Figure 37 - RQ Series 2-6 ton Standard Filter Layout .................................................................. 85
6
Page 7
AAON® RQ Series Features and Options Introduction
Energy Efficiency
• Direct Drive Backward Curved Plenum
Supply Fans
• Variable Capacity R-410A Scroll
Compressors
• Airside Economizers
• Factory Installed AAONAIRE
Recovery Wheels
• Double Wall Rigid Polyurethane Foam
Panel Construction, R-13 Insulation
• Modulating Natural Gas Heaters
• Modulating/SCR Electric Heaters
• Premium Efficiency Motors
• Variable Speed Supply/ Exhaust Fans
• Air-Source, Water-Source and
Geothermal Heat Pumps
Indoor Air Quality
• 100% Outside Air
• Constant Volume Outside Air Control
• Economizer CO
• High Efficiency Filtration
• Double Wall Rigid Polyurethane Foam
Override
2
Panel Construction, R-13 Insulation
• Interior Corrosion Protection
Humidity Control
• High Capacity Cooling Coils
• Variable Capacity Compressors
• Factory Installed AAONAIRE Total
Energy Recovery Wheels
• Modulating Hot Gas Reheat
Safety
• Burglar Bars
• Freeze Stats
• Hot Water/Steam Preheat Coils
• Electric Preheat
• Phase and Brown Out Protection
• Supply/Return Smoke Detectors
• Supply/Return Firestats
®
Energy
Installation and Maintenance
• Clogged Filter Switch
• Color Coded Wiring Diagram
• Compressors in Isolated Compartment
• Compressor Isolation Valves
• Convenience Outlet
• Direct Drive Supply Fans
• Hinged Access Doors with Lockable
Handles
• Magnehelic Gauge
• Service Lights
• Sight Glass
System Integration
• Chilled Water Cooling Coils
• Controls by Others
• Electric/Natural Gas/LP Heating
• Hot Water/Steam Heating Coil
• Non-Compressorized DX Coils
Environmentally Friendly
• Airside Economizers
• Factory Installed AAONAIRE Energy
Recovery Wheels
• R-410A Refrigerant
Extended Life
• 5 Year Compressor Warranty
• 15 Year Aluminized Steel Heat
Exchanger Warranty
• 25 Year Stainless Steel Heat Exchanger
Warranty
• Interior Corrosion Protection
• Polymer E-Coated Coils - 5 Year
Warranty
• Stainless Steel Coil Casing
• Stainless Steel Drain Pans
7
Page 8
Safety
G
CAUTIO
G
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
ELECTRIC SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death or property damage.
Before servicing, disconnect all
When servicing controls, label all
Verify proper operation after
WARNIN
electrical power to the furnace.
More than one disconnect may be
provided.
wires prior to disconnecting.
Reconnect wires correctly.
servicing. Secure all doors with
key-lock or nut and bolt.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
Never test for gas leaks with an
Use a gas detection soap solution
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
building.
open flame.
and check all gas connections
and shut off valves.
WARNIN
N
8
Page 9
G
G
G
G
G
CAUTIO
WARNIN
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
WARNIN
ROTATING COMPONENTS
Unit contains fans with moving parts
that can cause serious injury. Do not
open door containing fans until the
power to the unit has been
disconnected and fan wheel has
stopped rotating.
WARNIN
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNIN
During installation, testing, servicing
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNIN
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
N
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
9
Page 10
G
CAUTIO
CAUTIO
G
G
G
CAUTIO
CAUTIO
WARNIN
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
N
Failure to properly drain and vent
coils when not in use during freezing
temperature may result in coil and
equipment damage.
N
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
WARNIN
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNIN
WATER PRESSURE
Prior to connection of condensing
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
or death due to instantaneous
release of high pressure water, relief
valves should be field supplied on
system water piping.
WARNIN
Always use a pressure regulator,
valves and gauges to control
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
N
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not use alkaline chemical coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
N
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
10
Page 11
G
CAUTIO
CAUTIO
G
G
p
G
WARNIN
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
N
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
N
Cleaning the cooling tower or
condenser water loop with harsh
chemicals such as hydrochloric acid
(muriatic acid), chlorine or other
chlorides, can damage the
refrigerant-to-water heat exchanger.
Care should be taken to avoid
allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion Resistance for more
information.
WARNIN
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
of chemical corrosion is excluded
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer’s warranties.
WARNIN
WATER FREEZING
Failure of the condenser due to
freezing will allow water to enter the
refrigerant circuit and will cause
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
WARNIN
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts
er hour.
11
Page 12
1. Startup and service must be performed
by a Factory Trained Service
Technician.
2. Use only with type of the gas approved
for the furnace. Refer to the furnace
rating plate.
3. The unit is for outdoor use only. See
General Information section for more
information.
4. Provide adequate combustion ventilation
air to the furnace. If a vent duct
extension is used, a class III approved
vent is required. See the Locating Units
and Gas Heating sections of the
Installation section of the manual.
5. Always install and operate furnace
within the intended temperature rise
range and duct system external static
pressure (ESP) as specified on the unit
nameplate.
6. The supply and return air ducts must be
derived from the same space. It is
recommended ducts be provided with
access panels to allow inspection for
duct tightness. When a down flow duct
is used with electric heat, the exhaust
duct should be an L shaped duct.
7. Clean furnace, duct and components
upon completion of the construction
setup. Verify furnace operating
conditions including input rate,
temperature rise and ESP.
8. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
9. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
10. Keep this manual and all literature
safeguarded near or on the unit.
12
Page 13
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01
-334:A000-D0B-PJC-0BA-0D0000L-00-00B00000B
BASE MODEL
SERIES AND GENERATION
RQ
UNIT SIZE
002 = 2 ton Capacity
003 = 3 ton Capacity
004 = 4 ton Capacity
005 = 5 ton Capacity
006 = 6 ton Capacity
DISCHARGE/RETURN CONFIGURATION
AND INTERIOR CORROSION PROTECTION
V = Vertical Discharge and Return
H = Horizontal Discharge and Return
J = Option H + Interior Corrosion Protection
W = Option V + Interior Corrosion Protection
K = Vertical Discharge and Horizontal Return
L = Option K + Interior Corrosion Protection
M = Horizontal Discharge and Vertical Return
N = Option M + Interior Corrosion Protection
Model Option A: COOLING/HEAT
PUMP
A1: REFRIGERANT STYLE
0 = Air Handling Unit
B = R-410A - Non-Compressorized DX Air Handling
Unit
C = R-410A - Standard Efficiency
E = R-410A Variable Capacity Scroll Compressor High Efficiency
F = R-410A Variable Capacity Scroll Compressor Standard Efficiency
G = R-410A Two-Step Compressor - High Efficiency
H = R-410A Two-Step Compressor - Standard
Efficiency
:
5A5B5C6A6B6C78910111213
14A
14B1516171819202122
A2: UNIT CONFIGURATION
0 = No Cooling
A = Air-Cooled Cond. + Std Evap. Coil
B = Air-Cooled Cond. + 6 Row Evap. Coil
J = Water-Cooled Cond. + Std Evap. Coil
K = Water-Cooled Cond. + 6 Row Evap. Coil
U = Chilled Water Coil - 4 Row
W = Chilled Water Coil - 6 Row
2 = Non-Compressorized + Std Evap. Coil
4 = Non-Compressorized + 6 Row Evap. Coil
6 = Air-Source Heat Pump
7 = Water-Source/Geothermal Heat Pump
0 = No Cooling
1 = 1 Stage
2 = 2 Stage
9 = Modulating - Lead VCC
B = 1 Stage + 1 Stage Auxiliary Heat
C = 2 Stage + 1 Stage Auxiliary Heat
E = Modulating - Lead VCC + 1 Stage Aux. Heat
H = Single Serpentine 8 fpi
J = Half Serpentine 8 fpi
K = Single Serpentine 10 fpi
L = Half Serpentine 10 fpi
M = Single Serpentine 12 fpi
N = Half Serpentine 12 fpi
P = 1 Stage + 2 Stage Auxiliary Heat
Q = 2 Stage + 2 Stage Auxiliary Heat
S = Modulating - Lead VCC + 2 Stage Aux. Heat
U = 1 Stage + 4 Stage Auxiliary Heat
V = 2 Stage + 4 Stage Auxiliary Heat
Y = Modulating - Lead VCC + 4 Stage Aux. Heat
23
13
Page 14
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01-
Model Option B: HEATING
B1: HEATING TYPE
0 = No Heating
1 = Electric Heat
2 = Natural Gas Aluminized
3 = Natural Gas Stainless Steel
4 = High Altitude Natural Gas Aluminized
5 = High Altitude Natural Gas Stainless Steel
6 = LP Gas Aluminized
7 = LP Gas Stainless Steel
8 = High Altitude LP Gas Aluminized
9 = High Altitude LP Gas Stainless Steel
C = Steam Distributing Standard
D = Steam Distributing Polymer E-Coated
E = Hot Water Standard
F = Hot Water Polymer E-Coated
0 = No Heating
1 = 1 Stage
2 = 2 Stage
3 = 3 Stage
4 = 4 Stage
9 = Modulating Gas/SCR Electric
A = SCR Electric, 0-10V External Control
H = Single Serpentine 8 fpi
J = Half Serpentine 8 fpi
M = Single Serpentine 12 fpi
N = Half Serpentine 12 fpi
:
334:A000
5A5B5C6A6B6C78910111213
-D0B-PJC-0BA-0D0000L-00-00B00000B
Feature 1: RETURN/OUTSIDE AIR
1A: RETURN/OUTSIDE AIR SECTION
0 = Manually Adjustable OA Opening + RA Opening
A = Economizer
B = Econ + Power Exhaust
F = Low cfm Total Energy Recovery Wheel
G = Low cfm Total ERW + Bypass Damper
H = Low cfm Sensible ERW
J = Low cfm Sensible ERW + Bypass Damper
K = 100% Outside Air - No Return Air Opening
L = Motorized Outside Air Damper + RA Opening
M = Motorized Outside Air Damper - No RA
Opening
N = Empty ERW Option Box- No Power Exhaust
P = Empty ERW Option Box + Power Exhaust
5 = 100% Return Air
1B: RETURN/EXHAUST AIR BLOWER
CONFIGURATION
0 = Standard – None
A = 1 Blower + Standard Eff. Motor
C = 1 Blower + Premium Eff. Motor
E = 1 Blower + Premium Eff. Motor + 1 VFD
H = 1 Blower + High Efficiency EC Motor
J = 1 Blower + Single Phase Motor + Speed Control
0 = Standard - None
A = 0.25 hp - 850 rpm
B = 0.5 hp - 1075 rpm
C = 1 hp - 1750 rpm
D = 2 hp - 1760 rpm
W = 0.75 hp - 1760 rpm
Z = 0.167 hp - 825 rpm
14A14B1516171819202122
23
14
Page 15
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01-334:A000-
Feature 2: OUTSIDE AIR CONTROL
0 = Standard - None
A = 3 Position Actuator - Sensible Limit
B = 3 Position Actuator - Enthalpy Limit
C = Fully Modulating Actuator - Sensible Limit
D = Fully Modulating Actuator - Enthalpy Limit
E = DDC Actuator
M = 3 Pos. Act. - Sensible Limit + CO
N = 3 Pos. Act. - Enthalpy Limit + CO
P = Fully Mod. Act. - Sensible + CO
Q = Fully Mod. Act. - Enthalpy + CO
R = DDC Actuator + CO
Override
2
S = Dual Minimum Position Potentiometers + Fully
Mod. Act. - Sensible Limit
T = Dual Minimum Position Potentiometers + Fully
Mod. Act. - Enthalpy Limit
U = 2 Position Actuator
Feature 3: HEAT OPTIONS
0 = Standard - None
E = Discharge Air Override
K = Auxiliary Heat K
L = Auxiliary Heat L
M = Auxiliary Heat M
N = Auxiliary Heat N
Feature 4: MAINTENANCE OPTIONS
0 = Standard - None
A = Field Wired 115V Outlet
B = Factory Wired 115V Outlet
C = Blower Aux. Contact
D = Remote Start/Stop Terminals
E = Options A + C
F = Options A + D
G = Options B + C
H = Options B + D
J = Options A + C + D
K = Options B + C + D
L = Options C + D
:
Override
2
Override
2
Override
2
Override
2
5A5B5C6A6B6C78910111213
D0B-PJC- 0
Feature 5: SUPPLY AIR OPTIONS
5A: SUPPLY AIR BLOWER CONFIGURATION
P = 1 Blower + High Efficiency EC Motor
Q = 1 Blower + Inverter Rated Motor + 1 VFD
R = 1 Blower + Single Phase Motor + Speed Control
5B: SUPPLY AIR BLOWER
J = 18.5” Direct Drive Backward Curved Plenum
K = 18.5” Direct Drive BC Plenum - 60% Width
5C: SUPPLY AIR BLOWER MOTOR
A = 0.25 hp - 850 rpm
B = 0.5 hp - 1075 rpm
C = 1 hp - 1750 rpm
D = 2 hp - 1760 rpm
W = 0.75 hp - 1760 rpm
Z = 0.167 hp - 825 rpm
Feature 6: FILTERS
6A: PRE FILTER
0 = Standard - None
A = 2” Pleated - 30% Eff. - MERV 8
B = Metal Mesh Outside Air Filter
C = Lint Screen Filter
D = Exhaust Air ERW Filter
E = Option A + B
F = Option A + D
G = Option B + D
H = Option A + B + D
14A14B1516171819202122
BA-0D0000L-00-00B00000B
23
15
Page 16
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01-334:A000-D0B-PJC-0BA-
6B: UNIT FILTER
0 = 2” Throwaway or
2” Pleated - 30% Eff. - MERV 8
A = 2” Pleated - 30% Eff. - MERV 8
B = 4” Pleated - 30% Eff. - MERV 8
C = 2” Permanent Filter + Replaceable Media
F = 4” Pleated - 65% Eff. - MERV 11
G = 4” Pleated - 85% Eff. - MERV 13
H = 4” Pleated - 95% Eff. - MERV 14
6C: FILTER OPTIONS
0 = Standard
A = Clogged Filter Switch
B = Magnehelic Gauge
C = Options A + B
Feature 7: REFRIGERATION
CONTROL
0 = Standard
A = 5 Min. Time Delay Relay - Comp. Off
C = Non-Adjustable Fan Cycling or Adjustable Fan
Cycling
D = Adjustable Lockouts - Each Circuit
E = Freeze Stats - Each Circuit
G = Options A + C
H = Options A + D
J = Options A + E
N = Options C + D
P = Options C + E
Q = Options D + E
U = Options A + C + D
V = Options A + C + E
W = Options A + D + E
2 = Options C + D + E
6 = Options A + C + D + E
Feature 8: REFRIGERATION OPTIONS
0 = Standard
C = Hot Gas Reheat
D = Modulating Hot Gas Reheat
E = 0°F Low Ambient Lead Stage
M = Polymer E-Coated Hot Gas Reheat
N = Polymer E-Coated Modulating Hot Gas Reheat
