Setting the Curb / Unit ………………………………………………………………………… 07
Outside Air Hood ……………………………………………………………………………… 08
Electrical Info
Gas Piping Info ………………………………………………………………………………… 09
Service Clearances
Condensate Piping Info ……………………………………………………………………… 10
GAS UNIT LIGHTING INSTRUCTIONS …………………………………………………………… 11
IGNITION CONTROL CHECKOUT PROCEDURE ……………………………………………… 22
FACTORY START-UP FORM ………………………………………………………………………… 23
Owner should pay particular attention to the words: NOTE, CAUTION AND WARNING.
NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent
equipment damage. WARNINGS are given to alert owner that personal injury and/or equipment
damage may result if installation procedure is not handled properly.
It is the intent of
AAON, Inc.
AAON, Inc.
reserves the right to change pricing, specifications and/or design of it's products without notice, obligation or liablity.
to provide accurate and current specification information. However, in the interest of product improvement,
The units are designed as self-contained heating, cooling
or combination units for outdoor installation only, using
the refrigerant shown on the rating plate, chilled water,
natural or propane gas, electric resistance, steam or hot
water.
UNPACKING
When received, the unit should be checked for damage
that might have occurred in transit. If damage is found,
it should be noted on the carrier's Freight Bill. A request
for inspection by carrier's agent should be made in
writing at once.
CERTIFICATION
• GAS HEAT MODELS
(a)Design Certified as a forced air furnace with or without cooling unit.
(b)Certified for outdoor installation only.
(c)Certified for installation on combustible roof with a minimum of 12" high curb.
(d)Certified with Heat Exchanger located downstream from Evaporator coil.
GENERAL DESCRIPTION
!
▲
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Installation and
service must be performed by a qualified installer, service agency or the gas supplier.
NOTE: These units must not be used as a "construction heater" at any time during any phase of construction. Very low return air temperatures, harmful vapors, and misplacement of the filters will damage the
unit and its efficiency.
WARNING
• STEAM OR HOT WATER HEAT MODELS
(a)Certified as a forced air furnace with or without cooling unit.
(b)Certified for outdoor installation only.
(c)Certified for installation on combustible roof with a minimum of 12" high curb.
(d)ARI certified coils.
• ELECTRIC HEAT MODELS
(a)Certified as an electric warm air furnace with or without cooling unit.
(b)Certified for outdoor installation only.
(c)Certified for installation on combustible roof with a minimum of 12" high curb.
• COOLING MODELS
(a)Certified as a commercial central air-conditioner with or without electrically operated compressor.
(b)Certified for outdoor installation only.
(c)Certified for installation on combustible roof with a minimum of 12" high curb.
(d)ARI certified coils.
CODES AND ORDINANCES
System should be sized in accordance with National
Warm Air Heating and Air Conditioning Association
Literature, or the Guide of American Society of Heating,
Refrigeration and Air Conditioning Engineers. The
installation must conform with local building codes or, in
the absence of local codes with (United States) National
Fuel Gas Code "ANSI-Z223.1", (Canada) current CAN /
CGA- B149.1 or . 2. Installation Codes for Gas Burning
Appliances and Equipment, current C.S.A. Standard
C22.1, Canadian Electrical Code Part 1, and C.S.A.
Standard B52 Mechanical Refrigeration Code, and Local
Plumbing or Waste Water Codes.
! IMPORTANT
▲
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFC's and HCFC's) as of
July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for noncompliance.
3
OWNER'S INFORMATION
WARNING
Failure to observe the following instructions will result
in premature failure of your system, and possible voiding of the warranty.
DIRECT EXPANSION (DX) COOLING UNITS
Never cut off the main power supply to the unit, except
for complete shutdown. When power is cut off from the
unit, any compressors using crankcase heaters cannot
prevent refrigerant migration. This means the compressor will cool down, and liquid refrigerant will accumulate in the compressor. Since the compressor is designed
to pump refrigerant gas, damage may occur when power
is restored.
If power must be cut off for more than an hour, turn the
thermostat system switch to "OFF", and leave it off until
the main power switch has been turned on again for at
least twenty four hours for units with compressor crankcase heaters. This will give the crankcase heater time to
clear any liquid accumulation out of the compressor
before it is required to run.
Always control the system from the thermostat, or control panel, never at the main power supply (except for
emergency or for complete shutdown of the system).
During the cooling season, if the air flow is reduced due
to dirty air filters or any other reason, the cooling coils
will get too cold and will cause excessive liquid to return
to the compressor. As the liquid concentration builds up,
oil is washed out of the compressor, leaving it starved for
lubrication.
