11.2Fitting the Coaxial Flue (Ø 60/100 mm Horizontal)
11.3Fitting the Telescopic Flue (Ø 60/100 mm Horizontal)
11.4
11.5
Fitting the Coaxial Flue (Ø 60/100 mm - Vertical)
Fitting the Twin Pipe (Ø 80/80 mm)
12.Electrical Connections
13.Electrical System Diagrams
14.
15.
15.1
15.2Completion
15.3Removal and Fitting of the Case - Servicing
15.4Control Panel
15.5Initial Start-Up
15.6Sequence of Operation
15.7Operational
15.8Combustion Analysis
15.9Boiler Safety Systems
Water Circuit Diagrams
Commissioning
Initial Preparation
Adjustments
18.6Access to the Water Circuit
18.6.1
18.6.2Removing the display PCB
18.6.3Removing the heating return filter
18.6.4Removing the by-pass
18.6.5Removing the pressure relief valve (3 bar)
18.6.6Removing the pressure relief valve (6 bar)
18.6.7
18.6.8
18.6.9Removing the expansion vessel
18.6.10 Removing the overheat thermostat
18.6.11 Removing the heating temperature sensor
18.6.12 Removing the tank temperature sensor
18.6.13 Removing the DHW flow switch
18.6.14
18.6.15
18.6.16 Removing the tank
19.
Drain down
Removing the temperature &
valve (7 bar)
Removing the pump
Removing the DHW
Removing the flow limiter
expansion vessel
Fault Finding Guide
pressure relief
20.Short Spares List
21.Technical Information
2
Page 3
Dear Customer,
Thank you for choosing an ARISTON boiler.
We guarantee that your boiler is a reliable and technically sound product.
The following Instructions provide detailed instructions and recommendations for proper installation, use and maintenance.
Remember to keep this manual in a safe place for future reference e.g. by the gas meter.
Your local MTS Servicing Centre is at your complete disposal for all requirements.
TS (GB) Limited
M
The guarantee on this appliance is valid
for 24 months from the first day of
Repairs to the electric, hydraulic or gas
circuits may be carried out only by your
local authorised MTS Servicing Centre.
installation.
CAUTION
Installation, start-up, adjustments and maintenance must be
performed by a competent person only, in accordance with the
current Gas Safety (Installation & Use) Regulations and the
instructions provided. Improper installation may cause damage or
injury to individuals, animals and personal property, for which the
manufacturer will not be held liable.
To ensure efficient and safe operation it is recommended that the
boiler is serviced annually by a competent person.
If it is known or suspected that a fault exists on the appliance, it must
not be used until the fault has been corrected by a competent person.
Every attempt has been made to avoid
errors of any kind in this instruction
manual, the Management invites
customers to inform of any
inaccuracies which they may find. This
will help to improve our service.
IMPORTANT
Please read this manual carefully.
Please ensure this manual is kept with the appliance so that they can be used by the end-user, installer or our authorised engineer.
3
Page 4
1.GENERAL
P1
P2
O
FF ON
12341
234
00
R
R
P
r
o
g
.
h
m
Day
INFORMATION
MTS (GB) Limited support the initiative. Your installer will give
you, and show you how to use, a Log Book which will give you
important information about your boiler and heating system. Please
ave this Log Book to hand whenever you contact a service engineer or
h
us.
All CORGI Registered Installers carry a CORGI ID card, and have a
registration number. Both should be recorded in your boiler Log
Book. You can check your installer is CORGI registered by calling
CORGI direct on :- (01256) 372300.
This is a combined appliance for the production of central heating (C.H.)
ust be used only
nd domestic hot water (D.H.W.). This appliance
a
or the purpose for which it is designed. The manufacturer declines all
f
m
liability for damage caused by improper or negligent use.
Do not allow children or inexperienced persons to use the appliance
without supervision.
If you smell gas in the room,
do not turn on or off light switches, use
the telephone or any other object which might cause sparks.
Open doors and windows immediately to ventilate the room.
Shut the gas mains tap (on the gas meter) or the valve of the gas
cylinder and call your Gas Supplier immediately.
If you are going away for a long period of time, remember to shut the
mains gas tap or the gas cylinder valve.
2.CONTROL PANEL
25
32
28
26
27
Before any intervention within the boiler it is first necessary to cut
off the electrical power supply by turning the external switch to the
off position.
33
29
30
31
34
Legend:
25 - Selector Knob :
Central Heating and Hot Water
Hot Water Only
OStand-by
Central Heating Only
26 - D.H.W. temperature control knob
27 - C.H. temperature control knob
28 - Heating temperature indicator and diagnostic
indicator
29 - Green indicator - Power ON
30 - Orange indicator - Burner ON
31 - Red indicator - Lock out / flame failure
32 - Reset button
33 - Pressure gauge
Time clock (digital model shown)
34 -
4
Page 5
3.HOW TO USE
P1
P
2
O
FF ON
12341
234
00
RR
P
r
o
g
.
h
m
Day
+
+
+
5
2
33
32
28
26
27
FIG. 3.1FIG. 3.2
GAS COCK CLOSED
GAS COCK OPEN
Switching on
9
2
30
1
3
1. Check that the pressure in the heating system is
adequate, i.e. the pressure gauge
33 shows 1 bar
minimum and 1.5 bar maximum.
2. Check that the gas service tap
Figs. 3.1 and 3.2)and that the mains power is on,
(
he green indicator
34
t
he boiler is now ready to use.
T
9
2
39 (Fig. 3.3) is opened
ill light.
w
Note : If the boiler has been turned off for some time,
the presence of air in the gas pipe may result in a
lockout.
To obtain hot water only
Turn the selector switch 25to the «» position, the
reen LED
g
ndicate that the burner is alight.
i
ill light; the orange LED30will light to
29w
- To adjust the temperature of the domestic hot water,
it is necessary to rotate the control knob
26 «»
clockwise to increase and anti-clockwise to decrease
the temperature until the desired temperature is
achieved.
NOTE
On initial start-up, if the boiler has been switched off
for any period of time or when the storage tank is
emptied of hot water, it will be necessary for the
storage tank to be heated before hot water can be
drawn. It will also be necessary for occasional reheating of the storage tank to maintain the
temperature set on the hot water control knob
26 (this
will happen automaticall as long as the boiler is
powered, operating normally and the selector switch
25 is set to one of the hot water positions or
).
To obtain central heating and domestic hot water
39
green LED
29 will lightt; the orange LED 30 will light to
25 to the «» position, the
Turn the selector switch
indicate that the burner is alight.
- Upon a demand for domestic hot water the operation of
the central heating will be interrupted until the hot water
tank has been reheated to the set temperature.
- The control knob
27 «» allows you to adjust the
water temperature in the central heating circuit
according to seasonal requirements.
- Turn the control knob
27:
- Clockwise in cold weather
- Anti-clockwise in mild weather (by turning the knob
fully anti-clockwise, the Central Heating will switch
off).
FIG. 3.3
- The LEDs
28will display the temperature of the
water in the central heating circuit.
- Furthermore, your home must be fitted with a room
thermostat, ensure it is set to the desired indoor
temperature.
- The orange LED
30 will light each time the burner
operates.
5
Page 6
To obtain central heating only
- Turn the selector switch 25 to the «» position, the green LED
29 will light.
- Ensure that the time clock is on (see S
hermostat is calling for heat.
t
- The control knob
27 «» allows you to adjust the water
ECTION 8), and that the room
temperature in the central heating circuit according to seasonal
requirements.
- Turn the control knob
27:
- Clockwise in cold weather
- Anti-clockwise in mild weather (by turning the knob too far, the
Central Heating will switch off).
The LEDs
-
entral heating circuit.
c
8
2
ill display the temperature of the water in the
w
- Furthermore, your home must be fitted with a room thermostat, set
it to the desired indoor temperature.
The orange LED
-
ill light each time the burner operates.
30w
Stopping the central heating
- Turn the selector switch 25 to the “” position. In this state the
boiler will only produce domestic hot water, alternatively, you can
turn the time clock off or turn the room thermostat down.
Stand-by mode
- Turn the selector switch 25 to the «O » position, the green LED 29
will remain alight. The appliance will remain in stand-by mode
unless the anti-frost device is activated.
Turn off the appliance*
- Turn the selector switch 25 to the «O» position
- Turn off the external power supply to the boiler.
4.ANTI-FROST DEVICE
5.
MAINTENANCE
* NOTE: IN THIS STATE THE APPLIANCES ANTI-FROST DEVICE IS INACTIVE
The boiler is fitted with a device, which in the event that the water
temperature falls below 8
temperature of 18
temperature falls below 3
Hot Water and the burner fires on minimum power until a
temperature of 33
o
C is attained.
o
C the pump activates and runs until a
o
C is attained. In the event that the water
o
C, the diverter valve switches to Domestic
This device is only activated when the boiler is operating perfectly
and
the system pressure is sufficient;
-
- the boiler is powered electrically;
- gas is available.
Schedule an annual maintenance check-up for the boiler with a
CORGI registered Service Engineeer in the UK and with a competent
person as described in I.S.813 for IE.
Correct maintenance always results in savings in the cost of running
the system.
6
Page 7
6.TROUBLE
P1
P
2
OFF ON
12341
234
00
RR
P
r
o
g
.
h
m
Day
SHOOTING
3
3
31
FIG. 6.1
Incorrect functions are signalled by the diagnostic
indicator LED
31 display flashing. Contact your local
authorised Servicing Centre (unless a low water fault is
ndicated, in which case refer to Section 7 for filling
i
instructions).
7.FILLING
INSTRUCTIONS
A method for initially filling the system and replacing lost
water during servicing and initial filling (in accordance with
current Water Regulations), is provided as an integral part
of the connection kit (see Fig. 7.1).
To fill the system and replace lost water it is necessary to
proceed as follows:
- Switch off the power to the boiler;
- Ensure that the flexible hose is connected to both the
cold water inlet connection and the C.H. flow
connection;
- Open the black lever on the valve for the C.H. return
connection and slowly open the black handle on the
valve for the cold water inlet until water is heard
passing through the valves;
- Once the pressure gauge
33 (Fig. 6.1) reads between
1 and 1.5 bar close the levers on both the cold water
connection and the C.H. return connection
- Switch the power to the boiler back on.
NOTE: THE FLEXIBLE HOSE MUST BE REMOVED ONCE THE
SYSTEM HAS BEEN FILLED
.
FIG. 7.1
7
Page 8
8.TIME CLOCK
11
22
33
44
55
66
77
88
99
1010
1111
1212
1313
1414
1515
1616
1717
1818
1919
2020
2121
2222
2323
2424
99
66
1212
I
8.1Setting the Mechanical Clock
. General layout
1
he mechanical clock covers a 24 hour period. Each tappet represents
T
15 minutes A (Fig. 4). An override switch is located on the clock B (Fig
.
8.1)
. To set the time
2
To set the time of day, grasp the outer edge of the dial and turn slowly
lockwise until the correct time is lined up with the arrow
c
3. To Set the "On" and "Off" times
The clock uses a 24hours system. e.g. 8 = 8.00 am and
18 = 6.00 pm "ON" periods are set by sliding all tappets between the
"ON" time and the "OFF" time to the outer edge of the dial.The tappets
remaining at the centre of the dial are the "OFF" periods.
4. For operation
Put the selector switch B to the symbol to control the central heating
by the clock. Put the switch
«
0» to turn the central heating off permanently.
B to «I» to select permanent operation or to
(Fig. 8.1)
C
.
A
C
B
FIG. 8.1
8
Page 9
P
r
o
g
.
h
m
Day
Manual switch
Summer and
winter time
setting
Reset
E
nter
weekday/s
Enter
the hours
Week-
days
flash
Enter
minutes
Enter
switching
times
Imput
time
A
utomaticManualContinuous
OperationOperationOperation
The switchingIf the currentYou can only
times corres-switching mode isreturn to automatic
pond to thechanged manually,mode from the
programthe next switchingcontinuously-ON
entered.time will beand continuously-
carried out auto-OFF switching
matically againmodes by
according to thepressing the " "
entered switchingkey.
program.
