Figure 36 - Proper Unit Location ................................................................................................................ 69
Figure 37 - Improper Unit Locations .......................................................................................................... 70
Figure 38 - Water Makeup Valve ............................................................................................................... 72
7
Safety
CAUTIO
G
G
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
Attention should be paid to the following statements:
ELECTRIC SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
When servicing controls, label all
Verify proper operation after
electrical power to the furnace.
More than one disconnect may be
provided.
wires prior to disconnecting.
Reconnect wires correctly.
servicing. Secure all doors with
key-lock or nut and bolt.
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
Never test for gas leaks with an
Use a gas detection soap solution
Electric shock hazard. Before
Electric shock hazard. Shut off all
servicing, shut off all electrical power
electrical power to the unit to avoid
to the unit, including remote
shock hazard or injury from rotating
disconnects, to avoid shock hazard
parts.
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
building.
open flame.
and check all gas connections
and shut off valves.
WARNIN
WARNIN
N
8
G
G
CAUTIO
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
WARNING
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNING
Unit contains fans with moving parts
that can cause serious injury. Do not
open door containing fans until the
power to the unit has been
disconnected and fan wheel has
WARNING
ROTATING COMPONENTS
stopped rotating.
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNIN
GROUNDING REQUIRED
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
WARNIN
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
N
9
CAUTIO
CAUTIO
G
G
CAUTIO
G
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
UNIT HANDLING
Failure to properly drain and vent
coils when not in use during freezing
temperature may result in coil and
equipment damage.
N
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
N
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
Prior to connection of condensing
water supply, verify water pressure is
less than maximum pressure shown
on unit nameplate. To prevent injury
or death due to instantaneous
release of high pressure water, relief
valves should be field supplied on
system water piping.
WARNIN
WATER PRESSURE
Always use a pressure regulator,
valves and gauges to control
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
WARNIN
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not use alkaline chemical coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
N
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
WARNIN
damage, injury or death.
10
CAUTIO
CAUTIO
CAUTIO
G
G
G
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
Cleaning the cooling tower or
condenser water loop with harsh
chemicals such as hydrochloric acid
(muriatic acid), chlorine or other
chlorides, can damage the
refrigerant-to-water heat exchanger.
Care should be taken to avoid
allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion Resistance for more
information.
Failure of the condenser as a result
of chemical corrosion is excluded
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer’s warranties.
OPEN LOOP APPLICATIONS
WARNING
N
N
N
Failure of the condenser due to
freezing will allow water to enter the
refrigerant circuit and will cause
extensive damage to the refrigerant
circuit components. Any damage to
the equipment as a result of water
freezing in the condenser is excluded
from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
startsper hour.
1. Startup and service must be performed
by a Factory Trained Service
Technician.
2. Use only with type of the gas approved
for the furnace. Refer to the furnace
rating plate.
3. The unit is for outdoor use only. See
General Information section for more
information.
WATER FREEZING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
5 MINUTE MINIMUM ON TIME
WARNIN
WARNIN
WARNIN
11
4. Provide adequate combustion ventilation
air to the furnace. If a vent duct
extension is used, a class III approved
vent is required. See the Locating Units
and Gas Heating sections of the
Installation section of the manual.
5. Always install and operate furnace
within the intended temperature rise
range and duct system external static
pressure (ESP) as specified on the unit
nameplate.
6. The supply and return air ducts shall be
derived from the same space. It is
recommended ducts be provided with
access panels to allow inspection for
duct tightness. When a down flow duct
is used with electric heat, the exhaust
duct should be an L shaped duct.
7. Clean furnace, duct, and components
upon completion of the construction
setup. Verify furnace operating
conditions including input rate,
temperature rise, and ESP.
8. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
9. READ THE ENTIRE INSTALLATION,
OPERATION, AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
B = Blow-Through, R-410A, Dual Circuited
C = Draw-Through, R-410A, Dual Circuited
D = Blow Through - R-134a Variable Capacity OilFree Magnetic Bearing Centrifugal Compressors
E = Draw Through - R-134a Variable Capacity OilFree Magnetic Bearing Centrifugal Compressors
F = Blow-Through AHU w/ Vestibule
G = Draw-Through AHU w/ Vestibule
H = Blow-Through AHU w/ Front Control Panel
J = Draw-Through AHU w/ Front Control Panel
M = Blow-Through AHU w/ End Control Panel
N = Draw-Through AHU w/ End Control Panel
R = Blow-Through, R-410A, Independ Circuited
S = Draw-Through, R-410A, Independ Circuited
7 = Blow-Through, R410A VFD Compatible
Compressors
8 = Draw-Through, R410A VFD Compatible
Compressors
A2: COOLING CONFIGURATION
0 = No Cooling
A = Air-Cooled Cond, 4 Row High CFM Evap
B = Air-Cooled Cond, 6 Row High CFM Evap
C = Air-Cooled Cond, 4 Row Low CFM Evap
D = Air-Cooled Cond, 6 Row Low CFM Evap
E = Evap-Cooled Cond, 4 Row High CFM Evap
F = Evap-Cooled Cond, 6 Row High CFM Evap
G = Evap-Cooled Cond, 4 Row Low CFM Evap
H = Evap-Cooled Cond, 6 Row Low CFM Evap
J = Water-Cooled Cond, 4 Row High CFM Evap
K = Water-Cooled Cond, 6 Row High CFM Evap
L = Water-Cooled Cond, 4 Row Low CFM Evap
M = Water-Cooled Cond, 6 Row Low CFM Evap
U = Chilled Water, 4 Row High CFM
V = Chilled Water, 4 Row Low CFM
W = Chilled Water, 6 Row High CFM
Y = Chilled Water, 6 Row Low CFM
Z = Chilled Water, 8 Row High CFM
1 = Chilled Water, 8 Row Low CFM
2 = Non-Compressorized, 4 Row High CFM Evap
3 = Non-Compressorized, 4 Row Low CFM Evap
4 = Non-Compressorized, 6 Row High CFM Evap
5 = Non-Compressorized, 6 Row Low CFM Evap
23
13
R
A
RL Series Feature String Nomenclature
352
:
:BEBE
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE
06
–
Model Option A: COOLING
A3: COOLING COATING
0 = Standard
1 = Polymer E-Coated, Cooling Coil Only
2 = SS Coil Casing, Cooling Coil Only
6 = Polymer E-Coated, Evap and Cond
B = Polymer E-Coated, Cond Only
A4: COOLING STAGING
0 = No Cooling
2 = 2 Stage
3 = 3 Stage
4 = 4 Stage
6 = 6 Stage
8 = 8 Stage
A = Single Serp, 8 FPI
B = Half Serp, 8 FPI
H = 2 Stage, Shell & Tube
J = 3 Stage, Shell & Tube
K = 4 Stage, Shell & Tube
L = 6 Stage, Shell & Tube
M = 8 Stage, Shell & Tube
N = Single Serp, 10 FPI
P = Half Serp, 10 FPI
Q = Single Serp, 12 FPI
R = Half Serp, 12 FPI
Z = All Compressors Variable Speed
Model Option B: HEATING
B1: HEATING STYLE
0 = No Heat
1 = Electric Heat
2 = Natural Gas Single Rack
3 = Natural Gas Double Rack
4 = High Altitude Natural Gas Single Rack
5 = High Altitude Natural Gas Double Rack
A = Steam, Standard
B = Steam, Polymer E-coated
C = Steam Distributing, Standard
D = Steam Distributing, Polymer E-Coated
E = Hot Water, Standard
F = Hot Water, Polymer E-Coated
5A5B5C6A6B6C78910111213
D0 0–QFY–P0
–
B2: HEATING DESIGNATION
0 = No Heat
1 = Heat 1
2 = Heat 2
3 = Heat 3
4 = Heat 4
5 = Heat 5
6 = Heat 6
7 = Heat 7
8 = Heat 8
A = 1 Row Coil A
B = 1 Row Coil B
C = 1 Row Coil C
D = 1 Row Coil D
E = 2 Row Coil A
F = 2 Row Coil B
G = 2 Row Coil C
H = 2 Row Coil D
B3: HEATING STAGING
0 = No Heat
1 = 2 Stage
2 = 4 Stage
3 = 8 Stage
4 = 12 Stage
H = Single Serpentine
J = Half Serpentine
14A14B1516171819202122
0DBB000–00–0BB00AB0B
–
23
14
RL Series Feature String Nomenclature
R
EBE
A
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–352 :
Feature 1: RETURN/OUTSIDE AIR
1A: RETURN/OUTSIDE AIR SECTION
0 = Standard, Manual Outside Air
A = Economizer
B = Econ with Power Exhaust
C = Econ with Power Return
D = Energy Recovery Wheel (Total), Small
E = ERW (Total), Medium
F = ERW (Total), Large
G = ERW (Total), Extra Large
H = ERW (Sens), Small
J = ERW (Sens), Medium
K = ERW (Sens), Large
L = ERW (Sens), Extra Large
M = 100% Outside Air (No Return Air)