:
5A5B5C6A6B6C78910111213
Feature 9: REFRIGERATION
ACCESSORIES
0 = Standard
A = Sight Glass
B = Compressor Isolation Valves
C = Options A + B
D = ECM Condenser Fan - Multiple Speed
E = ECM Condenser Fan – Head Pressure Control
G = Options A + D
H = Options B + D
J = Options A + B + D
K = Options A + E
L = Options B + E
M = Options A + B + E
Feature 10: POWER OPTIONS
0 = Standard Power Block
A = 100 Amp Power Switch
B = 150 Amp Power Switch
F = 60 Amp Power Switch
Feature 11: SAFETY OPTIONS
0 = Standard
A = Return and Supply Air Firestat
B = Return Air Smoke Detector
C = Supply Air Smoke Detector
D = Options B + C
E = Options A + B
F = Options A + C
G = Options A + B + C
H = Remote Safety Shutoff Terminals
J = Options A + H
K = Options B + H
L = Options C + H
M = Options D + H
N = Options A + B + H
P = Options A + C + H
Q = Options A + D + H
OD 0 0 0
14A14B1516171819202122
0L-00 -00B00000B
23
16
Page 17
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01-334:A000-D0B-PJC-0BA-0D000
Feature 12: CONTROLS
0 = Standard
A = Low Limit Controls
B = Phase and Brown Out Protection
C = Energy Recovery Wheel Defrost
D = Energy Recovery Wheel Rotation Detection
E = Compressor Power Factor Correction
F = Options A + B
G = Options A + C
H = Options A + D
J = Options A + E
K = Options B + C
L = Options B + D
M = Options B + E
N = Options C + D
P = Options C + E
Q = Options D + E
R = Options A + B + C
S = Options A + B + D
T = Options A + B + E
U = Options A + C + D
V = Options A + C + E
W = Options A + D + E
Y = Options B + C + D
Z = Options B + C + E
1 = Options B + D + E
2 = Options C + D + E
3 = Options A + B + C + D
4 = Options A + B + C + E
5 = Options A + B + D + E
6 = Options A + C + D + E
7 = Options B + C + D + E
8 = Options A + B + C + D + E
:
5A5B5C6A6B6C78910111213
Feature 13: SPECIAL CONTROLS
0 = Terminal Block
D = VAV Unit Controller - VAV Cool + CV Heat
E = Constant Volume Unit Controller - CV Cool +
CV Heat
F = Makeup Air Unit Controller - CV Cool + CV
Heat
J = Factory Installed DDC Controls Furnished by
Others
K = Factory Installed DDC Controls Furnished by
Others with Isolation Relays
L = Terminal Block for Thermostat Control with
Isolation Relays
W = Terminal Block for Variable Capacity
Compressor Thermostat
Y = VAV Single Zone Heat Pump Unit Controller VAV Cool + VAV Heat
Z = Constant Volume Heat Pump Unit Controller CV Cool + CV Heat
1 = Makeup Air Heat Pump Unit Controller - CV
Cool + CV Heat
2 = VAV Single Zone Unit Controller VAV Cool +
CV Heat
3 = VAV Single Zone Unit Controller VAV Cool +
VAV Heat
4 = Field Installed DDC Controls by Others
5 = Field Installed DDC Controls Furnished by
Others with Isolation Relays
6 = Factory Installed DDC Controls Furnished by
Others with Isolation Relays (SPA)
Feature 14: PREHEAT
14A: PREHEAT CONFIGURATION
0 = Standard - None
A = Steam Distributing Preheat Coil - 1 Row
C = Hot Water Preheat Coil - 1 Row
E = Modulating Electric Preheat
14A14B1516171819202122
0L- 0
0-00B00000B
23
17
Page 18
RQ Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
RQ-005-3-V-BB01-334:A000-D0B-PJC-0BA-0D0000L-0
14B: PREHEAT SIZING
0 = Standard – None
A = Single Serpentine 8 fpi
B = Half Serpentine 8 fpi
E = Single Serpentine 12 fpi
F = Half Serpentine 12 fpi
G = 10 kW (7.5 kW @ 208V)
H = 15 kW (11.3 kW @ 208V)
J = 20 kW (15 kW @ 208V)
Feature 15: Glycol Percentage
0 = Standard
A = 20% Propylene Glycol
B = 40% Propylene Glycol
C = Field Adjustable for Glycol Percentage
Feature 16: INTERIOR CABINET
OPTIONS
0 = Standard
B = Service Lights
Feature 17: EXTERIOR CABINET
OPTIONS
0 = Standard
A = Base Insulation
B = Burglar Bars
D = Options A + B
Feature 18: CUSTOMER CODE
0 = Standard
:
5A5B5C6A6B6C78910111213
Feature 19: CODE OPTIONS
0 = Standard - ETL U.S.A. Listing
A = M.E.A.
B = Chicago - Cool + Gas
C = Chicago - Cool + Electric Heat
D = Chicago - Cool Only
E = Chicago - Gas Only
F = Chicago - Electric Heat Only
G = Chicago - No Cool + No Heat
H = ETL U.S.A. + Canada Listing
K = California OSHPD Certification
L = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156)
M = Seismic Construction (Non-Certified)
N = California OSHPD Certification + Chicago
P = Shake Table Cert. (ASCE 7-05/ICC-ES AC 156)
+ Chicago
Q = Seismic Construction (Non-Certified) + Chicago
Feature 20: CRATING
0 = Standard
A = Export Crating
B = Export Crating - No Condenser Section
0 = Standard - None
A = Balancing Valves
B = Water Flow Switch
C = Motorized Shut-off Valve
D = Head Pressure Control
E = Options A + B
F = Options A + C
G = Options A + D
H = Options B + C
J = Options B + D
L = Options A + B + C
M = Options A + B + D
R = CuNi Coaxial Heat Exchanger
S = Options A + R
T = Options B + R
U = Options C + R
V = Options D + R
W = Options A + B + R
Y = Options A + C + R
Z = Options A + D + R
1 = Options B + C + R
2 = Options B + D + R
3 = Options C + D + R
4 = Options A + B + C + R
5 = Options A + B + D + R
:
5A5B5C6A6B6C78910111213
14A14B1516171819202122
Feature 22: CONTROL VENDORS
0 = None
A = WattMaster Orion VCM-X Controls System
B = JENEsys Control System with Web UI
C = WattMaster Orion VCM-X Controls System with
Specials
E = Remote Mounted AAON Mini Controller or
Remote Mounted AAON Touchscreen Controller
F = JENEsys Control System with Web UI + Fox
G = JENEsys Control System with Web UI + Lon
H = JENEsys Control w/Web UI + BACnet MSTP
J = JENEsys Control w/Web UI + BACnet IP
K = JENEsys Control w/Web UI + Modbus RTU
L = JENEsys Control w/Web UI + Modbus TCP
T = WattMaster Orion VCB-X Controls System +
Integrated BACnet MSTP
U = WattMaster Orion VCB-X Controls System +
Integrated BACnet MSTP with Specials
Feature 23: TYPE
B = Standard - AAON Gray Paint
U = Special Pricing Authorization + Special Paint
X = Special Pricing Authorization + AAON Gray
Paint
4 = Standard Paint + 5 Year Parts Only Warranty
9 = Standard Paint + 10 Year Parts Only Warranty
23
00B
19
Page 20
G
CAUTIO
General Information
RQ Series packaged rooftop units, heat
pumps and outdoor air handling units have
been designed for outdoor installation only.
Units are assembled, wired, charged and run
tested at the factory.
Startup and service must be performed by a
Factory Trained Service Technician.
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.
Certification of Gas Heat Models
a. AAON gas heat exchangers have
b. Certified as a Category III forced air
WARNIN
successfully completed 10,000 burner
operation cycles and corrosion resistance
as specified per test standard ANSI
21.47. All gas heat exchangers used in
AAON appliances are certified for use
downstream of evaporator or cooling
coils.
furnace with or without cooling.
N
c. Certified for outdoor installation only.
d. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air heating system
with or without cooling.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically
operated compressors.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.
Codes and Ordinances
RQ Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236,
ANSI Safety Standard Z21.47b-2008/CSA
2.3b-2008, and ANSI Safety Standard
Z83.8-2006/CSA 2.6-2006.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
20
Page 21
Installation of RQ Series units must conform
CAUTIO
G
G
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. In the absence of local
codes installation must conform to the
current (United States) National Fuel Gas
Code ANSI-Z223.1/NFPA 54 or the current
(Canada) National Fuel & Propane
Installation Code CSA B149.1 or B149.2,
and Mechanical Refrigeration Code CSA
B52. All appliances must be electrically
grounded in accordance with local codes, or
in the absence of local codes, the current
National Electric Code, ANSI/NFPA 70 or
the current Canadian Electrical Code CSA
C22.1.
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling or reclaiming
must be followed.
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with
equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
WARNIN
WARNIN
N
transit. If damage is found it should be noted
on the carrier’s freight bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
If repairs must be made to damaged goods,
then the factory should be notified before
any repair action is taken in order to protect
the warranty. Certain equipment alteration,
repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact the
AAON Warranty Department for assistance
with handling damaged goods, repairs, and
freight claims: (918) 583-2266.
Note: Upon receipt check shipment for
items that ship loose such as filters and
remote sensors. Consult order and shipment
documentation to identify potential looseshipped items. Loose-shipped items may
have been placed inside unit cabinet for
security. Installers and owners should secure
all doors with locks or nuts and bolts to
prevent unauthorized access.
Figure 1 - Lockable Handle
The warranty card must be completed in full
and returned to AAON not more than 3
months after unit is delivered.
21
Page 22
G
CAUTIO
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Packaged Direct Expansion (DX) Units
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
DX refrigeration system is factory
assembled, leak tested, charged with
refrigerant and run tested.
Refrigerant system includes an evaporator,
condenser, liquid line filter drier, thermal
expansion valve (TXV), and scroll
compressor. Compressor is equipped with a
positive pressure forced lubrication system.
Never cut off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit crankcase heater
cannot prevent refrigerant migration into the
compressor. This means the compressor will
cool down and liquid refrigerant may
accumulate in the compressor. The
WARNIN
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
5 MINUTE MINIMUM ON TIME
compressor is designed to pump refrigerant
gas and damage may occur when power is
restored.
Some units are equipped with a
compressor crankcase heater, which
should be energized at least 24 hours
prior to cooling operation, to clear
any liquid refrigerant from the
compressor.
If power to the unit must be off for more
than an hour, turn the thermostat system
switch to "OFF", or turn the unit off at the
control panel, and leave the unit off until the
main power switch has been turned on again
for at least 24 hours for units with
compressor crankcase heaters. This will give
the crankcase heater time to clear any liquid
accumulation out of the compressor before it
is started.
Always control the unit from the thermostat,
or control panel, never at the main power
supply, except for servicing, emergency or
complete shutdown of the unit.
During the cooling season, if the air flow is
reduced due to dirty air filters or any other
reason, the cooling coil can get too cold
which will cause excessive liquid to return
to the compressor. As the liquid
concentration builds up, oil is washed out of
the compressor, leaving it starved for
lubrication.
The compressor life will be seriously
shorted by reduced lubrication and the
pumping of excessive amounts of liquid oil
and refrigerant.
CRANKCASE HEATER
OPERATION
N
22
Page 23
Note: Low Ambient Operation
Air-cooled DX units without a low ambient
option, such as condenser fan cycling, ECM
driven condenser fans or the 0°F low
ambient option, will not operate in the
cooling mode of operation properly when
the outdoor temperature is below 55°F. Low
ambient and/or economizer options are
recommended if cooling operation below
55°F is expected.
Note: Multiple Units with Multiple
Thermostats
When several heating and cooling units are
used to condition a space all unit thermostat
switches must be set in either heating mode,
cooling mode or off. Do not leave part of the
units switched to the opposite mode.
Cooling only units should be switched off at
the thermostat during the heating season.
Gas or Electric Heating
The unit is designed to heat a given amount
of air while operating. If this amount of air
is greatly reduced, approximately 1/3 during
the heating season, the gas heat exchanger or
electric heating coil may overheat, and may
cut the burner or heater off entirely by action
of the safety high temperature limit devices
which are factory mounted at the heat
exchanger and supply fan areas.
Airflow should be adjusted after installation
to obtain an air temperature rise within the
range specified on the unit rating plate at the
required external static pressure.
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
If unit has not been selected as a 100%
outside air unit (makeup air unit) the return
air duct must be sealed to the unit and the
return air temperature must be maintained
between 55°F and 80°F.
kW (230V, 380V ,
460V, 575V)
23
Page 24
CAUTIO
Table 2 - Auxiliary Electric Heating Capacities
Feature 3 kW (208V) kW (230V, 380V 460V,
*K = Heat K 7.5 10.0
*L = Heat L 15.0 20.0
*M = Heat M22.5 30.0
*N = Heat N 30.0 40.0
Wiring Diagrams
Unit specific wiring diagrams are laminated
and affixed inside the compressor and
control compartment door.
Condensate Drain Pan
Unit requires drain trap to be connected to
the condensate drain pan of the unit. Units
include one drain pan connection.
Condensate drain pipes or p-trap is factory
supplied and shipped loose in the control
compartment for field installation.
If codes require a condensate drain line, the
line should be the same pipe size or larger
than the drain connection, include a p-trap,
and pitch downward toward drain. An air
break should be used with long runs of
condensate lines.
