AAON HA-50 User Manual

AAON
®
HA SERIES
HORIZONTAL DISCHARGE
COOLING UNITS
USERS
INFORMATION
MANUAL
1
2
AAON
TABLE OF CONTENTS
SECTION PAGE NUMBER OWNER'S INFORMATION …………………………………………………………………………… 04
Unpacking Setting the Unit Electrical Cooling Low Ambient Operation …………………………………………………………………………05 Multiple Unit Operation Condensate Piping Electric Heat Option Blower Information Filter Installation / Replacement
SEQUENCE OF OPERATIONS ……………………………………………………………………… 06
Normal Operation General Information
SERVICE, INSPECTIONS & MAINTENANCE …………………………………………………… 07
Cooling Heating Service Replacement Parts Cleaning
®
TROUBLE SHOOTING ………………………………………………………………………………… 08 COMPRESSOR CHECKOUT PROCEDURE ……………………………………………………… 09 DIMENSIONAL DATA ………………………………………………………………………………… 11
!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
Owner should pay particular attention to the words: NOTE, CAUTION AND WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert owner that personal injury and/or equipment
WARNING
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC's and HCFC's) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non­compliance.
damage may result if installation procedure is not handled properly.
! IMPORTANT
It is the intent of
AAON, Inc.
HA USERS • P92200 • 2000
AAON, Inc.
reserves the right to change pricing, specifications and/or design of it's products without notice, obligation or liablity.
to provide accurate and current specification information. However, in the interest of product improvement,
AAON
© 2000
&
AAONAIRE
AAON, Inc.
, all rights reserved throughout the world.
are registered trademarks of
3
AAON, Inc.
, Tulsa, OK.
OWNER'S INFORMATION
The HA Series units are designed for fast, easy installa­tion as a self-contained cooling unit for outdoor instal­lation only.
UNPACKING When received, the unit should be inspected and checked for damage that might have occurred in transit. If damage is found, it should be noted on the carrier's Freight Bill. A request for inspection by the carrier's agent should be made in writing at once.
Before lifting the unit, be sure that all shipping material has been removed from the unit. Once shipping material has been removed, check inside the unit control compartment for the field installed "P­Trap" condensate connector. Also check the inlet air opening for the filter rails and filters that are shipped loose with the unit for field installation.
SETTING THE UNIT If cable or chains are used to hoist the unit, care should be taken to prevent damage to the cabinet. Secure hooks and cables at all lifting points / lugs provided on the unit. Hoist the unit to a point directly above the pad, and lower unit into place. Make sure unit is properly seated on the pad.
ELECTRICAL A complete set of unit specific wiring diagrams in both ladder and point-to-point form are provided with the unit. Check the unit data plate to make sure it agrees with the power supply. The power and control wiring may be brought to the unit through a hole in the side of the unit. Protect the branch circuit in accordance with code re­quirements and connect power to the unit according to the wiring diagram provided with the unit. If the control wires are to run inside the same conduit, use 600 volt wire or as required by applicable code. The unit must be electrically grounded in accordance with the National Electric Code. Power wiring is to the unit terminal block or compressor contactor. All wiring beyond this point is done by the manufacturer. After connecting the control wiring to the unit, power may now be applied to the unit. Be sure that the evaporator blower and condenser fan(s) rotate in the proper direction (this applies only to units having three phase blower motor).
COOLING SECTION • DIRECT EXPANSION (DX) All direct expansion refrigeration systems are factory assembled, charged with refrigerant, tested and oper­ated. On 13 - 25 ton units the refrigerant system includes dual circuit evaporator and condenser coils providing two stages of cooling. On 30 - 40 ton units the refrigera­tion system includes a four circuit evaporator coil and two dual circuited condensor coils providing two or four stages (optional) of cooling. These systems are provided with liquid line filter driers, expansion valves and fully hermetic compressors. Compressors are equipped with a positive pressure forced lubrication system and crank­case heater. The air cooled condenser coil(s) is con­structed of copper tubes with aluminum fins, the air is pulled through with propeller fans. The evaporator coil is draw through, made of copper tubes with aluminum fins.
NOTE: Crankcase Heater Operation Some units are equipped with a compressor crackcase heater, which should be energized at least 24 hours prior to setting the thermostat for cooling operation.
Never cut off the main power supply to the unit, except for complete shutdown. When power is cut off from the unit, any compressors using crankcase heaters cannot prevent refrigerant migration. This means the compres­sor will cool down, and liquid refrigerant will accumu­late in the compressor. Since the compressor is designed to pump refrigerant gas, damage may occur when power is restored. If power must be cut off for more than an hour, turn the thermostat system switch to "OFF", and leave it off until the main power switch has been turned on again for at least twenty four hours for units with compressor crank­case heaters. This will give the crankcase heater time to clear any liquid accumulation out of the compressor before it is required to run. Always control the system from the thermostat, or con­trol panel, never at the main power supply (except for emergency or for complete shutdown of the system).
The refrigeration section of these appliances has been found acceptable with applicable provisions of "ANSI / UL 1995" and current "C.S.A. Standard C22.2" by E.T.L.
! CAUTION
!
W ARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies. Failure to observe the following instructions will result in premature failure of your system, and possible voiding of the warranty.
On three phase units the rototation must be
checked on ALL MOTORS AND COMPRESSORS.
SCROLL COMPRESSORS ARE DIRECTIONAL.
Rotation must be checked on start-up by a
qualified service technician using
suction and discharge gauges.
Scroll compressors will FAIL if run in the wrong
direction. Blower and condenser rotation
should be checked and only be altered if
necessary at the power connection.