N = Motorized Outside Air (w/ Return Air)
P = Motorized Outside Air (No Return Air)
Q = Power Return + ERW (Total) Small
R = Power Return + ERW (Total), Medium
S = Power Return + ERW (Total), Large
T = Power Return + ERW (Total), Extra Large
U = Power Return + ERW (Sens), Small
V = Power Return + ERW (Sens), Medium
W = Power Return + ERW (Sens), Large
Y = Power Return + ERW (Sens), Extra Large
Z = Power Return, Plenum
1B: RETURN AIR BLOWER
CONFIGURATION
0 = None
A = 1 Blower, Standard Eff
B = 2 Blowers, Standard Eff
C = 1 Blower, Premium Eff
D = 2 Blowers, Premium Eff
E = 1 Blower, Premium Eff, 1 VFD
F = 2 Blowers, Premium Eff, 1 VFD
G = 2 Blowers, Premium Eff, 2 VFDs
H = 1 Blower, Premium Eff, 1 Field Installed VFD
J = 2 Blowers, Premium Eff, 1 Field Installed VFD
K = 2 Blowers, Premium Eff, 2 Field Installed VFDs
L = 1 Blower, Premium Eff, 1 VFD w/ Bypass
M = 2 Blowers, Premium Eff, 1 VFD w/ Bypass
N = 2 Blowers, Premium Eff, 2 VFDs w/ Bypass
:
D0 0–QFY–P0
B
–
5A5B5C6A6B6C78910111213
0DBB000–00–0BB00AB0B
–
1C: RETURN AIR BLOWER
0 = None
A = 36” Axial Flow, 6 Blades
B = 42” Axial Flow, 9 Blades
C = 42” Axial Flow, 12 Blades
D = 48” Axial Flow, 16 Blades
E = 27” Backward Curved
F = 30” Backward Curved
G = 33” Backward Curved
H = 36.5” Backward Curved
J = 42.5” Backward Curved
1D: RETURN AIR MOTOR
0 = None
D = 3 hp, 1170 rpm
E = 5 hp, 1170 rpm
F = 7.5 hp, 1170 rpm
G = 10 hp, 1170 rpm
H = 15 hp, 1170 rpm
J = 20 hp, 1170 rpm
K = 25 hp, 1170 rpm
L = 30 hp, 1170 rpm
M = 40 hp, 1170 rpm
N = 50 hp, 1170 rpm
T = 3 hp, 1760 rpm
U = 5 hp, 1760 rpm
V = 7.5 hp, 1760 rpm
W = 10 hp, 1760 rpm
Y = 15 hp, 1760 rpm
Z = 20 hp, 1760 rpm
1 = 25 hp, 1760 rpm
2 = 30 hp, 1760 rpm
3 = 40 hp, 1760 rpm
4= 50 hp, 1760 rpm
14A14B1516171819202122
23
15
R
Q
A
RL Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–3 5 2 : BEBE
Feature 2: OUTSIDE AIR CONTROL
0 = None
A = 3 Position Actuator, Sensible
B = 3 Position Actuator, Enthalpy
C = Full Mod Actuator, Sensible
D = Full Mod Actuator, Enthalpy
E = DDC Actuator
F = Constant Volume OA
G = Constant Volume OA, 3 Pos Act, Sensible
H = Constant Volume OA, 3 Pos Act, Enthalpy
J = Constant Volume OA, Full Mod Act, Sensible
K = Constant Volume OA, Full Mod Act, Enthalpy
L = Constant Volume OA, DDC Act
M = CO
N = CO
P = CO
Q = CO
R = CO
Override, 3 Pos Actuator, Sensible
2
Override, 3 Pos Actuator, Enthalpy
2
Override, Full Mod Actuator, Sensible
2
Override, Full Mod Actuator, Enthalpy
2
Override, DDC Actuator
2
S = Dual Min Pos, Full Mod Act, Sensible
T = Dual Min Pos, Full Mod Act, Enthalpy
U = 2 Position Actuator
Feature 3: DISCHARGE LOCATIONS
0 = Bottom Discharge
A = Front Discharge
B = Back Discharge
C = Top Discharge
D = End Discharge
Feature 4: RETURN LOCATIONS
0 = Bottom Return
A = End Return
B = Front Return High CFM w/o ERW or PE
C = Front Return Low CFM w/o ERW or PE
D = Back Return High CFM w/o ERW or PE
E = Back Return Low CFM w/o ERW or PE
F = Front Return High CFM w/ ERW or PE
G = Front Return Low CFM w/ ERW or PE
H = Back Return High CFM w/ ERW or PE
J = Back Return Low CFM w/ ERW or PE
K = Bottom Return w/ RA Bypass, 2’ Box
L = Bottom Return w/ RA Bypass, 4’ Box
M=Bottom Return High CFM Or w/o RA on 100%
OA
N=End Return High CFM w/o ERW or PE
:
–
D0 0
5A5B5C6A6B6C78910111213
–
FY–P0
0DBB000–00–0BB00AB0B
–
14A14B1516171819202122
Feature 5: SUPPLY AIR BLOWER
5A: SUPPLY AIR BLOWER CONFIGURATION
0 = 1 Blower, Standard Eff
A = 2 Blowers, Standard Eff
B = 3 Blowers, Standard Eff
C = 4 Blowers, Standard Eff
D = 1 Blower, Prem Eff
E = 2 Blowers, Prem Eff
F = 3 Blowers, Prem Eff
G = 4 Blowers, Prem Eff
H = 1 Blower, Prem Eff, w/ 1 VFD
J = 2 Blowers, Prem Eff, w/ 1 VFD
K = 2 Blowers, Prem Eff, w 2 VFDs
L = 3 Blowers, Prem Eff, w/ 1 VFD
M = 3 Blowers, Prem Eff, w/ 3 VFDs
N = 4 Blowers, Prem Eff, w/ 1 VFD
Q = 4 Blowers, Prem Eff, w/ 4 VFDs
