Figure 2 - RN Series C Cabinet, ................................................................................................... 29
Figure 3 - Forklifting an RN Series A, B and C Cabinet, 11, 13 and 16-30 ton tons ................... 31
Figure 4 - Lifting Details of a 11, 13 and 16-30 ton tons ton Standard or Power Exhaust Unit .. 32
Figure 5 - Lifting Details of a 11, 13 and 16-30 ton tons Energy Recovery Wheel or Power
Figure 30 - RN Series 11, 13, 16-25 and 30 ton Units ton Standard Filter Layouts ..................... 92
6
AAON® RN Series Horizontal Configuration
Features and Options Introduction
Energy Efficiency
• Direct Drive Backward Curved Plenum
Supply Fans
• Variable Capacity R-410A Scroll
Compressors
• Airside Economizers
• Factory Installed AAONAIRE
®
Energy
Recovery Wheels
• Double Wall Rigid Polyurethane Foam
Panel Construction, R-13 Insulation
• Modulating Natural Gas Heaters
• Modulating/SCR Electric Heaters
• Premium Efficiency Motors
• Variable Speed Supply/Return/Exhaust
Fans
• Water-Cooled Condensers
• Air-Source, Water-Source and
Geothermal Heat Pumps
Indoor Air Quality
• 100% Outside Air
• Constant Volume Outside Air Control
• Economizer CO
• High Efficiency Filtration
• Double Wall Rigid Polyurethane Foam
Override
2
Panel Construction, R-13 Insulation
• Interior Corrosion Protection
Humidity Control
• High Capacity Cooling Coils
• Variable Capacity Compressors
• Factory Installed AAONAIRE Total
Energy Recovery Wheels
• Mixed/Return Air Bypass
• Modulating Hot Gas Reheat
Safety
• Burglar Bars
• Freeze Stats
• Electric Preheat
• Phase and Brown Out Protection
• Supply/Return Smoke Detectors
• Supply/Return Firestats
Installation and Maintenance
• Clogged Filter Switch
• Color Coded Wiring Diagram
• Compressors in Isolated Compartment
• Compressor Isolation Valves
• Convenience Outlet
• Direct Drive Supply Fans
• Hinged Access Doors with Lockable
Handles
• Magnehelic Gauge
• Service Lights
• Sight Glass
System Integration
• Chilled Water Cooling Coils
• Controls by Others
• Electric/Natural Gas/LP Heating
• Hot Water/Steam Heating Coil
• Non-Compressorized DX Coils
• Water-Cooled Condensers
Environmentally Friendly
• Airside Economizers
• Factory Installed AAONAIRE Energy
Recovery Wheels
• Mixed/Return Air Bypass
• R-410A Refrigerant
Extended Life
• 5 Year Compressor Warranty
• 15 Year Aluminized Steel Heat
Exchanger Warranty
• 25 Year Stainless Steel Heat Exchanger
Warranty
• Condenser Coil Guards
• Interior Corrosion Protection
• Polymer E-Coated Coils - 5 Year
Warranty
• Stainless Steel Coil Casing
• Stainless Steel Drain Pans
7
Safety
G
CAUTIO
G
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation, and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
ELECTRIC SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
When servicing controls, label all
Verify proper operation after
WARNIN
electrical power to the furnace.
More than one disconnect may be
provided.
wires prior to disconnecting.
Reconnect wires correctly.
servicing. Secure all doors with
key-lock or nut and bolt.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
Never test for gas leaks with an
Use a gas detection soap solution
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
building.
open flame.
and check all gas connections
and shut off valves.
WARNIN
N
8
G
G
G
G
G
WARNIN
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion, or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
WARNIN
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNIN
ROTATING COMPONENTS
Unit contains fans with moving parts
that can cause serious injury. Do not
open door containing fans until the
power to the unit has been
disconnected and fan wheel has
stopped rotating.
WARNIN
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNIN
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
9
CAUTIO
G
CAUTIO
CAUTIO
G
G
N
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motor’s FLA rating as shown on the
motor nameplate.
WARNIN
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
N
Failure to properly drain and vent
coils when not in use during freezing
temperature may result in coil and
equipment damage.
N
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
WARNIN
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNIN
WATER PRESSURE
Prior to connection of condensing
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
or death due to instantaneous
release of high pressure water, relief
valves should be field supplied on
system water piping.
10
G
CAUTIO
G
CAUTIO
CAUTIO
CAUTIO
G
WARNIN
Always use a pressure regulator,
valves and gauges to control
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
N
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not use alkaline chemical coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
WARNIN
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
N
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
N
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
N
Cleaning the cooling tower or
condenser water loop with harsh
chemicals such as hydrochloric acid
(muriatic acid), chlorine or other
chlorides, can damage the
refrigerant-to-water heat exchanger.