575V)
Unit should not be operated without a
p-trap. Failure to install a p-trap may
result in overflow of condensate
water.
N
24
Page 25
Installation
G
G
AAON equipment has been designed for
quick and easy installation.
Unit Location
The curb should be mounted first and must
be located so that duct connections will be
clear of structural members of the building.
Verify rooftop or foundation can support the
total unit weight, including accessory
weights.
When locating gas fired units, it is
recommended the unit be installed so
that the flue discharge vents are
located at least 120 inches away
from any opening through which
combustion products could enter the
building.
Distances from adjacent public
walkways, adjacent buildings,
operable windows and building
openings, shall conform to local
codes and/or the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the
National Gas & Propane Code, CSA
B149.1
Do not position flue opening to discharge
into a fresh air intake of any other piece of
equipment. Unit should also be installed so
that the flow of combustion intake air is not
obstructed from reaching the furnace.
Vent opening must not be blocked by snow.
A minimum 12” curb must be used or the
WARNIN
WARNIN
vent outlet shall be greater than 12” off the
ground or roof.
Flue gas is dangerously hot and contains
contaminants. The user is responsible for
determining if vent gases may degrade
building materials.
The National Gas and Propane Installation
Code, B149.1 specifies a 6 ft. horizontal
vent terminal clearance to gas and electric
meters and relief devices.
Local codes may supersede or further place
restrictions on vent termination locations.
Table 3 - Unit Clearances
Location
Front -
(Heat Exchanger)
Back - (Outside Air) 36”
Left Side 24”
Right Side 48”
Top Unobstructed
Front
Figure 2 - RQ Series Orientation
Setting the Curb
Make openings in roof decking large enough
to allow for duct penetration and workspace
Unit Size
2-6 tons
36”
Back
Right Side
25
Page 26
CAUTIO
CAUTIO
only. Do not make openings larger than
necessary. Set the curb to coincide with the
openings. Make sure the curb is level. Unit
must be level in both horizontal axes to
support the unit and reduce noise and
vibration.
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
Where the supply or warm air duct
passes through a combustible roof, a
clearance of 1 inch must be
maintained between the outside
edges of the duct and combustible
material in accordance with National
Fire Protection Association Standard
No. 90A. Provide flashings or
enclosure between structure and roof
and all joints must be sealed with
mastic roofing to ensure a watertight
seal.
Be careful to install the provided gasket
according to Figure 3 prior to setting the unit
on the curb.
N
N
26
Page 27
Figure 3 - RQ Cabinet Standard and Power Exhaust Gasket Locations
27
Page 28
CAUTIO
CAUTIO
Incorrect lifting can cause damage to
the unit.
Forklifting the Unit
Units can be lifted using a forklift. Forks
must be 48” in length. Standard units can be
lifted from all sides except the outside air
side. Units with energy recovery wheels can
only be fork lifted from the left or right side.
Forks must be perpendicular to unit. When
lifting from either side, the forks must
extend through to the opposite side of the
N
unit. When lifting from the end of the unit,
the forks must extend at least 44” under the
unit. When lifting with 48” forks, the back
of the fork must be no more than 4” from the
unit.
Forks or Fork Extensions must be at
least 48” in length and must extend
44” under the unit.
FORKLIFTING
2-6 TON UNITS
N
Forks
Figure 4 - Forklifting an RQ Series Unit from the Side
Figure 5 - Forklifting an RQ Series Unit from the Front
28
Page 29
Lifting the Unit
The RQ Series units must be lifted using the
lifting points in the side base rails. A
spreader bar must be used to prevent the
lifting straps from damaging the unit. The
connection points on the spreader bar must
be 48”-60” apart. The minimum cable
length used to lift a standard length (82”
base length) is 72”. The minimum cable
length to lift energy recovery units (116”
base length) is 96”. The shackles used to
connect the cables to the lifting points in the
base should be ½” nominal size.
The rigging must be adjusted to lift the unit
level. Lifting the unit off-balance may cause
severe damage.
It is recommended to lift the unit with the
outside air hood in the downward shipping
position. However, the unit may be lifted
with the outside air hood in the open
position.
Before lifting unit, be sure that all shipping
material has been removed from unit. Secure
hooks and cables at all lifting points
provided on the unit.
Hoist unit to a point directly above the curb
and duct openings. Be sure that the gasket
material has been applied to curb.
Carefully lower and align the unit with
utility and duct openings. Lower the unit
until the unit skirt fits around the curb. Some
units are designed to overhang the curb.
Take care that any recessed base rails fit
around the curb. Make sure the unit is
properly seated on the curb and is level.
Figure 6 - Lifting Details of a 2-6 ton
Standard or Power Exhaust Unit
Figure 7 - Lifting Details of a 2-6 ton
Energy Recovery Wheel Unit
29
Page 30
CAUTIO
Vertical Duct Connection
Note: If outside air will be in contact with
the air tunnel base the unit should include
the base insulation option or the base must
be field insulated.
N
Do not drill or punch holes in the
base of the unit, from inside the unit
or from below the unit to attach
ductwork. Leaking may occur if unit
base is punctured.
Figure 8 - Vertical Duct Connection
30
Page 31
Seismic Curb Installation
Using a standard curb with a seismic unit
will void the certification of the unit. All
mounting details listed must be followed to
achieve seismic certification. The AAON
unit must be certified to ICC-ES AC156
when using a seismic curb for seismic
certifications to apply. Any deviations or
modifications to the unit or curb will void all
seismic certification.
Structural engineer of record must approve
building anchorage to unit or curb in
compliance with OSP-0180-10. Use
provided self tapping screws to attach base
of unit to seismic curb bracket.
Figure 11 - Seismic Solid Bottom Curb without Filters Detail A
Figure 12 -
Seismic Solid Bottom Curb without Filters Detail B
Page 33
Figure 13 - Seismic Rigid Mount Curb Cross Section
Horizontal Duct Connection
Note: If outside air will be in contact with
the air tunnel base the unit should include
the base insulation option or the base must
be field insulated.
Remove shipping covers and attach duct to
flanges provided on the unit. The installer is
responsible for sealing ducts to the flanges
to prevent water leaks.
Supply
Remove the two screws at the bottom of the
rain hood that secure it in the shipping
position. Remove the screws that attach the
side pieces of the hood to the top of the
hood.
Rotate the side pieces so that the holes along
one edge line up with the holes on the top
piece and the flange is on the inside of the
rain hood.
Attach the side pieces to the top of the hood
using the provided screws and attached the
side pieces to the end of the unit through the
flange.
Apply silicon caulking along the top and
both sides of the rain hood. Take care to seal
the top corners where the rain hood attaches
to the unit.
Return
Figure 14 - Horizontal duct connections
Outside Air Rain Hood
Rain hood must be opened before startup of
the unit. Fresh air intake adjustments should
be made according to building ventilation or
local code requirements.
33
Page 34
Figure 15 - RQ Series unit Closed Rain
Hood
Metal Mesh Filters
Metal mesh outside air filters require
installation of the filter rack on the intake of
the rain hood.
Figure 16 - RQ Series unit Open Rain Hood
Clips which hold the metal mesh filters in
the filter rack should face outward.
34
Figure 17 - Rain Hood with Metal Mesh Filter Rack Installation
Page 35
Electrical
G
CAUTIO
Verify the unit nameplate agrees with power
supply. Connect power and control wiring to
the unit as shown in Figure 12 and in the
unit specific wiring diagram, which shows
factory and field wiring and is attached to
the inside of the door of the control
compartment.
Electric shock hazard. Before
attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death, or property damage.
Route power and control wiring, separately,
through the utility entry in the base of the
unit. Do not run power and control signal
wires in the same conduit. The utility entry
is located in the unit base in the front right
hand corner of the unit (compressor
WARNIN
compartment). See unit drawing for specific
location.
Installing Contractor is responsible
for proper sealing of the electrical
and gas entries into the unit Failure
to seal the entries may result in
damage to the unit and property.
Figure 18 - Unit Base Utility Entry
N
Field
Connection
Location
Utility Entry
Figure 19 - Back View of Power Switch from Control Compartment
35
Page 36
CAUTIO
CAUTIO
Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 75°C.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Note: All units are factory wired for 208V,
230V, 380V, 460V, or 575V. The
transformer configuration must be checked
by a qualified technician prior to service,
especially if unit is to be connected to a
208V or 230V supply. For 208V service
interchange the yellow and red conductor on
the low voltage control transformer.
Red-Black for 208V
Yellow-Black for 230V
Wire power leads to the unit’s terminal
block or main disconnect. All wiring beyond
this point has been completed by the
manufacturer and cannot be modified
without effecting the unit’s agency/safety
certification.
Supply voltage must be within the min/max
range shown on the unit nameplate.
Available short circuit current should not
exceed the short circuit current rating
(SCCR) shown on the unit nameplate.
Three phase voltage imbalance will
cause motor overheating and
premature failure.
Three phase voltage imbalance will cause
motor overheating and premature failure.
The maximum allowable imbalance is 2.0%.
N
Voltage imbalance is defined as 100 times
the maximum deviation from the average
voltage divided by the average voltage.
Example:
(221V+230V+227V)/3 = 226V, then
100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit
disconnect switch and at the compressor
terminal. Contact your local power company
for line voltage corrections.
Installing contractor must check for proper
motor rotation and check blower motor
amperage listed on the motor nameplate is
not exceeded. Motor overload protection
may be a function of the variable frequency
drive and must not be bypassed.
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Supply fan,
exhaust fan, and condenser fan
motors should all be checked by a
qualified service technician at startup
and any wiring alteration should only
be made at the unit power
connection.
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.
N
36
Page 37
CAUTIO
N
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.
Table 4 - Control Wiring
Wire Size (Stranded)
- Copper Conductors
Only
Total Wire Distance
Allowable
20 AWG 200 ft
18 AWG 350 ft
16 AWG 500 ft
14 AWG 750 ft
12 AWG 1250 ft
Take the total wire distance allowable and
divide by the number of wires to be
connected. This indicates the distance
allowable for that size wire. The wiring to
the unit must not exceed the total wire
distance allowable. If the voltage at the
connectors is less than 21 VAC, isolation
relays must be installed. If under external
control 21 VAC must be field verified.
All external devices must be powered via a
separate external power supply.
Example:
A total of 8 wires must be pulled 75ft to
control the unit. What size wire should be
used?
According to the Table 4, 16 AWG allows
for 63ft (500 ft/8 wires) and 14 AWG allows
for 94ft (750 ft/8 wires). Thus, 14 AWG
should be used.
Gas Heating
FOR YOUR SAFETY
Read the entire gas heating
installation section of this manual
before beginning installation of the
gas heating section.
If you do not follow these instructions
exactly, a fire or explosion may result
causing property damage, personal
injury, or loss of life.
Verify the unit nameplate agrees with the
proper gas supply type and amount.
Gas piping must be installed in accordance
with local codes, or in the absence of local
codes, installation must conform to the
current (United States) National Fuel Gas
Code ANSI-Z223.1/NFPA 54 or the current
(Canada) National Fuel & Propane
Installation Code CSA B149.1 or B149.2.
37
Page 38
Table 5 - 2-6 ton Gas Connections
Model
Option
B2
Input
MBH
Connections
Quantity Size
Unit nameplate input rate value has been
calculated at the altitude where the unit was
shipped. Above 2,000 ft the input rate is
adjusted 4% for every 1,000 ft.
1 60.0
3 100.0
5 140.0
1 1/2”
7 160.0
After verifying gas inlet pressure and
manifold pressure the service technician
must time the gas flow rate through the gas
meter with a stopwatch to verify the gas
input rate.
Figure 20 - RQ Series Gas Heat Exchanger
Maximum Piping Capacities
Table 6 - Natural Gas (ft
3
/hr)
- Specific Gravity = 0.6, Supply Pressure ≤ 0.5 psi, Pressure Drop = 0.5” w.c.
Length of Pipe
Pipe Size
20 ft 50 ft. 100 ft. 150 ft. 200 ft.
1/2” 120 73 50 40 35
3/4” 250 151 103 84 72
Do not use gas piping smaller than unit gas
connections. Natural gas pipe runs longer
than 20 feet and propane gas pipe runs
longer than 50 feet may require a larger
supply pipe than the unit connection size.
Some utility companies may also require
pipe sizes larger than the minimum sizes
listed.
Piping Sizing Examples
A 100 ft pipe run is needed for a 1080 MBH
natural gas heater. The natural gas has a
38
Page 39
rating of 1000 Btu/ft3 and a specific gravity
CAUTIO
of 0.6 (Obtain these values from the local
gas supplier.)
3
ft
1080
MBH
1000
Btu
=×
1080 ft3/hr
From the natural gas maximum capacities
table, at 100 ft and 1080 ft3/hr the required
minimum pipe size is 2”.
A 100 ft pipe run is needed for a 270 MBH
propane gas heater.
270 MBH = 270 kBtu/hr
From the propane gas maximum capacities
table, at 100 ft and 270 kBtu/hr the required
minimum pipe size is 1”.
Inlet and Manifold Pressures
For natural gas units, the minimum inlet gas
pressure to the unit is 6” w.c. and maximum
inlet gas pressure to the unit is 10.5” w.c.
For propane units, the minimum inlet gas
pressure to the unit is 11” w.c. and the
maximum inlet gas pressure to the unit is
13” w.c. A field provided 1/8” NPT pressure
tap is required to be installed in the piping
just upstream of the shutoff valve for test
gage connection to allow checking of the
gas supply pressure at the unit.
A factory installed pressure tap on the outlet
end of the gas valve can be used to verify a
manifold pressure of 3.5” w.c. for natural
gas, or 10.5” w.c. for propane.
For two stage gas valves, the low stage
setting should be set at 1.1” w.c. for natural
gas, 5.0” w.c. for propane. For modulating
heaters, the safety shut-off valve would be
set following the instructions above, then
from a provided pressure tap in the gas train
immediately preceding the burner manifold
the modulating valve is set to maintain a
maximum of 3.5” w.c. and a minimum of
0.4” w.c.
