Figure 5 - SB Series Supply Fan ................................................................................................... 28
Figure 6 - ECM with Factory Provided Controls.......................................................................... 29
Figure 7 - ECM with Potentiometer Control ................................................................................ 29
Figure 8 - ECM with Field Installed Controls .............................................................................. 30
V14190 · Rev. A · 121227
(ACP 31227)
4
Attention should be paid to the following statements:
ELECTRIC SHOCK, FIRE OR
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
Improper servicing could result in
Before servicing, disconnect all
than one disconnect may be
wires prior to disconnecting.
Verify proper operation after
Electric shock hazard. Before
servicing, disconnect all electrical
FIRE, EXPLOSION OR CARBON
Failure to replace proper controls
could result in fire, explosion or
to follow safety warnings exactly
and liquids in the vicinity of this
Safety
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
EXPLOSION HAZARD
property damage.
dangerous operation, serious injury,
death or property damage.
electrical power to the unit. More
provided.
When servicing controls, label all
Reconnect wires correctly.
servicing. Secure all doors with
key-lock or nut and bolt.
power to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
MONOXIDE POISONING HAZARD
carbon monoxide poisoning. Failure
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
appliance.
5
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
WARNING
electrical components. Only a
qualified licensed electrician or
electrical components shall
70E, an OSHA
regulation requiring an Arc Flash
marked for identification of where
appropriate Personal Protective
To prevent injury or death lifting
power to the unit has been
disconnected and fan wheel has
During installation, testing, servicing
and troubleshooting of the equipment
it may be necessary to work with live
individual properly trained in handling
live
perform these tasks.
Standard NFPA-
Boundary to be field established and
Equipment (PPE) be worn, should be
followed.
GROUNDING REQUIRED
electrical code requirements. Failure
requirements.
6
UNIT HANDLING
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
ROTATING COMPONENTS
Unit contains fans with moving parts
that can cause serious injury. Do not
open door containing fans until the
stopped rotating.
Failure to properly drain and vent
coils when not in use during freezing
temperature may result in coil and
equipment damage.
Prior to connection of condensing
or death due to instantaneous
not use alkaline chemical coil
WARNING
CAUTION
in place of refrigerant and dry
Always use a pressure regulator,
ges to control
A sufficient quantity of
on all
should be checked for proper
Rotation must be checked
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
operation. Alterations should only be
made at the unit power connection
WATER PRESSURE
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
release of high pressure water, relief
valves should be field supplied on
system water piping.
Do not use oxygen, acetylene or air
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
valves and gau
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
Do not work in a closed area where
refrigerant or nitrogen gases may be
leaking.
vapors may be present and cause
injury or death.
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
7
Some chemical coil cleaning
Failure to follow
Door compartments containing
h door latches to
cooling tower or the
condenser water loop with harsh
(muriatic acid) or chlorine, can
Care should be taken to avoid
allowing chemicals to enter the
cooled condenser. See
Heat Exchanger
Corrosion Resistance for more
of chemical corrosion is excluded
Failure of the condenser due to
refrigerant circuit and will cause
from coverage under AAON
manufacturer warranties.
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
410A and other
and complete piping
system failure.
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions.
instructions may result in equipment
damage, injury or death.
hazardous voltage or rotating parts
are equipped wit
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
Cleaning the
chemicals, such as hydrochloric acid
damage the water-cooled condenser.
waterAppendix A -
information.
8
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer’s warranties.
WATER FREEZING
freezing will allow water to enter the
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
warranties and the heat exchanger
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
used with Rrefrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings
To prevent motor overheating
compressors must cycle off for a
To maintain the proper oil level
compressors must cycle on for a
starts per hour.
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
minimum of 5 minutes.
The cycle rate must not exceed 6
1. The unit is for indoor use only. See
General Information section for more
unit information.
2. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
3. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
4. Keep this manual and all literature
safeguarded near or on the unit.
9
Series and
Generation
Unit
Size
Configuration/Interior
Protection
Model Number
SB Base Model Description
SB
BASE MODEL
SERIES AND GENERATION
SB
UNIT SIZE
003 = 3 ton Capacity
004 = 4 ton Capacity
005 = 5 ton Capacity
006 = 6 ton Capacity
007 = 7 ton Capacity
009 = 9 ton Capacity
010 =10 ton Capacity
014 =14 ton Capacity
016 = 16 ton Capacity
018 = 18 ton Capacity
0 = Standard
1 = Polymer E-Coated Cooling Coil
D = Stainless Steel Cooling Coil Casing
A4: COOLING/HEAT PUMP STAGING
9 = Modulating - Variable Capacity Compressor
10
Model/Feature Number
SB Base Model and Features Description
0 0 0
:
B1 B2 B3 1A 1B 1C 1D 2 3 4
Model Option B: HEATING
B1: HEATING TYPE
0 = No Heating
3 = Electric Heat
C = Steam Distributing Standard Coil
D = Steam Distributing Polymer E-Coated Coil
E = Hot Water Standard Coil
F = Hot Water Polymer E-Coated Coil
B2: HEATING DESIGNATION
0 = No Heating
1 = 1 Row Coil
2 = 2 Row Coil
A = 7 kW (5.3 kW @ 208V)
