Aaon LZ-053 Installation Manual

LZ Series
Chillers and Outdoor Mechanical Rooms
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Be sure to read and understand the installation, operation and service instructions in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.
A copy of this IOM should be kept with the unit.
Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your
building.
Leave the building immediately. Immediately call you gas supplier
from a phone remote from the
building. Follow the gas supplier’s
instructions.
If you cannot reach your gas
supplier call the fire department.
Startup and service must be performed by a Factory Trained Service Technician.
Installation, Operation,
3
Table of Contents
Safety .............................................................................................................................................. 8
LZ Series Feature String Nomenclature ....................................................................................... 12
General Information ...................................................................................................................... 19
Codes and Ordinances ............................................................................................................... 19
Receiving Unit ........................................................................................................................... 19
Storage ....................................................................................................................................... 20
Outdoor Mechanical Room ....................................................................................................... 20
Wiring Diagrams ....................................................................................................................... 21
General Maintenance ................................................................................................................. 21
Chiller Primary Pumping .......................................................................................................... 21
Chiller Primary/Secondary Pumping ........................................................................................ 21
Condensing Boilers ................................................................................................................... 22
Makeup Water ........................................................................................................................... 22
Compression Tank ..................................................................................................................... 23
Pressure Relief Valve ................................................................................................................ 23
Automatic Air Vent ................................................................................................................... 24
Dual Pumps ............................................................................................................................... 24
Pressure Gauges and Thermometers ......................................................................................... 24
Pipe Insulation ........................................................................................................................... 24
Installation..................................................................................................................................... 25
Outdoor Mechanical Room Placement ..................................................................................... 25
Curb and Steel Mount Installation ............................................................................................ 25
Lifting and Handling ................................................................................................................. 27
Water Connection ...................................................................................................................... 29
Boiler Gas Connection .............................................................................................................. 30
Boiler Air Intake / Vent Piping ................................................................................................. 30
Sidewall Direct Boiler Venting ................................................................................................. 32
Vertical Direct Boiler Venting .................................................................................................. 34
Boiler Condensate Drain ........................................................................................................... 38
Split Unit Assembly .................................................................................................................. 38
Unit Mounting Isolation ............................................................................................................ 38
Access Doors ............................................................................................................................. 38
Low Ambient Operation ............................................................................................................ 38
Electrical .................................................................................................................................... 39
Startup ........................................................................................................................................... 43
Condenser Fan Pitch Adjustment .............................................................................................. 44
Boiler System Startup ................................................................................................................ 47
Boiler Sequence of Operations .................................................................................................. 48
Maintenance .................................................................................................................................. 48
General ...................................................................................................................................... 48
Refrigerant Filter Driers ............................................................................................................ 48
Evaporator/Heat Exchangers ..................................................................................................... 49
Adjusting Refrigerant Charge ................................................................................................... 49
Lubrication ................................................................................................................................ 53
Air-Cooled Condenser ............................................................................................................... 53
E-Coated Coil Cleaning ............................................................................................................ 53
Recommended Coil Cleaner .................................................................................................. 54
Recommended Chloride Remover ......................................................................................... 54
Microchannel Coil Cleaning ..................................................................................................... 54
Evaporative-Cooled Condenser ................................................................................................. 56
Severe Operating Conditions Service .................................................................................... 57
Safety ..................................................................................................................................... 57
Performance ........................................................................................................................... 57
Warranties .............................................................................................................................. 58
Condenser Tube Inspection ................................................................................................... 58
Freeze Protection ................................................................................................................... 58
Recirculating Water System .................................................................................................. 58
Startup .................................................................................................................................... 58
Cleanliness ............................................................................................................................. 58
Storage ................................................................................................................................... 58
Pump Operation ..................................................................................................................... 59
Running .................................................................................................................................. 59
Condenser Fan Motors ........................................................................................................... 59
Water Make Up Valve ........................................................................................................... 59
Water Treatment System ....................................................................................................... 60
Sequence of Operation for LZ Series units without Diagnostics .......................................... 60
Sequence of Operation for LZ Series units with Diagnostics ................................................ 61
Pump Maintenance ................................................................................................................ 62
Fan Motor Maintenance ......................................................................................................... 62
Access Doors ......................................................................................................................... 62
Bearings - Lubrication ........................................................................................................... 62
Recommended Monthly Inspection ....................................................................................... 62
Mist Eliminators .................................................................................................................... 62
Air Inlet .................................................................................................................................. 62
Stainless Steel Base Pan ........................................................................................................ 62
Propeller Fans and Motors ..................................................................................................... 63
Recommended Annual Inspection ......................................................................................... 63
Cleaning ................................................................................................................................. 63
Water Quality ......................................................................................................................... 63
Mechanical Cleaning ............................................................................................................. 64
Service ....................................................................................................................................... 64
Replacement Parts ..................................................................................................................... 64
Appendix - Water Piping Component Information ...................................................................... 65
Water Pressure Reducing Valve ................................................................................................ 65
Water Pressure Relief Valve ..................................................................................................... 67
Automatic Air Vent Valves ....................................................................................................... 67
Pumps - Installation and Operating Instructions ....................................................................... 69
Pump Piping - General .............................................................................................................. 71
Pump Operation ......................................................................................................................... 71
General Care .............................................................................................................................. 72
Dual Pump Specific Information ............................................................................................... 74
4
5
Horizontal and Vertical Expansion Tanks ................................................................................ 79
Suction Guides .......................................................................................................................... 80
Glycol Auto Fill Unit ................................................................................................................ 81
Flo-Trex Combination Valve .................................................................................................... 83
LZ Series Startup Form ................................................................................................................. 88
Index of Tables and Figures
Tables:
Table 1 - Service Clearances ......................................................................................................... 25
Table 2 - Unit Gas Pipe Information, Feature B4 = A-J ............................................................... 31
Table 3 - Unit Gas Pipe Information, Feature B4 = K-N.............................................................. 32
Table 4 - Air-Cooled Condenser Fan Pitch ................................................................................... 44
Table 5 - Evaporative-Cooled Condenser Fan Pitch ..................................................................... 44
Table 6 - Condenser Fan Pin Location (Bushing Mount) ............................................................. 46
Table 7 - Condenser Fan Pin Location (Rotation Direction) ........................................................ 46
Table 8 - Fan Assembly Bushing Torque Specifications.............................................................. 47
Table 9 - Filter Drier Maximum Pressure Drop ............................................................................ 49
Table 10 - Acceptable Refrigeration Circuit Values ..................................................................... 50
Table 11 - R-134a Refrigerant Temperature-Pressure Chart ........................................................ 51
Table 12 - R-410A Refrigerant Temperature-Pressure Chart ....................................................... 52
Table 13 - Recirculating Water Quality Guidelines ..................................................................... 63
Figures:
Figure 1 - Backflow Preventer ...................................................................................................... 23
Figure 2 - Pressure Relief Valve ................................................................................................... 24
Figure 3 - Curb Mounting with Dimensions ................................................................................. 26
Figure 4 - Curb End Detail............................................................................................................ 26
Figure 5 - Steel Mounting Rail with Dimensions ......................................................................... 26
Figure 6 - Concrete Pad Mounting with Dimensions ................................................................... 27
Figure 7 - Lifting Points ................................................................................................................ 27
Figure 8 - LZ Series Example Lifting Detail ................................................................................ 28
Figure 9 - Water Pipe Flashing Installation .................................................................................. 29
Figure 10 - Sidewall Vent Shipping Cover Removal ................................................................... 32
Figure 11 - Sidewall Vent Plate Installation ................................................................................. 32
Figure 12 - Typical Air Intake Piping ........................................................................................... 33
Figure 13 - Typical Flue Vent Piping ........................................................................................... 33
Figure 14 - Sidewall Vent Base .................................................................................................... 34
Figure 15 - Sidewall Vent Cap...................................................................................................... 34
Figure 16 - Roof Air Intake and Vent Piping Shipping Covers .................................................... 34
Figure 17 - Typical Vertical Air Intake Piping ............................................................................. 35
Figure 18 - Correct Joint Connection............................................................................................ 36
Figure 19 - Incorrect Joint Connection ......................................................................................... 36
Figure 20 - Typical Vertical Vent Piping ..................................................................................... 37
Figure 21 - Vertical Termination of Air Intake and Vent Piping ................................................. 37
Figure 22 - Evaporative-Cooled Condenser Section Layout ........................................................ 42
Figure 23 - Fan with the HUB on the top and RET on the bottom. .............................................. 45
Figure 24 - Bushing Mount Location............................................................................................ 45
Figure 25 - RET with Pin in Groove 4 .......................................................................................... 45
Figure 26 - Fan HUB and RET Castings ...................................................................................... 45
Figure 27 - Pitch Insert ................................................................................................................. 46
Figure 28 - Replaceable Core Filter Driers ................................................................................... 48
Figure 29 - Proper Unit Location .................................................................................................. 57
Figure 30 - Improper Unit Locations ............................................................................................ 57
Figure 31 - Water Makeup Valve ................................................................................................. 60
V45100 · Rev. A · 150715
6
7

