AAON HB-005 User Manual

B
H
Package Units & Air Handlers
R-410A DX or Chilled Water Cooling
Gas, Electric or Hot Water Heat
Bottom or Side Discharge
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
EXTINGUISH ANY OPEN FLAME
DO NOT TOUCH ANY ELECTRICAL SWITCH
DO NOT TRY TO LIGHT ANY APPLIANCE
DO NOT USE ANY PHONE IN YOUR BUILDING
IMMEDIATELY CALL YOUR GAS SUPPLIER
FROM A NEIGHBOR’S PHONE. FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS.
IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
Installation and User Manual
R-410A Package
Air Handler
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
Owner should pay particular attention to the words: NOTE, CAUTION, and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage.
Contents
WARNINGS are given to alert owner that personal injury and/or equipment damage may result if installation
is not handled properly.
1. Description ………………………………... 3
Important Safety Information Package Unit Orientation Air Handling Unit Orientation
2. Model Number Description ....………….. 6
Unit Model Number
3. User’s Information ……….....…………… 7
DX Cooling Units (and Remote Cond. Units) Hydronic Cooling & Heating Gas or Electric Heating Filter Sizes Multiple Unit Operation Wiring Diagrams Condensate Piping Normal Thermostat Operation Night and Vacancy Operation Gas Heating System Hot Gas Reheat & Hot Gas Bypass System Filter Sizes Cabinet Construction
4. Delivery ……………………………………. 10
Receipt & Inspection Storage
5. Installation ………………………………… 10
General Codes & Ordinances Handling Heating and Cooling Systems Service & Installation Clearances Setting the Unit Electrical Standard Control Board Optional Control Board Optional Control Board
Table Index: Figure Index
4.1
5.1
9.1
16.1
16.2
16.3
21.1
21.2
27.1
Package Unit Dimensions AHU Dimensions Filter Sizes Blink Codes: Standard Board Blink Codes: Optional Board Low Voltage Wiring Sizes Minimum Gas Piping Sizes Gas Piping Support Intervals Filter Sizes
4a 5a 7a 8a 9a
9b 12a 12b 12c
Thermostat
6. Start-Up …………………………….. 23
7. Operation & Maintenance ……….. 26
8. Hot Gas Bypass (External) …..….. 28
9. Hot Gas Reheat (Modulating) …... 28
10. Pressure-Temperature Chart …… 31
Economizer Option Return Air Bypass Option Modulating Hot Gas Reheat Gas Piping Condensate Piping
General Procedures Air Balancing Water Balancing Controls
General Maintenance Schedule Cooling Condenser Fan Blower Assembly Heating Sequence Chilled Water Filters Cleaning Service
Pkg. Unit Orientation AHU Orientation Piping Chase Location Heat Exchangers MHGRH+HGBP System Foam Panel (HPCP) Service Clearances Airflow Clearances Other Clearances
2
13a 14a 15a 18a 20a 22a 26a 27a 28a
Removing Shipping Brackets Lifting Lugs and Outside Air Hood Power and Control Wiring External Control Inputs to Control Board Reheated Supply Air Temperature Gas Piping Blower Section Filter Section Hot Gas Reheat System
1. Description
Important Safety Information
ONLY QUALIFIED PERSONNEL SHOULD PERFORM INSTALLATION, OPERATION, AND MAINTENANCE OF EQUIPMENT DESCRIBED IN THIS MANUAL.
HB series package units are designed for safe operation when installed, operated, and maintained within design specifications, and the instructions set forth in this manual. It is necessary to follow these instructions to avoid personal injury or damage to equipment or property during equipment installation, operation, and maintenance.
This equipment is protected by a standard limited warranty under the condition that initial installation, service, and maintenance is performed according to the instructions set forth in this manual. This manual should be read in its entirety prior to installation, and before performing any service or maintenance work.
Units described in this manual are available with many optional accessories. If you have questions after reading this manual in its entirety, consult other factory documentation, or contact your sales representative to obtain further information before manipulating this equipment, or its optional accessories.
IMPORTANT!
WARNING
RISK OF DAMAGE, INJURY, AND LOSS OF LIFE
- Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, or loss of life. A qualified installer or service agency must perform installation and service.
NOTE
RISK OF ELECTRICAL SHOCK ­Before attempting to perform any service or maintenance, turn the electrical power to the unit OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
RISK OF INJURY FROM MOVING PARTS ­Disconnect all power before servicing to prevent serious injury resulting from automatic starts. Unit may have multiple power supplies.
