AAON RQ-006 User Manual

RQ SERIES
Packaged Rooftop Units, Heat Pumps,
& Outdoor Air Handling Units
Do not touch any electrical switch; do not
Immediately call your gas supplier from a phone remote from the building. Follow the
If you cannot reach your gas supplier, call
Startup and service must be performed by a
WARNING
service instructions in this manual.
WARNING
& Maintenance
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Be sure to read and understand the installation, operation and
Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.
A copy of this IOM should be kept with the unit.
o Do not store gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance
o WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
use any phone in your building.
Leave the building immediately.
gas supplier’s instructions.
the fire department.
o
Factory Trained Service Technician.
Table of Contents
Safety .............................................................................................................................................. 9
RQ Series Feature String Nomenclature ....................................................................................... 14
General Information ...................................................................................................................... 23
Codes and Ordinances............................................................................................................... 23
Receiving Unit .......................................................................................................................... 24
Packaged Direct Expansion (DX) Units ................................................................................... 25
Gas or Electric Heating ............................................................................................................. 26
Wiring Diagrams ....................................................................................................................... 27
Condensate Drain Pan ............................................................................................................... 27
Installation..................................................................................................................................... 28
Unit Location ............................................................................................................................ 28
Setting the Curb ........................................................................................................................ 28
Forklifting the Unit ................................................................................................................... 31
Lifting the Unit ......................................................................................................................... 32
Vertical Duct Connection ......................................................................................................... 34
Seismic Curb Installation .......................................................................................................... 35
Horizontal Duct Connection ..................................................................................................... 37
Outside Air Rain Hood ............................................................................................................. 37
Metal Mesh Filters .................................................................................................................... 38
Electrical ................................................................................................................................... 39
Thermostat Control Wiring ................................................................................................... 41
Gas Heating ............................................................................................................................... 41
Maximum Piping Capacities ................................................................................................. 42
Piping Sizing Examples ........................................................................................................ 42
Inlet and Manifold Pressures ................................................................................................ 43
Gas Pressure Regulator & Overpressure Protection Device ................................................. 43
Additional Gas Piping Considerations .................................................................................. 44
Leak Testing.......................................................................................................................... 45
Refrigerant-to-Water Heat Exchanger ...................................................................................... 45
Open Loop Applications ....................................................................................................... 45
Freezing Water in the Heat Exchanger ................................................................................. 46
Water Piping ......................................................................................................................... 47
Condensate Drain Piping .......................................................................................................... 49
3
Discharge and Suction Line Piping ........................................................................................... 49
Heating Coils ............................................................................................................................ 52
Chilled Water Coil .................................................................................................................... 52
Startup ........................................................................................................................................... 53
Filters ........................................................................................................................................ 53
Adjusting Refrigerant Charge ................................................................................................... 53
Checking Liquid Sub-Cooling .............................................................................................. 54
Checking Evaporator Superheat ........................................................................................... 54
Adjusting Sub-Cooling and Superheat Temperatures ........................................................... 54
Gas Heater Instructions ............................................................................................................. 57
Supply Fan EC Motor Startup................................................................................................... 58
Condenser Fan EC Motor Startup ............................................................................................. 59
Operation....................................................................................................................................... 60
Thermostat Operation ............................................................................................................... 60
Packaged DX Cooling Operation and Control .......................................................................... 60
Gas Heater Operation ................................................................................................................ 60
Electric Heating Operation ....................................................................................................... 61
Steam or Hot Water Preheating and Heating Operation ........................................................... 61
Chilled Water or Non-Compressorized DX Cooling Operation ............................................... 61
Maintenance .................................................................................................................................. 62
Gas Heating ............................................................................................................................... 62
Gas Heat Exchanger Removal .................................................................................................. 63
DX Cooling ............................................................................................................................... 63
Condenser Fan .......................................................................................................................... 64
Condensate Drain Pans ............................................................................................................. 64
Evaporator Coil ......................................................................................................................... 64
E-Coated Coil Cleaning ............................................................................................................ 65
Microchannel Coil Cleaning ..................................................................................................... 67
Supply Fan ................................................................................................................................ 67
Phase and Brownout Protection ................................................................................................ 68
Variable Capacity Compressor Controller ................................................................................ 70
Filter Replacement .................................................................................................................... 71
Replacement Parts ..................................................................................................................... 72
Appendix A - Heat Exchanger Corrosion Resistance ................................................................... 73
4
Appendix B - Thermistor Temperature vs. Resistance Values ..................................................... 75
RQ Series Startup Form ................................................................................................................ 76
Maintenance Log .......................................................................................................................... 80
Literature Change History............................................................................................................. 81
R94490 · Rev. D · 130530
5
Index of Tables and Figures
Tables:
Table 1 - Electric and Gas Heating Capacities ............................................................................. 26
Table 2 - Auxiliary Electric Heating Capacities ........................................................................... 27
Table 3 - Unit Clearances ............................................................................................................. 28
Table 4 - Control Wiring ............................................................................................................... 41
Table 5 - 2-6 ton Gas Connections ............................................................................................... 41
Table 6 - Natural Gas (ft3/hr) ........................................................................................................ 42
Table 7 - Propane (kBtu/hr) .......................................................................................................... 42
Table 8 - Gas Piping Supports ...................................................................................................... 43
Table 9 - Glycol Freezing Points .................................................................................................. 47
Table 10 - Condenser Water Connections .................................................................................... 47
Table 11 - Hot Water Coil Connection Sizes ................................................................................ 52
Table 12 - Steam Coil Connection Sizes ...................................................................................... 52
Table 13 - Chilled Water Coil Connection Sizes .......................................................................... 52
Table 14 - Acceptable Refrigeration Circuit Values ..................................................................... 54
Table 15 - R-410A Refrigerant Temperature-Pressure Chart ....................................................... 56
Table 16 - EC Condenser Fan Cycling Options ............................................................................ 59
Table 17 - Demand Signal vs. Compressor Capacity Modulation ................................................ 70
Table 17 - RQ Series 2-6 ton Pre Filters ....................................................................................... 71
Table 18 - RQ Series 2-6 ton Unit Filters ..................................................................................... 72
Table 19 - RQ Series 2-6 ton Energy Recovery Wheel Filters ..................................................... 72
6
Figures:
Figure 1 - Lockable Handle .......................................................................................................... 24
Figure 2 - RQ Series Orientation .................................................................................................. 28
Figure 3 - RQ Cabinet Standard and Power Exhaust Gasket Locations ....................................... 30
Figure 4 - Forklifting an RQ Series Unit from the Side ............................................................... 31
Figure 5 - Forklifting an RQ Series Unit from the Front .............................................................. 31
Figure 6 - Lifting Details of a 2-6 ton Standard or Power Exhaust Unit ...................................... 32
Figure 7 - Lifting Details of a 2-6 ton Energy Recovery Wheel Unit .......................................... 33
Figure 8 - Vertical Duct Connection ............................................................................................. 34
Figure 9 - Solid Bottom Seismic Curb with Filters ...................................................................... 35
Figure 10 - Seismic Solid Bottom Curb without Filters Cross Section ........................................ 36
Figure 11 - Seismic Solid Bottom Curb without Filters Detail A................................................. 36
Figure 12 - Seismic Solid Bottom Curb without Filters Detail B ................................................. 36
Figure 13 - Seismic Rigid Mount Curb Cross Section ................................................................. 37
Figure 14 - Horizontal duct connections ....................................................................................... 37
Figure 15 - RQ Series unit Closed Rain Hood .............................................................................. 38
Figure 16 - RQ Series unit Open Rain Hood ................................................................................ 38
Figure 17 - Rain Hood with Metal Mesh Filter Rack Installation ................................................ 38
Figure 18 - Unit Base Utility Entry............................................................................................... 39
Figure 19 - Back View of Power Switch from Control Compartment ......................................... 39
Figure 20 - RQ Series Gas Heat Exchanger .................................................................................. 42
Figure 21 - Example 2-6 ton through the Base Gas Piping .......................................................... 44
Figure 22 - Post Corner Hole Location ......................................................................................... 50
Figure 23 - Post Back Hole Location ............................................................................................ 50
Figure 24 - Post Corner Hole Piping............................................................................................. 51
Figure 25 - Post Back Hole Location ............................................................................................ 51
Figure 26 - Gas Heater Instructions .............................................................................................. 57
Figure 27 - PIN Connectors on EC Supply Fan Motor Electronics .............................................. 58
Figure 28 - Gas Heat Exchanger ................................................................................................... 63
Figure 29 - Removal of a Condenser Fan Assembly .................................................................... 64
Figure 30 - Evaporator Coil Access .............................................................................................. 65
Figure 31 - 2-6 ton Supply Fan ..................................................................................................... 68
Figure 32 - RQ Supply Fan Removal Bolts .................................................................................. 68
Figure 33 - RQ Supply Fan Removal Slide .................................................................................. 68
Figure 34 - Voltage Monitor ......................................................................................................... 68
Figure 35 - Variable Capacity Compressor Controller ................................................................. 70
Figure 36 - Compressor Controller Flash Code Details................................................................ 71
Figure 37 - RQ Series 2-6 ton Standard Filter Layout .................................................................. 72
7
8

Safety

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
Before servicing, disconnect all
electrical power to the furnace. More than one disconnect may be provided.
When servicing controls, label all
wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with key-lock or nut and bolt.
WARNING
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit. Shut off main gas supply. Do not touch any electric switch. Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections and shut off valves.
CAUTION
Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
WARNING
9
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD
Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.
WARNING
WARNING
During installation, testing, servicing and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks.
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts that can cause serious injury. Do not open door containing fans until the power to the unit has been disconnected and fan wheel has stopped rotating.
WARNING
GROUNDING REQUIRED
All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.
WARNING
Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
CAUTION
10
UNIT HANDLING
To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
WARNING
Failure to properly drain and vent coils when not in use during freezing temperature may result in coil and equipment damage.
CAUTION
Rotation must be checked on all MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection
CAUTION
WATER PRESSURE
Prior to connection of condensing water supply, verify water pressure is less than maximum pressure shown on unit nameplate. To prevent injury or death due to instantaneous release of high pressure water, relief valves should be field supplied on system water piping.
WARNING
Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.
WARNING
Always use a pressure regulator, valves and gauges to control incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.
WARNING
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than
8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
CAUTION
Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturers usage instructions. Failure to follow instructions may result in equipment damage, injury or death.
WARNING
11
WATER FREEZING
Failure of the condenser due to freezing will allow water to enter the refrigerant circuit and will cause extensive damage to the refrigerant circuit components. Any damage to the equipment as a result of water freezing in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
CAUTION
Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latch are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.
CAUTION
Cleaning the cooling tower or condenser water loop with harsh chemicals such as hydrochloric acid (muriatic acid), chlorine or other chlorides, can damage the refrigerant-to-water heat exchanger. Care should be taken to avoid allowing chemicals to enter the refrigerant-to-water heat exchanger. See Appendix A - Heat Exchanger Corrosion Resistance for more information.
CAUTION
OPEN LOOP APPLICATIONS
Failure of the condenser as a result of chemical corrosion is excluded from coverage under AAON Inc. warranties and the heat exchanger manufacturer’s warranties.
WARNING
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
12
1. Startup and service must be performed
by a Factory Trained Service Technician.
2. Use only with type of the gas approved
for the furnace. Refer to the furnace rating plate.
3. The unit is for outdoor use only. See
General Information section for more information.
4. Provide adequate combustion ventilation
air to the furnace. If a vent duct extension is used, a class III approved vent is required. See the Locating Units and Gas Heating sections of the Installation section of the manual.
5. Always install and operate furnace
within the intended temperature rise range and duct system external static pressure (ESP) as specified on the unit nameplate.
6. The supply and return air ducts must be
derived from the same space. It is recommended ducts be provided with access panels to allow inspection for duct tightness. When a down flow duct is used with electric heat, the exhaust duct should be an L shaped duct.
7. Clean furnace, duct and components
upon completion of the construction setup. Verify furnace operating conditions including input rate, temperature rise and ESP.
8. Every unit has a unique equipment
nameplate with electrical, operational, and unit clearance specifications. Always refer to the unit nameplate for specific ratings unique to the model you have purchased.
9. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
10. Keep this manual and all literature
safeguarded near or on the unit.
13

