Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
electrical power to the furnace.
More than one disconnect may be
provided.
When servicing controls, label all
wires prior to disconnecting.
Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with
key-lock or nut and bolt.
WARNING
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections
and shut off valves.
CAUTION
7
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
WARNING
WARNING
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNING
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
CAUTION
8
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
CAUTION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
CAUTION
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
To prevent damage to the unit, do not
use acidic chemical coil cleaners.
Use alkaline chemical coil cleaners
with a pH value of 5-9, after mixing,
without first using an aluminum
corrosion inhibitor in the cleaning
solution.
CAUTION
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
WARNING
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
CAUTION
9
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
1. Startup and service must be performed
by a Factory Trained Service Technician
2. The unit is for outdoor use only. See
General Information section for more
information.
3. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
045 = 45 ton Capacity
055 = 55 ton Capacity
060 = 60 ton Capacity
075 = 75 ton Capacity
095 = 95 ton Capacity
105 = 105 ton Capacity
120 = 120 ton Capacity
140 = 140 ton Capacity
SERIES
A = 45-60 ton units
B = 75 ton unit
C = 95-140 ton units
C = R-410A Tandem VFD Compatible Scroll
Compressor
A2: CONDENSER STYLE
A = Air-Cooled Microchannel Condenser
A3: EVAPORATOR CONFIGURATION
A = Standard Brazed Plate Constant Flow
B = Oversized Brazed Plate Constant Flow
C = Standard Shell & Tube Constant Flow
D = Oversized Shell & Tube Constant Flow
A4: COATING
0 = Standard
E = Polymer E-Coated Condenser Coil
A5: STAGING
0 = Staged Compressors
E = All Circuits with Variable Capacity Compressors
- 2 Circuits
G = Half Circuits with Variable Capacity
Compressors - 2 Circuits
B1: BLANK
0 = Standard
B2: BLANK
0 = Standard
B3: BLANK
0 = Standard
B4: BLANK
0 = Standard
UNIT FEATURE OPTIONS
1: UNIT ORIENTATION
A = Standard Access Left Water Connections
B = Standard Access Right Water Connections
C = Standard Access Bottom Water Connections
2: PUMPING STYLE
0 = No Pumps
B = Constant Flow Primary Pumping System - Large
Pipe Size
D = Variable Flow Primary Pumping System - Large
Pipe Size
11
LN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D 6 7 8A
8B
8C 9
10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – C A C 0 E – 0 0 0 0 : A 0 – 000 0 – 0 0 0 0 – 0 0 0 0 – 0 0 – 0 0 0 – 0 – 0 E 0 0 –
0 = No Building Pumps
A = 1 Pump + High Eff Motor
B = 1 Dual Pump + High Eff Motors
D = 1 Pump + VFD + High Eff Motor
E = 1 Dual Pump + 2 VFD's + High Eff Motors
K = 1 Pump + Field Installed VFD + High Eff Motor
L = 1 Dual Pump + 2 Field Installed VFD's + High
Eff Motors
3B: BUILDING PUMP SERIES AND RPM
0 = No Building Pumps
A = 4360 (1,170 nominal rpm)
B = 4360 (1,760 nominal rpm)
C = 4360 (3,520 nominal rpm)
D = 4380 (1,170 nominal rpm)
E = 4380 (1,760 nominal rpm)
F = 4380 (3,520 nominal rpm)
K = 4382 (1,170 nominal rpm)
L = 4382 (1,760 nominal rpm)
M = 4382 (3,520 nominal rpm)
3C: PUMP SIZE
0 = No Building Pumps
A = 1.5B
B = 2B
C = 2D
D = 3D
E = 1.5x1.5x6
F = 2x2x6
G = 3x3x6
H = 4x4x6
J = 6x6x6
K = 1.5x1.5x8
L = 2x2x8
M = 3x3x8
N = 4x4x8
P= 5x5x8
Q = 6x6x8
R = 8x8x8
S = 2x2x10
T = 3x3x10
U = 4x4x10
V = 6x6x10
W = 8x8x10
Y = 4x4x11.5
Z = 5x5x11.5
1 = 6x6x11.5
2 = 8x8x11.5
3 = 4x4x13
4 = 6x6x13
5 = 8x8x13
12
LN Series Feature String Nomenclature
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2 3A
3B
3C
3D 4A
4B
4C
4D
5A
5B
5C
5D 6 7
8A
8B
8C
9 10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – C A C 0 E – 0 0 0 0 : A 0 – 0 0 0 0 – 0000 – 0000 – 00 – 000 – 0 – 0E0 0
0 = None
A = BACnet IP
B = BACnet MSTP
C = Modbus IP
D = Modbus RTU
E = Lontalk
H = No BMS Connection with Diagnostics
J = BACnet IP with Diagnostics
K = BACnet MSTP with Diagnostics
L = Modbus IP with Diagnostics
M = Modbus RTU with Diagnostics
N = Lontalk with Diagnostics
11: BLANK
0 = Standard
12: VESTIBULE ACCESSORIES
0 = Standard
C = Vestibule Heating (Electric)
13: MAINTENANCE ACCESSORIES
0 = Standard
A = 115VAC Convenience Outlet Factory Wired
B = 115VAC Convenience Outlet Field Wired
C = Service Lights
F = Options A + C
J = Options B + C
14: BLANK
0 = Standard
15: CODE OPTIONS
0 = Standard ETL U.S.A. Listing
A = Chicago Code
B = ETL U.S.A. + Canada Listing
16: SHIPPING SPLITS
0 = One Piece Unit
17: AIR-COOLED CONDENSER
ACCESSORIES
H = Cond Coil Guards + Three Phase Cond Fan
Motor + Fan Cycling- 35°F Low Ambient
J = Cond Coil Guards + VFD Cond Fan Head
Pressure Control - 0°F Low Ambient
18: BLANK
0 = Standard
19: BLANK
0 = Standard
20: BLANK
0 = Standard
21: BLANK
0 = Standard
22: BLANK
0 = Standard
23: BLANK
0 = Standard
24: CHILLER ACCESSORIES 1
0 = Standard
A = Glycol Chiller
C = Thermometers & Pressure Gauges
G = Option A + C
25: BLANK
0 = Standard
26A: BLANK
0 = Standard
26B: BLANK
0 = Standard
26C: BLANK
0 = Standard
14
LN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D 6 7 8A
8B
8C 9
10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – C A C 0 E – 0 0 0 0 : A 0 – 0 0 0 0 – 0 0 0 0 – 0 0 0 0 – 0 0 – 0 0 0 – 0 – 0 E 0 0 –
0 = Standard Warranty
D = Compressor Warranty Years 2-5
34: CABINET MATERIAL
0 = Standard - Double Wall + R-13 Foam Insulation
35: PAINT & SPECIAL PRICING
AUTHORIZATIONS
B = Premium AAON Gray Paint Exterior
E = Premium AAON Gray Paint Exterior + Shrink
Wrap
X = Special Pricing Authorization + Premium AAON
Gray Paint Exterior
1 = SPA + Premium AAON Gray Paint Exterior +
Shrink Wrap
4 = Special Pricing Authorization + Special Exterior
Paint Color
7 = SPA + Special Exterior Paint Color + Shrink
Wrap
15
General Information
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
CAUTION
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with
equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING
WARNING
AAON LN Series chillers are complete selfcontained liquid chilling units. They are
assembled, wired, charged and run-tested.
Models are available for air-cooled
applications. Chiller primary pumping
packages are available as optional features.
Codes and Ordinances
LN Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of LN Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
16
Chiller
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. All motors, to
include and not be limited to pump
motors and condenser fan motors,
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
at the unit power connection.
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CRANKCASE HEATER
OPERATION
Units may be equipped with
compressor crankcase heaters,
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the
warranty.
