ABB ACS55 Users Manual

ACS55
User's Guide
for type ACS55
AC Drives
from 0.18 to 2.2 kW
English EN Dansk DA Deutsch DE Español ES Suomi FI Français FR Italiano IT Nederlands NL Português PT Русский RU Svenska SV 中文 CN 한국어 KR
Table of contents
English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Dansk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Deutsch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Español . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Suomi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Français . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
Italiano . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
Nederlands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
Português . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
Русский . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189
Svenska . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .209
中文 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .229
3
한국어 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249
3AFE68929300 Rev B EN, DA, DE, ES, FI, FR, IT, NL, PT, RU, SV, CN, KR Effective: 25.02.2008
© 2008 ABB Oy. All Rights reserved.
4
EN 5
User's Guide
for type ACS55
AC Drives
from 0.18 to 2.2 kW
English EN
6 EN
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type code and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives Support and Service network on the right pane.
and selecting Drives – Sales,
Product training
For information on ABB product training, navigate to www.abb.com/drives and select Drives – Training courses on the right pane.
Providing feedback on ABB Drives manuals
Your comments on our manuals are welcome. Go to www.abb.com/drives, then select successively Drives – Document Library – Manuals feedback form (LV AC drives) on the right pane.
3AFE68929300 Rev B EN Effective: 25.02.2008
© 2008 ABB Oy. All Rights reserved.
ABB Oy
AC Drives P.O. Box 184 FI-00381 HELSINKI FINLAND Telephone +358 10 22 11 Fax +358 10 22 22681 Internet www.abb.com
EN 7

8
I
,
8
I
,
$&6($
,3
61<::5;;;;
$)(;;;;;;;;
3QPRWRUN:+3
a9 +]
$
a8
+]
$
5R+6
Safety instructions
Read the following instructions carefully before proceeding with the installation.
Warning! Dangerous voltage!
Only a competent electrician may install ACS55. Never work on the drive, the motor cable or the motor when main
power is applied. After switching off the input power, always wait at least for 5 minutes to let the intermediate circuit capacitors discharge before you start working on the drive.
Warning! If the heat sink is not earthed properly, you can get an electric shock if you touch the heat sink.
Note: DIP switches are at a dangerous voltage. Note: Even when the motor is stopped, dangerous voltages are
present at power circuit terminals L/R, N/S, T1/U, T2/V and T3/W. Note: Even when the unit is powered down, there may be
dangerous external voltages connected from outside to the relay output terminals.
Warning! Hot surfaces!
During operation, the cooling element may reach high temperature (>80°C). Make sure to follow the installation instructions.
General safety instructions
ACS55 starts the motor automatically after a supply break if the external start signal is on.
Altering the DIP switches will affect the function and performance of ACS55. Check that the changes will not cause any risk to persons or property.
About this manual
This guide provides information necessary to install and start-up the unit.
Delivery check
The delivery includes:
1. ACS55
2. User’s guide
3. Two clamps for the control cable (EMC units only).
Check the rating plate and ensure that the delivered device corresponds to the order.
EMC filter: E = Built in, N = No Max. continuous output current (I
):
2
01A4 = 1.4 A, 02A2 = 2.2 A, 04A3 = 4.3 A, 07A6 = 7.6 A, 09A8 = 9.8 A
Supply voltage (U
):
1
1 = 110…120 VAC +10%/-15% 2 = 200…240 VAC +10%/-15%
ACS55-01_-____-_
Never attempt to repair a broken unit. ACS55 is not a field repairable unit. Contact the supplier for replacement.
Install ACS55 in a locked or tool-openable space. Do not connect input power to the unit more than once every three
minutes.
Serial number (S/N) is printed on the rating plate. (Y = manufacturing year, WW = manufacturing week)
8 EN
Overview of the unit
ACS55 drive controls the speed of a 3-phase AC induction motor.
Protective earth (PE), page 17
Input terminals, page 17
Power on LED, page 21
Fault LED, page 21
Analogue input signal selector (voltage/current), page 18
DIP switches, page 14
Control potentiometers, page 16
DriveConfig kit interface, page 24
Relay output terminals, page 18
Control cable terminals, page 18
Motor cable shield, page 17
Motor cable terminals, page 17. Sliding cover provides additional insulation. Slide the cover left to close.
Mounting clip, pages 12 - 13
Clamp plate, page 19 (EMC units only)
EN 9
Installation and start-up steps
Read Safety instructions on page 7 before proceeding.
Action Pg.