AAON LZ Series Features and Options Introduction

Energy Efficiency
Staged or Variable Speed R-410A Scroll
Compressors
Oil-Free Magnetic Bearing R-134a
Turbocor Centrifugal Compressors
High Efficiency Air-Cooled
Microchannel Condenser Coils
AAON Evaporative-Cooled Condenser
VFD Controlled Pumping Packages
VFD Controlled Condenser Fans
98% Thermal Efficiency Boilers
Waterside Economizers
Factory Installed EXVs
Outdoor Mechanical Room
Chilled Water Applications up to 540
tons
Hot Water Applications up to 6,000
MBH
Lighted Walk-In Service Vestibule
Factory Engineered Primary or
Primary/Secondary Pumping Packages
Factory Installed Three Chemical Water
Treatment
Factory Installed Compression Tank
Brazed Plate or Shell and Tube
Evaporators
Factory Installed Option Boxes for Field
Installed Accessories
Safety
Phase and Brownout Protection
Single Point Non-Fused Disconnect
Power Switch
Factory Installed Refrigerant Leak
Detector
Water Piping Air Separator
Waterside Thermometer and Pressure
Gauge
Installation and Maintenance
Double Wall Rigid Polyurethane Foam
Injected Panel Construction
Lighted Walk-In Service Vestibule
Access Doors with Full Length Stainless
Steel Piano Hinges
Zinc Cast Lockable Handles
Factory Installed Convenience Outlet
Service Vestibule Heating and Cooling
Motorized Service Vestibule Fresh Air
Controls Diagnostics
Touchscreen Computer Controls
Interface
Evaporative-Cooled Condenser De-
Superheater
Evaporative-Cooled Condenser Sump
Heaters
Liquid Line Sight Glass
Compressor Isolation Valves
Auto Glycol Feeder
Color-Coded Wiring Diagrams
System Integration
Complete System with AAON Chilled
Water Air Handling Units
BMS Connectivity
Grooved End Water Piping Connections
Custom Color Paint Options
Environmentally Friendly
R-410A or R-134a Refrigerant
Extended Life
Optional 5 Year Compressor Warranty
Condenser Coil Guards
2,500 Hour Salt Spray Tested Exterior
Corrosion Protection
6,000 Hour Salt Spray Tested Polymer
E-Coated Condenser Coils
8
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
ELECTRIC SHOCK, FIRE OR
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or
Improper servicing could result in dangerous operation, serious injury,
Before servicing, disconnect all electrical power to the unit. More than one disconnect may be
When servicing controls, label all wires prior to disconnecting.
Verify proper operation after servicing. Secure all doors with key-lock or nut and bolt.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a
A copy of this IOM should be kept with the unit.
Do not use any phone in the Never test for gas leaks with an Use a gas detection soap solution
and check all gas connections and shut off valves.