Care should be taken to avoid
allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion Resistance for more
information.
WARNIN
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
of chemical corrosion is excluded
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer’s warranties.
11
G
p
G
Failure of the condenser due to
freezing will allow water to enter the
refrigerant circuit and will cause
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts
1. Startup and service must be performed
2. Use only with type of the gas approved
3. The unit is for outdoor use only. See
WARNIN
WATER FREEZING
WARNIN
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
5 MINUTE MINIMUM ON TIME
er hour.
by a Factory Trained Service
Technician.
for the furnace. Refer to the furnace
rating plate.
General Information section for more
information.
WARNING
4. Provide adequate combustion ventilation
air to the furnace. If a vent duct
extension is used, a class III approved
vent is required. See the Locating Units
and Gas Heating sections of the
Installation section of the manual.
5. Always install and operate furnace
within the intended temperature rise
range and duct system external static
pressure (ESP) as specified on the unit
nameplate.
6. The supply and return air ducts must be
derived from the same space. It is
recommended ducts be provided with
access panels to allow inspection for
duct tightness. When a down flow duct
is used with electric heat, the exhaust
duct should be an L shaped duct.
7. Clean furnace, duct and components
upon completion of the construction
setup. Verify furnace operating
conditions including input rate,
temperature rise and ESP.
8. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
9. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
10. Keep this manual and all literature
safeguarded near or on the unit.
12
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 -
A2
A3
A4
A5 B1
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
RN Series Feature String Nomenclature
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
9D 10A
B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
10B
11A
11B
12
13A
13B
13C
MODEL OPTIONS
SERIES AND GENERATION
RN
MAJOR REVISION
A
UNIT SIZE
011= 11 ton Capacity
013= 13 ton Capacity
016 = 16 ton Capacity
018 = 18 ton Capacity
020 = 20 ton Capacity
025 = 25 ton Capacity
030 = 30 ton Capacity
0 = No Compressor
A = R-410A Scroll Compressor
D = R-410A Variable Capacity Scroll Compressor
A2: CONDENSER STYLE
0 = No Condenser
A = Microchannel Air-Cooled Condenser
F = Water-Cooled Condenser
J = Air-Source Heat Pump
L = Water-Source Heat Pump
N = DX Air Handling Unit
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
A3: INDOOR COIL CONFIGURATION
0 = No Cooling Coil
A = Standard Evaporator
B = 6 Row Evaporator
E = 4 Row Chilled Water Coil
F = 6 Row Chilled Water Coil
A4: COOLING HEAT EXCHANGER
CONSTRUCTION
0 = Standard
A = Polymer E-Coated Cooling Coil
B = Stainless Steel Cooling Coil Casing
E = Polymer E-Coated Cond. Coil
J = Polymer E-Coated Evap. And Cond. Coil
N = SMO 254 Corrosion Resistant Refrigerant-toWater Heat Exchanger
P = Polymer E-Coated Evap. Coil + SMO 254
Corrosion Resistant Refrigerant-to-Water Heat
Exchanger
Q = Stainless Steel Evap. Coil Casing + SMO 254
Corrosion Resistant Refrigerant-to-Water Heat
Exchanger
A5: COOLING STAGING
0 = No Cooling
A = 1 Variable Capacity Comp + 1 On/Off Comp
B = 2 Variable Capacity Comp
F = Single Serpentine 8 FPI
G = Half Serpentine 8 FPI
H = Single Serpentine 10 FPI
J = Half Serpentine 10 FPI
K = Single Serpentine 12 FPI
L = Half Serpentine 12 FPI
N = DX Air Handler with 2 Refrigeration Circuits
2 = 2 Stage
31
32
33
34
35
36
37
13
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2
A2
A3
A4
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
RN Series Feature String Nomenclature
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