1 Check the delivery. 7 2 Ensure that the installation environment is suitable for ACS55. 10 3 Mount the unit. 12 -
13
4 Check applicability of the standard settings: Motor nominal frequency is 50 Hz; load is a pump or a fan; maximum output
frequency is 50 Hz. If the standard settings are not suitable, adjust the DIP switches.
5 Make sure the MOTOR I NOM potentiometer matches the rated current of the motor. It defines operation of the motor
thermal protection function. 6 Adjust the acceleration/deceleration time potentiometer ACC/DEC if necessary. 16 7 Connect the power supply cable and motor cables. 17 8 Connect the control wires. 18 9 Turn the power on. Green LED is illuminated. Note: Motor rotates if the start signal is active. 10 Set the speed reference and activate the start signal. The motor accelerates to the given speed reference. 20
14
16
10 EN
Environmental limits
Installation site Storage and transportation in a protective package
Air temperature -20°C (-4°F), no frost allowed
1)
-40°C (-40°F) to +70°C (158°F)
+40°C (104°F), with nominal load +50°C (122°F), if continuous output current is
max. 85% of the nominal output current I
Altitude 0…2000 m (0...6,600 ft). At altitudes
1000...2000 m (3,300...6,600 ft), P
and I2 are
N
.
2
No limitation
decreased by 1% for every 100 m. Relative humidity Less than 95%, non-condensing Less than 95%, non-condensing Contamination
levels (IEC 60721-3-3)
• No conductive dust allowed
• Air must be clean, free from corrosive materials and conductive dust
• Chemical gases: Class 3C2
Storage Transportation
• No conductive dust allowed
• Chemical gases: Class 1C2
• Solid particles: Class 1S2
• Solid particles: Class 3S2
Sinusoidal vibration
Frequency range: 5...150 Hz Constant peak acceleration: 1 g
In accordance with ISTA 1A specification
(IEC 60068-2-6)
• No conductive dust allowed
• Chemical gases: Class 2C2
• Solid particles: Class 2S2
Shock
Not allowed Max. 100 m/s
2
(330 ft/s2), 11 ms (36 fts)
(IEC 60068-2-29) Free fall Not allowed Not allowed
1) When operating the drive in subzero temperatures, keep the input power connected. Install the drive inside an enclosure. Ensure that heat generated by the drive will be properly dissipated.
Degree of protection of ACS55 is IP20.
EN 11
Dimensions
Frame
f
e
A mm (in.)
a b
c d
a53
(2.09)72(2.83)74(2.91)74(2.91)
b45
(1.77)
c128
(5.04)
d67.5
(2.66)
Frame
B mm (in.)
Frame
C mm (in.)
Frame
D mm (in.)
67.5
(2.66)70(2.76)70(2.76)
128
(5.04)
67.5
159
(6.26)
159
(6.26)
--
(2.66)
e- - 77
i
h
j
k
(3.03)77(3.03)
f- - 40
(1.57)40(1.57)
g- - 40
(1.57)40(1.57)
h183
(7.20)
i156
(6.14)
j170
(6.69)
g
k146.5
(5.77)
183
(7.20)
156
(6.14)
170
(6.69)
146.5
(5.77)
- 230
182
(7.17)
194
(7.64)
171
(6.73)
(9.06)
214
(8.43)
226
(8.90)
203
(7.99)
12 EN
Mounting
Warning! The unit will warm up to high temperature during normal operation. Ensure sufficient cooling air flow in all conditions:
- Always install ACS55 so that cooling fans are vertical.
- Leave sufficient space around frame A and B units. Frame C and D units are fan cooled, so they can be installed side by side without extra space between them.
Install the unit using the mounting clip on a 35 mm DIN rail or on a wall.
Mounting on DIN rail
"Click" ACS55 to the rail. Press the lever on top of the mounting clip to detach.
Mounting on wall
Install the unit onto the wall through the mounting clip. Use M4 screws.
Clearance distances
Always leave sufficient space around the unit to ensure proper cooling.
5 cm
(2 in.)
5 cm
(2 in.)
X
5 cm
(2 in.)
5 cm
(2 in.)
X
X
Frames
A and B
cm (in.)
X 1.5 (0.6) 0 (0)
Frames
C and D
cm (in.)
EN 13
Attaching and detaching the wall mounting clip
The unit can be mounted either with the wide or the narrow side against the wall. Install the mounting clip on the desired side. See instructions below for frames A and B. Detach the mounting clip of frames C and D by pulling downward and attach it by pushing upward.
Detaching the mounting clip, Frames A and B: Press the two plastic buttons to
detach the upper and lower part of the clip from each other.
Attaching the mounting clip, Frame A: Place the two parts as shown and click them together.
Attaching the mounting clip, Frame B:
Push the two parts between the cooling fins and click them together.