Never turn off the main power supply to the
unit, except for complete shutdown. When
power is cut off from the unit, any
compressors using crankcase heaters cannot
prevent refrigerant migration. This means
the compressor will cool down, and liquid
refrigerant may accumulate in the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored if liquid enters the
compressor.
Before unit operation, the main power
switch must be turned on for at least 24
hours for units with compressor crankcase
heaters. This will give the crankcase heater
time to clear any liquid accumulation out of
the compressor before it is required to run.
Never cut off the main power supply to the
unit, except for complete shutdown. Always
control the system from the building
management system, or control panel, never
at the main power supply (except for
emergency or for complete shutdown of the
system).
17
Scroll compressors must be on a minimum
of 5 minutes and off for a minimum of 5
minutes. The cycle rate must be no more
than 6 starts per hour.
The chiller is furnished with a pressure
differential switch that is factory installed
between the chilled water supply and return
connections. This sensor must not be
bypassed since it provides a signal to the
unit controller that water flow is present in
the heat exchanger and the unit can operate
without the danger of freezing the liquid.
Compressor life will be seriously shortened
by reduced lubrication, and the pumping of
excessive amounts of liquid oil and liquid
refrigerant.
Wiring Diagrams
A complete set of unit specific wiring
diagrams in both ladder and point-to-point
form are laminated in plastic and located
inside the control compartment door.
General Maintenance
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the chiller. This
includes reading and recording suction
pressures and checking for normal subcooling and superheat. See the air-cooled
condenser sections in this manual for
specific details.
Chiller Primary Pumping
Primary pumping uses a single pump to
move water (or glycol) through the chiller
barrel and back to the building. This
pumping package provides a constant flow
of water to the system. The pump is
activated whenever the chiller is given a run
signal.
Water enters the unit through the return
water piping, and then travels through an air
separator to remove any air that is entrapped
in the water. Following this, the water flows
through a suction guide with strainer. The
end of the suction guide is removable for
strainer access. The strainer assembly is
composed of two parts, the operational
strainer and the startup strainer, (located
inside the operational strainer) which is to
be removed 24 hours after startup.
The pump is installed after the suction
guide, and before a combination valve (FloTrex). This combination valve acts as
isolation valve, check valve, and flow
balancing valve. The shell and tube or
brazed plate evaporator, is placed after the
combination valve in the water circuit, with
a differential pressure switch installed across
its inlet and outlet. This pressure switch
closes when the differential pressure
increases above the setpoint, which should
be set 1-2 psig below the pressure drop
across the heat exchanger at design flow
rate. The closing differential pressure switch
signals the control system to indicate flow
through the heat exchanger and allow
cooling to activate as required to maintain
the setpoint. The water exiting the shell and
tube or brazed plate evaporator, leaves the
unit through the water out connection.
Automatic Air Vent
There is an automatic air vent installed at the
high point of the system inside the pumping
package compartment. The air vent valve
must be in the proper position for operation.
Ensure that the small vent cap is loosened
two turns from the closed position, allowing
air to be vented from the system. It is
advisable to leave the cap on to prevent
impurities from entering the valve. See
appendix for additional information.
18
Dual Pumps
When redundant pumping is required,
factory installed dual pumps can be ordered.
A dual pump is a pump with two
independent motors and pumps in a single
casing. This dual pump has a swing splitflapper valve in the discharge port to prevent
liquid recirculation when only one pump is
operating. Isolation valves in the casing
allow one pump to be isolated and removed
for service while the other pump is still
operating.
The controls package will activate the pump
when the unit is given a run command. If the
controls do not recognize flow in 60
seconds, the second pump will be activated
and an alarm signal will be generated. If the
second pump does not activate, the cooling
will be locked out. See appendix for
additional information.
Pressure Gauges and Thermometers
Pressure gauges and thermometers are
available as a factory installed option.
Thermometers are installed on the inlet and
outlet of the unit. One pressure gauge is
installed at each pump. This pressure gauge
is connected in three places to the water
piping before the suction guide/strainer,
after the suction guide and before the pump,
and after the pump. There is also a needle
valve at each of these points to isolate the
pressure. To measure the pressure at any
given point, open the needle valve at that
point and close the other two needle valves.
One gauge is used so that the calibration of
the pressure gauge is irrelevant in the
calculation of the differential pressure.
Pipe Insulation
The water piping and components on units
with pumping packages are not insulated at
the factory. Insulation should be installed on
the water piping after the system has been
checked for leaks.
19
Installation
Location
Unit Size
45-140 tons
Front -
(Controls Side)
72”
Back
72”
Ends
96”
Top
Unobstructed
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
CAUTION
Chiller Placement
The AAON LN Series is designed for
outdoor applications and mounting at
ground level or on a rooftop. It must be
placed on a level and solid foundation that
has been prepared to support its weight.
The placement relative to the building air
intakes and other structures must be
carefully selected. Be sure to observe the
dimensions that are on the rating plate of the
chiller for operational and service
clearances.
Table 1 - Service Clearances
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate
area around condenser must remain free of
debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb and Steel Mount Installation
Make openings in the roof decking large
enough to allow for water piping, electrical
penetrations, and workspace only. Do not
make openings larger than necessary. Set the
curb to coincide with the openings. Make
sure curb is level.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation
details.
Units require rail support along all four sides
of the unit base.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line. Care must
also be taken to protect the coil and fins
from damage due to vandalism or other
causes.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used
between the curb and the unit to reduce
vibration from the unit to the building.
Figure 1 - Curb Mounting with Dimensions
20
Figure 2 - Steel Mounting Rail with
Tons
A B C
D
45-140
142”
138”
134”
139”
Dimensions
Table 2 - Mounting Dimensions
Lifting and Handling
If cables or chains are used to hoist the unit
they must be the same length and care
should be taken to prevent damage to the
cabinet. See Figure 4 for additional
information.
Before lifting unit, be sure that all shipping
material has been removed from unit.
Secure hooks and cables at all lifting points/
lugs provided on the unit.
Hoist unit to a point directly above the curb
or mounting rail. Be sure that the gasket
material has been applied to the curb or
mounting rail.
Carefully lower and align unit with utility
and duct openings. Lower the unit until the
unit skirt fits around the curb. Make sure the
unit is properly seated on the curb and is
level.
Do not push, pull or lift the unit from
anything other than its base.
Figure 3 - Lifting Points
21
Figure 4 - Lifting Detail of a 45-75 ton Unit
Figure 5 - Lifting Detail of a 95-140 ton Unit
Lifting slot locations are unit specific.
Unit must be rigged at all marked lifting points.
22
Water Connection
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
The chiller must be operated only
with liquid flowing through the
evaporators.
WARNING
In order to prevent water leakage into
the roof curb, the factory provided
sheet metal flashings MUST BE
attached to the unit base to cover the
shipping slots at both ends of the
unit.
CAUTION
Installing Contractor is responsible
for proper sealing of the water piping
entries into the unit Failure to seal the
entries may result in damage to the
unit and property.
CAUTION
Connect the supply and return water lines.
The connection size is listed on the unit
rating sheet, along with the designed
volumetric flow rate. The maximum
operating pressure for AAON LN Series
units is 125 psi.
Mounting Isolation
For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Doors
Lockable access door is provided to the
compressor and control compartment. A
separate access door is also provided to the
pumping package compartment.
A light switch with service lights is provided
on the wall of the compressor and control
compartment.
End Flashing Installation
On all LN Series units the cabinet width will
overhang the shipping trailer on each side.
In order to secure and protect the unit during
transit the sheet metal end flashings have
been removed from the unit. The slot created
at the base of each end of the unit allows the
unit to set firmly on the trailer deck.
Sheet metal flashings are shipped loose with
the unit and once the unit is set into place
the flashings must be installed on each end
of the unit to complete the finished seal at
the base. The flashings are unit specific and
designed to cover the slot at each end of the
unit to prevent water run-off into the curb.