= ON= ON= Continuously ON
= OFF= OFF= Continuously OFF
8.2Setting the Digital Clock
Operating the time switch
The steps marked with the symbol “” are necessary to carry out a
switching program.
Preparing for Operation
Activate the “Res” switch (=RESET) to reset the time switch to its
default setting (activate using a pencil or similar pointed instrument).
Do this:
- every time you wish to “reset” the time switch
- to erase all switching times and the current time of day.
After approximately two seconds the following display appears:
Enter current time and weekday
- Keep the “” key pressed down
During the summer time period press the +/- 1h key once.
Enter the hour using the “h” key
Enter the minutes using the “m” key
Enter the day using the “Day” key
1 = “Monday”..............7 = Sunday
- Release the “” key.
Entering the switching times
You have 20 memory Iocations available. Each switching time takes
up one memory location.
Keep pressing the “Prog” key until a free memory location is shown in
the display “– –:– –”.
9
Page 10
Programme ON or OFF with the “” key:
“”= OFF; “”= ON
Enter the hour using “h”
Enter the minutes using “m”
If a switching command is to be carried out every day (1 2 3 4 5 6
7) then store using the “” key, otherwise select the day(s) it is to
e carried out by using the “Day” key.
b
hen the day seIection is left bIank, the programmed switching
W
instruction operates at the same time every day
1 2 3 4 5 6= Monday – Saturday
1 2 3 4 5= Monday – Friday
6 7=Saturday – Sunday
Selection of single days: 1 = Mon. .............. 2 =Tues.
Save the switching time with the “” key.
The time switch enters the automatic operating mode and displays
the current time of day.
Begin any further entry of a switching time with the “Prog” switch. If
your entry is incomplete, the segments not yet selected will blink in
the display. After programming is completed, and you return the
time clock to the current time display with the “” key, the time
clock will not activate any switching instruction required for the
current time. You may need to manually select the desired
switching state with the “” key. Thereafter, as the unit
encounters further switching instructions in the memory in real time,
it will correctly activate all subsequent switching instructions.
Manual Override Switch “”
With the “” you can change the current setting at any time. The
switching program already entered is not altered.
Reading the programmed switching times
Pressing the “Prog” key displays the programmed switching times until
the first free memory location appears in the display “– – : – –”.
If you now press the “Prog” key once again, the number of free memory
Iocations will be displayed, e.g. “
occupied, the display “
Changing the programmed switching times
Press the “Prog” key repeatedly until the switching time you want to
change is displayed. You can now enter the new data. See point
Entering the switching times”.
“
Notes on storing switching times:
If you end your entry of the switching times by pressing the “Prog” key,
then the switching time you have entered will be stored and the next
memory location displayed.
In addition, a complete switching command is stored
after around 90 seconds provided no other key is pressed. The time
switch then enters the automatic operating mode and displays the
current time again.
Deleting individual switching times
Press the “Prog” key repeatedly until the switching time you wish to
delete is shown in the display. Then set to “– –” using the “h” or “m” key
and keep the “
switching time is now erased and the current time is displayed.
00” appears.
” key pressed down for around 3 seconds. The
18”. If all memory locations are
automatically
10
AM / PM time display
If you press the “+/-1h” and “h” keys at the same time, the time display
switches into the AM/PM mode.
Page 11
9. GENERAL INFORMATION
FOR THE INSTALLER
Read the instructions and recommendations in these Installation and
Servicing Instructions carefully to ensure proper installation, use and
maintenance of the appliance.
Keep this manual in a safe place. You may need it for your own
reference while Servicing Technicians or your installer may need to
consult it in the future.
This is a combined appliance for the production of central heating (C.H.)
and domestic hot water (D.H.W.).
his appliance
T
esigned.
d
The manufacturer declines all liability for damage caused by improper
or negligent use.
No asbestos or other hazardous materials have been used in the
fabrication of this product.
Before connecting the appliance, check that the information shown on
the data plate and the Technical Information (Section 21) comply with
the electric, water and gas mains of the property. You will find the data
plate on the reverse of the control panel.
Do not install this appliance in a damp environment or close to
equipment which spray water or other liquids.
Do not place objects on the appliance.
Do not allow children or inexperienced persons to use the appliance
without supervision.
If you smell gas in the room,
the telephone or any other object which might cause sparks.
Open doors and windows immediately to ventilate the room.
Shut the gas mains tap (at or adjacent to the gas meter) or the valve of
the gas cylinder and call your Gas Supplier immediately.
If you are going away for a long period of time, remember to shut the
mains gas tap or the gas cylinder valve.
ust be used onlyfor the purpose for which it is
m
do not turn on or off light switches, use
Always disconnect the appliance either by unplugging it from the
mains or turning off the mains switch before cleaning the appliance or
carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the
gas tap. Do not tamper with the appliance.
For repairs, call your local Authorised Servicing Agent and request the
use of original spare parts. For in-guarantee repairs contact MTS (GB)
Limited.
Check the following at least once a year:
1 - Check the seal of water connections, replacing the gaskets if
necessary.
Check the seal of the gas connections, replacing the gaskets if
2 -
necessary.
3 - Check the general condition of the appliance and of the
combustion chamber visually.
4 - Visual check of the combustion: clean burners if necessary.
5 - With reference to point 3, dismantle and clean the combustion
chamber if necessary.
6 - With reference to point 4, dismantle and clean the injectors if
necessary.
11
Page 12
7 - Visual check of the primary heat exchanger:
P
r
o
g
.
h
m
Day
- check for overheating of the exchangers fins;
- clean the exhaust side of the exchanger and fan if necessary.
Regulate the gas pressure, ignition pressure, partial flame, maximum
8 -
flame.
9 - Check proper operation of the heating safety system:
- maximum safety temperature;
- maximum safety pressure.
10 - Check the proper operation of the gas safety system:
- gas or flame safety device;
- gas valve safety device.
Check that the electrical connections have been made in compliance
11-
it h the instructions shown in the Installation Instructions.
w
12 - Check the efficiency of the hot water supply (flow and temperature).
13 - Check pressure in the Domestic Expansion Vessel and top up as
necessary.
14 - Check manually by turning the test knob the Temperature & Pressure
Relief Valve.
15 - Check manually by turning the test knob the Expansion Relief Valve.
16 - Check discharge pipes from both the central heating and domestic hot
water for obstructions.
17 - Check general operation of the appliance.
18 - Check the exhaust system for the combustion products.
19 - Check all unvented domestic hot water controls and systems
12
9.1OVERALL VIEW
1. - Steel chassis
2. - Expansion vessel (primary)
3. - Fan
4. - Main heat exchanger made of copper
5. - Sealed chamber
6. - Stainless steel multi-gas burner
assembly comprising :
• removable burner manifold
• two ignition electrodes
• one flame detection electrode
7. - Gas section comprising :
• two safety valves
• one modulating valve
8. - Automatic air vent
9. - Stainless steel domestic hot water tank
10. - Pump
11. - Electrical box
12. - Igniter
13. - Overheating safety device
14. - Air pressure switch
15. - Tank thermistor
16. - Heating flow thermistor
17. - Heating return thermistor
18. -Three way valve
19. - Indirect coil
20. - DHW activator
21. - Hot water control thermistor
22. - DHW expansion vessel
23. - Programmer
24. - Safety valve T&P
K. - Flue kit fixing point (refer to Section 11)
NOTE: These checks are not exhaustive
24
9
14
21
19
16
17
22
15
7
11
23
20
K
1
3
13
4
5
6
12
18
2
8
10
Page 13
10.INSTALLATION
The technical information and instructions provided herein below are
intended for the installer / Servicing Technician so that the unit may be
installed and serviced correctly and safely.
10.1Delivery
10.2Reference Standards
There will be two items:
1 - The fully assembled boiler
2 - A separately boxed connection kit
WATER REGULATIONS
In GB it is necessary to comply with the Water Supply (Water Fittings)
Regulations 1999, for Scotland, The Water Bylaws 2000, Scotland. The
enus 30 Plus is an approved product under the Water Regulations.
G
To comply with the Water Regulations, your attention is drawn to The
Water Regulations guide published by the Water Regulations Advisory
Scheme (WRAS) gives full details of the requirements.
In IE, the requirements given in the current edition of I.S.813 and the
current Building Regulations must be followed.
BUILDING REGULATIONS
These are a statutory document and take priority over all other regulations
and recommendations. The installation of an unvented hot water storage
cylinder is classified as a "Controlled Service" and Regulation G3 applies.
To meet the requirements of the Regulation, installation of an unvented
system should be undertaken by a "competent installer".
All installations of unvented hot water storage systems having a capacity of
more than 15 litres should be notified to the relevant Local Authority by
means of Building Notice or by the submission of full plans. It is important
to note that it is a criminal offence to install an unvented hot water storage
system without notifying the Local Authority.
The installation of this appliance must be in accordance with the
relevant requirements of the Local Building Regulations, the current
I.E.E. Wiring Regulations, the bylaws of the local water authority, in
Scotland, in accordance with the Building Standards (Scotland)
Regulation and Health and Safety document No. 635 “Electricity at work
regulations 1989” and in the Republic of Ireland with the current edition
of I.S. 813, the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-hazardous
and no special precautions are required when servicing.
Installation should also comply with the following British Standard
Codes of Practice:
BS 7593Treatment of water in domestic hot water
central heating systems
BS 5546Installation of hot water supplies for
domestic purposes
BS 5440-1Flues
BS 5440-2Air supply
BS 5449Forced circulation hot water systems
BS 6798
BS 6891Installation of low pressure gas pipe up to
BS 7671
BS 7074Specification for expansion vessels
BS 5482Installation of L.P.G.
Installation of gas fired hot water boilers
of rated input not exceeding 60kW
28mm
IEE wiring regulations
13
Page 14
10.3Siting the Appliance
and in the Republic of Ireland in accordance with the following
Codes of Practice:
I.S. 813Domestic Gas Installations
The following BS Standards give valuable information;
S 5546Installation of hot water supplies for
B
omestic purposes
d
S 5449Forced circulation hot water systems
B
BS 7074Specification for expansion vessels
BS 7593Treatment of water in domestic hot water
central heating systems
WARNING!!
The addition of anything that may interfere with the normal
operation of the appliance without express written permission of
the manufacturer or his agent could invalidate the warranty. In GB
this could also infringe the
REGULATIONS
In the Republic of Ireland the installation and initial start up of the
appliance must be carried out by a Competent Person in
accordance with the current edition of I.S.813 “Domestic Gas
Installations” and the current Building Regulations, reference
should also be made to the current ETCI rules for electrical
installation.
The appliance may be installed in any room or indoor area,
although particular attention is drawn to the requirements of the
current I.E.E. Wiring Regulations, in Scotland, the electrical
provisions of the Building Regulations applicable in Scotland, and
in the Republic of Ireland, the current edition of I.S.813, with
respect to the installation of the combined appliance in a room
containing a bath or shower. The location of the boiler in a room
containing a bath or shower should only be considered if there is
no alternative.
.
GAS SAFETY (Installation and Use)
14
Where a room-sealed appliance is installed in a room
containing a bath or shower reference should be made to the
relevant requirements.
In GB this is the current I..E.E. WIRING REGULATIONS and
BUILDING REGULATIONS. In IE reference should be made to
the current edition of I.S.813 and the current ETCI rules.
If the boiler is to be sited into a timber framed building, reference
must be made to the current edition of the Institution of Gas
Engineers Publication IGE/UP/7 (Gas Installations in Timber
Framed Housing).
The location must permit adequate space for servicing and air
circulation around the appliance as indicated in Section 10.4.
The location must permit the provision of an adequate flue and
termination.
For unusual locations special procedures may be necessary.