14 EN
DIP switches
DIP switches are used to adapt ACS55 to the motor and the application.
Warning! The DIP switch is at a dangerous voltage (200 V). Turn off power and wait for 5 minutes before adjusting the switches. Keep the protective cover closed when ACS55 is powered.
Configuration
• Open the front cover using the tip of a screwdriver, and adjust the DIP switches.
• Use the tip of a screwdriver to slide the switch to the left or right. By default, all switches are in their left position.
• Close the front cover.
Basic information
DIP switch
# Name and function Default
setting
1 NOM FREQ HZ: Motor nominal frequency 50 Hz 60 Hz 2 SILENT: Motor noise level (PWM switching
frequency) 3 LOAD: Load torque type (U/f curve) P&F - Pump/fan CT - Constant torque 4 JOG HZ: Constant frequency for the jogging function 5 Hz 10 Hz 5 RELAY: Relay output operation FLT - Fault RUN - Motor running 6 AI OFFSET: Minimum value for analogue input OFF - 0 mA (0 V) ON - 4 mA (2 V) 7 AUTORESET: Automatic fault reset function OFF - No autoreset ON - Autoreset enabled 8 HI FREQ: High frequency mode OFF - Standard ON - High frequency
OFF - Normal (5 kHz)
Alternative setting
ON - Silent (16 kHz)
enabled
EN 15
Additional information
No. Name Information
1NOM
FREQ Hz
2 SILENT Defines the drive switching frequency. Note: The higher the frequency the more electromagnetic
Defines the motor nominal frequency (see the motor rating plate).
noise and the shorter the allowed motor cable length to comply with the European EMC
U
U
N
CT
regulations. See Technical data on page 22. Note: The switching frequency adapts to the ACS55 temperature.
3 LOAD Optimises the output voltage and frequency characteristics according to the load. Select P&F for
10%
the squared torque (e.g. pumps and fans) and CT for the constant torque loads (e.g. conveyors).
P&F
f
N
ACS55 automatically boosts the starting voltage 10% to compensate the motor losses and to increase the starting torque.
4 JOG Hz Defines the jogging frequency. Activate the jogging function on by connecting 12…24 VDC to digital input 3 ("JOG").
(Drive accelerates or decelerates to the jogging frequency, and keeps it until the input is switched off.)
5 RELAY Selects the drive state the normally open contact of the relay output indicates. FLT = Fault. Contact is opened while
at a fault state or at a power off state. RUN = Running. Contact is closed while running.
6AI
OFFSET
Activates a living zero supervision for the analogue input. 4 mA (2 V) = ACS55 trips on a fault if the value drops below the limit. See section Speed controlling on page 20 for information on analogue input scaling.
f
7AUTO-
RESET
Activates the automatic reset function for the following faults: Undervoltage, overvoltage, analogue input loss. ON = ACS55 will try to reset automatically three seconds after a fault trip. Maximum number of resets is ten in three minutes. If exceeded, ACS55 stops and will not attempt a new reset. See also Status indications and fault tracing on page 21. Warning! If the start signal is on, the motor will be started after a reset. Make sure that this will not cause danger.
8 HI FREQ Defines the maximum output frequency. OFF: Max. frequency = value defined by the NOM FREQ HZ switch. ON:
Max. frequency = value defined by the NOM FREQ HZ switch + value of HI FREQ potentiometer. See Control
potentiometers on page 16.
16 EN
Control potentiometers
The control potentiometers can be adjusted using a screwdriver. By default, all potentiometers are in their middle position.
MOTOR I NOM
Calculate MOTOR I NOM with the equation below or pick a value from the MOTOR I NOM selection chart below. ACS55 estimates the temperature of the motor based on the measured output current and the defined motor nominal current. The drive trips if the estimated temperature implies motor overheating. Note: If motor cables are long causing large capacitive currents, it might be necessary to increase the MOTOR I NOM setting.
MOTOR I NOM (%) =
Motor nominal current [A]
ACS55 nominal current [A]
• 100%
ACC/DEC Defines the acceleration and deceleration time from minimum to maximum frequency and vice versa in
seconds. The longer the ACC/DEC time, the more slowly ACS55 will follow the given reference.
HI FREQ Limits the output frequency to a desired value between nominal frequency and nominal frequency + 70 Hz.
To use this potentiometer, turn the high frequency mode on with the HI FREQ DIP switch. See DIP switches on page 14.
