ACS550 Technical Reference Manual
(available in electronic format only)
• Detailed Product Description
• Practical Engineering Guides
ACS550-PC/PD Packaged Drive with Disconnect
Supplement for ACS550-01/U1 User’s Manual
•Safety
•Installation
• Start-Up
• Maintenance
• Technical Data
ACS550- CC Packaged Drive with Bypass
Supplement for ACS550-01/U1 User’s Manual
•Safety
•Installation
• Start-Up
• Maintenance
• Technical Data
ACS550-PC/PD Packaged Drive with Disconnect1
Safety
WARNING! The ACS550 adjustable speed AC drive with Input Disconnect
should ONLY be instal led by a qualified electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at
the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the
frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected.
After disconnecting the supply, wait at least 5 minutes (to let the intermediate
circuit capacitors discharge) before removing the cover.
WARNING! Even when power is removed from the input terminals of the
ACS550, there may be dangerous voltage (from external sources) on the
terminals of the relay outputs.
WARNING! When the control terminals of two or more drive units are
connected in parallel, t he auxi liar y voltage for these control connect ions must
be taken from a single source which can either be one of the units or an
external supply.
WARNING! The ACS550 will start up automatically after an input voltage
interruption if the external run command is on.
WARNING! When the ACS550 with Input Disconne ct is connected to the line
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not
running. Do not make any connections when the ACS550 with Input
Disconnect is connected to the line. Disconnect and lock out power to the
drive before servicing the drive. Failure to disconnect power may cause
serious injury or death.
Note! For more technical information, contact the factory or your local ABB sales
representative.
Use of Warnings and Notes
There are two types of safety instructions throughout this manual:
•Notes draw attention to a particular condition or fact, or give information on a
subj
ect.
•Warnings caution you about condi tions whi ch can resul t in seri ous inju ry or death
and/o
r damage to the equipment. They also tell you how to avoid th e danger. The
warning symbols are used as follows:
Dangerous voltage warning warns of high voltage which can cause physical
injury and/or damage to the equipment.
Safety
2ACS550-PC/PD Packaged Drive with Disconnect
General warning warns about conditions, other than those caused by
electricity, which can result in physical injury and/or damage to the equipment.
Study t hese ins t a llat ion ins tr uctions car efu lly be for e proceedi ng. Failure t o observe
the warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read “Safety” on page 1.
WARNING! When the ACS550 with Input Disconne ct is connected to the line
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not
running. Do not make any connections when the ACS550 with Input
Disconnect is connected to the line. Disconnect and lock out power to the
drive before servicing the drive. Failure to disconnect power may cause
serious injury or death.
Application
This manual contains supplemental i nformation that is unique to ACS550 input
disconnect configurations (PC or PD). Refer to the base manual, AC550-01/U1
User’s Manual, for all other information.
Input Disconnect Features and Functions
The ACS550 with Input Disconnect is an ACS550 AC adjustable frequency dri ve
packaged with an input disconnect switch or circuit breaker, and with a door
mounted, external operating handle. The operat ing handle can be padlocked in the
OFF position (padlock not supplied). Enclosure options are UL Type 1, UL Type 12,
and UL Type 3R (NEMA 1, NEMA 12, and NEMA 3R).
The following is a typical power diagram.
Installation
ACS550-PC/PD Packaged Drive with Disconnect5
BP0093
ACS550 Drive
UL Type / NEMA 1 & 12UL Type / NEMA 1 & 12
BP0094
BP0096
EnclosuresEnclosures
UL Type / NEMA 1 & 12
Enclosures
Control Panel
Vertical ConstructionHinged Door Wall Mount
Floor Mount
PC00071
ACS550 Drive
Control Pa nel
with Hinged
Cover
UL Type
/ NEMA 3R
Enclosures
Operating Handle
for Disconnect Switch
or Circuit Breaker
The following figures show the front view of the ACS550 Drive with Input Discon nect
standard configurations, and identify the major components.