B = 14 kW (10.5 kW @ 208V)
C = 21 kW (15.8 kW @ 208V)
D = 28 kW (21.0 kW @ 208V)
E = 35 kW (26.3 kW @ 208V)
F = 42 kW (31.5 kW @ 208V)
G = 49 kW (37.0 kW @ 208V)
H = 56 kW (42.0 kW @ 208V)
J = 63 kW (47.3 kW @ 208V)
K = 70 kW (52.5 kW @ 208V)
B3: HEATING STAGING
0 = No Heating
1 = 1 Stage
2 = 2 Stage
3 = 3 Stage
4 = 4 Stage
9 = Modulating/SCR Electric - Potentiometer Control
A = Modulating/SCR Electric - 0-10VDC Control
Signal
H = Single Serpentine 8 fpi
J = Half Serpentine 8 fpi
K = Single Serpentine 10 fpi
L = Half Serpentine 10 fpi
M = Single Serpentine 12 fpi
N = Half Serpentine 12 fpi
0 0 0 0
Feature 1: RETURN/OUTSIDE AIR
1A: RETURN/OUTSIDE AIR SECTION
0 = Standard
1 = Mixing Box - Front and Front Openings
2 = Mixing Box - Top and Front Openings
3 = Mixing Box - Front and Right Openings
4 = Mixing Box - Front and Left Openings
5 = Mixing Box - Top and Right Openings
6 = Mixing Box - Top and Left Openings
1B: BLANK
0 = Standard
1C: FILTER LOCATION
0 = Standard
A = Mixing Box Filters
1D: MIXING BOX DAMPER CONTROL
0 = Standard - None
A = 2 Position Actuators (24V)
B = Fully Modulating Actuators (DDC)
C = Fixed Position Dampers
Feature 2: WATERSIDE
ECONOMIZER
0 = Standard - None
A = Waterside Economizer - 4 Row Single
Serpentine 12 FPI Coil
B = Waterside Economizer - 6 Row Single
Serpentine 12 FPI Coil
Feature 3: BLANK
0 = Standard
Feature 4: MAINTENANCE OPTIONS
0 = Standard
A = Blower Aux. Contact - Low Voltage Terminal
Block
B = Remote Start/Stop Terminals - Low Voltage
Terminal Block
C = Options A + B
-
0 0 0
-
11
Feature Number
SB Features Description
A B C
-
5A 5B 5C 6A 6B 6C 7 8 9 10 11 12
Feature 5: SUPPLY AIR OPTIONS
5A: SUPPLY AIR BLOWER CONFIGURATION
0 = No Airside - Condensing Unit Only
A = 1 Blower + High Efficiency EC Motor
B = 2 Blowers + High Efficiency EC Motors
5B: SUPPLY AIR BLOWER
0 = No Airside - Condensing Unit Only
A = 310 mm (14”) Direct Drive Backward Curved
Plenum Fan
B = 355 mm (16”) Direct Drive Backward Curved
Plenum Fan
C = 450 mm (18”) Direct Drive Backward Curved
Plenum Fan
5C: SUPPLY AIR BLOWER MOTOR
0 = No Airside - Condensing Unit Only
C = 1.7 kW (2.3 hp)
D = 3.0 kW (4.0 hp)
E = 6.0 kW (8.0 hp)
Feature 6: FILTERS
6A: PRE FILTER TYPE
0 = No Pre Filter
A = 2” Pleated - 30% Eff. - MERV 8
6B: UNIT FILTER TYPE
0 = No Unit Filter
A = 2” Pleated - 30% Eff. - MERV 8
B = 4” Pleated - 30% Eff. - MERV 8
C = 4” Pleated - 65% Eff. - MERV 11
D = 4” Pleated - 85% Eff. - MERV 13
E = 4” Pleated - 95% Eff. - MERV 14
F = 4” Carbon
G = Options C + F
H = Options D + F
J = Options E + F
K = Options C + D
L = Options C + E
6C: FILTER OPTIONS
0 = Standard
A = Clogged Filter Switch
B = Magnehelic Gauge
C = Options A + B
0 A 0
-
0 0 0 0 0 0
Feature 7: REFRIGERATION
CONTROL
0 = Standard
C = Freeze Stat - Each Circuit
Feature 8: REFRIGERATION OPTIONS
0 = Standard
D = Modulating Hot Gas Reheat
Feature 9: REFRIGERATION
ACCESSORIES
0 = Standard
A = Sight Glass
B = Compressor Isolation Valves
C = Options A + B
Feature 10: POWER OPTIONS
0 = Standard Power Block
Feature 11: SAFETY OPTIONS
0 = Standard
C = Supply Air Smoke Detector
H = Remote Safety Shutoff Terminals
L = Options A + H
Feature 12: CONTROLS
0 = Standard
A = Low Limit Controls
B = Phase and Brown Out Protection
C = Options A + B
12
Feature Number
SB Features Description
D
-
13 14A 14B 15
Feature 13: SPECIAL CONTROLS
D = VAV Unit Controller - VAV Cool + CV Heat
Y = VAV Single Zone Heat Pump Unit Controller VAV Cool + VAV Heat
Z = Constant Volume Heat Pump Unit Controller CV Cool + CV Heat
1 = Make Up Air Heat Pump Unit Controller - CV
Cool + CV Heat
4 = Field Installed DDC Controls by Others
5 = Field Installed DDC Controls by Others with
Isolation Relays
6 = Factory Installed DDC Controls Furnished by
Others with Isolation Relays
Feature 14: WATER-COOLED
CONDENSER AND WATERSIDE
ECONOMIZER
14A: WATER-COOLED CONDENSER
0 = Standard - None
B = Water Flow Switch
E = Balancing Valves + Option B
H = Motorized Shut-Off Valve + Option B
J = Head Pressure Control + Option B
L = Balancing Valves + Motorized Shut-Off Valve +
Option B
M = Balancing Valves + Head Pressure Control +
Option B
T = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Option B
W = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Balancing Valves + Option B
1 = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Motorized Shut-Off Valve + Option B
2 = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Head Pressure Control + Option B
4 = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Balancing Valves + Motorized Shut-Off
Valve + Option B
5 = CuNi Corrosion Resistant Coaxial Heat
Exchanger + Balancing Valves + Head Pressure
Control + Option B
E 0
-
14B: WATERSIDE ECONOMIZER PIPING
0 = Standard - None
A = Variable Water Flow Application Field Piped
Waterside Economizer
B = Constant Water Flow Application Field Piped
Waterside Economizer
C = Variable Water Flow Application Factory Piped
Waterside Economizer
D = Constant Water Flow Application Factory Piped
Waterside Economizer
Feature 15: GLYCOL PERCENTAGE
0 = Standard - None
A = Minimum 20% Propylene Glycol
B = Minimum 40% Propylene Glycol
0
13
Feature Number
SB Features Description
0 0 0 0 0 0 A B
16 17 18 19 20 21 22 23
Feature 16: INTERIOR CABINET
OPTIONS
0 = Standard - Double Wall Construction + R-6.5
Foam Insulation + Stainless Steel Drain Pan
A = Overflow Switch
B = Compressor Sound Blanket
C = Options A + B
Feature 17: EXTERIOR CABINET
OPTIONS
0 = Standard
A = AAON Gray Exterior Paint
B = Special Paint
C = Interior Corrosion Protection
D = Options A + C
Feature 18: WARRANTY
0 = Standard
A = Second to Fifth Year Extended Compressor
Warranty
Feature 19: CODE OPTIONS
0 = Standard - ETL U.S.A. Listing
Feature 20: CRATING
0 = Standard
A = Export Crating
B = Forkliftable Base - 5” Base
D = Options A + B
E = Shipping Shrink Wrap
F = Options B + E
G = Options A + B + E
Feature 21: UNIT SPLITS
0 = Standard - One Piece Unit
A = Two Piece Unit - One Compressorized Section +
One Air Tunnel Section
Feature 22: CONTROL VENDORS
0 = Standard
A = WattMaster Orion Controls System
E = Remote Mounted AAON Mini Controller
Feature 23: TYPE
B = Standard
X = Special Pricing Authorization
14
Improper installation, adjustment,
service or maintenance
can cause property damage,
personal injury or loss of life.
