General ……………………………………………………………………………………………………………...
Compressors………………………………………………………………………………………………………...
Refrigerant Filter Driers……………………………………………………………………………………………..
Evaporator/Heat Exchanger…………………………………………………………………………….…………...
Charging Refrigerant ………………………………………………………………………………………………..
Checking Liquid Sub-Cooling……………………………………………………………………………………… Checking Evaporator Superheat…………………………………………………………………………………….
Adjusting Sub-cooling and Superheat Temperatures……………………………………………………………….
Special Charging Instructions……………………………………………………………………………………….
Lubrication……………………………………………………………….……………………………………...…..
Service Information…………………………………………………….……………………………………………
14
14
14
14
15
15
15
15
16
16
16
17
EVAPORATIVE-COOLED CONDENSER SECTION……………………………………………………………………...
General Information…………………………………………………………………………………………………
Pre Start-Up…………………………………………………………………………………………………………
Maintenance Recommendations…………………………………………………………………………………….
Water Quality………………………………………………………………………………………………………..
AIR-COOLED CONDENSER SECTION…………………………………………………………………………………...
REFRIGERANT PIPING FOR CL SERIES…………………………..………………………………….………..…….......
Equivalent Line Length…………………………………………………………………………………….……….
Liquid Line Sizing…………………………………………………………………...……………………………...
Suction Line Sizing……………………………………………………………………………………..…………...
Hot Gas Bypass Line Sizing..………………………………………………………………….………….………... Predetermined Line Sizes…………………………………………………………………………………………...
TABLE RP-1 Predetermined Line sizes for Dual Circuit CL units with R-410A……………………….………….
TABLE RP-2 Predetermined Line sizes for Dual Circuit CL units with R-22………………………….…………..
TABLE RP-3 Predetermined Line sizes for Single Circuit CL units with R-410A………………….………..
TABLE RP-4 Predetermined Line sizes for Single Circuit CL units with R-22 ……………………….…………..
FIGURE RP-1 Riser height versus total equivalent line length Dual Circuit CL Units with R-410A .….…………
FIGURE RP-2 Riser height versus total equivalent line length Dual Circuit CL Units with R-22….. ….…………
FIGURE RP-3 Riser height versus total equivalent line length Single Circuit CL Units with R-410A ……………
FIGURE RP-4 Riser height versus total equivalent line length Single Circuit CL Units with R-22… ……………Hot Gas Bypass Line Routing Diagrams……………………………………………………………………………
32
33
CL SERIES STARTUP FORM………………………………………………………………………………………………
53
Literature Change History……………………………………………………………………………………………………..
56
It is the intent of AAON, Inc. to provide accurate and current specification information. However, in the
interest of product improvement, AAON, Inc. reserves the right to change pricing, specifications, and/or
design of its products without notice, obligation or liability
Single Point Power Connection
Air-Cooled or Evaporative Condensers
Environmentally Friendly
R-410A Refrigerant
Extended Life
2,500 Hour Salt Spray Tested Exterior
Corrosion Paint
Optional 5 Year Non-Prorated Compressor
Warranty
Sloped Condenser Coils with Outer Protection
5
GENERAL DESCRIPTION
All AAON 'CL Series' condensers are factory
assembled, wired, and charged with 15 lbs. of
refrigerant per system. Models are available for
air-cooled and evaporative-cooled applications.
Unpacking:
When received, the unit should be checked for
damage that might have occurred in transit. If
damage is found it should be noted on the
carrier’s Freight Bill. A request for inspection by
carrier’s agent should be made in writing at once.
Also, check the unit nameplate to ensure the
correct model size and voltage have been
received to match the job requirements.
the compressor. Since the compressor is designed
to pump refrigerant gas, damage may occur when
power is restored.
• Before unit operation, the main power switch
must be turned on for at least twenty four hours
for units with compressor crankcase heaters. This
will give the crankcase heater time to clear any
liquid accumulation out of the compressor before
it is required to run.
• Always control the system from the thermostat,
or control panel, never at the main power supply
(except for emergency or for complete shutdown
of the system).
• Improper installation, adjustment, alteration,
service, or maintenance can cause property
damage, personal injury or loss of life.
Installation and service must be performed by a
qualified installer, service agency or if gas fired
units, the gas supplier. Refer to installation
instructions provided with the unit and this
manual.
• The compressors must be on a minimum of 4
minutes and off for a minimum of 5 minutes. The
cycle rate must be no more than 8 starts per hour.
OWNER'S INFORMATION
Warning:
• Failure to observe the following instructions
will result in premature failure of your system,
and possible voiding of the warranty.
• Never cut off the main power supply to the unit,
except for complete shutdown. When power is
cut off from the unit, any compressors using
crankcase heaters cannot prevent refrigerant
migration. This means the compressor will cool
down, and liquid refrigerant may accumulate in
The compressor life will be seriously
shortened by reduced lubrication, and the
pumping of excessive amounts of liquid oil
and refrigerant.