R = 4 Blowers, Prem Eff, w/ 2 VFDs
S = 1 Blower, Prem Eff, w/ 1 Field Installed VFD
T = 2 Blowers, Prem Eff, w/ 1 Field Installed VFD
U = 2 Blowers, Prem Eff, w/ 2 Field Installed VFDs
V = 3 Blowers, Prem Eff, w/ 1 Field Installed VFD
W = 3 Blowers, Prem Eff, w/ 3 Field Installed VFDs
Y = 4 Blowers, Prem Eff, w/ 1 Field Installed VFD
Z = 4 Blowers, Prem Eff, w/ 4 Field Installed VFDs
1 = 4 Blowers, Prem Eff, w/ 2 Field Installed VFDs
2 = 1 Blower, Prem Eff, w/ 1 VFD w/ Bypass
3 = 2 Blowers, Prem Eff, w/ 1 VFD w/ Bypass
4 = 2 Blowers, Prem Eff, w 2 VFDs w/ Bypass
5 = 3 Blowers, Prem Eff, w/ 1 VFD w/ Bypass
6 = 3 Blowers, Prem Eff, w/ 3 VFDs w/ Bypass
7 = 4 Blowers, Prem Eff, w/ 1 VFD w/ Bypass
8 = 4 Blowers, Prem Eff, w/ 4 VFDs w/ Bypass
9 = 4 Blowers, Prem Eff, w/ 2 VFDs w/ Bypass
23
16
RL Series Feature String Nomenclature
R
Y
A
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–352 :BEBE–D00–Q
Feature 5: SUPPLY AIR BLOWER
5B: SUPPLY AIR BLOWER
A = 27” Backward Curved
B = 30” Backward Curved
C = 33” Backward Curved
D = 36.5” Backward Curved
E = 42.5” Backward Curved
F = 27” Backward Curved w/ Damper
G = 30” Backward Curved w/ Damper
H = 33” Backward Curved w/ Damper
J = 36.5” Backward Curved w/ Damper
K = 42.5” Backward Curved w/ Damper
5C: SUPPLY AIR MOTOR
D = 3 hp, 1170 rpm
E = 5 hp, 1170 rpm
F = 7.5 hp, 1170 rpm
G = 10 hp, 1170 rpm
H = 15 hp, 1170 rpm
J = 20 hp, 1170 rpm
K = 25 hp, 1170 rpm
L = 30 hp, 1170 rpm
M = 40 hp, 1170 rpm
N = 50 hp, 1170 rpm
T = 3 hp, 1760 rpm
U = 5 hp, 1760 rpm
V = 7.5 hp, 1760 rpm
W = 10 hp, 1760 rpm
Y = 15 hp, 1760 rpm
Z = 20 hp, 1760 rpm
1 = 25 hp, 1760 rpm
2 = 30 hp, 1760 rpm
3 = 40 hp, 1760 rpm
4 = 50 hp, 1760 rpm
:
5A5B5C6A6B6C78910111213
–
P0
F
0DBB000–00–0BB00AB0B
–
14A
14B1516171819202122
Feature 6: FILTERS
6A: PRE FILTER TYPE
0 = 2” Pleated, 30% Eff, Std Pos
A = 4” Pleated, 30% Eff, Std Pos
B = 2” Perm Filter with Replaceable Media, Std Pos
C = 2” Ple Pre, 30% Eff/12” Cart, 65% Eff, Std Pos
D = 2” Ple Pre, 30% Eff/12” Cart, 85% Eff, Std Pos
E = 2” Ple Pre, 30% Eff/12” Cart, 95% Eff, Std Pos
F = 4” Ple Pre, 30% Eff/12” Cart, 65% Eff, Std Pos
G = 4” Ple Pre, 30% Eff/12” Cart, 85% Eff, Std Pos
H = 4” Ple Pre, 30% Eff/12” Cart, 95% Eff, Std Pos
J = 2” Ple Pre, 30% Eff/30” Bag, 85% Eff, Std Pos
K = 2” Ple Pre, 30% Eff/30” Bag, 95% Eff, Std Pos
L = 4” Ple Pre, 30% Eff/30” Bag, 85% Eff, Std Pos
M = 4” Ple Pre, 30% Eff/30” Bag, 95% Eff, Std Pos
N = 2” Pleated, 30% Eff, Pre Pos
P = 4” Pleated, 30% Eff, Pre Pos
Q = 2” Perm Filter with Replaceable Media, Pre Pos
R = 2” Ple Pre, 30% Eff/12” Cart, 65% Eff, Pre Pos
S = 2” Ple Pre, 30% Eff/12” Cart, 85% Eff, Pre Pos
T = 2” Ple Pre, 30% Eff/12” Cart, 95% Eff, Pre Pos
U = 4” Ple Pre, 30% Eff/12” Cart, 65% Eff, Pre Pos
V = 4” Ple Pre, 30% Eff/12” Cart, 85% Eff, Pre Pos
W = 4” Ple Pre, 30% Eff/12” Cart, 95% Eff, Pre Pos
Y = 2” Ple Pre, 30% Eff/30” Bag, 85% Eff, Pre Pos
Z = 2” Ple Pre, 30% Eff/30” Bag, 95% Eff, Pre Pos
1 = 4” Ple Pre, 30% Eff/30” Bag, 85% Eff, Pre Pos
2 = 4” Ple Pre, 30% Eff/30” Bag, 95% Eff, Pre Pos
6B: FINAL FILTER TYPE
0 = None
A = 12” Cart, 85% Eff, Filter Box A
B = 12” Cart, 85% Eff, Filter Box B
C = 12” Cart, 85% Eff, Filter Box C
D = 12” Cart, 95% Eff, Filter Box A
E = 12” Cart, 95% Eff, Filter Box B
F = 12” Cart, 95% Eff, Filter Box C
G = 30” Bag, 85% Eff, Filter Box A
H = 30” Bag, 85% Eff, Filter Box B
J = 30” Bag, 85% Eff, Filter Box C
K = 30” Bag, 95% Eff, Filter Box A
L = 30” Bag, 95% Eff, Filter Box B
M = 30” Bag, 95% Eff, Filter Box C
N = Pre Filter Box A - No Final Filter
P = Pre Filter Box B - No Final Filter
Q = Pre Filter Box C - No Final Filter
23
17
R
RL Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–352 :BEBE–D00–QFY–P0
Feature 6: FILTERS
6C: FILTER OPTIONS
0 = Standard - None
A = Clogged Filter Switch, Pre Filters
B = Clogged Filter Switch, Final Filters
C = Magnehelic Gauge, Pre Filters