Installation and service must be
recovery, recycling, or reclaiming
must be followed.
Coils and sheet metal surfaces
working with
WARNING
“construction heater” at anytime
during any phase of construction.
Very low return air temperatures,
CAUTION
General Information
SB Series self contained units have been
designed for indoor installation only. Units
are assembled, wired, charged and runtested at the factory.
alteration,
performed by a qualified installer. A
copy of this IOM should be kept with
the unit.
These units must not be used as a
harmful vapors, and misplacement of
the filters will damage the unit and its
efficiency.
Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air heating system
with cooling.
b. Certified for indoor installation only.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with cooling.
b. Certified for indoor installation only.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with electrically operated
compressors.
b. Certified for indoor installation only.
c. Certified with refrigerant R-410A coils.
Codes and Ordinances
SB Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of units must conform to the
ICC standards of the International
Mechanical Code, the International Building
Code, Installation of Air Conditioning and
Ventilating Systems Standard, NFPA 90A,
and local building, plumbing and waste
water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
present sharp edges and care must
be taken when
equipment.
15
Failure to observe the following
WARNING
To prevent motor overheating
compressors must cycle off for a
maintain the proper oil level
compressors must cycle on for a
starts per hour.
WARNING
instructions will result in premature
failure of your system and possible
voiding of the warranty.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once.
Nameplate should be checked to ensure the
correct model sizes and voltages have been
received to match the job requirements.
If repairs must be made to damaged goods,
then the factory should be notified before
any repair action is taken in order to protect
the warranty. Certain equipment alteration,
repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact the
AAON Warranty Department for assistance
with handling damaged goods, repairs, and
freight claims: (903) 236-4403.
Note: Upon receipt check shipment for
items that ship loose such as filters and
remote sensors. Consult order and shipment
documentation to identify potential looseshipped items. Loose-shipped items may
have been placed inside unit cabinet for
security. Installers and owners should secure
all doors with locks or nuts and bolts to
prevent unauthorized access.
The warranty card must be completed in full
and returned to AAON not more than 3
months after unit is delivered.
16
Figure 1 - Lockable Handle
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Direct Expansion (DX) Systems
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To
minimum of 5 minutes.
The cycle rate must not exceed 6
All water-cooled condenser DX systems are
factory assembled, leak tested, charged with
R-410A refrigerant, and run tested.
Some units are equipped with
compressor crankcase heaters,
CAUTION
result in overflow of condensate
All DX systems include evaporator coils,
liquid line filter dryers, thermal expansion
valves (TXV), and scroll compressors.
Compressors are equipped with a positive
pressure forced lubrication system.
CRANKCASE HEATER
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
Never turn off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit crankcase heaters
cannot prevent refrigerant migration into the
compressors. This means the compressor
may cool down and liquid refrigerant may
accumulate in the compressor. The
compressor is designed to pump refrigerant
gas and damage may occur when power is
restored.
If power to the unit must be off for more
than an hour, turn the thermostat system
switch to "OFF", or turn the unit off at the
control panel, and leave the unit off until the
main power switch has been turned on again
for at least 24 hours for units with
compressor crankcase heaters. This will give
the crankcase heater time to clear any liquid
accumulation out of the compressor before it
is started.
Always control the unit from the thermostat,
or control panel, never at the main power
supply, except for emergency or complete
shutdown of the unit.
During the cooling season, if the air flow is
reduced due to dirty air filters or any other
reason, the cooling coils can get too cold
which will cause excessive liquid to return
to the compressor. As the liquid
concentration builds up, oil is washed out of
the compressor, leaving it starved for
lubrication.
The compressor life will be seriously
shorted by reduced lubrication and the
pumping of excessive amounts of liquid oil
and refrigerant.
Wiring Diagrams
Unit specific wiring diagrams are laminated
and affixed inside the controls compartment
door.
Condensate Drain Pans
Units require drain p-traps and lines to be
connected to the condensate drain pans of
the unit. The lines should be the same pipe
size or larger than the drain connection,
include a p-trap, and pitch downward toward
drain. An air break should be used with long
runs of condensate lines.
Waterside economizer coil units include a
separate condensate drain pan which drains
into the evaporator coil drain pan.
Unit should not be operated without a
p-trap. Failure to install a p-trap may
water.
17
Minimum
Clearance Required
Access Door Sides
36 inches
All Other Sides
6 inches
Emergency drain pan is
recommended for all applications
where a risk of water damage to
Installation
AAON equipment has been designed for
quick and easy installation.
Locating the Unit
Placement of the unit relative to ductwork,
electrical and plumbing must be carefully
considered. Return air plenum or duct can be
mounted directly to the return air flanges.
Use flexible gasket material to seal the duct
to the unit.
Verify floor or foundation can support the
total unit weight, including accessory
weights. Unit must be level in both
horizontal axes to support the unit and
reduce noise and vibration from the unit.
Allow adequate service clearances as shown
on the unit nameplate and unit drawing.
Consult your local building codes for
additional service clearance requirements.
Allow adequate space for piping access and
panel removal. Condenser water piping and
condensate drain connections are located on
either side of the unit.
Table 1 - SB Series Clearances
Location
surrounding structure or furnishings.
Refer to local codes.
Floor Mounted Units
Make sure the unit is level and mounted on a
field supplied platform with a minimum
height to allow for proper depth of the
condensate line p-trap. Other installation
provisions may be necessary according to
job specifications. SB Series vertical air
handling units are designed for up flow
applications only.
Figure 2 - SB Series
18
the unit, injury or death. Lifting
equipment capacity should exceed
of chemical corrosion is excluded
from coverage under AAON Inc.
Connections and service
Right Hand Side
Compressor and Heat
SB Series
Top View
Air Flow
Consider the air flow to be
Exchanger Compartment
Left Hand Side
Lifting and Handling the Unit
Before lifting unit, be sure that all shipping
material has been removed from unit.
Incorrect lifting can cause damage to
UNIT HANDLING
unit weight by an adequate safety
factor. Always test lift unit not more
than 24 inches high to verify proper
center of gravity lift point.
Care should be taken if using spreader bars,
blocking or other lifting devices to prevent
damage to the cabinet, coil or fans.
Supply Air
Return Air
hitting the back of your head.
Figure 3 - SB Series Unit Orientation
Refrigerant-to-Water Heat Exchanger
Water Piping
Condenser water pump, condenser water
piping, cooling tower, pressure gauges,
strainers, piping insulation and all
components of the waterside piping must be
field installed.
Open Loop Applications
This product contains one or more
refrigerant-to-water heat exchangers made
of cupronickel or copper and is subject to
severe corrosion and failure when exposed
to chlorides.