BS 6798-1987 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed
specifically for this purpose. No specific ventilation requirements
are needed for the installation within a cupboard.
This appliance is not suitable for outdoor installation.
Page 15
925
500
950
470
195
57
54145
39
40
41
42
43
38
188
135
80
54
17254
317
280
44
595
450mm minimum for
servicing purposes
180
The type C appliances (in which the combustion circuit,
air vent intake and combustion chamber are air-tight
with respect to the room in which the appliance is
nstalled) can be installed in any type of room.
i
Secondary ventilation is not required with this boiler. The
boiler must be installed on a solid, non-combustible,
permanent wall to prevent access from the rear.
10.4Clearances
10.5Overall Dimensions
Legend:
= Gas service tap
39
40 = Heating return
41 = Heating flow
42 = Water service tap
43 = Tank hot water flow
38 = Water tank
discharge valve
44 = Central heating
discharge valve
In order to allow for access to the interior of the boiler for
aintenance purposes, the boiler must be fitted with a
m
learance of 450mm in front 400mm below the boiler and
c
200mm above the boiler, and installed in compliance with the
clearance requirements indicated in
Fig. 10.1.
FIG. 10.1
15
Page 16
10.6Mounting the Appliance
40
41
38
After removing the boiler from its packaging, remove the
template from the separate box containing the connection
OTE: Pay particular attention to any test water that may
kit. N
pill from the appliance.
s
4
4
Place the template in the position the appliance is to be
mounted and after ensuring it is hanging squarely, use it to
3
flue pipe(s)
installation please refer to S
NB: For further information relating to the flue
ECTION 11 FLUE CONNECTION.(If
drill the holes for the hanging bracket, connection kit and
9
the appliance is to be fitted on a wall of combustible
ustbe protected by a sheet of fireproof
aterial, the wall
m
aterial).
m
m
If the appliance is to be fitted into a timber framed building,
guidance should be sought from the Institute of Gas
Engineers document R
E
: IGE/UP/7.
F
42
43
Legend:
39
= Gas service tap
40 = Heating return
41 = Heating flow
42 = Water service tap
43 = Tank hot water flow
38 = Water tank valve
44 = Heating valve
10.7Electrical Connection
FIG. 10.2
10.6.1.
Drill the wall and plug using those supplied with the
connections kit, position the hanging bracket and secure
with the wall bolts supplied, assemble the connection kit and
secure to the wall.
NOTE: It is highly recommended that a
spirit level be used to position the appliance to ensure that it
is perfectly level.
10.6.2. Position the appliance on the hanging bracket and
connect the connection kit to the boiler connections. (see
also Sections 10.8 Gas Connections, 10.9 Water
Connections & F
IG.10.2).
For safety purposes, have a competent person carefully
check the electrical system in the property, as the
manufacturer will not be held liable for damage caused by
the failure to earth the appliance properly or by anomalies in
the supply of power. Make sure that the residential electrical
system is adequate for the maximum power absorbed by the
unit, which is indicated on the rating plate. In addition, check
that the section of cabling is appropriate for the power
absorbed by the boiler.
The boiler operates with alternating current, as indicated in
the Technical Information table (Section 21), where the
maximum absorbed power is also indicated. Make sure that
the connections for the neutral and live wires correspond to
the indications in the diagram. The appliance electrical
connections are situated on the reverse of the control panel
(see the Servicing Instructions Section 18 for further
information).
16
FIG. 10.3
Important!
In the event that the power supply cord must be changed,
replace it with one with the same specifications. Make the
connections to the terminal board located within the control
panel, as follows:
- The yellow-green wire should be connected to the terminal
marked with the earth symbol; make sure to re-use the
ferrule mounted on the other supply cord;
- The blue wire should be connected to the terminal marked
“N”;
- The brown wire should be connected to the terminal
marked “L”.
Note: The diagrams for the electrical system are indicated in
Section 13.
Page 17
Warning, this appliance must be earthed.
External wiring must be correctly earthed, polarised and in
accordance with relevant regulations / rules. In GB this is the
current I.E.E. WIRING REGULATIONS. In IE reference should be
made to the current edition of the ETCI rules. This boiler is supplied
for connection to a 220 - 240 V~50 Hz supply.
The supply must be fused at 3 A.
The method of connection to the electricity supply must facilitate
complete electrical isolation of the appliance, by the use of a fused
ouble pole isolator having a contact separation of at least 3 mm in
d
ll poles or alternatively, by
a
and unswitched shuttered socket outlet both complying with BS
1363.
The point of connection to the Electricity supply must be readily
accessible and adjacent to the appliance unless the appliance is
installed in a bathroom when this must be sited outside the
bathroom.
eans of a 3 A fused three pin plug
m
10.8Gas Connection
10.9Water Connections
The local gas region contractor connects the gas meter to the
service pipe.
The gas installation should be in accordance with the relevant
standards. In GB this is BS6891 and in IE this is the current edition
of I.S.813.
The connection the the appliance is a 22mm copper tail located at
the rear of the gas service cock (Fig. 10.2).
If the gas supply for the boiler serves other appliances ensure that
an adequate supply is available both to the boiler and the other
appliances when they are in use at the same time.
Pipe work must be of an adequate size. Pipes of a smaller size than
the boiler inlet connection should not be used.
Central Heating
Detailed recommendations are given in BS 6798:1987 and BS
5449-1:1990, the following notes are given for general
guidance.
Pipe Work:
Copper tubing to BS EN 1057:1996 is recommended for water
pipes. Jointing should be either with capillary soldered or
compression fittings.
Where possible pipes should have a gradient to ensure air is
carried naturally to air release points and water flows naturally
to drain taps.
The appliance has a built-in automatic air release valve,
however it should be ensured as far as possible that the
appliance heat exchanger is not a natural collecting point for air.
Except where providing useful heat, pipes should be insulated
to prevent heat loss and avoid freezing.
Particular attention should be paid to pipes passing through
ventilated spaces in roofs and under floors.
By-pass:
The appliance includes an automatic by-pass valve, which
protects the main heat exchanger in case of reduced or
interrupted water circulation through the heating system, due to
the closing of thermostatic valves or cock-type valves within the
system.
17
Page 18
System Design:
This boiler is suitable only for sealed systems.
Drain Cocks:
These must be located in accessible positions to permit the
raining of the whole system. The taps must be at least 15mm
d
nominal size an manufactured in accordance with BS 2870:1980.
Safety Valve Discharge (Primary Water):
he discharge should terminate facing downwards on the exterior
T
of the building in a position where discharging (possibly boiling
water & steam) will not create danger or nuisance, but in an easily
visible position, and not cause damage to electrical components
and wiring.
The discharge must not be over an entrance or a window or any
other type of public access.
Mains Water Feed - Central Heating:
There must be no direct connection to the mains water supply
ven through a non-return valve, without the approval of the Local
e
Water Authority, and must be in accordance with water supply
regulations. Your attention is drawn to, for GB: Guidance G24.2
and recommendation R24.2 of the water regulations guide and for
IE: the current edition of I.S.813.
Filling:
A temporary method for initially filling the system and replacing
lost water during servicing and initial filling (complying to current
water regulations and byelaws) is provided. The flexible hose
must be removed once the system has been filled.
18
Domestic Hot Water
Storage Discharge Pipe Work
1) The tundish must be installed directly below the discharge outlet
connection of the boiler. The tundish must also be in a position visible
to the occupants, and positioned away from any electrical devices.
The discharge pipe from the tundish should terminate outside in a
safe place where there is no risk to persons in the vicinity of the
discharge and to be of metal.
2) Discharge pipes from the temperature & pressure relief and
expansion relief valve are joined together within the appliance.
3) The pipe diameter must be at least one pipe size larger than the
nominal outlet size of the safety device unless it's total equivalent
hydraulic resistance exceeds that of a straight pipe 9m long.
i.e. Discharge pipes between 9m and 18m equivalent resistance
length should be at least 2 sizes larger than the nominal outlet size of
the safety device. Between 18m and 27m at least 3 sizes larger, and
so on.
Bends must be taken into account in calculating the flow resistance.
See fig. 10.4 (page 18) and Table 1 (page 19).
4) The discharge pipe must have a vertical section of pipe at least 300m
in length, below the tundish before any elbows or bends in the
pipework.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the final point of
discharge, but where this is not possible or practically difficult; there
should be clear visibility at one or other of these locations. Examples
of acceptance are:
i) Ideally below a fixed grating and above the water seal in a trapped
gully.
ii) Downward discharges at a low level; i.e. up to 100mm above
external surfaces such as car parks, hard standings, grassed areas etc.
These are acceptable providing that where children may play or
otherwise come into contact with discharges, a wire cage or similar
guard is positioned to prevent contact, whilst maintaining visibility.
Page 19
iii) Discharges at high level; I.e. into a metal hopper and metal down
500 mm Max.
3
00 mm
Min.
Temperature & pressure
r
elief valve
Metal discharge pipe (D1) from
t
emperature & pressure relief valve.
to tundish.
Metal discharge pipe (D2) from tundish
w
ith continuous fall. See Table 2 and worked
example.
Tundish
F
ixed grating
Trapped gulley
Discharge below
f
ixed grating.
(see page 6 for
a
lternative points
of discharge).
pipe with the end of the discharge pipe clearly visible (tundish visible or
not).
r onto a roof capable of withstanding high temperature discharges of
O
water 3m from any plastic guttering systems that would take such a
discharge (tundish visible).
iv) Where a single pipe serves a number of discharges, such as in
blocks of flats, the number served should be limited to not more than 6
systems so that any installation can be traced reasonably easily.
Fig.10.4
The single common discharge pipe should be at least one pipe size large
than the largest individual discharge pipe to be connected.
If unvented hot water storage systems are installed where discharges
from safety devices may not be apparent I.e. in dwellings occupied by
the blind, infirm or disabled people, consideration should be given to
the installation of an electronically operated device to warn when
discharge takes place.
Note: The discharge will consist of scalding water and steam. Asphalt,
roofing felt and non-metallic rainwater goods may be damaged by such
discharges.
Warning
The outlet from the temperature & pressure relief valve must not be
used for any other purpose.
The temperature & pressure relief valve must not be removed in any
circumstances. Any of the above will totally invalidate the warranty.
Note
The discharge from the central heating and domestic hot water systems
may be joined together after the tundish.
Air Release Points:
These must be fitted at all high points where air naturally collects
and must be sited to facilitate complete filling of the system.
The appliance has an integral sealed expansion vessel to
accommodate the increase of water value when the system is
heated.
19
Page 20
It can accept up to 7l (1.5 gal) of expansion water. If the heating circuit
Valve outlet sizeMinimum size of
discharge pipe D1*
Minimum size of
discharge pipe D2*
from tundish
Maximum
resistance allowed,
expressed as a
length of pipe (i.e.
no elbow or bends)
Resistance created
by each elbow or
bend
G 1/215 mm22 mm
28 mm
35 mm
Up to 9 m
Up to 18 m
Up to 27 m
0.8 m
1.0 m
1.4 m
G 3/422 mm28 mm
35 mm
42 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.0 m
1.4 m
1.7 m
G 128 mm35 mm
42 mm
54 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.4 m
1.7 m
2.3 m
has an unusually high water content, calculate the total expansion and
add an additional sealed expansion vessel with adequate capacity.
omestic Water:
D
The domestic water must be in accordance with the relevant
recommendation of BS 5546:1990. Copper tubing to BS EN
1057:1996 is recommended for water carrying pipe work and must be
used for pipe work carrying drinking water. The domestic hot water
temperature should be be adjusted to trip at 60˚C. This temperature
will prevent the formation of limescale in hard water areas.
ote: This appliance is capable of producing domestic hot water of
N
p to 70˚C. For extra security against scalding a thermostatic
u
blending valve may be installed on the domestic hot water
outlet.