D = Magnehelic Gauge, Final Filters
E = Option A + B
F = Option A + C
G = Option A + D
H = Option B + C
J = Option B + D
K = Option A + B + C
L = Option A + B + D
M = Option A + C + D
N = Option B + C + D
P = Option A + B + C + D
Feature 7: REFRIGERATION
CONTROL
0 = Standard
A = 5 Min TDR Off
B = 20 Sec TDR
C = 115V Outlet, Field Wired
D = 115V Outlet, Factory Wired
E = Option A + B
F = Option A + C
G = Option A + D
H = Option A + B + C
J = Option A + B + D
K = Option B + C
L = Option B + D
Feature 8: REFRIGERATION OPTIONS
0 = Standard
A = Hot Gas Bypass Lead Stage
B = Hot Gas Reheat
C = Modulating Hot Gas Reheat
D = Hot Gas Bypass Lead and Lag Stages
E = Option A + B
F = Option A + C
G = Option B + D
H = Option C + D
J = Sub-cooling Coil, Reheat Position
K = Option A + J
L = Option D + J
:
5A5B5C6A6B6C78910111213
14A
14B1516171819202122
–
A
0DBB0
00
–00–
0BB00AB0B
Feature 9: REFRIGERATION
ACCESSORIES
0 = Standard
A = Sight Glass
B = Compressor Isolation Valves
C = Options A + B
D = Condenser Fan VFD's
E = Options A + D
F = Options B + D
G = Options A + B + D
Feature 10: POWER OPTIONS
0 = Standard Power Block
A = Power Switch (225 Amps)
B = Power Switch (400 Amps)
C = Power Switch (600 Amps)
D = Power Switch (800 Amps)
E = Power Switch (1200 Amps)
Feature 11: SAFETY OPTIONS
0 = Standard
A = RA and SA Firestat
B = RA Smoke Detector
C = SA Smoke Detector
D = Options B + C
E = Options A + B
F = Options A + C
G = Options A + D
H = SA High Static Pressure Switch
J = Options A+H
K = Options B+H
L = Options C+H
M = Options B+C+H
N = Options A+B+H
P = Options A+C+H
Q = Options A+B+C+H
23
18
RL Series Feature String Nomenclature
R
A
A
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–352 :BEBE–D00–QFY–P0
Feature 12: CONTROLS
0 = Standard, Terminal Block
A = Low Limit Controls
B = Phase and Brown Out Protection
C = ERW Defrost
D = ERW Rotation Detection
F = Option A + B
G = Option A + C
H = Option A + D
K = Option B + C
L = Option B + D
N = Option C + D
Q = Option A + B + C
R = Option A + B + D
T = Option A + C + D
V = Option B + C + D
Y = Option A + B + C + D
Feature 13: SPECIAL CONTROLS
0 = Standard
D = VAV Unit Controller
E = Constant Volume Unit Controller
F = MakeUp Air Unit Controller
H = Field Installed DDC Control by Others
J = Factory Installed DDC Controls by Others
5 = Field Installed DDC Controls w/ iso relays
6 = Factory Installed DDC Controls by other w/
relays
Feature 14: PREHEAT
14A: PREHEAT CONFIGURATION
0 = No Preheat
C = Hot Water Coil, OA Preheat
D = Steam Distributing Coil, OA Preheat
E = Hot Water Coil, Preheat 4ft Box
F = Steam Distributing Coil, Preheat 4ft Box
14B: PREHEAT SIZING
0 = No Preheat
A = Heat Qty A
B = Heat Qty B
C = Heat Qty C
D = Heat Qty D
:
5A5B5C6A6B6C78910111213
14A
14B1516171819202122
0DBB0
–
00
–00–
0BB
00
B0B
Feature 15: OPTION BOXES
0 = Standard
A = 2 ft Box After Heat
B = 2 ft Box After Cooling
C = 2 ft Box After Pre Filter
D = 2 ft Box After Return
E = 4 ft Box After Heat
F = 4 ft Box After Cooling
G = 4 ft Box After Pre Filter
H = 4 ft Box After Return
J = 6 ft Box After Heat
K = 6 ft Box After Cooling
L = 6 ft Box After Pre Filter
M = 6 ft Box After Return
N = 8 ft Box After Heat
P = 8 ft Box After Cooling
Q = 8 ft Box After Pre Filter
R = 8 ft Box After Return
S = 2 ft Box After Preheat Coil
T = 4 ft Box After Preheat Coil
U = 6 ft Box After Preheat Coil
V = 8 ft Box After Preheat Coil
Feature 16: INTERIOR CABINET
OPTIONS
0 = Standard
B = Marine Service Lights
Feature 17: CABINET OPTIONS
0 = Standard
A = Access Door Windows
B = Burglar Bars
C = Perf Liner, SA Plenum
D = Perf Liner, RA Plenum
F = Option A + B
G = Option A + C
H = Option A + D
K = Option B + C
L = Option B + D
N = Option C + D
Q = Option A + B + C
R = Option A + B + D
T = Option A + C + D
V = Option B + C + D
Y = Option A + B + C + D
23
19
R
A
RL Series Feature String Nomenclature