Safety

QUALIFIED INSTALLER
EXPLOSION HAZARD
property damage.
death, or property damage.
provided.
Factory Trained Service Technician.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit. Shut off main gas supply.
Reconnect wires correctly.
Do not touch any electric switch.
building.
open flame.
9
FIRE, EXPLOSION OR CARBON
Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.
Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
During installation, testing, servicing, and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.
Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.
Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
MONOXIDE POISONING HAZARD
GROUNDING REQUIRED
VARIABLE FREQUENCY DRIVES
perform these tasks.
10
To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
Always use a pressure regulator, valves and gauges to control incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.
Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latches are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.
Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils that are used in R-410A and other refrigerant systems will cause stress cracking of PVC or CPVC piping, even if only present in trace amounts. This will result in complete piping system failure.
CAUTION
To prevent motor overheating compressors must cycle off for a
To maintain the proper oil level compressors must cycle on for a
The cycle rate must not exceed 6 starts per hour.
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than
8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
UNIT HANDLING
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME
minimum of 3 minutes.
11
Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used with R-410A and R134a refrigeration systems. Refer to the compressor label for the proper compressor lubricant type.
CAUTION
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
Rotation must be checked on ALL MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection.
Some chemical coil cleaning
Use these substances only in accordance with the manufacturers usage instructions. Failure to follow instructions may result in equipment damage, injury or death.
WARNING
compounds are caustic or toxic.
1. Startup and service must be performed
by a Factory Trained Service Technician.
2. The unit is for outdoor use only. See
General Information section for more information.
3. Use only with type of the gas approved
for the boiler. Refer to the boiler rating plate.
4. Provide adequate combustion ventilation
air to the boiler.
5. Every unit has a unique equipment
nameplate with electrical, operational, and unit clearance specifications. Always refer to the unit nameplate for ratings unique to the model you have purchased.
6. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
7. Keep this manual and all literature
safeguarded near or on the unit.
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E
-
0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D
B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
12
Air-Cooled
Evaporative-Cooled
045 = 45 ton Capacity
053 = 53 ton Capacity
055 = 55 ton Capacity
061 = 61 ton Capacity
060 = 60 ton Capacity
069 = 69 ton Capacity
075 = 75 ton Capacity
078 = 78 ton Capacity
090 = 90 ton Capacity
090 = 90 ton Capacity
095 = 95 ton Capacity
106 = 106 ton Capacity
105 = 105 ton Capacity
120 = 120 ton Capacity
120 = 120 ton Capacity
121 = 121 ton Capacity
140 = 140 ton Capacity
134 = 134 ton Capacity
170 = 170 ton Capacity
150 = 150 ton Capacity
181 = 181 ton Capacity
161 = 161 ton Capacity
200 = 200 ton Capacity
180 = 180 ton Capacity
181 = 181 ton Capacity
193 = 193 ton Capacity
239 = 239 ton Capacity
240 = 240 ton Capacity
274 = 274 ton Capacity
300 = 300 ton Capacity
356 = 356 ton Capacity
360 = 360 ton Capacity
401 = 401 ton Capacity
441 = 441 ton Capacity
450 = 450 ton Capacity
478 = 478 ton Capacity
540 = 540 ton Capacity
Air-Cooled
A = 45-60 ton units B = 75 ton unit C = 95-140 ton units D = 175-200 ton units
Evaporative-Cooled
A = 53-69 ton units B = 78 ton unit C = 106-161 ton units D = 193-239 ton units E = 274-319 ton units F = 356-401 ton units G = 441-478 ton units
Air-Cooled
H = 90-120 ton units K = 181 ton unit
Evaporative-Cooled
H = 90-120 ton units J = 150-180 ton units K = 181 ton unit L = 240 ton unit M = 300-360 ton units N = 450-540 ton units