- B 0 1 B 0
: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
9D 10A
10B
11A
11B
12
13A
13B
13C
Model Option B: HEATING
B1: HEAT TYPE
0 = No Heat
B = Electric Heat
D = Natural Gas
G = LP Gas
K = Hot Water Coil
B2: HEAT CONSTRUCTION
0 = Standard
A = Aluminized Heat Exchanger
B = Stainless Steel Heat Exchanger
C = High Altitude Aluminized Heat Exchanger
D = High Altitude Stainless Steel Heat Exchanger
G=
0 = No Heat
A = 1 Stage
B = 2 Stage
C = 3 Stage
D = 4 Stage
E = 5 Stage
F = 6 Stage
G = 7 Stage
H = 8 Stage
K = Modulating Gas Heat
M = Modulating SCR Electric with Potentiometer
Control
N = Modulating SCR Electric with External 0-10
VDC
P = Single Serpentine 8 FPI
Q = Half Serpentine 8 FPI
R = Single Serpentine 10 FPI
S = Half Serpentine 10 FPI
T = Single Serpentine 12 FPI
U = Half Serpentine 12 FPI
B5: HEAT PUMP AUX HEATING
0 = No Heat Pump
A = Aux Heat 1 for Heat Pump 1 Stage
B = Aux Heat 2 for Heat Pump 1 Stage
C = Aux Heat 3 for Heat Pump 1 Stage
D = Aux Heat 4 for Heat Pump 1 Stage
E = Aux Heat 5 for Heat Pump 1 Stage
F = Aux Heat 6 for Heat Pump 1 Stage
K = Aux Heat 1 for Heat Pump 2 Stage
L = Aux Heat 2 for Heat Pump 2 Stage
M = Aux Heat 3 for Heat Pump 2 Stage
N = Aux Heat 4 for Heat Pump 2 Stage
P = Aux Heat 5 for Heat Pump 2 Stage
Q = Aux Heat 6 for Heat Pump 2 Stage
U = Aux Heat 1 for Heat Pump 4 Stage
V = Aux Heat 2 for Heat Pump 4 Stage
W = Aux Heat 3 for Heat Pump 4 Stage
Y = Aux Heat 4 for Heat Pump 4 Stage
Z = Aux Heat 5 for Heat Pump 4 Stage
1 = Aux Heat 6 for Heat Pump 4 Stage
31
32
33
34
35
36
37
14
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIE MNRE VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0 :
A2
A3
A4
A5 B1
B2
B3
B4
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
B5 1
2 3A
01-DQ0J
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
9D 10A
10B
-E00- 0000-0 0 0 0 - D A-A0AA-C0
11A
11B
12
13A
13B
1: UNIT ORIENTATION
0 = Standard Access - Hinged Access Doors with
Lockable Handles
2: SUPPLY & RETURN LOCATIONS
V = End Supply--No Return
Z=
End Supply--Right Return
1 = Horizontal Configuration- End Supply--End
Return
13C
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
Feature 3: SUPPLY FAN OPTIONS
3A: SUPPLY FAN CONFIGURATION
0 = 1 Fan
D = 1 Fan + Factory Installed VFD
N = 1 Fan + Field Installed VFD
3B: SUPPLY FAN
L = 22" Direct Drive Backward Curved Plenum 100% Width Aluminum
N = 24" Direct Drive Backward Curved Plenum 100% Width Aluminum
P = 24" Direct Drive Backward Curved Plenum 70% Width Aluminum
Q = 27" Direct Drive Backward Curved Plenum 100% Width Aluminum
R = 27" Direct Drive Backward Curved Plenum 70% Width Aluminum
3C: SUPPLY FAN MOTOR TYPE
0 =High Efficiency Motor (1,200 nominal rpm)
A = High Efficiency Motor (1,800 nominal rpm)
3D: SUPPLY FAN MOTOR SIZE
E = 1 hp
G = 2 hp
H = 3 hp
J = 5 hp
K = 7.5 hp
L = 10 hp
M = 15 hp
N = 20 hp
31
32
33
34
35
36
37
15
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0 : 0 1 - D Q 0 J -
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
3D 4A
4B
4C 5A
E00 - 0000
5B
5C
5D 6A
6B
6C
6D 7
8 9A
- 0 0 0 0 - D A - A 0 A A - C 0
9B
9C
9D 10A
10B
11A
11B
12
13A
13B
Feature 4: RETURN/OUTSIDE AIR
OPTIONS
4A: OUTSIDE AIR SECTION
0 = 100% Outside Air
A = 100% Outside Air with Motorized Dampers
B = Manual Outside Air + Return Air Opening
C = Motorized Outside Air Dampers + Return Air
Opening
D = 100% Return Air
E = Economizer
G = Econ + Power Exhaust
H = Econ + Power Return
K = Econ + Energy Recovery
Q = Econ + Energy Recovery + Bypass Damper
4B: ENERGY RECOVERY TYPE
0 = No Energy Recovery
A = Energy Recovery Wheel
B= Energy Recovery Wheel + 1% Purge
4C: ENERGY RECOVERY SIZE
0 = No Energy Recovery
A = Low CFM Enthalpy
B = High CFM Enthalpy
E = Low CFM Sensible
F = High CFM Sensible
J = Low CFM Enthalpy + Exhaust Filters
K = High CFM Enthalpy + Exhaust Filters
N = Low CFM Sensible + Exhaust Filters