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
warranties and the heat exchanger
manufacturer’s warranties.
access on right side for
right hand orientation
19
Cleaning the cooling tower or
condenser water loop with harsh
(muriatic acid), chlorine or other
chlorides, can damage the
Care should be taken to avoid
allowing chemicals to enter the
Corrosion Resistance for more
may result in premature failure of
Do not allow water containing any form of
chlorides to enter this heat exchanger.
Common forms of chlorides include:
1. Sea water mist entering an open cooling
tower system.
2. Contaminated make-up water containing
salt water.
3. Disinfection the water loop with solutions
containing sodium hypochlorite.
Chlorides will result in a premature failure
of the condenser.
Failure of the condenser as a result of
chemical corrosion is excluded from
coverage under AAON warranties and the
heat exchanger manufacturer warranties.
Failure of the condenser will allow water to
enter the refrigerant circuit and will cause
extensive damage to the refrigerant circuit
components. Any damage to the equipment
as a result of condenser failure from
chemical corrosion due the fluid in the
condenser is excluded from coverage under
AAON warranties and the heat exchanger
manufacturer warranties.
OPEN LOOP APPLICATIONS
Cupronickel refrigerant-to-water heat
exchangers are recommended with
all open loop applications. Failure to
use a Cupronickel heat exchanger
your system and possible voiding of
the warranty.
20
chemicals such as hydrochloric acid
refrigerant-to-water heat exchanger.
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
information.
Freezing Water in the Heat Exchanger
This product contains one or more
refrigerant-to-water heat exchangers. A
refrigerant-to-water heat exchanger contains
refrigerant in one passage and water in
another passage. Water is subject to freezing
at 32°F. When water freezes in a heat
exchanger significant forces are exerted on
the components of the heat exchanger where
the water is confined.
Failure of the condenser due to freezing will
allow water to enter the refrigerant circuit
and will cause extensive damage to the
refrigerant circuit components. Any damage
to the equipment as a result of water
freezing in the condenser is excluded from
coverage under AAON warranties and the
heat exchanger manufacturer warranties.
% Glycol
Ethylene
Glycol
Propylene
Glycol
20
18°F
19°F
30
7°F
9°F
40
-7°F
-6°F
50
-28°F
-27°F
Prior to connection of condensing
or death due to instantaneous
water piping. Supply water
Failure of the condenser due to
refrigerant circuit and will cause
from coverage under AAON
chemicals. Polyolester (POE) oils
410A and other
and fittings and complete piping
WATER FREEZING
freezing will allow water to enter the
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
warranties and the heat exchanger
manufacturer warranties.
Unit is capable of operating with Entering
Water Temperatures (EWT) as low as 57°F
during cooling mode without the need for
head pressure control. If the EWT is
expected to be lower than 57°F or more
stable operation is desired, a factory
provided head pressure control water valve
option is available.
Glycol solution should be used if ambient
temperatures are expected to fall below
freezing or if the loop water temperature is
below 50°F while operating in the heating
mode (heat pump units only). Adding glycol
to condenser water causes an increase in
pressure drop resulting in a decrease in unit
performance. A minimum concentration of
20% glycol solution is recommended.
Table 2 - Glycol Freezing Points
Water loop piping runs through unheated
areas or outside the building should be
insulated.
Water Piping
Installing contractor must ensure a
differential pressure switch or water flow
switch is installed between the condenser
water supply and return connections. This
sensor provides a signal to the unit
controller that water flow is present in the
heat exchanger and the unit can operate
without damaging unit components.
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
release of high pressure water, relief
valves should be field supplied on
connection may require a backflow
preventer to prevent supply makeup
water from backing up into the public
water system.
WATER PRESSURE
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
used with Rrefrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
system failure.
Only use approved water pipe material.
Avoid using galvanized material for water
lines/fittings as the material is corrosive and
may cause fouling of the water system.
21
Supply and Return
(in. FPT)
003, 004, 005
1
006, 007, 009, 010
1 1/4
014, 016, 018
1 1/2
to the unit should incorporate
CAUTION
Improper fluid
flow due to valves, piping, or
Table 3 - Condenser Water Connections
Model (SB-)
Connection Size
Condenser water pump must be field sized
and installed between the cooling tower or
geothermal wellfield and self contained unit.
System should be sized in accordance with
the ASHRAE Handbook. Use engineering
guidelines to maintain equal distances for
supply and return piping and limit bend
radiuses to maintain balance in the system.
Balancing valves, permanent thermometers
and gauges may be required.
Installing contractor is responsible for
properly sizing and installing water
system components.
improper pump operation may result
in unacceptable unit operation and
void warranty.
Follow national and local codes when
installing water piping. Connections
vibration eliminators to reduce noise
and vibration and shutoff valves to
facilitate servicing. Supply and return
water piping must be at least as large
as the unit connections and larger
depending on length of runs, rise and
bends.
WATER PIPING
Before connection to the unit, the condenser
water system should be flushed to remove
foreign material that could cause condenser
fouling. Install a screen strainer with a
minimum of 20 Mesh ahead of the
condenser inlet to prevent condenser fouling
and internal tube damage. Mineral content
of the condenser water must be controlled.
All make-up water has minerals in it and as
the water is evaporated in the cooling tower,
these minerals remain. As the mineral
content of the water increases, the
conductivity of the water increases.
Field provided and installed water treatment
program must be compatible with stainless
steel, copper, aluminum, ABS plastic, and
PVC. Batch feed processes should never be
used as concentrated chemicals can cause
corrosion. Never use hydrochloric acid
(muriatic acid) or chlorine as it will corrode
stainless steel.
Water loop piping runs through unheated
areas or outside the building should be
insulated.
NOTE: Ball valves should be installed in
the condenser water supply and return lines
for unit isolation and water flow balancing.
All manual flow valves should be of the ball
valve design. Globe or gate valves should
not be used due to high pressure drops and
poor throttling characteristics.
Pressure and temperature ports are
recommended in condenser water supply
and return lines for system balancing. These
openings should be 5 to 10 pipe diameters
from the unit water connections. To allow
for mixing and temperature stabilization,
wells in the water piping should extend at
least ½ pipe diameter into the pipe.
22
The foam insulation releases
Disconnect all electrical power
in injury or death from electrical
shock or entanglement in moving
Piping systems should not exceed 10 ft/sec
fluid velocity to ensure tube wall integrity
and reduce noise.
Electrical
Verify the unit nameplate agrees with power
supply. SB Series units are provided with
single point power wiring connections.
Connection terminations are made to the
main terminal block. A complete set of unit
specific wiring diagrams, showing factory
and field wiring are laminated in plastic and
located inside the controls compartment
door.
sources before servicing the unit.