N
Heater should be disconnected from
the gas supply piping during pressure
testing of the supply piping system
with pressures in excess of ½ psi. Gas
valves can be damaged if subjected to
more than ½ psi.
Gas Pressure Regulator & Overpressure
Protection Device
A gas pressure regulator must be installed if
natural gas supply pressure to the unit is
greater than 10.5” w.c. and less than 2 psi
(55.4” w.c.) and if propane gas supply
pressure is greater than 13” w.c. and less
than 2 psi (55.4” w.c.). Regulators must
comply with the latest edition of the
Standard for Line Pressure Regulators,
ANSI Z21.80/CSA 6.22.
Both a gas pressure regulator and
overpressure protection device (OPD) must
be installed if gas supply pressure to the unit
is greater than 2 psi (55.4” w.c.) and less
than 5 psi (138.4” w.c.), in compliance with
ANSI Z21.80/CSA 6.22. For proper heater
operation, pressure to the regulator MUST
NOT be greater than 5 psi (138.4” w.c.).
Piping Supports
Gas supply piping must be supported
directly at the connection to the unit and at
intervals listed in the following table with
metal straps, blocks, or hooks. Piping should
not be strained or bent.
Table 8 - Gas Piping Supports
Pipe Size Support Intervals
1/2” to 3/4” Every 6 ft
3/4” to 1” Every 8 ft
1-3/4” or Larger
(Horizontal)
1-1/4” or Larger
(Vertical)
Every 10 ft
Every Floor
39
Page 40
Additional Gas Piping Considerations
Local codes will usually require a field
provided and installed manual main shutoff
valve and union external to the unit. Main
shutoff valve should be labeled. A drip leg
should be installed near the unit connection
to trap sediment and condensate. Pipe joint
compounds used on all gas piping
connections should be resistant to liquid
petroleum gases. If flexible gas piping to the
unit, or in the unit, must be replaced
connectors cannot be reused, only new
connectors may be used.
Heat exchanger comes equipped with a
condensate drain which should be plumbed
to the appropriate drain according to the
(United States) National Fuel Gas Code
ANSI-Z223.1/NFPA 54 or the current
(Canada) National Fuel & Propane
Installation Code CSA B149.1 or B149.2,
the International Building Code, and any
applicable local and regional codes and
regulations.
The condensate drain connection is located
next to the gas entry location. The heat
exchanger condensate drain connection from
the unit is a 5/8” barbed nylon elbow
connection.
Figure 21 - Example 2-6 ton through the Base Gas Piping
40
Page 41
Leak Testing
G
CAUTIO
G
p
CAUTIO
All components of gas supply system,
including manual shut off valves and the
piping in the interior of the unit, should be
leak tested with a soap solution before
operating the appliance and at least on an
annual basis thereafter.
LEAK CHECK GAS PIPE
The gas pipe in the unit should be
checked for leaks before startup.
Leak checking is the responsibility of
the installing contractor. All
connections should be checked for
leaks annually after installation.
Failure to leak check could result in
fire, explosion, or other hazardous
situations.
DAN
ER
Do not use open flame or other
source of ignition for leak testing. Fire
or explosion could result causing
property damage, personal injury, or
death.
N
Some soaps used for leak detection
can be corrosive to certain metals.
Rinse piping thoroughly after leak
test has been completed.
All gas fired heat exchangers are completely
tested at the factory before shipment. This
will remove nearly all of the oils that have
been used in the manufacturing process.
However, trace amounts may remain. When
performing the initial startup at the jobsite, it
is highly recommended that people or any
other living animals, which may be sensitive
to the residual odors or gases, NOT be
present in the conditioned space during the
startup. In all cases, including the initial
factory firing and testing, any of the gases
will be under the acceptable level of
concentration for human occupancy.
WARNIN
Those sensitive to odors or gases
from trace amounts of residual oils
should NOT be present in the
conditioned space during the startup
of a gas fired installation.
Refrigerant-to-Water Heat Exchanger
Condenser water pump, condenser water
piping, cooling tower or geothermal loop,
pressure gauges, strainers, piping insulation
and all components of the waterside piping
must be field installed.
Water-Source Heat Pump Applications
Water-source heat pump units using 100%
outside air must have electric preheat if the
application has a potential for operation with
air entering the indoor coil below 43°F with
a water loop temperature of 70°F.
N
WATER-SOURCE HEAT
PUMP APPLICATIONS
Water-source heat pump units using
100% outside air must have electric
preheat if the application has a
potential for heat pump heating
operation with air entering the indoor
coil below 43°F with an entering
water loo
temperature of 70°F.
41
Page 42
G
G
CAUTIO
Open Loop Applications
This product contains one or more
refrigerant-to-water heat exchangers made
of copper, which is subject to corrosion and
failure when exposed to chlorides.
WARNIN
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
of chemical corrosion is excluded
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer’s warranties.
Do not allow water containing any form of
chlorides to enter this heat exchanger.
Common forms of chlorides include:
1. Sea water mist entering an open cooling
tower system.
2. Contaminated make-up water containing
salt water.
3. Disinfecting the water loop with solutions
containing sodium hypochlorite.
Chlorides will result in a premature failure
of the condenser.
Failure of the condenser as a result of
chemical corrosion is excluded from
coverage under AAON warranties and the
heat exchanger manufacturer warranties.
Failure of the condenser will allow water to
enter the refrigerant circuit and will cause
extensive damage to the refrigerant circuit
components. Any damage to the equipment
as a result of condenser failure from
chemical corrosion due to the fluid in the
condenser is excluded from coverage under
AAON warranties and the heat exchanger
manufacturer warranties.
WARNIN
OPEN LOOP APPLICATIONS
Cupronickel refrigerant-to-water heat
exchangers are recommended with
all open loop applications. Failure to
use a Cupronickel heat exchanger
may result in premature failure of
your system and possible voiding of
the warranty.
N
Cleaning the cooling tower or
condenser water loop with harsh
chemicals such as hydrochloric acid
(muriatic acid), chlorine or other
chlorides, can damage the
refrigerant-to-water heat exchanger.
Care should be taken to avoid
allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion Resistance for more
information.
Freezing Water in the Heat Exchanger
This product contains one or more
refrigerant-to-water heat exchangers. A
refrigerant-to-water heat exchanger contains
refrigerant in one passage and water in
another passage. Water is subject to freezing
at 32°F. When water freezes in a heat
exchanger significant forces are exerted on
the components of the heat exchanger where
the water is confined.
Failure of the condenser due to freezing will
allow water to enter the refrigerant circuit
and will cause extensive damage to the
refrigerant circuit components. Any damage
to the equipment as a result of water
freezing in the condenser is excluded from
42
Page 43
coverage under AAON warranties and the
heat exchanger manufacturer warranties.
Unit is capable of operating with Entering
Water Temperatures (EWT) as low as 57°F,
during the cooling mode, without the need
for head pressure control. If the EWT is
expected to be lower than 57°F or a more
stable operation is desired, a factory
provided head pressure control water valve
option is available.
WATER FREEZING
Failure of the condenser due to
freezing will allow water to enter the
refrigerant circuit and will cause
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
Glycol solution should be used if ambient
temperatures are expected to fall below
freezing or if the loop entering water
temperature to the unit is below 50°F while
operating in the heating mode (heat pump
units only).
causes an increase in pressure drop and also
results in a decrease in unit performance.
Adding glycol to condenser water
A
minimum concentration of 20% glycol
solution is recommended.
Water loop piping that runs through
unheated areas or outside the building
should be insulated.
Water Piping
Installing contractor must ensure a
differential pressure switch or water flow
switch is installed between the condenser
water supply and return connections. This
sensor provides a signal to the unit
controller that water flow is present in the
refrigerant-to-water heat exchanger and the
unit can operate without damaging unit
components.
WATER PRESSURE
Prior to connection of condensing
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
or death due to instantaneous
release of high pressure water, relief
valves should be field supplied on
water piping. Supply water
connection may require a backflow
preventer to prevent supply makeup
water from backing up into the public
water system.
Table 10 - Condenser Water Connections
Model (RQ-)
Supply and Return
Connection Size
002 3/4” Sweat
003, 004, 005, 006 1” Sweat
Only use approved water pipe material.
Avoid using galvanized material for water
lines/fittings as the material is corrosive and
may cause fouling of the water system.
43
Page 44
CAUTIO
CAUTIO
N
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
Condenser water pump must be field sized
and installed between the cooling
tower/geothermal loop and self-contained
unit. System should be sized in accordance
with the ASHRAE Handbook. Use
engineering guidelines to maintain equal
distances for supply and return piping and
limit bend radiuses to maintain balance in
the system. Balancing valves, permanent
thermometers and gauges may be required.
WATER PIPING
Follow national and local codes when
installing water piping. Connections
to the unit should incorporate
vibration eliminators to reduce noise
and vibration and shutoff valves to
facilitate servicing. Supply and return
water piping must be at least as large
as the unit connections and larger
depending on length of runs, rise and
bends.
Before connection to the unit the condenser
water system should be flushed to remove
foreign material that could cause condenser
fouling. Install a screen strainer with a
minimum of 20 Mesh ahead of the
condenser inlet to prevent condenser fouling
and internal tube damage.
Mineral content of the condenser water must
be controlled. All make-up water has
minerals in it and as the water is evaporated
in the cooling tower, these minerals remain.
As the mineral content of the water
increases, the conductivity of the water
increases.
Field provided and installed water treatment
program must be compatible with stainless
steel, copper, aluminum, ABS plastic, and
PVC. Batch feed processes should never be
used as concentrated chemicals can cause
corrosion. Never use hydrochloric acid
(muriatic acid) or chlorine as it will corrode
stainless steel.
N
Each heat exchanger is equipped
with a refrigerant pressure relief
device to relieve pressure should
excessive condensing pressures
(>675 psig) occur. Codes may
require installing contractor to
connect and route relief piping
outdoors. The relief valve has a 5/8”
male flare outlet connection.
NOTE: Ball valves should be installed in
the condenser water supply and return lines
for unit isolation and water flow balancing.
All manual flow valves should be of the ball
valve design. Globe or gate valves should
not be used due to high pressure drops and
poor throttling characteristics.
Pressure and temperature ports are
recommended in condenser water supply
and return lines for system balancing. These
openings should be 5 to 10 pipe diameters
from the unit water connections. To allow
44
Page 45
for mixing and temperature stabilization,
CAUTIO
CAUTIO
wells in the water piping should extend at
least ½ pipe diameter into the pipe.
Installing contractor is responsible for
properly sizing and installing water
system components. Improper fluid
flow due to valves, piping, or
improper pump operation may result
in unacceptable unit operation and
void warranty.
Piping systems should not exceed 10 ft/sec
fluid velocity to ensure tube wall integrity
and reduce noise.
Condensate Drain Piping
2-6 ton units are equipped with one
condensate drain pan connection, on the left
side of the unit, and are furnished with a ptrap for field installation.
All drain connections must be used and
individually trapped to ensure a minimum
amount of condensate accumulation in the
drain pans. ABS type cement should be used
to join the drain pipe connections.
Drainage of condensate directly onto the
roof may be acceptable in certain areas, refer
to local codes. If condensate is to drain
directly onto the roof a small drip pad
should be placed below the drain to protect
the roof from possible damage.
If condensate is piped into the building
drainage system, the drain pipe should
penetrate the roof external to the unit itself.
The drain line should be pitched away from
the unit at least 1/8 inch per foot. On longer
runs an air break should be used to ensure
proper drainage.
N
Unit should not be operated without a
p-trap. Failure to install a p-trap may
result in overflow of condensate
water into the unit.
Draw-through cooling coils will have a
negative static pressure in the drain pan area.
This will cause an un-trapped drain to back
up due to air being pulled up through the
condensate drain piping.
Condensate drain trapping and piping should
conform to all applicable governing codes.
Discharge and Suction Line Piping
There are two different locations to pipe out
of the unit, the post corner hole location and
the post back hole location. The post corner
hole location is to run pipe along the roof
and then down by the disconnect switch
(Figure 22 and Figure 24). The post back
hole location is to run the pipe along the
roof, back across the coil, and come out near
the blower access panel (Figure 23 and
Figure 25).
When drilling the holes, use a 1 ¼ inch hole
for the suction line and a 1 inch hole for the
liquid line (Figure 22 and Figure 23). For
pipe sizing, refer to appropriate guidelines in
the condenser or condensing unit installation
manual. The grommets will help seal in
between the holes in the sheet metal and the
piping. If you are piping through the back
post foam panel, attach grommet to the
inside skin of the foam part. If you are
piping through post corner hole location, use
caution around electrical wires. You will
need to turn off power to the unit.
N
45
Page 46
Figure 22 - Post Corner Hole Location
46
Figure 23 - Post Back Hole Location
Page 47
Figure 24 - Post Corner Hole Piping
Figure 25 - Post Back Hole Piping
47
Page 48
G
CAUTIO
Heating Coils
One or two row hot water and steam heating
and preheating coils can be factory installed.
All valve controls for heating operation are
field supplied and field installed. Hot water
and steam coil connections are spun copper
tube.
Water coils should not be subjected to
entering air temperatures below 38°F to
prevent coil freeze-up. If air temperature
across the coil is going to be below this
value, use a glycol solution to match the
coldest air expected.
Table 11 - Hot Water Coil Connection Sizes
Model (RQ-)
Hot Water Coil
Connection Size
002-006 7/8”
Table 12 - Steam Coil Connection Sizes
Model (RQ-)
002-006
Steam Coil Connection
Size
2 1/8” (standard coil)/
1 1/8” (preheat coil)
Chilled Water Coil
Four or six row chilled water cooling coils
can be factory installed. All valve controls
for cooling operation are field supplied and
field installed. Chilled water coil
connections are spun copper tube.
WARNIN
Piping shall be in accordance with
national and local codes. Pressure
limiting devices, backflow preventers
and all other safety requirements are
the sole responsibility of the installing
contractor.
Table 13 - Chilled Water Coil Connection
Sizes
Model (RQ-)
Chilled Water Coil
Connection Size
002-006 7/8”
N
Installing Contractor is responsible
for proper sealing of the water piping
entries into the unit Failure to seal the
entries may result in damage to the
unit and property.