Note! UL Type 3R, PX3R-1, PX3R-2, PX3R-3 & PX3R-4 enclosu res are designed to
be mounted on a wall. Mounting these 3R enclosures on an open rack system
requires the use of the supplied 3R enclosure back plat es to maintain 3R integrity.
See section
“Prepare the UL Type 3R ACS550 PX3R-1, PX3R-2, PX3R-3, PX3R-4
for UNISTRUT® mounting” for more details.
Installation
6ACS550-PC/PD Packaged Drive with Disconnect
Installation Flow Chart
The installation of Input Disconnect configurations for ACS550 drives follows the
outline below. The steps must be carried out in th e order shown. At the right of each
step are references to the detailed information needed for the correct in stallation of
the unit.
Note! References in the middle column below are to the ACS550-01/U1 User’s
Manual. References in the third column below are to this manual.
Task
PREPARE fo
installation
PREPARE the
Mounting Location
REMOVE the front
cover
MOUNT the drive“Mount the Drive” R7/R8: “Mount the Drive” on
r
ACS5
“Preparing for Installation” • R7/R8: “Lifting the Drive” on
“Prepare the Mounting Loc ation”• R7/R8: “Prepare the Mounting
“Remove Front Cover” R7/R8: “Remove Side Panel- R7
Refer to the
50-01/U1 User’s Manual
“Installation” section
Additional Reference in this
nual
Ma
page 7.
• “Drive Identification” on page 8.
• “Suitable Mounting Location”
on page 9.
Location – R7 and R8” on
page 9.
• “Dimensions and Weights
(Supplement to A CS550-01/ U1
User’s Manual)” on page 34.
and R8 UL Type/NEMA 1 & 12
Enclosures” on page 10.
page 10.
Installation
INSTALL wiring“Wiring Overview” and
“Install the Wiring”
CHECK installation“Check Installation”--
RE-INSTALL the
cover
APPLY power“Apply Power”--
START-UP“Start-Up” --
“Re-install Cove r” --
“Installing the Wirin g (Su ppl em ent
to ACS550-01/U1 User’s Manual)”
starting on page 12.
ACS550-PC/PD Packaged Drive with Disconnect7
PC00005
R70010
2
PC00003
30
o
Preparing for Installation (Supplement to ACS550-01/U1 User’s Manual)
Lifting the Drive
R7…R8
Warning! Handle and ship floor mounted enclosures
only in the upright position. These unit s are not
designed to be laid on their backs.
1. Use a pallet truck to move the package/enclosure to the
installation site.
2. Remove the cabinet side panels from UL Type/NEMA 1
and 12 enclosures for access to the cabinet/ pallet
mount
panel in place. Leave the side p anels off until later.)
3. Remove the 4 bolts that secure the cabi net to the shippi ng
pa
ing bolts. (6 torx screws hold each cabinet side
llet.
Warning! Use the lifting lugs/ bars at the top of the unit
to lift R7/R8 drives.
4. Use a hoist to lift the drive. (Do not place drive in final
position until mounting site is prepared.)
Installation
8ACS550-PC/PD Packaged Drive with Disconnect
Preparing for Installation (Supplement to ACS550-01/U1 User’s Manual)
Drive Identification
To identify the type of device you are install ing, r efer to t he ty pe code number on the
devi
ce identification label.
•Wall mounting base drives – label attached on the side surface of the heat sink.
•Packaged drive with screw cover – label attached to outside surface on the lef t
ide
of the enclosure.
•Enclosure with hinged cover/door – label on inside surface of the cover/door.
Type Code Number
Use the following to interpret the type code found on the identification label.
ACS550-U1-015A-4 +…+…
AC Drive = 550 Product Series
Construction
U1 = Base Drive
CC = Bypass with circuit breaker
PC = Drive with circuit breaker
PD = Drive with disconnect switch
Output current rating (See ratings chart for details)
Voltage rating
2 = 208…240 VAC
4 = 380…480 VAC
6 = 500…600 VAC
Enclosure protection class
No specification = UL Type 1/NEMA 1
+B055 = UL Type 12/NEMA 12
+B058 = UL Type 3R/NEMA 3R
Power options
+F267 = Service switch
Input/Output option modules
+L502 = Pulse encoder interface
+L511 = Relay output extension
+L512 = 115/230 V digital input interface
Charts in the “Ratings”sections of the ACS550-01/U1 User’s Manual and this
manual list technical specificati ons, and identify the drive’s frame size.
