AAON CN-140 User Manual

Page 1
CN Series
Condensing Units
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
WARNING
& Maintenance
Page 2
Page 3
3
Table of Contents
Safety .............................................................................................................................................. 5
CN Series Feature String Nomenclature ......................................................................................... 9
General Information ...................................................................................................................... 12
Codes and Ordinances ............................................................................................................... 12
Receiving Unit ........................................................................................................................... 12
Storage ....................................................................................................................................... 12
Wiring Diagrams ....................................................................................................................... 14
General Maintenance ................................................................................................................. 14
Installation..................................................................................................................................... 15
Unit Placement .......................................................................................................................... 15
Curb and Steel Mount Installation ............................................................................................ 15
Lifting and Handling ................................................................................................................. 16
End Flashing Installation ........................................................................................................... 16
Mounting Isolation .................................................................................................................... 18
Access Doors ............................................................................................................................. 18
Low Ambient Operation ............................................................................................................ 18
Expansion Valve Operation ...................................................................................................... 18
Determining Refrigerant Line Size ........................................................................................... 18
Liquid Line ............................................................................................................................ 19
Suction Line ........................................................................................................................... 20
Hot Gas Bypass Line ............................................................................................................. 21
Hot Gas Reheat ...................................................................................................................... 22
LAC Valve ................................................................................................................................ 23
Condenser Flooding .................................................................................................................. 24
Electrical .................................................................................................................................... 24
Startup ........................................................................................................................................... 26
Axial Flow Condenser Fans ...................................................................................................... 26
Maintenance .................................................................................................................................. 30
General ...................................................................................................................................... 30
Compressors .............................................................................................................................. 30
Refrigerant Filter Driers ............................................................................................................ 30
Adjusting Refrigerant Charge ................................................................................................... 30
Lubrication ................................................................................................................................ 34
Air-Cooled Condenser ............................................................................................................... 34
E-Coated Coil Cleaning ............................................................................................................ 34
Microchannel Coil Cleaning ..................................................................................................... 35
Service ....................................................................................................................................... 35
Replacement Parts ..................................................................................................................... 35
AAON Warranty, Service and Parts Department ...................................................................... 35
Refrigerant Piping Diagrams ........................................................................................................ 36
CN Series Startup Form ................................................................................................................ 44
Maintenance Log .......................................................................................................................... 47
Literature Change History............................................................................................................. 48
Page 4
4
Index of Tables and Figures
Tables:
Table 1 - Service Clearances......................................................................................................... 15
Table 2 - Condenser Flooding....................................................................................................... 24
Table 3 - Condenser Fan Pin Location ......................................................................................... 28
Table 4 - Condenser Fan Pin Location ......................................................................................... 28
Table 5 - Fan Assembly Bushing Torque Specifications.............................................................. 29
Table 6 - Filter Drier Maximum Pressure Drop............................................................................ 30
Table 7 - Acceptable Refrigeration Circuit Values ....................................................................... 31
Table 8 - R-410A Refrigerant Temperature-Pressure Chart ......................................................... 33
Figures:
Figure 1 - Curb Mounting with Dimensions ................................................................................. 16
Figure 2 - Steel Mounting Rail with Dimensions ......................................................................... 16
Figure 3 - Concrete Pad Mounting with Dimensions ................................................................... 16
Figure 4 - Lifting Points ................................................................................................................ 16
Figure 5 - CN Series A Cabinet Top Lifting Detail ...................................................................... 17
Figure 6 – CN Series B and C Cabinet Bottom Lifting Detial ..................................................... 17
Figure 7 - Piping Schematic of Example System using the LAC Valve. ..................................... 23
Figure 8 - Terminal Block............................................................................................................. 25
Figure 9 - Fan with the HUB on the top and RET on the bottom. ................................................ 26
Figure 10 - Bushing Mount Location............................................................................................ 27
Figure 11 - RET with Pin in Groove 4 .......................................................................................... 27
Figure 12 - Fan HUB and RET Castings ...................................................................................... 27
Figure 13 - Pitch Insert ................................................................................................................. 28
Figure 14 - A/C Only Piping, AHU Above CU ............................................................................ 36
Figure 15 - A/C Only Piping, AHU Below CU ............................................................................ 37
Figure 16 - Modulating Hot Gas Reheat Piping, AHU Above CU .............................................. 38
Figure 17 - Modulating hot gas reheat piping, AHU below CU ................................................... 39
Figure 18 - Hot gas bypass piping, AHU above CU..................................................................... 40
Figure 19 - Hot gas bypass piping, AHU below CU .................................................................... 41
Figure 20 - Modulating hot gas reheat with hot gas bypass piping, AHU above CU .................. 42
Figure 21 - Modulating hot gas reheat with hot gas bypass piping, AHU below CU .................. 43
V28960 · Rev. A · 140331
Page 5
5

Safety

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all
electrical power to the furnace. More than one disconnect may be provided.
When servicing controls, label all
wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with key-lock or nut and bolt.
WARNING
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit. Shut off main gas supply. Do not touch any electric switch. Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections and shut off valves.
CAUTION
Page 6
6
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD
Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.
Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.
WARNING
WARNING
During installation, testing, servicing, and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks.
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.
WARNING
Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
CAUTION
Page 7
7
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings and complete piping system failure.
CAUTION
UNIT HANDLING
To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
WARNING
Door compartments containing hazardous voltage or rotating parts are equipped with door latches that allow locks. Door latches are shipped with a nut and bolt requiring tooled access. If the shipping hardware is not replaced with a pad lock, always re-install the nut and bolt after closing the door to maintain tooled access.
CAUTION
Rotation must be checked on all MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection
CAUTION
Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.
WARNING
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than
8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
CAUTION
Page 8
8
Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturers usage instructions. Failure to follow instructions may result in equipment damage, injury or death.
WARNING
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
CAUTION
Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used in hydrofluorocarbon (HFC) refrigeration systems. Refer to the compressor label for the proper compressor lubricant type.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
1. Startup and service must be performed
by a Factory Trained Service Technician
2. The unit is for outdoor use only. See
General Information section for more information.
3. Every unit has a unique equipment
nameplate with electrical, operational, and unit clearance specifications. Always refer to the unit nameplate for specific ratings unique to the model you have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
5. Keep this manual and all literature
safeguarded near or on the unit.
Page 9