LZ Series Feature String Nomenclature

MODEL OPTIONS
Series and Generation
LZ
Major Revision
A
Unit Size
Series - Scroll Compressor
LZ Series Feature String Nomenclature
Series - Turbocor Compressor
Minor Revision
0
Voltage
2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz
A1: Compressor Style
F = R-410A Tandem VFD Compatible Scroll
Compressor H = R-134a Turbocor Centrifugal Compressor J = R-134a Turbocor Centrifugal Compressor with
Economizer
A2: Condenser Style
A = Air-Cooled Microchannel Condenser H = Evaporative-Cooled Condenser
A3: Evaporator Configuration
A = Brazed Plate B = Oversized Brazed Plate C = Shell & Tube D = Oversized Shell & Tube
A4: Coating
0 = Standard E = Polymer E-Coated Condenser Coil
A5: Staging
0 = Staged On/Off Compressors E = All Circuits Variable Capacity Compressors G = Half Circuits Variable Capacity Compressors
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E
-
0 0 0 0 : E 0 - 0
0
0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D
B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
13
B1: Type
0 = No Boilers
B2: Boiler Quantity
0 = No Boilers
B3: Type and Pipe Size
0 = No Boilers
B4: Boiler Capacity
0 = No Boilers
UNIT FEATURE OPTIONS
1: Unit Orientation
E = Walk-in Vestibule Left Access Left Water
Connections
F = Walk-in Vestibule Left Access Right Water
Connections
G = Walk-in Vestibule Left Access Bottom Water
Connections
J = Walk-in Vestibule Right Access Left Water
Connections
K = Walk-in Vestibule Right Access Right Water
Connections
L = Walk-in Vestibule Right Access Bottom Water
Connections
2: Pumping Style
0 = No Pumps A = Const. Primary Pumping System Small Pipe Size B = Const. Primary Pumping System Large Pipe Size C = Var. Primary Pumping System Small Pipe Size D = Var. Primary Pumping System Large Pipe Size E = Primary/Secondary Pumping System Small Pipe
Size
F = Primary/Secondary Pumping System Large Pipe
Size
3A: Building Pump Configuration
0 = No Building Pumps A = 1 Pump + High Eff Motor B = 1 Dual Pump + High Eff Motors C = 2 Single Pumps + High Eff Motors D = 1 Pump + VFD + High Eff Motor E = 1 Dual Pump + 2 VFD's + High Eff Motors F = 2 Single Pumps + 2 VFD’s + High Eff Motors K = 1 Pump + Field Installed VFD + High Eff Motor L = 1 Dual Pump + 2 Field Installed VFD's + High
Eff Motors
M = 2 Single Pumps + 2 Field Installed VFD’s +
High Eff Motors
3B: Building Pump Series and RPM
0 = No Building Pumps A = 4360 (1,200 nominal rpm) B = 4360 (1,800 nominal rpm) C = 4360 (3,600 nominal rpm) D = 4380 (1,200 nominal rpm) E = 4380 (1,800 nominal rpm) F = 4380 (3,600 nominal rpm) G = 4300 (1,200 nominal rpm) H = 4300 (1,800 nominal rpm) J = 4300 (3,600 nominal rpm) K = 4382 (1,200 nominal rpm) L = 4382 (1,800 nominal rpm) M = 4382 (3,600 nominal rpm) N = 4302 (1,200 nominal rpm) P = 4302 (1,800 nominal rpm) Q = 4302 (3,600 nominal rpm)
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E - 0 0 0 0 : E 0 - 0
0
0 0 - 0 0
0 0 - 0 0 0 0 - 0 0 - 0 0
0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D
B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
14
3C: Pump Size
0 = No Building Pumps A = 1.5B B = 2B C = 2D D = 3D E = 1.5x1.5x6 F = 2x2x6 G = 3x3x6 H = 4x4x6 J = 6x6x6 K = 1.5x1.5x8 L = 2x2x8 M = 3x3x8 N = 4x4x8 P = 5x5x8 Q = 6x6x8 R = 8x8x8 S = 2x2x10 T = 3x3x10 U = 4x4x10 V = 6x6x10 W = 8x8x10 Y = 4x4x11.5 Z = 5x5x11.5 1 = 6x6x11.5 2 = 8x8x11.5 3 = 4x4x13 4 = 6x6x13 5 = 8x8x13
3D: Building Pump Motor Size
0 = No Building Pumps A = 0.5 hp B = 0.75 hp C = 1 hp D = 1.5 hp E = 2 hp F = 3 hp G = 5 hp H = 7.5 hp J = 10 hp K = 15 hp L = 20 hp M = 25 hp N = 30 hp
P = 40 hp Q = 50 hp R = 60 hp S = 75 hp
4A: Recirculating Pump Configuration
0 = No Recirculating Pumps A = 1 Pump + High Eff Motor B = 1 Dual Pump + High Eff Motors C = 2 Single Pumps + High Eff Motors
4B: Recirculation Pump Series & RPM
0 = No Recirculating Pumps A = 4360 (1,200 nominal rpm) B = 4360 (1,800 nominal rpm) C = 4360 (3,600 nominal rpm) D = 4380 (1,200 nominal rpm) E = 4380 (1,800 nominal rpm) F = 4380 (3,600 nominal rpm) G = 4300 (1,200 nominal rpm) H = 4300 (1,800 nominal rpm) J = 4300 (3,600 nominal rpm) K = 4382 (1,200 nominal rpm) L = 4382 (1,800 nominal rpm) M = 4382 (3,600 nominal rpm) N = 4302 (1,200 nominal rpm) P = 4302 (1,800 nominal rpm) Q = 4302 (3,600 nominal rpm)
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0
0 0 - 0 0 0 0 - 0 0 - 0 0
0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D
B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
15
4C: Recirculating Pump Size
0 = No Recirculating Pumps A = 1.5B B = 2B C = 2D D = 3D E = 1.5x1.5x6 F = 2x2x6 G = 3x3x6 H = 4x4x6 J = 6x6x6 K = 1.5x1.5x8 L = 2x2x8 M = 3x3x8 N = 4x4x8 P = 5x5x8 Q = 6x6x8 R = 8x8x8 S = 2x2x10 T = 3x3x10 U = 4x4x10 V = 6x6x10 W = 8x8x10 Y = 4x4x11.5 Z = 5x5x11.5 1 = 6x6x11.5 2 = 8x8x11.5 3 = 4x4x13 4 = 6x6x13 5 = 8x8x13
4D: Recirculating Pump Motor Size
0 = No Recirculating Pumps A = 0.5 hp B = 0.75 hp C = 1 hp D = 1.5 hp E = 2 hp F = 3 hp G = 5 hp H = 7.5 hp J = 10 hp K = 15 hp L = 20 hp M = 25 hp N = 30 hp
P = 40 hp Q = 50 hp R = 60 hp S = 75 hp
5A: Boiler Building Pump Configuration
0 = No Boiler Pumps
5B: Boiler Building Pump Series & RPM
0 = No Boiler Pumps
5C: Boiler Building Pump Size
0 = No Boiler Pumps
5D: Boiler Building Pump Motor Size 0 = No Boiler Pumps
