AAON RQ-006 User Manual

RQ SERIES
Packaged Rooftop Units, Heat Pumps,
& Outdoor Air Handling Units
Do not touch any electrical switch; do not
Immediately call your gas supplier from a phone remote from the building. Follow the
If you cannot reach your gas supplier, call
Startup and service must be performed by a
WARNING
service instructions in this manual.
WARNING
& Maintenance
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Be sure to read and understand the installation, operation and
Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.
A copy of this IOM should be kept with the unit.
o Do not store gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance
o WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
use any phone in your building.
Leave the building immediately.
gas supplier’s instructions.
the fire department.
o
Factory Trained Service Technician.
Table of Contents
Safety .............................................................................................................................................. 9
RQ Series Feature String Nomenclature ....................................................................................... 14
General Information ...................................................................................................................... 23
Codes and Ordinances............................................................................................................... 23
Receiving Unit .......................................................................................................................... 24
Packaged Direct Expansion (DX) Units ................................................................................... 25
Gas or Electric Heating ............................................................................................................. 26
Wiring Diagrams ....................................................................................................................... 27
Condensate Drain Pan ............................................................................................................... 27
Installation..................................................................................................................................... 28
Unit Location ............................................................................................................................ 28
Setting the Curb ........................................................................................................................ 28
Forklifting the Unit ................................................................................................................... 31
Lifting the Unit ......................................................................................................................... 32
Vertical Duct Connection ......................................................................................................... 34
Seismic Curb Installation .......................................................................................................... 35
Horizontal Duct Connection ..................................................................................................... 37
Outside Air Rain Hood ............................................................................................................. 37
Metal Mesh Filters .................................................................................................................... 38
Electrical ................................................................................................................................... 39
Thermostat Control Wiring ................................................................................................... 41
Gas Heating ............................................................................................................................... 41
Maximum Piping Capacities ................................................................................................. 42
Piping Sizing Examples ........................................................................................................ 42
Inlet and Manifold Pressures ................................................................................................ 43
Gas Pressure Regulator & Overpressure Protection Device ................................................. 43
Additional Gas Piping Considerations .................................................................................. 44
Leak Testing.......................................................................................................................... 45
Refrigerant-to-Water Heat Exchanger ...................................................................................... 45
Open Loop Applications ....................................................................................................... 45
Freezing Water in the Heat Exchanger ................................................................................. 46
Water Piping ......................................................................................................................... 47
Condensate Drain Piping .......................................................................................................... 49
3
Discharge and Suction Line Piping ........................................................................................... 49
Heating Coils ............................................................................................................................ 52
Chilled Water Coil .................................................................................................................... 52
Startup ........................................................................................................................................... 53
Filters ........................................................................................................................................ 53
Adjusting Refrigerant Charge ................................................................................................... 53
Checking Liquid Sub-Cooling .............................................................................................. 54
Checking Evaporator Superheat ........................................................................................... 54
Adjusting Sub-Cooling and Superheat Temperatures ........................................................... 54
Gas Heater Instructions ............................................................................................................. 57
Supply Fan EC Motor Startup................................................................................................... 58
Condenser Fan EC Motor Startup ............................................................................................. 59
Operation....................................................................................................................................... 60
Thermostat Operation ............................................................................................................... 60
Packaged DX Cooling Operation and Control .......................................................................... 60
Gas Heater Operation ................................................................................................................ 60
Electric Heating Operation ....................................................................................................... 61
Steam or Hot Water Preheating and Heating Operation ........................................................... 61
Chilled Water or Non-Compressorized DX Cooling Operation ............................................... 61
Maintenance .................................................................................................................................. 62
Gas Heating ............................................................................................................................... 62
Gas Heat Exchanger Removal .................................................................................................. 63
DX Cooling ............................................................................................................................... 63
Condenser Fan .......................................................................................................................... 64
Condensate Drain Pans ............................................................................................................. 64
Evaporator Coil ......................................................................................................................... 64