Failure to attach and seal the end of unit
with the flashings may result in water
leakage into the curb.
Figure 6 - Factory Supplied End Flashings
23
Low Ambient Operation
Electric shock hazard. Before
attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death, or property damage.
WARNING
Installing Contractor is responsible
for proper sealing of the electrical
and gas entries into the unit. Failure
to seal the entries may result in
damage to the unit and property.
CAUTION
If the chiller is ordered for a Low Ambient
application, the liquid system must use a
glycol solution and the piping must be
insulated to be prepared for freezing
conditions. Care must be taken in the source
of electrical power for the heating tape and
thermostat.
Electrical
The single point electrical power
connections are made in the electrical
control compartment.
The microprocessor control furnished with
the unit is supplied with its own power
supply factory wired to the main power of
the outdoor mechanical room.
Verify the unit nameplate voltage agrees
with the power supply. Connect power and
control field wiring as shown on the unit
specific wiring diagram provided with the
unit.
Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 167°F (75°C).
Route power and control wiring, separately,
through the utility entry. Do not run power
and signal wires in the same conduit.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Power wiring is to the unit terminal block or
main disconnect. All wiring beyond this
point has been done by the manufacturer and
cannot be modified without effecting the
unit's agency/safety certification.
Figure 7 - Front View of Utility Entry and
Power Switch from Control Compartment
Startup technician must check for proper
motor rotation and check fan motor
amperage listed on the motor nameplate is
not exceeded. Motor overload protection
24
may be a function of the variable frequency
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Condenser fan
motors should all be checked by a
qualified service technician at startup
and any wiring alteration should only
be made at the unit power
connection. Variable frequency drives
are programmed to automatically
rotate the fan in the correct rotation.
Do not rely on fans with variable
frequency drives for compressor
rotation.
CAUTION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CAUTION
drive and must not be bypassed.
Note: All units are factory wired for
208/230V, 460V, or 575V. If unit is to be
connected to a 208V supply, the transformer
must be rewired to 208V service. For 208V
service interchange the yellow and red
conductor on the low voltage control
transformer.
Red-Black for 208V
Yellow-Black for 230V
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 221°F (105°C)
type AWM insulated conductors.
25
Startup
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Improper installation, adjustment,
alteration, service, or maintenance
can cause property damage,
personal injury, or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician
WARNING
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. All motors, to
include and not be limited to pump
motors and condenser fan motors,
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
at the unit power connection.
CAUTION
Before completing installation, a
complete operating cycle should be
observed to verify that all
components are functioning properly.
(See back of the manual for startup form)
Before the startup of the chiller be sure that
the following items have been checked.
1. Verify that electrical power is available
to the unit.
2. Verify that any remote stop/start device
connected to the chiller controller is
requesting the chiller to start.
3. Verify that liquid flow is present through
the chiller from the building.
4. There should be a building load of at
least 25% of the chiller capacity in order
to properly check operation.
5. With the main power switch off, review
the MCS Controller Manual provided
with the chiller. Understand the keypad
functions, how to set the leaving water
temperature setpoint, and how to initiate
the Run State.
Use the general check list at the top of the
startup form to make a last check that all the
components are in place, water flow is
present, and the power supply is energized.
Using the controller keypad, individually set
the outputs in “Manual On” to confirm relay
closure and compressor operation.
Cycle through all the compressors to
confirm that all are operating within
tolerance.
While performing the check, use the startup
form to record observations of compressor
amps and refrigerant pressures.
When all is running properly, place the
controller in the Run mode and observe the
system until it reaches a steady state of
operation.
Note: For more information on
programming the controller refer to the
MCS Controller manual provided with the
chiller.
26
Axial Flow Condenser Fans
Bushing
Mount
A
B
Bushing
Mount
Bushing
Bushing
1
2
3
4
Multi-Wing Z Series Aluminum Fan Blade
Pitch Angle Setting Instructions
1.Maintain the balance of fan
Mark the hub castings across a joint, so the
fan hub can be reassembled in the same
orientation.
Mark the location of any balancing weight.
Balancing weight will be on the outer bolt
circle, in the form of washers, and/or longer
bolts, or an additional balancing nut.
Number the blades and blade sockets, so that
they are replaced into their original position.
Location A is with the bushing mount on air
inlet side of the fan.
Location B is with the bushing mount on air
discharge side of the fan.
Figure 9 - Bushing Mount Location
4. Determine the pin location groove
Disassemble fan on a flat surface and note in
which groove the pin is located.
Figure 8 - Fan with the HUB on the top and
RET on the bottom.
2. Determine the direction of rotation
Right, R, is clockwise when facing the
discharge side of the fan and Left, L, is
counterclockwise when facing the discharge
side of the fan.
3. Determine the bushing mount location
The bushing mount is the center section of
the hub through which the fan is mounted to
the shaft, and typically contains either
setscrews or a center-tapered hole where the
bushing inserts.
Figure 10 - RET with Pin in Groove 4
27
5. Determine whether the pin is in the HUB
Type
Bushing
Mount
Blade Pitch Angle
20°
25°
28°
30°
33°
35°
38°
40°
45°
50°
5Z
A
-
RET
-
RET
RET
RET
HUB
HUB
HUB
HUB B -
HUB
-
HUB
HUB
HUB
RET
RET
RET
RET
Type
Rot.
Blade Pitch Angle
20°
25°
28°
30°
33°
35°
38°
40°
45°
50°
5Z
R - 4 - 3 2 1 4 3 2 1 L - 1 - 2 3 4 1 2 3
4
or RET
Figure 11 - Fan HUB and RET Castings
6. Determine the current blade pitch and the pin location for the new blades
Table 3 - Return/Exhaust Fan Pin Location
Table 4 - Return/Exhaust Fan Pin Location
7. Replace fan blades in the new pin
location and reassemble the fan
Replace the blades with the pin in the 1, 2,
3, or 4 groove position of either the HUB or
RET. Assemble the fan making sure to place
the blades in their previous blade sockets, to
match up the previous orientation of HUB
and RET and to replace any balancing
weights in their previous locations. Tighten
bolts in a cross pattern to 5-6 ft-lbs. of
torque.
28
Multi-Wing W Series Black Glass
Bushing
Tightening Torque
(in-lbs.)
H X 1.125"
95
H X 1.375"
95
SH X 1.125"
108
SH X 1.375"
108
SD X 1.125"
108
SD X 1.375"
108
SD X 1.625"
108
SD X 1.875"
108
SK X 2.125"
180
Reinforced Polypropylene Fan Blade Pitch
Angle Setting Instructions
Contact the AAON parts department to
acquire the new pitch pins for the fan blades.
Note original position of retaining plates,
center boss and all hardware including
additional hardware used for balancing.
1. Remove all the bolts and nuts.
2. Determine blade rotation – on the
concave side of the blade is a blade marking
showing 6WR, 6WL, 7WL, 7WR, or 9WR.
The “L” and “R” denote the rotation of the
blade.
3. Replace the pitch insert in the blade root
with an insert of the desired pitch.
Figure 12 - Pitch Insert
4. Replace blades to their original location.
5. Replace all nuts, bolts, and washers on the
fan hub.
6. Replace retaining plates and center boss
to original location.
7. Tighten nuts and bolts to 14 ft-lbs of
torque.
Fan Assembly Bushings
The fan assembly bushings should be
tightened to the specifications listed in the
following table.
Table 5 - Fan Assembly Bushing Torque
Specifications
29
Maintenance
The Clean Air Act of 1990 bans the
intentional venting of refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery,
recycling or reclaiming must be
followed. Fines and/or incarceration
may be levied for non-compliance.