48
Page 49
Electric Preheat
Figure 26 - Preheat Controller
The electric preheat controller is factory
installed within the preheat cabinet. The
following details are for EHC1 version 1.10
of the preheat controller.
Status Display Screens
These screens are access by pressing either
the left or right controller buttons and
scrolling through the following displays.
1. LAT - Measured leaving air temperature
(LAT), average of LAT A and B probes.
MOD - Modulation rate % currently
being applied to stage one SCR.
2. WKGset - "Working" LAT setpoint (°F)
(LATeet>>RESETset as adjusted by 010V RESET signal).
Flash Code LED
Screen
Controller
Buttons
3. LATset - Leaving air temperature (°F)
control setpoint.
4. RESETset - "Reset" air temperature
(°F) control setpoint.
5. OATset - Outside air temperature (°F)
control setpoint, measured outside
temperature must be less to enable
preheat.
49
Page 50
6. LLTset - “Low Limit Time”
temperature (°F) setpoint. If this
temperature is not reached at full output,
relay will pull in.
7. Stage - Current operating stage 1-6.
8. Stage - Current operating stage 1-6.
MOD - Modulation rate % being applied
to stage one heat strip SCR.
9. OAT - Outside air inlet temperature
(°F).
10. LATA - Leaving air probe "A"
temperature (°F).
11. LATB - Leaving air probe "B"
temperature (°F).
12. ManSTG - Manual override stage for
system testing. Any override
automatically cancels after ten minutes;
0 indicates normal operation, 1-6
corresponds to stages 1-6 being forced
on. Stage 1, the SCR, is forced to 50%.
System Setting Screens
These screens are access by pressing the up
button and then entering the technician
password 2425. The screens are scrolled
through by pressing either right or left
buttons on the controller. Adjustment is
made by pressing the up and down buttons.
After a short time of inactivity, the screen
will go back to the Status Display Screens.
1. StartDly - Seconds of delay after the
'Enable' call before heating starts. This is
to allow the Supply Fan to come up to
speed. Supply Fan VFD’s have a 45
second ramp up time. Range = 1sec60sec, and the default is 15sec.
50
Page 51
2. BelowLLT - "Below Low Limit Time".
Range = 10sec-1800sec, and the default
is 10sec. If ‘LLTset’ temperature is not
reached within ‘BelowLLT’ after
reaching full output, the status relay will
operate.
6. LLTset - “Low Limit Time”
temperature setpoint. Range = 35°F50°F, and the default is 35°F. If
‘LLTSet’ temperature is not reached
within ‘BelowLLT’ time after reaching
full output, the status relay will operate.
3. Stages - Number of stages. Range = 1-6,
and the default is 1. The number of
stages can be determined using Table 14.
Table 14 - Stages of Electric Preheat
Tonnages Feature 14B Stages
G = 10 kW
RQ 2-6 tons
1 H = 15 kW
J = 20 kW
4. LATset - Leaving air temperature
setpoint. Range = 35°F-80°F, and the
default is 50°F.
7. RESETset - “Reset Setpoint”
temperature. Range = 35°F-80°F, and
the default is 50°F.
8. ManSTG - Temporary manual override
a specified stage testing, 0=normal
operation, 1-6 to override corresponding
stages. Range = 0-6, and the default is 0.
The manual override may be used for
unit testing of each stage. Stage 1 will be
at 50% to test SCR and stages 2-6 will
be full capacity. A manual override will
expire in ten minutes if not manually
cancelled by resetting ‘ManSTG’ back
to zero.
5. OATset - Outside air temperature
setpoint. Range = 35°F-60°F, and the
default is 35°F.
51
Page 52
LED Flash Alarm Codes
The flashing red LED will be to the right of
the screen. The number of blinks is
described below. The LCD screen will also
display the screens.
1 = LATA probe open/short
2 = LATB probe open/short
3 = OAT sensor open/short
4 = Leaving air temp over limit
5 = Cooling down after hi limit’ event
6 = LAT below low limit
7 = Stage 1 only recovery after
mechanical limit
8 = Shutdown after too many hi limit
events
9 = Short or overload on the 0-10VDC
analog signal output
Operation
Controller receives 24VAC preheat enable
Controller evaluates if outside air
temperature “OAT” is below setpoint
‘OATset’
If OAT < ‘OATset’, controller will delay
heating startup by time setpoint
‘STARTDLY’, then stage up preheat to
maintain the setpoint ‘LATset’ to a
maximum number of stages set in setpoint
‘Stages’.
If a safety is reached with the controller’s
safety sensors then the electric preheat will
be de-energized for a period of 2 minutes.
Electric preheat will turn on stage one at
100% for 3 minutes to test if fault conditions
still exist after the cool down period. The
controller will repeat this and if 3 trips are
recorded in 60 minutes then the controller
will lockout and require manually cycling
power to reset.
52
Page 53
G
The modulating electric preheat option is
designed to temper the incoming outside air
to the unit based on an enable control signal
and the outside air conditions.
A 24VAC enable signal must be provided to
the [PHE] terminal to enable the operation
of the electric preheat. Once the preheat
controller is enabled it will monitor the
outside air temperature to determine if any
capacity of preheat is needed. If the outside
air temperature falls below the outside air
temperature setpoint the electric preheat will
be started up and maintain the leaving air
temperature setpoint with both SCR
controlled and staged electric preheat. Both
setpoints are set with push button LCD
interface on the preheat controller. Outside
air temperature sensors and preheat
discharge supply air temperature sensors are
factory installed and wired to the preheat
controller. Electric preheat has maximum
operating outside air temperature of 60°F
and a maximum preheat discharge air
temperature of 80°F.
[COM], [PHO] & [PHC] feedback terminals
are provided to communicate if the electric
preheat is in operation. PHO is a normally
open contact, PHC is a normally closed
contact, and COM is the common. These
terminals are not required to be connected.
[PHE] is the electric preheat operation
enable. [PH+] and [PH-] are the preheat set
point reset terminals.
Energy Recovery Units
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
General Information
AAONAIRE® units have been equipped
with an energy recovery wheel. This section
is provided to assure the energy recovery
feature will be properly setup to perform in
accordance with the job specifications for
your particular application.
The Energy Recovery Cassette consists of a
frame wheel, wheel drive system, and
energy transfer segments. Segments are
removable for cleaning or replacement. The
segments rotate through counter flowing
exhaust and outdoor air supply streams
where they transfer heat and/or water vapor
from the warm, moist air stream to the
cooler and/or drier air stream.
The initial setup and servicing of the energy
recovery wheel is very important to maintain
WARNIN
Energy Recovery Wheel
53
Page 54
proper operation efficiency and building
occupant comfort.
Normal maintenance requires periodic
inspection of filters, the cassette wheel,
drive belts, air seals, wheel drive motor, and
its electrical connections.
Wiring diagrams are provided with each
motor. When wired according to wiring
diagram, motor rotates clockwise when
viewed from the shaft/pulley side.
By carefully reviewing the information
within this section and following the
instructions, the risk of improper operation
and/or component damage will be
minimized.
It is important that periodic maintenance be
performed to help assure trouble free
operation.
Initial Mechanical Check and Setup
Outdoor units equipped with outside air
intake will have an outside air hood. The
outside air hood must be opened prior to unit
operation.
Outdoor air intake adjustments should be
made according to building ventilation, or
local code requirements.
After the unit installation is complete, open
the cassette access door and determine that
the energy wheel rotates freely when turned
by hand. Apply power and observe that the
wheel rotates at approximately 30 RPM. If
the wheel does not rotate when power is
applied, it may be necessary to readjust the
“diameter air seals”.
Air Seal Adjustments
Pile type air seals across both sides of the
energy wheel diameter are factory adjusted
to provide close clearance between the air
seal and wheel.
Cross Section of Air Seal Structure
Racking of the unit or cassette during
installation, and/or mounting of the unit on a
non-level support or in other than the factory
orientation can change seal clearances. Tight
seals will prevent rotation.
Wheel to Air Seal Clearance
To check wheel to seal clearance; first
disconnect power to the unit, in some units
the energy recovery wheel assembly can be
pulled out from the cabinet to view the air
seals. On larger units, the energy recovery
wheel may be accessible inside the walk-in
cabinet.
A business card or two pieces of paper can
be used as a feller gauge, (typically each
.004” thick) by placing it between the face
of the wheel and pile seal.
Using the paper, determine if a loose slip fit
exist between the pile seal and wheel when
the wheel is rotated by hand.
To adjust air seal clearance, loosen all seal
plate retaining screws holding the separate
seal retaining plates to the bearing support
channels and slide the seals plates away
from the wheel. Using the paper feeler
gauge, readjust and retighten one seal plate
54
Page 55
at a time to provide slip fit clearance when
p
G
the wheel is rotated by hand.
Confirm that the wheel rotates freely. Apply
power to the unit and confirm rotation.
Airflow Balancing and Checking
High performance systems commonly have
complex air distribution and fan systems.
Unqualified personnel should not attempt to
adjust fan operation, or air circulation, as all
systems have unique operations
characteristics. Professional air balance
specialists should be employed to establish
actual operating conditions, and to configure
the air delivery system for optimal
performance.
Controls
A variety of controls and electrical
accessories may be provided with the
equipment. Identify the controls on each unit
by consulting appropriate submittal, or order
documents, and operate according to the
control manufacturer’s instructions. If you
cannot locate installation, operation, or
maintenance information for the specific
controls, then contact your sales
representative, or the control manufacturer
for assistance.
Do not alter factory wiring. Deviation
from the supplied wiring diagram will
void all warranties, and may result in
equipment damage or personal
injury. Contact the factory with wiring
discre
Routine Maintenance and Handling
Handle cassettes with care. All cassettes
should be lifted by the bearing support
beam. Holes are provided on both sides of
the bearing support beams to facilitate
WARNIN
ancies.
rigging as shown in the following
illustration.
Routine maintenance of the Energy
Recovery Cassettes includes periodic
cleaning of the Energy Recovery Wheel as
well as inspection of the Air Seals and
Wheel Drive Components as follows:
Lifting Hole Locations
Cleaning
The need for periodic cleaning of the energy
recovery wheel will be a function of
operating schedule, climate and
contaminants in the indoor air being
exhausted and the outdoor air being supplied
to the building.
The energy recovery wheel is “selfcleaning” with respect to dry particles due to
its laminar flow characteristics. Smaller
particles pass through; larger particles land
on the surface and are blown clear as the
flow direction is reversed. Any material that
builds up on the face of the wheel can be
removed with a brush or vacuum. The
primary need for cleaning is to remove oil
based aerosols that have condensed on
energy transfer surfaces.
55
Page 56
CAUTIO
A characteristic of all dry desiccants, such
films can close off micron sized pores at the
surface of the desiccant material, reducing
the efficiency by which the desiccant can
adsorb and desorb moisture and also build
up so as to reduce airflow.
In a reasonably clean indoor environment
such as a school or office building,
measurable reductions of airflow or loss of
sensible (temperature) effectiveness may not
occur for several years. Measurable changes
in latent energy (water vapor) transfer can
occur in shorter periods of time in
applications such as moderate occupant
smoking or cooking facilities. In
applications experiencing unusually high
levels of occupant smoking or oil based
aerosols such as industrial applications
involving the ventilation of machine shop
areas for example, annual washing of energy
transfer may be necessary to maintain latent
transfer efficiency. Proper cleaning of the
energy recovery wheel will restore latent
effectiveness to near original performance.
To clean, gain access to the energy recovery
wheel and remove segments. Brush foreign
material from the face of the wheel. Wash
the segments or small wheels in a 5%
solution of non-acid based coil cleaner or
alkaline detergent and warm water.
Do not use acid based cleaners,
aromatic solvents, steam or
temperatures in excess of 170°F;
damage to the wheel may occur!
Soak in the solution until grease and tar
deposits are loosened (Note: some staining
of the desiccant may remain and is not
harmful to performance). Before removing,
rapidly run finger across surface of segment
N
to separate polymer strips for better cleaning
action. Rinse dirty solution from segment
and remove excess water before reinstalling
in wheel.
Air Seals
Four adjustable diameter seals are provided
on each cassette to minimize transfer of air
between the counter flowing airstreams.
To adjust diameter seals, loosen diameter
seal adjusting screws and back seals away
from wheel surface. Rotate wheel clockwise
until two opposing spokes are hidden behind
the bearing support beam. Using a folded
piece of paper as a feeler gauge, position
paper between the wheel surface and
diameter seals.
Adjust seals towards wheel surface until a
slight friction on the feeler gauge (paper) is
detected when gauge is moved along the
length of the spoke. Retighten adjusting
screws and recheck clearance with “feeler”
gauge.
Wheel Drive Components
The wheel drive motor bearings are prelubricated and no further lubrication is
necessary.
The wheel drive pulley is secured to the
drive motor shaft by a combination of either
a key or D slot and set screw.
The set screw is secured with removable
locktite to prevent loosening. Annually
confirm set screw is secure. The wheel drive
belt is a urethane stretch belt designed to
provide constant tension through the life of
the belt. No adjustment is required. Inspect
the drive belt annually for proper tracking
and tension. A properly tensioned belt will
turn the wheel immediately after power is
applied with no visible slippage during startup.
56
Page 57
Installation Considerations
CAUTIO
Energy recovery cassettes are incorporated
within the design of packaged units,
packaged air handlers and energy recovery
ventilators. In each case, it is recommended
that the following considerations be
addressed:
Accessibility
The cassette and all its operative parts; i.e.:
motor, belt, pulley, bearings, seals and
energy transfer segments must be accessible
for service and maintenance. This design
requires that adequate clearance be provided
outside the enclosure. Where cassettes are
permanently installed in a cabinet, access to
both sides of the cassette must be provided.
Orientation & Support
The Energy Recovery Cassette may be
mounted in any orientation. However, Care
must be taken to make certain that the
cassette frame remains flat and the bearing
beams are not racked.
To verify, make certain that the distance
between wheel rim and bearing beam is the
same at each end of the bearing beam, to
within 1/4 of an inch (dimension A & B).
This amount of racking can be compensated
for by adjusting the diameter seals.
If greater than 1/4 inch (dimension C),
racking must be corrected to ensure that
drive belt will not disengage from wheel.