CN Series Feature String Nomenclature

Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN
A - 055
- A - 0 - 3 - C A 0 0 E : 0 - 0 0 - E
0
- D 0 - 0 0 0 - 0 - D A 0 0 - 0 0 0 0 E 0
0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
9
CN Series Feature String Nomenclature
MODEL OPTIONS
Series and Generation
CN
Major Revision
A
Unit Size
055 = 55 ton Capacity 065 = 65 ton Capacity 075 = 75 ton Capacity 090 = 90 ton Capacity 105 = 105 ton Capacity 120 = 120 ton Capacity 130 = 130 ton Capacity 140 = 140 ton Capacity
Series
A = 55-75 ton units B = 90-105 ton units C = 120-140 ton units
Minor Revision
0
Voltage
2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz
A1: Compressor Style
C = R-410A VFD Compatible Scroll Compressor
A2: Condenser Style
A = Air-Cooled Microchannel Condenser
A3: Configuration 0 = Standard
A4: Coating
0 = Standard E = Polymer E-coated Condenser Coil
A5: Staging A = 1 Variable Capacity Comp + 1 On/Off Comp B = 2 Variable Capacity Comp + 2 On/Off Comp E = All Variable Capacity Compressors
UNIT FEATURE OPTIONS
1: Unit Orientation
A = Vertical Condenser Discharge with End Control Panel
2A: Refrigeration Control
0 = Standard B = Fan Cycling C = Adjustable Fan Cycling D = Adjustable Compressor Lockout K = Options B + D M = Options C + D
2B: Blank 0 = Standard
3A: Refrigeration Options
0 = None D = Hot Gas Bypass Non-Variable Compressors [HGBNV] E = Modulating Hot Gas Reheat [MHGR] L = Options D + E
3B: Blank 0 = Standard
Page 10
CN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN A -
055
- A - 0 -
3 - C A 0 0 E : 0 - 0 0 - E 0
-
D 0 - 0 0 0 - 0 - D A 0 0 - 0
0
0 0 E 0 0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
10
4: Refrigeration Accessories
0 = None A = Sight Glass B = Compressor Isolation Valves C = Options A + B D = Flooded Condenser 0°F Low Ambient Controls ­One Circuit E = Options A + D F = Options B + D G = Options A + B + D H = Flooded Condenser 0°F Low Ambient Controls ­Two Circuit J = Options A + H K = Options B + H L = Options A + B + H M = Flooded Condenser 0°F Low Ambient Controls ­Three Circuit N = Options A + M P = Options B + M Q = Options A + B + M R = Flooded Condenser 0°F Low Ambient Controls ­Four Circuit S = Options A + R T = Options B + R U = Options A + B + R
5: Blank 0 = Standard
6A: Unit Disconnect Type 0 = Standard Single Point Power Block A = Single Point Power Non-Fused Disconnect
6B: Disconnect Size J = 60 amps N = 100 amps R = 150 amps U = 225 amps Z = 400 amps 3 = 600 amps 5 = 800 amps 7 = 1200 amps
6C: Blank 0 = Standard
7: Accessories 0 = None B = Phase & Brown Out Protection D = Suction Pressure Transducer All Refrigeration Circuits L = Options B + D
8A: Control Sequence
B = VAV Single Zone Unit Controller - VAV Cool + CAV Heat C = VAV Single Zone Unit Controller - VAV Cool + VAV Heat D = VAV Unit Controller - VAV Cool + VAV Heat E = CAV Unit Controller - CAV Cool + CAV Heat F = MUA Unit Controller - CAV Cool + CAV Heat M = Field Installed DDC Controls by Others N = Field Installed DDC Controls w/ Isolation Relays P = Factory Installed DDC Controls Furnished by Others w/ Isolation Relays (SPA)
8B: Control Supplier 0 = AAON Refrigeration System Supervisory Controls A = WattMaster Orion Control System C = WattMaster Orion Control System (Main Controller in Air Handler)
8C: Control Supplier Options 0 = Standard
8D: BMS Connection & Diagnostics
0 = Standard
9: Blank 0 = Standard
10: Blank 0 = Standard
Page 11
CN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN A -
055
- A - 0 -
3 - C A 0 0 E : 0 - 0 0 - E 0 - D 0 - 0 0 0 - 0 - D A 0 0 - 0
0
0 0 E 0 0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
11
11: Maintenance Accessories 0 = None A = 115VAC Convenience Outlet - Factory Wired B = 115VAC Convenience Outlet - Field Wired C = Service Access Lights E = Remote Unit Start/Stop Terminals F = Options A + C H = Options A + E J = Options B + C L = Options B + E N = Options C + E R = Options A + C + E U = Options B + C + E
12: Code Options 0 = Standard ETL US Listing A = Chicago Code B = ETL US + Canada Listing
13: Air-Cooled Condenser H = Condenser Coil Guards + Three Phase Condenser Fan Motor J = Condenser Coil Guards + Three Phase Condenser Fan Motor + VFD Controlled Condenser Fans (35°F Low Ambient
14: Blank 0 = Standard
15: Blank 0 = Standard
16: Electrical Options 0 = Standard
17: Blank 0 = Standard
18: Blank 0 = Standard
19: Blank 0 = Standard
20: Cabinet Material
0 = Double Wall Galvanized Steel Cabinet + R-13 Foam Insulation
21: Warranty 0 = Standard Warranty D = Extended Compressor Warranty Years 2-5
22: Paint and Special Pricing Authorization B = Premium AAON Gray Paint Exterior E = Premium AAON Gray Paint Exterior + Shrink Wrap X = SPA + Option B 1 = SPA + Option E 4 = SPA + Special Exterior Paint Color 7 = SPA + Special Exterior Paint Color + Shrink Wrap
Page 12
12
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician.
WARNING
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be followed.
CAUTION
Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.
Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.
WARNING
WARNING

General Information

AAON CN Series condensing units are complete air-cooled condensing units ranging from 55 to 140 tons of cooling capacity. They are assembled, wired, and tested.

Codes and Ordinances

CN Series units have been tested and certified, by ETL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook.
Installation of CN Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, and local building, plumbing and waste water codes. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.

Receiving Unit

When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for inspection by carrier’s agent should be made
in writing at once. Nameplate should be checked to ensure the correct model sizes and voltages have been received to match the job requirements.