CAUTION
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
General
Qualified technicians must perform routine
service checks and maintenance. This
includes reading and recording the
condensing and suction pressures and
checking for normal sub-cooling and
superheat.
Air-cooled condenser units require
maintenance schedules/procedures. Unit
specific instructions are included in this
manual.
Compressors
The scroll compressors are fully hermetic
and require no maintenance except keeping
the shell clean.
Adjusting Refrigerant Charge
All AAON chillers are shipped with a full
factory charge. Periodically adjusting the
charge of a system may be required.
Adjusting the charge of a system in the field
must be based on determination of liquid
sub-cooling and evaporator superheat. On a
system with an expansion valve liquid subcooling is more representative of the charge
than evaporator superheat but both
measurements must be taken.
Before Charging
Refer to the unit nameplate as a reference
when determining the proper refrigerant
charge.
Unit being charged must be at or near full
load conditions before adjusting the charge.
Units equipped with hot gas bypass must
have the hot gas bypass valve closed to get
the proper charge.
After adding or removing charge the system
must be allowed to stabilize, typically 10-15
minutes, before making any other
adjustments.
The type of unit and options determine the
ranges for liquid sub-cooling and evaporator
superheat. Refer to Table 6 when
determining the proper sub-cooling.
For units equipped with low ambient (0°F)
option see the special charging instructions
at the end of this section.
Checking Liquid Sub-cooling
Measure the temperature of the liquid line as
it leaves the condenser coil.
Read the gauge pressure at the liquid line
close to the point where the temperature was
taken. You must use liquid line pressure as it
will vary from discharge pressure due to
condenser coil pressure drop.
30
Convert the pressure obtained to a saturated
Air-Cooled Condenser with Scroll
Compressors
Sub-Cooling
2
12-18°F
Superheat
1
10-15°F
Expansion valves must be adjusted
to approximately 10-15°F of suction
superheat. Failure to have sufficient
superheat will damage the
compressor and void the warranty.
CAUTION
DO NOT OVERCHARGE!
Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
CAUTION
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the measured liquid line
temperature from the saturated temperature
to determine the liquid sub-cooling.
Compare calculated sub-cooling to the table
below for the appropriate unit type and
options.
Checking Evaporator Superheat
Measure the temperature of the suction line
close to the compressor.
Read gauge pressure at the suction line close
to the compressor.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the saturated temperature from the
measured suction line temperature to
determine the evaporator superheat.
For refrigeration systems with tandem scroll
compressors, it is critical that the suction
superheat setpoint on the expansion valve is
set with one compressor running. The
suction superheat should be 10-13°F with
one compressor running. The suction
superheat will increase with both
compressors in a tandem running.
Inadequate suction superheat can allow
liquid refrigerant to return to the
compressors which will wash the oil out of
the compressor. Lack of oil lubrication will
destroy a compressor. Liquid sub-cooling
should be measured with both compressors
in a refrigeration system running.
Compare calculated superheat to Table 6 for
the appropriate unit type and options.
Table 6 - Acceptable Refrigeration Circuit
Values
1
One compressor running in tandem
2
Two compressors running in tandem
Adjusting Sub-cooling and Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator superheat is within the
temperature range as shown in Table 6 (high
superheat results in increased sub-cooling)
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
The system is undercharged if the superheat
is too high and the sub-cooling is too low.
31
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the expansion valve
may need adjustment to correct the
superheat.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
All original motors and bearings are
furnished with an original factory charge of
lubrication. Certain applications require
bearings be re-lubricated periodically. The
schedule will vary depending on operating
duty, temperature variations, or severe
atmospheric conditions.
Bearings should be re-lubricated at normal
operating temperatures, but not when
running.
Rotate the fan shaft by hand and add only
enough grease to purge the seals. DO NOT
OVERLUBRICATE.
Air-Cooled Condenser
The air-cooled condenser section rejects
heat by passing outdoor air over the fin tube
coils for cooling of the hot refrigerant gas
from the compressors. The heated air will
discharge from the top of the section
through the axial flow fans.
The condenser coils should be inspected
yearly to ensure unrestricted airflow. If the
installation has a large amount of airborne
dust or other material, the condenser coils
should be cleaned according to the
microchannel coil cleaning section.
Brazed Plate Heat Exchanger Cleaning
Because of a normally high degree of
turbulence in brazed plate heat exchangers,
for many applications the heat exchanger
channels are self-cleaning. For applications
that are not self-cleaning (i.e. hard water at
high temperatures, etc.) or applications
where additional cleaning is desired, it is
possible to clean the brazed plate heat
exchanger by circulating a cleaning liquid.
Use a tank with weak acid, 5% phosphoric
acid (H3PO4) or, if the exchanger is
frequently cleaned, 5% oxalic acid
(H2C2O4). Pump the cleaning liquid
through the exchanger. For optimum
cleaning, the cleaning solution flow rate
should be a minimum of 1.5 times the
normal flow rate, preferably in a back-flush
mode. After cleaning, the heat exchanger
must be rinsed with clean water. A solution
of 1-2% sodium hydroxide (NaOH) or
sodium bicarbonate (NaHCO) before the last
rinse ensures that all acid is neutralized.
E-Coated Coil Cleaning
Documented routine cleaning of e-coated
coils is required to maintain coating
warranty coverage.
Surface loaded fibers or dirt should be
removed prior to water rinse to prevent
restriction of airflow. If unable to back wash
the side of the coil opposite of the coils
entering air side, then surface loaded fibers
or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available,
a soft non-metallic bristle brush may be
used. In either case, the tool should be
applied in the direction of the fins. Coil
surfaces can be easily damaged (fin edges
bent over) if the tool is applied across the
fins.
Use of a water stream, such as a garden
hose, against a surface loaded coil will drive
the fibers and dirt into the coil. This will
make cleaning efforts more difficult. Surface
loaded fibers must be completely removed
prior to using low velocity clean water rinse.
34
A monthly clean water rinse is
Harsh chemicals, household bleach,
or acid cleaners should not be used
to clean outdoor or indoor e-coated
coils. These cleaners can be very
difficult to rinse out of the coil and
can accelerate corrosion and attack
the e-coating. If there is dirt below the
surface of the coil, use the
recommended coil cleaners.
High velocity water from a pressure
washer or compressed air should
only be used at a very low pressure
to prevent fin and/or coil damages.
The force of the water or air jet may
bend the fin edges and increase
airside pressure drop. Reduced unit
performance or nuisance unit
shutdowns may occur.
CAUTION
CAUTION
recommended for coils that are applied in
coastal or industrial environments to help to
remove chlorides, dirt, and debris. It is very
important when rinsing, that water
temperature is less than 130°F and pressure
is than 900 psig to avoid damaging the fin
edges. An elevated water temperature (not to
exceed 130°F) will reduce surface tension,
increasing the ability to remove chlorides
and dirt.
Quarterly cleaning is essential to extend
the life of an e-coated coil and is required
to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s
regularly scheduled maintenance
procedures. Failure to clean an e-coated coil
will void the warranty and may result in
reduced efficiency and durability.
For routine quarterly cleaning, first clean the
coil with the below approved coil
cleaner. After cleaning the coils with the
approved cleaning agent, use the approved
chloride remover to remove soluble salts and
revitalize the unit.
Recommended Coil Cleaner
The following cleaning agent, assuming it is
used in accordance with the manufacturer’s
directions on the container for proper mixing
and cleaning, has been approved for use on
e-coated coils to remove mold, mildew,
dust, soot, greasy residue, lint, and other
particulate:
Enviro-Coil Concentrate, Part Number HEC01.
Recommended Chloride Remover
CHLOR*RID DTS™ should be used to
remove soluble salts from the e-coated coil,
but the directions must be followed closely.
This product is not intended for use as a
degreaser. Any grease or oil film should first
be removed with the approved cleaning
agent.