E-Coated Coil Cleaning ............................................................................................................ 65
Microchannel Coil Cleaning ..................................................................................................... 67
Supply Fan ................................................................................................................................ 67
Phase and Brownout Protection ................................................................................................ 68
Variable Capacity Compressor Controller ................................................................................ 70
Filter Replacement .................................................................................................................... 71
Replacement Parts ..................................................................................................................... 72
Appendix A - Heat Exchanger Corrosion Resistance ................................................................... 73
4
Appendix B - Thermistor Temperature vs. Resistance Values ..................................................... 75
RQ Series Startup Form ................................................................................................................ 76
Maintenance Log .......................................................................................................................... 80
Literature Change History............................................................................................................. 81
R94490 · Rev. D · 130530
5
Index of Tables and Figures
Tables:
Table 1 - Electric and Gas Heating Capacities ............................................................................. 26
Table 2 - Auxiliary Electric Heating Capacities ........................................................................... 27
Table 3 - Unit Clearances ............................................................................................................. 28
Table 4 - Control Wiring ............................................................................................................... 41
Table 5 - 2-6 ton Gas Connections ............................................................................................... 41
Table 6 - Natural Gas (ft3/hr) ........................................................................................................ 42
Table 7 - Propane (kBtu/hr) .......................................................................................................... 42
Table 8 - Gas Piping Supports ...................................................................................................... 43
Table 9 - Glycol Freezing Points .................................................................................................. 47
Table 10 - Condenser Water Connections .................................................................................... 47
Table 11 - Hot Water Coil Connection Sizes ................................................................................ 52
Table 12 - Steam Coil Connection Sizes ...................................................................................... 52
Table 13 - Chilled Water Coil Connection Sizes .......................................................................... 52
Table 14 - Acceptable Refrigeration Circuit Values ..................................................................... 54
Table 15 - R-410A Refrigerant Temperature-Pressure Chart ....................................................... 56
Table 16 - EC Condenser Fan Cycling Options ............................................................................ 59
Table 17 - Demand Signal vs. Compressor Capacity Modulation ................................................ 70
Table 17 - RQ Series 2-6 ton Pre Filters ....................................................................................... 71
Table 18 - RQ Series 2-6 ton Unit Filters ..................................................................................... 72
Table 19 - RQ Series 2-6 ton Energy Recovery Wheel Filters ..................................................... 72
6
Figures:
Figure 1 - Lockable Handle .......................................................................................................... 24
Figure 2 - RQ Series Orientation .................................................................................................. 28
Figure 3 - RQ Cabinet Standard and Power Exhaust Gasket Locations ....................................... 30
Figure 4 - Forklifting an RQ Series Unit from the Side ............................................................... 31
Figure 5 - Forklifting an RQ Series Unit from the Front .............................................................. 31
Figure 6 - Lifting Details of a 2-6 ton Standard or Power Exhaust Unit ...................................... 32
Figure 7 - Lifting Details of a 2-6 ton Energy Recovery Wheel Unit .......................................... 33
Figure 8 - Vertical Duct Connection ............................................................................................. 34
Figure 9 - Solid Bottom Seismic Curb with Filters ...................................................................... 35
Figure 10 - Seismic Solid Bottom Curb without Filters Cross Section ........................................ 36
Figure 11 - Seismic Solid Bottom Curb without Filters Detail A................................................. 36
Figure 12 - Seismic Solid Bottom Curb without Filters Detail B ................................................. 36
Figure 13 - Seismic Rigid Mount Curb Cross Section ................................................................. 37
Figure 14 - Horizontal duct connections ....................................................................................... 37
Figure 15 - RQ Series unit Closed Rain Hood .............................................................................. 38
Figure 16 - RQ Series unit Open Rain Hood ................................................................................ 38
Figure 17 - Rain Hood with Metal Mesh Filter Rack Installation ................................................ 38
Figure 18 - Unit Base Utility Entry............................................................................................... 39
Figure 19 - Back View of Power Switch from Control Compartment ......................................... 39
Figure 20 - RQ Series Gas Heat Exchanger .................................................................................. 42
Figure 21 - Example 2-6 ton through the Base Gas Piping .......................................................... 44
Figure 22 - Post Corner Hole Location ......................................................................................... 50
Figure 23 - Post Back Hole Location ............................................................................................ 50
Figure 24 - Post Corner Hole Piping............................................................................................. 51
Figure 25 - Post Back Hole Location ............................................................................................ 51
Figure 26 - Gas Heater Instructions .............................................................................................. 57
Figure 27 - PIN Connectors on EC Supply Fan Motor Electronics .............................................. 58
Figure 28 - Gas Heat Exchanger ................................................................................................... 63
Figure 29 - Removal of a Condenser Fan Assembly .................................................................... 64
Figure 30 - Evaporator Coil Access .............................................................................................. 65
Figure 31 - 2-6 ton Supply Fan ..................................................................................................... 68
Figure 32 - RQ Supply Fan Removal Bolts .................................................................................. 68
Figure 33 - RQ Supply Fan Removal Slide .................................................................................. 68
Figure 34 - Voltage Monitor ......................................................................................................... 68
Figure 35 - Variable Capacity Compressor Controller ................................................................. 70
Figure 36 - Compressor Controller Flash Code Details................................................................ 71
Figure 37 - RQ Series 2-6 ton Standard Filter Layout .................................................................. 72
7
8