P = High CFM Sensible + Exhaust Filters
13C
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
Feature 5: RETUREN FAN OPTIONS
5A: RETURN FAN CONFIGURATION
0 = Standard
A = 1 Fan
B = 2 Fans
C = 1 Fan + Factory Installed VFD
D = 2 Fans + 1 Factory Installed VFD
E = 2 Fans + 2 Factory Installed VFD's
G = 1 Fan + Field Installed VFD
H = 2 Fans + 1 Field Installed VFD
J = 2 Fans + 2 Field Installed VFD's
5B: RETURN FANS
0 = Standard
B = 22" Direct Drive Axial Flow Fan
5C: RETURN FAN MOTOR TYPE
0 = Standard
A = High Efficiency Motor (1,200 nominal rpm)
B =
High Efficiency Motor (1,800 nominal rpm)
5D: RETURN MOTOR SIZE
0 = Standard
E = 1 hp
G = 2 hp
H = 3 hp
J = 5 hp
K = 7.5 hp
L = 10 hp
M = 15 hp
N = 20 hp
31
32
33
34
35
36
37
16
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000-
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
6B
6C
6D 7
0 0 0 0 - D A
8 9A
9B
9C
9D 10A
-A0AA-C0
10B
11A
11B
12
13A
13B
13C
Feature 6: EXHAUST FAN OPTIONS
6A: EXHAUST FAN CONFIGURATION
0 = Standard
A = 1 Fan
C = 1 Fan + Factory Installed VFD
G = 1 Fan + Field Installed VFD
6B: EXHAUST FAN
0 = Standard
L = 22" Backward Curved Plenum Fan - 100% Width
Aluminum
T= 22" Backward Curved Plenum Fan - 70% Width
Aluminum
6C: EXHAUST FAN MOTOR TYPE
0 = Standard
B = High Efficiency Motor (1,800 nominal rpm)
6D: EXHUAST MOTOR
0 = Standard
E = 1 hp
G = 2 hp
H = 3 hp
J = 5 hp
K = 7.5 hp
L = 10 hp
M = 15 hp
N = 20 hp
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
30
17B
18A
18B
18C
31
7: O/A CONTROL
0 = Standard
A = 3 Position Actuator - Sensible Limit
B = 3 Position Actuator - Enthalpy Limit
C = Fully Modulating Actuator - Sensible Limit
D = Fully Modulating Actuator - Enthalpy Limit
E = DDC Actuator
F = Constant Volume Outside Air
G = Options A + F
H = Options B + F
J = Options C + F
K = Options D + F
L = Options E + F
M = 3 Pos. Act. - Sensible Limit + CO2 Override
N = 3 Pos. Act. - Enthalpy Limit + CO2 Override
P = Fully Mod. Act. - Sensible + CO2 Override
Q = Fully Mod. Act. - Enthalpy + CO2 Override
R = DDC Actuator + CO2 Override
S = Dual Minimum Position Potentiometers + Fully
Mod. Act. - Sensible Limit
T = Dual Minimum Position Potentiometers + Fully
Mod. Act. - Enthalpy Limit
U = 2 Position Actuator
8: EXHAUST DAMPERS & RA BYPASS
0 = No Return Opening
A = Standard Return Opening without EA Dampers
C = Standard Barometric Relief EA Dampers
G= Standard Barometric without EA Dampers + RA
Bypass
J = Standard Barometric Relief EA Dampers + RA
Bypass
32
33
34
35
36
37
17
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D 7
8 9A
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
0 = Standard Filters in Standard Position
B = High Efficiency Filters in Standard Position
9C: FINAL FILTER TYPE
0 = No Final Filters
A = 12" Cartridge MERV 13
D = 12" Cartridge MERV 14
U=
4" Pleated MERV 13
Y= 4" Pleated MERV 14
9D: FILTER OPTIONS
0 = None
A = Clogged Filter Switch - Unit Filters
B = Clogged Filter Switch - Unit + Energy Recovery
Filters
C = Clogged Filter Switch - Unit + Final Filters
D = Clogged Filter Switch - Unit + Energy Recovery
+ Final Filters
E = Magnehelic Gauge - Unit Filters
F = Magnehelic Gauge - Unit + Energy Recovery
Filters
G = Magnehelic Gauge - Unit + Final Filters
H = Magnehelic Gauge - Unit + Energy Recovery +
Final Filters
J = CFS + Magnehelic Gauge - Unit Filters
K = CFS + Magnehelic Gauge - Unit + Energy
Recovery Filters
L = CFS + Magnehelic Gauge - Unit + Final Filters
M = CFS + Magnehelic Gauge - Unit + Energy
Feature 10: REFRIGERATION CONTROL
10A: REFRIGERATION CONTROL
0 = None
A = 5 Minute Compressor Off Timer and 20 Second
Compressor Stage Delay
B = Fan Cycling
C = Adjustable Fan Cycling
D = Adjustable Compressor Lock Outs (each circuit)
E = Freeze Stats (each circuit)
F = Option A + B
G = Option A + C
H = Option A + D
J = Option A + E
K = Option B + D
L = Option B + E
M = Option C + D