RQ Series Feature String Nomenclature

Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RQ005 – 3V – BB 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
BASE MODEL
SERIES AND GENERATION
RQ
UNIT SIZE
002 = 2 ton Capacity 003 = 3 ton Capacity 004 = 4 ton Capacity 005 = 5 ton Capacity 006 = 6 ton Capacity
VOLTAGE
1 = 230V/1Φ/60Hz 2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz 9 = 208V/1Φ/60Hz
DISCHARGE/RETURN CONFIGURATION AND INTERIOR CORROSION PROTECTION
V = Vertical Discharge and Return H = Horizontal Discharge and Return J = Option H + Interior Corrosion Protection W = Option V + Interior Corrosion Protection K = Vertical Discharge and Horizontal Return L = Option K + Interior Corrosion Protection M = Horizontal Discharge and Vertical Return N = Option M + Interior Corrosion Protection
Model Option A: COOLING/HEAT PUMP
A1: REFRIGERANT STYLE
0 = Air Handling Unit B = R-410A - Non-Compressorized DX Air Handling Unit C = R-410A - Standard Efficiency E = R-410A Variable Capacity Scroll Compressor ­High Efficiency F = R-410A Variable Capacity Scroll Compressor ­Standard Efficiency G = R-410A Two-Step Compressor - High Efficiency H = R-410A Two-Step Compressor - Standard Efficiency
A2: UNIT CONFIGURATION
0 = No Cooling A = Air-Cooled Cond. + Std Evap. Coil B = Air-Cooled Cond. + 6 Row Evap. Coil J = Water-Cooled Cond. + Std Evap. Coil K = Water-Cooled Cond. + 6 Row Evap. Coil U = Chilled Water Coil - 4 Row W = Chilled Water Coil - 6 Row 2 = Non-Compressorized + Std Evap. Coil 4 = Non-Compressorized + 6 Row Evap. Coil 6 = Air-Source Heat Pump 7 = Water-Source/Geothermal Heat Pump
14
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Model Option A: COOLING/HEAT PUMP
A3: COIL COATING
0 = Standard 1 = Polymer E-Coated Evap. and Cond. Coils 8 = Polymer E-Coated Cond. Coil 9 = Polymer E-Coated Cooling Coil A = Stainless Steel Evap. Coil Casing + Polymer E­Coated Cond. Coil D = Stainless Steel Cooling Coil Casing
A4: COOLING/HEAT PUMP STAGING
0 = No Cooling 1 = 1 Stage 2 = 2 Stage 9 = Modulating - Lead VCC B = 1 Stage + 1 Stage Auxiliary Heat C = 2 Stage + 1 Stage Auxiliary Heat E = Modulating - Lead VCC + 1 Stage Aux. Heat H = Single Serpentine 8 fpi J = Half Serpentine 8 fpi K = Single Serpentine 10 fpi L = Half Serpentine 10 fpi M = Single Serpentine 12 fpi N = Half Serpentine 12 fpi P = 1 Stage + 2 Stage Auxiliary Heat Q = 2 Stage + 2 Stage Auxiliary Heat S = Modulating - Lead VCC + 2 Stage Aux. Heat U = 1 Stage + 4 Stage Auxiliary Heat V = 2 Stage + 4 Stage Auxiliary Heat Y = Modulating - Lead VCC + 4 Stage Aux. Heat
Model Option B: HEATING
B1: HEATING TYPE
0 = No Heating 1 = Electric Heat 2 = Natural Gas Aluminized 3 = Natural Gas Stainless Steel 4 = High Altitude Natural Gas Aluminized 5 = High Altitude Natural Gas Stainless Steel 6 = LP Gas Aluminized 7 = LP Gas Stainless Steel 8 = High Altitude LP Gas Aluminized 9 = High Altitude LP Gas Stainless Steel C = Steam Distributing Standard D = Steam Distributing Polymer E-Coated E = Hot Water Standard F = Hot Water Polymer E-Coated
B2: HEATING DESIGNATION
0 = No Heating 1 = Heat 1 2 = Heat 2 3 = Heat 3 4 = Heat 4 5 = Heat 5 7 = Heat 7 H = 1 Row Coil J = 2 Row Coil
15
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Model Option B: HEATING
B3: HEATING STAGING
0 = No Heating 1 = 1 Stage 2 = 2 Stage 3 = 3 Stage 4 = 4 Stage 9 = Modulating Gas/SCR Electric A = SCR Electric, 0-10V External Control H = Single Serpentine 8 fpi J = Half Serpentine 8 fpi M = Single Serpentine 12 fpi N = Half Serpentine 12 fpi
Feature 1: RETURN/OUTSIDE AIR
1A: RETURN/OUTSIDE AIR SECTION
0 = Manually Adjustable OA Opening + RA Opening A = Economizer B = Econ + Power Exhaust F = Low cfm Total Energy Recovery Wheel G = Low cfm Total ERW + Bypass Damper H = Low cfm Sensible ERW J = Low cfm Sensible ERW + Bypass Damper K = 100% Outside Air - No Return Air Opening L = Motorized Outside Air Damper + RA Opening M = Motorized Outside Air Damper - No RA Opening N = Empty ERW Option Box- No Power Exhaust P = Empty ERW Option Box + Power Exhaust 5 = 100% Return Air
16
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3
4
5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 1: RETURN/OUTSIDE AIR
1B: RETURN/EXHAUST AIR BLOWER CONFIGURATION
0 = Standard – None A = 1 Blower + Standard Eff. Motor C = 1 Blower + Premium Eff. Motor E = 1 Blower + Premium Eff. Motor + 1 VFD H = 1 Blower + High Efficiency EC Motor J = 1 Blower + Single Phase Motor + Speed Control
1C: RETURN/EXHAUST AIR BLOWER
0 = Standard - None B = 15” Backward Curved Plenum J = 15” Backward Curved Plenum - 70% Width N= 16” Axial Flow
1D: RETURN/EXHAUST AIR BLOWER MOTOR
0 = Standard - None A = 0.25 hp - 850 rpm B = 0.5 hp - 1075 rpm C = 1 hp - 1750 rpm D = 2 hp - 1760 rpm W = 0.75 hp - 1760 rpm Z = 0.167 hp - 825 rpm
Feature 2: OUTSIDE AIR CONTROL
0 = Standard - None A = 3 Position Actuator - Sensible Limit B = 3 Position Actuator - Enthalpy Limit C = Fully Modulating Actuator - Sensible Limit D = Fully Modulating Actuator - Enthalpy Limit E = DDC Actuator M = 3 Pos. Act. - Sensible Limit + CO2 Override N = 3 Pos. Act. - Enthalpy Limit + CO2 Override P = Fully Mod. Act. - Sensible + CO2 Override Q = Fully Mod. Act. - Enthalpy + CO2 Override R = DDC Actuator + CO2 Override S = Dual Minimum Position Potentiometers + Fully Mod. Act. - Sensible Limit T = Dual Minimum Position Potentiometers + Fully Mod. Act. - Enthalpy Limit U = 2 Position Actuator
Feature 3: HEAT OPTIONS
0 = Standard - None E = Discharge Air Override K = Auxiliary Heat K L = Auxiliary Heat L M = Auxiliary Heat M N = Auxiliary Heat N
17
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3
4
5A
5B
5C
6A
6B
6C
7 8 9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 BP J C0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 4: MAINTENANCE OPTIONS
0 = Standard - None A = Field Wired 115V Outlet B = Factory Wired 115V Outlet C = Blower Aux. Contact D = Remote Start/Stop Terminals E = Options A + C F = Options A + D G = Options B + C H = Options B + D J = Options A + C + D K = Options B + C + D L = Options C + D
Feature 5: SUPPLY AIR OPTIONS
5A: SUPPLY AIR BLOWER CONFIGURATION
P = 1 Blower + High Efficiency EC Motor Q = 1 Blower + Inverter Rated Motor + 1 VFD R = 1 Blower + Single Phase Motor + Speed Control
5B: SUPPLY AIR BLOWER
J = 18.5” Direct Drive Backward Curved Plenum K = 18.5” Direct Drive BC Plenum - 60% Width
5C: SUPPLY AIR BLOWER MOTOR
A = 0.25 hp - 850 rpm B = 0.5 hp - 1075 rpm C = 1 hp - 1750 rpm D = 2 hp - 1760 rpm W = 0.75 hp - 1760 rpm Z = 0.167 hp - 825 rpm
Feature 6: FILTERS
6A: PRE FILTER
0 = Standard - None A = 2” Pleated - 30% Eff. - MERV 8 B = Metal Mesh Outside Air Filter C = Lint Screen Filter D = Exhaust Air ERW Filter E = Option A + B F = Option A + D G = Option B + D H = Option A + B + D
6B: UNIT FILTER
0 = 2” Throwaway A = 2” Pleated - 30% Eff. - MERV 8
B = 4” Pleated - 30% Eff. - MERV 8 C = 2” Permanent Filter + Replaceable Media F = 4” Pleated - 65% Eff. - MERV 11 G = 4” Pleated - 85% Eff. - MERV 13 H = 4” Pleated - 95% Eff. - MERV 14
6C: FILTER OPTIONS
0 = Standard A = Clogged Filter Switch B = Magnehelic Gauge C = Options A + B
18
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C
7
8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 7: REFRIGERATION CONTROL
0 = Standard A = 5 Min. Time Delay Relay - Comp. Off C = Fan Cycling D = Adjustable Lockouts - Each Circuit E = Freeze Stats - Each Circuit G = Options A + C H = Options A + D J = Options A + E N = Options C + D P = Options C + E Q = Options D + E U = Options A + C + D V = Options A + C + E W = Options A + D + E 2 = Options C + D + E 6 = Options A + C + D + E
Feature 8: REFRIGERATION OPTIONS
0 = Standard C = Hot Gas Reheat D = Modulating Hot Gas Reheat E = 0°F Low Ambient Lead Stage M = Polymer E-Coated Hot Gas Reheat N = Polymer E-Coated Modulating Hot Gas Reheat
Feature 9: REFRIGERATION ACCESSORIES
0 = Standard A = Sight Glass B = Compressor Isolation Valves C = Options A + B D = ECM Condenser Fan - Multiple Speed E = ECM Condenser Fan – Head Pressure Control G = Options A + D H = Options B + D J = Options A + B + D K = Options A + E L = Options B + E M = Options A + B + E
Feature 10: POWER OPTIONS
0 = Standard Power Block A = 100 Amp Power Switch B = 150 Amp Power Switch F = 60 Amp Power Switch
Feature 11: SAFETY OPTIONS
0 = Standard A = Return and Supply Air Firestat B = Return Air Smoke Detector C = Supply Air Smoke Detector D = Options B + C E = Options A + B F = Options A + C G = Options A + B + C H = Remote Safety Shutoff Terminals J = Options A + H K = Options B + H L = Options C + H M = Options D + H N = Options A + B + H P = Options A + C + H Q = Options A + D + H
19
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L 0 0 – 0 0 B 0 0 0 0 0 B
Feature 12: CONTROLS
0 = Standard A = Low Limit Controls B = Phase and Brown Out Protection C = Energy Recovery Wheel Defrost D = Energy Recovery Wheel Rotation Detection E = Compressor Power Factor Correction F = Options A + B G = Options A + C H = Options A + D J = Options A + E K = Options B + C L = Options B + D M = Options B + E N = Options C + D P = Options C + E Q = Options D + E R = Options A + B + C S = Options A + B + D T = Options A + B + E U = Options A + C + D V = Options A + C + E W = Options A + D + E Y = Options B + C + D Z = Options B + C + E 1 = Options B + D + E 2 = Options C + D + E 3 = Options A + B + C + D 4 = Options A + B + C + E 5 = Options A + B + D + E 6 = Options A + C + D + E 7 = Options B + C + D + E 8 = Options A + B + C + D + E
Feature 13: SPECIAL CONTROLS
0 = Terminal Block D = VAV Unit Controller - VAV Cool + CV Heat E = Constant Volume Unit Controller - CV Cool + CV Heat F = Makeup Air Unit Controller - CV Cool + CV Heat J = Factory Installed DDC Controls Furnished by Others K = Factory Installed DDC Controls Furnished by Others with Isolation Relays L = Terminal Block for Thermostat Control with Isolation Relays W = Terminal Block for Variable Capacity Compressor Thermostat Y = VAV Single Zone Heat Pump Unit Controller ­VAV Cool + VAV Heat Z = Constant Volume Heat Pump Unit Controller ­CV Cool + CV Heat 1 = Makeup Air Heat Pump Unit Controller - CV Cool + CV Heat 2 = VAV Single Zone Unit Controller VAV Cool + CV Heat 3 = VAV Single Zone Unit Controller VAV Cool + VAV Heat 4 = Field Installed DDC Controls by Others 5 = Field Installed DDC Controls Furnished by Others with Isolation Relays 6 = Factory Installed DDC Controls Furnished by Others with Isolation Relays (SPA)
Feature 14: PREHEAT
14A: PREHEAT CONFIGURATION
0 = Standard - None A = Steam Distributing Preheat Coil - 1 Row C = Hot Water Preheat Coil - 1 Row
14B: PREHEAT SIZING
0 = Standard – None A = Single Serpentine 8 fpi B = Half Serpentine 8 fpi E = Single Serpentine 12 fpi F = Half Serpentine 12 fpi
20
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 15: Glycol Percentage
0 = Standard A = 20% Propylene Glycol B = 40% Propylene Glycol C = Field Adjustable for Glycol Percentage
Feature 16: INTERIOR CABINET OPTIONS
0 = Standard B = Service Lights
Feature 17: EXTERIOR CABINET OPTIONS
0 = Standard A = Base Insulation B = Burglar Bars D = Options A + B
Feature 18: CUSTOMER CODE
0 = Standard
Feature 19: CODE OPTIONS
0 = Standard - ETL U.S.A. Listing A = M.E.A. B = Chicago - Cool + Gas C = Chicago - Cool + Electric Heat D = Chicago - Cool Only E = Chicago - Gas Only F = Chicago - Electric Heat Only G = Chicago - No Cool + No Heat H = ETL U.S.A. + Canada Listing K = California OSHPD Certification L = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156) M = Seismic Construction (Non-Certified) N = California OSHPD Certification + Chicago P = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156) + Chicago Q = Seismic Construction (Non-Certified) + Chicago
Feature 20: CRATING
0 = Standard A = Export Crating B = Export Crating - No Condenser Section
Feature 21: WATER-COOLED CONDENSER
0 = Standard - None A = Balancing Valves B = Water Flow Switch C = Motorized Shut-off Valve D = Head Pressure Control E = Options A + B F = Options A + C G = Options A + D H = Options B + C J = Options B + D L = Options A + B + C M = Options A + B + D R = CuNi Coaxial Heat Exchanger S = Options A + R T = Options B + R U = Options C + R V = Options D + R W = Options A + B + R Y = Options A + C + R Z = Options A + D + R 1 = Options B + C + R 2 = Options B + D + R 3 = Options C + D + R 4 = Options A + B + C + R 5 = Options A + B + D + R
21
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 22: CONTROL VENDORS
0 = None A = WattMaster Orion Controls System B = JENEsys Control System with Web UI C = WattMaster Orion Controls System with Specials E = Remote Mounted AAON Mini Controller F = JENEsys Control System with Web UI + Fox G = JENEsys Control System with Web UI + Lon H = JENEsys Control w/Web UI + BACnet MSTP J = JENEsys Control w/Web UI + BACnet IP K = JENEsys Control w/Web UI + Modbus RTU L = JENEsys Control w/Web UI + Modbus TCP
Feature 23: TYPE
B = Standard - AAON Gray Paint U = Special Pricing Authorization + Special Paint X = Special Pricing Authorization + AAON Gray Paint 4 = Standard Paint + 5 Year Parts Only Warranty 9 = Standard Paint + 10 Year Parts Only Warranty
22