6: Refrigeration Options
0 = None A = Hot gas bypass on non-variable capacity
compressor circuits B = Hot gas bypass on all circuits
7: Refrigeration Accessories
0 = Standard A = Sight Glass B = Compressor Isolation Valves C = Option A + B
8A: Unit Disconnect Type
0 = Standard Single Point Power Block A = Single Point Power Non-fused Disconnect
8B: Disconnect 1 Size
0 = Power Block N = 100 amps R = 150 amps U = 225 amps Z = 400 amps 3 = 600 amps 5 = 800 amps 7 = 1200 amps
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0
0
0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J
0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
16
8C: Blank 0 = Standard
9: Accessories
0 = None B = Phase & Brown Out Protection
10A: Unit Control Sequence
0 = Standard AAON Controls
10B: Unit Control Supplier
E = MCS Controls
10C: Control Supplier Options
0 = None A = Touchscreen Computer Interface C = Modem G = Option A + C
10D: BMS Connection & Diagnostics
0 = None A = BACnet IP B = BACnet MSTP C = Modbus IP D = Modbus RTU E = LonTalk H = No BMS Connection with Diagnostics J = BACnet IP with Diagnostics K = BACnet MSTP with Diagnostics L = Modbus IP with Diagnostics M = Modbus RTU with Diagnostics N = LonTalk with Diagnostics
11: Cabinet Options
0 = None B = Access Door Windows
12: Vestibule Accessories
0 = None A = Refrigerant Leak Detector B = Motorized Service Vestibule Fresh Air C = Vestibule Heating (Electric) D = Vestibule Cooling (Fan/Coil) F = Option A + B G = Option A + C
H = Option A + D K = Option B + C L = Option B + D N = Option C + D R = Option A + B + C S = Option A + B + D U = Option A + C + D Y = Option B + C + D 3 = Option A + B + C + D
13: Maintenance Accessories
0 = None A = 115VAC Convenience Outlet Factory Wired B = 115VAC Convenience Outlet Field Wired C = Service Lights F = Option A + C J = Option B + C
14: Option Boxes
0 = None A = 2 ft Option Box B = 4 ft Option Box C = 6 ft Option Box D = 8 ft Option Box F = 10 ft Option Box G = 12 ft Option Box
15: Code Options
0 = Standard ETL U.S.A. Listing A = Chicago Code B = ETL U.S.A. + Canada Listing
16: Shipping Splits
0 = One Piece Unit A = Two Piece Unit
17: Air-Cooled Condenser Accessories
0 = None (No Air-Cooled Condenser) H = Cond Coil Guards + 3Φ Condenser Fan Motor +
Fan Cycling (25°F) J = Cond Coil Guards + 3Φ Condenser Fan Motor +
VFD Condenser Fan Head Pressure Control (0°F)
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0
0 0 - 0 0 0 0 - 0 0 - 0 0
0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D
B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
17
18: Evaporative-Cooled Condenser Accessories
0 = None (No Evaporative-Condenser) A = No Sump Heat B = Sump Heaters
19: Blank
0 = None
20: Blank
0 = None
21: Chiller Compression Tank
0 = None A = AX-15V B = AX-20V C = AX-40V D = AX-60V E = AX-80V F = AX-100V G = AX-120V H = AX-180V J = AX-200V K = AX-240V L = AX-260V M = AX-280V
22: Boiler Compression Tank
0 = None
23: Blank
0 = Standard
24: Chiller Accessories 1
0 = None A = Glycol chiller B = Air Separator C = Thermometers & Pressure Gauges D = Chemical Pot Feeder E = Auto Glycol Feeder F = Option A + B G = Option A + C H = Option A + D J = Option A + E K = Option B + C L = Option B + D
M = Option B + E N = Option C + D P = Option C + E Q = Option D + E R = Option A + B + C S = Option A + B + D T = Option A + B + E U = Option A + C + D V = Option A + C + E W = Option A + D + E Y = Option B + C + D Z = Option B + C + E 1 = Option B + D + E 2 = Option C + D + E 3 = Option A + B + C + D 4 = Option A + B + C + E 5 = Option A + B + D + E 6 = Option A + C + D + E 7 = Option B + C + D + E 8 = Option A + B + C + D + E
25: Blank
0 = Standard
26A: Blank
0 = Standard
26B: Blank
0 = Standard
26C: Blank
0 = Standard
26D: Blank
0 = Standard
26E: Blank
0 = Standard
26F: Blank
0 = Standard
27: Blank
0 = Standard
LZ Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5 B1
B2
B3
B4 1 2
3A
3B
3C
3D 4A
4B
4C
4D 5A
5B
5C
5D 6 7
8A
8B
8C
LZ A -
140
- C - 0 - 3 - F A C 0
E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0
0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0
0 0 0 0 - 0 0 D B
9
10A
10B
10C
10D
11
12
13
14
15 16
17
18
19
20 21
22
23
24
25 26A
26B
26C
26D
26E
26F
27
28
29
30
31 32
33
34
35
18
28: Blank
0 = Standard
29: Blank
0 = Standard
30: Blank
0 = Standard
31: Blank
0 = Standard
32: Blank
0 = Standard
33: Warranty
0 = Standard Warranty D = Compressor Warranty Years 2-5
34: Cabinet Material
D = Galvanized Cabinet 6” Base Rail + Double Slope
Roof
H = Galvanized Cabinet 8” Base Rail + Double Slope
Roof
35: Paint & Special Pricing Authorizations
B = Premium AAON Gray Paint Exterior E = Premium AAON Gray Paint Exterior + Shrink
Wrap X = Special Pricing Authorization + Premium AAON
Gray Paint Exterior 1 = Option X + Shrink Wrap 4 = Special Pricing Authorization + Special Exterior
Paint Color 7 = Option 4 + Shrink Wrap
19
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a
Electrical raceways are located in the upper wall sections of the unit. DO NOT CUT OR DRILL into the wall sections of the unit that are within 12 inches of the roofline.
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling, or reclaiming
Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.
Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.

