Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
electrical power to the furnace.
More than one disconnect may be
provided.
When servicing controls, label all
wires prior to disconnecting.
Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with
key-lock or nut and bolt.
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections
and shut off valves.
8
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
9
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
CAUTION
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
To prevent damage to the unit, do not
use acidic chemical coil cleaners.
Use alkaline chemical coil cleaners
with a pH value of 5-9, after mixing,
without first using an aluminum
corrosion inhibitor in the cleaning
solution.
CAUTION
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
WARNING
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
CAUTION
10
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
1. Startup and service must be performed
by a Factory Trained Service Technician
2. The unit is for outdoor use only. See
General Information section for more
information.
3. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
045 = 45 ton Capacity
055 = 55 ton Capacity
060 = 60 ton Capacity
075 = 75 ton Capacity
095 = 95 ton Capacity
105 = 105 ton Capacity
120 = 120 ton Capacity
140 = 140 ton Capacity
SERIES
A = 45-60 ton units
B = 75 ton unit
C = 95-140 ton units
F = R-410A Tandem VFD Compatible Scroll
Compressor
A2: CONDENSER STYLE
A = Air-Cooled Microchannel Condenser
A3: EVAPORATOR CONFIGURATION
A = Standard Brazed Plate Constant Flow
B = Oversized Brazed Plate Constant Flow
C = Standard Shell & Tube Constant Flow
D = Oversized Shell & Tube Constant Flow
A4: COATING
0 = Standard
E = Polymer E-Coated Condenser Coil
A5: STAGING
0 = Staged Compressors
E = All Circuits with Variable Capacity Compressors
- 2 Circuits
G = Half Circuits with Variable Capacity
Compressors - 2 Circuits
B1: BLANK
0 = Standard
B2: BLANK
0 = Standard
B3: BLANK
0 = Standard
B4: BLANK
0 = Standard
UNIT FEATURE OPTIONS
1: UNIT ORIENTATION
A = Standard Access Left Water Connections
B = Standard Access Right Water Connections
C = Standard Access Bottom Water Connections
2: PUMPING STYLE
0 = No Pumps
B = Constant Flow Primary Pumping System - Large
Pipe Size
D = Variable Flow Primary Pumping System - Large
Pipe Size
12
LN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D 6 7 8A
8B
8C 9
10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – F A C 0 E – 0 0 0 0 : A 0 – 000 0 – 0 0 0 0 – 0 0 0 0 – 0 0 – 0 0 0 – 0 – 0 E 0 0 –
0 = No Building Pumps
A = 1 Pump + High Eff Motor
B = 1 Dual Pump + High Eff Motors
D = 1 Pump + VFD + High Eff Motor
E = 1 Dual Pump + 2 VFD's + High Eff Motors
K = 1 Pump + Field Installed VFD + High Eff Motor
L = 1 Dual Pump + 2 Field Installed VFD's + High
Eff Motors
3B: BUILDING PUMP SERIES AND RPM
0 = No Building Pumps
A = 4360 (1,170 nominal rpm)
B = 4360 (1,760 nominal rpm)
C = 4360 (3,520 nominal rpm)
D = 4380 (1,170 nominal rpm)
E = 4380 (1,760 nominal rpm)
F = 4380 (3,520 nominal rpm)
K = 4382 (1,170 nominal rpm)
L = 4382 (1,760 nominal rpm)
M = 4382 (3,520 nominal rpm)
3C: PUMP SIZE
0 = No Building Pumps
A = 1.5B
B = 2B
C = 2D
D = 3D
E = 1.5x1.5x6
F = 2x2x6
G = 3x3x6
H = 4x4x6
J = 6x6x6
K = 1.5x1.5x8
L = 2x2x8
M = 3x3x8
N = 4x4x8
P= 5x5x8
Q = 6x6x8
R = 8x8x8
S = 2x2x10
T = 3x3x10
U = 4x4x10
V = 6x6x10
W = 8x8x10
Y = 4x4x11.5
Z = 5x5x11.5
1 = 6x6x11.5
2 = 8x8x11.5
3 = 4x4x13
4 = 6x6x13
5 = 8x8x13
13
LN Series Feature String Nomenclature
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2 3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6 7 8A
8B
8C
9 10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – F A C 0 E – 0 0 0 0 : A 0 – 0 0 0 0 – 0000 – 0000 – 00 – 000 – 0 – 0E0 0 -
0 = None
A = BACnet IP
B = BACnet MSTP
C = Modbus IP
D = Modbus RTU
E = Lontalk
H = No BMS Connection with Diagnostics
J = BACnet IP with Diagnostics
K = BACnet MSTP with Diagnostics
L = Modbus IP with Diagnostics
M = Modbus RTU with Diagnostics
N = Lontalk with Diagnostics
11: BLANK
0 = Standard