General Information

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
WARNING
These units must not be used as a
“construction heater” at any time
during any phase of construction. Very low return air temperatures, harmful vapors, and misplacement of the filters will damage the unit and its efficiency.
CAUTION
RQ Series packaged rooftop units, heat pumps and outdoor air handling units have been designed for outdoor installation only. Units are assembled, wired, charged and run tested at the factory.
Startup and service must be performed by a Factory Trained Service Technician.
Certification of Gas Heat Models
a. AAON gas heat exchangers have
successfully completed 10,000 burner operation cycles and corrosion resistance as specified per test standard ANSI
21.47. All gas heat exchangers used in AAON appliances are certified for use downstream of evaporator or cooling coils.
b. Certified as a Category III forced air
furnace with or without cooling.
c. Certified for outdoor installation only. d. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Steam or Hot Water Heat Models
a. Certified as a forced air heating system
with or without cooling.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically operated compressors.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.

Codes and Ordinances

RQ Series units have been tested and certified, by ETL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236, ANSI Safety Standard Z21.47b-2008/CSA
2.3b-2008, and ANSI Safety Standard Z83.8-2006/CSA 2.6-2006.
System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook.
23
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed.
CAUTION
Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.
WARNING
Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.
WARNING
Installation of RQ Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, and local building, plumbing and waste water codes. In the absence of local codes installation must conform to the current (United States) National Fuel Gas Code ANSI-Z223.1/NFPA 54 or the current (Canada) National Fuel & Propane Installation Code CSA B149.1 or B149.2, and Mechanical Refrigeration Code CSA B52. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
24

Receiving Unit

When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted
on the carrier’s freight bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be checked to ensure the correct model sizes and voltages have been received to match the job requirements.
If repairs must be made to damaged goods, then the factory should be notified before any repair action is taken in order to protect the warranty. Certain equipment alteration, repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact the AAON Warranty Department for assistance with handling damaged goods, repairs, and freight claims: (918) 583-2266.
Note: Upon receipt check shipment for items that ship loose such as filters and remote sensors. Consult order and shipment documentation to identify potential loose­shipped items. Loose-shipped items may have been placed inside unit cabinet for security. Installers and owners should secure all doors with locks or nuts and bolts to prevent unauthorized access.
Figure 1 - Lockable Handle
The warranty card must be completed in full
CRANKCASE HEATER
OPERATION
Some units are equipped with a compressor crankcase heater, which should be energized at least 24 hours prior to cooling operation, to clear any liquid refrigerant from the compressor.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
and returned to AAON not more than 3 months after unit is delivered.
Storage
If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose-shipped items.

Packaged Direct Expansion (DX) Units

DX refrigeration system is factory assembled, leak tested, charged with refrigerant and run tested.
Refrigerant system includes an evaporator, condenser, liquid line filter drier, thermal expansion valve (TXV), and scroll compressor. Compressor is equipped with a positive pressure forced lubrication system.
Never cut off the main power supply to the unit, except for servicing, emergency, or complete shutdown of the unit. When power is cut off from the unit crankcase heater cannot prevent refrigerant migration into the compressor. This means the compressor will cool down and liquid refrigerant may accumulate in the compressor. The compressor is designed to pump refrigerant gas and damage may occur when power is restored.
If power to the unit must be off for more than an hour, turn the thermostat system switch to "OFF", or turn the unit off at the control panel, and leave the unit off until the main power switch has been turned on again for at least 24 hours for units with compressor crankcase heaters. This will give the crankcase heater time to clear any liquid accumulation out of the compressor before it is started.
Always control the unit from the thermostat, or control panel, never at the main power supply, except for servicing, emergency or complete shutdown of the unit.
During the cooling season, if the air flow is reduced due to dirty air filters or any other reason, the cooling coil can get too cold which will cause excessive liquid to return
25
Model
Option B2
Gas Heat
Electric Heat
Input Capacity
Output Capacity
Capacity
MBH
MBH
kW (208V)
kW (230V, 460V, 575V)
1 = Heat 1
60.0
48.0
7.5
10
2 = Heat 2
15.0
20
3 = Heat 3
100.0
80.0
22.5
30
4 = Heat 4
30.0
40
5 = Heat 5
140.0
112.0
6 = Heat 6
7 = Heat 7
160.0
128.0
to the compressor. As the liquid concentration builds up, oil is washed out of the compressor, leaving it starved for lubrication.
The compressor life will be seriously shorted by reduced lubrication and the pumping of excessive amounts of liquid oil and refrigerant.
Note: Low Ambient Operation Air-cooled DX units without a low ambient option, such as condenser fan cycling, ECM driven condenser fans or the 0°F low ambient option, will not operate in the cooling mode of operation properly when the outdoor temperature is below 55°F. Low ambient and/or economizer options are recommended if cooling operation below 55°F is expected.
Note: Multiple Units with Multiple Thermostats When several heating and cooling units are used to condition a space all unit thermostat switches must be set in either heating mode, cooling mode or off. Do not leave part of the units switched to the opposite mode. Cooling only units should be switched off at the thermostat during the heating season.
Table 1 - Electric and Gas Heating Capacities

Gas or Electric Heating The unit is designed to heat a given amount of air while operating. If this amount of air is greatly reduced, approximately 1/3 during the heating season, the gas heat exchanger or electric heating coil may overheat, and may cut the burner or heater off entirely by action of the safety high temperature limit devices which are factory mounted at the heat exchanger and supply fan areas.

Airflow should be adjusted after installation to obtain an air temperature rise within the range specified on the unit rating plate at the required external static pressure.
Should overheating occur with a gas heat exchanger, or the gas supply fail to shut off, shut off the manual gas valve to the furnace before shutting off the electrical supply.
Prolonged overheating of the heat exchanger will shorten its life.
If unit has not been selected as a 100% outside air unit (makeup air unit) the return air duct must be sealed to the unit and the return air temperature must be maintained between 55F and 80F.
26
Table 2 - Auxiliary Electric Heating Capacities
Feature 3
kW (208V)
kW (230V, 460V, 575V)
*K = Heat K
7.5
10.0
*L = Heat L
15.0
20.0
*M = Heat M
22.5
30.0
*N = Heat N
30.0
40.0
Unit should not be operated without a p-trap. Failure to install a p-trap may result in overflow of condensate water.
CAUTION

Wiring Diagrams Unit specific wiring diagrams are laminated and affixed inside the compressor and control compartment door.

Condensate Drain Pan Unit requires drain trap to be connected to the condensate drain pan of the unit. Units include one drain pan connection. Condensate drain pipes or p-trap is factory supplied and shipped loose in the control compartment for field installation.

If codes require a condensate drain line, the line should be the same pipe size or larger than the drain connection, include a p-trap, and pitch downward toward drain. An air break should be used with long runs of condensate lines.
27
Location
Unit Size
2-6 tons
Front -
(Heat Exchanger)
36
Back - (Outside Air)
36
Left Side
24
Right Side
48”
Top
Unobstructed
When locating gas fired units, it is recommended the unit be installed so that the flue discharge vents are located at least 120 inches away from any opening through which combustion products could enter the building.
WARNING
Back
Right Side
Front
Distances from adjacent public walkways, adjacent buildings, operable windows and building openings, shall conform to local codes and/or the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the National Gas & Propane Code, CSA B149.1
WARNING

Installation

AAON equipment has been designed for quick and easy installation.

Unit Location

The curb should be mounted first and must be located so that duct connections will be clear of structural members of the building.
Verify rooftop or foundation can support the total unit weight, including accessory weights.
Do not position flue opening to discharge into a fresh air intake of any other piece of equipment. Unit should also be installed so that the flow of combustion intake air is not obstructed from reaching the furnace.
Vent opening must not be blocked by snow.
A minimum 12” curb must be used or the
28
vent outlet shall be greater than 12” off the ground or roof.
Flue gas is dangerously hot and contains containments. The user is responsible for determining if vent gases may degrade building materials.
The National Gas and Propane Installation Code, B149.1 specifies a 6 ft. horizontal vent terminal clearance to gas and electric meters and relief devices.
Local codes may supersede or further place restrictions on vent termination locations.
Table 3 - Unit Clearances
Figure 2 - RQ Series Orientation

Setting the Curb Make openings in roof decking large enough to allow for duct penetration and workspace

only. Do not make openings larger than
All roofing work should be performed by competent roofing contractors to avoid any possible leakage.
CAUTION
Where the supply or warm air duct passes through a combustible roof, a clearance of 1 inch must be maintained between the outside edges of the duct and combustible material in accordance with National Fire Protection Association Standard No. 90A. Provide flashings or enclosure between structure and roof and all joints must be sealed with mastic roofing to ensure a watertight seal.
CAUTION
necessary. Set the curb to coincide with the openings. Make sure the curb is level. Unit must be level in both horizontal axes to support the unit and reduce noise and vibration.
Be careful to install the provided gasket according to Figure 3 prior to setting the unit on the curb.
29
Figure 3 - RQ Cabinet Standard and Power Exhaust Gasket Locations
30
Incorrect lifting can cause damage to the unit.
CAUTION
Forks
FORKLIFTING
2-6 TON UNITS
Forks or Fork Extensions must be at
least 48” in length and must extend
44” under the unit.
CAUTION

Forklifting the Unit

Units can be lifted using a forklift. Forks must be 48” in length. Standard units can be lifted from all sides except the outside air side. Units with energy recovery wheels can only be fork lifted from the left or right side.
Forks must be perpendicular to unit. When lifting from either side, the forks must extend through to the opposite side of the
unit. When lifting from the end of the unit, the forks must extend at least 44” under the unit. When lifting with 48” forks, the back of the fork must be no more than 4” from the unit.
Figure 4 - Forklifting an RQ Series Unit from the Side
Figure 5 - Forklifting an RQ Series Unit from the Front
31

