Aaon SB-003 Installation Manual

vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
WARNING
SB Series
Vertical Self Contained Units
Installation, Operation
personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
QUALIFIED INSTALLER
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the
Table of Contents
Safety .............................................................................................................................................. 5
SB Series Feature String Nomenclature ....................................................................................... 11
General Information ...................................................................................................................... 15
Codes and Ordinances .............................................................................................................. 15
Receiving Unit .......................................................................................................................... 16
Storage ...................................................................................................................................... 16
Direct Expansion (DX) Systems ............................................................................................... 16
Wiring Diagrams ....................................................................................................................... 17
Condensate Drain Pans ............................................................................................................. 17
Installation..................................................................................................................................... 18
Locating the Unit ...................................................................................................................... 18
Lifting and Handling the Unit ................................................................................................... 19
Refrigerant-to-Water Heat Exchanger Water Piping ................................................................ 19
Electrical ................................................................................................................................... 23
Duct Connection ....................................................................................................................... 26
Condensate Drain Piping .......................................................................................................... 26
Waterside Economizer .............................................................................................................. 27
Heating Coils ............................................................................................................................ 28
Electric Preheat ......................................................................................................................... 28
Startup ........................................................................................................................................... 29
Supply Fans ............................................................................................................................... 29
Filters ........................................................................................................................................ 32
Adjusting Refrigerant Charge ................................................................................................... 32
Operation....................................................................................................................................... 35
Packaged DX Cooling Operation and Control ......................................................................... 35
Electric Heating Operation ....................................................................................................... 35
Steam or Hot Water Preheating Operation ............................................................................... 35
Modulating Electric Preheat ..................................................................................................... 35
Maintenance .................................................................................................................................. 35
DX Cooling ............................................................................................................................... 35
Condensate Drain Pans ............................................................................................................. 36
E-Coated Coil Cleaning ............................................................................................................ 36
Supply Fans ............................................................................................................................... 37
Filter Replacement .................................................................................................................... 38
Replacement Parts ..................................................................................................................... 38
AAON Longview Product Support ........................................................................................... 38
Filter Information .......................................................................................................................... 39
Appendix A - Heat Exchanger Corrosion Resistance ................................................................... 42
3
Index of Tables and Figures
Tables:
Table 1 - SB Series Clearances ..................................................................................................... 18
Table 2 - Glycol Freezing Points .................................................................................................. 21
Table 3 - Condenser Water Connections ...................................................................................... 22
Table 4 - Control Wiring ............................................................................................................... 25
Table 5 - Drain Trap Dimensions ................................................................................................. 27
Table 6 - Acceptable Water-Cooled Refrigeration Circuit Values ............................................... 33
Table 7 - R-410A Refrigerant Temperature-Pressure Chart ......................................................... 34
Table 8 - 3-5 ton (B Cabinet) Pre and Unit Filters ....................................................................... 39
Table 9 - 6-10 ton (C Cabinet) Pre and Unit Filters ..................................................................... 39
Table 10 - 14-18 ton (D Cabinet) Pre and Unit Filters ................................................................. 39
Table 11- 3-5 ton (B Cabinet) Mixing Box Filters ....................................................................... 40
Table 12 - 6-10 ton (C Cabinet) Mixing Box Filters .................................................................... 40
Table 13 - 14-18 ton (D Cabinet) Mixing Box Filters .................................................................. 41
Figures:
Figure 1 - Lockable Handle .......................................................................................................... 16
Figure 2 - SB Series ...................................................................................................................... 18
Figure 3 - SB Series Unit Orientation ........................................................................................... 19
Figure 4 - Drain Trap .................................................................................................................... 26
Figure 5 - SB Series Supply Fan ................................................................................................... 29
Figure 6 - ECM with Factory Provided Controls.......................................................................... 30
Figure 7 - ECM with Potentiometer Control ................................................................................ 30
Figure 8 - ECM with Field Installed Controls .............................................................................. 31
V14190 · Rev. B · 150727
(ACP 31227)
4