MOTOR I NOM selection chart
ACC/DEC time
ACS55-01x-
-01A4-x
-02A2-x
-04A3-x
-07A6-x
-09A8-x
MOTOR I NOM
Motor nominal current (A)
0,7 0,8 1,0 1,2
1,11,31,51,82,0
2,2 2,6 3,0 3,5 4,0
3,84,65,36,16,8
4,95,96,97,88,8
50 60 70 80 90
1,4
2,2
4,3
7,6
9,8
100
1,6 1,8 2,0 2,1
2,4 2,6 2,8 3,0 3,3
4,7 5,2 5,6 6,0 6,5
8,4 9,3 10,2 11,4
10,8 12,0 13,3 14,7
110 120 130 140 150%
Ref. [%]
100
t
ACC/DEC
EN 17
Connecting power supply and motor
1-phase
input voltage
Warning! Before installation ensure that the main supply is off.
Note: Ensure power supply is correct! Connecting 230 VAC to the ACS55 unit rated for 115 VAC input will damage
the drive!
Terminal Description Wire size Tightening
torque
L/R, N/S 1~ power supply input Max. 2.5 mm
2
T1/U, T2/V, T3/W Power output to motor
4mm
(frames C and D) single core copper
2
(frames A and B) or max.
0.5 Nm /
0.6 Nm
wire
PE Protective earth.
Motor cable protective conductor and shield.
Use multi-strand copper wire. Size of the wire is not allowed to be smaller than the size of the power cable used.
1 Nm(*)
Warning! If the heat sink is not earthed properly, you can get an electric shock if you touch the heat sink.
Note: Use only supplied M4x8 Combi screws. Maximum allowed intrusion depth for the grounding screws is 6mm.
Follow local rules for cable cross sections. Use 60°C (140°F) rated power cable, or 75°C (167°F) rated cable if ambient temperature is above 30°C (86°F). See also Additional cabling and EMC instructions on page 19.
Earth leakage current of the ACS55 can exceed 3.5 mA AC / 10 mA DC. According to EN50178, ACS55 may only be used in permanent installation.
Input fuse
See Technical data on page 22 for recommended fuse types.
Motor
The motor must be a 3-phase AC induction motor, with nominal voltage U frequency f
either 50 or 60 Hz. Motor nominal current must be less than or equal to the nominal output current (I2)
N
from 200 to 240 V and nominal
N
of the drive. If the phases are connected, U-U, V-V and W-W, and the selected direction is forward, the shaft rotates clockwise
as seen from the drive shaft end.
18 EN
Connecting control wires
Internal (1) or external (2) power supply can be used for the digital inputs. Analogue control voltage is 0…10 VDC as default. (The AI jumper must be in voltage ("U") position).
+10V
1)
+12V
2)
COM
COM
SPEED/AI
START
+-
12...24 VDC supply
REV
SCR
JOG
COM
SPEED/AI
COM
+10V
1...10 kohm
START
+12V
REV
JOG
SCR
I
AI
U
Control terminals
2
Use multi-strand 0.5...1.5 mm
wire (AWG22 - AWG16).
# Name Description
1 COM Common for digital or analogue inputs 2 COM Common for digital or analogue input
1)
1)
3 AI Analogue input: Speed (frequency) reference.
0/2…10 VDC (Ri=190 kohm), or 0/4…20 mA (Ri=100 ohm). Resolution 0.1%, accuracy +/-1%.
4 +10V Reference voltage for analogue input.
Accuracy +/-2%. Max. 10 mA. 5 +12V Auxiliary voltage for digital inputs. Max. 30 mA. 6 START Digital input 1: Start (resets the drive after a fault
2)
trip) 7 REV Digital input 2: Reverse rotation direction 8 JOG Digital input 3: Activate jog speed
2)
2)
Using 0/4…20 mA current signal:
- Change AI jumper to current ("I") position.
- Set AI OFFSET switch to ON position if 4…20 mA current signal is desired.
U
9 SCR Earth for signal cable screen. Connected internally
COM
+-
COM SPEED/AI +10V
Relay output 1 RO1 Fault: Relay opens.12 V...250 VAC / 30 VDC
+12V
I
AI
START REV JOG
2RO2
1) Connected internally to frame (earth) through 1 Mohm resistor.
2) Digital input impedance is 1.5 kohm.
to frame earth.
10 mA...2 A
SCR
EN 19
Additional cabling and EMC instructions
Follow these instructions for trouble free operation and to ensure compatibility with the European EMC directive.
Motor cable
The motor cable must be a symmetrical three conductor cable with a concentric PE conductor or a four conductor cable with a concentric shield. Braided metallic screen is recommended, e.g. type MCCMK (NK Cables).
- Twist the cable screen wires together into a bundle, and connect to the earthing terminal . Keep the bundle as short as possible.
- Clamp the cable screen as shown in the figure when internal or external EMC filter is used.