General Information

AAON LZ Series chiller outdoor mechanical rooms are complete self­contained liquid chilling units. They are assembled, wired, charged, and run-tested. Models are available for air-cooled and evaporative-cooled applications. Chiller primary pumping packages, primary/secondary pumping packages, and boilers with pumping package are available as optional features.
Factory Trained Service Technician.
Installation of LZ Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, and local building, plumbing and waste water codes. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
must be followed.
RISK OF ELECTRICAL SHOCK

Codes and Ordinances

LZ Series units have been tested and certified, by TL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook.

Receiving Unit

When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be checked to ensure the correct model sizes
20
To prevent motor overheating compressors must cycle off for a
To maintain the proper oil level compressors must cycle on for a
The cycle rate must not exceed 6 starts per hour.
Before unit operation, the main power switch must be turned on for at least 24 hours for units equipped with crankcase heaters.
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. All motors, to include and not be limited to pump motors and condenser fan motors, should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
Scroll compressors are directional and will be damaged by operation in the wrong direction. High pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should be made at the unit power connection.
and voltages have been received to match the job requirements.

Storage

If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Leave all internal packaging in place and secure all loose­shipped items.

Outdoor Mechanical Room

COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
Never turn off the main power supply to the unit, except for complete shutdown. When power is cut off from the unit, any compressors equipped with crankcase heaters cannot prevent refrigerant migration. This means the compressor will cool down, and liquid refrigerant may accumulate in the compressor. The compressor is designed to pump refrigerant gas and damage may occur when power is restored if liquid enters the compressor.
minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME
minimum of 3 minutes.
Failure to observe the following instructions will result in premature failure of your system, and possible voiding of the warranty.
Always control the system from the building management system, or control panel, never at the main power supply (except for emergency or for complete shutdown of the system).
21
Some units may require field wired connections. Refer to the wiring diagrams contained within the unit to identify any components or controls requiring additional wiring in the field before placing the unit into service. All additional field wiring should be performed by a Factory Trained Service Technician.
CAUTION
Scroll compressors must be on a minimum of 3 minutes and off for a minimum of 3 minutes. The cycle rate must be no more than 6 starts per hour.
The chiller is furnished with a flow switch installed on the outlet of each heat exchanger. This sensor must not be bypassed since it provides a signal to the unit controller that water flow is present in the heat exchanger and the unit can operate without the danger of freezing the liquid.
Compressor life will be seriously shortened by reduced lubrication, and the pumping of excessive amounts of liquid oil and refrigerant.

Wiring Diagrams

A complete set of unit specific wiring diagrams in both ladder and point-to-point form are laminated in plastic and located inside the control vestibule.
FIELD WIRED CONNECTIONS

General Maintenance

When the initial startup is made and on a periodic schedule during operation, it is necessary to perform routine service checks on the performance of the chiller and boiler. This includes reading and recording suction pressures and checking for normal sub­cooling and superheat. See the evaporative-
cooled condenser and air-cooled condenser sections in this manual for specific details.

Chiller Primary Pumping

Primary pumping uses a single pump to move water (or glycol) through the chiller evaporator and back to the building. This pumping package provides a constant or variable flow of water to the building. The pump is activated whenever the chiller is given a run signal.
Water enters the unit through the return water piping, and then travels through an air separator to remove any air that is entrapped in the water. Following this, the water flows through a suction guide with an integral strainer. The end of the suction guide is removable for strainer access. The strainer assembly is composed of two parts, the operational strainer and the startup strainer, (located inside the operational strainer) which is to be removed 24 hours after startup.
The pump is installed after the suction guide, and before a combination valve (Flo­Trex). This combination valve acts as an isolation valve, check valve, and flow balancing valve. The evaporator is placed after the combination valve in the water circuit, with a flow switch installed at its inlet and outlet. This pressure switch closes when the velocity is above .7 feet per second. The closing flow switch signals the control system to indicate flow through the heat exchanger and allow cooling to activate as required to maintain the setpoint. The water exiting the chiller evaporator leaves the unit through the water out connection.

Chiller Primary/Secondary Pumping

Primary/secondary pumping option provides variable flow to the system. It consists of a constant flow pump for the chiller heat exchanger and a variable flow pump for the
22
building. The controls package senses differential pressure across the pump with pressure transducers installed at the suction and discharge, and varies the speed of the pump using a VFD in order to maintain a given differential pressure across the pump.
The primary/secondary pumping package is essentially composed of two piping loops coupled together. The primary loop has a constant flow rate in order to keep the chiller heat exchanger from freezing, and the secondary, variable flow loop, provides water to the building. The two loops are coupled via a water line that compensates for excess flow in either loop. As the flow in the secondary loop decreases below the flow in the primary loop, excess flow bypasses the building loop and circulates through the bypass water line. On the other hand, as the flow in the secondary loop increases above the flow in the primary loop, excess flow bypasses the chiller and circulates through the bypass water line.
The secondary pump has its own suction guide, combination valve, and isolation valve, similar to the primary pump, with the addition of an air separator to remove any air that is entrapped in the water.