Wiring Diagrams:
• A complete set of unit specific wiring diagrams
in both ladder and point-to-point form are
laminated in plastic and located inside the control
compartment door.
6
Location
Unit Size
045-135
134-230
Front - Vestibule Door Side
100"
142"
Back - Opposite of Front
100"
142"
Left Side - Condenser End
100"
100"
Right Side - Opposite of Left
100"
100"
Top
UNOBSTRUCTED
OWNER'S INFORMATION cont.
General Maintenance:
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks on
the performance of the condenser. This includes
reading and recording suction pressures and
checking for normal sub-cooling and superheat.
See the evaporative-cooled condenser and aircooled condenser sections in this manual for
specific details.
INSTALLATION
Lifting and Handling:
• If cables or chains are used to hoist the unit
they must be the same length and care should be
taken to prevent damage to the cabinet.
• Before lifting unit, be sure that all shipping
material has been removed from unit. Secure
hooks and cables at all lifting points/lugs
provided on the unit.
• Do not push, pull or lift the unit from anything
other than its base.
UNIT MUST BE RIGGED AT ALL
MARKED LIFTING POINTS (Typical)
Condenser Placement:
• The AAON condenser is designed for outdoor
applications and mounting at ground level or on
a rooftop. It must be placed on a level and solid
foundation that has been prepared to support its
weight. When installed at ground level, a onepiece concrete slab should be used with footings
that extend below the frost line.
• With ground level installation, care must be
taken to protect the coil fins from damage due to
vandalism or other causes.
• The placement relative to the building air
intakes and other structures must be carefully
selected. Be sure to observe the dimensions that
are on the rating plate of the condenser for
operational and service clearances, which will
appear as follows:
Service Clearances
• Condenser coils and fans must be free of any
obstructions in order to start and operate properly
with a correct amount of airflow.
• For proper unit operation, the immediate area
around condenser must remain free of debris that
may be drawn in and obstruct airflow in the
condensing section.
• Consideration must be given to obstruction
caused by snow accumulation when placing the
unit.
Compressor Compartment Exhaust Fan:
Prior to unit operation the compressor
compartment exhaust fan shipping support
MUST BE removed from the exterior of the unit.
The exhaust fan also requires the installation of
the exterior rain hood provided with the unit.
Mounting Isolation:
• For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Doors:
• A lockable access door is provided to the
compressor and electrical compartment.
• A light switch is on the wall of the compressor
control compartment.
7
INSTALLATION cont.
Low Ambient Operation:
• The AAON low ambient (condenser floodback) system is used to operate a refrigerant
system below 25°F outside air temperature. As
the ambient temperature drops, the condenser
becomes more effective therefore lowering the
head pressure. When the head pressure gets too
low, there will be insufficient pressure to operate
the expansion valve properly. During low
ambient temperatures, it is difficult to start a
system because the refrigerant will migrate to the
cold part of the system (condenser) and make it
difficult for refrigerant to flow.
• The AAON low ambient system maintains
normal head pressure during periods of low
ambient by restricting liquid flow from the
condenser to the receiver, and at the same time
bypassing hot gas around the condenser to the
inlet of the receiver. This backs liquid
refrigerant up into the condenser reducing its
capacity that in turn increases the condensing
pressure. At the same time the bypassed hot gas
raises liquid pressure in the receiver, allowing
the system to operate properly.
• There are different types of low ambient control
used. The following describe the different
systems. Inspect the unit to determine the system
used.
LAC Valve:
The LAC valve is a non-adjustable three way
valve that modulates to maintain receiver
pressure. As the receiver pressure drops below
the valve setting (180 psig for R-22 and 295 psig
for R-410A), the valve modulates to bypass
discharge gas around the condenser. The
discharge gas warms the liquid in the receiver
and raises the pressure to the valve setting. The
following schematic shows an example system
using the LAC valve.
Piping Schematic of Example system using the LAC valve.
8
INSTALLATION cont.
OROA Valve:
This system uses a nonadjustable head pressure
control valve that performs the function of
limiting the flow of liquid refrigerant from the
condenser and at the same time regulates the
flow of the hot gas around the condenser to the
receiver. The valve setpoint is 180 psig. This
valve is called an OROA valve (Open on Rise of
Outlet pressure). The following schematic
shows an example system using the OROA
valve.
Piping Schematic of Example system using the OROA valve.