N = Option C + E
P = Option D + E
Q = Option A + B + D
R = Option A + B + E
S = Option B + D + E
T = Option C + D + E
U = Option A + B + D + E
V = Option A + C + D + E
10B: BLANK
0 = None
Recovery + Final Filters
9B
9C
9D 10A
A0AA -C0
31
32
33
34
35
36
10B
37
18
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
B 0 - G - 0 0 0 - 4
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
9D 10A
10B
11A
11B
12
13A
13B
13C
Feature 11: REFRIGERATION OPTIONS
11A: REFRIGERATION OPTIONS
0 = None
A = Hot Gas Bypass Lead Stage
B = Hot Gas Bypass Lead and Lag Stages
C = On/Off Hot Gas Reheat
D = Hot Gas Bypass Non-Variable Compressor
Circuits
E = Modulating Hot Gas Reheat
G = Options A + C
H = Options B + C
J = Options A + E
K = Options B + E
L = Options D + C
M = Options D + E
P = Polymer E-Coated On/Off Hot Gas Reheat
Q = Polymer E-Coated Modulating Hot Gas Reheat
R = Options A + P
S = Options B + P
T = Options A + D
U = Options B + Q
V = Options D + P
W = Options D + Q
11B: BLANK
0 = None
12: REFRIGERATION ACCESSORIES
0 = None
A = Sight Glass
B = Compressor Isolation Valves
C = Option A + B
D = One Circuit 0°F Low Ambient
E = Option A + D
F = Option B + D
G = Option A + B + D
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
30
17B
18A
18B
18C
31
Feature 13: POWER OPTIONS
13A: UNIT DISCONNECT TYPE
0 = Single Point Power - Standard Power Block
A = Single Point Power - Non-fused Disconnect
Power Switch
13B: DISCONNECT 1 SIZE
N = 100 amps
R = 150 amps
U = 225 amps
Z = 400 amps
3 = 600 amps
13C: BLANK
0 = None
14: SAFETY OPTIONS
0 = None
A = Return and Supply Air Firestat
B = Return Air Smoke Detector
C = Supply Air Smoke Detector
E = Remote Safety Shutdown Terminals
F = Option A + B
G = Option A + C
J = Option A + E
K = Option B + C
M = Option B + E
P = Option C + E
R = Option A + B + C
T = Option A + B + E
V = Option A + C + E
Z = Option B + C + E
4 = Option A + B + C + E
32
33
34
35
36
37
19
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
A2
A3
A4
A5 B1
B2
B 0 - G - 0 0 0 - 4
B3
B4
B5 1
A - E A 0 0
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
- 0 0 - 5 W 0 - B F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
9D 10A
10B
11A
11B
12
13A
13B
13C
15: ACCESSORIES
0 = None
A = Low Limit Controls
B = Phase & Brown Out Protection
F = Option A + B
Feature 16: UNIT CONTROLS
16A: CONTROL SEQUENCE
0 = Standard Terminal Block for Thermostat
A = Terminal Block for Thermostat + Isolation
Relays
B = Single Zone VAV Unit Controller - VAV Cool +
CAV Heat
C = Single Zone VAV Unit Controller - VAV Cool +
VAV Heat
D = VAV Unit Controller - VAV Cool + CAV Heat
E = Constant Air Volume Unit Controller - CAV
Cool + CAV Heat
F = Makeup Air Unit Controller
G = Single Zone VAV Heat Pump Unit Controller VAV Cool + VAV Heat
H = Constant Air Volume Heat Pump Unit Controller
- CAV Cool + CAV Heat
J = Makeup Air Heat Pump Unit Controller - CAV
Cool + CAV Heat
K = PAC - Precise Air Controller (No VCC)
L = D-PAC - Digital Precise Air Controller
M = Field Installed DDC Controls by Others
N = Field Installed DDC Controls + Installation
Relays
P = Factory Installed DDC Controls by Others +
Installation Relays
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
16B: CONTROL SUPPLIER
0 = None
A = WattMaster VCM-X
C = WattMaster VCB-X
E = JENEsys
16C: CONTROL SUPPLIER OPTIONS
0 = None
B = Web UI
16D: BMS CONNECTION & DIAGNOSTICS
0 = None
A = BACnet IP
B = BACnet MSTP
C = Modbus IP
D = Modbus RTU
E = Lontalk
F = Fox
31
32
33
34
35
36
37
20
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
B 0 - G - 0 0 0 - 4 A - E A 0 0 -
3B
3C
3D 4A
4B
4C 5A
0 0 - 5W0 - B
5B
5C
5D 6A
6B
6C
6D 7
8 9A
9B
9C
9D 10A
F 0 Q A 0 - A 0 0 0 0 0 - 0 0 0 0 0 0 X
10B
11A
11B
12
13A
13B
13C
Feature 17: PREHEAT OPTIONS
17A: PREHEAT CONFIGURATION
0 = Standard
A = Modulating Electric Preheat - Outside Air
D = Hot Water Preheat Coil -Mixed Air