4
OWNER'S INFORMATION
During the cooling season, if the air flow is reduced due to dirty air filters or any other reason, the cooling coils will get too cold and will cause excessive liquid to return to the compressor. As the liquid concentration builds up, oil is washed out of the compressor, leaving it starved for lubrication.
THE COMPRESSOR LIFE WILL BE SERIOUSLY SHORTENED BY THIS REDUCED LUBRICATION, AND THE PUMPING OF EXCESSIVE AMOUNTS OF LIQUID OIL AND REFRIGERANT.
CAUTION: While the following incorrect operations may not cause damage to the system, they will impair the performance, and may cause the built-in safety devices to cut the system off completely.
1. LOW AMBIENT OPERATION The cooling section of a direct expansion (DX) unit will not operate properly when the outdoor temperature is below 55° degrees. Outside air intake options are recommended if operation below 55° degrees is expected.
2. MULTIPLE UNIT OPERATION When several units are used in conditioning the space, and part or all of them are combination heating-cooling units, all systems thermostat switches must be set at either heating or cooling (or set at "off"). Do not leave part of the systems switched to the opposite mode. All cooling only units should be switched to "off" at the thermo­stat during the heating season.
CONDENSATE PIPING The unit requires a drain trap to be connected to the
drain pan at the unit. If codes require a condensate drain line, the line should be the same pipe size as the drain nipple and should pitch downward toward drain. The condensate drain pipe ("P" trap) is factory supplied and is shipped loose in the control access compartment for field installation. An air break should be used with long runs of condensate lines. Drain pans in any air conditioning equipment, even when they have a built-in slope to the drain, will have moisture present and will require periodic cleaning to prevent any build up of algae of bacteria.
Cleaning of the drain pans will also prevent any possible plugging of the drain lines and an over­flow of the pan itself. All cleaning of the drain pans and inside of the equipment should be done by qualified personnel.
ELECTRIC HEATING (Optional) The electric heat is available as an option. Heating is accomplished by passing electrical current through a specified amount of resistance heaters which will produce the required heat. The indoor blower motor will energize at the same time as the heaters. When heat is called for, the cooling section in inoperable except for the indoor blower motor.
The system is designed to heat or cool a given amount of air each minute it operates. If this amount of air is greatly reduced (approximately 1/3 during the heating season), the heater coil will overheat, and may cut the heater off entirely by action of the safety high tempera­ture limit device.
BLOWER INFORMATION DUE TO JOB SPECIFICATION REVISIONS, IT MAY
BE NECESSARY TO ADJUST OR CHANGE THE SHEAVE OR PULLEY TO OBTAIN THE DESIRED AIRFLOW AT THE TIME OF INSTALLATION.
START-UP TECHNICIAN MUST CHECK BLOWER MOTOR AMPERAGE TO ENSURE THAT THE AM­PERAGE LISTED ON THE MOTOR NAMEPLATE IS NOT EXCEEDED.
Clean blower wheels are necessary to reduce electrical use, maintain capacity and reduce stress on the unit.
FILTER INSTALLATION / REPLACEMENT Filter rails and filters are shipped inside the unit for field installation. Install filter rails and slide filters into place before operation of the unit. To replace filters, slide each filter out of filter rack and inspect. Replace old filters with the size indicated on each filter. Be sure arrow points towards the blower.
Filters should be checked every 30 days and replaced or cleaned as necessary.
Do not permit the unit to be operated unless filters are in place. Operation of the unit without filters will result in a clogged evaporator coil.
IT IS IMPORTANT TO KEEP COILS,
BLOWER AND FIL TERS CLEAN !
!
Before leaving installation, a complete
operating cycle should be observed
to verify that all components
are functioning properly.
CAUTION
5
SEQUENCE OF OPERATIONS
NORMAL OPERATION
COOLING Set the thermostat system switch to "COOL". Set the thermostat fan switch to "AUTO" or "ON". Set the thermostat temperature at the desired point.
HEATING Set the thermostat system switch to "HEAT". Set the thermostat fan switch to "AUTO" or "ON". Set the thermostat temperature at the desired point.
AIR CIRCULATION Set the thermostat system switch to "OFF". Set the thermostat fan switch to "ON". Do not change temperature setting. With these settings, the air circulating blower will run continuously but the air will not be heated or cooled.
SYSTEM OFF Set the thermostat system switch to "OFF". Set the thermostat fan switch to "AUTO". Do not change temperature setting. With these settings, the system is shut down, with the exception of the control system power (24 volts), and the crankcase heater of the compressor (about 60 watts).
DO NOT TURN OFF THE MAIN POWER SWITCH.
I. GENERAL INFORMATION A. COOLING
1. Packaged Units When the thermostat calls for cooling from the space, 'Y1' makes 'R' to 'CC1' through the LPS (low pressure switch), HPS (high pressure switch) and optional GOT (guaran­tee off timer). On larger units 'CC3' is also made. If additional cooling is required 'CC2' and 'CC4' are made through their respective pressure switches and timers.
B. HEATING (Optional)
1. Electric When the thermostat calls for heat 'W1' makes 'R' to the heat relay. All N.O. contacts close, and all N.C. contacts open. The heat relay makes 'R' to the first stage of electric heat.
On a fault condition the main limit located in the supply air or the auxiliary limit located in thesupply air fan housing will remove power from all contactors.
If additional heating is required a second set of elements can be turned on by 'W2'.
NIGHT AND VACANT WEEKEND OPERATION If it is desired to reduce the operating time during the night, and during periods when the space is unused, it is recommended that the temperature setting be raised about five degrees during these periods of the cooling season, and lowered about ten degrees during the heating season.
6
Loading...
+ 13 hidden pages