More than one power source may be
provided. Failure to do so may result
parts.
All units require field supplied electrical
overcurrent and short circuit protection.
Device must not be sized larger than the
Maximum Overcurrent Protection (MOP)
shown on the unit nameplate.
Codes may require a disconnect switch be
within sight of the unit.
It is recommended that the field installed
overcurrent protection or disconnect switch
not be installed on the unit.
Electrical supply can enter through the
bottom or side of the controls compartment.
Entry must be field cut into panels of the
unit.
A single point connection to a terminal
block is provided. Split units may require
connection between the units. High voltage
conductors should enter the control panel in
a separate opening and separate conduit than
24V low voltage conductors.
dangerous fumes when it is burnt. Do
not cut a foam part with a cutting
torch or plasma cutter. Do not weld to
a foam filled part.
Note: Locations for field cut electrical
entries are marked on the unit. Field cut
openings must be a minimum of 6 inches
away from all components and wiring to
prevent damage due to drilling or cutting.
To pass wires through the wall or roof of the
unit, a hole should be cut and conduit passed
through it. Use the following procedure to
cut a round hole in a foam panel.
Cutting Electrical Openings
1. Locate the placement of the hole. Be sure
that the conduit will not interfere with the
operation of any component or prevent
access of any door or removable panel.
2. Drill a pilot hole all the way through the
foam panel.
3. Using a hole saw cut the hole through the
metal on both sides of the foam part.
4. With a knife cut the foam out of the hole.
5. After the conduit is installed in the hole
caulk the entire perimeter of the hole on
both sides with an industrial grade silicone
sealant or a duct seal compound.
If a larger cut-out is needed for additional
duct connections not provided by the
factory, or for any other reason, it is very
important that the foam be completely
sealed. Insulation covers should be
fabricated from sheet metal to cover the
23
cause motor overheating and
Rotation must be checked on all
at the unit power connection.
CAUTION
foam at the cut. The edges and corners that
are not covered should then be sealed using
silicone caulking or a duct seal compound.
If a reciprocating saw is used to make the
cut-out take care that the metal skins of the
foam part do not separate from the foam,
this would result in reduced structural
integrity of the part.
Size supply conductors based on the unit
Minimum Current Ampacity (MCA) rating.
Supply conductors must be rated a minimum
of 75°C.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Note: Units are factory wired for 208V,
230V, 460V, or 575V. In some units, the
208V and 230V options may also be
provided in single or three phase
configurations. The transformer
configuration must be checked by a
qualified technician prior to startup.
Wire power leads to the unit’s terminal
block or main disconnect. All wiring beyond
this point has been completed by AAON and
cannot be modified without effecting the
unit’s agency/safety certification.
Supply voltage must be within the min/max
range shown on the unit nameplate.
Available short circuit current should not
exceed the short circuit current rating
(SCCR) shown on the unit nameplate.
Three phase voltage imbalance will
premature failure.
Three phase voltage imbalance will cause
motor overheating and premature failure.
The maximum allowable imbalance is 2.0%.
Voltage imbalance is defined as 100 times
the maximum deviation from the average
voltage divided by the average voltage.
Example:
(221V+230V+227V)/3 = 226V, then
100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit
disconnect switch and at the compressor
terminal. Contact your local power company
for line voltage corrections.
Installing contractor must check for proper
motor rotation and check blower motor
amperage listed on the motor nameplate is
not exceeded.
MOTORS AND COMPRESSORS of
three phase units. Supply fan motors
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
24
Wire Size (Stranded)
Only
Total Wire Distance
20 AWG
200 ft
18 AWG
350 ft
16 AWG
500 ft
14 AWG
750 ft
12 AWG
1250 ft
the wrong direction. Low pressure
disconnected after factory testing.
Rotation should be checked by a
gauges and any wiring alteration
should only be made at the unit
Scroll compressors are directional
and will be damaged by operation in
switches on compressors have been
qualified service technician at startup
using suction and discharge pressure
power connection.
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.
Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.
Table 4 - Control Wiring
- Copper Conductors
Allowable
Total Wire Distance Allowable =
(Quantity of Control Wires) x
(Control Wire Distance)
Take the total wire distance allowable and
divide by the number of wires to be
connected. This indicates the distance
allowable for that size wire. The wiring to
the unit must not exceed the total wire
distance allowable. If the voltage at the
connectors is less than 21 VAC, isolation
relays must be installed. If under external
control 21 VAC must be field verified.
All external devices must be powered via a
separate external power supply.
Example:
A total of 8 wires must be pulled 75ft to a
control the unit. What size wire should be
used?
According to the Table 2, 16 AWG allows
for 63ft (500 ft/8 wires) and 14 AWG allows
for 94ft (750 ft/8 wires). Thus, 14 AWG
should be used.
Duct Connection
Remove shipping covers and attach duct to
flanges provided on the unit. The installer is
responsible for sealing ducts to the flanges
to prevent water leaks.
Intake air enters the back of the SB Series
unit, where the air filters are located.
Ductwork should be sized in accordance
with the ASHRAE Handbook. Ductwork
should be installed in accordance with
NFPA Standard 90A.
When attaching duct to the unit, use a
flexible/compressible material rated for duct
connections. A three inch flexible connector
for both return and supply duct connections
is recommended.
25
Draw-Through
Drain Pan Pressure
Trap Dimensions
Negative Static
X
X/2
(inches of water)
(inch)
(inch)
-0.50
1.50
0.75
-1.00
2.00
1.00
-1.50
2.50
1.25
-2.00
3.00
1.50
-2.50
3.50
1.75
-3.00
4.00
2.00
result in overflow of condensate
Condensate Drain Piping
Unit may be equipped with more than one
condensate drain pan connection. A p-trap
and drain line must be installed on at least
one section’s drain connection, with the ptrap not to exceed 6” from the drain
connection. The lines should be the same
pipe size or larger than the drain connection,
include a p-trap, and pitch downward toward
drain. An air break should be used with long
runs of condensate lines.
Unit should not be operated without
p-traps. Failure to install a p-trap may
water.
Draw-through cooling coils will have a
negative static pressure in the drain pan area.
This will cause an un-trapped drain to back
up due to air being pulled up through the
condensate drain piping.
Condensate drain trapping and piping should
conform to all applicable governing codes.
Note: The drain pan connection(s) is a 1”
MPT fitting.
The X dimension on the draw-through trap
should be at least equal to the absolute value
of the negative static pressure in the drain
pan plus one inch. To calculate the static
pressure at the drain pan add the pressure
drops of all components upstream of the
drain pan, including the cooling coil, and
add the return duct static pressure. Include
the dirt allowance pressure drop for the
filters to account for the worst-case scenario.