E = Steam Distributing Preheat Coil -Mixed Air
K = Polymer E-Coated Hot Water Preheat Coil Mixed Air
L = Polymer E-Coated Steam Distributing Preheat
Coil - Mixed Air
17B: PREHEAT SIZING
0 = Standard
A = Heat Qty A
B = Heat Qty B
C = Heat Qty C
D = Heat Qty D
E = Heat Qty E
F = Heat Qty F
G = Heat Qty G
H = Heat Qty H
J = Heat Qty J
K = Heat Qty K
L = Heat Qty L
M = Heat Qty M
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
Feature 18: OPTION BOXES
18A: BOX QUANTITY & LOCATION
0 = None
5= Empty Energy Recovery Wheel Option Box
18B: BOX SIZE
0 = None
W= Empty Energy Recovery Wheel Option Box
18C: BOX ACCESSORIES
0 = None
19: OUTSIDE AIR ACCESSORIES
0 = No Outside Air Hood - 100% Return Air
A = Outside Air Hood
B = Outside Air Hood with Metal Mesh Filters
31
32
33
34
35
36
37
21
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B
5B
5C
5D 6A
6B
F 0 Q A 0 - A 0
6C
6D 7
8 9A
9B
9C
9D 10A
0 0 0 0 - 0 0 0 0 0 0 X
10B
11A
11B
12
13A
20: CABINET OPTIONS
0 = None
A = Base Insulation
B = SA & RA Burglar Bars
F = Option A + B
21: BLANK
0 = None
22: MAINTENANCE ACCESSORIES
0 = None
A = Factory Wired 115V Convenience Outlet
B = Field Wired 115V Convenience Outlet
C = Service Lights
D = Remote Start/Stop contacts
E = Supply Fan Auxiliary Contacts
F = Option A + C
G = Option A + D
H = Option A + E
J = Option B + C
K = Option B + D
L = Option B + E
M = Option C + D
N = Option C + E
P = Option D + E
Q = Option A + C + D
R = Option A + C + E
S = Option A + D + E
T = Option B + C + D
U = Option B + C + E
V = Option B + D + E
W = Option C + D + E
Y = Option A + C + D + E
Z = Option B + C + D + E
13B
13C
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
30
17B
18A
18B
18C
31
23: CODE OPTIONS
0 = Standard - ETL U.S.A. Listing
A = Chicago Code
B = ETL U.S.A. + Canada Listing
24: SHIPPING SPLITS
0 = Standard
25: AIR COOLED CONDENSER
ACESSORIES
0 = Standard
A = Cond Coil Guards
C = ECM Condenser Fan Head Pressure Control
E = VFD Condenser Fan Head Pressure Control
G = Cond Coil Guards + ECM Condenser Fan Head
Pressure Control
J = Cond Coil Guards + VFD Cond Fan Head
Pressure Control
26: BLANK
0 = None
32
33
34
35
36
37
22
RN Series Feature String Nomenclature
GEN
MJREV SIZE SERIES MNREV VLT A1
RN A - 11 - C 0 - 3 - A A A 0 2 - B 0 1 B 0: 01-DQ0J -E00-0000- 0 0 0 0 - D A-A0AA-C0
A2
A3
A4
A5 B1
B2
B3
B4
B5 1
2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
B 0 - G - 0 0 0 - 4 A - E A 0 0 - 0 0 - 5 W 0 - B F 0 Q A 0 - A 0
6C
6D 7
8 9A
9B
9C
9D 10A
0 0 0 0 - 0 0 0 0 0 0 X
10B
11A
11B
12
13A
13B
27: WATER - COOLED CONDENSER
ACCESSORIES
0 = None (No Water Condenser)
A = Balancing Valves
B = Water Flow Switch
D = Motorized Shut-off Valve
E = Head Pressure Control
F = Option A + B
H = Option A + D
J = Option A + E
L = Option B + D
M = Option B + E
R = Option A + B + D
S = Option A + B + E
28: ENERGY RECOVERY WHEEL
ACCESSORIES
0 = None
A = Energy Recovery Wheel Defrost - Start/Stop
B = Energy Recovery Wheel Rotation Detection
F = Option A + B
29: BLANK
0 = None
30: BLANK
0 = Standard
31: BLANK
0 = Standard
32: BLANK
0 =Standard
13C
14
15
16A
16B
16C
16D 17A
19
20
21
22
23
24
25
26
27
28
29
17B
18A
18B
18C
30
33: BLANK
0 = Standard
34: BLANK
0 = Standard
35: WARRANTY
0 = Standard Warranty
A = 2 Year Parts Warranty
B = 5 Year Parts Warranty
C = 10 Year Parts Warranty
36: CABINET MATERIAL
0 = Galvanized Cabinet
37: TYPE
B = Premium AAON Gray Paint Exterior Paint
C = Premium AAON Gray Paint Exterior Paint +
Interior Corrosion Protection
X = SPA + Premium AAON Gray Paint Exterior
Paint
Y = SPA + Premium AAON Gray Paint Exterior
Paint + Interior Corrosion Protection
4 = SPA + Special Exterior Paint Color
5 = SPA + Special Exterior Paint Color + Interior
Corrosion Protection
31
32
33
34
35
36
37
23
G
CAUTIO
General Information
RN Series packaged rooftop units, heat
pumps and outdoor air handling units have
been designed for outdoor installation only.