Storage

If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose-shipped items.
Page 13
13
Scroll compressors are directional and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should only be made at the unit power connection.
CRANKCASE HEATER
OPERATION Units may be equipped with compressor crankcase heaters, which should be energized at least 24 hours prior to cooling operation, to clear any liquid refrigerant from the compressors.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 6 starts per hour.
WARNING
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. All motors, to include and not be limited to pump motors and condenser fan motors, should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
Failure to observe the following instructions will result in premature failure of your system, and possible voiding of the warranty.
Never turn off the main power supply to the unit, except for complete shutdown. When power is cut off from the unit, any compressors using crankcase heaters cannot prevent refrigerant migration. This means the compressor will cool down, and liquid refrigerant may accumulate in the compressor. The compressor is designed to pump refrigerant gas and damage may occur when power is restored if liquid enters the compressor.
Before unit operation, the main power switch must be turned on for at least 24 hours for units with compressor crankcase heaters. This will give the crankcase heater time to clear any liquid accumulation out of the compressor before it is required to run.
Never cut off the main power supply to the unit, except for complete shutdown. Always control the system from the building management system, or control panel, never at the main power supply (except for emergency or for complete shutdown of the system).
Scroll compressors must be on a minimum of 5 minutes and off for a minimum of 5 minutes. The cycle rate must be no more than 6 starts per hour.
Page 14
14
Compressor life will be seriously shortened by reduced lubrication, and the pumping of excessive amounts of liquid oil and liquid refrigerant.

Wiring Diagrams

A complete set of unit specific wiring diagrams in both ladder and point-to-point form are laminated in plastic and located inside the control compartment door.

General Maintenance

When the initial startup is made and on a periodic schedule during operation, it is necessary to perform routine service checks on the performance of the condensing unit. This includes reading and recording suction pressures and checking for normal sub­cooling and superheat. See the air-cooled condenser sections in this manual for specific details.
Page 15
15
Location
Unit Size
55-140 tons
Front -
(Controls Side)
72
Back
48
Ends
96
Top
Unobstructed
All roofing work should be performed by competent roofing contractors to avoid any possible leakage.
CAUTION
The base beneath the condenser section is open and must be considered when mounting on a curb.
CAUTION

Installation

Unit Placement

The AAON CN Series is designed for outdoor applications and mounting at ground level or on a rooftop. It must be placed on a level and solid foundation that has been prepared to support its weight.
The placement relative to the building air intakes and other structures must be carefully selected. Be sure to observe the dimensions that are on the rating plate of the condensing unit for operational and service clearances.
Table 1 - Service Clearances
Condenser coils and fans must be free of any obstructions in order to start and operate properly with a correct amount of airflow. For proper unit operation, the immediate area around condenser must remain free of debris that may be drawn in and obstruct airflow in the condensing section.
Consideration must be given to obstruction caused by snow accumulation when placing the unit.

Curb and Steel Mount Installation

Make openings in the roof decking large enough to allow for water piping, electrical penetrations, and workspace only. Do not make openings larger than necessary. Set the curb to coincide with the openings. Make sure curb is level.
Unit specific curb drawing is included with job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation details.
Units require rail support along all four sides of the unit base.
When installed at ground level, a one-piece concrete slab should be used with footings that extend below the frost line. Care must also be taken to protect the coil and fins from damage due to vandalism or other causes.
If unit is elevated a field supplied catwalk is recommended to allow access to unit service doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used between the curb and the unit to reduce vibration from the unit to the building.
Page 16
16
Figure 1 - Curb Mounting with Dimensions
Before lifting unit, be sure that all shipping material has been removed from unit. Secure hooks and cables at all lifting points/ lugs provided on the unit.
Hoist unit to a point directly above the curb or mounting rail. Be sure that the gasket material has been applied to the curb or mounting rail.
Carefully lower and align unit with utility and duct openings. Lower the unit until the unit skirt fits around the curb. Make sure the unit is properly seated on the curb and is level.
Do not push, pull or lift the unit from anything other than its base.
Figure 2 - Steel Mounting Rail with
Dimensions
Figure 3 - Concrete Pad Mounting with
Dimensions

Lifting and Handling

If cables or chains are used to hoist the unit they must be the same length and care should be taken to prevent damage to the cabinet. See Figure 6 for additional information.
Figure 4 - Lifting Points

End Flashing Installation

AAON CN Series condensing units are 142” wide, and the cabinet width will overhang the shipping trailer on each side.
In order to secure and protect the unit during transit the sheet metal end flashings have been removed from the unit. The slot created at the base of each end of the unit allows the unit to set firmly on the trailer deck.
Sheet metal flashings are shipped loose with the unit and once the unit is set into place
Page 17
17
the flashings must be installed on each end of the unit to complete the finished seal at the base. The flashings are unit specific and designed to cover the slot at each end of the unit to prevent water run-off into the curb.
Failure to attach and seal the end of unit with the flashings may result in water leakage into the curb.
Figure 5 - CN Series A Cabinet Top Lifting Detail
Figure 6 - CN Series B and C Cabinet Bottom Lifting Detial
Lifting slot locations are unit specific.
Unit must be rigged at all marked lifting points.
Page 18
18
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings and complete piping system failure.
CAUTION
Line sizes must be selected to meet actual installation conditions, not simply based on the connection sizes at the condensing unit or air handling unit.
CAUTION

Mounting Isolation

For roof mounted applications or anytime vibration transmission is a factor, full perimeter vibration isolators may be used.

Access Doors

Lockable access doors are provided to the compressor and control compartment.

Low Ambient Operation

The AAON low ambient (condenser flood­back) system is used to operate a refrigerant system below 35°F outside air temperature. As the ambient temperature drops, the condenser becomes more effective therefore lowering the head pressure. When the head pressure gets too low, there will be insufficient pressure to operate the expansion valve properly. During low ambient temperatures, it is difficult to start a system because the refrigerant will migrate to the cold part of the system (condenser) and make it difficult for refrigerant to flow.
The low ambient system maintains normal head pressure during periods of low ambient operation by restricting liquid flow from the condenser to the receiver, and at the same time bypassing hot gas around the condenser to the inlet of the receiver. This backs liquid refrigerant up into the condenser reducing its capacity that in turn increases the
condensing pressure. At the same time the bypassed hot gas raises liquid pressure in the receiver, allowing the system to operate properly.
There are different types of low ambient control used. The following figure shows the type of system available on the CN Series.