Secondary Return:
he secondary return connection can be used as an option. A Non
T
Return Valve (not supplied) must be fitted to prevent back flow and a
Bronze Pump will be needed in conjunction with a Pipe Thermostat to
circulate the hot water (neither of which are supplied).
Table 1. Sizing of copper discharge pipe “D2” for
common temperature valve outlet sizes.
20
Worked Example:
The example below is for a G 1/2 Temperature & Pressure Relief valve
with a discharge pipe (D2) having 4 no. elbows and length of 7m from the
Tundish to the point of discharge.From Table 1
Maximum resistance allowed for a straight length of 22mm copper
discharge pipe (D2) from G 1/2 T & P valve is 9m.
Subtract the resistance for 4 no. 22mm elbows at 0.8m each = 3.2m.
Therefore the maximum permitted length equates to: 5.8m.
As 5.8m is less than the actual length of 7m therefore calculate the next
largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from
G 1/2 T & P valve equates to: 18m.
Subtract the resistance for 4 no. 28mm elbow at 1.0m each = 4m.
Therefore the maximum permitted length equates to: 14m
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
Page 21
GV
PV
0
4
3
2
1
5
6
100
200
800
700
600
500
400
300
900
1000
1100
1200
l/h
m
CE
Minimum flow (thermostatic valves closed)
O
perating Pressure
A
BC D E F
Other
Users
Pressure
Reducing Valve
Cold Water Inlet
13
Drain Tap
(at lowest point)
12
11
10
9
8
8
4
5
6
7
V
31
2
16
m
/H
Residual Head of the Boiler ∆T = 20oC
O
2
Fig. 10.5
A -Gas Inlet
B -C.H. Return
C -C.H. Flow
D -D.H.W. Secondary Return
E -D.H.W. Flow
F -C.W. Inlet
1 -Gas Meter Inlet Cock
2 -Gas Meter
3 -Gas Meter Outlet Cock
4 -Internal Gas Cock
5 -Appliance Gas Inlet Cock
NOTE:BOILER CONNECTIONS SHOWN FROM THE REAR OF THE APPLIANCE
21
Page 22
136
11. Connecting the Flue
Fig. 11.1
T
ERMINALPOSITION
A - Directly above or below an openable window
or other opening300
B - Below gutters, solid pipes or drain pipes75
C - Below eaves200
D - Below balconies or car-port roof200
E - From vertical drain pipes and soil pipes150
F - From internal or external corners300
G - Above ground or balcony level300
H - From a surface facing a terminal600
I - From a terminal facing a terminal1200
J -From an opening in the car port
(e.g. door, window) into dwelling1200
K - Vertically from a terminal in the same wall1500
L - Horizontally from a terminal in the same wall300
M - Horizontally from an opening window300
N - Fixed by vertical flue terminal
mm
11.1 Flue Connections
Flue System
The provision for satisfactory flue termination must be made as
described in BS 5440-1, for IE recommendations I.S.813.
he appliance must be installed so that the flue terminal is exposed to
T
utdoor air, consideration must be given to terminal discharges onto a
o
pathway or passageway, check that the combustion discharges will not
cause a nuisance and that the terminal will not obstruct the
passageway.
The terminal must not discharge into another room or space such as
an outhouse or lean-to.
It is important that the position of the terminal allows a free passage
of air across it at all times.
f the terminal is fitted within 1 metre of a plastic gutter, within 500mm
I
f a painted eave or a painted gutter, an aluminium shield of at least
o
1 metre long should be fitted to the underside of the gutter or painted
surface. An air space of 5mm should be left between shield and
gutter.
The terminal should be located with due regard for the damage or
discolouration that might occur on buildings in the vicinity.
In cold or humid weather water vapour may condense on leaving the
flue terminal. The effect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground
or above a flat roof to which people have access, then a suitable
terminal guard must be fitted. When ordering a terminal guard, quote
the appliance model number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
NOTE:THE FLUE MUST TERMINAL MUST
BE ATLEAST
OPENING IN A BUILDING OPPOSITE AND
SHOULD
BOUNDARIES
FLUE MUST NOT TERMINATE IN A PLACE
LIKELY TO CAUSE NUISANCE
2 METRES FROM ANY
DISCHARGE ACROSS
NOT
ADDTION
. IN
TO
THIS
, THE
.
In addition, it is also possible to use a split system
by fitting a special adapter to the flue discharge
collar and using one of the apertures for the air
vent intake located on the top part of the
combustion chamber (Fig. 11.3)
See Section 11.6.
Fig. 11.2
Fig.11.3
22
Page 23
Flue
Clamp
145 mm
Maximum Lenght = 3 m
Minimum Lenght = 370 mm
100 mm
107 mm
9
5 mm
X
WA
L max = 3 m
RNING
!!
The exhaust gas ducts must not be in contact with or
lose to inflammable material and should not pass
c
through building structures or walls made of inflammable
material.
When replacing an old appliance, the flue must be
changed.
IMPORTANT!!
Ensure that the flue is not blocked.
nsure that the flue is assembled correctly, is secure and
E
s free of leaks.
i
Ø 60/100 mm
The minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Fig. 11.1
he boiler is designed to be connected to a coaxial flue
T
discharge system.
The boiler must only be installed with a flue supplied by the
boiler manufacturer.
These kits are supplied separately to the appliance in order to
respond to different installation solutions. For more information
with regard to the inlet/outlet accessories consult the flue guide
nd the following instructions. The boiler is predisposed for the
a
onnection to a concentric air intake and exhaust duct system.
c
FIG. 11.4
11.2 Fitting the coaxial flue (Ø 60/100
Horizontal)
FIG. 11.5
WARNING!!
Consult the table on Page 28, to see if a restrictor is
required for the type of flue system being used. Should it
be necessary to fit the restrictor, it must be placed in the air
inlet connection on the boilers exhaust terminal.
CONTENTS:
X SILICONE O-RING (60mm)
1
X ELBOW (90
1
X WALL SEALS (INTERNAL &EXTERNAL)
2
X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (1 METRE - 60/100)
1
X FLUE CLAMPS
2
O
)
4X SCREWS
2X RECTANGULAR FOAM PADS
Once the boiler has been positioned on the wall, insert the
elbow into the socket and rotate to the required position.
O
It is possible to rotate the elbow 360
on its vertical axis.
Using the flue clamps, pads and screws supplied
secure the elbow to the boiler.
)
11.5
The 1 metre horizontal flue kit (705958) supplied is suitable for
an exact
flue kit (705785) is suitable for an exact
X dimension of 823mm, and the 750mm horizontal
X dimension of
573mm.
Measure the distance from the face of the external wall to the
face of the flue elbow
(X - Fig 11.4), add 22 mm to this
measurement, you now have the total length of flue required
(including the terminal), this figure must now be subtracted
from 860mm, you now have the total amount to be cut from the
plain end of the flue.
Cut the flue to the required length ensuring that the distance
between the inner and the outer flue is maintained (Fig 11.6).
NOTE:
(Figs 11.4 &
23
Page 24
e.g.
25 mm
25 mm
25 mm
X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain end of
he flue).
t
Once cut to the required length, ensure that the flue is free from
burrs and reassemble the flue. If fitting the flue from inside of
the building attach the grey outer wall seal to the flue terminal
and push through the flue through the hole, once the wall seal
has passed through the hole, pull the flue back until the seal is
flush with the wall. Alternatively, the flue can be installed from
utside of the building, the grey outer seal being fitted last.
o
11.3 Fitting the telescopic flue (Ø 60/100
Horizontal)
Fig 11.6
CONTENTS:
1
X SILICONE O-RING (60mm)
X ELBOW (90
1
2
X WALL SEALS (INTERNAL & EXTERNAL)
X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC -
1
60/100)
X FLUE CLAMPS
2
8X SCREWS
2X SEALS
The telscopic flue is suitable for use with an exact minimum X
dimension
470mm.
IMPORTANT!!
Do not extend the telescopic flue to an X dimension of
more than 470mm.
extension pieces as necessary. Under no circumstances
must the telescopic flue be cut.
The wall must then be made good around the flue (ensuring a
fall of 1
Once made good, place the inner (white) wall seal over the flue
and push up to the wall, secure the flue to the elbow by using
the clamp supplied.
O
)
of 270mm and an exact maximum X dimension
If longer lengths are required use
o
is maintained away from the boiler to the flue terminal).
24
o
For each additional 90
elbow 1 metre must be removed from
the total flue length (maximum 3 metres including the 1st
o
elbow). For each additional 45
elbow 0.5 metre must be
subtracted from the total flue length (Fig 11.8).
Page 25
11.4 Fitting the coaxial flue (Ø 60/100
P
g
m
D
Vertical)
FIG 11.7
CO
1
X SI
1
X CO
1
X VE
3
X SC
:
NTENTS
O-RING(60mm)
LICONE
NICALADAPTOR
RTICALFLUEKIT
REWS
60/100mm : 80/125mm)
(
(80/125mm)
The vertical flue kit is supplied with a specially designed
weather proof terminal fitted, it can be used either with a flat
oof or a pitched roof. (see Figs. 11.7 and 11.9).
r
The Vertical flue kits maximum and minimum useable lengths
with both flat and pitched roof flashings are indicated in Figs.
1.9 and 11.10 also
1
.
Before proceeding to fit the flue, ensure that the maximum flue
ength has not been exceeded and that all elbows and bends
l
have been taken into consideration, the maximum flue length is
3 metres, for each additional 90
ubtracted from the total flue length, and for each 45
s
metres must be subtracted from the total flue length
o
and height of 2 x 45
bends can be seen in Fig. 11.12).
o
elbow 1 metre must be
(the offset
o
.5
0
Mark the position of the flue hole in the ceiling and/or roof (see
Fig. 11.9 for distance from wall to the centre of the flue).
Cut a 130mm diameter hole through the ceiling and/or roof and
fit the flashing plate to the roof.
Should it be necessary to cut the flue
DO
cut the outer
NOT
white ar inlet tube, cut the aluminium exhaust flue 6mm longer
than the outer white air tube when used at minimum length.
NOT
DO
cut more that 250mm from the inner aluminium
exhaust flue.
NOTE:
M
AX LENGTH =
a+a+a +
b+b = a+a+a+0.5+0.5
COMBINED LENGTH
EXCEED
TO
3
NOT
m
FIG 11.8
To connect the vertical flue kit directly to the boiler, place the
adaptor (see Fig. 11.7) (supplied with vertical flue kit) onto the
exhaust manifold and secure with the clamp, the vertical flue kit
must then be inserted through the roof flashing from the
outside, this will ensure that the correct clearance above the
roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1 metre
(Part No. 705786), 500mm (Part No. 705790) and 160mm
lengths
(Part No. 705812), they must be connected directly to
the boiler and secured with the clamp supplied before
connecting the adaptor to allow the vertical flue kit to be fitted.
In the event that extension pieces need to be shortened, they
must only be cut at the male end and it must be ensured that
the distance between the inner and outer flue are kept (Fig.
11.6).
When utilising the vertical flue system, action must be taken to
ensure that the flue is supported adequately to prevent the
weight being transferred to the appliance flue connection.
When the flue passes through a ceiling or wooden floor, there
must be an air gap of 25mm between any part of the flue
system and any combustible material. The use of a ceiling
plate will facilitate this. Also when the flue passes from one
room to another a fire stop must be fitted to prevent the
passage of smoke or fire, irrespective of the structural material
through which the flue passes.
FIG. 11.9
25
Page 26
11.5 Fitting the twin pipe (Ø80/80)
Where it is not possible to terminate the flue within the distance
permitted for coaxial flues, the twin flue pipe can be used by
fitting a special adaptor to the flue connector and using the
perture for the air intake located on top of the combustion
a
chamber.
Considerations necessary for twin flue installation;
It is most important to avoid any possible condense formation
entering the appliance.
ondense may form when the exhaust pipe is longer than
C
.6m. If this is the case, there are two options;
6
1)Where condense will form but can be negated with insulated
flue, install the insulated flue ensuring it has a fall of 5mm in
every metre away from the boiler.