- At the motor end the motor cable screens must be earthed 360 degrees with an EMC cable gland or the screen wires must be twisted together into a bundle not longer than 5 times its width and connected to the PE terminal of the motor.
Control cables
Control cables must be multi-core cables with a braided copper wire screen. A double shielded twisted pair cable is recommended for the analogue signals.
- Twist the screen together into a bundle and connect to terminal SCR. Keep the bundle as short as possible.
- Clamp the control cable as shown in the figure (EMC units only).
- Route the motor cable away from the control wires and the power supply cable to avoid electromagnetic interference (distance > 20 cm).
Note: Never mix 24 VDC and 115/230 VAC signals in the same cable.
control cable
motor cable
clamps
20 EN
Speed controlling
The analogue input gives the speed (frequency) reference for ACS55. The correspondence between the analogue input and the reference depends on the settings of the DIP switches as shown below. Output frequency follows the reference changes as defined by the ACC/DEC potentiometer.
High frequency mode OFF (default) High frequency mode ON
f
f
N
a
b
Input*
0
2 V
4 mA
10 V
20 mA
[V, mA]
DIP switch settings: HI FREQ = OFF AI OFFSET = OFF (curve a) or ON** (curve b) MOTOR NOM FREQ = 50 or 60 Hz
The output frequency is limited to the selected nominal frequency of the motor.
+ 70 Hz
f
N
f
f
N
frequency reference
output frequency limit
a
b
0
2 V
4 mA
10 V
20 mA
Input*
[V, mA]
DIP switch settings: HI FREQ = ON AI OFFSET = OFF (curve a) or ON** (curve b) MOTOR NOM FREQ = 50 or 60 Hz
Actual output frequency is limited to a value between f
and fN + 70 Hz by the
N
HI FREQ potentiometer. The potentiometer does not affect the scaling of the analogue input.
* Use AI jumper to select voltage or current signal. See page 18. ** To protect the drive against analogue input signal loss, the drive trips if the signal value is below 2 V (4 mA).
EN 21
Status indications and fault tracing
ACS55 has two status indication LEDs, visible through the front cover.
Green LED Red LED Description
On Off ACS55 operates normally.
If the drive detects a problem, the red LED will blink. After fixing the problem, reset by switching the start signal off. If start is off already, turn it first on and then off again.
See the table below for the fault codes (= the number of LED blinks).
On Blinking Protective function has been activated. Number of
On
Off
12
Blinking Blinking
blinks indicates the fault code.
ACS55 will reset automatically within 3 seconds. (*)
Warning! Motor starts, if start signal is on.
# Possible causes and what to do # Possible causes and what to do
1 DC overvoltage (*). 1) Mains voltage is too high: Check
supply. 2) Deceleration ramp time is too short compared to
6 Analogue input value is less than 4 mA/2 V. (*) Note: This
supervision is active if AI OFFSET is ON.
the load inertia: Increase ACC/DEC time with potentiometer.
2 DC undervoltage (*). Mains voltage is too low: Check supply. 7 Motor overload (I
2
t overload): 1) Check the load, and verify that the motor size is suitable for ACS55. 2) Verify that setting of MOTOR I NOM potentiometer is correct.
3 Output short circuit: Switch off the power and check the motor
windings and motor cable.
8 Inverter overload or excessive internal temperature: 1) Load
is too high or 2) drive cooling is insufficient.
4 Output overcurrent. 1) Acceleration time is too short
compared to the load inertia: Increase ACC/DEC time with
9 Other fault. Internal error. Turn power off and on again. If
problem persists, replace the unit.
potentiometer. 2) Motor and drive sizes do not match: Check motor.
5 Reserved 10 Parametrization fault. Note: Both LEDs will blink. DIP
switches have been moved from default setting after the drive has been parametrized with DriveConfig tool. Put the switches back to default position.
(*) Automatically reset if the AUTORESET is ON. See DIP switches on page 14.