Expansion Valve Operation

AAON recommends the use of electronic expansion valves in matching air handling units when using variable speed compressors in CN Series condensing units. Thermostatic expansion valves do not have enough turn down capacity and cannot properly manage suction superheat during low load conditions. Electronic expansion valves must be observed during startup through the entire operating range of the variable speed compressor to ensure that suction superheat never falls below 7°F. Insufficient suction superheat can introduce liquid refrigerant to the compressor and significantly reduce compressor life.

Determining Refrigerant Line Size

The piping between the condenser and low side must ensure:
1. Minimum pressure drop, and
2. Continuous oil return, and
3. Prevention of liquid refrigerant slugging, or carryover
Minimizing the refrigerant line size is favorable from an economic perspective,
Page 19
19
reducing installation costs, and reducing the potential for leakage. However, as pipe diameters narrow, pressure-reducing frictional forces increase.
Excessive suction line pressure drop causes loss of compressor capacity and increased power usage resulting in reduced system efficiency. Excessive pressure drops in the liquid line can cause the liquid refrigerant to flash, resulting in faulty expansion valve operation and improper system performance. In order to operate efficiently and cost effectively, while avoiding malfunction, refrigeration systems must be designed to minimize both cost and pressure loss.
Equivalent Line Length
All line lengths discussed in this manual, unless specifically stated otherwise, are Equivalent Line Lengths. The frictional pressure drop through valves, fittings, and accessories is determined by establishing the equivalent length of straight pipe of the same diameter. Always use equivalent line lengths when calculating pressure drop. Special piping provisions must be taken when lines are run underground, up vertical risers, or in excessively long line runs.

Liquid Line

When sizing the liquid line, it is important to minimize the refrigerant charge to reduce installation costs and improve system reliability. This can be achieved by minimizing the liquid line diameter. However, reducing the pipe diameter will increase the velocity of the liquid refrigerant which increases the frictional pressure drop in the liquid line, and causes other undesirable effects such as noise.
Maintaining the pressure in the liquid line is critical to ensuring sufficient saturation temperature, avoiding flashing upstream of the expansion valve, and maintaining system
efficiency. Pressure losses through the liquid line due to frictional contact, installed accessories, and vertical risers are inevitable. Maintaining adequate sub­cooling at the condenser to overcome these losses is the only method to ensure that liquid refrigerant reaches the expansion valve.
Liquid refrigerant traveling upwards in a riser loses head pressure. If the evaporator is below the condenser, and the liquid line does not include risers, the gravitational force will increase the pressure of the liquid refrigerant. This will allow the refrigerant to withstand greater frictional losses without the occurrence of flashing prior to the expansion vavle.
A moisture-indicating sight glass may be field installed in the liquid line to indicate the occurrence of premature flashing or moisture in the line. The sight glass should not be used to determine if the system is properly charged. Use temperature and
pressure measurements to determine liquid sub-cooling, not the sight glass.
Liquid Line Routing
Care should be taken with vertical risers. When the system is shut down, gravity will pull liquid down the vertical column, and back to the condenser when it is below the evaporator. This could potentially result in compressor flooding. A check valve can be installed in the liquid line where the liquid column rises above the condenser to prevent this. The liquid line is typically pitched along with the suction line, or hot gas line, to minimize the complexity of the configuration.
Liquid Line Insulation
When the liquid line is routed through regions where temperature losses are expected, no insulation is required, as this
Page 20
20
Suction line must be sized in accordance to the minimum capacity of the variable speed compressor.
CAUTION
may provide additional sub-cooling to the refrigerant. When routing the liquid line through high temperature areas, insulation of the line is appropriate to avoid loss of sub­cooling through heat gain.
Liquid Line Guidelines
In order to ensure liquid at the expansion valve, frictional losses must not exceed available sub-cooling. A commonly used guideline to consider is a system design with pressure losses due to friction through the line not to exceed a corresponding 1-2°F change in saturation temperature.
If the velocity of refrigerant in the liquid line is too great, it could cause excessive noise or piping erosion. The recommended maximum velocities for liquid lines are 100 fpm from the condenser to a receiver tank to discourage fluid backup, and 300 fpm from receiver tank to the evaporator to minimize valve induced liquid hammer.
Liquid Line Accessories
Liquid line shut off valves and filter driers are factory provided. The total length equivalent of pressure losses through valves, elbows and fittings must be considered when adding additional components in the field. It is a good practice to utilize the fewest elbows that will allow the mating units to be successfully joined.

Suction Line

The suction line is more critical than the liquid line from a design and construction standpoint. More care must be taken to ensure that adequate velocity is achieved to return oil to the compressor at minimum loading conditions. However, reducing the piping diameter to increase the velocity at minimal load can result in excessive pressure losses, capacity reduction, and noise at full load.
Suction Line Routing
Pitch the suction line in the direction of flow (about 1 foot per 120 feet of length) to maintain oil flow towards the compressor, and keep it from flooding back into the evaporator. Crankcase heaters may be provided to keep any condensed refrigerant that collects in the compressor from causing damage or wear. Make sure to provide support to maintain suction line positioning, and insulate completely between the evaporator and condensing unit.
It is important to consider part load operation when sizing suction lines. At minimum capacity, refrigerant velocity may not be adequate to return oil up the vertical riser. Decreasing the diameter of the vertical riser will increase the velocity, but also the frictional loss.
A double suction riser can be applied to the situation of part load operation with a suction riser. A double suction riser is designed to return oil at minimum load while not incurring excessive frictional losses at full load. A double suction riser consists of a small diameter riser in parallel with a larger diameter riser, and a trap at the base of the large riser. At minimum capacity, refrigerant velocity is not sufficient to carry oil up both risers, and it collects in the trap, effectively closing off the larger diameter riser, and diverting refrigerant up the small riser where velocity of the refrigerant is sufficient to maintain oil flow. At full load, the mass flow clears the trap of oil, and refrigerant is carried through both risers. The smaller diameter pipe should be
Page 21
21
sized to return oil at minimum load, while the larger diameter pipe should be sized so that flow through both pipes provides acceptable pressure drop at full load.
Suction Line Insulation
The entire suction line should be insulated with a minimum 1 inch thick Armaflex insulation. This prevents condensation from forming on the line, and reduces any potential loss in capacity associated with heat gain placing additional load on the system.
Suction Line Guidelines
For proper performance, suction line velocities less than a 4,000 fpm maximum are recommended. The minimum velocity required to return oil is dependent on the pipe diameter, however, a general guideline of 1,000 fpm minimum may be applied.
In a fashion similar to the liquid line, a common guideline to consider is a system design with pressure losses due to friction through the line not to exceed a corresponding 1-2°F change in saturation temperature.
At points where small pipe size can be used to provide sufficient velocity to return oil in vertical risers at part loads, greater pressure losses are incurred at full loads. This can be compensated for by over sizing the horizontal runs and vertical drop sections. This will however require additional refrigerant charge.
Suction Line Accessories
If the job requirements specify suction accumulators, they must be separately purchased and field installed.