THE COMPRESSOR LIFE WILL BE SERIOUSLY
SHORTENED BY THIS REDUCED LUBRICATION,
AND THE PUMPING OF EXCESSIVE AMOUNTS OF
LIQUID OIL AND REFRIGERANT.
GAS OR ELECTRIC HEATING
The system is designed to cool or heat a given amount of
air each minute it operates. If this amount of air is
greatly reduced (approximately 1/3 during the heating
season), the heat exchanger / heater coil will overheat,
and may cut the burner / heater off entirely by action of
the safety high temperature limit device which is incorporated in the exchanger or heating area.
GAS HEAT UNITS - Should overheating occur, or the
gas supply fail to shut off; shut off the manual gas valve
to the furnace before shutting off the electrical supply.
PROLONGED OVERHEATING OF THE HEAT
EXCHANGER WILL SHORTEN ITS LIFE.
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury or loss of life. Installation and service must be
performed by a qualified installer, service agency or if
gas fired units, the gas supplier. Refer to installation
instructions provided with the unit and this manual.
CAUTION:While the following incorrect operations
may not cause damage to the system, they will impair
the performance, and may cause the built-in safety
devices to cut the system off completely.
1.LOW AMBIENT OPERATION
The cooling section of a direct expansion (DX)
unit will not operate properly when the outdoor
temperature is below 55° degrees. Outside air
intake options are recommended if operation
below 55° degrees is expected.
2.MULTIPLE UNIT OPERATION
When several units are used in conditioning the
space, and part or all of them are combination
heating-cooling units, all systems thermostat
switches must be set at either heating or cooling
(or set at "off"). Do not leave part of the systems
switched to the opposite mode. All cooling only
units should be switched to "off" at the thermostat during the heating season.
WIRING DIAGRAMS
A complete set of unit specific wiring diagrams in both
ladder and point-to-point form are laminated in plastic
and located inside the control compartment door.
CONDENSATE PIPING
The unit requires a drain trap to be connected to the
drainpan at the unit. If codes require a condensate drain
line, the line should be the same pipe size as the drain
nipple and should pitch downward toward drain.
The condensate drain pipe ("P" trap) is factory supplied
and is shipped loose in the control access compartment
for field installation. An air break should be used with
long runs of condensate lines.
!
▲
WARNING
Scroll compressors will be damaged by
operation with the wrong rotation.
THE LOW PRESSURE SWITCH HAS BEEN
DISCONNECTED AFTER TESTING
AT THE FACTORY.
The wiring must be reconnected and proper
rotation determined at the time of start-up by
a qualified service technician using suction
and discharge pressures gauges.
Any alteration should only be made at
the unit power connection.
4
HEATING & COOLING SYSTEMS
NORMAL OPERATION
HEATING
Set the thermostat system switch to "HEAT".
Set the thermostat fan switch to "AUTO" or "ON".
Set the thermostat temperature at the desired point.
COOLING
Set the thermostat system switch to "COOL".
Set the thermostat fan switch to "AUTO" or "ON".
Set the thermostat temperature at the desired point.
AIR CIRCULATION
Set the thermostat system switch to "OFF".
Set the thermostat fan switch to "ON".
Do not change temperature setting.
With these settings, the air circulating blower will run
continuously but the air will not be heated or cooled.
SYSTEM OFF
Set the thermostat system switch to "OFF".
Set the thermostat fan switch to "AUTO".
Do not change temperature setting.
With these settings, the system is shut down, with the
exception of the control system power (24 volts), and the
crankcase heater of the compressor (about 60 watts).
DO NOT TURN OFF THE MAIN POWER SWITCH.
NIGHT AND VACANT WEEKEND OPERATION
If it is desired to reduce the operating time during the
night, and during periods when the space is unused,
it is recommended that the temperature setting be
raised about five degrees during these periods of the
cooling season, and lowered about ten degrees during
the heating season.
GAS HEATING SYSTEM
The heating section is for use with natural gas supply
pressure of 6" to 10.5" Water Column. The unit can also
be fired on propane gas with a supply pressure to the
valve of 11" to 12" Water Column. A 1/8" pressure tap
must be supplied by the installer in the piping just ahead
of the gas valve. The rating plate on the furnace shall be
inspected to make sure that the unit is stamped for the
proper gas. The pressure tap on the outlet end of the gas
valve should be removed and the valve adjusted for the
proper manifold pressure to 3.5" on natural gas and
10.5" for propane gas.
The burner area is not sealed and combustion air is
supplied by a centrifugal blower which draws in fresh air
through a protected opening. This air is introduced into
the burner tubes by the action of the induced draft
blower. This insures an even flow of primary and secondary air to the burners.