FIG. 11.10
Minimum offset distance when using 2x 45obends
2)The exhaust flue will have a fall of 3
o
back to the boiler and a
suitable trap will be fitted on the exhaust as close to the boiler
as possible, condense will then be suitably disposed of.
Where the flue runs through cold spots, i.e. loft areas,
condense is likely to be formed, therefore in such cases a fall
back to the boiler and a trap is required.
Always ensure that the flue is adequately supported, avoiding
low points. (MTS supply suitable clamps as Part No. 705778).
To utilise the air intake it is necessary to:
1) Take the air intake cover off
2) Assemble the flange on the header supplied with the boiler
3) Insert the restrictor if necessary, on the tube or the elbow
4) Insert the header on the tube or the elbow up until the lower
stop (you do not have to use the washer).
5) Insert the elbow/header in the boiler air intake hole and
fasten it with screws
The twin flue pipes can be fitted with or without additional
elbows and need no clamps, simply ensure that the red o-ring
is inserted in the female end of the flue pipe and push the
extension piece fully into the previous section of flue pipe or
elbow, check that the o-ring is not dislodged when assembling
the flue.
FIG. 11.11
26
Twin pipe can also be converted back to Coaxial flue to enable
vertical termination with a coaxial kit by using the pipe bridge
(Twin - Coaxial Adaptor - Part No. 705767). When running the
twin flue pipe vertically, a condense trap must always be used
on the exhaust pipe.
It is not recommended that the pipe bridge be used for
horizontal termination, however in the unlikely event that this
proves to be a necessity it is extremely important that the entire
o
flue has a fall of 3
back to the boiler, is suitably trapped and
where the 60mm inner flue of the concentric terminal connects
to the pipe bridge, this point must be adequately sealed with
silicone sealant to avoid condense leakage at this point.
Page 27
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
FIG.11.12
his procedure must be done as follows:
T
1 - Remove the air vent intake in the area indicated in
Fig. 11.13, by breaking the perforated ring.
Use a tool to grasp the lid and remove it completely.
2 3 - Clean any burrs or sharp edges with a knife or an
appropriate tool.
NOTE: Vertical twin flue installations must have a trap on the
exhaust. MTS supply a suitable condense trap Part No.
705774 and recommend that this be used in the event that the
lue may form condense.
f
When siting the twin flue pipe, the air intake and exhaust
terminals must terminate on the same wall, the centres of the
terminals
intake
must be a minimum of 280 mm apart and the air
must not be sited above the exhaust terminal (refer to
Fig. 11.14). The air intake pipe can be run horizontally,
however, the terminal and the final 1 metre of flue must be
installed with a fall away from the boiler to avoid rain ingress.
t is also strongly recommended that the air intake pipe run be
I
constructed of insulated pipe to prevent condense forming on
the outside of the tube.
The maximum permissible flue length for twin flue is dependent
on the type of run used.
For flue runs with the intake and exhaust pipes under the same
atmospheric conditions (T
YPE 4) the maximum length is 34
metres (30kW), for runs with the terminals under different
atmospheric conditions (T
YPE 5) the exhaust terminal must
extend 0.5 metres above the ridge of the roof (this is not
obligatory if the exhaust and air intake pipes are located on the
same side of the building). For T
YPE 5 also, the maximum
permissible combined length is 56 metres (30kW).
FIG. 11.13
The maximum length is reached by combining the total lengths
of both the air intake and exhaust pipes. Therefore a maximum
length of 56 metres for example, will allow a flue run of 28
metres for the air intake and 28 metres for the exhaust pipes,
also for each 90
total length and for each 45
o
elbow 1.3 metres must be subtracted from the
o
elbow 1 metre must be subtracted
from the total flue length.
Some of the acceptable flue configurations are detailed page
28.
For further information relating to flue runs not illustrated,
please contact the Technical Department on 0870 241 8180.
NOTE:
EVENT THAT
I
THE
N
PERMISSIABLE TO EXTEND THE EXHAUST PIPE
280MM CENTRES
CANNOT
BE ACHEIVED
, IT
IS
300MM FROM THE WALL
FIG. 11.14
27
Page 28
oncentric outletRestrictor
C
60/100ø 88.5Without restrictorMax. length
30 kWL min. = 0.3 mL min. = 1 m3 m
(Type 1, Type 2, Type 3)L max. = 1 mL max. = 3 m/
total length of gas intake and exhaust ducts.
L =
Twin flue outletRestrictorWithoutRisk of condense
30 kWø 42restrictorforming
Type 4L min. > 0 mL min. > 4.5 mL > 6.6 m
80/80L max. = 4.5 mL max. = 34 mL > 6.6 m
Type 5L min. > 0 mL min. > 11.5 mL > 6.6 m
80/80L max. = 11.5 mL max. = 56 mL > 6.6 m
Air intake length 1 m.
L = total length of gas intake and exhaust ducts.
f the exhaust gas duct length is longer than 6.6 m, you will need a condensate drain
I
For coaxial systems, the maximum development value L, mentioned in the table above also takes into accout an elbow.
For twin flue isystems the maximum development value L, mentioned in the table includes the exhaust gas/air intake terminal.
Type 5 outlets should respect the following instructions:
1- Keep the same ø 80 mm for the gas intakes and exhaust gas ducts.
2- If you need to insert elbows in the gas intake and exhaust gas ducts, you should consider for each one the equivalent length
to be included in the calculation of developed length.
3- The exhaust gas duct should jut above the roof by at least 0.5 m.
4- The intake and exhaust gas ducts in Type 5 must be installed on the same wall, or where the exhaust is vertical and the air
intake horizontal, the terminals must be on the same side of the building.
28
TYPE 1
TYPE 4
TYPE 2
TYPE 5
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
TYPE 3
FIG. 11.15
Page 29
12.Electrical Connections
THERMOSTATAMBIANCE
ROOMTHERMOSTAT
Raccordement côtéboîtier électriquepré-cablé
S
The 220-240 V and earth connection are
made by using the lead provided
C (Fig.
12.1)
FIG. 12.1
C
IM
PORTANT
C
O
NNECTION SHOULD BE MADE VIA A
F
USED DOUBLE POLE ISOLATING SWITCH WITH
CONTACT SEPERATION OF AT LEAST
B
OTH POLES
PIN PLUG AND UNSWITCHED SOCKET MAY BE
3
U
SED
T
AINING A BATH OR SHOWER
SUPPLY THE APPLIANCE
xternal Controls
E
!
!
3MM ON
. AL
TERNATIVELY
, P
ROVIDED IT IS NOT USED IN A ROOM CON
, A
FUSED
. IT
SHOULD ONLY
.
3 A
MP
3 AMP,
-
Open the cover B with a screwdriver (Fig.
12.2)
The room thermostat is connected onto this
connector
remove the bridge
-
B (Fig. 12.1)
S (Fig. 12.3)
- connect the thermostat in place of the
S (Fig. 12.3)
bridge
- If a remote time clock is to be fitted, using a
B
volt-free switching time clock, connect the
wires from the time clock following the
points above. (see also Fig. 12.4)
Room thermostat
Connector
Note: Before connecting an external time
clock, disconnect the internal time clock as
described in Section 18.3.4 (page 45)
IMPORTANT!!
DO NOT RUN 240 V AND 24 V CABLES TOGETHER.
B
Side view of the
connection to the pre
cabled electrical box
F
IG. 12.2
IG. 12.3
F
29
Page 30
Air pressure
Switch
Earth
Earth
13.Electrical/System Diagrams
FIG. 12.4
30
Page 31
36
3
1
2
4
13
7
11
14
8
9
10
12
5
6
19
18
1
7
16
20
3
0
29
28
2
6
2
5
2
4
23
2
2
2
1
31333234
35
37
14.Water circuit Diagrams
LEGEND :
1. - Main heat exchanger
2. - Burner
3. - Ignition electrodes
4. - Flame detection electrode
5. - Modulating valve
6. - Safety valve
7. - Safety valve
8. - Domestic hot water tank
9. - Water tank valve
10. - Water service tap
11. - Heating flow thermistor
12. - Tank thermistor
13. - Hot water control thermistor
14. - Pump
16. - DHW activator
17. - Heating return thermistor
18. - Heating expansion vessel
19. - Three way valve
20. - Heating safety valve
21. - Pressure gauge
22. - Electrical box
23. - Overheating safety device
24. - Air pressure switch
25. - Fan
26. - Flue pipe
27. - By-pass
28. - Non-return valve
29. - Flow limiter
30. - Filter
31. - Gas tap
32. - Heating return tap
33. - Heating flow tap
34. - Water service tap
35. - DHW expansion kit
36. - Thermostatic mixing kit (optional)
37. - D.H.W. circulation kit (optional)
31
Page 32
15.COMMISSIONING
15.1Initial Preparation
MTS (GB) Limited support the initiative. Within the information
pack you will find a copy of the Log Book. It is important that
this is completed in the presence of your customer, they are shown
ow to use it, and it is signed by them. Please instruct your customer
h
that they must have their Log Book with them whenever they
contact a service engineer or us.
Preliminary electrical system checks to ensure electrical safety must be
carried out by a competent person i.e. polarity, earth continuity,
resistance to earth and short circuit.
FILLING THE HEATING SYSTEM:
ower the control panel and remove the case panels (see
L
15.3 for further information).
Open the central heating flow and return cocks supplied with the
connection kit.
Unscrew the cap on the automatic air release valve one full turn and
leave open permanently.
Close all air release valves on the central heating system.
Gradually open valve(s) at the filling point (filling-loop) connection to
the central heating system until water is heard to flow, do not open
fully.
Open each air release tap starting with the lowest point and close
them only when clear water, free of air, is visible.
SECTION
FIG. 15.1
Purge the air from the pump by unscrewing the pump plug
anticlockwise, also manually rotate the pump shaft in the
direction indicated by the pump label to ensure the pump is
free.
Refit the pump plug.
Continue filling the system until at least 1.5 bar registers on the
pressure gauge.
Inspect the system for water soundness and remedy any leaks
discovered.
FILLING OF THE D.H.W. SYSTEM:
Close all hot water draw-off taps.
Open the cold water inlet cock supplied with the connection kit.
Open slowly each draw-off tap and close them only when clear
water, free of bubbles, is visible.
GAS SUPPLY:
Inspect the entire installation including the gas meter and test for
soundness. The gas installation should be in accordance with the
relevant standards. In GB this is BS6891 and in IE this is the
current edition of I.S.813.
32
The connection to the appliance is a 15mm copper tail located at the
rear of the gas service cock (Fig. 10.3).
If the gas supply for the boiler serves other appliances ensure that
an adequate supply is available both to the boiler and the other
appliances when they are in use at the same time.
Pipe work must be of an adequate size. Pipes less than the 22mm
should not be used.
Open the gas cock (supplied with the connection kit) to the
appliance and check the gas connections on the appliance for leaks.
Page 33
When the installation and filling are completed, flush the system while
cold, refill, turn on the Central Heating system (
until the temperature has reached the boiler operating temperature.
The system must then be immediately flushed through.
The flushing procedure must be in line with BS 7593:1992 code of
practice for treatment of water in domestic hot water central heating
systems.
During this operation, we highly recommend the use of a central
eating flushing detergent (Fernox Superfloc or equivalent), whose
h
unction is to dissolve any foreign matter that may be in the system.
f
Substances different from these could create serious problems to
the pump or other components.
The use of an inhibitor in the system such as Fernox MB-1 or
equivalent is strongly recommended to prevent corrosion (
damaging the boiler and system, following the flushing procedure..
Failure to carry out this procedure may invalidate the appliance
warranty.
SE
CTION
3) and run it
sludge)
15.2Completion
For IE it is necessary to complete a “Declaration of Conformity” to
indicate compliance to I.S.813. An example of this is given in the
current edition of I.S.813. In addition it is necessary to complete the
Log Book.