Lifting the Unit

The RQ Series units must be lifted using the lifting points in the side base rails. A spreader bar must be used to prevent the lifting straps from damaging the unit. The connection points on the spreader bar must
be 48”-60” apart. The minimum cable
length used to lift a standard length (82” base length) is 72”. The minimum cable
length to lift energy recovery units (116” base length) is 96”. The shackles used to connect the cables to the lifting points in the base should be ½” nominal size.
The rigging must be adjusted to lift the unit level. Lifting the unit off-balance may cause severe damage.
It is recommended to lift the unit with the outside air hood in the downward shipping
position. However, the unit may be lifted with the outside air hood in the open position.
Before lifting unit, be sure that all shipping material has been removed from unit. Secure hooks and cables at all lifting points provided on the unit.
Hoist unit to a point directly above the curb and duct openings. Be sure that the gasket material has been applied to curb.
Carefully lower and align the unit with utility and duct openings. Lower the unit until the unit skirt fits around the curb. Some units are designed to overhang the curb. Take care that any recessed base rails fit around the curb. Make sure the unit is properly seated on the curb and is level.
32
Figure 6 - Lifting Details of a 2-6 ton Standard or Power Exhaust Unit
Figure 7 - Lifting Details of a 2-6 ton Energy Recovery Wheel Unit
33
Do not drill or punch holes in the base of the unit, from inside the unit or from below the unit to attach ductwork. Leaking may occur if unit base is punctured.
CAUTION
Vertical Duct Connection Note: If outside air will be in contact with
the air tunnel base the unit should include the base insulation option or the base must be field insulated.
34
Figure 8 - Vertical Duct Connection

Seismic Curb Installation

Using a standard curb with a seismic unit will void the certification of the unit. All mounting details listed must be followed to achieve seismic certification. The AAON unit must be certified to ICC-ES AC156 when using a seismic curb for seismic certifications to apply. Any deviations or
modifications to the unit or curb will void all seismic certification.
Structural engineer of record must approve building anchorage to unit or curb in compliance with OSP-0180-10. Use provided self tapping screws to attach base of unit to seismic curb bracket.
Figure 9 - Solid Bottom Seismic Curb with Filters
35
Figure 10 - Seismic Solid Bottom Curb without Filters Cross Section
36
Figure 11 - Seismic Solid Bottom Curb without Filters Detail A
Figure 12 - Seismic Solid Bottom Curb without Filters Detail B
Figure 13 - Seismic Rigid Mount Curb Cross Section
Return
Supply
Horizontal Duct Connection Note: If outside air will be in contact with
the air tunnel base the unit should include the base insulation option or the base must be field insulated.
Remove shipping covers and attach duct to flanges provided on the unit. The installer is responsible for sealing ducts to the flanges to prevent water leaks.
Remove the two screws at the bottom of the rain hood that secure it in the shipping position. Remove the screws that attach the side pieces of the hood to the top of the hood.
Rotate the side pieces so that the holes along one edge line up with the holes on the top piece and the flange is on the inside of the rain hood.
Attach the side pieces to the top of the hood using the provided screws and attached the side pieces to the end of the unit through the flange.
Apply silicon caulking along the top and both sides of the rain hood. Take care to seal the top corners where the rain hood attaches to the unit.
Figure 14 - Horizontal duct connections

Outside Air Rain Hood Rain hood must be opened before startup of the unit. Fresh air intake adjustments should be made according to building ventilation or local code requirements.

37
Figure 15 - RQ Series unit Closed Rain Hood

Metal Mesh Filters Metal mesh outside air filters require installation of the filter rack on the intake of the rain hood.

Figure 16 - RQ Series unit Open Rain Hood
Clips which hold the metal mesh filters in the filter rack should face outward.
38
Figure 17 - Rain Hood with Metal Mesh Filter Rack Installation

Electrical

Figure 19 - Back View of Power Switch from Control Compartment
Electric shock hazard. Before attempting to perform any installation, service, or maintenance, shut off all electrical power to the unit at the disconnect switches. Unit may have multiple power supplies. Failure to disconnect power could result in dangerous operation, serious injury, death, or property damage.
WARNING
Utility Entry
Field
Connection
Location
Verify the unit nameplate agrees with power supply. Connect power and control wiring to the unit as shown in Figure 12 and in the unit specific wiring diagram, which shows factory and field wiring and is attached to the inside of the door of the control compartment.
Route power and control wiring, separately, through the utility entry in the base of the unit. Do not run power and control signal wires in the same conduit. The utility entry is located in the unit base in the front right hand corner of the unit (compressor compartment). See unit drawing for specific location.
Figure 18 - Unit Base Utility Entry
Size supply conductors based on the unit MCA rating. Supply conductors must be rated a minimum of 75°C.
Protect the branch circuit in accordance with code requirements. The unit must be electrically grounded in accordance with local codes, or in the absence of local codes,
39
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Supply fan, exhaust fan, and condenser fan motors should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
CAUTION
Scroll compressors are directional and will be damaged by operation in the wrong direction. Low pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should only be made at the unit power connection.
CAUTION
Three phase voltage imbalance will cause motor overheating and premature failure.
CAUTION
the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
Note: All units are factory wired for 208V, 230V, 460V, or 575V. The transformer configuration must be checked by a qualified technician prior to service, especially if unit is to be connected to a 208V or 230V supply. For 208V service interchange the yellow and red conductor on the low voltage control transformer.
Red-Black for 208V Yellow-Black for 230V
Wire power leads to the unit’s terminal block or main disconnect. All wiring beyond this point has been completed by the manufacturer and cannot be modified
without effecting the unit’s agency/safety
certification.
Supply voltage must be within the min/max range shown on the unit nameplate. Available short circuit current should not exceed the short circuit current rating (SCCR) shown on the unit nameplate.
Three phase voltage imbalance will cause motor overheating and premature failure. The maximum allowable imbalance is 2.0%.
Voltage imbalance is defined as 100 times the maximum deviation from the average voltage divided by the average voltage.
40
Example: (221V+230V+227V)/3 = 226V, then 100*(226V-221V)/226V = 2.2%, which exceeds the allowable imbalance.
Check voltage imbalance at the unit disconnect switch and at the compressor terminal. Contact your local power company for line voltage corrections.
Installing contractor must check for proper motor rotation and check blower motor amperage listed on the motor nameplate is not exceeded. Motor overload protection may be a function of the variable frequency drive and must not be bypassed.
Wire control signals to the unit’s low
Wire Size (Stranded)
- Copper Conductors Only
Total Wire Distance
Allowable
20 AWG
200 ft
18 AWG
350 ft
16 AWG
500 ft
14 AWG
750 ft
12 AWG
1250 ft
Model
Option
B2
Input
MBH
Connections
Quantity
Size
1
60.0
1
1/2”
3
100.0
5
140.0
7
160.0
FOR YOUR SAFETY Read the entire gas heating installation section of this manual before beginning installation of the gas heating section.
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
WARNING
voltage terminal block located in the controls compartment.
If any factory installed wiring must be replaced, use a minimum 105°C type AWM insulated conductors.

Thermostat Control Wiring

If a thermostat is used for unit control, thermostat should be located on an inside wall 4-5 feet above the floor where it will not be subjected to drafts, sun exposure, or heat from electrical fixtures of appliances. Control wiring must deliver adequate voltage to components to assure proper operation. Control voltage returning from controller circuit must be a minimum of 21 VAC. To assure proper wiring use the following chart to determine the allowable wiring distances.
Table 4 - Control Wiring
Take the total wire distance allowable and divide by the number of wires to be connected. This indicates the distance allowable for that size wire. The wiring to the unit must not exceed the total wire distance allowable. If the voltage at the connectors is less than 21 VAC, isolation relays must be installed. If under external control 21 VAC must be field verified.
All external devices must be powered via a separate external power supply.
Example: A total of 8 wires must be pulled 75ft to control the unit. What size wire should be used?
According to the Table 3, 16 AWG allows for 63ft (500 ft/8 wires) and 14 AWG allows for 94ft (750 ft/8 wires). Thus, 14 AWG should be used.

Gas Heating

Verify the unit nameplate agrees with the proper gas supply type and amount.
Gas piping must be installed in accordance with local codes, or in the absence of local codes, installation must conform to the current (United States) National Fuel Gas Code ANSI-Z223.1/NFPA 54 or the current (Canada) National Fuel & Propane Installation Code CSA B149.1 or B149.2.
Table 5 - 2-6 ton Gas Connections
41
Pipe Size
Length of Pipe
20 ft
50 ft.
100 ft.
150 ft.
200 ft.
1/2”
120
73
50
40
35
3/4
250
151
103
84
72
1”
465
285
195
160
135
1-1/4”
950
580
400
325
280
1-1/2”
1460
900
620
500
430
2”
2750
1680
1150
950
800
2-1/2”
4350
2650
1850
1500
1280
Pipe Size
Length of Pipe
20 ft
50 ft.
100 ft.
150 ft.
200 ft.
1/2”
189
114
78
63
55
3/4”
393
237
162
132
112
1”
732
448
307
252
213
1-1/4”
1496
913
630
511
440
1-1/2”
2299
1417
976
787
675
2”
4331
2646
1811
1496
1260
Btu
ft
MBH
1000
1080
3
After verifying gas inlet pressure and manifold pressure the service technician must time the gas flow rate through the gas meter with a stopwatch to verify the gas input rate.
Unit nameplate input rate value has been calculated at the altitude where the unit was shipped. Above 2,000 ft the input rate is adjusted 4% for every 1,000 ft.

Maximum Piping Capacities

Table 6 - Natural Gas (ft3/hr)
- Specific Gravity = 0.6, Supply Pressure ≤ 0.5 psi, Pressure Drop = 0.5” w.c.
Figure 20 - RQ Series Gas Heat Exchanger
Table 7 - Propane (kBtu/hr)
- Specific Gravity = 1.52, Supply Pressure = 11” w.c., Pressure Drop, 0.5” w.c.
Do not use gas piping smaller than unit gas connections. Natural gas pipe runs longer than 20 feet and propane gas pipe runs longer than 50 feet may require a larger supply pipe than the unit connection size. Some utility companies may also require pipe sizes larger than the minimum sizes listed.

Piping Sizing Examples A 100 ft pipe run is needed for a 1080 MBH natural gas heater. The natural gas has a rating of 1000 Btu/ft3 and a specific gravity of 0.6 (Obtain these values from the local gas supplier.)

1080 ft3/hr
42
From the natural gas maximum capacities
Pipe Size
Support Intervals
1/2” to 3/4”
Every 6 ft
3/4” to 1”
Every 8 ft
1-3/4” or Larger
(Horizontal)
Every 10 ft
1-1/4” or Larger
(Vertical)
Every Floor
Heater should be disconnected from the gas supply piping during pressure testing of the supply piping system with pressures in excess of ½ psi. Gas valves can be damaged if subjected to more than ½ psi.
CAUTION
table, at 100 ft and 1080 ft3/hr the required minimum pipe size is 2”.
A 100 ft pipe run is needed for a 270 MBH propane gas heater.
270 MBH = 270 kBtu/hr
From the propane gas maximum capacities table, at 100 ft and 270 kBtu/hr the required minimum pipe size is 1”.

Inlet and Manifold Pressures For natural gas units, the minimum inlet gas pressure to the unit is 6” w.c. and maximum inlet gas pressure to the unit is 10.5” w.c. For propane units, the minimum inlet gas

pressure to the unit is 11” w.c. and the
maximum inlet gas pressure to the unit is 13” w.c. A field provided 1/8” NPT pressure tap is required to be installed in the piping just upstream of the shutoff valve for test gage connection to allow checking of the gas supply pressure at the unit.
A factory installed pressure tap on the outlet end of the gas valve can be used to verify a manifold pressure of 3.5” w.c. for natural gas, or 10.5” w.c. for propane.
For two stage gas valves, the low stage
setting should be set at 1.1” w.c. for natural gas, 5.0” w.c. for propane. For modulating
heaters, the safety shut-off valve would be set following the instructions above, then from a provided pressure tap in the gas train immediately preceding the burner manifold the modulating valve is set to maintain a
maximum of 3.5” w.c. and a minimum of
0.4” w.c.