Safety

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
Before servicing, disconnect all
electrical power to the furnace. More than one disconnect may be provided.
When servicing controls, label all
wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with key-lock or nut and bolt.
WARNING
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit. Shut off main gas supply. Do not touch any electric switch. Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections and shut off valves.
CAUTION
Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
WARNING
9
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD
Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.
WARNING
WARNING
During installation, testing, servicing and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks.
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts that can cause serious injury. Do not open door containing fans until the power to the unit has been disconnected and fan wheel has stopped rotating.
WARNING
GROUNDING REQUIRED
All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.
WARNING
Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
CAUTION
10
UNIT HANDLING
To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
WARNING
Failure to properly drain and vent coils when not in use during freezing temperature may result in coil and equipment damage.
CAUTION
Rotation must be checked on all MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection
CAUTION
WATER PRESSURE
Prior to connection of condensing water supply, verify water pressure is less than maximum pressure shown on unit nameplate. To prevent injury or death due to instantaneous release of high pressure water, relief valves should be field supplied on system water piping.
WARNING
Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.
WARNING
Always use a pressure regulator, valves and gauges to control incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.
WARNING
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than
8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
CAUTION
Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturers usage instructions. Failure to follow instructions may result in equipment damage, injury or death.
WARNING
11
WATER FREEZING
Failure of the condenser due to freezing will allow water to enter the refrigerant circuit and will cause extensive damage to the refrigerant circuit components. Any damage to the equipment as a result of water freezing in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacturer warranties.
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
CAUTION
Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latch are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.
CAUTION
Cleaning the cooling tower or condenser water loop with harsh chemicals such as hydrochloric acid (muriatic acid), chlorine or other chlorides, can damage the refrigerant-to-water heat exchanger. Care should be taken to avoid allowing chemicals to enter the refrigerant-to-water heat exchanger. See Appendix A - Heat Exchanger Corrosion Resistance for more information.
CAUTION
OPEN LOOP APPLICATIONS
Failure of the condenser as a result of chemical corrosion is excluded from coverage under AAON Inc. warranties and the heat exchanger manufacturer’s warranties.
WARNING
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
12
1. Startup and service must be performed
by a Factory Trained Service Technician.
2. Use only with type of the gas approved
for the furnace. Refer to the furnace rating plate.
3. The unit is for outdoor use only. See
General Information section for more information.
4. Provide adequate combustion ventilation
air to the furnace. If a vent duct extension is used, a class III approved vent is required. See the Locating Units and Gas Heating sections of the Installation section of the manual.
5. Always install and operate furnace
within the intended temperature rise range and duct system external static pressure (ESP) as specified on the unit nameplate.
6. The supply and return air ducts must be
derived from the same space. It is recommended ducts be provided with access panels to allow inspection for duct tightness. When a down flow duct is used with electric heat, the exhaust duct should be an L shaped duct.
7. Clean furnace, duct and components
upon completion of the construction setup. Verify furnace operating conditions including input rate, temperature rise and ESP.
8. Every unit has a unique equipment
nameplate with electrical, operational, and unit clearance specifications. Always refer to the unit nameplate for specific ratings unique to the model you have purchased.
9. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
10. Keep this manual and all literature
safeguarded near or on the unit.
13