12: VESTIBULE ACCESSORIES
0 = Standard
C = Vestibule Heating (Electric)
13: MAINTENANCE ACCESSORIES
0 = Standard
A = 115VAC Convenience Outlet Factory Wired
B = 115VAC Convenience Outlet Field Wired
C = Service Lights
F = Options A + C
J = Options B + C
14: BLANK
0 = Standard
15: CODE OPTIONS
0 = Standard ETL U.S.A. Listing
A = Chicago Code
B = ETL U.S.A. + Canada Listing
16: SHIPPING SPLITS
0 = One Piece Unit
17: AIR-COOLED CONDENSER
ACCESSORIES
H = Cond Coil Guards + Three Phase Cond Fan
Motor + Fan Cycling- 25°F Low Ambient
J = Cond Coil Guards + VFD Cond Fan Head
Pressure Control - 0°F Low Ambient
18: BLANK
0 = Standard
19: BLANK
0 = Standard
20: BLANK
0 = Standard
21: BLANK
0 = Standard
22: BLANK
0 = Standard
23: BLANK
0 = Standard
24: CHILLER ACCESSORIES 1
0 = Standard
A = Glycol Chiller
C = Thermometers & Pressure Gauges
G = Option A + C
25: BLANK
0 = Standard
26A: BLANK
0 = Standard
26B: BLANK
0 = Standard
26C: BLANK
0 = Standard
15
LN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV
SIZE SERIES
MNREV VLT
A1
A2
A3
A4
A5
B1
B2
B3
B4 1 2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D 6 7 8A
8B
8C 9
10A
10B
10C
10D
LN A – 140 – C – 0 – 3 – F A C 0 E – 0 0 0 0 : A 0 – 0 0 0 0 – 0 0 0 0 – 0 0 0 0 – 0 0 – 0 0 0 – 0 – 0 E 0 0 –
0 = Standard Warranty
D = Compressor Warranty Years 2-5
34: CABINET MATERIAL
0 = Standard - Double Wall + R-13 Foam Insulation
35: PAINT & SPECIAL PRICING
AUTHORIZATIONS
B = Premium AAON Gray Paint Exterior
E = Premium AAON Gray Paint Exterior + Shrink
Wrap
X = Special Pricing Authorization + Premium AAON
Gray Paint Exterior
1 = SPA + Premium AAON Gray Paint Exterior +
Shrink Wrap
4 = Special Pricing Authorization + Special Exterior
Paint Color
7 = SPA + Special Exterior Paint Color + Shrink
Wrap
16
General Information
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with
equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
AAON LN Series chillers are complete selfcontained liquid chilling units. They are
assembled, wired, charged and run-tested.
Models are available for air-cooled
applications. Chiller primary pumping
packages are available as optional features.
Codes and Ordinances
LN Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of LN Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
17
Chiller
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. All motors, to
include and not be limited to pump
motors and condenser fan motors,
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
at the unit power connection.
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CRANKCASE HEATER
OPERATION
Units may be equipped with
compressor crankcase heaters,
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the
warranty.
Never turn off the main power supply to the
unit, except for complete shutdown. When
power is cut off from the unit, any
compressors using crankcase heaters cannot
prevent refrigerant migration. This means
the compressor will cool down, and liquid
refrigerant may accumulate in the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored if liquid enters the
compressor.
Before unit operation, the main power
switch must be turned on for at least 24
hours for units with compressor crankcase
heaters. This will give the crankcase heater
time to clear any liquid accumulation out of
the compressor before it is required to run.
Never cut off the main power supply to the
unit, except for complete shutdown. Always
control the system from the building
management system, or control panel, never
at the main power supply (except for
emergency or for complete shutdown of the
system).
18
Scroll compressors must be on a minimum
of 5 minutes and off for a minimum of 5
minutes. The cycle rate must be no more
than 6 starts per hour.
The chiller is furnished with a pressure
differential switch that is factory installed
between the chilled water supply and return
connections. This sensor must not be
bypassed since it provides a signal to the
unit controller that water flow is present in
the heat exchanger and the unit can operate
without the danger of freezing the liquid.
