If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
WARNING
FOR YOUR SAFETY
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
Installation, Operation,
& Maintenance
3
Table of Contents
Codes and Ordinances ............................................................................................................... 13
Receiving Unit ........................................................................................................................... 13
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
electrical power to the furnace.
More than one disconnect may be
provided.
When servicing controls, label all
wires prior to disconnecting.
Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with
key-lock or nut and bolt.
WARNING
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections
and shut off valves.
CAUTION
7
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
WARNING
WARNING
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNING
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
CAUTION
8
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches that
allow locks. Door latches are shipped
with a nut and bolt requiring tooled
access. If the shipping hardware is
not replaced with a pad lock, always
re-install the nut and bolt after closing
the door to maintain tooled access.
CAUTION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service technician. Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should be checked for proper
operation. Alterations should only be
made at the unit power connection
CAUTION
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not use alkaline chemical coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
CAUTION
9
Some chemical coil cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with the manufacturer’s usage
instructions. Failure to follow
instructions may result in equipment
damage, injury or death.
WARNING
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
CAUTION
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
1. Startup and service must be performed
by a Factory Trained Service Technician
2. The unit is for outdoor use only. See
General Information section for more
information.
3. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
5. Keep this manual and all literature
safeguarded near or on the unit.
CN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN A -
055
- A - 0 -
3 - C A 0 0 E : 0 - 0 0 - E 0 - D 0 - 0 0 0 - 0 - D A 0 0 - 0
0
0 0 J 0 0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
10
CN Series Feature String Nomenclature
MODEL OPTIONS
Series and Generation
CN
Major Revision
A
Unit Size
055 = 55 ton Capacity
065 = 65 ton Capacity
075 = 75 ton Capacity
090 = 90 ton Capacity
105 = 105 ton Capacity
120 = 120 ton Capacity
130 = 130 ton Capacity
140 = 140 ton Capacity
Series
A = 55-75 ton units
B = 90-105 ton units
C = 120-140 ton units
C = R-410A VFD Compatible Scroll Compressor
F = R-410A VFD Compatible Tandem Scroll
Compressor
A2: Condenser Style
A = Air-Cooled Microchannel Condenser
A3: Configuration
0 = Standard
A4: Coating
0 = Standard
E = Polymer E-coated Condenser Coil
A5: Staging
A = 1 Variable Capacity Comp + 1 On/Off Comp
B = 2 Variable Capacity Comp + 2 On/Off Comp
E = All Variable Capacity Compressors
J = 2 On/Off Refrigeration Systems
K= 1 Variable Capacity Refrigeration Systems + 1
On/Off Refrigeration System
L= 2 Variable Capacity Refrigeration Systems
UNIT FEATURE OPTIONS
1: Unit Orientation
A = Vertical Condenser Discharge with End Control
Panel
2A: Refrigeration Control
0 = Standard
B = Fan Cycling
C = Adjustable Fan Cycling
D = Adjustable Compressor Lockout
K = Options B + D
M = Options C + D
2B: Blank
0 = Standard
3A: Refrigeration Options
0 = None
D = Hot Gas Bypass Non-Variable Compressors
[HGBNV]
E = Modulating Hot Gas Reheat [MHGR]
L = Options D + E
3B: Blank
0 = Standard
CN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN A -
055
- A - 0 -
3 - C A 0 0 E : 0 - 0 0 - E 0 - D 0 - 0 0 0 - 0 - D A 0 0 - 0
0
0 0 J 0 0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
11
4: Refrigeration Accessories
0 = None
A = Sight Glass
B = Compressor Isolation Valves
C = Options A + B
D = Flooded Condenser 0°F Low Ambient Controls One Circuit
E = Options A + D
F = Options B + D
G = Options A + B + D
H = Flooded Condenser 0°F Low Ambient Controls Two Circuit
J = Options A + H
K = Options B + H
L = Options A + B + H
M = Flooded Condenser 0°F Low Ambient Controls Three Circuit
N = Options A + M
P = Options B + M
Q = Options A + B + M
R = Flooded Condenser 0°F Low Ambient Controls Four Circuit
S = Options A + R
T = Options B + R
U = Options A + B + R
5: Blank
0 = Standard
6A: Unit Disconnect Type
0 = Standard Single Point Power Block
A = Single Point Power Non-Fused Disconnect
6B: Disconnect Size
J = 60 amps
N = 100 amps
R = 150 amps
U = 225 amps
Z = 400 amps
3 = 600 amps
5 = 800 amps
7 = 1200 amps
6C: Blank
0 = Standard
7: Accessories
0 = None
B = Phase & Brown Out Protection
D = Suction Pressure Transducer All Refrigeration
Circuits
L = Options B + D
8A: Control Sequence
B = VAV Single Zone Unit Controller - VAV Cool +
CAV Heat
C = VAV Single Zone Unit Controller - VAV Cool +
VAV Heat
D = VAV Unit Controller - VAV Cool + VAV Heat
E = CAV Unit Controller - CAV Cool + CAV Heat
F = MUA Unit Controller - CAV Cool + CAV Heat
M = Field Installed DDC Controls by Others
N = Field Installed DDC Controls w/ Isolation Relays
P = Factory Installed DDC Controls Furnished by
Others w/ Isolation Relays (SPA)
8B: Control Supplier
0 = AAON Refrigeration System Supervisory
Controls
A = WattMaster Orion Control System
C = WattMaster Orion Control System (Main
Controller in Air Handler)
8C: Control Supplier Options
0 = Standard
8D: BMS Connection & Diagnostics