RQ Series Feature String Nomenclature

Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RQ005 – 3V – BB 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
BASE MODEL
SERIES AND GENERATION
RQ
UNIT SIZE
002 = 2 ton Capacity 003 = 3 ton Capacity 004 = 4 ton Capacity 005 = 5 ton Capacity 006 = 6 ton Capacity
VOLTAGE
1 = 230V/1Φ/60Hz 2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz 9 = 208V/1Φ/60Hz
DISCHARGE/RETURN CONFIGURATION AND INTERIOR CORROSION PROTECTION
V = Vertical Discharge and Return H = Horizontal Discharge and Return J = Option H + Interior Corrosion Protection W = Option V + Interior Corrosion Protection K = Vertical Discharge and Horizontal Return L = Option K + Interior Corrosion Protection M = Horizontal Discharge and Vertical Return N = Option M + Interior Corrosion Protection
Model Option A: COOLING/HEAT PUMP
A1: REFRIGERANT STYLE
0 = Air Handling Unit B = R-410A - Non-Compressorized DX Air Handling Unit C = R-410A - Standard Efficiency E = R-410A Variable Capacity Scroll Compressor ­High Efficiency F = R-410A Variable Capacity Scroll Compressor ­Standard Efficiency G = R-410A Two-Step Compressor - High Efficiency H = R-410A Two-Step Compressor - Standard Efficiency
A2: UNIT CONFIGURATION
0 = No Cooling A = Air-Cooled Cond. + Std Evap. Coil B = Air-Cooled Cond. + 6 Row Evap. Coil J = Water-Cooled Cond. + Std Evap. Coil K = Water-Cooled Cond. + 6 Row Evap. Coil U = Chilled Water Coil - 4 Row W = Chilled Water Coil - 6 Row 2 = Non-Compressorized + Std Evap. Coil 4 = Non-Compressorized + 6 Row Evap. Coil 6 = Air-Source Heat Pump 7 = Water-Source/Geothermal Heat Pump
14
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Model Option A: COOLING/HEAT PUMP
A3: COIL COATING
0 = Standard 1 = Polymer E-Coated Evap. and Cond. Coils 8 = Polymer E-Coated Cond. Coil 9 = Polymer E-Coated Cooling Coil A = Stainless Steel Evap. Coil Casing + Polymer E­Coated Cond. Coil D = Stainless Steel Cooling Coil Casing
A4: COOLING/HEAT PUMP STAGING
0 = No Cooling 1 = 1 Stage 2 = 2 Stage 9 = Modulating - Lead VCC B = 1 Stage + 1 Stage Auxiliary Heat C = 2 Stage + 1 Stage Auxiliary Heat E = Modulating - Lead VCC + 1 Stage Aux. Heat H = Single Serpentine 8 fpi J = Half Serpentine 8 fpi K = Single Serpentine 10 fpi L = Half Serpentine 10 fpi M = Single Serpentine 12 fpi N = Half Serpentine 12 fpi P = 1 Stage + 2 Stage Auxiliary Heat Q = 2 Stage + 2 Stage Auxiliary Heat S = Modulating - Lead VCC + 2 Stage Aux. Heat U = 1 Stage + 4 Stage Auxiliary Heat V = 2 Stage + 4 Stage Auxiliary Heat Y = Modulating - Lead VCC + 4 Stage Aux. Heat
Model Option B: HEATING
B1: HEATING TYPE
0 = No Heating 1 = Electric Heat 2 = Natural Gas Aluminized 3 = Natural Gas Stainless Steel 4 = High Altitude Natural Gas Aluminized 5 = High Altitude Natural Gas Stainless Steel 6 = LP Gas Aluminized 7 = LP Gas Stainless Steel 8 = High Altitude LP Gas Aluminized 9 = High Altitude LP Gas Stainless Steel C = Steam Distributing Standard D = Steam Distributing Polymer E-Coated E = Hot Water Standard F = Hot Water Polymer E-Coated
B2: HEATING DESIGNATION
0 = No Heating 1 = Heat 1 2 = Heat 2 3 = Heat 3 4 = Heat 4 5 = Heat 5 7 = Heat 7 H = 1 Row Coil J = 2 Row Coil
15
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Model Option B: HEATING
B3: HEATING STAGING