Hot Gas Bypass Line

Hot Gas Bypass is available for use with DX systems that may experience low suction
pressure during the operating cycle. This may be due to varying load conditions associated with VAV applications or units supplying a large percentage of outside air. The system is designed to divert refrigerant from the compressor discharge to the low pressure side of the system in order to keep the evaporator from freezing and to maintain adequate refrigerant velocity for oil return at minimum load.
Hot discharge gas is redirected to the evaporator inlet via an auxiliary side connector (ASC) to false load the evaporator when reduced suction pressure is sensed.
Field piping between the condensing unit and the evaporator is required.
Hot Gas Bypass Piping Considerations for Evaporator above Condensing Unit
Pitch the hot gas bypass (HGB) line downward in the direction of refrigerant flow, toward the evaporator.
When installing hot gas bypass risers, an oil drip line must be provided at the lowest point in the system. The oil drip line must be vertical, its diameter should be the same as the diameter of the riser, and it should be 1 foot long. Install a sight glass in the oil drip line for observation. Run an oil return line, using 1/8 inch capillary tube, 10 feet in length, from the oil drip line to the suction line. Connect the oil return line below the sight glass and 1 inch above the bottom of the oil drip line.
HGB valves are adjustable. Factory HGB valve settings will be sufficient for most applications, but may require slight adjustments for some applications, including some make up air applications.
Insulate the entire length of the HGB line with a minimum 1 inch thick Armaflex insulation.
Page 22
22
Hot Gas Bypass Piping Considerations for Evaporator Below Condensing Unit
The line must slope downward from the HGB valve toward the evaporator.
Hot Gas Bypass Line Guidelines
Choose a small size line to ensure oil return, and minimize refrigerant charge.
Maintain velocities below a maximum of 4,000 fpm. A general minimum velocity guideline to use is approximately 1,000 fpm.

Hot Gas Reheat

The AAON modulating hot gas reheat system diverts hot discharge gas from the condenser to the air handling unit through the hot gas line. Field piping between the
condensing unit and the air handler is required.
The line delivers the hot discharge gas to the reheat coil and/or the hot gas bypass valve, so it is sized as a discharge line.
Discharge lines should be sized to ensure adequate velocity of refrigerant to ensure oil return, avoid excessive noise associated with velocities that are too high, and to minimize efficiency losses associated with friction.
Pitch the hot gas line in the direction of flow for oil return.
When installing hot gas reheat risers, an oil drip line must be provided at the lowest point in the system. The oil drip line must be vertical, its diameter should be the same as the diameter of the riser, and it should be 1 foot long. Run a drip line, using 1/8 inch capillary tube, 10 feet in length, from the oil drip line to the suction line. Connect the oil return line below the sight glass and 1 inch above the bottom of the oil drip line.
Insulate the entire length of the hot gas line with a minimum 1 inch thick Armaflex insulation.
Hot Gas Reheat Guidelines
Maintain velocities below a maximum of 3,500 fpm. A general minimum velocity guideline is 2,000 fpm.
Page 23
23

LAC Valve

The LAC valve is a non-adjustable three way valve that modulates to maintain receiver pressure. As the receiver pressure drops below the valve setting (295 psig for R-410A), the valve modulates to bypass discharge gas around the condenser. The discharge gas warms the liquid in the receiver and raises the pressure to the valve setting. The following schematic shows an example system using the LAC valve.
Figure 7 - Piping Schematic of Example System Using the LAC Valve.
Page 24
24
PERCENTAGE OF CONDENSER TO BE
FLOODED
Ambient
Temperature
(°F)
Evaporating Temperature (°F)
0°
10°
20°
30°
35°
40°
45°
50°
70°
40
24 0 0 0 0 0 0
60°
60
47
33
17
26
20
10
4
50°
70
60
50
38
45
40
33
28
40°
76
68
60
50
56
52
46
42
30°
80
73
66
59
64
60
55
51
20°
86
77
72
65
69
66
62
59
0°
87
83
78
73
76
73
70
68
-20°
91
87
82
77
80
79
76
73
Electric shock hazard. Before attempting to perform any installation, service, or maintenance, shut off all electrical power to the unit at the disconnect switches. Unit may have multiple power supplies. Failure to disconnect power could result in dangerous operation, serious injury, death, or property damage.
WARNING

Condenser Flooding

In order to maintain head pressure in the refrigeration system, liquid refrigerant is backed up in the condenser to reduce condenser surface. The following chart shows the percentage that a condenser must be flooded in order to function properly at the given ambient temperature.
Table 2 - Condenser Flooding
During higher ambient temperatures the entire condenser is required to condense refrigerant. During these higher ambient temperatures, a receiver tank is used to contain the refrigerant that was required to flood the condenser during low ambient operation. The receiver must be sized to contain all of the flooded volume otherwise there will be high head pressures during higher ambient conditions.