33
Page 34
15.3Removal and fitting of the case -
A
A
A
A
Day
Day
Servicing
Removal of the case
- undo the 4 case retaining screws (Fig. 15.1)
disengage the clips
-
- remove the case
FIG. 15.2
detail
Fitting the case
Remove the protective film from the front and
rear of the case
- position the case (Fig. 15.2)
- engage both clips in the case (see detail)
- fasten the 4 retaining screws
FIG. 15.3
A on the front
Servicing
To maintain the unit, it is possible to move the electrical
box without having to disconnect it. The electrical box
is clipped onto the heating outlet pipe or onto the
bottom of the chassis. (Fig. 15.3)
34
FIG. 15.4
Page 35
15.4Control Panel
P
1
P2
OFF ON
12341
234
00
RR
P
r
o
g
.
h
m
Day
25
32
27
28
26
33
egend:
L
25 - Selector Knob :
entral Heating and Hot Water
9
2
30
31
C
Hot Water Only
OStand-by
Central Heating Only
26 - D.H.W. temperature control knob
27 - C.H. temperatre control knob
28 - Heating temperature indicator and diagnostic
indicator
9 - Green indicator - Power ON
2
30 - Orange indicator - Burner ON
31 - Red indicator - Lock out / flame failure
2 - Reset button
3
33 - Pressure gauge
34
34 - Time clock
15.5Initial Start-up
The checks to be run before initial start-up are as follows:
1. Make sure that:
-the screw on the automatic air valve has been loosened when the
system is full;
- If the water pressure in the system is below 1.5 bar, bring it up to
the appropriate level;
-Check to ensure the gas cock is open;
- Make sure that the electrical connection has been made properly
and that the earth wire is connected to an efficient earthing system
To obtain hot water only
- Turn the selector switch 25 to the «» position, the green LED
29 will light; the orange LED 30 will light to indicate that the
burner is alight.
- To adjust the temperature of the domestic hot water, it is
necessary to rotate the control knob
26 «» clockwise to
increase and anti-clockwise to decrease the temperature until the
desired temperature is achieved.
To obtain central heating and domestic hot water
- Turn the selector switch 25 to the «» position, the green LED
29 will light; the orange LED 30 will light to indicate that the burner is
alight.
- Upon a demand for domestic hot water the operation of the central
heating will be interrupted until the hot water tank has been reheated
to the set temperature.
- The control knob
27 «» allows you to adjust the water
temperature in the central heating circuit according to seasonal
requirements.
- Turn the control knob
- Clockwise in cold weather
- Anti-clockwise in mild weather (by turning the knob fully anticlockwise, the Central Heating will switch off).
- The LEDs
central heating circuit.
28will display the temperature of the water in the
- Furthermore, if your home is fitted with a room thermostat, set it
to the desired indoor temperature.
- The orange LED
27:
30 will light each time the burner operates.
35
Page 36
To obtain central heating only
- Turn the selector switch 25 to the «» position, the green LED
29 will light.
Ensure that the time clock is on (see Section 4), and if fitted that
the room thermostat is calling for heat.
- The control knob
27 «» allows you to adjust the water
temperature in the central heating circuit according to seasonal
requirements.
- Turn the control knob
27:
- Clockwise in cold weather
- Anti-clockwise in mild weather (by turning the knob too far, the
entral Heating will switch off).
C
The LEDs
-
8
2
ill display the temperature of the water in the
w
central heating circuit.
- Furthermore, if your home is fitted with a room thermostat, set it
to the desired indoor temperature.
- The orange LED
30 will light each time the burner operates.
Stopping the central heating
- Turn the selector switch 25 to the “” position. In this state the
boiler will only produce domestic hot water,alternatively, you can
turn the time clock off or if fitted turn the room thermostat down.
Stand-by mode
- Turn the selector switch 25 to the «O » position, the green LED 29
will remain alight. The appliance will remain in stand-by mode
unless the anti-frost device is activated.
Turn off the appliance*
- Turn the selector switch 25 to the «O» position
- Turn off the external power supply to the boiler.
*NOTE:IN THIS STATE THE APPLIANCES ANTI-FROST DEVICE IS INACTIVE
The boiler is fitted with a device, which in the event that the water
temperature falls below 8
temperature of 18
temperature falls below 3
o
C the pump activates and runs until a
o
C is attained. In the event that the water
o
C, the diverter valve switches to Domestic
Hot Water and the burner fires on minimum power until a
O
temperature of 33
C is attained.
This device is only activated when the boiler is operating perfectly
and
the system pressure is sufficient;
-
the boiler is powered electrically;
-
- gas is available.
15.6Sequence of OperationCentral Heating Mode
(Unless the hot water cylinder is being heated), when the time clock
and room thermostat are calling for heat, the pump starts. When all
other demands are in operation and the safety devices are satisfied
(eg. fan and air pressure switch)
sequence. Once the flame is detected by the ionisation system, for
the initial 30 seconds of operation the electronics monitor the
between the flow and return NTC’s to ensure there is a correct flow
through the appliance.
- If the
- If the
∆Tois less than 40oC the central heating cycle continues.
∆Tois equal to or more than 40oC, or if the return
temperature is more than 10
then the burner switches off and the relevant error code is shown
on the display.
the burner goes through an ignition
o
C above the flow temperature
∆T
o
36
The flow NTC
adjusts the output of the boiler by modulating the
burner between the minimum and maximum pressure.
Page 37
By comparing the actual temperature in relation to the set point on
the thermostat control knob. The thermostat control knob regulates
o
the temperature to between approximately 40
nce the maximum set temperature has been achieved the burner
O
C to 85oC.
switches off. To avoid rapid burner cycling the re-ignition of the
burner can be delayed between 30 seconds and 3 minutes.
When the boiler switches off because either the time clock or room
thermostat is satisfied there is a pump over run which is adjustable
between 0 to 5 minutes to avoid residual heat build up.
Hot Water Mode (with no water flow rate)
hen the storage temperature of the tank (measured by the uppper
W
NTC on the tank) is 4
control thermostat the appliance operates to recover the storage
temperature. The 3 way valve moves into the DHW position, the
pump runs, the burner lights and the ionisation electrodes detect the
prescence of a flame.
calorifier in the storage cylinder and heats the water indirectly. The
upper NTC continues to monitor the cylinder temperature and
modulates the burner via the gas valve. The flow NTC limits the
temperature to 85
o
C or more below the set point of the hot water
The primary water is pumped around a
o
C.
When the cylinder temperature is equal to the set temperature the
burner switches off and the pump stops. If the primary water
o
temperature is greater than or equal to 85
the primary temperature drops to 80
C the fan over runs until
o
C to avoid residual heat build
up.
Hot Water Mode (with water flow rate)
With a draw off rate equal to or greater than 1.9l/min:
When the domestic hot water flow switch detects a water flow rate
the 3 way valve moves into the DHW position, the pump, fan and
controls operate and the burner lights. The upper NTC on the
cylinder regulates the temperature of the hot water by adjusting the
modulation rate of the gas valve. If whilst drawing DHW the
difference in temperature monitored between the upper NTC
the lower NTC on the cylinder is equal to or greater than 1
and
o
C the
electronics increases the the output of the appliance to anticipate
the reheating of the cylinder. The lower NTC is therefore used as a
booster.
After drawing DHW
or greater than 85
the fan over runs if the primary water is equal to
o
C.
Hot Water Mode (with water flow rate)
With a draw off rate equal to or less than 1.9l/min:
With a DHW flow rate insufficient to operate the DHW flow switch
the upper NTC measures the temperature of the water in the
cylinder. If the
thermostat set point, the 3 way valve moves into the DHW
the controls and systems operate and the burner lights. The upper
NTC regulates the temperature of the DHW in relation to the
thermostat set point. When the set point is reached the burner
switches off and the fan over runs if the primary water temperature
is equal to or greater than 85
∆Tois equal to or greater than 5oC in relation to the
position,
o
C.
37
Page 38
15.7Operational Adjustments
P1
P2
OFF ON
A1
A2
A3
A4
ONOFF
B1
B2
B3
B4
P1
P2
OFF ON
1
2
3
41
2
3
4
SETTINGS
The boiler is delivered with all dip switches set to the OFF position with the exception of B2 which is set to the ON position (Fig.
15.6). The maximum heating power can be adjusted by turning the potentiometer (
To do this it is first necessary to open the electrical box and proceed as follows:
witch off the external power supply, remove the front panel (Section 18.2.1 and 18.2.2), Open the box by pressing the tab
S
5.5), the adjustment potentiometers are on the P.C.B. behind the tab
1
ets the pump to operate permanently or stop when the room thermostat is satisfied.
-
A1S
A2 Sets the operation of the pump to low or high speed for Central Heating operation.
-
-
A3 Adjusts the Anti-Cycle delay for the Central Heating from 30 seconds to 3 minutes.
ets the burner to fully modulating or step modulating (ON/OFF).
-
A4S
B1 Sets the maximum Central Heating Temperature to either 85°C or 90°C
-
-
B2 Selects or de-selects the programmer (For the UK and IE it must always be in the ON position).
-
B3 No function
B4 Sets the boiler to work in conjunction with the D.H.W. thermostatic cartridge kit, when in the on position the D.H.W. is set to a
-
P.
fixed temperature of 60°C regardless of the postion of the D.H.W. temperature control knob
P1) between the Min and Max position.
26 (Fig. 3.1)
P (
Fig.
P2
P1
P
Note : After the power has been cut to the boiler, or the
P.C.B. has been reset the TAC is cancelled for 3
minutes.
P1 :Adjusts the Central Heating ouput power (see
Section 16).
- P2 : Adjusts the ignition pressure of the boiler (softlight) between the minimum and maximum
setting
J12 connector provided with a shunt is designed to
The
connect to either a room thermostat or external
programmer (see Section 12).
Once all adjustments have been completed, replace the
P and reassemble the boiler.
tab
FIG. 15.5
Factory setting
FIG. 15.6
38
Page 39
15.8Combustion Analysis
The boiler is designed to make it easy to analyse the
combustion by-products.
Using the specially designed test points, readings can be
taken on the temperature of the combustion by-products
and of the combustion air, as well as of the
oncentrations of O
c
he best maximum-power test conditions for the heating
T
system are obtained by turning the Selector Knob
(Section 15.4) to central heating only and turning the
C.H. temperature control knob
2
a
nd CO
2
etc.
,
27 to maximum.
15.9Boiler Safety Systems
If a fault occurs in the appliance, one or more LEDs (28 Fig.3.1) flash according to the fault type listed in the table below.
CodeFAULTINFORMATION
30 40 50 60 70 80
25
mmmmmmmmmml
mmmmmmmmlll
mmmmmmllmml
mmmmmmllllm
m
mmmmmmlllll
mmmmllmmmmm
m
mmmmllmmmml
mmmmllmmllm
m
mmmmllmmlll
mmmmllllmmm
m
mmmmllllmml
mmmmllllllm
m
mmllmmmmmml
mmllmmmmllm
mmllmmllmmm
m
m
mmllmmllmml
mmllmmllllm
m
l
Overheating safety feature
l
No flame detection
l
l
Lack of water circulation
Primary water circulation defect
l
D.H.W. thermistor faulty (open cicrcuit)
D.H.W.
l
Central heating return thermistor faulty (open circuit)
Central heating return thermistor faulty (short circuit)
l
Central heating flow thermistor faulty (open circuit)
Central heating flow thermistor faulty (short circuit)
l
Low water pressure in the heating system
Re-ignition attempt
Wiring problem (or fuse 1.25 A)
l
Fan on but does not activate air pressure switch
Fan off but air pressure switch fails to return to off position
thermistor faulty (short circuit)
Anti-frost mode on (pump in operation)
Anti-frost mode on (burner and pump in operation)
mmllmmlllll
mmllllmmmmm
mmllllmmmml
mmllllmmllm
mmllllmmlll
llmmmmmmmmm
mm
= LED off
ll
= LED blinking
l
Low fan speed
m
Operating control fault of the fan
l
Thermistor «comfort» (open circuit)
m
Thermistor «comfort» (short circuit)
l
Cylinder temperature 5oC above set point
m
Communication defect with the main PCB
39
Page 40
16.Gas Adjustments
C
D
E
F
AA
BB
FIG. 16.1
When converting to a gas different from the one for which the boiler is
equipped, you should replace the parts delivered with the conversion
kit, and make the gas valve adjustments as described below:
Setting the minimum and the maximum power of the boiler
Check that the supply pressure and dynamic pressure to the gas valve
is a minimum of 20 mbar for natural gas. To do this, loosen the screw
“A”.