0 = No Heating 1 = 1 Stage 2 = 2 Stage 3 = 3 Stage 4 = 4 Stage 9 = Modulating Gas/SCR Electric A = SCR Electric, 0-10V External Control H = Single Serpentine 8 fpi J = Half Serpentine 8 fpi M = Single Serpentine 12 fpi N = Half Serpentine 12 fpi
Feature 1: RETURN/OUTSIDE AIR
1A: RETURN/OUTSIDE AIR SECTION
0 = Manually Adjustable OA Opening + RA Opening A = Economizer B = Econ + Power Exhaust F = Low cfm Total Energy Recovery Wheel G = Low cfm Total ERW + Bypass Damper H = Low cfm Sensible ERW J = Low cfm Sensible ERW + Bypass Damper K = 100% Outside Air - No Return Air Opening L = Motorized Outside Air Damper + RA Opening M = Motorized Outside Air Damper - No RA Opening N = Empty ERW Option Box- No Power Exhaust P = Empty ERW Option Box + Power Exhaust 5 = 100% Return Air
16
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3
4
5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 1: RETURN/OUTSIDE AIR
1B: RETURN/EXHAUST AIR BLOWER CONFIGURATION
0 = Standard – None A = 1 Blower + Standard Eff. Motor C = 1 Blower + Premium Eff. Motor E = 1 Blower + Premium Eff. Motor + 1 VFD H = 1 Blower + High Efficiency EC Motor J = 1 Blower + Single Phase Motor + Speed Control
1C: RETURN/EXHAUST AIR BLOWER
0 = Standard - None B = 15” Backward Curved Plenum J = 15” Backward Curved Plenum - 70% Width N= 16” Axial Flow
1D: RETURN/EXHAUST AIR BLOWER MOTOR
0 = Standard - None A = 0.25 hp - 850 rpm B = 0.5 hp - 1075 rpm C = 1 hp - 1750 rpm D = 2 hp - 1760 rpm W = 0.75 hp - 1760 rpm Z = 0.167 hp - 825 rpm
Feature 2: OUTSIDE AIR CONTROL
0 = Standard - None A = 3 Position Actuator - Sensible Limit B = 3 Position Actuator - Enthalpy Limit C = Fully Modulating Actuator - Sensible Limit D = Fully Modulating Actuator - Enthalpy Limit E = DDC Actuator M = 3 Pos. Act. - Sensible Limit + CO2 Override N = 3 Pos. Act. - Enthalpy Limit + CO2 Override P = Fully Mod. Act. - Sensible + CO2 Override Q = Fully Mod. Act. - Enthalpy + CO2 Override R = DDC Actuator + CO2 Override S = Dual Minimum Position Potentiometers + Fully Mod. Act. - Sensible Limit T = Dual Minimum Position Potentiometers + Fully Mod. Act. - Enthalpy Limit U = 2 Position Actuator
Feature 3: HEAT OPTIONS
0 = Standard - None E = Discharge Air Override K = Auxiliary Heat K L = Auxiliary Heat L M = Auxiliary Heat M N = Auxiliary Heat N
17
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3
4
5A
5B
5C
6A
6B
6C
7 8 9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 BP J C0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 4: MAINTENANCE OPTIONS
0 = Standard - None A = Field Wired 115V Outlet B = Factory Wired 115V Outlet C = Blower Aux. Contact D = Remote Start/Stop Terminals E = Options A + C F = Options A + D G = Options B + C H = Options B + D J = Options A + C + D K = Options B + C + D L = Options C + D
Feature 5: SUPPLY AIR OPTIONS
5A: SUPPLY AIR BLOWER CONFIGURATION
P = 1 Blower + High Efficiency EC Motor Q = 1 Blower + Inverter Rated Motor + 1 VFD R = 1 Blower + Single Phase Motor + Speed Control
5B: SUPPLY AIR BLOWER
J = 18.5” Direct Drive Backward Curved Plenum K = 18.5” Direct Drive BC Plenum - 60% Width
5C: SUPPLY AIR BLOWER MOTOR
A = 0.25 hp - 850 rpm B = 0.5 hp - 1075 rpm C = 1 hp - 1750 rpm D = 2 hp - 1760 rpm W = 0.75 hp - 1760 rpm Z = 0.167 hp - 825 rpm
Feature 6: FILTERS
6A: PRE FILTER
0 = Standard - None A = 2” Pleated - 30% Eff. - MERV 8 B = Metal Mesh Outside Air Filter C = Lint Screen Filter D = Exhaust Air ERW Filter E = Option A + B F = Option A + D G = Option B + D H = Option A + B + D