Frame
Bearing beams shown
racked
A
Wheel
Bearing
beams
C
Flat surface
B
Avoid Racking of Cassette Frame
Operation
N
Keep hands away from rotating
wheel! Contact with rotating wheel
can cause physical injury.
Startup Procedure
1. By hand, turn wheel clockwise (as viewed
from the pulley side), to verify wheel turns
freely through 360º rotation.
2. Before applying power to drive motor,
confirm wheel segments are fully engaged in
wheel frame and segment retainers are
completely fastened. (See Segment
Installation Diagram).
3. With hands and objects away from
moving parts, activate unit and confirm
wheel rotation. Wheel rotates clockwise (as
viewed from the pulley side).
4. If wheel has difficulty starting, turn power
off and inspect for excessive interference
between the wheel surface and each of the
four (4) diameter seals. To correct, loosen
diameter seal adjusting screws and back
adjustable diameter seals away from surface
of wheel, apply power to confirm wheel is
free to rotate, then re-adjust and tighten hub
57
Page 58
CAUTIO
and diameter seals, as shown in hub seal
adjustment diagram.
5. Start and stop wheel several times to
confirm seal adjustment and to confirm belt
is tracking properly on wheel rim
(approximately 1/4” from outer edge of
rim).
Diameter Seal Adjustment
Service
Disconnect electrical power before
servicing energy recovery cassette.
Always keep hands away from
bearing support beam when installing
or removing segments. Failure to do
so could result in severe injury to
fingers or hand.
Segment Installation & Replacement
Wheel segments are secured to the wheel
frame by a Segment Retainer which pivots
on the wheel rim and is held in place by a
Segment Retaining Catch.
N
58
Hub Seal Adjustment
Segment Retainer
To install wheel segments follow steps one
through five below. Reverse procedure for
segment removal.
1. Unlock two segment retainers (one on
each side of the selected segment opening.
2. With the embedded stiffener facing the
motor side, insert the nose of the segment
between the hub plates.
Page 59
Segment Installation
3. Holding segment by the two outer
corners, press the segment towards the
center of the wheel and inwards against the
spoke flanges. If hand pressure does not
fully seat the segment, insert the flat tip of a
screw driver between the wheel rim and
outer corners of the segment and apply
downward force while guiding the segment
into place.
4. Close and latch each Segment Retainer
under Segment Retaining Catch.
5. Slowly rotate the wheel 180º. Install the
second segment opposite the first for
counterbalance. Rotate the two installed
segments 90º to balance the wheel while the
third segment is installed. Rotate the wheel
180º again to install the fourth segment
opposite the third. Repeat this sequence with
the remaining four segments.
Wheel Drive Motor and Pulley
Replacement
1. Disconnect power to wheel drive motor.
2. Remove belt from pulley and position
temporarily around wheel rim.
3. Loosen set screw in wheel drive pulley
using a hex head wrench and remove pulley
from motor drive shaft.
4. While supporting weight of drive motor in
one hand, loosen and remove (4) mounting
bolts.
5. Install replacement motor with hardware
kit supplied.
6. Install pulley to dimension as shown and
secure set screw to drive shaft.
7. Stretch belt over pulley and engage in
groove.
8. Follow start-up procedure.
Belt Replacement
1. Obtain access to the pulley side bearing
access plate if bearing access plates are
provided. Remove two bearing access plate
retaining screws and the access plate.
2. Using hexagonal wrench, loosen set screw
in bearing locking collar. Using light
hammer and drift (in drift pin hole) tap
collar in the direction of wheel rotation to
unlock collar. Remove collar.
3. Using socket wrench with extension,
remove two nuts which secure bearing
housing to the bearing support beam. Slide
bearing from shaft. If not removable by
hand, use bearing puller.
4. Form a small loop of belt and pass it
through the hole in the bearing support
beam. Grasp the belt at the wheel hub and
pull the entire belt down.
Note: Slight hand pressure against wheel
rim will lift weight of wheel from inner race
of bearing to assist bearing removal and
installation.
Protect hands and belt from possible
sharp edges of hole in Bearing
Support Beam.
5. Loop the trailing end of the belt over the
shaft (belt is partially through the opening).
59
Page 60
6. Reinstall the bearing onto the wheel shaft,
being careful to engage the two locating pins
into the holes in the bearing support beam.
Secure the bearing with two self-locking
nuts.
7. Install the belts around the wheel and
pulley according to the instructions provided
with the belt.
8. Reinstall diameter seals or hub seal and
tighten retaining screws. Rotate wheel in
clockwise direction to determine that wheel
rotates freely with slight drag on seals.
9. Reinstall bearing locking collar. Rotate
collar by hand in the direction the wheel
rotates (see label provided on each cassette
for wheel rotation).
10. Lock in position by tapping drift pin
hole with hammer and drift. Secure in
position by tightening set screw.
11. Reinstall Bearing Access Cover.
12. Apply power to wheel and ensure that
the wheel rotates freely without interference.
60
Belt Replacement
Page 61
Startup
G
G
CAUTIO
CAUTIO
(See back of the manual for startup form.)
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
During startup, it is necessary to perform
routine checks on the performance of the
unit. This includes checking the air flow, air
filters, condenser water flow, dampers,
heaters, and refrigerant charge.
Filters
Do not operate the unit without filters in
place. Unit should be checked for correct
filter placement during startup. Operation of
the equipment without filters will result in a
clogged evaporator coil.
Before completing startup and
leaving the unit a complete operating
cycle should be observed to verify
that all components are functioning
properly.
WARNIN
WARNIN
N
Adjusting Refrigerant Charge
Adjusting the charge of a system in the field
must be based on determination of liquid
sub-cooling and evaporator superheat. On a
system with a TXV liquid sub-cooling is
more representative of the charge than
evaporator superheat but both measurements
must be taken.
The Clean Air Act of 1990 bans the
intentional venting of refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery,
recycling or reclaiming must be
followed. Fines and/or incarceration
may be levied for non-compliance.
Before Charging
Unit being charged must be at or near full
load conditions before adjusting the charge.
Units equipped with hot gas reheat must be
charged with the hot gas reheat valves
closed while the unit is in cooling mode to
get the proper charge. After charging, unit
should be operated in reheat
(dehumidification) mode to check for
correct operation.
Units equipped with heat pump options
should be charged in heating mode to get the
proper charge. After charging, unit should
be operated in cooling mode to check for
correct charge. Charge may need to be
adjusted for cooling mode. If adjustments
are made in the cooling mode, heating mode
must be rerun to verify proper operation.
After adding or removing charge, the system
must be allowed to stabilize, typically 10-15
minutes, before making any other
adjustments.
N
61
Page 62
CAUTIO
CAUTIO
The type of unit and options determine the
ranges for liquid sub-cooling and evaporator
superheat. Refer to Table 13 below when
determining the proper sub-cooling.
Checking Liquid Sub-Cooling
Measure the temperature of the liquid line as
it leaves the condenser coil.
Read the gauge pressure at the liquid line
close to the point where the temperature was
taken. You must use liquid line pressure as it
will vary from discharge pressure due to
condenser coil pressure drop.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the measured liquid line
temperature from the saturated temperature
to determine the liquid sub-cooling.
Compare calculated sub-cooling to Table 15
for the appropriate unit type and options.
Checking Evaporator Superheat
Measure the temperature of the suction line
close to the compressor.
Read gauge pressure at the suction line close
to the compressor.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the saturated temperature from the
measured suction line temperature to
determine the evaporator superheat.
Compare calculated superheat to the table
below for the appropriate unit type and
options.
Table 15 - Acceptable Refrigeration Circuit
Values
Air-Cooled Cond./Air-Source Heat Pump
Sub-Cooling 12-18°F
Sub-Cooling with
Hot Gas Reheat
Superheat 8-15°F
Water-Cooled Cond./Water-Source Heat
Pump
Sub-Cooling 4-8°F
Superheat 8-15°F
Thermal expansion valve must be
adjusted to approximately 8-15°F of
suction superheat. Failure to have
sufficient superheat will damage the
compressor and void the warranty.
Adjusting Sub-Cooling and Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator superheat is within the
temperature range as shown in the table
above (high superheat results in increased
sub-cooling).
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
DO NOT OVERCHARGE!
15-22°F
N
N
62
Page 63
The system is undercharged if the superheat
is too high and the sub-cooling is too low
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
Freeze Stat is an adjustable temperature
sensor (-10 to 70°F) mounted on the
tubing of the first cooling circuit and wired
to de-energize all cooling circuits if tubing
temperature falls below setpoint. Option is
used to prevent freezing of evaporator coil.
Recommended Setting: 32° F to 35º F
Supply Fan EC Motor Startup
Figure 28 - PIN Connectors on EC Supply Fan Motor Electronics
65
Page 66
Speed adjustment is made by varying the
DC voltage on pin 8 (+) & 16 (-). If
WattMaster, Mini Controller, or JENEsys
control systems are installed on the system
then they will provide the 0-10VDC signal
for speed control. The controller will be
wired directly to pin 8 & 16. If a
potentiometer is installed in the unit, the
10VDC output of the motor electronics will
be wired through the potentiometer and then
back into pin 8 & 16 for speed control. By
adjusting the potentiometer from 0-100%
you can manually adjust the speed of the
motor.
If the rotation direction is wrong, check the
brown wire on the control connector and
ensure that it is connected from pin 13 to pin
11. Making/Breaking this wire changes the
rotation of the motor.
If there is no rotation and/or no speed
change, try the following:
1. Check the line-to-line voltage on the
fuse block connected to the supply fan
motor and ensure it is between 187VAC
to 264VAC
2. Turn the potentiometer to 50%
3. Energize the BC relay by making a
blower call.
4. Check DC voltage on S1 (-) and S2 (+),
0-10VDC signal on S1 & S2 sets the
speed of the motor – thus 0VDC is no
speed and 10VDC is full speed.
5. If DC Voltage is present on S1 & S2
then ensure that BC (blower relay) is
energized and is passing the DC voltage
through to the motor. If BC is not
energized then check wiring for 24VAC
blower call.
6. If no DC voltage is present on S1 & S2
then check S1 (-) & S3 (+), this is the
+10VDC output from the motor that is
supplied to the Potentiometer for speed
control.
If the following troubleshooting suggestions
do not solve the issue, contact AAON for
assistance.
Condenser Fan EC Motor Startup
The fan cycling option uses a fan cycle
switch to switch between one of the discrete
speed inputs (see
66
Page 67
Table 17) on the motor thus cycling between
two preset speeds based upon discharge
pressure of the unit. By connecting 24VAC
to a single or combination of the yellow,
white, or orange wires, the motor will run at
the discrete speeds in Table 12.
WattMaster Condenser Head Pressure
Module is used for variable speed control of
the motor to maintain a head pressure. The
motor should be factory wired to the PWM
outputs of the WattMaster Condenser Head
Pressure Module. See WattMaster literature
for further information
(http://www.orioncontrols.com).
Note
High voltage wires out of the motor:
Black & Brown – 1 Phase Line Voltage
Green - Ground
Low control voltage wires out of the motor:
Blue – Common
Yellow – Variable Speed Control
The switch will come factory set to cut-in at
425psi (+/– 5psi) and a differential of 155psi
(or open at 270psi (+/– 5psi)).
To adjust the fan cycle switch you will need a
flathead screwdriver.
Settings for CUT IN and DIFFERENTIAL
PRESSURE are indicated with two slider
gauges.
Cut InDifferential
Each adjustment screw sits above the setting
that it controls.
69
Page 70
Cut In Gauge
To lower the pressure set point for the CUT IN
gauge, turn the adjustable screw clockwise.
Differential
Gauge
Cut In Gauge
To raise the pressure set point for the CUT IN
gauge, turn the adjustable screw counter
clockwise.
Differential
Gauge
To raise the pressure set point for the
DIFFERENTIAL Gauge, turn the adjustable
screw clockwise.
NOTE: The pressure values on the gauge should be verified with gauges on the refrigerant line.
The gauge scale is for illustration purposes only.
70
To lower the pressure set point for the
DIFFERENTIAL Gauge, turn the adjustable
screw counter clockwise.
Page 71
Operation
G
Unit operations should be controlled with
thermostat, or unit controller, never at the
main power supply, except for servicing,
emergency, or complete shutdown of the
unit.
Thermostat Operation
Heating
Thermostat system switch - "Heat"
Thermostat fan switch - "Auto" or "On"
Thermostat temperature set to desired point.
Cooling
Thermostat system switch - "Cool"
Thermostat fan switch - "Auto" or "On"
Thermostat temperature set to desired point.
Air Circulation
Thermostat system switch - "Off"
Thermostat fan switch - "Auto" or "On"
No change of the thermostat temperature.
With these settings, the supply blower will
run continuously but the supply air will not
be heated, cooled, or dehumidified.
System Off
Thermostat system switch - "Off"
Thermostat fan switch - "Auto"
No change of the thermostat temperature.
With these settings the system is shut down,
with the exception of control system power.
Night and Weekend Unoccupied Operation
To reduce the operating time of the unit
when the space is unoccupied, such as nights
and weekends, it is recommended that the
temperature setting be raised about 5°F
while unoccupied during the cooling season
and lowered about 10°F during the heating
season.
Packaged DX Cooling Operation and
Control
When a call for cooling (G and Y1, Y2, etc.)
is made the supply blower motors and
compressors will energize.
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
Gas Heater Operation
When heat (G and W1, W2, etc.) is called
for the combustion motor starts and the
ignition control is energized. The control
sends 24 VAC to the main gas valve and
high voltage to the igniter. If a burner flame
has been detected within 10 seconds, the
spark is extinguished and the flame
continues. If a flame has not been detected
after 10 seconds, the gas valve closes, the
spark ceases and the induced draft blower
continues to purge the heat exchanger. After
45 seconds of purge, the ignition system will
attempt to light the burners again. Should no
flame be detected after 3 tries, the ignition
control will lock out the system. Power to
the ignition control must be cycled to reset
the heater control.
On a fault the gas train is shut down by a
main limit located in the heat exchanger area
or by an auxiliary limit mounted in the
supply fan compartment.
WARNIN
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
5 MINUTE MINIMUM ON TIME
71
Page 72
Electric Heating Operation
When a call for heating (G and W1, W2,
etc.) is made the supply blower motors and
electric resistance heaters will energize.