Gas Pressure Regulator & Overpressure Protection Device

A gas pressure regulator must be installed if natural gas supply pressure to the unit is
greater than 10.5” w.c. and less than 2 psi (55.4” w.c.) and if propane gas supply
pressure is greater than 13” w.c. and less
than 2 psi (55.4” w.c.). Regulators must comply with the latest edition of the Standard for Line Pressure Regulators, ANSI Z21.80/CSA 6.22.
Both a gas pressure regulator and overpressure protection device (OPD) must be installed if gas supply pressure to the unit is greater than 2 psi (55.4” w.c.) and less than 5 psi (138.4” w.c.), in compliance with ANSI Z21.80/CSA 6.22. For proper heater operation, pressure to the regulator MUST NOT be greater than 5 psi (138.4” w.c.).
Piping Supports
Gas supply piping must be supported directly at the connection to the unit and at intervals listed in the following table with metal straps, blocks, or hooks. Piping should not be strained or bent.
Table 8 - Gas Piping Supports
43

Additional Gas Piping Considerations Local codes will usually require a field provided and installed manual main shutoff valve and union external to the unit. Main shutoff valve should be labeled. A drip leg should be installed near the unit connection to trap sediment and condensate. Pipe joint compounds used on all gas piping connections should be resistant to liquid petroleum gases. If flexible gas piping to the unit, or in the unit, must be replaced connectors cannot be reused, only new connectors may be used.

Heat exchanger comes equipped with a condensate drain which should be plumbed
to the appropriate drain according to the (United States) National Fuel Gas Code ANSI-Z223.1/NFPA 54 or the current (Canada) National Fuel & Propane Installation Code CSA B149.1 or B149.2, the International Building Code, and any applicable local and regional codes and regulations. The condensate drain connection is located next to the gas entry location. The heat exchanger condensate drain connection from
the unit is a 5/8” barbed nylon elbow
connection.
Figure 21 - Example 2-6 ton through the Base Gas Piping
44

Leak Testing

Do not use open flame or other source of ignition for leak testing. Fire or explosion could result causing property damage, personal injury, or death.
DANGER
LEAK CHECK GAS PIPE The gas pipe in the unit should be checked for leaks before startup. Leak checking is the responsibility of the installing contractor. All connections should be checked for leaks annually after installation. Failure to leak check could result in fire, explosion, or other hazardous situations.
DANGER
Some soaps used for leak detection can be corrosive to certain metals. Rinse piping thoroughly after leak test has been completed.
CAUTION
Those sensitive to odors or gases from trace amounts of residual oils should NOT be present in the conditioned space during the startup of a gas fired installation.
WARNING

OPEN LOOP APPLICATIONS

Failure of the condenser as a result of chemical corrosion is excluded from coverage under AAON Inc. warranties and the heat exchanger manufacturer’s warranties.
WARNING
All components of gas supply system, including manual shut off valves and the piping in the interior of the unit, should be leak tested with a soap solution before operating the appliance and at least on an annual basis thereafter.
All gas fired heat exchangers are completely tested at the factory before shipment. This will remove nearly all of the oils that have been used in the manufacturing process. However, trace amounts may remain. When performing the initial startup at the jobsite, it is highly recommended that people or any
other living animals, which may be sensitive to the residual odors or gases, NOT be present in the conditioned space during the startup. In all cases, including the initial factory firing and testing, any of the gases will be under the acceptable level of concentration for human occupancy.

Refrigerant-to-Water Heat Exchanger

Condenser water pump, condenser water piping, cooling tower or geothermal loop, pressure gauges, strainers, piping insulation and all components of the waterside piping must be field installed.
Open Loop Applications
This product contains one or more refrigerant-to-water heat exchangers made of copper, which is subject to corrosion and failure when exposed to chlorides.
Do not allow water containing any form of chlorides to enter this heat exchanger.
45
OPEN LOOP APPLICATIONS
Cupronickel refrigerant-to-water heat exchangers are recommended with all open loop applications. Failure to use a Cupronickel heat exchanger may result in premature failure of your system and possible voiding of the warranty.
WARNING
Cleaning the cooling tower or condenser water loop with harsh chemicals such as hydrochloric acid (muriatic acid), chlorine or other chlorides, can damage the refrigerant-to-water heat exchanger. Care should be taken to avoid allowing chemicals to enter the refrigerant-to-water heat exchanger. See Appendix A - Heat Exchanger Corrosion Resistance for more information.
CAUTION
Common forms of chlorides include:
1. Sea water mist entering an open cooling tower system.
2. Contaminated make-up water containing salt water.
3. Disinfecting the water loop with solutions containing sodium hypochlorite.
Chlorides will result in a premature failure of the condenser.
Failure of the condenser as a result of chemical corrosion is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
Failure of the condenser will allow water to enter the refrigerant circuit and will cause extensive damage to the refrigerant circuit components. Any damage to the equipment as a result of condenser failure from chemical corrosion due to the fluid in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
46

Freezing Water in the Heat Exchanger This product contains one or more refrigerant-to-water heat exchangers. A refrigerant-to-water heat exchanger contains refrigerant in one passage and water in another passage. Water is subject to freezing at 32°F. When water freezes in a heat exchanger significant forces are exerted on the components of the heat exchanger where the water is confined.

Failure of the condenser due to freezing will allow water to enter the refrigerant circuit and will cause extensive damage to the refrigerant circuit components. Any damage to the equipment as a result of water freezing in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
Unit is capable of operating with Entering Water Temperatures (EWT) as low as 57°F, during the cooling mode, without the need for head pressure control. If the EWT is expected to be lower than 57°F or a more stable operation is desired, a factory provided head pressure control water valve option is available.
% Glycol
Ethylene
Glycol
Propylene
Glycol
20
18°F
19°F
30
7°F
9°F
40
-7°F
-6°F
50
-28°F
-27°F
Model (RQ-)
Supply and Return
Connection Size
002
3/4 Sweat
003, 004, 005, 006
1” Sweat
WATER PRESSURE Prior to connection of condensing water supply, verify water pressure is less than maximum pressure shown on unit nameplate. To prevent injury or death due to instantaneous release of high pressure water, relief valves should be field supplied on water piping. Supply water connection may require a backflow preventer to prevent supply makeup water from backing up into the public water system.
WARNING
WATER FREEZING
Failure of the condenser due to freezing will allow water to enter the refrigerant circuit and will cause extensive damage to the refrigerant circuit components. Any damage to the equipment as a result of water freezing in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
WARNING
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings and complete piping system failure.
Glycol solution should be used if ambient temperatures are expected to fall below freezing or if the loop entering water temperature to the unit is below 50°F while operating in the heating mode (heat pump units only). Adding glycol to condenser water
causes an increase in pressure drop and also results in a decrease in unit performance. A
minimum concentration of 20% glycol solution is recommended.
Table 9 - Glycol Freezing Points
Water loop piping that runs through unheated areas or outside the building should be insulated.

Water Piping Installing contractor must ensure a differential pressure switch or water flow switch is installed between the condenser water supply and return connections. This sensor provides a signal to the unit controller that water flow is present in the

refrigerant-to-water heat exchanger and the unit can operate without damaging unit components.
Table 10 - Condenser Water Connections
Only use approved water pipe material. Avoid using galvanized material for water lines/fittings as the material is corrosive and may cause fouling of the water system.
47
WATER PIPING Follow national and local codes when installing water piping. Connections to the unit should incorporate vibration eliminators to reduce noise and vibration and shutoff valves to facilitate servicing. Supply and return water piping must be at least as large as the unit connections and larger depending on length of runs, rise and bends.
CAUTION
Each heat exchanger is equipped with a refrigerant pressure relief device to relieve pressure should excessive condensing pressures (>675 psig) occur. Codes may require installing contractor to connect and route relief piping outdoors. The relief valve has a 5/8” male flare outlet connection.
CAUTION
Installing contractor is responsible for properly sizing and installing water system components. Improper fluid flow due to valves, piping, or improper pump operation may result in unacceptable unit operation and void warranty.
CAUTION
Condenser water pump must be field sized and installed between the cooling tower/geothermal loop and self-contained unit. System should be sized in accordance with the ASHRAE Handbook. Use engineering guidelines to maintain equal distances for supply and return piping and limit bend radiuses to maintain balance in the system. Balancing valves, permanent thermometers and gauges may be required.
Before connection to the unit the condenser water system should be flushed to remove foreign material that could cause condenser fouling. Install a screen strainer with a minimum of 20 Mesh ahead of the condenser inlet to prevent condenser fouling and internal tube damage.
Mineral content of the condenser water must be controlled. All make-up water has minerals in it and as the water is evaporated in the cooling tower, these minerals remain. As the mineral content of the water increases, the conductivity of the water increases.
Field provided and installed water treatment program must be compatible with stainless steel, copper, aluminum, ABS plastic, and PVC. Batch feed processes should never be
48
used as concentrated chemicals can cause corrosion. Never use hydrochloric acid (muriatic acid) or chlorine as it will corrode stainless steel.
NOTE: Ball valves should be installed in the condenser water supply and return lines for unit isolation and water flow balancing. All manual flow valves should be of the ball valve design. Globe or gate valves should not be used due to high pressure drops and poor throttling characteristics.
Pressure and temperature ports are recommended in condenser water supply and return lines for system balancing. These openings should be 5 to 10 pipe diameters from the unit water connections. To allow for mixing and temperature stabilization, wells in the water piping should extend at least ½ pipe diameter into the pipe.
Piping systems should not exceed 10 ft/sec
Unit should not be operated without a p-trap. Failure to install a p-trap may result in overflow of condensate water into the unit.
CAUTION
fluid velocity to ensure tube wall integrity and reduce noise.

Condensate Drain Piping

2-6 ton units are equipped with one condensate drain pan connection, on the right side of the unit, and are furnished with a p-trap for field installation.
All drain connections must be used and individually trapped to ensure a minimum amount of condensate accumulation in the drain pans. ABS type cement should be used to join the drain pipe connections.
Drainage of condensate directly onto the roof may be acceptable in certain areas, refer to local codes. If condensate is to drain directly onto the roof a small drip pad should be placed below the drain to protect the roof from possible damage.
If condensate is piped into the building drainage system, the drain pipe should penetrate the roof external to the unit itself. The drain line should be pitched away from the unit at least 1/8 inch per foot. On longer runs an air break should be used to ensure proper drainage.
Draw-through cooling coils will have a negative static pressure in the drain pan area. This will cause an un-trapped drain to back up due to air being pulled up through the condensate drain piping.
Condensate drain trapping and piping should conform to all applicable governing codes.

Discharge and Suction Line Piping There are two different locations to pipe out of the unit, the post corner hole location and the post back hole location. The post corner hole location is to run pipe along the roof and then down by the disconnect switch (Figure 22 and Figure 24). The post back hole location is to run the pipe along the roof, back across the coil, and come out near the blower access panel (Figure 23 and Figure 25).

When drilling the holes, use a 1 ¼ inch hole for the suction line and a 1 inch hole for the liquid line (Figure 22 and Figure 23). For pipe sizing, refer to appropriate guidelines in the condenser or condensing unit installation manual. The grommets will help seal in between the holes in the sheet metal and the piping. If you are piping through the back post foam panel, attach grommet to the inside skin of the foam part. If you are piping through post corner hole location, use caution around electrical wires. You will need to turn off power to the unit.
49
Figure 22 - Post Corner Hole Location
50
Figure 23 - Post Back Hole Location
Figure 24 - Post Corner Hole Piping
Figure 25 - Post Back Hole Piping
51
Model (RQ-)
Hot Water Coil
Connection Size
002-006
7/8”
Model (RQ-)
Steam Coil Connection
Size
002-006
2 1/8” (standard coil)/
1 1/8” (preheat coil)
Model (RQ-)

Chilled Water Coil

Connection Size
002-006
7/8”
Piping shall be in accordance with national and local codes. Pressure limiting devices, backflow preventers and all other safety requirements are the sole responsibility of the installing contractor.
WARNING

Heating Coils One or two row hot water and steam heating and preheating coils can be factory installed. All valve controls for heating operation are field supplied and field installed. Hot water and steam coil connections are spun copper tube.

Water coils should not be subjected to entering air temperatures below 38°F to prevent coil freeze-up. If air temperature across the coil is going to be below this value, use a glycol solution to match the coldest air expected.
Table 11 - Hot Water Coil Connection Sizes
Table 12 - Steam Coil Connection Sizes
Chilled Water Coil Four or six row chilled water cooling coils can be factory installed. All valve controls for cooling operation are field supplied and field installed. Chilled water coil connections are spun copper tube.
Table 13 - Chilled Water Coil Connection
Sizes
52

Startup

Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician.
WARNING
Before completing startup and leaving the unit a complete operating cycle should be observed to verify that all components are functioning properly.
CAUTION
The Clean Air Act of 1990 bans the intentional venting of refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
CAUTION
(See back of the manual for startup form.)
During startup, it is necessary to perform routine checks on the performance of the unit. This includes checking the air flow, air filters, condenser water flow, dampers, heaters, and refrigerant charge.

