximum velocity of 400 FPM.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 2-inch pleated filter is also available as an optional accessory. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending the metal tabs holding the 1-inch filter down. There are two tabs on each side of the filter.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service panel.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.
All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
This unit employs an automatic condensate disposal system consisting of a base drain pan, drain valve and fan blade with slinger ring. A plastic drain hose extends from the evaporator drain pain at the top of the unit to the base drain pan at the bottom. At temperatures above 40°, the drain valve located between the condenser coil and fan shroud is closed allowing water to build up in the base to a height of 5/8" to 3/4". The fan blade with slinger then rotates in this water and throws the water onto the condenser coil. This disposes of the water by evaporating it on the hot condenser.
At temperatures below 40°, the drain valve opens draining the base pan and preventing freeze ups that could damage the coil or fan blade.
FIGURE 2
FRESH AIR DAMPER
Manual 2100-234I Page 7 of 17
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.
NOTE: If the combination SUPPLY / RETURN
Grille Assembly model CRSG-1 is to be used in conjunction with this unit a different size wall opening is required.
2. Locate and mark lag bolt locations, if desired. See Figure 3.
3. Hook top rain flashing under back bend of top. Top rain flashing is shipped attached to the back of the unit on the right side.
4. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lab bolts.
5. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.
6. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
7. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and allow proper airflow to outdoor coil. Additional clearance may be required to meet local or national codes.
Manual 2100-234I Page 8 of 17
FIGURE 3
MOUNTING INSTRUCTIONS
Manual 2100-234I Page 9 of 17
FIGURE 4
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 - MOUNTING INSTRUCTIONS
FIGURE 5
WALL MOUNTING INSTRUCTIONS
SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS
Manual 2100-234I Page 10 of 17
FIGURE 6
COMMON WALL-MOUNTING INSTALLATIONS
Manual 2100-234I Page 11 of 17
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” of “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
WIRING – LOW VOLTAGE WIRING
230/208, 1 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
PATEGNAR
042-352612 802-022781
NOTE: The voltage should be measured at the field power
connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 7.
THERMOSTAT WIRE SIZE
remrofsnarT
AVALFeguaGeriW
043.2
WALL THERMOSTAT
tatsomrehTserutaeFetanimoderP
750-3048
3511D0225HT
850-3048
1511D0225HT
060-3048
)544-0211(
TABLE 3
TABLE 4
ecnatsiDmumixaM
teeFni
eguaG02 eguaG81 eguaG61 eguaG41 eguaG21
taeHegats1,looCegats1
elbammargorP-noNcinortcelE
revoegnahclaunaMrootuA taeHegats2,looCegats2
elbammargorP-noNcinortcelE
revoegnahclaunaMrootuA
taeHegats3;looCegats3
lanoitnevnoCroPH
revoegnahclaunaMrootuA
54 06
001 061 052
cinortcelEelbammargorP-noN/elbammargorP
Manual 2100-234I Page 12 of 17
FIGURE 7
LOW VOLTAGE WIRING
Manual 2100-234I Page 13 of 17
START UP
IMPORTANT INSTALLER NOTE
For improved start up performance, wash the indoor coil with a dishwasher detergent.
SERVICE HINTS
1. Caution owner to maintain clean air filters at all times. Also not to needlessly close off supply and return air registers. This reduces airflow through the system which shortens equipment service life as well as increasing operation costs.
2. The unit is equipped with a high pressure cut out switch.
3. Check all power fuses or circuit breakers to be sue they are the correct rating.
4. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
HIGH PRESSURE SWITCH
The WA121 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a call for heating, circuit R-W1 make at the thermostat pulling in heat contact for the strip heat and blower operation.
the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on make periods have expired.
During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.
Low Pressure Switch, Bypass and Lockout Sequence
If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer that 120 seconds, the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.
Alarm Relay Output
COMPRESSOR CONTROL MODULE
The compressor control module is optional on the models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Adjustable Delay on Make and Break Timer
On initial power up or any time power is interrupted to the unit the delay on make period begins, which will be 2 minutes plus 10% of the delay on break setting. When
Manual 2100-234I Page 14 of 17
Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.
NOTE: Both high and low pressure switch controls are
inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.
ADJUSTMENTS
Adjustable Delay on Make and Delay on Break Timer
The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay of Make (DOM) timing on power up and after power interruptions is equal to 2 minutes plus 10% of Delay of Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power interruptions the compressor will operate on demand with not delay.
Typical Settings for Dual Unit Installation:
Unit No. 1: DOB set at 2 minutes, and DOM is 132
seconds.
Unit No. 2: DOB set at 4 minutes, and DOM is 144
seconds.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure chart can be found later in the manual covering all models. It is imperative to match the correct pressure chart to the unit by model number.
Manual 2100-234I Page 15 of 17
TROUBLESHOOTING
.P.S.E
Hni
2
O
121AW
V032
/yrDteW
0.
1.
2.
3.
4.
/035 /584 /044 /093 /523
005 064 524 573 003
ledoMPSE
00A-121AW 30A 50A
53.
53.
53.
00K-121AW 20K
53.
53.
00G-121AW 20G 30G
53.
53.
53.
FAN BLADE SETTING DIMENSIONS
Show in Figure 8 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 8
FAN BLADE SETTING DIMENSION
TABLE 5
FAN BLADE DIMENSION
TABLE 7
INDOOR BLOWER
PERFORMANCE
CFM @ 230V
TABLE 8
RATED CFM AND ESP
RECOMMENDED AIRFLOW RANGE
detaR
ledoM
121AW00452.003-005
* Rated CRM and ESP on high speed tap.
*MFC
detaR
*PSE
dednemmoceR
egnaRwolfriA
ledoMAnoisnemiD
121AW"2/1
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6" from compressor as shown in Table 6.
TABLE 6
SUCTION LINE TEMPERATURE
detaR
ledoM
121AW00465-4576-56
wolfriA
59oDO
erutarepmeT
The suction line temperatures in Table 6 are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.
Manual 2100-234I Page 16 of 17
o
28
TABLE 9
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
DO
erutarepmeT
Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.
TABLE 10
PRESSURE TABLE
COOLING
ledoM
121AW
Air Temperature Entering Outdoor Coil
riAnruteR
erutarepmeTerusserP57
BD.ged57
BW.ged26
BD.ged08
BW.ged76
BD.ged58
BW.ged27
o
o
o
08
58
ediSwoL
ediSwoL
ediSwoL
27
47
ediShgiH
781
102
67
97
ediShgiH
291
702
18
58
ediShgiH
891
412
o
09
59
67
97
612
232
28
48
222
832
88
19
032
742
TABLE 11
OPTIONAL FIELD INSTALLED ACCESSORIES
o
F
o
o
o
o
001
501
001
18
38
68
842
562
282
78
09
29
552
272
092
49
79
99
462
282
003
o
511
88
19
003
913
59
79
903
823
201
401
913
933
ledoMnoitpircseD
WA121
A1-POBetalPffOknalBX 1-DAFBrepmaDriAhserFcirtemoraBX
1-MFIEtsuahxEhtiwrezimonocEX
6-AMClortnoCtneibmAwoLX
02-AMCCAL+RDT+CPLX
Manual 2100-234I Page 17 of 17
Loading...