Heating is accomplished by passing
electrical current through a specified amount
of resistance heaters which will produce the
required heat.
On a fault condition the main limit located
in the supply air or the auxiliary limit
located downstream the supply blower will
remove power from all contactors.
Steam or Hot Water Preheating and
Heating Operation
Valve control for steam and hot water
heating coils are by others. Heating is
accomplished by passing steam or hot water
through the steam or hot water coil
assembly.
Modulating Electric Preheat
Electric preheat is used to temper the
incoming outside air to the unit based on an
enable control signal and outside air
conditions. Electric preheat has a maximum
operation outside air temperature of 60°F
and a maximum preheat discharge air
temperature of 80°F.
Chilled Water or Non-Compressorized
DX Cooling Operation
Controls for chilled water cooling coils and
non-compressorized DX coil are by others.
72
Page 73
Maintenance
G
G
(See back of the manual for maintenance
log)
At least once each year, a trained, qualified
service technician should check out the unit.
Fans, evaporator coils, and filters should be
inspected at least monthly.
Gas Heating
Once a year, before the unit is in
operation for the heating season, a
qualified service technician should
inspect all flue product carrying areas
of the furnace and main burners for
continued safe operation.
The gas pipe in the unit should be
checked for leaks before startup.
Leak checking is the responsibility of
the installing contractor. All
connections should be checked for
leaks annually after installation.
Failure to leak check could result in
fire, explosion, or other hazardous
situations.
Make sure all gas supply lines have been
purged of air before turning on the electrical
power switch. Turn the gas valve to the on
position (see startup instructions). Turn the
main electrical power on and set the controls
to the heating mode of operation.
The combustion ventilation motor should
operate. The control will automatically
supply energy to the igniter and the gas
valve after the heating call is made.
The flame sensing probe detects the
presence of the flame. Should no flame be
detected in 10 seconds, the ignition system
WARNIN
DAN
LEAK CHECK GAS PIPE
ER
will recycle. If no flame is detected after 3
tries, ignition system will lockout.
Remove the call for heating. The main gas
valves should be extinguished.
The supply fans are controlled by the
ignition system. In the fan “Auto” mode the
fan comes on 45 seconds after the flame is
proved and goes off 120 seconds after the
heating call is removed.
Furnace combustion ventilation air and flue
openings should be checked annually for
debris and obstructions. If vent extensions
are used they must meet category III
requirements.
This appliance contains a wire screen at the
vent outlet. Each heating season, prior to
placing the appliance in heat mode
maintenance check that no debris or foreign
matter has accumulated in the vent outlet. A
good practice is to check for debris each
time the air filters are changed.
In the event the vent outlet becomes blocked
do not attempt to start the appliance in heat
mode until the entire vent opening is
cleared.
In the event the unit shut down because the
vent was blocked a qualified technician or
service agency should monitor the unit prior
to re-starting.
The gas burner and heat exchanger should
never require cleaning. If cleaning is
necessary, this indicates faulty operation of
the unit. Cleaning should only be done by a
qualified service agency and only after
consultation with an AAON service
representative.
If induced draft blower/motor assembly has
to be replaced, care must be taken to provide
an airtight seal between the blower housing
and the burner box.
73
Page 74
G
G
G
Gas Heat Exchanger Removal
WARNIN
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
DAN
ER
LEAK CHECK GAS PIPE
The gas pipe in the unit should be
checked for leaks before startup.
Leak checking is the responsibility of
the installing contractor. All
connections should be checked for
leaks annually after installation.
Failure to leak check could result in
fire, explosion, or other hazardous
situations.
Removal
Disconnect all wiring on the heat exchanger.
Disconnect flex gas lines and pull out of the
way.
Remove screws around the perimeter of the
heat exchanger face plate that connect it to
the unit. Only the outermost screws should
be removed.
Pull the heat exchanger straight back and out
of the unit. It may be necessary to remove
some of the control door jambs.
Reinstallation
Ensure that the neoprene gasket is installed
around the perimeter of the heat exchanger.
Insert heat exchanger into opening so that
the back of the main plate is against the unit
bulkhead.
Figure 29 - Gas Heat Exchanger
Attach the heat exchanger to the bulkhead
using the holes around the perimeter.
Connect flex gas lines to the piping on the
heat exchanger. If flexible gas piping in the
unit must be replaced connectors cannot be
reused, only new connectors must be used.
Connect wiring per the wiring diagram on
the controls compartment door.
Purge gas lines to the gas valves at the unit.
DX Cooling
Set unit controls to cooling mode of
operation with supply fans on. Check the fan
for correct operating direction, amperage
and voltage. Check compressor operation,
rotation, amperage and voltage to the unit
nameplate (check the amperage on the load
side of the compressor contactor).
Condenser Fan
WARNIN
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
74
Page 75
G
G
WARNIN
Improper installation, adjustment,
alteration, service, or maintenance
can cause property damage,
personal injury, or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
Removal
Take off the fan grill by removing the
screws that attach it to the top of the unit.
Disconnect the wiring from the motor and
loosen the bolt that clamps the motor mount
to the motor. Remove the motor and fan
through the top of the orifice.
the drain lines and overflow of the pan itself.
Cleaning of the drain pans and inside of the
unit should be done only by qualified
service technician.
Evaporator Coil
Electric shock hazard. Shut off all
WARNIN
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
Removal
Evacuate refrigerant from the systems.
Remove the TXV bulbs from the suction
lines. Disconnect the suction and liquid line
copper connections to the evaporator coil.
Figure 30 - Removal of a Condenser Fan
Assembly
Reinstallation
Set the motor back into the motor mount and
tighten bolt. Adjust fan until the top of the
blade is even with the top of the orifice.
Reconnect wires, then attach the fan grill at
all the points where screws were removed.
Condensate Drain Pans
Drain pans will have moisture present and
require periodic cleaning to prevent
microbial growth. Cleaning of the drain pans
will also prevent any possible plugging of
Figure 31 - Evaporator Coil Access
Remove screws attaching filter rack to the
evaporation coil at the front and back of the
coil. It may be necessary to remove the
economizer assembly (if equipped) to access
the screws at the back.
Slide the evaporator coil straight out of the
unit.
It may be necessary to make a vertical cut in
the front flange of the drain pan on either
side of the coil and bend the flange down
between the cuts to remove the evaporator
coil.
75
Page 76
p
G
C
AUTIO
Reinstallation
Slide the new coil into the unit through the
notch cut in the front of the drain pan.
Re-bend the cut flange back to the original
position, then seal the cuts with
polyurethane caulking.
Attach the filter at the front and back of the
evaporation coil. Reinstall economizer
assembly if necessary.
Connect the suction and liquid copper
connections to the evaporator coil. Reinstall
the TXV bulb on the suction line.
Evacuate the refrigerant system. Weigh in
the nameplate refrigerant charge.
See Adjusting Refrigerant Charge section to
check for proper sub-cooling and superheat
of the refrigerant systems.
E-Coated Coil Cleaning
Documented routine cleaning of e-coated
coils is required to maintain coating
warranty coverage.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
arts.
Surface loaded fibers or dirt should be
removed prior to water rinse to prevent
restriction of airflow. If unable to back wash
the side of the coil opposite of the coils
entering air side, then surface loaded fibers
or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available,
a soft non-metallic bristle brush may be
used. In either case, the tool should be
applied in the direction of the fins. Coil
surfaces can be easily damaged (fin edges
bent over) if the tool is applied across the
fins.
WARNIN
Use of a water stream, such as a garden
hose, against a surface loaded coil will drive
the fibers and dirt into the coil. This will
make cleaning efforts more difficult. Surface
loaded fibers must be completely removed
prior to using low velocity clean water rinse.
A monthly clean water rinse is
recommended for coils that are applied in
coastal or industrial environments to help to
remove chlorides, dirt, and debris. It is very
important when rinsing, that water
temperature is less than 130°F and pressure
is less than 900 psig to avoid damaging the
fin edges. An elevated water temperature
(not to exceed 130°F) will reduce surface
tension, increasing the ability to remove
chlorides and dirt.
High velocity water from a pressure
washer or compressed air should
only be used at a very low pressure
to prevent fin and/or coil damages.
The force of the water or air jet may
bend the fin edges and increase
airside pressure drop. Reduced unit
performance or nuisance unit
shutdowns may occur.
Quarterly cleaning is essential to extend
the life of an e-coated coil and is required
to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s
regularly scheduled maintenance
procedures. Failure to clean an
will void the warranty and may result in
reduced efficiency and durability.
N
e-coated coil
76
Page 77
CAUTIO
Harsh chemicals, household bleach,
or acid cleaners should not be used
to clean outdoor or indoor e-coated
coils. These cleaners can be very
difficult to rinse out of the coil and
can accelerate corrosion and attack
the e-coating. If there is dirt below the
surface of the coil, use the
recommended coil cleaners.
For routine quarterly cleaning, first clean the
coil with the below approved coil
cleaner. After cleaning the coils with the
approved cleaning agent, use the approved
chloride remover to remove soluble salts and
revitalize the unit.
Recommended Coil Cleaner
The following cleaning agent, assuming it is
used in accordance with the manufacturer’s
directions on the container for proper mixing
and cleaning, has been approved for use on
e-coated coils to remove mold, mildew,
dust, soot, greasy residue, lint, and other
particulate:
Enviro-Coil Concentrate, Part Number HEC01.
Recommended Chloride Remover
CHLOR*RID DTS™ should be used to
remove soluble salts from the e-coated coil,
but the directions must be followed closely.
This product is not intended for use as a
degreaser. Any grease or oil film should first
be removed with the approved cleaning
agent.
Remove Barrier - Soluble salts adhere
themselves to the substrate. For the effective
use of this product, the product must be able
to come in contact with the salts. These salts
may be beneath any soils, grease or dirt;
therefore, these barriers must be removed
prior to application of this product. As in all
surface preparation, the best work yields the
best results.
N
Apply CHLOR*RID DTS - Apply directly
onto the substrate. Sufficient product must
be applied uniformly across the substrate to
thoroughly wet out surface, with no areas
missed. This may be accomplished by use of
a pump-up sprayer or conventional spray
gun. The method does not matter, as long as
the entire area to be cleaned is wetted. After
the substrate has been thoroughly wetted,
the salts will be soluble and is now only
necessary to rinse them off.
Rinse - It is highly recommended that a hose
be used, but a pressure washer will damage
the fins. The water to be used for the rinse is
recommended to be of potable quality,
though a lesser quality of water may be used
if a small amount of CHLOR*RID DTS is
added. Check with CHLOR*RID
International, Inc. for recommendations on
lesser quality rinse water.
Microchannel Coil Cleaning
Air-cooled heat exchangers may include
microchannel coils.
Cleaning microchannel coils is necessary in
all locations. In some locations it may be
necessary to clean the coils more or less
often than recommended. In general, a
condenser coil should be cleaned at a
minimum of once a year. In locations where
there is commonly debris or a condition that
causes dirt/grease build up it may be
necessary to clean the coils more often.
Proper procedure should be followed at
every cleaning interval. Using improper
cleaning technique or incorrect chemicals
will result in coil damage, system
performance fall off, and potentially leaks
requiring coil replacement.
Documented routine cleaning of
microchannel coils with factory provided ecoating is required to maintain coating
warranty coverage. Use the E-Coated Coil
Cleaning section for details on cleaning ecoated coils.
77
Page 78
G
Field applied coil coatings are not
recommended with microchannel coils.
Allowed Chemical Cleaners and
Procedures
AAON recommends certain chemicals that
can be used to remove buildup of grime and
debris on the surface of microchannel coils.
These chemicals have been tested for
performance and safety and are the only
chemicals that AAON will warrant as
correct for cleaning microchannel coils.
There are three procedures that are outlined
below that will clean the coils effectively
without damage to the coils. Use of any
other procedure or chemical may void the
warranty to the unit where the coil is
installed. With all procedures make sure the unit is off before starting.
WARNIN
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
The water pressure used to clean should not
exceed 140 psi, from no closer than 3 inches
from the coils, and with the water aimed
perpendicular to the coils.
#1 Simple Green
Simple Green is available from AAON Parts
and Supply (Part# T10701) and is
biodegradable with a neutral 6.5 pH.
Recommendation is to use it at a 4 to 1 mix.
Use the following procedure.
1. Rinse the coil completely with water.
Use a hard spray but be careful not to
bend or damage the fins. A spray that is
too hard will bend the fins. Spray from
the fan side of the coil.
2. With a pump sprayer filled with a mix of
4 parts water to one part Simple Green
spray the air inlet face of the coil. Be
sure to cover all areas of the face of the
coil.
3. Allow the coil to soak for 10-15 minutes.
4. Rinse the coil with water as in step one.
5. Repeat as necessary.
#2 Vinegar
This is standard white vinegar available in
gallons from most grocery stores. It has a
pH of 2-3, so it is slightly acidic. Use the
following procedure.
1. Rinse the coil completely with water.
Use a hard spray but be careful not to
bend or damage the fins. A spray that is
too hard will bend the fins. Spray from
the fan side of the coil.
2. Use a pump sprayer filled with vinegar
(100%). Spray from the face of the coil
in the same direction as the airflow. Be
sure to cover all areas of the face of the
coil.
3. Allow the coil to soak for 10-15 minutes.
4. Rinse the coil with water as in step one.
5. Repeat as necessary.
#3 Water Flush
This procedure can be used when the only
material to cause the coil to need cleaning is
debris from plant material that has impinged
the coil face.
1. Rinse the coil completely with water.
Use a hard spray but be careful not to
bend or damage the fins. A spray that is
too hard will bend the fins. Spray from
the fan side of the coil.
2. Spray and rinse the coil from the face.
CAUTION
Use pressurized clean water, with
pressure not to exceed 140 psi.
Nozzle should be 6” and 80° to 90°
from coil face. Failure to do so could
result in coil damage.
78
Page 79
Application Examples
G
CAUTIO
The three procedures can be used to clean
microchannel coils. They will fit with the
application depending on the area. In some
areas where the spring/summer has a large
cottonwood bloom #3 might work fine if the
unit is installed on an office building and no
other environmental factors apply.