Filters Do not operate the unit without filters in place. Unit should be checked for correct filter placement during startup. Operation of the equipment without filters will result in a clogged evaporator coil.

Adjusting Refrigerant Charge Adjusting the charge of a system in the field must be based on determination of liquid sub-cooling and evaporator superheat. On a system with a TXV liquid sub-cooling is more representative of the charge than evaporator superheat but both measurements must be taken.

Before Charging
Unit being charged must be at or near full load conditions before adjusting the charge.
Units equipped with hot gas reheat must be charged with the hot gas reheat valves closed while the unit is in cooling mode to get the proper charge. After charging, unit should be operated in reheat (dehumidification) mode to check for correct operation.
Units equipped with heat pump options should be charged in heating mode to get the proper charge. After charging, unit should be operated in cooling mode to check for correct charge. Charge may need to be adjusted for cooling mode. If adjustments are made in the cooling mode, heating mode must be rerun to verify proper operation.
After adding or removing charge, the system must be allowed to stabilize, typically 10-15 minutes, before making any other adjustments.
53
Air-Cooled Cond./Air-Source Heat Pump
Sub-Cooling
12-18°F
Sub-Cooling with
Hot Gas Reheat
15-22°F
Superheat
8-15°F
Water-Cooled Cond./Water-Source Heat
Pump
Sub-Cooling
4-8°F
Superheat
8-15°F
DO NOT OVERCHARGE!
Refrigerant overcharging leads to excess refrigerant in the condenser coils resulting in elevated compressor discharge pressure.
CAUTION
Thermal expansion valve must be adjusted to approximately 8-15°F of suction superheat. Failure to have sufficient superheat will damage the compressor and void the warranty.
CAUTION
The type of unit and options determine the ranges for liquid sub-cooling and evaporator superheat. Refer to Table 13 below when determining the proper sub-cooling.

Checking Liquid Sub-Cooling Measure the temperature of the liquid line as it leaves the condenser coil.

Read the gauge pressure at the liquid line close to the point where the temperature was taken. You must use liquid line pressure as it will vary from discharge pressure due to condenser coil pressure drop.
Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Subtract the measured liquid line temperature from the saturated temperature to determine the liquid sub-cooling.
Compare calculated sub-cooling to Table 14 for the appropriate unit type and options.

Checking Evaporator Superheat Measure the temperature of the suction line close to the compressor.

Read gauge pressure at the suction line close to the compressor.
Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Subtract the saturated temperature from the measured suction line temperature to determine the evaporator superheat.
Compare calculated superheat to the table below for the appropriate unit type and options.
54
Table 14 - Acceptable Refrigeration Circuit
Values

Adjusting Sub-Cooling and Superheat Temperatures

The system is overcharged if the sub-cooling temperature is too high and the evaporator is fully loaded (low loads on the evaporator result in increased sub-cooling) and the evaporator superheat is within the temperature range as shown in the table above (high superheat results in increased sub-cooling).
Correct an overcharged system by reducing the amount of refrigerant in the system to lower the sub-cooling.
The system is undercharged if the superheat is too high and the sub-cooling is too low
Correct an undercharged system by adding refrigerant to the system to reduce superheat and raise sub-cooling.
If the sub-cooling is correct and the superheat is too high, the TXV may need adjustment to correct the superheat.
55
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
20
78.3
47
134.7
74
213.7
101
321.0
128
463.2
21
80.0
48
137.2
75
217.1
102
325.6
129
469.3
22
81.8
49
139.7
76
220.6
103
330.2
130
475.4
23
83.6
50
142.2
77
224.1
104
334.9
131
481.6
24
85.4
51
144.8
78
227.7
105
339.6
132
487.8
25
87.2
52
147.4
79
231.3
106
344.4
133
494.1
26
89.1
53
150.1
80
234.9
107
349.3
134
500.5
27
91.0
54
152.8
81
238.6
108
354.2
135
506.9
28
92.9
55
155.5
82
242.3
109
359.1
136
513.4
29
94.9
56
158.2
83
246.0
110
364.1
137
520.0
30
96.8
57
161.0
84
249.8
111
369.1
138
526.6
31
98.8
58
163.8
85
253.7
112
374.2
139
533.3
32
100.9
59
166.7
86
257.5
113
379.4
140
540.1
33
102.9
60
169.6
87
261.4
114
384.6
141
547.0
34
105.0
61
172.5
88
265.4
115
389.9
142
553.9
35
107.1
62
175.4
89
269.4
116
395.2
143
560.9
36
109.2
63
178.4
90
273.5
117
400.5
144
567.9
37
111.4
64
181.5
91
277.6
118
405.9
145
575.1
38
113.6
65
184.5
92
281.7
119
411.4
146
582.3
39
115.8
66
187.6
93
285.9
120
416.9
147
589.6
40
118.1
67
190.7
94
290.1
121
422.5
148
596.9
41
120.3
68
193.9
95
294.4
122
428.2
149
604.4
42
122.7
69
197.1
96
298.7
123
433.9
150
611.9
43
125.0
70
200.4
97
303.0
124
439.6
44
127.4
71
203.6
98
307.5
125
445.4
45
129.8
72
207.0
99
311.9
126
451.3
46
132.2
73
210.3
100
316.4
127
457.3
Table 15 - R-410A Refrigerant Temperature-Pressure Chart
56

Gas Heater Instructions

Figure 26 - Gas Heater Instructions
57

Supply Fan EC Motor Startup

Figure 27 - PIN Connectors on EC Supply Fan Motor Electronics
Speed adjustment is made by varying the DC voltage on pin 8 (+) & 16 (-). If WattMaster, Mini Controller, or JENEsys control systems are installed on the system then they will provide the 0-10VDC signal for speed control. The controller will be wired directly to pin 8 & 16. If a potentiometer is installed in the unit, the 10VDC output of the motor electronics will be wired through the potentiometer and then
58
back into pin 8 & 16 for speed control. By adjusting the potentiometer from 0-100% you can manually adjust the speed of the motor.
If the rotation direction is wrong, check the brown wire on the control connector and ensure that it is connected from pin 13 to pin
11. Making/Breaking this wire changes the rotation of the motor.
If there is no rotation and/or no speed
Color
Terminal
Customer Connection
Option 1
Option 2
Option 3
Option 4
Option 5
Black
0.50 BWS
L1
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
Brown
0.50 BWS
L2
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
Green
#10
EYELET
Ground
GND
GND
GND
GND
GND
Blue
0.50 BWS
Common
Common
24 VAC
24 VAC
24 VAC
24 VAC
Yellow
0.50 BWS
Signal
PWM
24 VAC
24 VAC
White
0.50 BWS
Signal 24 VAC
24 VAC
Orange
0.50 BWS
Signal
24 VAC
24 VAC
RPM
300-1100
300
500
850
1100
Rotation
CCW
CCW
CCW
CCW
CCW
ECM Toolbox ID
Variable
Speed 4
Speed 3
Speed 2
Speed 1
20% PWM RPM
300
100% PWM RPM
1100
change, try the following:
1. Check the line-to-line voltage on the
fuse block connected to the supply fan motor and ensure it is between 187VAC to 264VAC
2. Turn the potentiometer to 50%
3. Energize the BC relay by making a
blower call.
4. Check DC voltage on S1 (-) and S2 (+),
0-10VDC signal on S1 & S2 sets the speed of the motor – thus 0VDC is no speed and 10VDC is full speed.
5. If DC Voltage is present on S1 & S2
then ensure that BC (blower relay) is energized and is passing the DC voltage through to the motor. If BC is not energized then check wiring for 24VAC blower call.
6. If no DC voltage is present on S1 & S2
then check S1 (-) & S3 (+), this is the +10VDC output from the motor that is supplied to the Potentiometer for speed control.
If the following troubleshooting suggestions do not solve the issue, contact AAON for assistance.
Table 16 - EC Condenser Fan Cycling Options

Condenser Fan EC Motor Startup The fan cycling option uses a fan cycle switch to switch between one of the discrete speed inputs (see Table 16) on the motor thus cycling between two preset speeds based upon discharge pressure of the unit. By connecting 24VAC to a single or combination of the yellow, white, or orange wires, the motor will run at the discrete speeds in Table 12.

WattMaster Condenser Head Pressure Module is used for variable speed control of the motor to maintain a head pressure. The motor should be factory wired to the PWM outputs of the WattMaster Condenser Head Pressure Module. See WattMaster literature for further information (http://www.orioncontrols.com).
Note
High voltage wires out of the motor: Black & Brown – 1 Phase Line Voltage Green - Ground
Low control voltage wires out of the motor: Blue – Common Yellow Variable Speed Control
59
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING

Operation

Unit operations should be controlled with thermostat, or unit controller, never at the main power supply, except for servicing, emergency, or complete shutdown of the unit.

Thermostat Operation Heating Thermostat system switch - "Heat" Thermostat fan switch - "Auto" or "On" Thermostat temperature set to desired point.

Cooling Thermostat system switch - "Cool" Thermostat fan switch - "Auto" or "On" Thermostat temperature set to desired point.
Air Circulation Thermostat system switch - "Off" Thermostat fan switch - "Auto" or "On" No change of the thermostat temperature. With these settings, the supply blower will run continuously but the supply air will not be heated, cooled, or dehumidified.
System Off Thermostat system switch - "Off" Thermostat fan switch - "Auto" No change of the thermostat temperature. With these settings the system is shut down, with the exception of control system power.
Night and Weekend Unoccupied Operation To reduce the operating time of the unit when the space is unoccupied, such as nights and weekends, it is recommended that the temperature setting be raised about 5°F while unoccupied during the cooling season and lowered about 10°F during the heating season.
60

Packaged DX Cooling Operation and Control

When a call for cooling (G and Y1, Y2, etc.) is made the supply blower motors and compressors will energize.

Gas Heater Operation When heat (G and W1, W2, etc.) is called for the combustion motor starts and the ignition control is energized. The control sends 24 VAC to the main gas valve and high voltage to the igniter. If a burner flame has been detected within 10 seconds, the spark is extinguished and the flame continues. If a flame has not been detected after 10 seconds, the gas valve closes, the spark ceases and the induced draft blower continues to purge the heat exchanger. After 45 seconds of purge, the ignition system will attempt to light the burners again. Should no flame be detected after 3 tries, the ignition control will lock out the system. Power to the ignition control must be cycled to reset the heater control.

On a fault the gas train is shut down by a main limit located in the heat exchanger area
or by an auxiliary limit mounted in the supply fan compartment.

Electric Heating Operation When a call for heating (G and W1, W2, etc.) is made the supply blower motors and electric resistance heaters will energize. Heating is accomplished by passing electrical current through a specified amount of resistance heaters which will produce the required heat.

On a fault condition the main limit located in the supply air or the auxiliary limit located downstream the supply blower will remove power from all contactors.

Steam or Hot Water Preheating and Heating Operation

Valve control for steam and hot water heating coils are by others. Heating is accomplished by passing steam or hot water through the steam or hot water coil assembly.

Chilled Water or Non-Compressorized DX Cooling Operation

Controls for chilled water cooling coils and non-compressorized DX coil are by others.
61
Once a year, before the unit is in operation for the heating season, a qualified service technician should inspect all flue product carrying areas of the furnace and main burners for continued safe operation.
WARNING
LEAK CHECK GAS PIPE The gas pipe in the unit should be checked for leaks before startup. Leak checking is the responsibility of the installing contractor. All connections should be checked for leaks annually after installation. Failure to leak check could result in fire, explosion, or other hazardous situations.
DANGER

Maintenance

(See back of the manual for maintenance log)
At least once each year, a trained, qualified service technician should check out the unit. Fans, evaporator coils, and filters should be inspected at least monthly.

Gas Heating

Make sure all gas supply lines have been purged of air before turning on the electrical power switch. Turn the gas valve to the on position (see startup instructions). Turn the main electrical power on and set the controls to the heating mode of operation.
The combustion ventilation motor should operate. The control will automatically supply energy to the igniter and the gas valve after the heating call is made.
62
The flame sensing probe detects the presence of the flame. Should no flame be detected in 10 seconds, the ignition system will recycle. If no flame is detected after 3 tries, ignition system will lockout.
Remove the call for heating. The main gas valves should be extinguished.
The supply fans are controlled by the
ignition system. In the fan “Auto” mode the
fan comes on 45 seconds after the flame is proved and goes off 120 seconds after the heating call is removed.
Furnace combustion ventilation air and flue openings should be checked annually for debris and obstructions. If vent extensions are used they must meet category III requirements.
This appliance contains a wire screen at the vent outlet. Each heating season, prior to placing the appliance in heat mode maintenance check that no debris or foreign matter has accumulated in the vent outlet. A good practice is to check for debris each time the air filters are changed.
In the event the vent outlet becomes blocked do not attempt to start the appliance in heat mode until the entire vent opening is cleared.
In the event the unit shut down because the vent was blocked a qualified technician or service agency should monitor the unit prior to re-starting.
The gas burner and heat exchanger should never require cleaning. If cleaning is necessary, this indicates faulty operation of the unit. Cleaning should only be done by a qualified service agency and only after
consultation with an AAON service
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
LEAK CHECK GAS PIPE The gas pipe in the unit should be checked for leaks before startup. Leak checking is the responsibility of the installing contractor. All connections should be checked for leaks annually after installation. Failure to leak check could result in fire, explosion, or other hazardous situations.
DANGER
representative.
If induced draft blower/motor assembly has to be replaced, care must be taken to provide an airtight seal between the blower housing and the burner box.