Fit the pipe of the pressure gauge to the inlet pressure connection of
the gas valve
perate the appliance and check for the correct working pressure.
o
hen you have completed this operation, replace the screw
W
“B” check for the correct standing pressure, then
“
A”
securely into its housing to seal off the gas (check for tightness).
To check the pressure supplied by the gas valve to the burner, loosen
the screw
test point of the gas valve
“C”. Fit the pipe of the pressure gauge to the pressure outlet
“D”.
FIG. 16.2
FIG. 16.3
C
D
D1
E
Disconnect the compensation pipe
“D1” either from the gas valve or
from the sealed chamber.
Turn the boiler on, and ensure that the hot water temperature control
knob is set to maximum. Turn on the boiler by running a hot water tap.
Adjust the 10mm nut
“E” on the modureg to set the maximum gas
pressure, turn the nut clockwise to increase and anti clockwise to
decrease the pressure until the required pressure is achieved (see
MAXIMUM BURNER PRESSURE TABLE page 41).
To set the minimum power, disconnect a supply terminal
modureg and adjust screw
“F” (ensure the 10mm nut is held in
“F1” from the
position). Turn the screw clockwise to increase the gas pressure and
counter-clockwise to decrease the gas pressure (displayed on the
pressure gauge) corresponding to the minimum power (see
MINIMUM
BURNER PRESSURE TABLE page 41).
When you have completed the above operations, turn off the hot water
tap, re-connect the supply terminal to the modureg on the gas valve
and replace the cap on the screw of the modureg.
Setting the maximum heating circuit power
To set the maximum heating circuit power, turn the boiler on and turn
the Central Heating temperature control knob to maximum, ensuring all
extermal controls are calling for heat.
40
FIG. 16.4
Remove the inspection panel of the P.C.B. and fit a small cross-head
screwdriver in to potentiometer P1 (see page 38). Turn clockwise to
increase the pressure or counter-clockwise to reduce the pressure.
Adjust the setting to the required heating pressure value (displayed on
the pressure gauge), as indicated in the tables shown on page 41.
Turn off the boiler by placing the main switch to the "OFF" position.
F
Adjusting the ignition output
The potentiometer P2 (Fig. 15.6) on the PCB permits this adjustment
see Operational Adjustments on page 38).
(
F1
Disconnect the detection electrode
(see section 18.4.4).
Start the boiler and during the ignition sequence adjust the P2
potentiometer until the gas pressure reads the required gas pressure
as per the table on page 41.
Page 41
nce the gas pressure is set turn off the boiler and re-
O
onnect the detection electrode.
c
NB.: It may be necessary to reset the flame failure reset
a number of times during this operation.
Gas valve restrictor diameter...........................9.0 mm9.0 mm9.0 mm
(1 mbar = 10.197mm column of water)
The outlet pressure of the gas cock is obtained by completely loosening the screw on the solenoid. The maximum pressure of the gas
to the burner will be equal to the nominal delivery pressure minus the head loss within the gas valve.
...................................1.23 mm
16.1Changing the Type
of Gas
3
/h0.89 kg/h0.88 kg/h
0.74 mm0.74 mm
The boiler can be converted to use either methane (natural) gas
(G20) or LPG (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1.Adjust the maximum and minimum thermal capacity values for the
boiler (see table below).
Minimum PressureNominal Pressure
G20G30-G31G20G30-G31
2.712.512.527.9
41
Page 42
17.Maintenance
It is recommended that the following checks be made on the
boiler at least once a year:
1 - Check the seals for the water connections; replacement of any
faulty seals.
- Check the gas seals; replacement of any faulty gas seals.
2
3 - Visual check of the entire unit.
- Visual check of the combustion process and cleaning of the
4
burners if needed.
- If called for by check no. 3, dismantling and cleaning of the
5
combustion chamber.
6 - If called for by check no. 4, dismantling and cleaning of the
injectors.
- Visual check of the primary heat exchanger:
7
- check for overheating in the blade assembly;
- clean the exhaust fan if needed.
8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load
and full load.
- Check of the heating safety systems:
9
- safety device for maximum temperature;
- safety device for maximum pressure.
10- Check of the gas safety systems:
- safety device for lack of gas or flame ionisation (detection
electrode);
- safety device for gas cock.
11- Check of the electrical connection (make sure it complies with the
instructions in the manual).
12- Check of domestic hot water production efficiency (delivery rate and
temperature)
13 - Check pressure in the Domestic Expansion Vessel and top up as
necessary.
14 - Check manually by turning the test knob of the Temperature &
Pressure Relief Valve.
15 - Check manually by turning the test knob the Expansion Relief Valve.
16 - Check discharge pipes from both the central heating and domestic
hot water for obstructions.
17- Check of the general performance of the unit.
18- General check of the discharge/ventilation of the combustion by
products.
NOTE: THESE CHECKS ARE NOT EXHAUSTIVE
42
Page 43
18. Servicing Instructions
To ensure efficient safe operation, it is recommended that the
oiler is serviced annually by a competent person.
b
Before starting any servicing work, ensure both the gas and
electrical supplies to the boiler are isolated and the boiler is
cool.
Before and after servicing, a combustion analysis should be
made via the flue sampling point (please refer to Section 15.8).
fter servicing, preliminary electrical system checks must be
A
carried out to ensure electrical safety (i.e. polarity, earth
continuity, resistance to earth and short circuit).
18.1 Replacement of Parts
The life of individual components vary and they will need
servicing or replacing as and when faults develop.
The fault finding sequence chart in Section 19 will help to locate
which component is the cause of any malfunction, and
instructions for removal, inspection and replacement of the
individual parts are given in the following pages.
A
Fig. 18.1
A
A
18.2 To Gain General Access
All testing and maintenance operations on the boiler require the
control panel to be lowered. This will also require the removal of
the casing.
18.2.1 Removing the front panel :
1. Remove the 4 retaining screws “A” (see fig. 18.1);
2. Disengage the 2 clips (see fig. 18.2);
3. Remove the front panel from the rest of the casing (see
fig. 18.3).
18.2.2 Removing the control panel :
1. Remove the front panel as above;
2. Pull the control panel toward you to disengage it from
the bottom of the chassis
3. Clip the top of the control panel onto the bottom of the
chassis.
(see fig. 18.5).
(see fig. 18.4);
Fig.18.2
Fig. 18.3
Fig. 18.5
Fig. 18.4
43
Page 44
18.3Access to the Control System
8.3.1 Removing the main P.C.B.
1
1. Isolate electricity and carry out step 18.2.1 ;
2. Open the control box by pushing on the 2 right clips “B” (see
Fig. 18.6 )
3. Push on the pressure gauge to disengage it (see Fig. 18.7) ;
4. Disconnect all the connectors on the P.C.B. ;
5. Remove the T20 screw in the middle of the P.C.B. , then
ull the card toward you
p
6. Reassemble in reverse order.
;
see Fig.18.8 and Fig 18.9)
(
;
B
Fig. 18.6
8.3.2 Removing the display P.C.B.
1
1. Isolate electricity;
2. Carry out step 18.2.1;
3. Open the control box (see Fig. 18.6);
4. Remove the three control knobs (see Fig.18.10 &
;
18.11)
5. Remove the display card connector on the main P.C.B.
see Fig.18.12);
(
6. Remove the five T20 screws on the P.C.B., then pull the
card toward you
7. Reassemble in reverse order.
(see Fig.18.13);
Fig. 18.10
Fig. 18.11
Fig. 18.7
Fig. 18.12
Fig. 18.8
44
Fig. 18.9
Fig. 18.13
Page 45
18.3.3 Removing the fuses
18.3.4 Removing the time clock
1. Carry out step 18.2.1 ;
2. Open the electrical box as in step 18.3.1 Fig.18. 6
emove the fuse box cover “C” (see Fig. 18.14);
3.R
ull out the fuse (see Fig. 18.15)
4.P
eassemble in reverse order.
5.R
;
C
Fig. 18.14
arry out step 18.2.1
1.C
pen the electrical box as in step 18.3.1 Fig. 18.6;
2.O
3. Disconnect the programmer plug (see Fig. 18.16);
4. Push on the two clips to remove the programmer (see Fig.
18.17);
5. Reassemble in reverse order.
;
Fig. 18.16
Fig. 18.15
Fig. 18.17
45
Page 46
18.4 Access to the Sealed Chamber
18.4.1 Removing the sealed chamber front panel
1. Carry out step 18.2.1;
2. Unscrew the six self tapping screws “D” to release the
sealed chamber front panel and lift clear
3. Reassemble in reverse order.
(see Fig. 18.18);
D
18.4.3 Removing the burner
1. Carry out steps 18.2.1, 18.4.1 and 18.4.2 as above;
isconnect the electrode wires (see Fig. 18.20);
2.D
3. Remove the two caps “F” from the bottom of the
combustion chamber
4. Remove the nut “G” between manifold and gas pipe(see
Fig. 18.23);
5. Then, pull the burner toward you (see Fig. 18.24);
6. Reassemble in reverse order and carry out combustion
tests.
(see Fig. 18.21, Fig 18.22);
Fig. 18.18
18.4.2 Removing the combustion chamber front panel
1. Carry out steps 18.2.1 and 18.4.1;
2. Unscrew the four self tapping screws “E”
combustion chamber front panel and lift clear
3. Reassemble in reverse order.
to release the
(see Fig. 18.19);
E
Fig. 18.20
Fig. 18.21
F
Fig. 18.22
G
Fig. 18.23
46
Fig. 18.19
Fig. 18.24
Page 47
18.4.4 Removing the electrodes
18.4.5 Removing the burner manifold
1. Carry out steps 18.2.1, 18.4.1 and 18.4.2 as above;
2. Disconnect the electrode wires (see Fig. 18.20, Fig 18.21 &
18.22);
or the ionisation electrode :
3.F
emove the screw “H1
R
(see Fig. 18.26);
For the ignition electrodes :
It’s necessary to disengage the burner in part as in step
18.4.3, and then remove the two self tapping screws “H2”
(see Fig. 18.25);
ull up the electrodes (see Fig. 18.27);
P
4. Reassemble in reverse order.
see Fig. 18.25), and pull it up
” (
arry out steps 18.2.1, 18.2.2, 18.4.1 and 18.4.2
1.C
2. Remove the burner as in step 18.4.3;
3. Remove the 3 screws “ I ” securing the manifold and lift
(see Fig. 18.28);
clear
4. Reassemble in reverse order positioning the stop lug in
the correct postion.
(see Fig. 18.29).