6B: UNIT FILTER
0 = 2” Throwaway A = 2” Pleated - 30% Eff. - MERV 8
B = 4” Pleated - 30% Eff. - MERV 8 C = 2” Permanent Filter + Replaceable Media F = 4” Pleated - 65% Eff. - MERV 11 G = 4” Pleated - 85% Eff. - MERV 13 H = 4” Pleated - 95% Eff. - MERV 14
6C: FILTER OPTIONS
0 = Standard A = Clogged Filter Switch B = Magnehelic Gauge C = Options A + B
18
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C
7
8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 7: REFRIGERATION CONTROL
0 = Standard A = 5 Min. Time Delay Relay - Comp. Off C = Fan Cycling D = Adjustable Lockouts - Each Circuit E = Freeze Stats - Each Circuit G = Options A + C H = Options A + D J = Options A + E N = Options C + D P = Options C + E Q = Options D + E U = Options A + C + D V = Options A + C + E W = Options A + D + E 2 = Options C + D + E 6 = Options A + C + D + E
Feature 8: REFRIGERATION OPTIONS
0 = Standard C = Hot Gas Reheat D = Modulating Hot Gas Reheat E = 0°F Low Ambient Lead Stage M = Polymer E-Coated Hot Gas Reheat N = Polymer E-Coated Modulating Hot Gas Reheat
Feature 9: REFRIGERATION ACCESSORIES
0 = Standard A = Sight Glass B = Compressor Isolation Valves C = Options A + B D = ECM Condenser Fan - Multiple Speed E = ECM Condenser Fan – Head Pressure Control G = Options A + D H = Options B + D J = Options A + B + D K = Options A + E L = Options B + E M = Options A + B + E
Feature 10: POWER OPTIONS
0 = Standard Power Block A = 100 Amp Power Switch B = 150 Amp Power Switch F = 60 Amp Power Switch
Feature 11: SAFETY OPTIONS
0 = Standard A = Return and Supply Air Firestat B = Return Air Smoke Detector C = Supply Air Smoke Detector D = Options B + C E = Options A + B F = Options A + C G = Options A + B + C H = Remote Safety Shutoff Terminals J = Options A + H K = Options B + H L = Options C + H M = Options D + H N = Options A + B + H P = Options A + C + H Q = Options A + D + H
19
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L 0 0 – 0 0 B 0 0 0 0 0 B
Feature 12: CONTROLS
0 = Standard A = Low Limit Controls B = Phase and Brown Out Protection C = Energy Recovery Wheel Defrost D = Energy Recovery Wheel Rotation Detection E = Compressor Power Factor Correction F = Options A + B G = Options A + C H = Options A + D J = Options A + E K = Options B + C L = Options B + D M = Options B + E N = Options C + D P = Options C + E Q = Options D + E R = Options A + B + C S = Options A + B + D T = Options A + B + E U = Options A + C + D V = Options A + C + E W = Options A + D + E Y = Options B + C + D Z = Options B + C + E 1 = Options B + D + E 2 = Options C + D + E 3 = Options A + B + C + D 4 = Options A + B + C + E 5 = Options A + B + D + E 6 = Options A + C + D + E 7 = Options B + C + D + E 8 = Options A + B + C + D + E
Feature 13: SPECIAL CONTROLS
0 = Terminal Block D = VAV Unit Controller - VAV Cool + CV Heat E = Constant Volume Unit Controller - CV Cool + CV Heat F = Makeup Air Unit Controller - CV Cool + CV Heat J = Factory Installed DDC Controls Furnished by Others K = Factory Installed DDC Controls Furnished by Others with Isolation Relays L = Terminal Block for Thermostat Control with Isolation Relays W = Terminal Block for Variable Capacity Compressor Thermostat Y = VAV Single Zone Heat Pump Unit Controller ­VAV Cool + VAV Heat Z = Constant Volume Heat Pump Unit Controller ­CV Cool + CV Heat 1 = Makeup Air Heat Pump Unit Controller - CV Cool + CV Heat 2 = VAV Single Zone Unit Controller VAV Cool + CV Heat 3 = VAV Single Zone Unit Controller VAV Cool + VAV Heat 4 = Field Installed DDC Controls by Others 5 = Field Installed DDC Controls Furnished by Others with Isolation Relays 6 = Factory Installed DDC Controls Furnished by Others with Isolation Relays (SPA)