The height from top of the bottom bend of
the trap to the bottom of the leaving pipe
must be at least equal to one half of the X
dimension. This ensures that enough water
is stored in the trap to prevent losing the
drain seal during unit startup
Note: The absolute value of the fan inlet
pressure will always be greater than or equal
to the absolute value of the static pressure in
the drain pan on draw-through units, so the
fan inlet pressure is a safe value to use for
the drain pan static pressure.
Table 5 - Drain Trap Dimensions
Figure 4 - Drain Trap
26
Waterside Economizer
Cooling and pre-cooling waterside
economizer coil is factory installed upstream
of the evaporator coil. Factory tested and
field installed water piping kit includes fully
modulating waterside economizer valve and
fully modulating waterside economizer
bypass valve.
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life.
Installation and service must be
WARNING
The waterside economizer circuit can
operate in three modes: waterside
economizer only, waterside economizer with
mechanical cooling, and mechanical cooling
only.
During waterside economizer only mode of
operation condenser water flows through the
waterside economizer coil with modulating
valves maintaining supply air temperature
setpoint. The condenser water then passes
through water-cooled condenser.
During waterside economizer with
mechanical cooling mode of operation
condenser water flows through the waterside
economizer coil with the waterside
economizer modulating valve fully open.
The condenser water then passes through
water-cooled condenser.
During mechanical cooling only mode of
operation condenser water flows around the
waterside economizer coil with the
waterside economizer bypass valve fully
open. The condenser water then passes
through water-cooled condenser.
Waterside economizer coil condensate drain
outlet drains into evaporator coil drain pan.
See the previous section on evaporator coil
condensate drain piping.
Mineral content of the condenser water must
be controlled. All make-up water has
minerals in it and as the water is evaporated
in the cooling tower, these minerals remain.
As the mineral content of the water
increases, the conductivity of the water
increases.
Field provided and installed water treatment
program must be compatible with stainless
steel, copper, aluminum, ABS plastic, and
PVC. Batch feed processes should never be
used as concentrated chemicals can cause
corrosion. Never use hydrochloric acid
(muriatic acid) or chlorine as it will corrode
stainless steel.
Heating Coils
Factory installed one or two row hot water
and steam heating coils can be factory
mounted. These coils are supplied from a
source through separate piping from the
condenser water source. All controls for
heating operation are field supplied and field
installed.
Always connect the supply to the top of the
coil and the return to the bottom. Water coils
should not be subjected to entering air
temperatures below 38°F to prevent coil
freeze-up. If air temperature across the coil
is going to be below this value, use a glycol
solution to match the coldest air expected.
Piping shall be in accordance with
national and local codes. Pressure
limiting devices, backflow preventers
and all other safety requirements are
the sole responsibility of the installing
contractor.
Startup
(See back of the manual for startup form)
performed by a qualified installer. A
copy of this IOM should be kept with
the unit.
27
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
During startup, it is necessary to perform
routine checks on the performance of the
unit. This includes checking of the air flow,
the air filters, condenser water flow and
refrigerant charge.
Supply Fans
SB Series units are equipped with direct
drive backward curved plenum supply fan
assemblies that deliver the air volume
specified according to unit size and job
requirements.
Figure 5 - SB Series Supply Fan
Supply Fan Airflow Adjustment
Supply fan Electronically Commutated
Motors (ECM) speed adjustment may be
required at startup for airflow adjustment.
With WattMaster controls supply fans are
controlled directly from the controller with a
0-10 VDC signal.
With customer provided field installed
controls the supply fans can be controlled
with either a factory installed potentiometer
or with a 0-10 VDC signal provided by the
controller.
28
Figure 6 - ECM with Factory Provided Controls
Figure 7 - ECM with Potentiometer Control
29
30
Figure 8 - ECM with Field Installed Controls
Before completing startup and
venting of refrigerant
recycling or reclaiming must be
Filters
Do not operate the unit without filters in
place. Unit should be checked for correct
filter placement during startup. Operation of
the equipment without filters will result in a
clogged evaporator coil.
leaving the unit a complete operating
cycle should be observed to verify
that all components are functioning
properly.
Adjusting Refrigerant Charge
Adjusting the charge of a system in the field
must be based on determination of liquid
sub-cooling and evaporator superheat. On a
system with a TXV liquid sub-cooling is
more representative of the charge than
evaporator superheat but both measurements
must be taken.
Before Charging
Unit being charged must be at or near full
load conditions before adjusting the charge.
The Clean Air Act of 1990 bans the
intentional
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery,
followed. Fines and/or incarceration
may be levied for non-compliance.
Units equipped with hot gas reheat must be
charged with the hot gas reheat valves
closed while the unit is in cooling mode to
get the proper charge. After charging, unit
should be operated in reheat
(dehumidification) mode to check for
correct operation.
After adding or removing charge the system
must be allowed to stabilize, typically 10-15
minutes, before making any other
adjustments.
The type of unit and options determine the
ranges for liquid sub-cooling and evaporator
superheat. Refer to the tables below when
determining the proper sub-cooling.
Checking Liquid Sub-Cooling
Measure the temperature of the liquid line as
it leaves the condenser.
Read the gauge pressure at the liquid line
close to the point where the temperature was
taken. Use liquid line pressure as it will vary
from discharge pressure due to condenser
pressure drop.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the measured liquid line
temperature from the saturated temperature
to determine the liquid sub-cooling.
Compare calculated sub-cooling to the table
below for the appropriate unit type and
options.
Checking Evaporator Superheat
Measure the temperature of the suction line
close to the compressor.
Read gauge pressure at the suction line close
to the compressor.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
31
Water-Cooled
Condenser
Sub-Cooling
6-10°F
Sub-Cooling with
Hot Gas Reheat
Superheat
8-15°F
Refrigerant overcharging leads to
Thermal expansion valve must be
suction superheat. Failure to have
CAUTION
Refrigerant overcharging leads to
Subtract the saturated temperature from the
measured suction line temperature to
determine the evaporator superheat.
Compare calculated superheat to the table
below for the appropriate unit type and
options.
DO NOT OVERCHARGE!
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
Table 6 - Acceptable Water-Cooled
Refrigeration Circuit Values
Adjusting Sub-Cooling and Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator superheat is within the
temperature range as shown in the table
above (high superheat results in increased
sub-cooling).
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
DO NOT OVERCHARGE!
8-12°F
The system is undercharged if the superheat
is too high and the sub-cooling is too low
adjusted to approximately 8-15°F of
sufficient superheat will damage the
compressor and void the warranty.
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.
service or maintenance
can cause property damage,
personal injury or loss of life.