Condensing Boilers

AAON LZ chillers are available with factory installed condensing boilers. All boiler systems will include either fixed or variable speed building pumps. All boiler building pumps will be supplied with a suction guide with a strainer and triple duty valve. The suction guide contains both an operational strainer and a startup strainer. The startup strainer should be removed 24 hours after startup. The triple duty valve functions as an isolation valve, check valve, and flow balancing valve.
The condensing boilers will be a water tube design or a fire tube design. In a water-tube boiler, the water flows through tubes with the combustion products heating from the outside. These boilers require a constant water flow and will be provided with a primary pump for each heat exchanger. Some boilers have two heat exchangers and will have two primary pumps. The primary pump is controlled by the boiler and will only come on when it has a call for heat. Water-tube boilers are provided with flow switches, which must make before the boiler can operate.
In fire-tube boilers water flows through a tank, with the combustion products inside tubes. These boilers are capable of significant water flow turn-down and do not require individual primary pumps. A control valve, operate by the boiler controls, is provided with each boiler. A water flow switch is not required with fire-tube boilers. A low-level cutoff switch is used which will prevent the boiler from operating when there is not a sufficient water level present. Upon initial startup, the boiler may have to be cycled several times to generate an adequate water level.

Makeup Water

A city make up water connection is provided to replace water that is lost from the system.
Glycol units require a glycol feeder (optional factory installed or field installed) to replace fluid that is lost in the system. Water should not be directly added to glycol applications as this would dilute the glycol concentration and thereby increase the freezing temperature of the fluid.
The makeup water connection is provided with a backflow preventer that has isolation valves on the inlet and outlet for service.
23
Figure 1 shows the pressure drop versus flow rate for the backflow preventer.
Figure 1 - Backflow Preventer
There is a pressure-reducing valve after the backflow preventer. This valve reduces the city water pressure to maintain the operating pressure of the system. This valve is adjustable from 10-35 psig with a factory setting of 30 psig. The system pressure varies with the height of the system. The pressure-reducing valve setting should be set so that the pressure at the high point in the system is high enough to vent air from the system (usually 4 psig). There should be air vents at all parts in the system where air could be trapped. If the pressure is not high enough throughout the system, flashing could occur in the piping or the pump could cavitate. There is an isolation valve on the inlet and outlet of the pressure-reducing valve for service.
The pressure reducing valve fills the system at a reduced rate. There is a bypass around the pressure reducing valve for the initial fill of the system to increase the initial fill speed. After the initial system fill, this valve should be closed.

Compression Tank

As the water temperature in the system increases, the volume that water displaces increases. In order to compensate for these expansion forces, a compression or expansion tank must be used. The factory installed tank option includes a pre-
pressurized diaphragm compression tank that is preset for 12 psig.
The factory pre-charge pressure may need to be field adjusted. The tank must be pre­charged to system design fill pressure before placing into operation. Remove the pipe plug covering the valve enclosure. Check and adjust the charge pressure by adding or releasing air.
If the system has been filled, the tank must be isolated from the system and the tank emptied before charging. This ensures that all fluid has exited the diaphragm area and proper charging will occur.
If the pre-charge adjustment is necessary, oil and water free compressed air or nitrogen gas may be used. Check the pre-charge using an accurate pressure gauge at the charging valve and adjust as required. Check air valve for leakage. If evident, replace the Schrader valve core. Do not depend on the valve cap to seal the leak. After making sure the air charge is correct, replace the pipe plug over the charging valve for protection.
Purge air from system before placing tank into operation. All models have system water contained behind the diaphragm.
It is recommended that the pre-charge be checked annually to ensure proper system protection and long life for the vessel.

Pressure Relief Valve

Required pressure relief valve is installed in the unit. This valve is set at 125 psig. Figure 2 shows inlet pressure versus capacity for this pressure relief valve. See appendix for additional information.
24
Figure 2 - Pressure Relief Valve

Automatic Air Vent

There is an automatic air vent installed at the high point of the system inside the pumping package compartment. The air vent valve must be in the proper position for operation. Ensure that the small vent cap is loosened two turns from the closed position, allowing air to be vented from the system. It is advisable to leave the cap on to prevent impurities from entering the valve. See appendix for additional information.

Dual Pumps

When redundant pumping is required, factory installed dual pumps or two single pumps can be ordered. A dual pump is a pump with two independent motors and impellors in a single casing. This dual pump has a swing split-flapper valve in the discharge port to prevent liquid recirculation when only one pump is operating. Isolation valves in the casing allow one pump to be isolated and removed for service while the other pump is still operating.
When redundant pumping is required with high flow rates, two independent pumps may be installed in parallel. Each pump will have its own suction guide/strainer, combination valve, and isolation valves.
The controls package will activate the pump when the unit is given a run command. If the controls do not recognize flow in 60 seconds (factory default), the second pump will be activated and an alarm signal will be generated. If the second pump does not activate, the cooling will be locked out. See Appendix - Water Piping Component Information for additional information.