I
;
Fig.18. 28
H1
Fig.18. 29
H2
Fig.18. 25
Fig.18. 26
Fig.18. 27
47
Page 48
18.4.6 Removing the main heat exchanger
arry out steps 18.2.1,and 18.4.1 as above;
1.C
rain the boiler (only heating circuit) as in step 18.6.1
2.D
3. Remove the NTC clips “J1” and overheat sensor clip “J2” (see Fig. 18.30 and 18.31);
4. Remove the 2 clips “J3” securing the heat exchanger (see Fig. 18.30 and 18.31);
5. Unscrew the nut “J4” from the tank (see Fig. 18.30 and 18.31);
6. Pull the heat exchanger toward you to remove it (see Fig. 18.32);
7. Reassemble in reverse order, do not forget to grease o rings before reassembly.
;
Fig. 18.30
J4
J2
J3
J1
Fig. 18.31
Fig. 18.32
48
Page 49
18.4.7 Removing the air pressure switch
18.4.8 Removing the fan
1. Carry out steps 18.2.1 and 18.4.1;
2. Disconnect the wire connectors “K1” (see Fig. 18.33);
3. Disconnect the pressure pipes “K2” noting positions
see Fig. 18.33 )
(
otate the the pressure switch clockwise to disengage
4.R
it
(see Fig. 18.34);
5 Reassemble in reverse order ensuring that the wiring is
reconnected.
;
K1
1. Carry out steps 18.2.1 and 18.4.1;
2. Disconnect the wire connectors “L1” and the earth wire
L2”
“
see Fig. 18.35)
(
emove the screw “M” fixing the fan on the flue outlet,
3.R
(see Fig. 18.35);
4. Slide the fan to disengage from flue outlet and lift clear
(see Fig. 18.35, 18.36, 18.37);
5. Disconnect the pressure pipes noting positions (see Fig. 18.38);
6. Reassemble in reverse order ensuring that the wiring is
reconnected correctly and the screw tightened.
;
L2
L1
K2
Fig. 18.33
Fig. 18.34
M
Fig. 18.35
Fig. 18.36
Fig. 18.37
Fig. 18.38
49
Page 50
18.5Access to the Gas Valve
8.5.2 Removing the gas valve
1
Important. ensure gas supply to boiler is turned off
18.5.1 Removing the spark generator
1. Carry out step 18.2.1 ;
2. Open the control box by pushing on the 2 right clips as in
8.3.1 Fig 18.6;
tep
1
s
3. Disconnect electrical connections “N1” on the P.C.B. (see Fig.
;
18.42)
4. Disconnect the electrodes wires “N2” and remove the screw
N3” (see Fig. 18.43) ;
“
5. Remove the spark generator by pulling it toward the right
(see Fig.18.43);
6. Reassemble in reverse order.
N1
Carry out step 18.2.1 ;
1.
emove the spark generator by only removing the screw
2.R
and pull it toward the right as in Fig.18.43
N3”
“
3. Disconnect the wires from the modulator coil “O1”(see Fig.
;
18.44)
4. Undo the 2 gas pipe nuts “O2” (spanner 30) and the nut
O3” securing the gas valve from the combustion chamber
“
(see Fig.18.45);
5. Pull the gas valve toward you (see Fig.18.46);
6. Reassemble in reverse order replacing the gaskets.
;
O1
Fig. 18.44
N3
O3
O2
Fig. 18.42
Fig. 18.45
N2
50
Fig. 18.43
Fig. 18.46
Page 51
18.6Access to the Water Circuit
Important ! Before any component is removed (except the 3
ay valve motor), the boiler must be drained of all water.
w
18.6.1 Drain down
For the primary circuit :
1. Carry out step 18.2.1 ;
2. Open the pressure relief valve (on the pump) (see Fig. 18.47)
or the drain screw “P1” on the right hydraulic block (see
Fig.18.48)
or the D.H.W. circuit :
F
1. Close the water inlet tap;
2. Open a D.H.W. hot water tap;
3. Open the drain screw “P2” on the boiler (see Fig. 18.48)
To drain the tank more quickly remove the cap on the tank
(see Fig. 18.49);
Important!! Take care when removing the cap to drain the
;
cylinder
18.6.2 Removing the 3 way valve
1. Carry out steps 18.2.1 and 18.2.2 ;
2. Remove the clip “Q1” and the three way valve motor (see
Fig. 18.50)
3. Remove the two screws “Q2” (see Fig. 18.51);
hen pull up the three way valve shutter (see Fig. 18.52);
4.T
5. Reassemble in reverse order.
;
Q1
Fig. 18.50
P2
Q2
Fig. 18.47
Fig. 18.51
Fig. 18.52
P1
Fig. 18.48
Fig. 18.49
Fig. 18.53
51
Page 52
8.6.3 Removing the heating return filter
1
8.6.5 Removing the pressure relief valve (3 bar)
1
1. Unscrew 1/4 ball screw “R” (see Fig. 18.58);
2. Pull it down (see Fig. 18.59);
3. Reassemble in reverse order.
R
Fig. 18.58
1. Carry out steps 18.2.1 and 18.2.2;
2. Remove the clip securing the valve and disconnect the
safety valve outlet
3. Disconnect the flexible pipe (see Fig. 18.63);
4. Reassemble in reverse order.
(see Fig. 18.62) and pull it toward the left;
Fig. 18.62
Fig. 18.63
Fig. 18.59
18.6.4 Removing the by-pass
1. Carry out steps 18.2.1 and 18.2.2;
2. Remove the heating filter as in step 18.6.3 ;
3. Remove the clip and pull out the By-pass (see Fig. 18.60);
4. Reassemble in reverse order.
Fig. 18.60
18.6.6 Removing the pressure relief valve (6 bar)
1. Carry out steps 18.2.1 and 18.2.2;
2. Remove the clip securing the valve and unscrew the nut
(see Fg. 18.64);
3. Reassemble in reverse order.
Fig. 18.64
18.6.7 Removing the temperature and pressure relief
valve (7 bar)
1. Unscrew the nut and then unscrew the valve (see Fig. 18.65);
2. Reassemble in reverse order.
Fig. 18.65
52
Fig. 18.61
Page 53
8.6.8 Removing the pump
1
arry out step 18.2.1
1.C
pen the electrical box cover as in step 18.3.1 Fig. 18.6
2.O
emove the pump plug from the control board and earth
3.R
plug from earth socket “
4. Remove the pressure relief valve 3 bar as in step 18.6.5;
5. Unscrew the pump nut “T1” and remove the clip “T2” on the
pump volute
6. Pull the pump toward you and remove the clip “T3” securing
the pressure gauge
eassemble in reverse order.
7.R
(see Fig. 18.67 & Fig 18.68);
;
S” (see Fig. 18.66);
(see Fig. 18.69);
S
8.6.9 Removing the expansion vessel
1
arry out step 18.2.1
1.C
emove the screw “U1” (see Fig. 18.70)
2.R
ull the expansion vessel toward you and remove the nut
3.P
“
U2” with a No.17 spanner (see Fig. 18.71);
4. To ensure the easiest access to the hydraulic parts, hang
the expansion vessel on the chassis without removing the
(see Fig. 18.72);
nut
5. Reassemble in reverse order.
;
;
T2
Fig. 18.66
Fig. 18.67
T1
U1
Fig. 18.70
U2
Fig. 18.71
Fig. 18.68
T3
Fig. 18.69
Fig. 18.72
53
Page 54
8.6.10. Removing the overheat thermostat
1
1. Remove the casing as in step 18.2.1 ;
2. Pull off the thermostat connections. Then remove the
thermostat from the pipe by releasing it’s securing clip
(see Fig. 18.73).
Fig. 18.73
18.6.11 Removing the heating temperature sensor
8.6.13 Removing the flow switch
1
emove the casing as in step 18.2.1
1.R
2. Remove electrical connection and the two clips fixing the
flow switch
3. Pull down the lower pipe and remove the flow switch;
4. Reassemble in reverse order, the arrow must be
positioned correctly
5. Reassemble in reverse order
(see Fig. 18.76);
(see Fig. 18.77 and 18.78).
;
1. Remove the casing as in step 18.2.1 ;
2. Pull off the NTC connections. Then remove the NTC
from the pipes by releasing clips
(see Fig. 18.74).
Fig. 18.74
18.6.12 Removing the tank temperature sensor
1. Remove the casing as in step 18.2.1 ;
2. Pull off the NTC connections. Then remove the NTC
from the tank by removing the screws
(see Fig. 18.75).
Fig. 18.76
Fig. 18.77
54
Fig. 18.78
Fig.18.75
Page 55
18.6.14 Removing the D.H.W. expansion vessel
18.6.15 Removing the flow limiter
1. Remove the casing as in step 18.2.1 ;
2. Remove the clip (see Fig. 18.79 & 18.80);
3. Pull up the first tie on the top of the expansion vessel (see
Fig. 18.81)
ull up the expansion vessel to disengage it from the
4.P
second tie;
5. Reassemble in reverse order.
;
1. Carry out steps 18.2.1 and 18.2.2;
2. Remove the two clips and remove the pipe (see Fig. 18.82);
3. Remove the two screws (see Fig. 18.83) and pull the block
toward you;
emove the limiter from the block (see Fig.18.84)
4.R
5. Reassemble in reverse order.
Fig. 18.83
;
Fig. 18.82
Fig. 18.79
Fig. 18.80
Fig. 18.84
Fig. 18.85
Fig. 18.81
55
Page 56
18.6.16 Removing the tank
1. Remove the casing as in steps 18.2.1 and 18.2.2;
2. Remove all clips, nuts (No. 30 spanner) and eletrical connections (NTC) from the tank (see Fig. 18.86 & 18.87);
3. Remove the clip on the bottom of the boiler to disengage the pipe between the chassis and the thermal valve (see Fig. 18.88);
4. Disconnect the D.H.W expansion vessel from the left hydraulic block (see Fig. 18.80);
5. Remove the two screws V on the left side panel (see Fig. 18.89);
emove the nut (No. 10 spanner ) on the top of the tank (see Fig. 18.90)
6.R
ull up the tank to disengage it, and then toward you to remove it.
7.P
eassemble in reverse order
8.R
;
ig.18. 86
F
ig. 18.87
F
56
Fig. 18.88
V
Fig. 18.89
Fig. 18.90
Page 57
PRELIMARY CHECKS
MAKE SURE THAT:
IS
THE POWER
L.E.D.
ON?
ESTATE
NONO
YESYES
1 - Check the fuses
2 - Check the power supply
cable, plug and outlet
3 - Check/replace the power
supply to the P.C.B.
4 - Check/replace the P.C.B
T
URN THE SELECTOR
K
NOB TO
TURN THE CH
CONTROL KNOB TO MAX
A
1 - There is sufficient water in
the system
2 - The gas is turned on
3 - The electrical supply is
turned on
IS DHW BEING
DRAWN
YESYES
YESYES
TURN THE DHW
CONTROL KNOB TO MAX
NONO
NONO
NONO
YESYES
IS CLOCK TURNED
ON AND THE ROOM
THERMOSTAT
TURNED UP
NONO
YESYES
FC P001
19. FAULT FINDING GUIDE (Flow-chart)
It is possible to detect and correct defects by using the standard fault finding diagrams described in this chapter.
emp. of Exhaust Fumes at Nominal Capacity with Methane°C
T
2
Content%
CO
Noxmg/kWh
CO Contentppm
Minimum Ambient Temperature°C
Heating Temperature (approx) max/min °C
Temperature & Pressure Relief Valve Settingbar/°C
Stored D.H.W. Cylinder Capacityl
Stored D.H.W. min/max Temperature (approx)max/min °C
Specific flow rate* (IN 10’ ∆T=30°C)l/min
Time Taken to Raise Tempertature from 15°C to 65°C**min
Time Taken to Raise 70% of the Stored Volume to 65°C**min
D.H.W. Expansion Vessel Capacityl
D.H.W. Expansion Vessel Pre-load Chargebar
D.H.W. Operating Pressurebar
Maximum Supply Pressure to Pressure Reducing Valvebar
Heating Expansion Vessel Capacityl
Heating Expansion Vessel Pre-load Chargebar
Maximum Water Content in Systeml
Maximum Heating Pressurebar
Nominal PressureNatural Gas (G20)mbar
LPG (G30-G31)mbar
Electrical SupplyV/Hz
Power ConsumptionW
Protection Grade of Electrical SystemIP
Internal Fuse Rating
Weight (empty)
Maximum Flue Length (horizontal and vertical)