The heating system and safety controls are 100% tested
on each unit before it leaves the factory.
INSTALLATION IS TO BE ADJUSTED
TO OBTAIN AN AIR TEMPERATURE RISE
WITHIN THE RANGE SPECIFIED ON THE
RATING PLATE.
The units are equipped with a direct spark ignition
system which proves the burner operation during each
call for heat.
Power to the ignition control is 24 volts to reduce hazards. Burner ignition is by a high intensity spark.
When heat is called for, the cooling system is inoperable
except for the indoor blower motor. Actual heating is
accomplished by firing gas into the heat exchanger
assembly.
ELECTRIC HEATING SYSTEM
Heating is accomplished by passing electrical current
through a specified amount of resistance heaters which
will produce the required heat. The indoor blower motor
will energize at the same time as the heaters.
STEAM OR HOT WATER HEATING SYSTEM
Heating is accomplished by passing steam or hot water
through the steam or hot water coil assembly.
COOLING SECTION • DX
All direct expansion refrigeration systems are factory
assembled, charged with refrigerant, tested and operated. On all units 8 ton and larger the refrigerant system
includes multiple circuit evaporator and condenser coils
providing two or more stages of cooling. These systems
are provided with liquid line filter driers, expansion
valves and fully hermetic compressors. Compressors are
equipped with a positive pressure forced lubrication
system. The air cooled condenser coil(s) is constructed of
copper tubes with aluminum fins, the air is pulled
through with propeller fans. The evaporator coil is draw
through, made of copper tubes with aluminum fins.
The refrigeration section of these appliances has been
found acceptable with applicable provisions of "ANSI /
UL 1995" and current "C.S.A. Standard C22.2" by E.T.L.
NOTE: Crankcase Heater Operation
Some units are equipped with a compressor crankcase
heater, which should be energized at least 24 hours prior
to setting the thermostat for cooling operation.
COOLING SECTION • CHILLED WATER
or NON-COMPRESSORIZED UNIT
Chilled water or non-compressorized units have factory
installed coils. These systems are provided with internal
header connections for field connection. Coils are aluminum fin / copper tube construction.
5
INSTALLATION
12
12
12
12
12
12
12
12
12
12
12
12
12
12
!
▲
CAUTION
!
▲
WARNING
If outside air is in contact with the bottom
of the unit, the unit must have the bottom
insulation option or be field insulated.
DO NOT DRILL OR PUNCH HOLES IN BASE
OF UNIT FROM INSIDE THE UNIT OR FROM
BELOW TO ATTACH DUCTWORK. LEAKING
MAY OCCUR IF UNIT BASE IS PUNCTURED.
SEE DETAIL "A"
SECTIONAL VIEW OF UNIT ON ROOF CURB
INSULATION MATERIALS MAY
DUCT /
FLEX
CONNECTOR*
STRUCTURAL
STEEL *
BE COMBUSTIBLE
GASKET
COUNTER
FLASHING *
WOOD
NAILER *
CANT STRIP *
RIGID
INSULATION *
CURB
ROOF
DECK *
DETAIL 'A'
DUCT / UNIT CONNECTION
* FIELD SUPPLIED
ROOFING
MATERIAL*
GASKET
WOOD
NAILER *
COUNTER
FLASHING *
RIGID
INSULATION *
CANT STRIP *
ROOFING
MATERIAL*
ROOF
DECK *
DUCT /
FLEX
CONNECTOR*
DUCT RAIL
CURB
STRUCTURAL
STEEL *
WOOD
NAILER *
RIGID
INSULATION *
GASKET
COUNTER
FLASHING *
CANT STRIP *
ROOFING
MATERIAL*
ROOF
DECK *
SOLIDBOTTOM
ACOUSTIC CURB
STRUCTURAL
STEEL *
DUCT / FLEX CONNECTOR*
DETAIL 'A'
OPEN BOTTOM CURB
DUCT RAIL CONNECTION
* FIELD SUPPLIED
6
DETAIL 'A'
ACOUSTIC CURB
* FIELD SUPPLIED
INSTALLATION continued
AAON Rooftop units are designed for fast, easy installation. The curb is mounted first and must be located so
that duct connections will be clear of structural members of the building.
SETTING THE CURB
When using the factory curb, make openings in roof
decking large enough to allow for duct penetrations and
workspace only. Do not make openings larger than
necessary. Set the curb to coincide with the openings.
Make sure the curb is level.
SETTING THE UNIT
If cables or chains are used to hoist the unit they must be
the same length and care should be taken to prevent
damage to the cabinet / coils or condenser fans.
It is recommended lifting the unit with the outside air
hood in the downward shipping position, however the
unit may be lifted with the outside air hood in the open
position.