WARNING
WARNING
ON 3 PHASE UNITS ONLY - Scroll compressors will be damaged by operation with the wrong rotation. THE LOW PRESSURE SWITCH HAS BEEN DISCONNECTED AFTER TESTING AT THE FACTORY. The wiring must be reconnected and proper rotation determined at the time of start­up by a qualified service technician using suction and discharge pressure gauges. Any alteration should only be made at the unit power connection.
This equipment uses R-410A only, and operates at higher pressures than standard R-22 systems. Do not use R-22 service equipment or tools on R­410A systems. Improper use or service may result in injuries from parts under high pressure.
WARNING
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non­compliance.
WARNING
3
Package Unit Orientation (Compressorized)
Service access is from the front of the unit. As you face the front of the unit, the condensing section will be on
the right end of the unit, and the air handling section on the left. The drain connection is located on the back.
Figure 4a, Package Unit Orientation
Return /
Outside Air /
Economizer
Section
Filter
Section
Controls
Section
Evaporator
Section
Supply Air
Section
Heating Section
Forklift
Openings
Table 4.1, Package Unit Dimensions
Model Width Length Height
002 - 005 42.25” 74.25” (93.25”)* 38”
*If present, the outside air hood will increase the overall installed unit length by 19” for a total length of 93.25”.
Compressor
Compartment
Top Lifting Lugs on Each Corner
Condenser
Section
4
Air Handling Unit Orientation (Non-Compressorized)
Service access is from the front of the unit. As you face the front of the unit, the controls section will be on the
right end of the unit, and the air handling section on the left. The drain connection is located on the back.
Figure 5a, Air Handler (Non-Compressorized) Unit Orientation
Return /
Outside Air /
Economizer
Section
Filter
Section
Coil Section
Heating Section
Table 5.1, AHU Dimensions
Model Width Length Height
002 - 005 42.25” 44.75” (63.75”)* 38”
*If present, the outside air hood will increase the overall installed unit length by 19” for a total length of 63.75”.
Top Lifting Lugs on Each Corner
Controls
Section
Power Disconnect
Switch
Forklift
Openings
5
2. Model Number Description
Unit Model Number
002 = 003 = 004 = 005 =
3 = A = B =
V = H =
A1
0 = A = B =
A2
0 = 2 = 3 = A = Q = U = W = Y = Z =
A3
0 = 1 = 8 = 9 =
A4
Nom. Tons Model
HB
Nominal Tons
2 Tons 3 Tons 4 Tons 5 Tons
Voltage
460V/3/60HZ 208-230V/1/60HZ 208-230V/3/60HZ
- -
Discharge
Vertical Horizontal
Style
No Refrigerant R-410A R-410A w/ 2 Step Compressor
Configuration
No Cooling Non-comp. w/ Std. DX Coil Non-comp. w/ Std. DX Coil w/ RA Bypass Air Cooled Cond. w/ Std. DX Coil Air Cooled Cond. w/ Std. DX Coil w/ RA Bypass Chilled Water 4 Row Coil Chilled Water 4 Row Coil w/ RA Bypass Chilled Water 3 Row Coil w/ 1 Row Preheat Chilled Water 3 Row Coil w/ RA Bypass & 1 Row Preheat
Coating
No Coating Phenolic Coated Coils - Evap. & Cond. Phenolic Coated Condenser Coil Only Phenolic Coated Evaporator Coil Only
Staging
No Cooling
0 =
Single Stage
1 =
Dual Stage (w/ 2 step compressor)
2 =
Single Serpentine Chilled Water
M =
Half Serpentine Chilled Water
N =
Voltage
Main Features
Discharge
Location
- - -
A1 A2 A3 A4
Cooling
Heating
B1 B2 B3
B1
Type*
0 =
No Heat
1 =
Electric Heat
2 =
Natural Gas Aluminized
E =
Hot Water
F =
Hot Water w/ Phenolic Coating
Note: LP gas and high altitude conversion kits are available for field installation.
B2
Designation
Gas Capacity Electric Capacity
Mbtu kW 208V kW 240-480V
0 = 1 = 2 = 3 = 4 = 5 =
No Heat 45 60 75 100 125
-
7.5 15
22.5
-
-
B3
Staging
No Heat
0 =
1 Stage (Gas or Electric)
1 =
2 Stage (Gas or Electric)
2 =
3 Stage (Electric Only)
3 =
Single Serpentine (Hot Water)
M =
Half Serpentine (Hot Water)
N =
6
­10 20 30
-
-
3. User’s Information
Failure to observe the following instructions may result in premature failure of your system, and possible voiding of the warranty.