Electrical

The single point electrical power connections are made in the electrical control compartment.
The microprocessor control furnished with the unit is supplied with its own power supply factory wired to the main power of the condensing unit.
Verify the unit nameplate voltage agrees with the power supply. Connect power and control field wiring as shown on the unit specific wiring diagram provided with the unit.
Size supply conductors based on the unit MCA rating. Supply conductors must be rated a minimum of 167°F (75°C).
Route power and control wiring, separately, through the utility entry. Do not run power and signal wires in the same conduit.
Protect the branch circuit in accordance with code requirements. The unit must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1.
Power wiring is to the unit terminal block or main disconnect. All wiring beyond this point has been done by the manufacturer and cannot be modified without effecting the unit's agency/safety certification.
Page 25
25
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Condenser fan motors should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection. Variable frequency drives are programmed to automatically rotate the fan in the correct rotation. Do not rely on fans with variable frequency drives for compressor rotation.
CAUTION
Scroll compressors are directional and will be damaged by operation in the wrong direction. Low pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should only be made at the unit power connection.
CAUTION
Figure 8 - Terminal Block
Startup technician must check for proper motor rotation and check fan motor amperage listed on the motor nameplate is not exceeded. Motor overload protection may be a function of the variable frequency drive and must not be bypassed.
Note: All units are factory wired for 208/230V, 460V, or 575V.
Wire control signals to the unit’s low
voltage terminal block located in the controls compartment.
If any factory installed wiring must be replaced, use a minimum 221°F (105°C) type AWM insulated conductors.
Page 26
26
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Startup and service must be performed by a Factory Trained Service Technician
WARNING
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. All motors, to include and not be limited to pump motors and condenser fan motors, should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
CAUTION
Before completing installation, a complete operating cycle should be observed to verify that all components are functioning properly.
CAUTION
Bushing Mount

Startup

(See back of the manual for startup form)
Before the startup of the condensing unit be sure that the following items have been checked.
1. Verify that electrical power is available
to the unit.
2. Verify that any remote stop/start device
is requesting the condensing unit to start.
Cycle through all the compressors to confirm that all are operating within tolerance.
While performing the check, use the startup form to record observations of compressor amps and refrigerant pressures.

Axial Flow Condenser Fans

Multi-Wing Z Series Aluminum Fan Blade Pitch Angle Setting Instructions
1. Maintain the balance of fan
Mark the hub castings across a joint, so the fan hub can be reassembled in the same orientation.
Mark the location of any balancing weight. Balancing weight will be on the outer bolt circle, in the form of washers, and/or longer bolts, or an additional balancing nut.
Number the blades and blade sockets, so that they are replaced into their original position.
Figure 9 - Fan with the HUB on the top and
RET on the bottom.
Page 27
27
A
B
Bushing
Mount
Bushing
Bushing
1
2
3
4
2. Determine the direction of rotation
Right, R, is clockwise when facing the discharge side of the fan and Left, L, is counterclockwise when facing the discharge side of the fan.
3. Determine the bushing mount location
The bushing mount is the center section of the hub through which the fan is mounted to the shaft, and typically contains either setscrews or a center-tapered hole where the bushing inserts.
Location A is with the bushing mount on air inlet side of the fan. Location B is with the bushing mount on air discharge side of the fan.
Figure 11 - RET with Pin in Groove 4
5. Determine whether the pin is in the HUB
or RET
Figure 10 - Bushing Mount Location
4. Determine the pin location groove
Disassemble fan on a flat surface and note in which groove the pin is located.
Figure 12 - Fan HUB and RET Castings
Page 28
28
Type
Bushing
Mount
Blade Pitch Angle
20°
25°
28°
30°
33°
35°
38°
40°
45°
50°
5Z
A
-
RET
-
RET
RET
RET
HUB
HUB
HUB
HUB B -
HUB
-
HUB
HUB
HUB
RET
RET
RET
RET
Type
Rot.
Blade Pitch Angle
20°
25°
28°
30°
33°
35°
38°
40°
45°
50°
5Z
R - 4 - 3 2 1 4 3 2 1 L - 1 - 2 3 4 1 2 3
4
6. Determine the current blade pitch and the pin location for the new blades
Table 3 - Condenser Fan Pin Location
Table 4 - Condenser Fan Pin Location
7. Replace fan blades in the new pin
location and reassemble the fan
Replace the blades with the pin in the 1, 2, 3, or 4 groove position of either the HUB or RET. Assemble the fan making sure to place the blades in their previous blade sockets, to match up the previous orientation of HUB and RET and to replace any balancing weights in their previous locations. Tighten bolts in a cross pattern to 5-6 ft-lbs. of torque.
Multi-Wing W Series Black Glass Reinforced Polypropylene Fan Blade Pitch Angle Setting Instructions
Contact the AAON parts department to acquire the new pitch pins for the fan blades.
Note original position of retaining plates, center boss and all hardware including additional hardware used for balancing.
1. Remove all the bolts and nuts.
2. Determine blade rotation – on the concave side of the blade is a blade marking showing 6WR, 6WL, 7WL, 7WR, or 9WR.
The “L” and “R” denote the rotation of the
blade.
3. Replace the pitch insert in the blade root with an insert of the desired pitch.
Figure 13 - Pitch Insert
4. Replace blades to their original location.
5. Replace all nuts, bolts, and washers on the fan hub.
6. Replace retaining plates and center boss to original location.
7. Tighten nuts and bolts to 14 ft-lbs of torque.
Page 29
29
Bushing
Tightening Torque
(in-lbs.)
H X 1.125"
95
H X 1.375"
95
SH X 1.125"
108
SH X 1.375"
108
SD X 1.125"
108
SD X 1.375"
108
SD X 1.625"
108
SD X 1.875"
108
SK X 2.125"
180
Fan Assembly Bushings
The fan assembly bushings should be tightened to the specifications listed in the following table.
Table 5 - Fan Assembly Bushing Torque
Specifications
Page 30
30
Circuit Loading
Max. Pressure Drop
100%
10 psig
50%
5 psig
The Clean Air Act of 1990 bans the intentional venting of refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
CAUTION
Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used in hydrofluorocarbon (HFC) refrigeration systems. Refer to the compressor label for the proper compressor lubricant type.
CAUTION

Maintenance

General

Qualified technicians must perform routine service checks and maintenance. This includes reading and recording the condensing and suction pressures and checking for normal sub-cooling and superheat.
Air-cooled condenser units require maintenance schedules/procedures. Unit specific instructions are included in this manual.

Compressors

The scroll compressors are fully hermetic and require no maintenance except keeping the shell clean.