AAON SB Series Features and Options Introduction

Energy Efficiency
Direct Drive Backward Curved Plenum
Supply Fans
10-100% Variable Capacity Scroll
Compressors
Double Wall Rigid Polyurethane Foam
Injected Panel Construction
Airside and Waterside Economizers
Modulating SCR Electric Heat
Modulating Head Pressure Control
High Efficiency Electronically
Commutated Motors
Coaxial Refrigerant-to-Water Heat
Exchanger
Water-Source and Geothermal Heat
Pumps
Single Zone Variable Air Volume
Indoor Air Quality
Up to 100% Outside Air with Optional
Electric Pre-Heat
Multiple High Efficiency Unit and
Mixing Box Filters
Double Wall Construction with No
Exposed Insulation
Humidity Control
10-100% Variable Capacity Scroll
Compressors
Modulating Hot Gas Reheat
Safety
Freeze Stats
Phase and Brown Out Protection
Installation and Maintenance
Direct Drive Backward Curved Plenum
Supply Fans
Clogged Filter Switch and Magnehelic
Gauge
Color Coded Wiring Diagram
Isolated Compressor and Controls
Compartment
Compressor Isolation Valves
Hinged Access Doors with Lockable
Handles
Liquid Line Sight Glass
System Integration
Customer Provided Controls
Electric, Steam, or Hot Water Heating
Refrigerant-to-Water Heat Exchangers
Condensing Unit Only Options
Split System Configurations
Environmentally Friendly
R-410A Refrigerant
Geothermal Heat Pump Configurations
Extended Life
Standard 5 Year Compressor Warranty
Double Wall Rigid Polyurethane Foam
Injected Cabinet Construction
2,500 Hour Salt Spray Tested Interior
and Exterior Corrosion Protection
Polymer E-Coated Coils
Stainless Steel Drain Pans
Custom Color Paint Options
5
FIRE, EXPLOSION OR CARBON
Failure to replace proper controls could result in fire, explosion or
to follow safety warnings exactly
and liquids in the vicinity of this
WARNING
Electric shock hazard. Before servicing, disconnect all electrical
ELECTRIC SHOCK, FIRE OR
Failure to follow safety warnings
n dangerous
operation, serious injury, death or
Improper servicing could result in
Before servicing, disconnect all
may be
wires prior to disconnecting. Verify proper operation after
Attention should be paid to the following statements:

Safety

NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
EXPLOSION HAZARD
exactly could result i property damage.
dangerous operation, serious injury, death or property damage.
electrical power to the unit. More than one disconnect provided.
When servicing controls, label all
Reconnect wires correctly.
servicing. Secure all doors with key-lock or nut and bolt.
6
power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
MONOXIDE POISONING HAZARD
carbon monoxide poisoning. Failure could result in serious injury, death or
property damage. Do not store or use gasoline or other flammable vapors
appliance.
power to the unit has been disconnected and fan wheel has
To prevent injury or death lifting
WARNING
All field installed wiring must be completed by qualified personnel. Field installed wiring must comply
to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code
electrical components. Only a qualified licensed electrician or
live electrical components shall
70E, an OSHA
regulation requiring an Arc Flash marked for identification of where
appropriate Personal Protective
WARNING
During installation, testing, servicing and troubleshooting of the equipment it may be necessary to work with live
individual properly trained in handling perform these tasks. Standard NFPA­Boundary to be field established and
Equipment (PPE) be worn, should be followed.
GROUNDING REQUIRED
UNIT HANDLING
equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
ROTATING COMPONENTS
Unit contains fans with moving parts that can cause serious injury. Do not open door containing fans until the
stopped rotating.
with NEC/CEC, local and state electrical code requirements. Failure
requirements.
Failure to properly drain and vent coils when not in use during freezing temperature may result in coil and equipment damage.
7
not use alkaline chemical coil
CAUTION
CAUTION
A sufficient quantity of
WARNING
Always use a pressure regulator,
ges to control
WARNING
in place of refrigerant and dry
WARNING
Prior to connection of condensing
or death due to instantaneous
on all
should be checked for proper
CAUTION
Rotation must be checked MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation
operation. Alterations should only be made at the unit power connection
WATER PRESSURE
water supply, verify water pressure is less than maximum pressure shown on unit nameplate. To prevent injury
release of high pressure water, relief valves should be field supplied on system water piping.
Do not use oxygen, acetylene or air
valves and gau incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.
Do not work in a closed area where refrigerant or nitrogen gases may be leaking. vapors may be present and cause injury or death.
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do
nitrogen for leak testing. A violent explosion may result causing injury or death.
8
cleaners with a pH value greater than
8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
by certain
chemicals. Polyolester (POE) oils
410A and other
and fittings and complete piping
CAUTION
Failure of the condenser due to refrigerant circuit and will cause
verage under AAON
manufacturer warranties.
of chemical corrosion is excluded from coverage under AAON Inc.
WARNING
Cleaning the cooling tower or the condenser water loop with harsh
(muriatic acid) or chlorine, can Care should be taken to avoid
allowing chemicals to enter the
cooled condenser. See
Heat Exchanger
Corrosion Resistance for more
CAUTION
Door compartments containing
CAUTION
Some chemical coil cleaning
Failure to follow
compounds are caustic or toxic. Use these substances only in accordance with the manufacturer’s usage instructions. instructions may result in equipment damage, injury or death.
hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latch are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.
chemicals, such as hydrochloric acid damage the water-cooled condenser.
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
warranties and the heat exchanger manufacturer’s warranties.
WATER FREEZING
freezing will allow water to enter the extensive damage to the refrigerant
circuit components. Any damage to the equipment as a result of water freezing in the condenser is excluded from co warranties and the heat exchanger
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack
water­Appendix A -
information.
used with R­refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping
system failure.
9
To prevent motor overheating compressors must cycle off for a
To maintain the proper oil level compressors must cycle on for a
starts per hour.
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
minimum of 5 minutes. The cycle rate must not exceed 6
1. Startup and service must be performed
by a Factory Trained Service Technician.
2. The unit is for indoor use only. See
General Information section for more unit information.
3. Every unit has a unique equipment
nameplate with electrical, operational, and unit clearance specifications. Always refer to the unit nameplate for specific ratings unique to the model you have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
5. Keep this manual and all literature
safeguarded near or on the unit.
10