WARNING
DX (Direct Expansion) Package Units and DX Units with Remote Condenser
Never cut off the main power supply to the unit, except for complete shutdown.
Always control the system from the thermostat, or control panel, and never at the main power supply (except in an emergency, or complete shutdown of the system).
During the cooling season, if the airflow is reduced due to dirty air filters, or other reasons, the cooling coils will get too cold and result in excessive liquid return to the compressor. As the liquid concentration accumulates, oil is washed out of the compressor leaving it starved for lubrication.
The compressors must be on a minimum of four minutes, and off for a minimum of five minutes. The cycle rate must not exceed eight starts per hour.
THE COMPRESSOR LIFE WILL BE SERIOUSLY SHORTENED BY RESULTING REDUCED LUBRICATION, AND THE PUMPING OF EXCESS AMOUNTS OF LIQUID OIL AND REFRIGERANT.
Hydronic Cooling and Heating
Non-compressorized units may contain chilled water and/or hot water coils. Units are provided with internal header connections for field piping. Vent and drain connections can be accessed within the unit.
Piping is to be run via the 4” x 7” piping chase located in the cabinet floor inside the coil compartment, accessible through the coil compartment access door on the front of the unit. Piping to coil header connections must be supported independently of the coil to prevent undue stress from weakening connections over time. Allow adequate flexibility for thermal expansion of the piping.
Use proper glycol solutions or brines to help prevent coil freezing. Consult the designer or project engineer if you have concerns about lower than normal entering
air temperatures (typically air temperatures below 40°F) that could cause coils to freeze.
Figure 7a, Piping Chase Location
Utility Entry
4” x 2 1/2”
Shipping
Bracket
Piping Chase
4” x 7”
Front
Return Supply
Back
Gas or Electric Heating
The system is designed to heat a given amount of air each minute of operation. If the amount of air heated is greatly reduced (approximately 1/3 capacity), the heat exchanger (or heater coil if electric) temperature will increase above acceptable levels, and will result in shut down by a high temperature safety switch incorporated into either the heat exchanger, or the heater area.
GAS HEAT UNITS – If heat shuts off due to safety switch, or gas supply shut off failure, then always close manual gas valve to unit prior to any electrical service. Prolonged overheating of the heat exchanger will shorten its life.
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Installation and service must be performed by a qualified installer, service agency, or if gas fired units, the gas supplier. Refer to installation instructions provided with the unit, and this manual.
WARNING
WARNING
7
Multiple Unit Operation
When several units are used in conditioning the space, and any are combination heating-cooling units, all system thermostat switches must be set at either heating, cooling, or set at ‘OFF’. Do not run part of a system switched to an opposite mode. Cooling only units should be switched to ‘OFF’ at the thermostat during the heating season.
Wiring Diagrams
A complete set of unit specific wiring diagrams in both ladder and point-to-point form are laminated in plastic and affixed to the inside of the service access door.
Condensate Piping
A drain trap must be connected to the drain connection located on the back of the unit. If codes require a condensate drain line, it should be the same pipe size as the drain nipple and should pitch downward for its entire length toward the drain. A “P” Trap is factory supplied and shipped in the control access compartment for field installation. An air break should be used with long runs of cond ensate lines.
Normal Thermostat Operation
For Heating
- Set system switch to ‘HEAT’
- Set fan switch to ‘AUTO’ or ‘ON’
- Set the desired temperature
For Cooling
- Set system switch to ‘COOL’
- Set fan switch to ‘AUTO’ or ‘ON’
Air Circulation
Set the system switch to ‘OFF’
-
Set the fan switch to ‘ON’
­System Off
-
Set the system switch to ‘OFF’ Set the fan switch to ‘AUTO’
-
-
Do not change temperature setting With these settings the system is shut down,
-
except for the 24-volt control system power, and the compressor crankcase heater (approx. 60W).
Night and Vacancy Operation
To reduce the operation time during low load periods, it is recommended that the temperature setting be increased by 5°F during non-occupied periods of the cooling season in commercial buildings, such as nights and weekends. Decrease the temperature by 10°F at these times during the heating season.
Gas Heating System
The heating section is for use with natural gas supply pressure of 6” to 10.5” w.g. The unit may also utilize propane gas (after installation of a field conversion kit) with a supply pressure to the valve of 11” to 12” w.g. The rating plate on the furnace must be inspected to make sure the unit is stamped for proper gas. A 1/8” pressure tap should be field supplied by the installer in the piping just ahead of the gas valve. The pressure tap on the outlet end of the gas valve can be checked to verify manifold pressure of 3.2” to 3.5” w.g. for natural gas or 11” to 12” w.g. for propane.