Refrigerant Filter Driers

Each refrigerant circuit contains a filter drier. Replacement is recommended when there is excessive pressure drop across the assembly or moisture is indicated in a liquid line sight glass.
Table 6 - Filter Drier Maximum Pressure
Drop

Adjusting Refrigerant Charge

All AAON CN Series condensing units are shipped with a 15 lb refrigerant charge per refrigeration system and will not be the full system charge. Adjusting the charge of a system will be required.
Adjusting the charge of a system in the field must be based on determination of liquid sub-cooling and evaporator superheat. On a system with an expansion valve liquid sub­cooling is more representative of the charge
than evaporator superheat but both measurements must be taken.
Before Charging
Refer to the unit nameplate as a reference when determining the proper refrigerant charge.
Unit being charged must be at or near full load conditions before adjusting the charge.
Units equipped with hot gas bypass must have the hot gas bypass valve closed to get the proper charge.
After adding or removing charge the system must be allowed to stabilize, typically 10-15 minutes, before making any other adjustments.
The type of unit and options determine the ranges for liquid sub-cooling and evaporator superheat. Refer to Table 7 when determining the proper sub-cooling.
Page 31
31
Air-Cooled Condenser
Sub-Cooling
12-18°F
Sub-Cooling with
Hot Gas Reheat
15-22°F
Superheat
8-15°F
Expansion valves must be adjusted to approximately 10-15°F of suction superheat. Failure to have sufficient superheat will damage the compressor and void the warranty.
CAUTION
For units equipped with low ambient (0°F) option see the special charging instructions at the end of this section.
Checking Liquid Sub-cooling
Measure the temperature of the liquid line as it leaves the condenser coil.
Read the gauge pressure at the liquid line close to the point where the temperature was taken. You must use liquid line pressure as it will vary from discharge pressure due to condenser coil pressure drop. Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Subtract the measured liquid line temperature from the saturated temperature to determine the liquid sub-cooling.
Compare calculated sub-cooling to the table below for the appropriate unit type and options.
Checking Evaporator Superheat
Measure the temperature of the suction line close to the compressor.
Read gauge pressure at the suction line close to the compressor.
Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Subtract the saturated temperature from the measured suction line temperature to determine the evaporator superheat.
For refrigeration systems with tandem scroll compressors, it is critical that the suction superheat setpoint on the expansion valve is set with one compressor running. The suction superheat should be 10-13°F with one compressor running. The suction
superheat will increase with both compressors in a tandem running. Inadequate suction superheat can allow liquid refrigerant to return to the compressors which will wash the oil out of the compressor. Lack of oil lubrication will destroy a compressor. Liquid sub-cooling should be measured with both compressors in a refrigeration system running.
Compare calculated superheat to Table 7 for the appropriate unit type and options.
Table 7 - Acceptable Refrigeration Circuit
Values
Adjusting Sub-cooling and Superheat Temperatures
The system is overcharged if the sub-cooling temperature is too high and the evaporator is fully loaded (low loads on the evaporator result in increased sub-cooling) and the evaporator superheat is within the temperature range as shown in Table 7 (high superheat results in increased sub-cooling)
Correct an overcharged system by reducing the amount of refrigerant in the system to lower the sub-cooling.
Page 32
32
DO NOT OVERCHARGE!
Refrigerant overcharging leads to excess refrigerant in the condenser coils resulting in elevated compressor discharge pressure.
CAUTION
DO NOT OVERCHARGE!
Refrigerant overcharging leads to excess refrigerant in the condenser coils resulting in elevated compressor discharge pressure.
CAUTION
The system is undercharged if the superheat is too high and the sub-cooling is too low.
Correct an undercharged system by adding refrigerant to the system to reduce superheat and raise sub-cooling.
If the sub-cooling is correct and the superheat is too high, the expansion valve may need adjustment to correct the superheat.
Special Low Ambient Option Charging Instructions
For units equipped with low ambient refrigerant flood back option being charged in the summer when the ambient temperature is warm:
Once enough charge has been added to get the evaporator superheat and sub-cooling values to the correct setting more charge must be added. Add approximately 80% of the receiver tank volume to the charge to help fill the receiver tank. The additional charge is required for the system when running in cold ambient conditions.
For units equipped with low ambient refrigerant flood back option being charged in the summer when the ambient temperature is cold:
Once enough charge has been added to get the evaporator superheat and sub-cooling values to the correct setting more charge
may need to be added. If the ambient temperature is 0°F no more charge is required. If the ambient temperature is around 40°F add approximately 40% of the receiver tank volume.
The unit will have to be checked for proper operation once the ambient temperature is above 80°F.
Page 33
33
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
20
78.3
47
134.7
74
213.7
101
321.0
128
463.2
21
80.0
48
137.2
75
217.1
102
325.6
129
469.3
22
81.8
49
139.7
76
220.6
103
330.2
130
475.4
23
83.6
50
142.2
77
224.1
104
334.9
131
481.6
24
85.4
51
144.8
78
227.7
105
339.6
132
487.8
25
87.2
52
147.4
79
231.3
106
344.4
133
494.1
26
89.1
53
150.1
80
234.9
107
349.3
134
500.5
27
91.0
54
152.8
81
238.6
108
354.2
135
506.9
28
92.9
55
155.5
82
242.3
109
359.1
136
513.4
29
94.9
56
158.2
83
246.0
110
364.1
137
520.0
30
96.8
57
161.0
84
249.8
111
369.1
138
526.6
31
98.8
58
163.8
85
253.7
112
374.2
139
533.3
32
100.9
59
166.7
86
257.5
113
379.4
140
540.1
33
102.9
60
169.6
87
261.4
114
384.6
141
547.0
34
105.0
61
172.5
88
265.4
115
389.9
142
553.9
35
107.1
62
175.4
89
269.4
116
395.2
143
560.9
36
109.2
63
178.4
90
273.5
117
400.5
144
567.9
37
111.4
64
181.5
91
277.6
118
405.9
145
575.1
38
113.6
65
184.5
92
281.7
119
411.4
146
582.3
39
115.8
66
187.6
93
285.9
120
416.9
147
589.6
40
118.1
67
190.7
94
290.1
121
422.5
148
596.9
41
120.3
68
193.9
95
294.4
122
428.2
149
604.4
42
122.7
69
197.1
96
298.7
123
433.9
150
611.9
43
125.0
70
200.4
97
303.0
124
439.6
44
127.4
71
203.6
98
307.5
125
445.4
45
129.8
72
207.0
99
311.9
126
451.3
46
132.2
73
210.3
100
316.4
127
457.3
Table 8 - R-410A Refrigerant Temperature-Pressure Chart
Page 34
34
Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
WARNING
High velocity water from a pressure washer or compressed air should only be used at a very low pressure to prevent fin and/or coil damages. The force of the water or air jet may bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdowns may occur.
CAUTION

Lubrication

All original motors and bearings are furnished with an original factory charge of lubrication.