Note! Some instructions in th is document var y, depending on the drive’s frame size.
To read the Ratings table, you need the “Output current rating” entry from the type
code (see above).
ACS550-PC/PD Packaged Drive with Disconnect9
PC00023
Fastening points when installed
back against a wall (Top view)
Fastening points when installed
back against back
Cabinet top
M12 bolt (1/2 to 9/16 in)
L-bracket
Fastening the cabinet at the top
using L-brackets (side view)
Suitable Mounting Location
For selecting a suitable mounting location for PC/PD configurations, refer to:
•Preparing for installation in the ACS550-01/U1 User’s Manual, and
•The Technical Data section of this manual for information on dimensions and
wei
ghts.
Installing the Drive (Supplement to ACS550-01/U1 User’ s Manual)
Warning! Metal shavings or debris in the enclosure can damage electrical
equipment and create a hazardous condition. Where parts, such as conduit
plates require cutting or drilling, first remove the part. If that is not practical,
cover nearby electrical components to protect them from all shavings or
debris.
Prepare the Mounting Location – R7 and R8
The ACS550 should only be mounted
where
“Preparing for In stallation” are met.
all of the requirements defined in
Frame sizes R7 and R8 have mounting
holes inside the enclosure base. See “UL
Type/NEMA 1&12, Floor Mount Enclosure
Mounting Dimensions” on page 37.
Where it is not possible to use either
mounting hole at the back of the base, use
an L-bracket at the top of the enclosure to
secure the cabinet to a wall or to the back
of another enclosure. Bol t the L-bracket to
the enclosure using the li fting lug bolt hole
on the top of the enclosure.
Installation
10ACS550-PC/PD Packaged Drive with Disconnect
2.
R70020
PC00003
30
o
Remove Side Panels – R7 and R8 UL Type/NEMA 1 & 12 Enclosures
Cabinet Door
1. To open the cabinet door, loosen the quarter-turn screws
t
hat hold the cabinet door closed.
2. Installation access is easier if these panels are kept off
t
hroughout the installation.
Mount the Drive
R7…R8
1. Use a hoist to move the cabinet into position.
Note! If the cabinet location does not provide access to
the cabinet sides, be sure to re-mount side panels before
positioning cabinet.
2. Install and tighten mounting bolts.
Installation
ACS550-PC/PD Packaged Drive with Disconnect11
Vent on back
of cabinet for
cooling.
Prepare the UL Type 3R ACS550 PX3R-1, PX3R-2, PX3R-3, PX3R-4 for UNISTRUT®
mounting
The ACS550 UL Type 3R cabinet fr ame sizes PX3R-1, PX3R-2, PX3R-3, PX3R-4,
PX3R-5,
PX3R-6 are designed to be mounted on a solid vertical surface or using
UNISTRUT. On frame sizes PX3R-1, PX3R-2, PX3R-3, PX3R-4, the d esign requi res
the use of a back plate that is provided with each UL Type 3R PX3R-1, PX3R-2,
PX3R-3, PX3R-4 shipment.
As delivered, UL Type 3R ACS550 drives PX3R-1, PX3R-2, PX3R-3, PX3R-4 frame
sizes are supplied such that mounting the cabinet on an open back allows rain/sn ow
to enter the pre-cut vent. To meet UL Type 3R requirements, install back plate
provided with the drive.
ACx550 UL Type 3R Back Plate Instructions
1. Install back plate.
Note! If cabinet is mounted on a soli d surface, bac k plate shipp ed with cabi net is not
required but may still be installed.
2. Install 2 bolts on top and bottom with back plate installed behind cabinet.
Note! If cabinet is mounted on a soli d surface, bac k plate shipp ed with cabi net is not
required, but may still be installed.
Installation