Compressor life will be seriously shortened
by reduced lubrication, and the pumping of
excessive amounts of liquid oil and liquid
refrigerant.
Wiring Diagrams
A complete set of unit specific wiring
diagrams in both ladder and point-to-point
form are laminated in plastic and located
inside the control compartment door.
General Maintenance
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the chiller. This
includes reading and recording suction
pressures and checking for normal subcooling and superheat. See the air-cooled
condenser sections in this manual for
specific details.
Chiller Primary Pumping
Primary pumping uses a single pump to
move water (or glycol) through the chiller
barrel and back to the building. This
pumping package provides a constant flow
of water to the system. The pump is
activated whenever the chiller is given a run
signal.
Water enters the unit through the return
water piping, and then travels through an air
separator to remove any air that is entrapped
in the water. Following this, the water flows
through a suction guide with strainer. The
end of the suction guide is removable for
strainer access. The strainer assembly is
composed of two parts, the operational
strainer and the startup strainer, (located
inside the operational strainer) which is to
be removed 24 hours after startup.
The pump is installed after the suction
guide, and before a combination valve (FloTrex). This combination valve acts as
isolation valve, check valve, and flow
balancing valve. The shell and tube or
brazed plate evaporator, is placed after the
combination valve in the water circuit, with
a differential pressure switch installed across
its inlet and outlet. This pressure switch
closes when the differential pressure
increases above the setpoint, which should
be set 1-2 psig below the pressure drop
across the heat exchanger at design flow
rate. The closing differential pressure switch
signals the control system to indicate flow
through the heat exchanger and allow
cooling to activate as required to maintain
the setpoint. The water exiting the shell and
tube or brazed plate evaporator, leaves the
unit through the water out connection.
Automatic Air Vent
There is an automatic air vent installed at the
high point of the system inside the pumping
package compartment. The air vent valve
must be in the proper position for operation.
Ensure that the small vent cap is loosened
two turns from the closed position, allowing
air to be vented from the system. It is
advisable to leave the cap on to prevent
impurities from entering the valve. See
appendix for additional information.
19
Dual Pumps
When redundant pumping is required,
factory installed dual pumps can be ordered.
A dual pump is a pump with two
independent motors and pumps in a single
casing. This dual pump has a swing splitflapper valve in the discharge port to prevent
liquid recirculation when only one pump is
operating. Isolation valves in the casing
allow one pump to be isolated and removed
for service while the other pump is still
operating.
The controls package will activate the pump
when the unit is given a run command. If the
controls do not recognize flow in 60
seconds, the second pump will be activated
and an alarm signal will be generated. If the
second pump does not activate, the cooling
will be locked out. See appendix for
additional information.
Pressure Gauges and Thermometers
Pressure gauges and thermometers are
available as a factory installed option.
Thermometers are installed on the inlet and
outlet of the unit. One pressure gauge is
installed at each pump. This pressure gauge
is connected in three places to the water
piping before the suction guide/strainer,
after the suction guide and before the pump,
and after the pump. There is also a needle
valve at each of these points to isolate the
pressure. To measure the pressure at any
given point, open the needle valve at that
point and close the other two needle valves.
One gauge is used so that the calibration of
the pressure gauge is irrelevant in the
calculation of the differential pressure.
Pipe Insulation
The water piping and components on units
with pumping packages are not insulated at
the factory. Insulation should be installed on
the water piping after the system has been
checked for leaks.
20
Installation
Location
Unit Size
45-140 tons
Front -
(Controls Side)
72”
Back
72”
Ends
96”
Top
Unobstructed
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
CAUTION
Chiller Placement
The AAON LN Series is designed for
outdoor applications and mounting at
ground level or on a rooftop. It must be
placed on a level and solid foundation that
has been prepared to support its weight.
The placement relative to the building air
intakes and other structures must be
carefully selected. Be sure to observe the
dimensions that are on the rating plate of the
chiller for operational and service
clearances.
Table 1 - Service Clearances
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate
area around condenser must remain free of
debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb and Steel Mount Installation
Make openings in the roof decking large
enough to allow for water piping, electrical
penetrations, and workspace only. Do not
make openings larger than necessary. Set the
curb to coincide with the openings. Make
sure curb is level.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation
details.
Units require rail support along all four sides
of the unit base.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line. Care must
also be taken to protect the coil and fins
from damage due to vandalism or other
causes.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used
between the curb and the unit to reduce
vibration from the unit to the building.
Figure 1 - Curb Mounting with Dimensions
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.