22 EN
Technical data
230 V 115 V Built-in EMC, ACS55-01E- 01A4-2 02A2-2 04A3-2 07A6-2 09A8-2 01A4-1 02A2-1 No EMC, ACS55-01N- 01A4-2 02A2-2 04A3-2 07A6-2 09A8-2 01A4-1 02A2-1
Motor continuous output power kW 0.18 0.37 0.75 1.5 2.2 0.18 0.37
hp 1/4 1/2 1 2 3 1/4 1/2 Frame size (no EMC) A A B C C A A Frame size (EMC) A A B D D A A
Nominal ratings
Input voltage U
1
Continuous output current I Max. output current I Output voltage U Input current I
2
1
* A 2.1 3.3 6.5 11.4 14.7 2.1 3.3
2max
2
V 200-240 (+10/-15%) 110-120 (+10/-15%) A 1.42.24.37.69.81.42.2
V0-U1, 3-phase 0-2xU1, 3-phase A 4.4 6.9 10.8 18.2 22.0 6.4 9.5
Switching frequency kHz 5 (max. 16)
Protection limits
Overcurrent (peak) A 4.4 6.9 13.5 23.9 30.9 4.4 6.9 Overtemperature 95°C / 203°F (heat sink)
Maximum wire sizes
Power terminals mm2 2.5 (AWG 14) 4 (AWG 12) 2.5 (AWG 14) Control terminals mm2 1.5 (AWG 16)
Power losses W 21 32 51 74 103 24 35 Line fuse size**
IEC, type IEC269 gG A 10 16 16 25 32 10 16 UL, types CC and T A 10 15 20 25 30 10 15
* Allowed for 1 minute. ** Recommended values. Do not use ultra rapid or low peak fuses. Follow local rules.
EN 23
Maximum motor cable lengths
To comply with European EMC regulations, the motor cable length has to be limited as specified in the table below. The shorter the motor cable, the lower the noise emissions to the supply line and the environment.
Built-in EMC filter External EMC filter ACS55-01E- ACS55-IFAB-01 and
ACS55-01N/E
Converter type 5 kHz 16 kHz
1)
5 kHz 16 kHz
EN61800-3, First environment, unrestricted distribution
2)
1)
01A4-2, …, 02A2-1 10 m 3 m - ­07A6-2, …, 09A8-2 10 m 3 m - -
EN61800-3, First environment, restricted distribution
3)
01A4-2, …, 02A2-1 10 m 10 m 30 m 10 m 07A6-2, …, 09A8-2 20 m 10 m - -
EN61800-3, Second environment
3)
01A4-2, …, 02A2-2 10 m 10 m 50 m 10 m 04A3-2 10 m 10 m 75 m 10 m 01A4-1, …, 02A2-1 10 m 10 m 50 m 10 m 07A6-2, …, 09A8-2 30 m 10 m - -
1) Switching frequency can be selected with the DIP switch. See page 15.
2) Applicable for conducted emissions only.
3) Applicable for conducted and radiated emissions.
Protections
Overvoltage, undervoltage, output short circuit, overcurrent, analogue input loss, motor overload, inverter overload.
Distribution networks isolated from earth
Drives with built-in EMC filter, or ACS55-IFAB-01 external input filter must not be used in a floating network or in a high impedance earthed industrial distribution network.
Environmental information
A product to be disposed contains valuable raw material that should be recycled, thus preserving energy and natural resources. Instructions for disposal are available from ABB sales and service companies.
Liability limits
The manufacturer is not responsible for:
• Any costs resulting from a failure if the installation, commissioning, repair, alteration or ambient conditions of the drive do not fulfil the requirements specified in the documentation delivered with the unit and other relevant documentation.
• Units subjected to misuse, negligence or accident.
• Units comprised of materials provided or designs stipulated by the purchaser.
In no event shall the manufacturer, its suppliers or subcontractors be liable for special, indirect, incidental or consequential damages, losses or penalties.
If you have any question concerning your ABB drive, please contact the local distributor or ABB office. The technical data, information and specifications are valid at the time of printing. The manufacturer reserves the right to modifications without prior notice.
24 EN
Approvals
CE
The ACS55 complies with the requirements of the European
• Low Voltage Directive 73/23/EEC with amendments
• EMC Directive 89/336/EEC with amendments. Corresponding declarations and a list of main standards are available on request.
Electromagnetic compatibility:
The ACS55 fulfils the following standards provided that installation is done properly and according to the instructions of this manual:
Conductive high frequency emissions
Radiated high frequency emissions
Immunity EN61800-3 second environment Line current harmonics IEC61000-3-2
1) Observe the maximum allowed motor cable lengths and switching frequency, page 23. See also cabling instructions on page 19.
EN61800-3 first environment, unrestricted/restricted distribution
EN61800-3 first environment, restricted distribution
1)
UL, cUL:
The ACS55 is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical amperes, 230 volts maximum, when protected by CC or T class fuses.
C-Tick:
For the electromagnetic compatibility, see the specification in section CE above.