Remove Barrier - Soluble salts adhere
themselves to the substrate. For the effective
use of this product, the product must be able
to come in contact with the salts. These salts
may be beneath any soils, grease or dirt;
therefore, these barriers must be removed
prior to application of this product. As in all
surface preparation, the best work yields the
best results.
Apply CHLOR*RID DTS - Apply directly
onto the substrate. Sufficient product must
be applied uniformly across the substrate to
thoroughly wet out surface, with no areas
missed. This may be accomplished by use of
a pump-up sprayer or conventional spray
gun. The method does not matter, as long as
35
the entire area to be cleaned is wetted. After
Batch-loading chemicals into the unit
is NOT PERMITTED. The control
system must regulate the chemical
feed.
WARNING
Detergents or coil cleaners are not
recommended with microchannel
condenser coils. Use pressurized
clean water, with pressure not to
exceed 140 psi. Nozzle should be 6”
and 80° to 90° from coil face. Failure
to do so could result in coil damage.
CAUTION
the substrate has been thoroughly wetted,
the salts will be soluble and is now only
necessary to rinse them off.
Rinse - It is highly recommended that a hose
be used, as a pressure washer will damage
the fins. The water to be used for the rinse is
recommended to be of potable quality,
though a lesser quality of water may be used
if a small amount of CHLOR*RID DTS is
added. Check with CHLOR*RID
International, Inc. for recommendations on
lesser quality rinse water.
Microchannel Coil Cleaning
Documented routine cleaning of
microchannel coils with factory provided ecoating is required to maintain coating
warranty coverage. See E-Coated Coil
Cleaning section.
Air-cooled heat exchangers may include
microchannel coils. Only clean water is
recommended for cleaning microchannel
coils. The water pressure used to clean
should not exceed 140 psi, from no closer
than 3 inches from the coils, and with the
water aimed perpendicular to the coils.
Only clean water is recommended for
cleaning microchannel coils. However, if
solutions are mandatory to clean the unit, a
cleaning solution with a pH between 5 and 9
that does not contain chlorides, sulfates,
copper, iron, nickel, or titanium is required.
Field installed coil coatings are not
recommended with microchannels.
Service
If the unit will not operate correctly and a
service company is required, only a
company with service technicians qualified
and experienced in both refrigerant chillers
and air conditioning are permitted to service
the systems to keep warranties in effect. If
assistance is required, the service technician
must contact AAON.
Replacement Parts
Parts for AAON equipment may be obtained
from your local AAON representative.
When ordering parts reference the unit serial
number and part number.
AAON Warranty, Service and Parts
Department
2424 S. Yukon Ave.
Tulsa, OK 74107
Ph: 918-583-2266
Fax: 918-382-6364
www.aaon.com
Note: Before calling, technician should have
model and serial number of the unit
available for the service department to help
answer questions regarding the unit
36
Appendix - Water Piping Component Information
Automatic Air Vent Valves
Automatic Air Vent Valves provide
automatic air venting for hot or cold water
distribution systems. These vents purge air
that may be in the water system.
The vent valve utilizes a float to actuate the
valve plug which is located at the top of the
valve. Once the air is displaced and the
system pressure is sustained, the valve plug
seals and prevents any water from escaping
from the system.
The float vent can also operate as an antivacuum device since it will permit air to
enter the system when it must be drained. It
can also be installed to permit the separation
and dispersal of air while fluid is actually
circulating in the system.
Overview
Body and cover are brass construction.
Air vent with silicone rubber seal.
Impurities do not usually affect function
as maximum float line of water is always
lower than the valve seal.
Float is high temperature resistant
polyethylene.
Suitable for use with glycol systems.
Can be disassembled for inspection and
cleaning.
Operating Range:
Minimum working pressure: 1.45psi (10
kPa)
Maximum working pressure: 150psi (10
bars)
Temperature Range: 33°F – 240°F (5°C –
116°C)
Performance
Performance curve details the quantity of air
vented by the “Float Vent” according to the
pressure in the system.
Note: In order to get the best results in
venting air from risers, use connecting pipes
37
of at least 1⁄2" diameter between the “Float
Vent” valves and installation.
Installation
When the air vent valve is installed as
shown, the air will not be vented while the
fluid is circulating in the system, but it can
vent when the system is shut off.
The figure below shows the installation of
the vent valve for the venting of air while
the fluid is circulating in the system and the
required increase in pipe size in order to
obtain proper separation of air from water.
The valve should be mounted only in a
vertical position as its operation is based on
the vertical movement of the float.
While the air vent valve is in operation, back
off the small vent cap two turns. This is the
proper operating setting which will allow air
to be vented from the system. It is advisable
to leave the cap on to prevent impurities
from entering the valve.
Maintenance
No maintenance is normally necessary.
However, if the FV-4M1 is disassembled for
inspection or cleaning it is important that
when re-assembling to ensure that the spring
loaded lever properly engages under the
float collar
38
Dimensions – Weights:
No Installation of this equipment
should take place unless this
document has been read and
understood.
CAUTION
Pumps - Installation and Operating
Instructions
Introduction
This document contains specific information
regarding the safe installation, operating,
and maintenance of Vertical In-Line pumps
and should be read and understood by
installing, operating, and maintenance
personnel. The equipment supplied has been
designed and constructed to be safe and
without risk to health and safety when
properly installed, operated, and maintained.
The instructions following must be strictly
adhered to. If clarification is needed on any
point please contact Armstrong quoting the
equipment serial number.
Where under normal operating conditions
the limit of 68°C/155°F (Restricted Zone)
for normal touch, or 80°C/176°F
(Unrestricted Zone) for unintentional touch,
may be experienced, steps should be taken
to minimize contact or warn operators/users
that normal operating conditions will be
exceeded. In certain cases where the
temperature of the pumped liquid exceeds
the above stated temperature levels, pump
casing temperatures may exceed
100°C/212°F and not withstanding pump
insulation techniques appropriate measures
must be taken to minimize risk for operating
personnel.
Storage
Pumps removed from service and stored,
must be properly prepared to prevent
excessive rusting. Pump port protection
plates must not be removed until the pump is
ready to connect to the piping. Rotate the
shaft periodically (At least monthly) to keep
39
rotating element free and bearings fully
Discharge valve only is to be used to
throttle pump flow.
Use Caution. Piping may carry high
temperature fluid.
CAUTION
CAUTION
functional.
For long term storage, the pump must be
placed in a vertical position in a dry
environment. Internal rusting can be
prevented by removing the plugs at the top
and bottom of the casing and drain or air
blow out all water to prevent rust buildup or
the possibility of freezing. Be sure to
reinstall the plugs when the unit is made
operational. Rust-proofing or packing the
casing with moisture absorbing material and
covering the flanges is acceptable. When
returning to service be sure to remove the
drying agent from the pump.
Handling Large VIL Units
One effective way of lifting a large pumping
unit is to place lifting hooks through the
motor lifting rings or straps around the
upper part of the motor. The pump and
motor unit will free-stand on the casing ribs.
Remove the coupling guard and place (2)
lifting straps through the pump/motor
pedestal, one on each side of the motor shaft
and secure to the lifting device.
With the straps in place, using a spacer bar if
necessary to protect the motor fan cover, the
whole assembly can now be lifted securely.
Note:Handling, transportation and
installation of this equipment should only be
undertaken by trained personnel with proper
use of lifting equipment.
Remove coupling guard and place lifting
straps on each side of coupling, use spacer
bar if necessary to protect motor fan cover.
Vertical Inline Pump Lifting Strap
Positioning:
Note: All split-coupled pumps contain a
tapped hole in the motor bracket above the
discharge flange for draining the well. Pipe
this drain hole to a floor drain to avoid
overflow of the cavity caused by collecting
chilled water condensate or from seal
failure.