Installation and service must be
WARNING
To prevent motor overheating
compressors must cycle off for a
To maintain the proper oil level
compressors must cycle on for a
starts per hour.
WARNING
Operation
Unit operations should be controlled with
thermostat or unit controller, never at the
main power supply, except for emergency or
complete shutdown of the unit.
Packaged DX Cooling Operation and
Control
When a call for cooling is made the supply
fan motors and compressors will energize.
Electric Heating Operation
When a call for heating (G and W1, W2,
etc.) is made the supply fan motors and
electric resistance heaters will energize.
Heating is accomplished by passing
electrical current through a specified amount
of resistance heaters which will produce the
required heat.
On a fault condition the main limit located
in the supply air or the auxiliary limit
located downstream the supply blower will
remove power from all contactors.
Steam or Hot Water Preheating
Operation
Valve control for steam and hot water
heating coils are by others. Heating is
accomplished by passing steam or hot water
34
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
minimum of 5 minutes.
The cycle rate must not exceed 6
through the steam or hot water coil
assembly.
Maintenance
(See back of the manual for maintenance
log.)
At least once each year, a qualified service
technician should check out the unit. Supply
fans, evaporator coils and air filters should
be inspected monthly.
alteration,
performed by a qualified installer. A
copy of this IOM should be kept with
the unit.
Periodically during operation, it is necessary
to perform routine service checks on the
performance of the unit. This includes
checking of the air flow, the air filters,
condenser water flow and refrigerant charge.
See Startup section for information on air
flow adjustment and refrigerant charge
adjustment.
DX Cooling
Set unit controls to cooling mode of
operation with supply fans on. Check the
fans for correct operating direction,
amperage and voltage. Check compressor
operation, rotation, amperage and voltage to
the unit nameplate (check the amperage on
the load side of the compressor contactor).
Condensate Drain Pans
Drain pans will have moisture present and
require periodic cleaning to prevent
microbial growth. Cleaning of the drain pans
will also prevent any possible plugging of
the drain lines and overflow of the pan itself.
parts.
WARNING
air should
bend the fin edges and increase
performance or nuisance unit
Cleaning of the drain pans and inside of the
unit should be done only by qualified
personnel.
E-Coated Coil Cleaning
Documented routine cleaning of e-coated
coils is required to maintain coating
warranty coverage.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
Surface loaded fibers or dirt should be
removed prior to water rinse to prevent
restriction of airflow. If unable to back wash
the side of the coil opposite of the coils
entering air side, then surface loaded fibers
or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available,
a soft non-metallic bristle brush may be
used. In either case, the tool should be
applied in the direction of the fins. Coil
surfaces can be easily damaged (fin edges
bent over) if the tool is applied across the
fins.
Use of a water stream, such as a garden
hose, against a surface loaded coil will drive
the fibers and dirt into the coil. This will
make cleaning efforts more difficult. Surface
loaded fibers must be completely removed
prior to using low velocity clean water rinse.
A monthlyclean water rinse is
recommended for coils that are applied in
coastal or industrial environments to help to
remove chlorides, dirt, and debris. It is very
important when rinsing, that water
temperature is less than 130°F and pressure
is than 900 psig to avoid damaging the fin
edges. An elevated water temperature (not to
exceed 130°F) will reduce surface tension,
increasing the ability to remove chlorides
and dirt.
High velocity water from a pressure
washer or compressed
only be used at a very low pressure
to prevent fin and/or coil damages.
The force of the water or air jet may
airside pressure drop. Reduced unit
shutdowns may occur.
Quarterly cleaning is essential to extend
the life of an e-coated coil and is required
to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s
regularly scheduled maintenance
procedures. Failure to clean an e-coated coil
will void the warranty and may result in
reduced efficiency and durability.
Harsh chemicals, household bleach,
or acid cleaners should not be used
to clean outdoor or indoor e-coated
coils. These cleaners can be very
difficult to rinse out of the coil and
can accelerate corrosion and attack
the e-coating. If there is dirt below the
surface of the coil, use the
recommended coil cleaners.
For routine quarterly cleaning, first clean the
coil with the below approved coil
cleaner. After cleaning the coils with the
approved cleaning agent, use the approved
chloride remover to remove soluble salts and
revitalize the unit.
Recommended Coil Cleaner
The following cleaning agent, assuming it is
used in accordance with the manufacturer’s
directions on the container for proper mixing
and cleaning, has been approved for use on
e-coated coils to remove mold, mildew,
35
Electric shock hazard. Shut off all
WARNING
dust, soot, greasy residue, lint and other
particulate:
Enviro-Coil Concentrate, Part Number HEC01.
Recommended Chloride Remover
CHLOR*RID DTS™ should be used to
remove soluble salts from the e-coated coil,
but the directions must be followed closely.
This product is not intended for use as a
degreaser. Any grease or oil film should first
be removed with the approved cleaning
agent.
Remove Barrier - Soluble salts adhere
themselves to the substrate. For the effective
use of this product, the product must be able
to come in contact with the salts. These salts
may be beneath any soils, grease or dirt;
therefore, these barriers must be removed
prior to application of this product. As in all
surface preparation, the best work yields the
best results.
Apply CHLOR*RID DTS - Apply directly
onto the substrate. Sufficient product must
be applied uniformly across the substrate to
thoroughly wet out surface, with no areas
missed. This may be accomplished by use of
a pump-up sprayer or conventional spray
gun. The method does not matter, as long as
the entire area to be cleaned is wetted. After
the substrate has been thoroughly wetted,
the salts will be soluble and is now only
necessary to rinse them off.
Rinse - It is highly recommended that a hose
be used, as a pressure washer will damage
the fins. The water to be used for the rinse is
recommended to be of potable quality,
though a lesser quality of water may be used
if a small amount of CHLOR*RID DTS is
added. Check with CHLOR*RID
International, Inc. for recommendations on
lesser quality rinse water.
Supply Fans
Blower wheels must be inspected for
excessive dust build up periodically
and cleaned if required. Excessive
dust build up on blower wheels may
cause an unbalanced state; leading
to vibration and/or component failure.
Damages due to excessive dust build
up will not be covered under factory
warranty.
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
Supply Fan Lubrication
All original blower motors and bearings are
furnished with factory lubrication. Some
applications will require that bearings be relubricated periodically. The schedule will
depend on the operating duty, temperature
variations or other severe atmospheric
conditions.
Bearings should be re-lubricated when at
normal operating temperatures, but not
running. Rotate the fan shaft by hand and
add only enough grease to purge the seals.
DO NOT OVERLUBRICATE.