SB Series Feature String Nomenclature

:
SB - 007
- 3 - 0 - E 7 0 9 - 0 0 0
:
Model Options
GEN
SIZE
SB Series Feature String Nomenclature
MODEL OPTIONS
Series and Generation
SB
Unit Size
003 = 3 ton Capacity 004 = 4 ton Capacity 005 = 5 ton Capacity 006 = 6 ton Capacity 007 = 7 ton Capacity 009 = 9 ton Capacity 010 =10 ton Capacity 014 =14 ton Capacity 016 = 16 ton Capacity 018 = 18 ton Capacity
Voltage
1 = 230V/1Φ/60Hz 2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz 9 = 208V/1Φ/60Hz
Configuration
0 = Right Hand Unit + Top Vertical Discharge A = Left Hand Unit + Top Vertical Discharge
A1: Refrigerant Style
E = R-410A Variable Capacity Scroll Compressor
A2: Unit Configuration
0 = Water-Cooled Condenser - Condensing Unit Only 7 = Water-Source/Geothermal Heat Pump + Std Evap. Coil - Coaxial Heat Exchanger 8 = Water-Source/Geothermal Heat Pump + 6 Row Evap. Coil - Coaxial Heat Exchanger 9 = Water-Source/Geothermal Heat Pump ­Condensing Unit Only
A3: Coil Coating
0 = Standard 1 = Polymer E-Coated Cooling Coil
VLT
CONFIG
A1
A2
A3
A4
B1
B2
Unit Feature Options
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C 6A
6B
6C 7 8 9
10
11
0 0 0 0 - 0 0 0 - A B C - 0 A 0 - 0 0 0 0 0 0 Y - E 0
0 0 0 0 0 0 0 A B
15
16
17
18
A4: Cooling / Heat Pump Staging
9 = Modulating - Variable Capacity Compressor
B1: Heating Type 0 = No Heating 3 = Electric Heat C = Steam Distributing Standard Coil D = Steam Distributing Polymer E-Coated Coil E = Hot Water Standard Coil F = Hot Water Polymer E-Coated Coil
B2: Heating Designation
0 = No Heating 1 = 1 Row Coil 2 = 2 Row Coil A = 7 kW (5.3 kW @ 208V) B = 14 kW (10.5 kW @ 208V) C = 21 kW (15.8 kW @ 208V) D = 28 kW (21.0 kW @ 208V) E = 35 kW (26.3 kW @ 208V) F = 42 kW (31.5 kW @ 208V) G = 49 kW (37.0 kW @ 208V) H = 56 kW (42.0 kW @ 208V) J = 63 kW (47.3 kW @ 208V) K = 70 kW (52.5 kW @ 208V)
B3: Heating Staging
0 = No Heating 1 = 1 Stage 2 = 2 Stage 3 = 3 Stage 4 = 4 Stage 9 = Modulating/SCR Electric - Potentiometer Control A = Modulating/SCR Electric - 0-10VDC Control Signal H = Single Serpentine 8 fpi J = Half Serpentine 8 fpi K = Single Serpentine 10 fpi L = Half Serpentine 10 fpi M = Single Serpentine 12 fpi N = Half Serpentine 12 fpi
12
19
13 14A
20
21
14B
22
23
11
SB Series Feature String Nomenclature
:
1A
1C
1D 2
3 4
5A
5C
6B
6C 7 8 9
: 0 0 0 0 - 0 0 0 - A B C - 0 A 0 - 0 0 0
Model Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1B
Unit Feature Options
5B
6A
10
11
12
13 14A
14B
SB - 007 - 3 - 0 - E 7 0 9 - 0 0 0
UNIT FEATURE OPTIONS
1A: Return / Outside Air Section
0 = Standard 2 = Mixing Box - Top and Front Openings
1B: Blank
0 = Standard
1C: Filter Location
0 = Standard
1D: Mixing Box Damper Control
0 = Standard - None A = 2 Position Actuators (24V) B = Fully Modulating Actuators (DDC) C = Fixed Position Dampe r s
2: Waterside Economizer
0 = Standard - None
3: Blank
0 = Standard
4: Maintenance Options
0 = Standard A = Blower Aux. Contact - Low Voltage Terminal Block B = Remote Start/Stop Terminals - Low Voltage Terminal Block C = Options A + B
5A: Supply Air Blower Configuration
0 = No Airside - Condensing Unit Only A = 1 Blower + High Efficiency EC Motor B = 2 Blowers + High Efficiency EC Motors
5B: Supply Air Blower
0 = No Airside - Condensing Unit Only A = 310 mm (14”) Direct Drive Backwa rd C ur ve d Plenum Fan B = 355 mm (16”) Direct Drive Backward Curved Plenum Fan C = 450 mm (18”) Direct Drive Backward Curved Plenum Fan
0 0 0 0 0 0 0 A B
15
5C: Supply Air Blower Motor
0 = No Airside - Condensing Uni t Only C = 1.7 kW (2.3 hp) D = 3.0 kW (4.0 hp) E = 6.0 kW (8.0 hp)
6A: Pre-Filter Type
0 = No Pre Filter A = 2” Pleated - 30% Eff. - MERV 8
6B: Unit Filter Type