Product protection in the USA
This product is protected by one or more of the following US patents
4,920,306 5,301,085 5,463,302 5,521,483 5,532,568 5,589,754 5,612,604 5,654,624 5,799,805 5,940,286 5,942,874 5,952,613 6,094,364 6,147,887 6,175,256 6,184,740 6,195,274 6,229,356 6,252,436 6,265,724 6,305,464 6,313,599 6,316,896 6,335,607 6,370,049 6,396,236 6,448,735 6,498,452 6,552,510 6,597,148 6,741,059 6,774,758 6,844,794 6,856,502 6,859,374 6,922,883 6,940,253 6,934,169 6,956,352 6,958,923 6,967,453 6,972,976 6,977,449 6,984,958 6,985,371 6,992,908 6,999,329 7,023,160 7,034,510 7,036,223 7,045,987 7,057,908 7,059,390 7,067,997 7,082,374 7,084,604 7,098,623 7,102,325 D503,931 D510,319 D510,320 D511,137 D511,150 D512,026 D512,696 D521,466
Other patents pending.
The current harmonic levels can be reduced by fitting external input chokes.
UL, cUL and C-Tick markings
See the rating plate.
Accessories
EMC filter: ACS50-IFAB-01 Input chokes: CHK-A1, CHK-B1, CHK-C1, CHK-D1 Output choke: ACS-CHK-B3, ACS-CHK-C3 Potentiometer unit: ACS50-POT DriveConfig kit, for more information please contact your local ABB
office.
DA 25
Brugermanual
for type ACS55
AC drev
fra 0,18 til 2,2 kW
Dansk DA
26 DA
Produkt- og serviceforespørgsler
Har De spørgsmål om produktet, beder vi Dem henvende Dem til Deres lokale ABB selskab. Vi beder Dem venligst oplyse typekode og serienummer på det drev, det drejer sig om. På ABBs hjemmeside findes en oversigt over salgs-, support- og servicekontakter. Gå ind på www.abb.com/drives
network
Produkttræning
i det højre felt.
og vælg Drives – Sales, Support and Service
Oplysninger om ABBs produkttræning findes på www.abb.com/drives. Vælg herefter Drives – Training courses i det højre felt.
Feedback vedr. ABB drevmanualer
Vi er meget interesseret i at modtage Deres eventuelle kommentarer til vore manualer. Gå ind på www.abb.com/
drives. Herefter vælges DrivesDocument LibraryManuals feedback form (LV AC drives) i det højre felt.
3AFE68929300 Rev B DA Gældende fra: 25.02.2008
© 2008 ABB Oy. All Rights reserved.
ABB A/S
Meterbuen 33 DK-2740 Skovlunde Tlf: 45 44 50 44 50 Fax: 45 44 50 43 65 Internet www.abb.com
DA 27

8
I
,
8
I
,
$&6($
,3
61<::5;;;;
$)(;;;;;;;;
3QPRWRUN:+3
a9 +]
$
a8
+]
$
5R+6
Sikkerhedsinstruktioner
Læs omhyggeligt nedenstående instruktioner, inden installationen påbegyndes.
Advarsel! Farlig spænding!
Kun en uddannet elektriker må installere ACS55. Der må aldrig arbejdes med drevet, motorkablet eller motoren, når
netspændingen er indkoblet. Efter at have udkoblet netspændingen, skal man vente mindst 5 minutter for at lade mellemkredskondensatorerne aflade, inden arbejdet med drevet påbegyndes.
Advarsel! Hvis kølepladen ikke er jordet rigtigt, kan man få stød,
hvis man rører kølepladen.
Bemærk: DIP switches har farlig spænding. Bemærk: Selv når motoren er standset, er der farlig spænding ved
effektklemmerne L/R, N/S, T1/U, T2/V og T3/W.
Bemærk: Selv når enheden ikke er tilsluttet netspændingen, kan
der være farlige, eksterne spændinger forbundet til relæudgangsklemmerne.
Tilslut ikke netspænding til enheden mere end én gang hvert tredje minut.
En ændring af DIP switchene vil have indflydelse på ACS55's funktion og ydelse. Undersøg at ændringerne ikke vil kunne forårsage skader på personer eller ejendom.
Om denne manual
Denne guide giver de nødvendige informationer om installation og opstart af enheden.
Kontrol ved levering
Leverancen indeholder
1. ACS55
2. Brugermanual
2. To bøjler for styrepanelet (kun EMC
omformere) Kontroller mærkepladen og vær sikker på, at den
leverede enhed svarer til ordren.
Advarsel! Varme overflader!
Under driften kan køleelementet nå en høj temperatur (>80 °C). Vær sikker på, at installationsinstruktionerne overholdes.
Generelle sikkerhedsinstruktioner
ACS55 starter automatisk motoren efter en netafbrydelse, hvis det eksterne startsignal er aktivt.
Forsøg aldrig at reparere en enhed, der er ødelagt. ACS55 er ikke en enhed, der kan repareres på montagestedet. Tag kontakt til leverandøren for at få en erstatningsenhed.