Units are assembled, wired, charged and run
tested at the factory.
Startup and service must be performed by a
Factory Trained Service Technician.
Improper installation, adjustment,
alteration, service, or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.
Certification of Gas Heat Models
a. AAON gas heat exchangers have
b. Certified as a Category III forced air
WARNIN
successfully completed 10,000 burner
operation cycles and corrosion resistance
as specified per test standard ANSI
21.47. All gas heat exchangers used in
AAON appliances are certified for use
downstream of evaporator or cooling
coils.
furnace with or without cooling.
N
c. Certified for outdoor installation only.
d. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air heating system
with or without cooling.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically
operated compressors.
b. Certified for outdoor installation only.
c. Certified for installation on a
combustible roof with a minimum of 12”
high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.
Codes and Ordinances
RN Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236,
ANSI Safety Standard Z21.47b-2008/CSA
2.3b-2008, and ANSI Safety Standard
Z83.8-2006/CSA 2.6-2006.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
24
CAUTIO
G
G
Installation of RN Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. In the absence of local
codes installation must conform to the
current (United States) National Fuel Gas
Code ANSI-Z223.1/NFPA 54 or the current
(Canada) National Fuel & Propane
Installation Code CSA B149.1 or B149.2,
and Mechanical Refrigeration Code CSA
B52. All appliances must be electrically
grounded in accordance with local codes, or
in the absence of local codes, the current
National Electric Code, ANSI/NFPA 70 or
the current Canadian Electrical Code CSA
C22.1.
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with
equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
WARNIN
WARNIN
N
transit. If damage is found it should be noted
on the carrier’s freight bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
If repairs must be made to damaged goods,
then the factory should be notified before
any repair action is taken in order to protect
the warranty. Certain equipment alteration,
repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact the
AAON Warranty Department for assistance
with handling damaged goods, repairs, and
freight claims: (918) 583-2266.
Note: Upon receipt check shipment for
items that ship loose such as filters and
remote sensors. Consult order and shipment
documentation to identify potential looseshipped items. Loose-shipped items may
have been placed inside unit cabinet for
security. Installers and owners should secure
all doors with locks or nuts and bolts to
prevent unauthorized access.
Figure 1 - Lockable Handle
25
p
G
CAUTIO
The warranty card must be completed in full
and returned to AAON not more than 3
months after unit is delivered.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Packaged Direct Expansion (DX) Units
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts
All DX refrigeration systems are factory
assembled, leak tested, charged with
refrigerant, and run tested.
All refrigerant systems include an
evaporator, condenser, liquid line filter
driers, thermal expansion valves (TXV) and
scroll compressors. Compressors are
equipped with a positive pressure forced
lubrication system.
WARNIN
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
5 MINUTE MINIMUM ON TIME
er hour.
Some units are equipped with
compressor crankcase heaters,
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
Never cut off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit crankcase heaters
cannot prevent refrigerant migration into the
compressors. This means the compressor
will cool down and liquid refrigerant may
accumulate in the compressor. The
compressor is designed to pump refrigerant
gas and damage may occur when power is
restored.
If power to the unit must be off for more
than an hour, turn the thermostat system
switch to "OFF", or turn the unit off at the
control panel, and leave the unit off until the
main power switch has been turned on again
for at least 24 hours for units with
compressor crankcase heaters. This will give
the crankcase heater time to clear any liquid
accumulation out of the compressor before it
is started.
Always control the unit from the thermostat,
or control panel, never at the main power
supply, except for servicing, emergency or
complete shutdown of the unit.
During the cooling season, if the air flow is
reduced due to dirty air filters or any other
reason, the cooling coils can get too cold
which will cause excessive liquid to return
to the compressor. As the liquid
CRANKCASE HEATER
OPERATION
N
26
concentration builds up, oil is washed out of
the compressor, leaving it starved for
lubrication.