0 = No Unit Filter A = 2” Pleated - 30% Eff. - MERV 8 B = 4” Pleated - 30% Eff. - MERV 8 C = 4” Pleated - 65% Eff. - MERV 11 D = 4” Pleated - 85% Eff. - MERV 13 E = 4” Pleated - 95% Eff. - MERV 14
6C: Filter Options
0 = Standard A = Clogged Filter Switch B = Magnehelic Gauge C = Options A + B
7: Refrigeration Control
0 = Standard C = Freeze Stat - Each Circuit
8: Refrigeration Options
0 = Standard D = Modulating Hot Gas Reheat
9: Refrigeration Accessories
0 = Standard A = Sight Glass B = Compressor Isolation Valves C = Options A + B
0 0 0 Y - E 0
16
17
18
19
20
21
22
23
12
SB Series Feature String Nomenclature
:
11
0 0 0 Y - E 0
0 0 0
0
15
16
18
Model Options
GEN
SIZE
VLT CONFIG A1
A2
A3
A4 B1
B2
B3 1A
1B
1C
1D 2 3 4 5A
SB - 007 - 3 - 0 - E 7 0 9 - 0 0 0 : 0 0 0 0 - 0 0 0 - A B C - 0 A 0 - 0 0 0
10: Power Options
0 = Standard Power Block
11: Safety Options
0 = Standard C = Supply Air Smoke Detector H = Remote Safety Shutoff Terminals L = Options A + H
12: Controls
0 = Standard A = Low Limit Controls B = Phase and Brown Out Protection C = Options A + B
13: Special Controls
D = VAV Unit Controller - VAV Cool + CV Heat Y = VAV Single Zone Heat Pump Unit Controller ­VAV Cool + VAV Heat Z = Constant Volume Heat Pump Unit Controller ­CV Cool + CV Heat 1 = Make Up Air Heat Pump Unit Controller - CV Cool + CV Heat 5 = Field Installed DDC C ontrols by Others with Isolation Relays 6 = Factory Installed DDC Controls Furnished by Others with Isolation Relays
14A: Water-Cooled Co ndenser
0 = Standard - None B = Water Flow Switch E = Balancing Valves + Option B H = Motorized Shut-Off Valve + Option B J = Head Pressure Control + Option B L = Balancing Valves + Option H M = Balancing Valves + Option J T = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option B W = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option E 1 = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option H 2 = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option J 4 = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option L
5 = CuNi Corrosion Resistant Coaxial Heat Exchanger + Option M
14B: Waterside Economizer Piping 0 = Standard - None
15: Glycol Percentage
0 = Standard - None A = Minimum 20% Propylene Glycol B = Minimum 40% Propylene Glycol
16: Interior Cabinet Options
0 = Standard - Double Wall Construction + R-6.5 Foam Insulation + Stainless Steel Drain Pan A = Overflow Switch B = Compressor Sound Blanket C = Options A + B
17: Exterior Cabinet Options
0 = Standard A = AAON Gray Exterior Paint B = Special Paint C = Interior Corrosion Protection D = Options A + C
18: Blank
0 = Standard
Unit Feature Options
5B
5C 6A
6B
6C 7 8 9
10
12
13
14A
14B
0 0 0 A B
19
20
21
22
17
23
13
SB Series Feature String Nomenclature
:
0 0 0 A B
Model Options
GEN
SIZE
VLT CONFIG A1
A2
A3
A4 B1
B2
B3 1A
1B
1C
1D 2 3 4 5A
SB - 007 - 3 - 0 - E 7 0 9 - 0 0 0 : 0 0 0 0 - 0 0 0 - A B C - 0 A 0 - 0 0 0 0 0 0 Y - E 0
19: Code Options
0 = Standard - ETL U.S.A. Listing
20: Crating
0 = Standard A = Export Crating B = Forkliftable Base - 5” Base D = Options A + B E = Shipping Shrink Wrap
22: Control Vendors
0 = Standard A = WattMaster Orion Controls System
23: Type
B = Standard X = Special Pricing Authorization
F = Options B + E G = Options A + B + E
21: Unit Splits
0 = Standard - One Piece Unit A = Two Piece Unit - One Compressorized Section + One Air Tunnel Section
Unit Feature Options
5B
5C 6A
6B
6C 7 8 9
0 0 0 0
15
10
11
12
13
14A
16
17
18
19
20
21
22
14B
23
14
Coils and sheet metal surfaces be taken when working with
recovery, recycling, or reclaiming must be followed.
“construction heater” at anytime during any phase of construction. Very low return air temperatures,
CAUTION
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
WARNING