Installer ACS55 et sted, hvor den kan stå aflåst, eller kun er tilgængelig ved brug af værktøj.
ACS55-01_-____-_
EMC filter: E = Indbygget, N = Nej Max. kontinuerlig udgangsstrøm (I2):
01A4 = 1,4 A, 02A2 = 2,2 A, 04A3 = 4,3 A 07A6 = 7,6 A, 09A8 = 9,8 A
Netspænding (U1):
1 = 110…120 VAC +10%/-15% 2 = 200…240 VAC +10%/-15%
Serienummer (S/N) er trykt på mærkepladen. (Y = Fremstillingsår, WW = fremstillingsuge)
28 DA
Oversigt
ACS55 drevet styrer en 3-faset asynkronsmotors hastighed.
Indgangsterminaler, side
37
Net LED, side 41
Fejl LED, side 41
Beskyttelsesjord (PE), side
DIP switches, side 34
Styrepotentiometre, side 36
DriveConfig kit interface, side 44
Relæudgangsterminaler, side 38
Styrekabelterminaler, side 38
Motorkabelskærm, side
37
37
Valg af analog inputsignal (spænding/strøm), side
Monteringsflap, side 32 - 33
38
Motorkabelterminaler, side 37. Dækslet giv­er ekstra isoaltion. Skub dækslet mod ven­stre for at lukke.
Bøjleplade, side 39 (Kun EMC omformere)
DA 29
Installation og opstart
Læs Sikkerhedsinstruktioner på side 27, inden der fortsættes.
Handling Side
1 Check leverancen. 27 2 Vær sikker på, at installationsmiljøet er egnet for ACS55. 30 3 Monter omformeren. 32 -
33
4 Check standardinstillingerne: Motorens nominelle frekvens er 50 Hz; belastningen er en pumpe eller en ventilator; den
maksimale udgangsfrekvens er 50 Hz. Hvis standardindstillingerne ikke passer, reguleres DIP-switchene.
5 Vær sikker på, at MOTOR I NOM potentiometeret passer til motorens mærkestrøm. Det definerer virkning af motorens
termiske beskyttelsesfunktion. 6 Tilpas om nødvendigt accelerations-/decelerationstidspotentiometeret ACC/DEC. 36 7 Tilslut net- og motorkabler. 37 8 Tilslut styrekablerne. 38 9 Tilslut indgangsspændingen. Grøn LED tænder. Bemærk: Motoren roterer, hvis startsignalet er aktivt. 10 Indstil hastighedsreferencen og aktiver startsignalet. Motoren accelererer op til den valgte hastighedsreference.
34
36
40
30 DA
Omgivelsesbetingelser
Montagested Lagring og transport i beskyttelsesemballage
Lufttemperatur -20 °C (-4 °F), frost ikke tilladt 1)
+40 °C (104 °F), ved nominel last +50 °C (122 °F), hvis kontinuerlig
udgangsstøm er max. 85% af nominel udgangsstrøm
I
.
2
Højde over havet 0…2000 m (0...6,600 ft). Ved højder mellem
1000...2000 m (3,300...6,600 ft), reduceres
P
og I2 med 1% for hver 100 m.
N
Relativ
Mindre end 95%, kondens ikke tilladt Mindre end 95%, kondens ikke tilladt
luftfugtighed Forurenings-
niveau (IEC 60721-3-3)
• Ledende støv ikke tilladt
• Luften skal være ren og fri for korroderende materialer og ledende støv.
• Kemiske gasser: Klasse 3C2
• Faste partikler: Klasse 3S2
Sinusformet vibration
Frekvensområde: 5...150 Hz Konstant acceleration: 1 g
(IEC 60068-2-29)
-40 °C (-40 °F) til +70 °C (158 °F)
Ingen begrænsning
Lagring Transport
• Ledende støv ikke tilladt
• Kemiske gasser: Klasse 1C2
• Faste partikler: Klasse 1S2
• Ledende støv ikke tilladt
• Kemiske gasser: Klasse 2C2
• Faste partikler: Klasse 2S2
I henhold til ISTA 1A specifikationer
Chok
Ikke tilladt Max. 100 m/s
2
(330 ft/s2), 11 ms (36 fts)
(IEC 60068-2-29) Frit fald: Ikke tilladt Ikke tilladt
1) Når drevet benyttes ved minustemperaturer, skal drevet fortsat være tilsluttet spændingen. Monter drevet indvendig i en ekstra kapsling. Det skal sikres, at varmen, som genereres af drevet, kan bortskaffes.
Beskyttelsesgraden for ACS55 er IP20.
Loading...
+ 240 hidden pages