Pump Piping - General
The discharge valve only is to be used to
throttle pump flow, not the suction valve.
Care must be taken in the suction line layout
and installation, as it is usually the major
source of concern in centrifugal pump
applications
40
Alignment
Do not run pumps with discharge
valve closed or under very low flow
conditions.
CAUTION
Check rotation arrow prior to
operating the unit.
CAUTION
Alignment is unnecessary on close-coupled
pumps as there is no shaft coupling.
Split-coupled units are accurately aligned at
the factory prior to being shipped and do not
need re-aligning when installed.
Pump Operation
Starting Pump
Ensure that the pump turns freely by hand,
or with some mechanical help such as a
strap and lever on larger pumps. Ensure that
all protective guarding is securely fixed in
position.
The pump must be fully primed on start up.
Fill the pump casing with liquid and rotate
the shaft by hand to remove any air trapped
in the impeller. On split coupled units, any
air trapped in the casing as the system is
filled must be removed by the manual air
vent in the seal flush line. Close-coupled
units are fitted with seal flush/vent lines
piped to the pump suction area. When these
units operate residual air is drawn out of the
pump towards the suction piping.
‘Bump’ or energize the motor momentarily
and check that the rotation corresponds with
the directional arrow on the pump casing. To
reverse rotation of a three phase motor,
interchange any two power leads.
Start the pump with the discharge valve
closed and the suction valve open, and then
gradually open the discharge valve when the
motor is at operating speed. The discharge
valve may be ‘cracked’ or open slightly at
start up to help eliminate trapped air.
When stopping the pump: Close the
discharge valve and de-energize the motor.
DO NOT run the pump against a closed
discharge valve for an extended period of
time. (A few minutes maximum)
Star-Delta motor starters should be fitted
with electronic/mechanical interlocks that
have a timed period of no more than 40
milliseconds before switching from star
(Starting) to delta (Run) connection yet
allow the motor to reach full star (Starting)
speed before switching to delta (Run).
Should the pump be noisy or vibrate on
start-up a common reason is overstated
system head. Check this by calculating the
pump operating head by deducting the
suction pressure gauge value from the
discharge gauge reading. Convert the result
into the units of the pump head as stated on
the pump nameplate and compare the
values. Should the actual pump operating
head be significantly less than the nameplate
head value it is typically permissible to
throttle the discharge isolation valve until
the actual operating head is equal to the
nameplate value.
Any noise or vibration usually disappears.
The system designer or operator should be
made aware of this soon as some adjustment
may be required to the pump impeller
diameter or drive settings, if applicable, to
make the pump suitable for the system as
installed.
41
Check rotation arrow prior to operating the
Electric shock hazard. Before
attempting to perform any service or
maintenance on pumping unit,
disconnect power source to the
driver, LOCK IT OFF and tag with the
reason.
WARNING
unit. The rotation of all Vertical In-Line
units is “clockwise” when viewed from the
drive end. (Looking from on top of / behind
the motor)
General Care
Vertical In-Line pumps are built to operate
without periodic maintenance, other than
motor lubrication on larger units. A
systematic inspection made at regular
intervals, will ensure years of trouble-free
operation, giving special attention to the
following:
Keep unit clean
Keep moisture, refuse, dust or other
loose particles away from the pump and
ventilating openings of the motor.
Avoid operating the unit in overheated
surroundings (Above 100ºF/40ºC).
Any possibility of the unit starting while
being serviced must be eliminated.
If mechanical seal environmental
accessories are installed, ensure water is
flowing through the sight flow indicator and
that filter cartridges are replaced as
recommended.
Pump Lubrication
Lubrication is not required. There are no
bearings in the pump that need external
lubrication service.
Large Series split-coupled units are installed
with a shaft bushing located beneath the
impeller that is lubricated from the pump
discharge. This bearing is field removable
for service on the 20x20x19 size without
disturbing the motor or other major pump
components.
Motor
Follow the lubrication procedures
recommended by the motor manufacturer.
Many small and medium sized motors are
permanently lubricated and need no added
lubrication. Generally if there are grease
fittings evident the motor needs periodic
lubrication, and if there are no grease fittings
evident, no periodic lubrication is required.
Check the lubrication instructions supplied
with the motor for the particular frame size
indicated on the motor nameplate.
Mechanical Seal
Mechanical seals require no special
attention. The mechanical seal is fitted with
a flush line. The seal is flushed from
discharge of the pump casing on splitcoupled pumps and is flushed/vented to the
suction on close coupled pumps.
The split-coupled pump is flushed from the
pump discharge because the mechanical seal
chamber is isolated from the liquid in the
pump by a throttle bushing. Because the seal
chamber is isolated, seal environmental
controls such as filters and separators, when
installed in the split-coupled flush line are
very effective, as only the seal chamber
needs cleansing, and will prolong seal life in
HVAC systems.
Do not run the pump unless properly filled
with water as the mechanical seals need a
film of liquid between the faces for proper
operation.
42
Mechanical seals may ‘weep’ slightly at
Double Check Prior to Startup
CAUTION
start-up. Allow the pump to continue
operating for several hours and the
mechanical seal to ‘seat’ properly prior to
calling for service personnel.
System Cleanliness
Before starting the pump the system must be
thoroughly cleaned, flushed and drained and
replenished with clean liquid.
Welding slag and other foreign materials,
“Stop Leak” and cleaning compounds and
improper or excessive water treatment are
all detrimental to the pump internals and
sealing arrangement.
Proper operation cannot be guaranteed if the
above conditions are not adhered to.
Note
Particular care must be taken to check the
following before the pump is put into
operation:
1. Pump primed?
2. Rotation OK?
3. Lubrication OK?
4. Pipe work properly supported?
5. Voltage supply OK?
6. Overload protection OK?
7. Is the system clean?
8. Is the area around the pump clean?
Warranty
Does not cover any damages to the
equipment resulting from failure to observe
the above precautions.
Noise Levels
Estimated Pumping Unit Sound Power Level, Decibels, A-Weighted, at 1 m (3 ft.) from unit.
43
Vibration Levels
Vertical In-Line pumps are designed to meet vibration levels set by Hydraulic Institute Standard
HI Pump Vibration 9.6.4. Standard levels are as detailed below:
Dual Pump Specific Information
Dual Pump Flapper Valve Operating
Instructions
This unit is fitted with internal valves to
allow isolation of one pump for service and
to automatically prevent recirculation of the
flow when only one pump is running.
Procedure for Parallel or Stand-By
Pumping
Discharge and suction valve stems should be
locked in the center position. This is
indicated by both locking handles in the
vertical position and the center pin of the
locking arms (4) locked by the handles. This
procedure allows the discharge flapper
valves to pivot freely and locks the suction
valve firmly in the center position.
Procedure for Isolation of One Side
1. Stop the pump to be serviced.
2. Close and lock the suction and discharge
valves: as per instructions below.
3. Ensure seal flush line interconnection
valve is closed and drain the isolated
casing.
4. Service isolated pump as required.
Procedure for Starting the Pump after
Servicing
1. Ensure serviced pump is fully re-
assembled including all seal flush lines
and drain plugs.
2. Fill the dry casing with system fluid by
opening the seal flush line
interconnecting valve and the air vent
fitting.
3. Allow the pressure to equalize in the two
casings, if necessary, by opening seal
flush line interconnected valve.
4. Unlock the discharge valve as per
instructions below.
5. Unlock the suction valve as per
instructions below.
NOTE: Keep hands and tools away from
locked suction valve arm, as the differential
pressure may cause the arm to rotate quickly
with force when unlocked.
6. Close the seal flush line interconnect
valve and restart pump.
Valve Operation - Refer to following 3”, 4”
& 6” valve illustration and the 8” valve
illustration.
44
Discharge Valve
Care should be taken when
performing procedures 3 and 4. Read
instructions carefully.