A centrifugal blower that draws in outside air through a protected opening supplies combustion air. This induced draft blower introduces the air to the blower tubes, which assures even primary and secondary airflow.
Gas heating units use AAON’s patented high efficiency twisted tube, or dimpled heat exchanger. All heating system and related safety controls are 100% tested on each unit prior to shipment.
Figure 8a, HB Gas Heat Exchangers
Dimpled Tube
Twisted Tube
8
Modulating Hot Gas Reheat and Hot Gas Bypass Systems on DX Units
Some DX cooling units may contain Modulating Hot Gas Reheat (MHGRH) and/or Hot Gas Bypass (HGBP) systems as factory installed options. Piping and valves for these systems will be located on the inside wall of the condenser section. The condenser top must be removed for access to these components.
Figure 9a, MHGRH and HGBP System
Piping to
Compressor and
Coil Compartments
HGBP
Valve
Receiver
Tank
Check
Valve
MHGRH
Valves
Filter Sizes
Table 9.1, Pleated Filter Sizes
All 2-5 Ton HB Packaged Units
Qty. Size
2 20” x 25” x 2”
Cabinet Construction
All HB units are insulated with closed-cell polyurethane foam, which has twice the R-value of fiberglass insulation. All cabinet walls and roof use double-wall G90 galvanized steel. The solid core foam interior provides a rigid, impact resistant surface. All panels have a thermal break with no metal-to-metal contact from outside to inside.
Figure 9b, High Performance Composite Panel
Thermal Break
Foam Core
Double-Wall
9
4. Delivery
ALL SHIPMENTS ARE F.O.B. THE FACTORY. IT IS THE RESPONSIBILITY OF THE RECEIVING PARTY TO INSPECT THE EQUIPMENT UPON ARRIVAL.
Receipt & Inspection
The unit should be inspected for damage that may have occurred in transit. Do the following upon receipt:
1. Inspect all items for internal, external, and concealed damage before accepting
2. Assure carrier is in compliance with Bill of Lading instructions
If damage is found:
1. Note all damage on Bill of Lading immediately
Photograph damage if possible
Do not move or discard damaged
packaging materials
2. Call carrier immediately to file a freight claim, and to schedule a freight inspection
3. When damage is repairable, contact the factory for replacement parts: 918-583-2266
4. With permission of carrier, make the repairs
5. Stay in contact with carrier to ensure payment of your claim
If repairs must be made to damaged goods, the factory must be notified before any repair action is taken. Equipment alteration, repair, or unauthorized manipulation of damaged equipment without the manufacturer’s consent will void all product warranties. Contact the AAON Warranty Department for assistance with handling damaged goods, repairs, and freight claims: 918-583-2266.
Verify the equipment against the order documents upon delivery. If what you received does not match your order exactly, then notify your Sales Representative at once.
Storage
This equipment is designed for outdoor use. However, if installation will not occur immediately following delivery, then store equipment in a protected area, and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose­shipped items.
5. Installation
General
DX models of this unit use R-410A refrigerant only, and should not be used with any other refrigerant. HB package units are for outdoor installation only.
Codes & Ordinances
System should be sized in accordance with National Warm Air Heating and Air Conditioning Association Literature, or the Guide of American Society of Heating, Refrigeration and Air Conditioning Engineers. The installation must conform with local building codes, or in the absence of local codes, with (United States) National Fuel Gas Code “ANSI-Z223.1”, (Canada) current CAN/CGA-B149.1 or B149.2. Installation codes for Gas Burning Appliances and Equipment, current C.S.A. Standard C22.1, Canadian Electrical Code Part 1, and C.S.A. Standard B52 Mechanical Refrigeration Code, and Local Plumbing or Waste Water Codes.
It is the responsibility of the installing contractor to comply with codes, ordinances, local and municipal building laws, and manufacturer’s instructions. Personal injury and/or equipment damage may result if proper procedures are not followed.
Handling
Be aware of what is contained in the equipment!
Dependent upon the optional accessories that were ordered, this equipment may contain fragile components and delicate electronics. Although the unit is constructed of sturdy materials, avoid impacts and handling methods that may damage internal apparatus and structure, or the exterior painted surfaces of the unit. Take care not to apply destructive force to coils, or other parts protruding beyond the extents of the unit casing. Always handle the unit by its exterior casing.
Keep equipment free from debris, and construction waste during installation. Foreign materials may adversely affect unit operation resulting in premature failures that will not be covered by the manufacturer’s
WARNING
10
Loading...
+ 22 hidden pages