0 = Standard
9: Blank
0 = Standard
10: Blank
0 = Standard
CN Series Feature String Nomenclature
Model Options
:
Unit Feature Options
GEN
MJREV SIZE SERIES MNREV VLT A1
A2
A3
A4
A5
1 2A
2B 3A
3B 4 5
6A
6B
6C 7 8A
8B
8C
8D 9
10
11
12
13
14
15
CN A -
055
- A - 0 -
3 - C A 0 0 E : 0 - 0 0 - E 0 - D 0 - 0 0 0 - 0 - D A 0 0 - 0
0
0 0 J 0 0
0 0 0 0 0 0 B
16
17
18
19
20
21
22
12
11: Maintenance Accessories
0 = None
A = 115VAC Convenience Outlet - Factory Wired
B = 115VAC Convenience Outlet - Field Wired
C = Service Access Lights
E = Remote Unit Start/Stop Terminals
F = Options A + C
H = Options A + E
J = Options B + C
L = Options B + E
N = Options C + E
R = Options A + C + E
U = Options B + C + E
12: Code Options
0 = Standard ETL US Listing
A = Chicago Code
B = ETL US + Canada Listing
13: Air-Cooled Condenser
H = Condenser Coil Guards + Three Phase
Condenser Fan Motor
J = Condenser Coil Guards + Three Phase Condenser
Fan Motor + VFD Controlled Condenser Fans (35°F
Low Ambient
21: Warranty
0 = Standard Warranty
D = Extended Compressor Warranty Years 2-5
22: Paint and Special Pricing Authorization
B = Premium AAON Gray Paint Exterior
E = Premium AAON Gray Paint Exterior + Shrink
Wrap
X = SPA + Option B
1 = SPA + Option E
4 = SPA + Special Exterior Paint Color
7 = SPA + Special Exterior Paint Color + Shrink
Wrap
13
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
CAUTION
Coils and sheet metal surfaces
present sharp edges and care must
be taken when working with
equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING
WARNING
General Information
AAON CN Series condensing units are
complete air-cooled condensing units
ranging from 55 to 140 tons of cooling
capacity. They are assembled, wired, and
tested.
Codes and Ordinances
CN Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of CN Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
14
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CRANKCASE HEATER
OPERATION
Units may be equipped with
compressor crankcase heaters,
which should be energized at least
24 hours prior to cooling operation, to
clear any liquid refrigerant from the
compressors.
CAUTION
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To prevent motor overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. All motors, to
include and not be limited to pump
motors and condenser fan motors,
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
at the unit power connection.
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the
warranty.
Never turn off the main power supply to the
unit, except for complete shutdown. When
power is cut off from the unit, any
compressors using crankcase heaters cannot
prevent refrigerant migration. This means
the compressor will cool down, and liquid
refrigerant may accumulate in the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored if liquid enters the
compressor.
Before unit operation, the main power
switch must be turned on for at least 24
hours for units with compressor crankcase
heaters. This will give the crankcase heater
time to clear any liquid accumulation out of
the compressor before it is required to run.
Never cut off the main power supply to the
unit, except for complete shutdown. Always
control the system from the building
management system, or control panel, never
at the main power supply (except for
emergency or for complete shutdown of the
system).
Scroll compressors must be on a minimum
of 5 minutes and off for a minimum of 5
minutes. The cycle rate must be no more
than 6 starts per hour.
15
Compressor life will be seriously shortened
by reduced lubrication, and the pumping of
excessive amounts of liquid oil and liquid
refrigerant.
Wiring Diagrams
A complete set of unit specific wiring
diagrams in both ladder and point-to-point
form are laminated in plastic and located
inside the control compartment door.
General Maintenance
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the condensing unit.
This includes reading and recording suction
pressures and checking for normal subcooling and superheat. See the air-cooled
condenser sections in this manual for
specific details.
16
Location
Unit Size
55-140 tons
Front -
(Controls Side)
60”
Left Side
72”
Right Side
72”
Top
Unobstructed
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
CAUTION
The base beneath the condenser
section is open and must be
considered when mounting on a curb.
CAUTION
Installation
Unit Placement
The AAON CN Series is designed for
outdoor applications and mounting at
ground level or on a rooftop. It must be
placed on a level and solid foundation that
has been prepared to support its weight.
The placement relative to the building air
intakes and other structures must be
carefully selected. Be sure to observe the
dimensions that are on the rating plate of the
condensing unit for operational and service
clearances.
Table 1 - Service Clearances
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate
area around condenser must remain free of
debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb and Steel Mount Installation
Make openings in the roof decking large
enough to allow for water piping, electrical
penetrations, and workspace only. Do not
make openings larger than necessary. Set the
curb to coincide with the openings. Make
sure curb is level.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation
details.
Units require rail support along all four sides
of the unit base.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line. Care must
also be taken to protect the coil and fins
from damage due to vandalism or other
causes.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used
between the curb and the unit to reduce
vibration from the unit to the building.
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.