General Information

SB Series self contained units have been designed for indoor installation only. Units are assembled, wired, charged and run­tested at the factory.
personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
These units must not be used as a
harmful vapors, and misplacement of the filters will damage the unit and its efficiency.
Certification of Steam or Hot Water Heat Models
a. Certified as a forced air heating system
with cooling.
b. Certified for indoor installation only.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with cooling.
b. Certified for indoor installation only.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with electrically operated compressors.
b. Certified for indoor installation only. c. Certified with refrigerant R-410A coils.

Codes and Ordinances

SB Series units have been tested and certified, by ETL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook.
Installation of units must conform to the ICC standards of the International Mechanical Code, the International Building Code, Installation of Air Conditioning and Ventilating Systems Standard, NFPA 90A, and local building, plumbing and waste water codes. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of
present sharp edges and care must equipment.
15
To prevent motor overheating compressors must cycle off for a
oil level
compressors must cycle on for a
starts per hour.
WARNING
Failure to observe the following
WARNING
instructions will result in premature failure of your system and possible voiding of the warranty.

Receiving Unit

When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted on the carrier’s Freight Bill. A request for inspection by carrier’s agent should be made in writing at once.
Nameplate should be checked to ensure the correct model sizes and voltages have been received to match the job requirements.
If repairs must be made to damaged goods, then the factory should be notified before any repair action is taken in order to protect the warranty. Certain equipment alteration, repair, and manipulation of equipment without the manufacturer’s consent may void the product warranty. Contact the AAON Warranty Department for assistance with handling damaged goods, repairs, and freight claims: (903) 236-4403.
Note: Upon receipt check shipment for items that ship loose such as filters and remote sensors. Consult order and shipment documentation to identify potential loose­shipped items. Loose-shipped items may have been placed inside unit cabinet for security. Installers and owners should secure all doors with locks or nuts and bolts to prevent unauthorized access.
The warranty card must be completed in full and returned to AAON not more than 3 months after unit is delivered.
16
Figure 1 - Lockable Handle

Storage

If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose-shipped items.

Direct Expansion (DX) Systems

COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper minimum of 5 minutes. The cycle rate must not exceed 6
Loading...
+ 36 hidden pages