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–352 :BEBE–D00–QFY–P0
Feature 18: CUSTOMER CODE
0 = None
Feature 19: CODE OPTIONS
0 = Standard ETL USA Listing
A = MEA, New York
B = Chicago Code, Cool and Gas
C = Chicago Code, Cool and Electric
D = Chicago Code, Cool Only
E = Chicago Code, Gas Only
F = Chicago Code, Electric Only
G = Chicago Code, No Cool No Heat
H = ETL USA + Canada Listing
Feature 20: CRATING
0 = Standard, One Piece Unit
A = Two Piece Unit
:
5A5B5C6A6B6C78910111213
14A
14B1516171819202122
0DBB000–00–0BB
–
00AB
0B
23
Feature 21: EVAPORATIVE-COOLED
AND WATER-COOLED CONDENSER
0 = None
A = No Sump or Vest Heaters
B = Sump and Vest Heaters
C = Balancing Valves
D = Single Point Water Connection
E = Condenser Vest Heater
F = Motorized Shutoff Valves
G = Head Pressure Control
H = Option C + D
J = Option C + E
K = Option C + F
L = Option C + G
M = Option D + E
N = Option D + F
P = Option D + G
Q = Option E + F
R = Option E + G
S = Option F + G
T = Option C + D + E
U = Option C + D + F
V = Option C + D + G
W = Option D + E + F
Y = Option D + E + G
Z = Option E + F + G
1 = Option C + D + E + F
2 = Option C + D + E + G
3 = Option C + D + F + G
4 = Option C + E + F + G
5 = Option C + D + E + F + G
20
RL Series Feature String Nomenclature
R
A
Model OptionsUnit Feature Options
GEN
SIZE
VLT
CONFIGA1A2A3A4B1B2B31A1B1C1D234
L–100–3–0–BE0 6–3 5 2 : BEBE–D0 0–QFY–P0
Feature 22: CONTROL VENDORS
0 = None
A = WattMaster Orion Controls System
B = JENEsys Controls System
C = WattMaster Orion Controls System with Specials
D = JENEsys Controls System with Specials
E = MCS Controls
F = MCS Controls w/ diagnostics
G = MCS Controls w/ modem
H = MCS Controls w/ diagnostics and modem
J = MCS Controls w/ diagnostics and touchscreen
interface
K = MCS Controls w/ diagnostics, touchscreen,
modem
L = Option E with BACnet IP, Modbus, N2
M = Option F with BACnet IP, Modbus, N2
N = Option G with BACnet IP, Modbus, N2
P = Option H with BACnet IP, Modbus, N2
Q = Option J with BACnet IP, Modbus, N2
R = Option K with BACnet IP, Modbus, N2
S = Option E with BACnet MSTP
T = Option F with BACnet MSTP
U = Option G with BACnet MSTP
V = Option H with BACnet MSTP
W = Option J with BACnet MSTP
Y = Option K with BACnet MSTP
Z = Option E with Lontalk
1 = Option F with Lontalk
2 = Option G with Lontalk
3 = Option H with Lontalk
4 = Option J with Lontalk
5 = Option K with Lontalk
:
5A5B5C6A6B6C78910111213
Feature 23: TYPE
B = Standard Paint
U = Special Pricing Authorization with Special Paint
X = Special Pricing Authorization with Standard
Paint
14A14B1516171819202122
0DBB000–00–0BB00AB
–
0B
23
21
CAUTIO
General Information
RL Series packaged rooftop and outdoor air
handling units have been designed for
outdoor installation only.
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.
Certification of Gas Heat Models
a. Certified as a forced air furnace with or
b. Certified for outdoor installation only.
c. Certified for installation on combustible
d. Certified with heat exchanger located
Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air furnace with or
b. Certified for outdoor installation only.
c. Certified for installation on combustible
WARNING
N
without cooling.
roof with a minimum of 12” high curb.
downstream of evaporator coil.
without cooling unit.
roof with a minimum of 12” high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling unit.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically
operated compressors.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.
Codes and Ordinances
RL Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236,
ANSI Safety Standard Z83.8-2006/CSA 2.62006, ANSI Z83.4-2004, and ANSI Z83.18-
2004.
System should be sized in accordance with
practices described in the American Society
of Heating, Refrigeration, and Air
Conditioning Engineers Handbooks.