When a unit is installed where the sprinkler
system has water being sprayed onto the
condenser coil you might have better results
using #2. Vinegar is slightly acidic and may
help with the calcium build up from drying
water. This also works well when grease is
part of the inlet air to a condenser coil.
Generally the best and broadest based
procedure is #1. The grease cutting effect of
the Simple Green is good for restaurant
applications.
Other Coil Cleaners
There are many cleaners on the market for
condenser coils. Before using any cleaner
that is not covered in this section you must
get written approval from the AAON
warranty and service department. Use of
unapproved chemicals will void the
warranty.
AAON testing has determined that unless a
chemical has a neutral pH (6-8) it should not
be used.
Beware of any product that claims to be a
foaming cleaner. The foam that is generated
is caused by a chemical reaction to the
aluminum fin material on tube and fin coils
and with the fin, tube, and coating material
on microchannel coils.
Microchannel coils are robust in many ways,
but like any component they must be treated
correctly. This includes cleaning the coils
correctly to give optimal performance over
many years.
Roofing
The cleaning procedures outlined here use
relatively benign ingredients. When working
with a rooftop unit care should be taken to
make sure the chemicals will not adversely
affect the roof coating. Checking with the
roofing supplier/manufacturer is the best
way to proceed. If the roofing
supplier/manufacturer is not available
testing of the chemicals on the roof coating
is recommended.
Commercial roofing material manufacturers
using PVC and EPDM have been contacted
and indicate that there should be no problem
with any of the procedures outlined above.
Supply Fan
WARNIN
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
N
Blower wheels and bands must be
inspected for excessive dust build up
periodically and cleaned if required.
Excessive dust build up on blower
wheels may cause an unbalanced
state; leading to vibration and/or
component failure. Damages due to
excessive dust build up will not be
covered under factory warranty.
Factory Lubrication
Note: Bearing lubrication only applies to
belt driven fan motors such as the energy
recovery wheel power exhaust fan motor.
All original fan motors and bearings are
furnished with factory lubrication. Some
applications will require that bearings be relubricated periodically. The schedule will
depend on the operating duty, temperature
79
Page 80
variations or other severe atmospheric
conditions.
Bearings should be re-lubricated when at
normal operating temperatures, but not
running. Rotate the fan shaft by hand and
add only enough grease to purge the seals.
DO NOT OVERLUBRICATE.
Recommended greases are:
SHELL OIL - DOLIUM R
CHEVRON OIL - SRI No. 2
TEXACO INC. - PREMIUM RB
Removal
Remove fan access panel on the back side of
the unit. Panel is attached with eight 5/16”
bolts.
Figure 33 - RQ Supply Fan Removal Bolts
Through the coil access door, remove the
two 5/16” bolts that connect the blower
assembly to the inlet wall from air entering
side of the wall (see Figure 33).
Slide blower assembly (wire frame motor
mount, motor, blower wheel, inlet, and
sheet-metal slide) out of unit through blower
access opening (see Figure 34).
Figure 32 - 2-6 ton Supply Fan
Remove wire connections from motor. For
EC motors unplug the wire harness at the
control module that connects to the unit
control panel.
Through the blower access opening, remove
the two 5/16” bolts that connect the blower
assembly to the inlet wall (see Figure 33).
80
Figure 34 - RQ Supply Fan Removal Slide
Page 81
Phase and Brownout Protection Module
The DPM is a Digital Phase Monitor that
monitors line voltages from 200VAC to
240VAC 1ɸ and 200VAC to 600VAC 3ɸ.
The DPM is 50/60 Hz self-sensing. DPM
should be wired according to unit specific
wiring diagram include in the control
compartment
When the DPM is connected to the line
voltage, it will monitor the line and if
everything is within the setup parameters,
the output contacts will be activated. If the
line voltages fall outside the setup
parameters, the output relay will be deenergized after the trip delay.
Once the line voltages recover, the DPM
will re-energize the output relay after the
restart time delay. All settings and the last 4
faults are retained, even if there is a
complete loss of power.
DPM Setup Procedure
With the supply voltage active to the
module, you can setup all of the DPM’s
settings without the line voltage connected.
To change the setpoint parameters use the
right arrow key to advance forward through
the setpoint parameters and the left arrow to
backup if needed. When each parameter is
displayed use the up/down keys to change
and set the parameter.
After adjustments are made or if no
adjustments are made it will take 2 to 4
minutes before the DPM energizes the
output relay unless there is an out of
tolerance issue with the incoming line
voltage.
Recommended Default Set-up
Line Voltage 460VAC, 3Ø
Over & Undervoltage ±10%
Trip Time Delay 5 Seconds
Re-Start Time Delay 2 Minutes
Phase Imbalance 5%
81
Page 82
Screens
Manufacturer’s Screen
R-K Electronics
DPM v0.0.00
Average Voltage Screen
VAvg Imb Hz
460 0 60 off
Default – the default screen shows the real time voltage detected in each of the 3 phases:
“0” most recent faults, “1” previous fault “2” third oldest fault & “3” fourth oldest fault.
Fault Words:
“Phase a Loss” (There is no voltage sensed on 3-L1/S)
“Voltage Low” (Average line voltage is less than selected Undervoltage Percentage)
“Voltage High” (Average line voltage is more than selected Overvoltage Percentage)
“Imbalance” (One phase is lower than the average voltage by more than the Imbalance
“Phase Loss (One phase is more than 30% below the Line Voltage selection)
“Bad Rotation” (The phase rotation sequence is reversed)
“Bad Freq” (Line frequency out of allowable range of 45 to 65 Hz)
percentage)
82
Page 83
G
Variable Capacity Compressor
Controller
Units with variable capacity scroll
compressors may include the following
compressor controller. The following is an
explanation of the terminals and
troubleshooting alert flash codes of the
controller. For more information on the
compressor controller, see Emerson Climate
Bulletin AE8-1328.
Figure 35 - Variable Capacity Compressor
Controller
Low Voltage Terminals
24COM Module Common
24VAC Module Power
C1 & C2 Demand Input
P1 Pressure Common
P2 Pressure Input
P3 Pressure Power 5VDC
P4 Pressure Shield
P5 & P6 Pressure Output
T1 & T2 Discharge Temperature Sensor
Table 18 - Demand Signal vs. Compressor Capacity Modulation
Demand
Signal (VDC)
1.00 Off Off Off Off 0%
1.44 10% 90% 1.5 sec 13.5 sec 10%
3.00 50% 50% 7.5 sec 7.5 sec 50%
4.20 80% 20% 12 sec 3 sec 80%
5.00 100% 0% 15 sec 0 sec 100%
Loaded % Unloaded % Time Loaded
High Voltage Terminals
A1 & A2 Alarm Relay Out
M1 & M2 Contractor
L1 Control Voltage N
L2 Control Voltage L
U1 & U2 Digital Unloader Solenoid
V1 & V2 Vapor Injection Solenoid
To avoid damaging the Compressor
Controller do not connect wires to
terminals C3, C4, T3, T4, T5, or T6.
The compressor controller modulates the
compressor unloader solenoid in an on/off
pattern according to the capacity demand
signal of the system. The following table
shows the linear relationship between the
demand signal and compressor capacity
modulation. The compressor controller
protects the compressor against high
discharge temperature. Refer to Appendix B
for the relationship between thermistor
temperature readings and resistance values.
Monthly air filter inspection is required to
maintain optimum unit efficiency.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNIN
Table 19 - RQ Series 2-6 ton Pre Filters
Feature 6A Quantity / Size Type
0 No Pre Filters
A 2 / 20” x 20” x 2” Pleated, 30% Eff, MERV 8
B 1 / 16”x20”x1” Metal Mesh, Outside Air
It is strongly recommended that filter media
be replaced monthly. Filters are located
upstream of the evaporator coil in the filter
and economizer section. Open access door
and pull filters straight out to inspect all of
the filters. Replace filters with the size
indicated on each filter or as shown in the
tables below. Arrow on the replacement
filters must point towards the blower. (PE =
Power Exhaust)
84
Page 85
Table 20 - RQ Series 2-6 ton Unit Filters
Feature 6B Quantity / Size Type
0 2 / 20” x 20” x 2” Pleated, 30% Eff, MERV 8
B 2 / 20” x 20” x 4” Pleated, 30% Eff, MERV 8
C 2 / 20” x 20” x 2”
F
G Pleated, 85% Eff, MERV 13
2 / 20” x 20” x 4”
Permanent Filter Frame -
Pleated, 65% Eff, MERV 11
H Pleated, 95% Eff, MERV 14
Table 21 - RQ Series 2-6 ton Energy Recovery Wheel Filters
Feature 1A Quantity / Size Type
1 / 16” x 16” x 2”
With Energy Recovery Wheel Exhaust
F, G, H, J, Q, R, S, T
Air Filters, Feature 6A - D, F, G, H
Pleated, 30% Eff, MERV 8
OA - 1 / 16” x 16” x 2”
EA - 1 / 16” x 16” x 2”
20” 20”
Replaceable Media
20”
Figure 37 - RQ Series 2-6 ton Standard Filter Layout
(Viewed from the Upstream Side of the Cooling Coil)
Replacement Parts
Parts for AAON equipment may be obtained
from your local AAON representative.
Reference the unit serial number and part
number when ordering parts.
AAON
Warranty, Service and Parts Department
2424 S. Yukon Ave.
Tulsa, OK 74107
Ph: 918-583-2266
Fax: 918-382-6364
www.aaon.com
Note: Before calling, technician should have
model and serial number of the unit
available for the service department to help
answer questions regarding the unit.
85
Page 86
Appendix A - Heat Exchanger Corrosion Resistance
The resistance guide provides the corrosion resistance of stainless steel type AISI 316 and pure
Copper (99.9%) in water, to a number of important chemical factors. The actual corrosion is a
very complex process influenced by many different factors in combination.
Explanations: + Good resistance under normal conditions
0 Corrosion problems may occur especially when more factors are valued 0
- Use is not recommended
Water
Containing
Alkalinity
-
/ SO
3
-
)
3
2-
)
4
2-
4
(HCO
Sulfate (SO
HCO
Electrical
Conductivity
pH
Ammonium
+
(NH
)
4
Chlorides (Cl-)*
Free Chlorine
(Cl
)
2
Hydrogen
Sulfide (H2S)
Free (aggressive)
Carbon Dioxide
(CO
2)
*See Chloride Content Table
Concentration
(mg/l or ppm)
< 70
70-300 + + + +
Time Limits -
Analyze Before
Within 24 Hours
AISI
316
SMO
254
Copper
Alloy
Nickel
Alloy
+ + 0 +
> 300 + + 0/+ +
< 70
70-300 + + 0/- +
No Limit
+ + + +
> 300 0 0 - +
> 1.0
< 1.0 + + 0/- +
No Limit
< 10µS/cm
10-500 µS/cm + + + +
No Limit
+ + + +
+ + 0 +
> 500 µS/cm + + 0 +
< 6.0
6.0-7.5 0/+ + 0 +
7.5-9.0 + + + +
Within 24 Hours
0 0 0 +
> 9.0 + + 0 +
< 2
2-20 + + 0 +
Within 24 Hours
+ + + +
> 20 + + - +
< 300
> 300 0 + 0/+ +
No Limit
< 1
1-5 + + 0 +
Within 5 Hours
+ + + +
+ + + +
> 5 0/+ + 0/- +
< 0.05
> 0.05 + + 0/- +
No Limit
< 5
5-20 + + 0 +
No Limit
+ + + +
+ + + +
> 20 + + - +
86
Page 87
Water
Containing
Total Hardness
(°dH)
Nitrate (NO3)
Iron (Fe)
Aluminum (Al)
Manganese (Mn)
Chloride Content
= 10 ppm SS 304 SS 304 SS 304 SS 316
= 25 ppm SS 304 SS 304 SS 316 SS 316
= 50 ppm SS 304 SS 316 SS 316 Ti / SMO 254
= 80 ppm SS 316 SS 316 SS 316 Ti / SMO 254
= 150 ppm SS 316 SS 316 Ti / SMO 254 Ti / SMO 254
= 300 ppm SS 316 Ti / SMO 254 Ti / SMO 254 Ti / SMO 254
> 300 ppm Ti / SMO 254 Ti / SMO 254 Ti / SMO 254 Ti / SMO 254
Preheat Leaving Air Temperature Setpoint ________°F
Stage Amps Stage Amps
1 3
2 4
92
Page 93
Maintenance Log
This log must be kept with the unit. It is the responsibility of the owner and/or
maintenance/service contractor to document any service, repair or adjustments. AAON Service
and Warranty Departments are available to advise and provide phone help for proper operation
and replacement parts. The responsibility for proper startup, maintenance and servicing of the
equipment falls to the owner and qualified licensed technician.
Entry Date Action Taken Name/Tel.
93
Page 94
Literature Change History
February 2011
Added information regarding the charging of a heat pump and added additional information
regarding freezing water in the heat exchanger.
June 2011
Updated filter information.
April 2012
Added chilled water, hot water, and steam coil connection sizes.
August 2012
Added seismic curb installation instructions.
November 2012
Update of the IOM adding information about compressor cycling.
May 2013
Added options to the feature string, added curb gasket information, added auxiliary electric
heating capacities table, corrected condenser water connections table, added section for variable
capacity compressor controller, and added Appendix B.
October 2013
Added cautions calling for the need to seal water, electrical, and gas entries into the unit.
January 2014
Added electric preheat options and installation information.
February 2014
Added energy recovery wheel installation, maintenance, and startup information.
July 2014
Added electric preheat controller operation information. Added VCB-X and 380V/50Hz features.
August 2014
Added more detailed microchannel coil cleaning instructions.
January 2015
Table Gas Heat Output Capacities updated.
July 2015
Removed 2” Throwaway Unit Filter-25% Efficient from Filter Replacement information.
September 2015
Updated RQ Metal Mesh Filter sizes.
94
Page 95
January 2016
Updated Phase and Brownout Protection Module section and added Freeze Stat Startup section.
April 2016
Added Adjustable Fan Cycling Switch Procedure section.
95
Page 96
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
RQ Series
Installation, Operation &
Maintenance
R94490 · Rev. E · 160506
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.