Gas Heat Exchanger Removal

Removal
Disconnect all wiring on the heat exchanger.
Disconnect flex gas lines and pull out of the way.
Remove screws around the perimeter of the heat exchanger face plate that connect it to the unit. Only the outermost screws should be removed.
Pull the heat exchanger straight back and out of the unit. It may be necessary to remove some of the control door jambs.
Reinstallation
Ensure that the neoprene gasket is installed around the perimeter of the heat exchanger.
Insert heat exchanger into opening so that the back of the main plate is against the unit bulkhead.
Figure 28 - Gas Heat Exchanger
Attach the heat exchanger to the bulkhead using the holes around the perimeter.
Connect flex gas lines to the piping on the heat exchanger. If flexible gas piping in the unit must be replaced connectors cannot be reused, only new connectors must be used.
Connect wiring per the wiring diagram on the controls compartment door. Purge gas lines to the gas valves at the unit.

DX Cooling Set unit controls to cooling mode of operation with supply fans on. Check the fan for correct operating direction, amperage and voltage. Check compressor operation, rotation, amperage and voltage to the unit nameplate (check the amperage on the load side of the compressor contactor).

63
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Startup and service must be performed by a Factory Trained Service Technician.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING

Condenser Fan

Removal
Take off the fan grill by removing the screws that attach it to the top of the unit.
Disconnect the wiring from the motor and loosen the bolt that clamps the motor mount to the motor. Remove the motor and fan through the top of the orifice.
Reinstallation
Set the motor back into the motor mount and tighten bolt. Adjust fan until the top of the blade is even with the top of the orifice.
Reconnect wires, then attach the fan grill at all the points where screws were removed.

Condensate Drain Pans Drain pans will have moisture present and require periodic cleaning to prevent microbial growth. Cleaning of the drain pans will also prevent any possible plugging of the drain lines and overflow of the pan itself. Cleaning of the drain pans and inside of the unit should be done only by qualified service technician.

Evaporator Coil

Removal Evacuate refrigerant from the systems.
Remove the TXV bulbs from the suction lines. Disconnect the suction and liquid line copper connections to the evaporator coil.
Figure 29 - Removal of a Condenser Fan
Assembly
64
Figure 30 - Evaporator Coil Access
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
Remove screws attaching filter rack to the evaporation coil at the front and back of the coil. It may be necessary to remove the economizer assembly (if equipped) to access the screws at the back.
Slide the evaporator coil straight out of the unit.
It may be necessary to make a vertical cut in the front flange of the drain pan on either side of the coil and bend the flange down between the cuts to remove the evaporator coil.
Reinstallation Slide the new coil into the unit through the notch cut in the front of the drain pan.
Re-bend the cut flange back to the original position, then seal the cuts with polyurethane caulking.
Attach the filter at the front and back of the evaporation coil. Reinstall economizer assembly if necessary.
Connect the suction and liquid copper connections to the evaporator coil. Reinstall the TXV bulb on the suction line.
Evacuate the refrigerant system. Weigh in the nameplate refrigerant charge.
See Adjusting Refrigerant Charge section to check for proper sub-cooling and superheat of the refrigerant systems.

E-Coated Coil Cleaning

Documented routine cleaning of e-coated coils is required to maintain coating warranty coverage.
Surface loaded fibers or dirt should be removed prior to water rinse to prevent restriction of airflow. If unable to back wash the side of the coil opposite of the coils entering air side, then surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins.
Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.
A monthly clean water rinse is recommended for coils that are applied in coastal or industrial environments to help to remove chlorides, dirt, and debris. It is very important when rinsing, that water
65
Harsh chemicals, household bleach, or acid cleaners should not be used to clean outdoor or indoor e-coated coils. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the e-coating. If there is dirt below the surface of the coil, use the recommended coil cleaners.
High velocity water from a pressure washer or compressed air should only be used at a very low pressure to prevent fin and/or coil damages. The force of the water or air jet may bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdowns may occur.
CAUTION
CAUTION
temperature is less than 130°F and pressure is less than 900 psig to avoid damaging the fin edges. An elevated water temperature (not to exceed 130°F) will reduce surface tension, increasing the ability to remove chlorides and dirt.
Quarterly cleaning is essential to extend the life of an e-coated coil and is required to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s
regularly scheduled maintenance procedures. Failure to clean an e-coated coil will void the warranty and may result in reduced efficiency and durability.
For routine quarterly cleaning, first clean the coil with the below approved coil cleaner. After cleaning the coils with the approved cleaning agent, use the approved
66
chloride remover to remove soluble salts and revitalize the unit.
Recommended Coil Cleaner The following cleaning agent, assuming it is
used in accordance with the manufacturer’s
directions on the container for proper mixing and cleaning, has been approved for use on e-coated coils to remove mold, mildew, dust, soot, greasy residue, lint, and other particulate:
Enviro-Coil Concentrate, Part Number H­EC01.
Recommended Chloride Remover CHLOR*RID DTS™ should be used to remove soluble salts from the e-coated coil, but the directions must be followed closely. This product is not intended for use as a degreaser. Any grease or oil film should first be removed with the approved cleaning agent.
Remove Barrier - Soluble salts adhere themselves to the substrate. For the effective use of this product, the product must be able to come in contact with the salts. These salts may be beneath any soils, grease or dirt; therefore, these barriers must be removed prior to application of this product. As in all surface preparation, the best work yields the best results.
Apply CHLOR*RID DTS - Apply directly onto the substrate. Sufficient product must be applied uniformly across the substrate to thoroughly wet out surface, with no areas missed. This may be accomplished by use of a pump-up sprayer or conventional spray gun. The method does not matter, as long as the entire area to be cleaned is wetted. After the substrate has been thoroughly wetted, the salts will be soluble and is now only necessary to rinse them off.
Rinse - It is highly recommended that a hose
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
Blower wheels and bands must be inspected for excessive dust build up periodically and cleaned if required. Excessive dust build up on blower wheels may cause an unbalanced state; leading to vibration and/or component failure. Damages due to excessive dust build up will not be covered under factory warranty.
CAUTION
Do not use any detergents or coil cleaners with microchannel condenser coils. Use pressurized clean water, with pressure not to exceed 140 psi. Nozzle should be 6” and 80° to 90° from coil face. Failure to do so could result in coil damage.
CAUTION
be used, but a pressure washer will damage the fins. The water to be used for the rinse is recommended to be of potable quality, though a lesser quality of water may be used if a small amount of CHLOR*RID DTS is added. Check with CHLOR*RID International, Inc. for recommendations on lesser quality rinse water.

Microchannel Coil Cleaning Documented routine cleaning of microchannel coils with factory provided e­coating is required to maintain coating warranty coverage. See E-Coated Coil Cleaning section.

Air-cooled heat exchangers may include microchannel coils. Only clean water is recommended for cleaning microchannel coils. The water pressure used to clean should not exceed 140 psi, from no closer than 3 inches from the coils, and with the water aimed perpendicular to the coils.
Field installed coil coatings are not recommended with microchannel coils.

Supply Fan

Factory bLubrication
Note: Bearing lubrication only applies to belt driven fan motors such as the energy recovery wheel power exhaust fan motor.
All original fan motors and bearings are furnished with factory lubrication. Some applications will require that bearings be re­lubricated periodically. The schedule will depend on the operating duty, temperature variations or other severe atmospheric conditions. Bearings should be re-lubricated when at normal operating temperatures, but not running. Rotate the fan shaft by hand and add only enough grease to purge the seals. DO NOT OVERLUBRICATE.
Recommended greases are: SHELL OIL - DOLIUM R CHEVRON OIL - SRI No. 2 TEXACO INC. - PREMIUM RB
Removal Remove fan access panel on the back side of
the unit. Panel is attached with eight 5/16”
bolts.
67
Phase
LED
On/Off
Figure 31 - 2-6 ton Supply Fan
Remove wire connections from motor. For EC motors unplug the wire harness at the control module that connects to the unit control panel.
Through the blower access opening, remove
the two 5/16” bolts that connect the blower
assembly to the inlet wall (see Figure 32).
Through the coil access door, remove the
two 5/16” bolts that connect the blower
assembly to the inlet wall from air entering side of the wall (see Figure 32).
Slide blower assembly (wire frame motor mount, motor, blower wheel, inlet, and sheet-metal slide) out of unit through blower access opening (see Figure 33).
Figure 33 - RQ Supply Fan Removal Slide

Phase and Brownout Protection Voltage monitor should be wired according to unit specific wiring diagram include in the control compartment.

Before applying power to the unit the voltage monitor should be set up. The three knobs on the front of the monitor should be adjusted.
Figure 32 - RQ Supply Fan Removal Bolts
68
LED
Figure 34 - Voltage Monitor
Adjust the top knob labeled LINE VOLT to the operating voltage. This should be the operating voltage for the equipment and the
Loss/Rev.
measured voltage on the single or three phase lines.
Adjust the knob labeled to either SINGLE PHASE on the left side of the dial or 3 PHASE on the right side of the dial. After selecting single or three phase set the knob to the percentage of Over or Under voltage desired. A typical over and under voltage percentage is 10%.
Adjust the bottom knob labeled RESTART DELAY. For automatic restart after recovery of voltage select from 2 seconds up to 5 minutes. After recovery of line voltage this is how long the monitor will wait before energizing the output relay. For manual reset adjust the knob fully clockwise to MR. After recovery of line voltage the MANUAL RESET button located between the 2 LEDs must be pressed.
Now that the settings have been made, you can apply the supply and line voltages to the monitor. The monitor will only operate when the supply voltage is available.
On power up, with the line voltage and the supply voltage applied, the monitor takes 3 to 10 seconds to evaluate the line voltage, compare that voltage to the knob settings and then energize if all parameters are satisfied or will remain off if any operating parameter is incorrect.
All of the knob adjustments are adjustable after power up, except the voltage range will not change and going from single or three phase to the other will not change (i.e. within 440 to 480 VAC, but not to 208 or 230 VAC).
LED Codes
Powering up with voltage present which matches knob settings:
1. On/Off LED = Alternating Green/Red
Phase Loss LED = Out
2. On/Off LED = Out Phase Loss LED = Alt. G/R
3. On/Off LED = Alt. G/R Phase Loss LED = Out
4. On/Off LED = Alt. G/R Flashing Phase Loss LED = Green
5. On/Off LED = Green Phase Loss LED = Green
Powering up with no voltage present:
1. On/Off LED = Alternating Green/Red Phase Loss LED = Out
Going into trip condition after operating conditions were good:
1. On/Off LED = Green Phase Loss LED = Green
2. On/Off LED = Green Flashing Phase Loss LED = Red
3. On/Off LED = Red Phase Loss LED = Red
Going to good condition from trip condition
- automatic reset:
1. On/Off LED = Red Phase Loss LED = Red
2. On/Off LED = Alt. G/R Flashing Phase Loss LED = Green
3. On/Off LED = Green Phase Loss LED = Green
Going to good condition from trip condition
- manual reset:
1. On/Off LED = Red Phase Loss LED = Red
2. On/Off LED = Alt. G/R Flashing Phase Loss LED = Green
3. Manual Reset button is pressed
4. On/Off LED = Green Phase Loss LED = Green
69
24COM
Module Common
24VAC
Module Power
C1 & C2
Demand Input
P1
Pressure Common
P2
Pressure Input
P3
Pressure Power 5VDC
P4
Pressure Shield
P5 & P6
Pressure Output
T1 & T2
Discharge Temperature Sensor
A1 & A2
Alarm Relay Out
M1 & M2
Contractor
L1
Control Voltage N
L2
Control Voltage L
U1 & U2
Digital Unloader Solenoid
V1 & V2
Vapor Injection Solenoid
Demand
Signal (VDC)
Loaded %
Unloaded %
Time Loaded
Time
Unloaded
% Compressor
Capacity
1.00
Off
Off
Off
Off
0%
1.44
10%
90%
1.5 sec
13.5 sec
10%
3.00
50%
50%
7.5 sec
7.5 sec
50%
4.20
80%
20%
12 sec
3 sec
80%
5.00
100%
0%
15 sec
0 sec
100%
To avoid damaging the Compressor Controller do not connect wires to terminals C3, C4, T3, T4, T5, or T6.
WARNING