Installation of RL Series units must conform
to the International Code Council (ICC)
standards of the International Mechanical
Code, the International Building Code, and
local building, plumbing, and waste water
codes. In the absence of local codes
installation must conform to current
National Fuel Code ANSI Z223.1/NFPA 54
or the National Gas & Propane Installation
Code CSA B149.1, and CSA B52
Mechanical Refrigeration Code. All
appliances must be electrically grounded in
accordance with local codes, or in the
absence of local codes, the National Electric
Code, ANSI/NFPA 70, and/or the Canadian
Electrical Code CSA C22.1.
22
CAUTIO
CAUTIO
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
N
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with this
equipment.
WARNING
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found, it should be
noted on the carrier’s Freight Bill. A request
for inspection by carrier’s agent should be
made in writing at once. Nameplate should
be checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Packaged Direct Expansion (DX) Units
All DX refrigeration systems are factory
assembled, leak tested, charged with
refrigerant, and run tested.
All refrigerant systems include evaporator
and condenser coils. Each unit includes
liquid line filter driers, thermal expansion
valves (TXV), and scroll compressors.
Compressors are equipped with a positive
pressure forced lubrication system.
Some units are equipped with
compressor crankcase heaters,
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
N
CRANKCASE HEATER
OPERATION
Never turn off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit, crankcase heaters
cannot prevent refrigerant migration into the
compressors. This means the compressor
may cool down and liquid refrigerant may
accumulate in the compressor. The
compressor is designed to pump refrigerant
gas and damage may occur when power is
restored if liquid enters the compressor.
If power to the unit must be off for more
than an hour, turn the thermostat system
switch to "OFF", or turn the unit off at the
control panel, and leave the unit off until the
main power switch has been turned on again
for at least 24 hours for units with
compressor crankcase heaters. This will give
the crankcase heater time to clear any liquid
23
accumulation out of the compressor before it
is started.
Always control the unit from the thermostat,
or control panel, never at the main power
supply, except for emergency or complete
shutdown of the unit.
During the cooling season, if the airflow is
reduced due to dirty air filters or any other
reason, the cooling coils can get too cold
which will cause excessive liquid to return
to the compressor. As the liquid
concentration builds up, oil is washed out of
the compressor, leaving it starved for
lubrication.
Compressor life will be shorted by reduced
lubrication and the pumping of excessive
amounts of liquid oil and refrigerant.
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
Note: Low Ambient Operation
Air-cooled DX units without a low ambient
option, such as condenser fan cycling or the
0°F low ambient option, will not operate in
the cooling mode of operation properly
when the outdoor temperature is below
55°F. Low ambient and/or economizer
options are recommended if cooling
operation below 55°F is expected.
Note: Multiple Units with Multiple
Thermostats
When several heating and cooling units are
used to condition a space, all unit thermostat
switches must be set in either heating mode,
cooling mode or off. Do not leave part of the
units switched to the opposite mode.
Cooling only units should be switched off at
the thermostat during the heating season.
Gas or Electric Heating
The unit is designed to heat a given airflow.
If this amount of air is reduced the gas heat
exchanger or electric heating coil may
overheat, and may turn the burner or heater
off entirely by action of the safety high
temperature limit devices which are factory
mounted at the heat exchanger and supply
blower areas.
Airflow should be adjusted after installation
to obtain an air temperature rise within the
range specified on the unit rating plate at the
required external static pressure.
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
Wiring Diagrams
Unit specific wiring diagrams in both ladder
and point-to-point form are laminated and
affixed inside the controls compartment
door.
Condensate Drain Pan
Unit requires drain traps to be connected to
the condensate drain pan of the unit. Units
include drain pan connections on both the
front and back sides of the unit. See
Installation section of this manual for more
information.
If codes require a condensate drain line, the
line should be the same pipe size or larger
than the drain connection, include a p-trap,
and pitch downward toward drain. An air
24
break should be used with long runs of
CAUTIO
CAUTIO
condensate lines.
Unit should not be operated without a
p-trap. Failure to install a p-trap may
result in overflow of condensate
water.
N
Installation
AAON equipment is designed to be easily
installed and serviced.
Locating Units
The curb should be mounted first and must
be located so that duct connections will be
clear of structural members of the building.
When locating gas fired units, it is
recommended the unit be installed so
that the flue discharge vents are
located at least 120 inches away
from any opening through which
combustion products could enter the
building.
Do not position flue opening to discharge
into a fresh air intake of any other piece of
equipment. Unit should also be installed so
that the flow of combustion intake air is not
obstructed from reaching the furnace.
Table 1 - Unit Clearances
Location Clearance
Front 100”
Back 100”
Left End 100”
Right End 100”
Top Unobstructed
WARNING
Figure 1 - RL Series Unit Orientation
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate
area around the condenser must remain free
of debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb Installation
Make openings in the roof decking large
enough to allow for duct penetrations and
workspace only. Do not make openings
larger than necessary. Set the curb to
coincide with the openings. Make sure curb
is level.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural
Sheet Metal Manual and HVAC Duct
Construction Standards for curb installation
details.
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
N
25
CAUTIO
Where the supply or warm air duct
passes through a combustible roof, a
clearance of 1 inch must be
maintained between the outside
edges of the duct and combustible
material in accordance with National
Fire Protection Association Standard
No. 90A. Provide flashings or
enclosure between structure and roof
and all joints must be sealed with
mastic roofing to ensure a watertight
seal.