Before lifting unit, be sure that all shipping material has
been removed from unit. Secure hooks and cables at all
lifting points / lugs provided on the unit.
Hoist unit to a point directly above the curb and duct
openings. Lower unit while guiding the unit to align with
utility opening and duct openings. Be sure that the
gasket material has been applied to curb. Continue lowering the unit until the unit skirt fits around the curb.
Make sure the unit is properly seated on the curb and is
level.
180" minimum
length
99" minimum
length
LIFTING DETAIL
TYPICAL FOR
2 - 25 TON UNITS
!
▲
WARNING
Improper installation, adjustment,
alteration, service or maintenance can
cause property damage, personal injury
or loss of life. Installation and service must
be performed by a qualified installer,
service agency or the gas supplier.
Install the gas fired unit to assure the flow
of combustion and ventilating air is not
obstructed from reaching the heater and
that the flue outlet is located at least
120 inches away from any opening
through which combustion products
could enter the building.
LIFTING DETAIL
TYPICAL FOR
26 - 60 TON UNITS
The unit shall be installed so that the rectangular flue (if
applicable) is located at least 120" away from any opening through which combustion products could enter the
building. The unit shall also be installed so that the flow
of combustion and ventilating air is not obstructed from
reaching the furnace. Do not position flue opening to
discharge into a fresh air intake of any other piece of
equipment.
!
▲
CAUTION
Where the supply or warm air duct passes
through a combustible roof, a clearance
of one inch must be maintained between
the outside edges of the duct and
combustible material in accordance
with National Fire Protection Association
Standard No. 90A. Provide flashings or
enclosure between structure and roof
and all joints must be sealed with mastic
roofing to ensure a watertight seal.
All roofing work should be performed by
competent roofing contractors to avoid
any possible leakage.
7
INSTALLATION continued
OUTSIDE AIR HOOD
For proper unit operation, the air hood must be opened at
start-up as shown below:
AIR HOOD SHOWN IN THE SHIPPING POSITION
(CLOSED)
ELECTRICAL
Check the unit data plate voltage to make sure it agrees
with the power supply. Connect power to the unit
according to the wiring diagram provided with the unit.
The power and control wiring may be brought up through
the utility entry. Protect the branch circuit in accordance with code requirements. Control wires should not
be run inside the same conduit. The unit must be
electrically grounded in accordance with the current
National Electric Code, ANSI / NFPA No. 70. In Canada
use current C.S.A. Standard C22.1 Canadian Electric
Code Part 1.
Power wiring is to the unit terminal block or main
disconnect. All wiring beyond this point has been done
by the manufacturer and cannot be modified without
effecting the unit's agency / safety certification.
AIRFLOW IS TO BE ADJUSTED AFTER INSTALLATION TO OBTAIN AN AIR TEMPERATURE RISE
WITHIN THE RANGE SPECIFIED ON THE RATING
PLATE.
Remove shipping screws from each side of the hood in the
"closed" postion. Lift hood to the "open" position, seal
flange and secure with sheet metal screws.
Air hoods may vary according to unit size and options.
The illustration shown is for practical guidelines for all
outside air hoods.
Outdoor air intake adjustments should be made according building ventilation or local code requirements.
DUE TO JOB SPECIFICATION REVISIONS, IT MAY
BE NECESSARY TO ADJUST OR CHANGE THE
SHEAVE OR PULLEY TO OBTAIN THE DESIRED
AIRFLOW AT THE TIME OF INSTALLATION.
START-UP TECHNICIAN MUST CHECK BLOWER
MOTOR AMPERAGE TO ENSURE THAT THE AMPERAGE LISTED ON THE MOTOR NAMEPLATE IS
NOT EXCEEDED.
NOTE: All units are factory
wired for 208 / 230, 460 or
575 volt. If unit is to be
connected to a 208v supply,
the transformer must be
rewired for 208v service.
For 208v service interchange
the yellow and red conductor
on the low voltage control
transformer.
RED - BLK 208 volt ;
YEL - BLK 230 volt.
AIR HOOD SHOWN IN THE OPEN POSITION
!
▲
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to
OFF at disconnect switch(es). Unit may have
multiple power supplies.
W ARNING
! CAUTION
▲
On three phase units the rototation must be
checked on ALL MOTORS AND COMPRESSORS.
SCROLL COMPRESSORS ARE DIRECTIONAL.
Rotation must be checked on start-up by a
qualified service technician using
suction and discharge gauges.
Scroll compressors will FAIL if run in the wrong
direction. Blower and condenser rotation
should be checked and only be altered if
necessary at the power connection.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.