Feature 14: PREHEAT
14A: PREHEAT CONFIGURATION
0 = Standard - None A = Steam Distributing Preheat Coil - 1 Row C = Hot Water Preheat Coil - 1 Row
14B: PREHEAT SIZING
0 = Standard – None A = Single Serpentine 8 fpi B = Half Serpentine 8 fpi E = Single Serpentine 12 fpi F = Half Serpentine 12 fpi
20
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 15: Glycol Percentage
0 = Standard A = 20% Propylene Glycol B = 40% Propylene Glycol C = Field Adjustable for Glycol Percentage
Feature 16: INTERIOR CABINET OPTIONS
0 = Standard B = Service Lights
Feature 17: EXTERIOR CABINET OPTIONS
0 = Standard A = Base Insulation B = Burglar Bars D = Options A + B
Feature 18: CUSTOMER CODE
0 = Standard
Feature 19: CODE OPTIONS
0 = Standard - ETL U.S.A. Listing A = M.E.A. B = Chicago - Cool + Gas C = Chicago - Cool + Electric Heat D = Chicago - Cool Only E = Chicago - Gas Only F = Chicago - Electric Heat Only G = Chicago - No Cool + No Heat H = ETL U.S.A. + Canada Listing K = California OSHPD Certification L = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156) M = Seismic Construction (Non-Certified) N = California OSHPD Certification + Chicago P = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156) + Chicago Q = Seismic Construction (Non-Certified) + Chicago
Feature 20: CRATING
0 = Standard A = Export Crating B = Export Crating - No Condenser Section
Feature 21: WATER-COOLED CONDENSER
0 = Standard - None A = Balancing Valves B = Water Flow Switch C = Motorized Shut-off Valve D = Head Pressure Control E = Options A + B F = Options A + C G = Options A + D H = Options B + C J = Options B + D L = Options A + B + C M = Options A + B + D R = CuNi Coaxial Heat Exchanger S = Options A + R T = Options B + R U = Options C + R V = Options D + R W = Options A + B + R Y = Options A + C + R Z = Options A + D + R 1 = Options B + C + R 2 = Options B + D + R 3 = Options C + D + R 4 = Options A + B + C + R 5 = Options A + B + D + R
21
RQ Series Feature String Nomenclature
Model Options : Unit Feature Options
GEN
SIZE
VLT
CONFIG
A1
A2
A3
A4
B1
B2
B3
1A
1B
1C
1D 2 3 4 5A
5B
5C
6A
6B
6C 7 8 9 10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
R Q – 0 0 5 – 3 – V – B B 0 1 – 3 3 4 : A 0 0 0 – D 0 B – P J C – 0 B A – 0 D 0 0 0 0 L – 0 0 – 0 0 B 0 0 0 0 0 B
Feature 22: CONTROL VENDORS
0 = None A = WattMaster Orion Controls System B = JENEsys Control System with Web UI C = WattMaster Orion Controls System with Specials E = Remote Mounted AAON Mini Controller F = JENEsys Control System with Web UI + Fox G = JENEsys Control System with Web UI + Lon H = JENEsys Control w/Web UI + BACnet MSTP J = JENEsys Control w/Web UI + BACnet IP K = JENEsys Control w/Web UI + Modbus RTU L = JENEsys Control w/Web UI + Modbus TCP
Feature 23: TYPE
B = Standard - AAON Gray Paint U = Special Pricing Authorization + Special Paint X = Special Pricing Authorization + AAON Gray Paint 4 = Standard Paint + 5 Year Parts Only Warranty 9 = Standard Paint + 10 Year Parts Only Warranty
22