Variable Capacity Compressor Controller

Units with variable capacity scroll compressors may include the following compressor controller. The following is an explanation of the terminals and troubleshooting alert flash codes of the controller. For more information on the compressor controller, see Emerson Climate Bulletin AE8-1328.
Figure 35 - Variable Capacity Compressor
Controller
Low Voltage Terminals
High Voltage Terminals
The compressor controller modulates the compressor unloader solenoid in an on/off pattern according to the capacity demand signal of the system. The following table shows the linear relationship between the demand signal and compressor capacity modulation. The compressor controller protects the compressor against high discharge temperature. Refer to Appendix B for the relationship between thermistor temperature readings and resistance values.
Table 17 - Demand Signal vs. Compressor Capacity Modulation
70
Figure 36 - Compressor Controller Flash Code Details
Feature 6A
Quantity / Size
Type
0
No Pre Filters
A
2 / 20” x 20” x 2”
Pleated, 30% Eff, MERV 8
B
1 / 20” x 20” x 1”
Metal Mesh, Outside Air
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING

Filter Replacement

Monthly air filter inspection is required to maintain optimum unit efficiency.
Table 18 - RQ Series 2-6 ton Pre Filters
It is strongly recommended that filter media be replaced monthly. Filters are located upstream of the evaporator coil in the filter and economizer section. Open access door and pull filters straight out to inspect all of the filters. Replace filters with the size indicated on each filter or as shown in the tables below. Arrow on the replacement filters must point towards the blower. (PE = Power Exhaust)
71
Feature 6B
Quantity / Size
Type
0
2 / 20” x 20” x 2”
Fiberglass Throwaway,
25% Eff, MERV 4
A
Pleated, 30% Eff, MERV 8
B
2 / 20” x 20” x 4”
Pleated, 30% Eff, MERV 8
C
2 / 20” x 20” x 2”
Permanent Filter Frame -
Replaceable Media
F
2 / 20” x 20” x 4”
Pleated, 65% Eff, MERV 11
G
Pleated, 85% Eff, MERV 13
H
Pleated, 95% Eff, MERV 14
Feature 1A
Quantity / Size
Type
F, G, H, J, Q, R, S, T
1 / 16” x 16” x 2”
Pleated, 30% Eff, MERV 8
With Energy Recovery Wheel Exhaust
Air Filters, Feature 6A - D, F, G, H
OA - 1 / 16” x 16” x 2”
EA - 1 / 16” x 16” x 2”
20”
20”
20”
Table 19 - RQ Series 2-6 ton Unit Filters
Table 20 - RQ Series 2-6 ton Energy Recovery Wheel Filters
Figure 37 - RQ Series 2-6 ton Standard Filter Layout
(Viewed from the Upstream Side of the Cooling Coil)

Replacement Parts

Parts for AAON equipment may be obtained from AAON at www.aaonparts.com. When ordering parts reference the unit serial number and part number.
72
AAON Warranty, Service and Parts Department
2424 S. Yukon Ave. Tulsa, OK 74107 Ph: 918-583-2266 Fax: 918-382-6364 www.aaon.com
Note: Before calling, technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit.

Appendix A - Heat Exchanger Corrosion Resistance

Water
Containing
Concentration (mg/l or ppm)
Time Limits -
Analyze Before
AISI
316
SMO
254
Copper
Alloy
Nickel
Alloy
Alkalinity
(HCO
3
-
)
< 70
Within 24 Hours
+ + 0 + 70-300
+ + + + > 300
+ + 0/+
+
Sulfate (SO
4
2-
)
< 70
No Limit
+ + + + 70-300
+ + 0/- + > 300
0 0 -
+
HCO
3
-
/ SO
4
2-
> 1.0
No Limit
+ + + + < 1.0
+ + 0/-
+
Electrical
Conductivity
< 10µS/cm
No Limit
+ + 0 + 10-500 µS/cm
+ + + + > 500 µS/cm
+ + 0
+
pH
< 6.0
Within 24 Hours
0 0 0 + 6.0-7.5
0/+ + 0 + 7.5-9.0
+ + + + > 9.0
+ + 0
+
Ammonium
(NH
4
+
)
< 2
Within 24 Hours
+ + + + 2-20
+ + 0 + > 20
+ + -
+
Chlorides (Cl-)*
< 300
No Limit
+ + + + > 300
0 + 0/+
+
Free Chlorine
(Cl2)
< 1
Within 5 Hours
+ + + + 1-5
+ + 0 + > 5
0/+ + 0/-
+
Hydrogen
Sulfide (H2S)
< 0.05
No Limit
+ + + + > 0.05
+ + 0/-
+
Free (aggressive)
Carbon Dioxide
(CO
2)
< 5
No Limit
+ + + + 5-20
+ + 0 + > 20
+ + -
+
The resistance guide provides the corrosion resistance of stainless steel type AISI 316 and pure Copper (99.9%) in water, to a number of important chemical factors. The actual corrosion is a very complex process influenced by many different factors in combination.
Explanations: + Good resistance under normal conditions 0 Corrosion problems may occur especially when more factors are valued 0
- Use is not recommended
*See Chloride Content Table
73
Water
Containing
Concentration (mg/l or ppm)
Time Limits -
Analyze Before
AISI
316
SMO
254
Copper
Alloy
Nickel
Alloy
Total Hardness
(°dH)
4.0-8.5
No Limit
+ + +
+
Nitrate (NO3)
< 100
No Limit
+ + + + > 100
+ + 0
+
Iron (Fe)
< 0.2
No Limit
+ + + + > 0.2
+ + 0
+
Aluminum (Al)
< 0.2
No Limit
+ + + + > 0.2
+ + 0
+
Manganese (Mn)
< 0.1
No Limit
+ + + + > 0.1
+ + 0
+
Chloride Content
Maximum Temperature
60°C (140°F)
80°C (176°F)
120°C (248°F)
130°C (266°F)
= 10 ppm
SS 304
SS 304
SS 304
SS 316
= 25 ppm
SS 304
SS 304
SS 316
SS 316
= 50 ppm
SS 304
SS 316
SS 316
Ti / SMO 254
= 80 ppm
SS 316
SS 316
SS 316
Ti / SMO 254
= 150 ppm
SS 316
SS 316
Ti / SMO 254
Ti / SMO 254
= 300 ppm
SS 316
Ti / SMO 254
Ti / SMO 254
Ti / SMO 254
> 300 ppm
Ti / SMO 254
Ti / SMO 254
Ti / SMO 254
Ti / SMO 254
Chloride Content
74

Appendix B - Thermistor Temperature vs. Resistance Values

Deg C
Deg F
Resistance (kOhms)
-40
-40
2889.6
-35
-31
2087.22
-30
-22
1522.20
-25
-13
1121.44
-20
-4
834.72
-15 5 627.28
-10
14
475.74
-5
23
363.99
0
32
280.82
5
41
218.41
10
50
171.17
15
59
135.14
20
68
107.44
25
77
86.00
30
86
69.28
35
95
56.16
40
104
45.81
45
113
37.58
50
122
30.99
55
131
25.68
60
140
21.40
65
149
17.91
Deg C
Deg F
Resistance (kOhms)
70
158
15.07
75
167
12.73
80
176
10.79
85
185
9.20
90
194
7.87
95
203
6.77
100
212
5.85
105
221
5.09
110
230
4.45
115
239
3.87
120
248
3.35
125
257
2.92
130
266
2.58
135
275
2.28
140
284
2.02
145
293
1.80
150
302
1.59
155
311
1.39
160
320
1.25
165
329
1.12
170
338
1.01
175
347
0.92
180
356
0.83
75
Job Name:_______________________________________________
Date:______________
Address:______________________________________________________________________
______________________________________________________________________________
Model Number:_________________________________________________________________
Serial Number:_____________________________________________
Tag:_______________
Startup Contractor:______________________________________________________________
Address:______________________________________________________________________
_______________________________________________________
Phone:______________
Pre Startup Checklist
Installing contractor should verify the following items.
1. Is there any visible shipping damage?
Yes No
2. Is the unit level?
Yes No
3. Are the unit clearances adequate for service and operation?
Yes No
4. Do all access doors open freely and are the handles operational?
Yes No
5. Have all electrical connections been tested for tightness?
Yes No
6. Does the electrical service correspond to the unit nameplate?
Yes No
7. On 208/230V units, has transformer tap been checked?
Yes No
8. Has overcurrent protection been installed to match the unit nameplate
requirement?
Yes No
9. Have all set screws on the fans been tightened?
Yes No
10. Do all fans rotate freely?
Yes No
11. Does any field water piping to the unit appear to be correct per design
parameters?
Yes No
12. Is all copper tubing isolated so that it does not rub?
Yes No
13. Has outside air rain hood been opened?
Yes No
14. Have the damper assemblies been inspected?
Yes No
15. Are air filters installed with proper orientation?
Yes No
16. Have condensate drain and p-trap been connected?
Yes No
Ambient Dry Bulb Temperature ________°F
Ambient Wet Bulb Temperature ________°F

RQ Series Startup Form

Ambient Temperature
76
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
Band Size_____________________
VAV Controls_________________
VFD Frequency________________
Wheel Spins Freely
Check Rotation
FLA ________
Number
hp
L1
L2
L3
1
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
Band Size_____________________
VFD Frequency________________
Operation Check
Damper Wiring Check
Gears Check
Damper Actuator Type:__________________________________________________________
Economizer Changeover Type and Operation:_______________________________________
Water-Cooled Condenser
Air-Cooled Condenser
No Water Leaks
Condenser Safety Check
Water Flow ________ gpm
Water Inlet Temperature ________°F
Water Outlet Temperature ________°F
Supply Fan Assembly
Energy Recovery Wheel Assembly
Power Exhaust Fan Assembly
Outside Air/Economizer Dampers
Unit Configuration
77
Compressors/DX Cooling
Check Rotation
Number
L1
L2
L3
Head
Pressure
PSIG
Suction
Pressure
PSIG
1 - Full
Capacity
1 - Reduced
Capacity
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
Refrigeration System 1 Full Capacity - Cooling Mode
Refrigeration System 1 Reduced Capacity - Cooling Mode
Refrigeration System 1 Full Capacity - Heating Mode (Heat Pump Only)
Refrigeration System 1 Reduced Capacity - Heating Mode (Heat Pump Only)
Air-Cooled Condenser Fans
78
1. Has the entire system been flushed and pressure checked?
Yes No
2. Has the entire system been filled with fluid?
Yes No
3. Has air been bled from the heat exchangers and piping?
Yes No
4. Is the glycol the proper type and concentration (N/A if water)?
Yes No
5. Is there a minimum load of 50% of the design load?
Yes No
6. Has the water piping been insulated?
Yes No
7. What is the freeze point of the glycol (N/A if water)? ______________________________
Natural Gas
Propane
Purge Air from Lines
Verify Pilot Spark
Stage
Manifold Pressure (w.c.)
Stage
Manifold Pressure (w.c.)
1 3 2 4
Stages__________
Limit Lockout
Aux. Limit Lockout
Stage
Amps
Stage
Amps 1 3 2 4
Water/Glycol System
Gas Heating
Electric Heating
79

Maintenance Log

Entry Date
Action Taken
Name/Tel.
This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper startup, maintenance and servicing of the equipment falls to the owner and qualified licensed technician.
80

Literature Change History

February 2011
Added information regarding the charging of a heat pump and added additional information regarding freezing water in the heat exchanger.
June 2011
Updated filter information.
April 2012
Added chilled water, hot water, and steam coil connection sizes.
August 2012
Added seismic curb installation instructions.
November 2012
Update of the IOM adding information about compressor cycling.
May 2013
Added options to the feature string, added curb gasket information, added auxiliary electric heating capacities table, corrected condenser water connections table, added section for variable capacity compressor controller, and added Appendix B.
81
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
RQ Series
Installation, Operation &
Maintenance
R94490 · Rev. D · 130530
It is the intent of AAON to provide accurate and current product information. However, in the interest of product improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice, obligation, or liability.
Copyright © AAON, all rights reserved throughout the world.
AAON® and AAONAIRE® are registered trademarks of AAON, Inc., Tulsa, OK.
Loading...