WARNING
This valve performs the dual function of
automatically sealing the discharge of the
inactive pump when one pump is running
and can manually be closed and locked to
isolate one pump for service.
Automatic Flapper Operation
In the flapper mode the two halves of the
discharge valve are free to pivot
independently under normal operating
conditions. The locking handle (3) should be
secured with the set screw (11) in the
vertical position with the center pin of the
locking arm (4) trapped by the locking
handle (3).
Manual Valve Locking
The locking feature of this valve is to ensure
a positive seal (leak proof) of the discharge
port on the pump to be serviced.
Note: Ensure the pump to be isolated is not
operating before attempting to release the
locking mechanism. Failure to do so may
result in injury to the operator and/or
damage to the pump.
Locking
1. Loosen discharge side set screw (11) to
release the locking handle (3).
2. Rotate the discharge side locking handle
(3) so that the handle points toward the
pump to be serviced and secure in the
horizontal position, using set screw (11).
This releases the discharge locking arm
(4).
3. Rotate discharge valve shaft (16)
towards the pump to be isolated. The
orientation of the shaft is indicated by
the center pin on the locking arm (4).
4. Raise the locking handle (3) so that the
cam on the base of the handle forces the
pin of the locking arm (4) towards the
pump to be isolated. The locking handle
(3) should be raised to between 45
degrees and the vertical position.
5. Tighten set screw (11) to lock the
locking handle (3) in position.
This handle should not be rotated past the
vertical position.
Note: Ensure the isolated pump is not
operating before attempting to release the
locking mechanism. Failure to do so may
result in injury to the operator and/or
damage the pump.
Unlocking
1. Open the interconnecting valve on the
seal flush line to pressurize the serviced
pump and vent air through bleeder valve
on series 4302
2. Close these valves once the pressure is
equalized and air removed.
3. Loosen set screw (11) and lower locking
handle (3) to the horizontal position,
secure with set screw (11).
4. Rotate valve to center position so that
the center pin of the locking arm (4)
locates in the recess on the locking
handle (3).
5. Loosen set screw (11) and raise locking
arm (3) to the vertical position, locking
the center pin in the locking arm recess,
secure with set screw (11).
Suction Valve
Manual Operation
The suction side valve is designed for use as
a manually operated isolation valve. This
valve is not designed to automatically pivot
as the discharge flappers do.
45
Locking
Care should be taken when
performing procedures 3 and 4. Read
instructions carefully.
WARNING
1. Loosen suction side set screw (11) to
release the locking handle (3).
2. Rotate the suction side locking handle
(3) so that the handle points towards the
pump to be serviced and secure in the
horizontal position, using set screw (11).
This releases the suction locking arm
(4).
Note: The locking handle (3) should only be
rotated towards the pump stopped for
service. The suction valve is designed to
prevent the locking handle (1) from rotating
towards the running pump, as the suction of
the running pump could cause the valve to
slam shut with sufficient force to injure the
operator and/or cause damage to the pump.
Do not attempt to circumvent this safety
feature.
3. Rotate the suction valve towards the
pump to be isolated. The orientation of
the shaft is indicated by the center pin on
the locking arm (4).
4. Loosen set screw (11) and raise the
locking handle (3) so that the cam on the
base on the handle forces the pin of the
locking arm (4) towards the pump to be
isolated. The locking handle (3) should
be raised to between 45 degrees and the
vertical position.
This handle should not be rotated past the
vertical position.
5. Tighten set screw (11) to secure the
locking handle (3) in position.
Unlocking
1. Open the interconnecting valve on the
seal flush line to pressurize the serviced
pump and vent air through bleeder valve
on series 4302. Close these valves once
the pressure is equalized and air
removed.
2. Loosen set screw (11) and lower locking
handle (3) to the horizontal position,
secure with set screw (11).
NOTE: Keep hands and tools away from
suction valve locking arm when freed by
locking handle as differential pressure may
cause arm to rotate quickly with force when
unlocked.
3. Rotate valve to center position so that
the center pin of the locking arm (4) is
located in the recess on the locking
handle (3).
4. Loosen set screw (11) and raise locking
arm (3) to the vertical position, locking
the center pin in the locking arm recess,
secure with set screw.
46
47
48
Suction Guides
Introduction
Suction Guides are designed for bolting
directly onto the suction flange of horizontal
or vertical shaft centrifugal pumps.
Operating Limits
The suction guide is designed to be a fourfunction fitting. Each Suction Guide is a 90º
elbow, a Pipe Strainer and a Flow Stabilizer.
It may also be used as a Reducing Elbow,
should the suction piping be larger than the
pump inlet.
Installation
The Suction Guides may be installed in any
arrangement feasible the arrangement of the
pump flange bolt-holes.
Inspection
Suction Guides are thoroughly tested and
inspected before shipment to assure they
meet with your order requirements. All units
must be carefully examined upon arrival for
possible damage during transit. Any
evidence of mishandling should be reported
immediately to the carrier and noted on the
freight bill.
Operation
No special attention need be paid to the
Suction Guide at start-up. The fitting is
stationary and will strain the pumped fluid
and stabilize the flow into the pump
automatically.
Temporary strainer must be removed
following system clean up.
After all debris has been removed from the
system, or a maximum of 24 running hours,
stop the pump and close the pump isolation
valves. Drain the Suction Guide by
removing the drain plug or opening the
blowdown valve, if installed
Remove the Suction Guide cover and
remove the strainer assembly from the valve
body.
A temporary fine-mesh start-up strainer is
tack-welded to the permanent stainless steel
strainer. This temporary strainer should now
be removed from the permanent strainer.
The fine-mesh strainer is designed to
remove small particulate from new piping
49
systems and could easily clog with debris if
Table A1. Armgrip Flange Adapter Details
Valve Size
125 psi/150 psi
250 psi/300 psi
Ductile Iron Bolt
Ductile Iron Bolt
No.
Size
No.
Size
2-1/2
4
5/8 8 3/4 3 4
5/8 8 3/4 4 8
5/8 8 3/4 5 8
3/4 8 3/4 6 8
3/4
12
3/4 8 8
3/4
12
7/8
10
12
7/8
16 1 12
12
7/8
16
1-1/8
left in place. This will be detrimental to the
operation of the pump.
Inspect the cover O-ring and replace if
necessary.
Replace the permanent strainer into the
fitting body, once the temporary strainer is
removed.
Replace the cover into the body. Ensuring
that the strainer is properly seated, tighten
the cover bolts diagonally, evenly and
firmly.
Flo-Trex Combination Valve
Introduction
The Flo-Trex combination valves are
designed for installation on the discharge
side of centrifugal pumps, and incorporate
three functions in one valve:
1. Drip-tight shut-off valve
2. Spring closure design, Non-slam check
valve
3. Flow throttling valve
Armgrip Flange Adapter Installation
1. Position the two halves of the Armgrip
flange adapter on the valve body
ensuring that the lugs on each half of the
flange adapters are located between the
anti-rotation lugs on the valve body (as
shown).
Insert two bolts of specified size (Table A1)
to secure the halves of the flange adapter to
the valve body (as shown).
50
The gasket cavity should face out to the
Safety glasses should be worn.
Probes should not be left inserted
into fittings for long periods of time as
leakage may result.
CAUTION
adjoining flange.
2. Lubricate the inner and outer diameter of
the gasket with the lubricant provided or
a similar non-petroleum based water
soluble grease.
3. Press the gasket firmly into the flange
cavity ensuring that the sealing lip is
pointed outward. When in place, the
gasket should not extend beyond the end
of the pipe (as shown).
4. Position the adjoining flange or the pipe
to the Armgrip flange adapter and install
the remaining bolts. The two locking
bolts should be tightened first in order to
position the flange correctly.
Note: Care should be taken to ensure that
the gasket is not pinched or bent between
flanges.