General Information

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
WARNING
These units must not be used as a
“construction heater” at any time
during any phase of construction. Very low return air temperatures, harmful vapors, and misplacement of the filters will damage the unit and its efficiency.
CAUTION
RQ Series packaged rooftop units, heat pumps and outdoor air handling units have been designed for outdoor installation only. Units are assembled, wired, charged and run tested at the factory.
Startup and service must be performed by a Factory Trained Service Technician.
Certification of Gas Heat Models
a. AAON gas heat exchangers have
successfully completed 10,000 burner operation cycles and corrosion resistance as specified per test standard ANSI
21.47. All gas heat exchangers used in AAON appliances are certified for use downstream of evaporator or cooling coils.
b. Certified as a Category III forced air
furnace with or without cooling.
c. Certified for outdoor installation only. d. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Steam or Hot Water Heat Models
a. Certified as a forced air heating system
with or without cooling.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically operated compressors.
b. Certified for outdoor installation only. c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.

Codes and Ordinances

RQ Series units have been tested and certified, by ETL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236, ANSI Safety Standard Z21.47b-2008/CSA
2.3b-2008, and ANSI Safety Standard Z83.8-2006/CSA 2.6-2006.
System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook.
23
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed.
CAUTION
Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.
WARNING
Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.
WARNING
Installation of RQ Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, and local building, plumbing and waste water codes. In the absence of local codes installation must conform to the current (United States) National Fuel Gas Code ANSI-Z223.1/NFPA 54 or the current (Canada) National Fuel & Propane Installation Code CSA B149.1 or B149.2, and Mechanical Refrigeration Code CSA B52. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
24

Receiving Unit

When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted
on the carrier’s freight bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be checked to ensure the correct model sizes and voltages have been received to match the job requirements.
If repairs must be made to damaged goods, then the factory should be notified before any repair action is taken in order to protect the warranty. Certain equipment alteration, repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact the AAON Warranty Department for assistance with handling damaged goods, repairs, and freight claims: (918) 583-2266.
Note: Upon receipt check shipment for items that ship loose such as filters and remote sensors. Consult order and shipment documentation to identify potential loose­shipped items. Loose-shipped items may have been placed inside unit cabinet for security. Installers and owners should secure all doors with locks or nuts and bolts to prevent unauthorized access.
Figure 1 - Lockable Handle
The warranty card must be completed in full
CRANKCASE HEATER
OPERATION
Some units are equipped with a compressor crankcase heater, which should be energized at least 24 hours prior to cooling operation, to clear any liquid refrigerant from the compressor.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
and returned to AAON not more than 3 months after unit is delivered.
Storage
If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose-shipped items.

Packaged Direct Expansion (DX) Units

DX refrigeration system is factory assembled, leak tested, charged with refrigerant and run tested.
Refrigerant system includes an evaporator, condenser, liquid line filter drier, thermal expansion valve (TXV), and scroll compressor. Compressor is equipped with a positive pressure forced lubrication system.
Never cut off the main power supply to the unit, except for servicing, emergency, or complete shutdown of the unit. When power is cut off from the unit crankcase heater cannot prevent refrigerant migration into the compressor. This means the compressor will cool down and liquid refrigerant may accumulate in the compressor. The compressor is designed to pump refrigerant gas and damage may occur when power is restored.
If power to the unit must be off for more than an hour, turn the thermostat system switch to "OFF", or turn the unit off at the control panel, and leave the unit off until the main power switch has been turned on again for at least 24 hours for units with compressor crankcase heaters. This will give the crankcase heater time to clear any liquid accumulation out of the compressor before it is started.
Always control the unit from the thermostat, or control panel, never at the main power supply, except for servicing, emergency or complete shutdown of the unit.
During the cooling season, if the air flow is reduced due to dirty air filters or any other reason, the cooling coil can get too cold which will cause excessive liquid to return
25
Model
Option B2
Gas Heat
Electric Heat
Input Capacity
Output Capacity
Capacity
MBH
MBH
kW (208V)
kW (230V, 460V, 575V)
1 = Heat 1
60.0
48.0
7.5
10
2 = Heat 2
15.0
20
3 = Heat 3
100.0
80.0
22.5
30
4 = Heat 4
30.0
40
5 = Heat 5
140.0
112.0
6 = Heat 6
7 = Heat 7
160.0
128.0
to the compressor. As the liquid concentration builds up, oil is washed out of the compressor, leaving it starved for lubrication.
The compressor life will be seriously shorted by reduced lubrication and the pumping of excessive amounts of liquid oil and refrigerant.
Note: Low Ambient Operation Air-cooled DX units without a low ambient option, such as condenser fan cycling, ECM driven condenser fans or the 0°F low ambient option, will not operate in the cooling mode of operation properly when the outdoor temperature is below 55°F. Low ambient and/or economizer options are recommended if cooling operation below 55°F is expected.
Note: Multiple Units with Multiple Thermostats When several heating and cooling units are used to condition a space all unit thermostat switches must be set in either heating mode, cooling mode or off. Do not leave part of the units switched to the opposite mode. Cooling only units should be switched off at the thermostat during the heating season.
Table 1 - Electric and Gas Heating Capacities

Gas or Electric Heating The unit is designed to heat a given amount of air while operating. If this amount of air is greatly reduced, approximately 1/3 during the heating season, the gas heat exchanger or electric heating coil may overheat, and may cut the burner or heater off entirely by action of the safety high temperature limit devices which are factory mounted at the heat exchanger and supply fan areas.

Airflow should be adjusted after installation to obtain an air temperature rise within the range specified on the unit rating plate at the required external static pressure.
Should overheating occur with a gas heat exchanger, or the gas supply fail to shut off, shut off the manual gas valve to the furnace before shutting off the electrical supply.
Prolonged overheating of the heat exchanger will shorten its life.
If unit has not been selected as a 100% outside air unit (makeup air unit) the return air duct must be sealed to the unit and the return air temperature must be maintained between 55F and 80F.
26
Loading...
+ 58 hidden pages