Pressure Gauges and Thermometers

Pressure gauges and thermometers are available as a factory installed option. Thermometers are installed on the inlet and outlet of the unit. One pressure gauge is installed at each pump. This pressure gauge is connected in three places to the water piping before the suction guide/strainer, after the suction guide and before the pump, and after the pump. There is also a valve at each of these points to isolate the pressure. To measure the pressure at any given point, open the valve at that point and close the other two valves. One gauge is used so that the calibration of the pressure gauge is irrelevant in the calculation of the differential pressure.

Pipe Insulation

The water piping and components on units with pumping packages are not insulated at the factory. Insulation should be installed on the water piping after the system has been checked for leaks.
25
Location
Unit Size
45-540 tons
Left
96”
Right
Compressor End
72”
Chiller HXC End
Top
Unobstructed
All roofing work should be performed by competent roofing contractors to

Installation

Outdoor Mechanical Room Placement

The AAON LZ Series is designed for outdoor applications and can be mounted at ground level or on a rooftop. It must be placed on a level and solid foundation that has been prepared to support its weight.
The placement relative to the building air intakes and other structures must be carefully selected. Be sure to observe the dimensions that are on the rating plate of the chiller for operational and service clearances.
Table 1 - Service Clearances
Condenser coils and fans must be free of any obstructions in order to start and operate properly with a correct amount of airflow. For proper unit operation, the immediate area around condenser(s) must remain free of debris that may be drawn in and obstruct airflow in the condensing section.
Consideration must be given to obstruction caused by snow accumulation when placing the unit.

Curb and Steel Mount Installation

Make openings in the roof decking large enough to allow for water piping, electrical,
and gas penetrations and workspace only. Do not make openings larger than necessary. Set the curb to coincide with the openings. Make sure curb is level.
Unit specific curb drawing is included with job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation details.
avoid any possible leakage.
When installed at ground level, a one-piece concrete slab should be used with footings that extend below the frost line. Care must also be taken to protect the coil and fins from damage due to vandalism or other causes.
If unit is elevated a field supplied catwalk is recommended to allow access to unit service doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used between the curb and the unit to reduce vibration transmission from the unit to the building.
26
Figure 3 - Curb Mounting with Dimensions
Figure 4 - Curb End Detail
Figure 5 - Steel Mounting Rail with Dimensions
27
Figure 6 - Concrete Pad Mounting with Dimensions

Lifting and Handling

If cables or chains are used to hoist the unit they must be the same length and care should be taken to prevent damage to the cabinet. See Figure 8 for additional information.
Before lifting unit, be sure that all shipping material has been removed from unit. Secure hooks and cables at all lifting points/ lugs provided on the unit.
Hoist unit to a point directly above the curb or mounting rail. Be sure that the gasket material has been applied to the curb or mounting rail.
Carefully lower and align unit with utility openings. Lower the unit until the unit skirt fits around the curb. Make sure the unit is properly seated on the curb and is level.
Do not push, pull or lift the unit from anything other than its base.
Figure 7 - Lifting Points
28
Figure 8 - LZ Series Example Lifting Detail
Lifting slot locations are unit specific.
Unit must be rigged at all marked lifting points.
29
The chiller must be operated only with liquid flowing through the evaporators.
Boilers must be operated only with liquid flowing through the boiler.
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings. This will result in complete piping system failure.
Installing Contractor is responsible for proper sealing of the water piping and electrical entries into the unit Failure to seal the entries may result in damage to the unit and property.

Water Connection

Remove the shipping cover from the water connection cutout in the post. Connect the supply and return water lines. The standard water connection is grooved end pipe. The connection size is listed on the unit rating sheet along with the designed volumetric flow rate. The maximum operating pressure for AAON LZ Series unit is 125 psi. Install the flashing provided by AAON according to the steps in Figure 9. Finished water connection will be water tight.
Figure 9 - Water Pipe Flashing Installation
30
Failure to apply sealing compound as detailed can result in property damage, personal injury, or death.
DO NOT use matches, candles, open flames, or other ignition sources to check for gas leaks. Use only approved leak detection methods. Failure to comply with this warning can result in property damage, personal injury, or death.
Failure to provide a properly installed vent and air system can result in property damage, personal injury, or death.

Boiler Gas Connection Before making gas connection, make sure the boiler is being supplied with the type of fuel shown on the boiler nameplate.

Table 2 and Table 3 show the gas connection size and type (NPT or flanged) provided along with the required inlet gas pressure for the unit. Refer to feature B on the LZ Series unit feature string to determine which line of the table to use. For example, a unit with feature B = A3CC will
have a 2” NPT gas connection and require
an inlet gas pressure in the range of 6-14” W.C.
Use only pipe sealing compound that is compatible with propane gases on all threaded connections. Apply sparingly only to the male threads of the pipe joints so that the pipe sealing compound does not block any gas flow.
Before being placed in operation, the boiler and all gas piping connections must be checked for leaks. The boiler must be disconnected from the gas supply piping system during any pressure testing of the
system at pressures in excess of .5 psig (14”
W.C.). The boiler must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the system at pressures equal to or less than .5 psig (14” W.C.).
Some leak test solutions, including soap and water, may cause corrosion. These solutions should be rinsed off with water after testing.

Boiler Air Intake / Vent Piping Each boiler requires the installation of air intake and vent piping. This piping has been removed for shipping purposes. All piping must be reinstalled according to the instructions provided in this section prior to boiler operation.

All boilers must be vented and supplied with combustion and ventilation air as described in this section and in the Lochinvar Installation & Operation Manual included with the boiler. Ensure the vent and air piping and combustion air supply comply with instructions regarding vent system, air system, and combustion air quality.
Inspect finished vent and air intake piping thoroughly to ensure all are airtight and comply with the instructions provided and with all requirements of applicable codes.
Loading...
+ 70 hidden pages