5. Tighten remaining nuts evenly by
following bolting instructions, so that the
flange faces remain parallel (as shown in
the figure labeled Recommended Bolt
Tightening Procedure). Flange bolts
should be tightened to 70 ft-lbs torque
minimum to assure firm metal to metal
contact. When raised face flanges are
sued, there will be a gap between the
faces of the outer diameter.
6. Flange gaskets are not interchangeable
with other mechanical pipe couplings or
flange gaskets.
Recommended Bolt Tightening Procedure
Field Conversion (Straight to Angle
Pattern Valve:
1. Open valve at least one complete turn.
2. Remove the body bolts from valve body
using Allen Key
3. Rotate one half of the valve body 180°
making sure the lower valve seat and O
ring stay in position. Inspect the O ring
for any cuts or nicks and replace if
necessary.
4. Replace body bolts and torque evenly to
70 ft-lbs.
Flow Measurement with the valve in the
Wide Open position
Where approximate indication of flow is
acceptable the Flo-Trex valve can be used.
Step 1. Measure and record the differential
pressure across the valve.
51
Step 2. With valve in fully open position,
Valve Size
2-1/2
3 4 5 6 8
10
12
Number of
Rings
5 5 6 9 10
12
18
28
(valve fully
open)
100
34) x (400
100
34) x (25.2
locate the differential pressure on the
Performance curve, and for the given valve
size in use, read the corresponding flow rate.
Flow Measurement with the valve in the
throttled position
Step 1. The valve stem with its grooved
rings and positioning sleeve is the flow
indicator scale for the throttled position of
the valve.
The quarter turn graduations on the sleeve,
with the scribed line on the stem provide an
approximate flow measurement.
Note: The valve is shipped in closed
position. The indicator on the plastic
sleeve is aligned with the vertical scribed
line on the stem.
Step 2. Record the size of the valve and
stem position using the flow indicator scale.
Calculate the percentage of valve opening
based on the number of rings at the fully
open position.
Step 3. Measure and record the differential
pressure across the valve in the throttled
position.
Step 4. Locate percentage of valve opening
on the flow characteristic curve. For the
given valve, record the percentage of
maximum flow rate.
Step 5. Locate the differential pressure
determined for the valve in the throttled
position on the Flo-Trex Performance
Curve. Determine the flow rate for the
given valve size at this differential pressure.
Step 6. Calculate the flow rate of the valve
in the throttled position by multiplying the
flow rate (Step 5) by the percentage of
maximum flow rate (Step 4).
Example:
Valve size: 4 in.
Differential pressure is 5.4 ft
Number of open rings is 3.
From the table, the number of rings for the 4
in valve fully open is 6.
Divide open rings by total, 3/6 = 50%
throttled.
From the Flo-Trex performance curve, a 4
in. valve with 5.4 ft of pressure drop
represents a flow of 400 USgpm
From the flow characteristic curve, a 4 inch
valve at 50% open represents 34% of
maximum flow.
The approximate flow of a 4 inch valve with
a 5.4 ft pressure drop when 50% throttled is:
=136 USgpm
=8.57 L/s
52
Note:To prevent premature valve failure
Safety glasses should be worn.
CAUTION
it is not recommended that the valve
operate in the throttled position with
more than 25 ft pressure differential.
Instead the pump impeller should be
trimmed or valves located elsewhere in
the system to partially throttle the flow.
Operation
To assure tight shut-off, the valve must be
closed using a wrench with 25 to 30 ft-lbs of
torque.
To assure trouble free check valve operation
and shut-off operation, the valve should be
periodically opened and closed to keep valve
seat and valve disc guide stem free of
buildup of system contaminants.
Repacking of Flo-Trex valve under full
system pressure
If it is necessary, the stem O ring can be
changed under full system pressure.
‘’
Step1. Record the valve setting.
Step 2. Turn the valve stem
counterclockwise until the valve is fully
open and will not turn any further. Torque
to a maximum of 45 ft-lbs. This will ensure
good metal to metal contact and minimal
leakage.
Step 3. The valve bonnet may now be
removed. There may be a slight leakage, as
the metal to metal backseating does not
provide a drip-tight seal.
Step 4. Clean exposed portion of valve stem
being careful not to leave scratches.
Step 5. Remove and replace the O ring
gasket.
Step 6. Install the valve bonnet.
Step 7. Tightening the valve bonnet is
necessary to stop any leaks.
Step 8. Open valve to balance set point as
recorded in Step 1.
Note: On valve sizes of 2-1/2 inch and 3
inch, the full open position is 5 turns,
though the valve will open to 5-1/2 turns
which is just back of seating of valve.
Seat Replacement
Step 1. Drain the system and remove valve
from piping.
Step 2. Remove the body bolts from the
body using an Allen Key.
Step 3. Remove seat and O Ring. O rings
are not used on valves of 8 inches or larger.
Step 4. Inspect and clean O ring cavity and
install new O ring and seat. Valve disc stem
should be inspected and replaced if worn.
Valve stem O ring should be replaced at this
time as discussed under Repacking of FloTrex section.
Installing contractor should verify the following items.
1. Is there any visible shipping damage?
Yes No
2. Is the unit level?
Yes No
3. Are the unit clearances adequate for service and operation?
Yes No
4. Do all access doors open freely and are the handles operational?
Yes No
5. Have all shipping braces been removed?
Yes No
6. Have all electrical connections been tested for tightness?
Yes No
7. Does the electrical service correspond to the unit nameplate?
Yes No
8. On 208/230V units, has transformer tap been checked?
Yes No
9. Has overcurrent protection been installed to match the unit nameplate
requirement?
Yes No
10. Have all set screws on the fans been tightened?
Yes No
11. Do all fans rotate freely?
Yes No
12. Does the field water piping to the unit appear to be correct per design
parameters?
Yes No
Ambient Dry Bulb Temperature ________°F
Ambient Wet Bulb Temperature ________°F
Pre Startup Checklist
LN Series Startup Form
Ambient Temperature
55
Water/Glycol System
1. Has the entire system been flushed and pressure checked?
Yes No
2. Have isolation valves to the chiller been installed?
Yes No
3. Has the entire system been filled with fluid?
Yes No
4. Has air been bled from the heat exchangers and piping?
Yes No
5. Is there a minimum load of 50% of the design load?
Yes No
6. Has the water piping been insulated?
Yes No
7. Is the glycol the proper type and concentration (N/A if water)?
Yes No
8. What is the freeze point of the glycol (N/A if water)? ______________________________
Air-Cooled Condenser
Low Ambient Control
Condenser Safety Check
No Water Leaks
Water Flow ________ gpm
Chilled Water In Temperature ________°F
Chilled Water Out Temperature ________°F
Check Rotation
Number
Model #
L1
L2
L3
Head
Pressure
PSIG
Suction
Pressure
PSIG
Crankcase
Heater
Amps
1 2 3 4
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Chiller Configuration
Compressors/DX Cooling
Refrigeration System 1 - Cooling Mode
Refrigeration System 2 - Cooling Mode
56
Condenser Fans
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
2
3
4
5
6
7
8
hp
L1
L2
L3
Flow (gpm)
Chiller Building Pump #1
Chiller Building Pump #2
Pumping Package
57
Maintenance Log
Entry Date
Action Taken
Name/Tel.
This log must be kept with the unit. It is the responsibility of the owner and/or
maintenance/service contractor to document any service, repair or adjustments. AAON Service
and Warranty Departments are available to advise and provide phone help for proper operation
and replacement parts. The responsibility for proper start-up, maintenance and servicing of the
equipment falls to the owner and qualified licensed technician.
Literature Change History
February 2014
Initial version.
59
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
LN Series
Installation, Operation, &
Maintenance
V28980 · Rev. A · 140225
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.