The compressor life will be seriously
shorted by reduced lubrication and the
pumping of excessive amounts of liquid oil
and refrigerant.
Note: Low Ambient Operation
Air-cooled DX units without a low ambient
option, such as condenser fan cycling or the
0°F low ambient option, will not operate in
the cooling mode of operation properly
when the outdoor temperature is below
55°F. Low ambient and/or economizer
options are recommended if cooling
operation below 55°F is expected.
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
Note: Multiple Units with Multiple
Thermostats
When several heating and cooling units are
used to condition a space all unit thermostat
switches must be set in either heating mode,
cooling mode or off. Do not leave part of the
units switched to the opposite mode.
Cooling only units should be switched off at
the thermostat during the heating season.
Gas or Electric Heating
The unit is designed to heat a given amount
of air while operating. If this amount of air
is greatly reduced, approximately 1/3 during
the heating season, the gas heat exchanger or
electric heating coil may overheat, and may
cut the burner or heater off entirely by action
of the safety high temperature limit devices
which are factory mounted at the heat
exchanger and supply fan areas.
Airflow should be adjusted after installation
to obtain an air temperature rise within the
range specified on the unit rating plate at the
required external static pressure.
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
If unit has not been selected as a 100%
outside air unit (makeup air unit) the return
air duct must be sealed to the unit and the
return air temperature must be maintained
Unit specific wiring diagrams are laminated
and affixed inside the controls compartment
door.
Condensate Drain Pan
Unit requires drain traps to be connected to
the condensate drain pan of the unit. The 11,
13, 16-25 and 30 ton units include one drain
pan connection. Condensate drain pipe or ptrap for each connection is factory supplied
and shipped loose in the controls
compartment for field installation. See
Installation section of this manual for more
information.
If codes require a condensate drain line, the
line should be the same pipe size or larger
than the drain connection, include a p-trap,
and pitch downward toward drain. An air
break should be used with long runs of
condensate lines.
Unit should not be operated without a
p-trap. Failure to install a p-trap may
result in overflow of condensate
water.
N
Installation
AAON equipment has been designed for
quick and easy installation.
Locating Units
The curb should be mounted first and must
be located so that duct connections will be
clear of structural members of the building.
Verify rooftop or foundation can support the
total unit weight, including accessory
weights.
When locating gas fired units, it is
recommended the unit be installed so
that the flue discharge vents are
located at least 120 inches away
from any opening through which
combustion products could enter the
building.
WARNIN
28
G
Distances from adjacent public
walkways, adjacent buildings,
operable windows and building
openings, shall conform to local
codes and/or the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the
National Gas & Propane Code, CSA
B149.1
Do not position flue opening to discharge
into a fresh air intake of any other piece of
equipment. Unit should also be installed so
that the flow of combustion intake air is not
obstructed from reaching the furnace.
Vent opening must not be blocked by snow.
A minimum 12” curb must be used or the
vent outlet shall be greater than 12” off the
ground/roof.
Flue gas is dangerously hot and contains
containments. The user is responsible for
determining if vent gases may degrade
building materials.
The National Gas and Propane Installation
Code, B149.1 specifies a 6 ft. horizontal
vent terminal clearance to gas and electric
meters and relief devices.
Local codes may supersede or further place
restrictions on vent termination locations.
WARNIN
Table 2 - C Cabinet Unit Clearances
Unit Size
Location
Front -
(Supply Air)
Back - (Outside
Air)*
***Left Side 6”
Right Side 60”
Top Unobstructed
*Clearance is measured from the end of the
outside air rain hood.
**Units with an energy recovery wheel
require 48”of clearance.
***Units with a water-cooled condenser or
chilled water coil require 48” of clearance
on the left side for service access.
Figure 2 - RN Series C Cabinet,
11, 13, 16-25 and 30
Setting the Curb
Make openings in roof decking large enough
to allow for duct penetration and workspace
only. Do not make openings larger than
necessary. Set the curb to coincide with the
openings. Make sure the curb is level. Unit
must be level in both horizontal axes to
support the unit and reduce noise and
vibration.
11, 13,16-25 and 30
tons
6”
20”**
29
CAUTIO
CAUTIO
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
Where the supply or warm air duct
passes through a combustible roof, a
clearance of 1 inch must be
maintained between the outside
edges of the duct and combustible
material in accordance with National
Fire Protection Association Standard
No. 90A. Provide flashings or
enclosure between structure and roof
and all joints must be sealed with
mastic roofing to ensure a watertight
seal.
Be careful to install the provided neoprene
gasket according to the following figure
prior to setting the unit on the curb.
N
N
30
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.