N
For horizontal return and discharge
applications, total height of mounting rail
and unit base rail must be high enough so
that adequate condensate drain p-trap can be
included. Units require steel mounting rail
support along all four sides of the unit base.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line. Care must
also be taken to protect the coil and fins
from damage due to vandalism or other
causes.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used
between the curb and the unit to reduce
vibration from the unit to the building.
Duct Connection
Figure 2 - Curb Mounting
Rubber Gasket
Duct
*
Wood Nailer
Rigid
Installation
Curb
Structural
Steel
Counter
Cant Strip *
Roong Material
Roof Deck
26
Detail ‘A’
* Field Supplied
Figure 3 - Curb Detail
Figure 4 - Curb Mounting with Dimensions
with the outside air hood in the open
position.
Before lifting unit, be sure that all shipping
material has been removed from the unit.
Secure hooks and cables at all marked lifting
points provided on the unit.
Hoist unit to a point directly above the curb
and duct openings. Be sure that the gasket
material has been applied to the curb.
Carefully lower and align unit with utility
and duct openings. Lower the unit until the
unit skirt fits around the curb. Make sure the
unit is properly seated on the curb and is
level.
Figure 5 - Steel Mounting Rail with
Dimensions
Table 2 - Mounting Dimensions
Tons A B C D
45-135 100” 96” 92” 97”
134-230 142” 138” 134” 139”
Lifting the Unit
If cables or chains are used to hoist the unit
they must be the same length. See figure on
the next page for dimensions.
It is recommended to lift the unit with the
outside air hood in the downward shipping
position. However, the unit may be lifted
Figure 6 - Marked Lifting Points
27
28
Reassembling Split Units
p
CAUTIO
Some RL Series units are built and shipped
in two separate sections.
Shipping covers should be removed from the
ends where the sections will connect.
Lifting and setting the largest section first is
recommended, checking for the correct
location and position.
In order to simplify the connection of the
two sections, it is important to position and
set the second section as close as possible to
the first section. This will allow the use of a
come-along tool, to pull the second section
against the first section. One come-along
tool is required on each side of the unit,
connected at the base slots. The two sections
must be tightly adjoined before the splicing
parts can be installed.
All parts required for splicing the sections
together are factory provided. Neoprene
gasket is provided to be applied on ends of
both sections.
Once the unit is completely assembled, it is
important to visually inspect all exposed
areas and fill any gaps with butyl caulking.
Splicing
1. Align base rail and side sections.
2. Check roof alignment and connecting
flange.
3. Fill post seam with butyl caulking.
Apply butyl caulking between roof
flange sections.
4. Attach splice plate to outside of post to
cover seam. Splice plate is typically
required on both sides of the unit.
5. Install factory provided roof splice cap
over the two sections connecting flange
and secure with screws along the length
of the cap.
6. Apply butyl caulking to all seams and
perimeter of splice and to the perimeter
of the roof splice cap against the roof of
the unit.
Figure 7 - Unit Base and Sides
Attach splice cap with screws from
each side of the cap only. Do not
install screws from the to
Figure 8 - Unit Roof Flange Splice Detail
N
.
29
CAUTIO
Electrical Connection of Split Units
Before attempting to make wire connections
between sections it is important to refer to
the unit specific wiring diagram located in
the unit controls compartment to obtain
additional details related to the wiring of the
specific unit.
Adjoining sections are factory wired and
ready for field connection. The electrical
wiring is unit specific and designed
according to the overall unit configuration.
A factory supplied and mounted terminal
block is located in the main section of the
unit that must be used in making the roughin wire connections.
Each wire being spliced from section to
section is tagged at both ends according to
its termination. Junctions for wiring the
sections together are separated according to
voltage.
All wire terminations MUST BE made
before applying power to the unit.
The unit will not operate unless all
circuits are made.
N
Outside Air Rain Hood
For proper unit operation, the outside air
hood must be opened at start-up as shown
below:
Remove shipping screws from each side of
the closed hood.
Lift hood outward to the open position and
secure with sheet metal screws. Apply butyl
caulking along the top and both sides of the
rain hood. Take care to seal the top corners
where the rain hood attaches to the unit.
Outdoor air intake adjustments should be
made according to building ventilation or
local code requirements.
Air hoods vary according to unit size and
options. Figure below is shown as a practical
guideline for all outside air rain hoods.
Figure 9 - Air Hood Shown in the Open
Position
End Flashing Installation
On RL Series D and E cabinet units which
are 142” wide (RL-150, 155, 180, 190, 210,
230) the cabinet width will overhang the
trailer on each side.
In order to secure and protect the unit during
transit the sheet metal end flashings have
been removed from the unit. The slot created
at the base of each end of the unit allows the
unit to set firmly on the trailer deck.
Sheet metal flashings are shipped loose with
the unit and once the unit is set into place
the flashings must be installed on each end
of the unit to complete the finished seal at
the base. The flashings are unit specific and
designed to cover the slot at each end of the
unit to prevent water run-off into the curb.
Failure to attach and seal the end of unit
with the flashings will result in water
leakage into the curb.
30
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.