Recommended greases are:
SHELL OIL - DOLIUM R
CHEVRON OIL - SRI No. 2
TEXACO INC. - PREMIUM R
36
Feature 6A
Quantity/Size
Type
0
No Pre Filters
A
1/24” x 24” x 2”
Pleated, 30% Eff, MERV 8
Feature 6B
Quantity/Size
Type
0
No Standard Filters
A
1/24” x 24” x 2”
Pleated, 30% Eff, MERV 8
B
Pleated, 30% Eff, MERV 8
C
Pleated, 65% Eff, MERV 11
D
Pleated, 85% Eff, MERV 13
E
Pleated, 95% Eff, MERV 14
Feature 6A
Quantity/Size
Type
0
No Pre Filters
A
4/16” x 20” x 2”
Pleated, 30% Eff, MERV 8
Feature 6B
Quantity/Size
Type
0
No Standard Filters
A
4/16” x 20” x 2”
Pleated, 30% Eff, MERV 8
B
Pleated, 30% Eff, MERV 8
C
Pleated, 65% Eff, MERV 11
D
Pleated, 85% Eff, MERV 13
E
Pleated, 95% Eff, MERV 14
Filter Replacement
Monthly filter inspection is required to
maintain optimum unit efficiency.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
It is strongly recommended that filter media
be replaced monthly. Filters are located
upstream of the evaporator coil. Open access
panel and pull filters straight out to inspect
all of the filters. Replace filters with the size
indicated on each filter. Arrow on the
replacement filters must point towards the
blower.
Replacement Parts
Parts for AAON equipment may be obtained
from AAON at www.aaonparts.com. When
ordering parts, reference the unit serial
number and part number.
Note: Before calling, technician should have
model and serial number of the unit
available to help answer questions regarding
the unit.
Filter Information
Table 8 - 3-5 ton (B Cabinet) Pre and Unit Filters
1/24” x 24” x 4”
Table 9 - 6-10 ton (C Cabinet) Pre and Unit Filters
4/16” x 20” x 4”
37
Feature 6A
Quantity/Size
Type
0
No Pre Filters
A
4/18” x 24” x 2”
Pleated, 30% Eff, MERV 8
Feature 6B
Quantity/Size
Type
0
No Standard Filters
A
4/18” x 24” x 2”
Pleated, 30% Eff, MERV 8
B
Pleated, 30% Eff, MERV 8
C
Pleated, 65% Eff, MERV 11
E
Pleated, 95% Eff, MERV 14
Filter Type
Quantity/Size
Type
Pre Filters
1/24” x 24” x 2”
2” Pleated, 30% Eff, MERV 8
High Efficiency
Filters
Secondary High
Efficiency Filters
Filter Type
Quantity/Size
Type
Pre Filters
4/16” x 20” x 2”
2” Pleated, 30% Eff, MERV 8
High Efficiency
Filters
Secondary High
Efficiency Filters
Filter Type
Quantity/Size
Type
Pre Filters
4/18” x 24” x 2”
2” Pleated, 30% Eff, MERV 8
High Efficiency
Filters
Secondary High
Efficiency Filters
Table 10 - 14-18 ton (D Cabinet) Pre and Unit Filters
D Pleated, 85% Eff, MERV 13
Table 11- 3-5 ton (B Cabinet) Mixing Box Filters
Table 12 - 6-10 ton (C Cabinet) Mixing Box Filters
Table 13 - 14-18 ton (D Cabinet) Mixing Box Filters
4/18” x 24” x 4”
1/24” x 24” x 4” 4” Pleated
1/24” x 24” x 4” 4” Pleated
4/16” x 20” x 4” 4” Pleated
4/16” x 20” x 4” 4” Pleated
38
4/18” x 24” x 4” 4” Pleated
4/18” x 24” x 4” 4” Pleated
Water
Containing
Concentration
(mg/l or ppm)
Time Limits -
Analyze Before
AISI
316
SMO
254
Copper
Alloy
Nickel
Alloy
< 70
+ + 0 + 70-300
+ + + + > 300
+ + 0/+
+
< 70
+ + + + 70-300
+ + 0/- + > 300
0 0 -
+
> 1.0
+ + + + < 1.0
+ + 0/-
+
< 10µS/cm
+ + 0 + 10-500 µS/cm
+ + + + > 500 µS/cm
+ + 0
+
< 6.0
0 0 0 + 6.0-7.5
0/+ + 0 + 7.5-9.0
+ + +
+
> 9.0
+ + 0
+
< 2
+ + + + 2-20
+ + 0 + > 20
+ + -
+
< 300
+ + + + > 300
0 + 0/+
+
< 1
+ + + + 1-5
+ + 0 + > 5
0/+ + 0/-
+
Hydrogen
< 0.05
+ + + + > 0.05
+ + 0/-
+
< 5
+ + + + 5-20
+ + 0 + > 20
+ + -
+
Appendix A - Heat Exchanger Corrosion Resistance
The resistance guide below provides the corrosion resistance of stainless steel type AISI 316 and
pure Copper (99.9%) in water, to a number of important chemical factors. The actual corrosion is
a very complex process influenced by many different factors in combination.
Explanations: + Good resistance under normal conditions
0 Corrosion problems may occur especially when more factors are valued 0
Refrigeration System 1 - Heating Mode (Heat Pump Only)
Pressure
Unit Configuration
Pressure
Pressure
Sub-cooling Superheat
Sub-cooling Superheat
Water Inlet Temperature ________°F
42
Water Outlet Temperature ________°F
1. Has the entire system been flushed and pressure checked?
Yes No
2. Has the entire system been filled with fluid?
Yes No
3. Has air been bled from the heat exchangers and piping?
Yes No
4. Is the glycol the proper type and concentration (N/A if water)?
Yes No
5. Is there a minimum load of 50% of the design load?
Yes No
6. Has the water piping been insulated?
Yes No
Water/Glycol System
7. What is the freeze point of the glycol (N/A if water)? ______________________________
43
Entry Date
Action Taken
Name/Tel.
Maintenance Log
This log must be kept with the unit. It is the responsibility of the owner and/or
maintenance/service contractor to document any service, repair or adjustments. AAON Service
and Warranty Departments are available to advise and provide phone help for proper operation
and replacement parts. The responsibility for proper startup, maintenance, and servicing of the
equipment falls to the owner and qualified licensed technician.
44
Literature Change History
November 2012
First Revision, Rev. A, of the SB Series IOM.
December 2012
Manual updated with the voltage options corrected, option 1 = 230V/1Φ/60Hz and option 9 =
208V/1Φ/60Hz. Condensing unit only options and ECM driven fan airflow adjustment
information added.
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
SB Series
Installation, Operation &
Maintenance
V14190 · Rev. A · 121227
(ACP 31227)
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.