Air-Cooled Condenser

The air-cooled condenser section rejects heat by passing outdoor air over the fin tube coils for cooling of the hot refrigerant gas from the compressors. The heated air will discharge from the top of the section through the axial flow fans.
The condenser coils should be inspected yearly to ensure unrestricted airflow. If the installation has a large amount of airborne dust or other material, the condenser coils should be cleaned according to the microchannel coil cleaning section.

E-Coated Coil Cleaning

Documented routine cleaning of e-coated coils is required to maintain coating warranty coverage.
Surface loaded fibers or dirt should be removed prior to water rinse to prevent restriction of airflow. If unable to back wash the side of the coil opposite of the coils entering air side, then surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins.
Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.
A monthly clean water rinse is recommended for coils that are applied in coastal or industrial environments to help to remove chlorides, dirt, and debris. It is very important when rinsing, that water temperature is less than 130°F and pressure is than 900 psig to avoid damaging the fin edges. An elevated water temperature (not to exceed 130°F) will reduce surface tension, increasing the ability to remove chlorides and dirt.
Quarterly cleaning is essential to extend the life of an e-coated coil and is required to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s regularly scheduled maintenance procedures. Failure to clean an e-coated coil will void the warranty and may result in reduced efficiency and durability.
For routine quarterly cleaning, first clean the coil with the below approved coil cleaner. After cleaning the coils with the approved cleaning agent, use the approved chloride remover to remove soluble salts and revitalize the unit.
Page 35
35
Harsh chemicals, household bleach, or acid cleaners should not be used to clean outdoor or indoor e-coated coils. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the e-coating. If there is dirt below the surface of the coil, use the recommended coil cleaners.
CAUTION
Detergents or coil cleaners are not recommended with microchannel condenser coils. Use pressureized clean water, with pressure not to
exceed 140 psi. Nozzle should be 6”
and 80° to 90° coil face. Failure to do so could result in coil damage.
CAUTION

Microchannel Coil Cleaning Documented routine cleaning of microchannel coils with factory provided e­coating is required to maintain coating warranty coverage. See E-Coated Coil Cleaning section.

Air cooled heat exchangers may include microchannel coils. Only clean water is recommended for cleaning microchannel coils. The water pressure used to clean should not exceed 140 psi, from no closer than 3 inches from the coils, and with the water aimed perpendicular to the coils.
Field installed coil coatings are not recommended with microchannels.
Only clean water is recommended for cleaning microchannel coils. However, if solutions are mandatory to clean the unit, a cleaning solution with a pH between 5 and 9
that does not contain chlorides, sulfates, copper, iron, nickel, or titanium is required.
Field installed coil coatings are not recommended with microchannel coils.

Service

If the unit will not operate correctly and a service company is required, only a company with a Factory Trained Service Technician qualified and experienced in air conditioning is permitted to service the systems to keep warranties in effect.

Replacement Parts

Parts for AAON equipment may be obtained from your local AAON sales representative. When ordering parts reference the unit serial number and part number.

AAON Warranty, Service and Parts Department

2424 S. Yukon Ave. Tulsa, OK 74107 Ph: 918-583-2266 Fax: 918-382-6364 www.aaon.com
Note: Before calling, the Factory Trained Service Technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit
Page 36
36

Refrigerant Piping Diagrams

Figure 14 - A/C Only Piping, AHU Above CU
Page 37
37
Figure 15 - A/C Only Piping, AHU Below CU
Page 38
38
Figure 16 - Modulating Hot Gas Reheat Piping, AHU Above CU
Page 39
39
Figure 17 - Modulating Hot Gas Reheat Piping, AHU Below CU
Page 40
40
Figure 18 - Hot Gas Bypass Piping, AHU Above CU
Page 41
41
Figure 19 - Hot Gas Bypass Piping, AHU Below CU
Page 42
42
Figure 20 - Modulating Hot Gas Reheat with Hot Gas Bypass Piping, AHU Above CU
Page 43
43
Figure 21 - Modulating Hot Gas Reheat with Hot Gas Bypass Piping, AHU Below CU
Page 44
44
Job Name:_______________________________________________
Date:______________
Address:______________________________________________________________________
______________________________________________________________________________
Model Number:_________________________________________________________________
Serial Number:_____________________________________________
Tag:_______________
Startup Contractor:______________________________________________________________
Address:______________________________________________________________________
_______________________________________________________
Phone:______________
Installing contractor should verify the following items.
1. Is there any visible shipping damage?
Yes No
2. Is the unit level?
Yes No
3. Are the unit clearances adequate for service and operation?
Yes No
4. Do all access doors open freely and are the handles operational?
Yes No
5. Have all shipping braces been removed?
Yes No
6. Have all electrical connections been tested for tightness?
Yes No
7. Does the electrical service correspond to the unit nameplate?
Yes No
8. On 208/230V units, has transformer tap been checked?
Yes No
9. Has overcurrent protection been installed to match the unit nameplate
requirement?
Yes No
10. Have all set screws on the fans been tightened?
Yes No
11. Do all fans rotate freely?
Yes No
Ambient Dry Bulb Temperature ________°F
Ambient Wet Bulb Temperature ________°F
Pre Startup Checklist

CN Series Startup Form

Ambient Temperature
Page 45
45
Check Rotation
Number
Model #
L1
L2
L3
Head
Pressure
PSIG
Suction
Pressure
PSIG
Crankcase
Heater
Amps
1 2 3 4
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Compressors/DX Cooling
Refrigeration System 1 - Cooling Mode
Refrigeration System 2 - Cooling Mode
Refrigeration System 3 - Cooling Mode
Refrigeration System 4 - Cooling Mode
Page 46
46
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
2
3
4
5
6
7
8
Condenser Fans
Page 47
47
Entry Date
Action Taken
Name/Tel.

Maintenance Log

This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper start-up, maintenance and servicing of the equipment falls to the owner and qualified licensed technician.
Page 48
48

Literature Change History

March 2014
Initial version.
Page 49
Page 50
Page 51
Page 52
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
CN Series
Installation, Operation, &
Maintenance
V28960 · Rev. A · 140331
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.
Copyright © AAON, all rights reserved throughout the world.
AAON® and AAONAIRE
®
are registered trademarks of AAON, Inc., Tulsa, OK.
Loading...