ORI/ORD Valves:
This system uses a two-valve arrangement. The
head pressure control valve is an inlet pressure
regulating valve and responds to changes in
condensing pressure. This valve is located in the
discharge of the condenser and is called an ORI
valve (Open on Rise of Inlet pressure). As the
ambient temperature drops, the condenser
capacity increases and the condensing pressure
falls, causing the ORI to modulate toward the
closed position. The condenser bypass valve is a
pressure differential valve that responds to
changes in the pressure differential across the
valve. This valve is called an ORD valve (Open
on Rise of Differential pressure). As the ORI
starts to restrict liquid flow from the condenser, a
pressure differential is created across the ORD.
When the differential reaches the setpoint, the
ORD starts to open and bypass hot gas to the
liquid line. The ORI valve is adjustable from 65
to 225 psig (factory setting of 180 psig). The
ORD is not adjustable. On refrigeration systems
that are too large for a single ORI and ORD
valve, there will be two ORI and two ORD
valves in parallel. The schematic on the
following page shows an example system using
the ORI/ORD valves.
9
PERCENTAGE OF CONDENSER TO BE FLOODED
Ambient
Temperature
(°F)
Evaporating Temperature (°F)
0°
10°
20°
30°
35°
40°
45°
50°
70°
40
24 0 0 0 0 0 0
60°
60
47
33
17
26
20
10
4
50°
70
60
50
38
45
40
33
28
40°
76
68
60
50
56
52
46
42
30°
80
73
66
59
64
60
55
51
20°
86
77
72
65
69
66
62
59
0°
87
83
78
73
76
73
70
68
-20°
91
87
82
77
80
79
76
73
INSTALLATION cont.
Piping Schematic of Example system using the ORI/ORD valve.
The pressure setting of the ORI valve determines
how well the system will operate. The proper
setting is a function of the specific system in
which is installed. Generally, the setting should
be equivalent to a condensing temperature of
90°F to 100°F or a receiver pressure equivalent
to a temperature of 80°F to 90°F. This means
that as the ambient temperature falls below 70°F,
the head pressure control valve will begin to
throttle. To adjust the ORI valve, remove the cap
and turn the adjustment screw with the proper
size hex wrench (1/4” for ORI-6 and 5/16” for
ORI-10). A clockwise rotation increases the
valve setting while a counter-clockwise rotation
decreases the setting. To obtain the desired
setting, a pressure gauge should be used at the
compressor discharge service valve so the effects
of any adjustment can be observed. Small
adjustments are recommended in order to allow
the system adequate time to stabilize after each
adjustment.
Condenser Flooding:
In order to maintain head pressure in the
refrigeration system, liquid refrigerant is backed
up in the condenser to reduce condenser surface.
The following chart shows the percentage that a
condenser must be flooded in order to function
properly at the given ambient temperature.
10
INSTALLATION cont.
During higher ambient temperatures the entire
condenser is required to condense refrigerant.
During these higher ambient temperatures, a
receiver tank is used to contain the refrigerant
that was required to flood the condenser during
low ambient operation. The receiver must be
sized to contain all of the flooded volume
otherwise there will be high head pressures
during higher ambient conditions.
Electrical:
• The single point electrical power connections
are made in the electrical control compartment.
• Check the unit data plate voltage to make sure
it agrees with the power supply. Connect power
to the unit according to the wiring diagram
provided with the unit.
• The power and control wiring may be brought
up through the utility entry. Protect the branch
circuit in accordance with code requirements.
Control wires and power should not be run inside
the same conduit. The unit must be electrically
grounded in accordance with the current National
Electric Code.
• Power wiring is to the unit terminal block or
main disconnect. All wiring beyond this point
has been done by the manufacturer and cannot be
modified without effecting the unit's
agency/safety certification.
Note: Startup technician must check motor
amperage to ensure that the amperage listed
on the motor nameplate is not exceeded.
Refrigerant Piping Connections
• CL condensing unit refrigerant piping
connections are located in the upper corner of the
service vestibule side of the unit (opposite the
condenser section) as shown in the figure.
• The piping connections are protected with a
shipping cover that must be removed prior to
copper connection and installation.
Evaporative-cooled Condenser Field Piping
Connections:
• There are two field water connections that must
be made for the evaporative-cooled condenser.
There is a ¾” PVC socket city make-up water
connection and a 2” PVC socket drain
connection (as shown on the next page). This
drain should connect to a sanitary sewer or other
code permitted drain. These connections can go
through the base or the wall of the unit.
• There is a cutout in the base with a cap that is
1” tall and the cap is sealed to the unit base to
prevent any leaks in the unit from penetrating
into the building. Any piping through the base
should go through a field cutout in this cap. The
pipes must be sealed to the cap once the piping is
complete to prevent any leaks in the unit from
penetrating into the building.
• A field cutout must be made in the wall if the
evaporative-cooled condenser piping is to go
through the unit wall. This cutout must be
sealed once the piping is installed to prevent
water from leaking into the unit.
11
Diagram of Evaporative-cooled condenser Section including field water connections and base cutout
tap
12
STARTUP
Pre-Startup:
After the installation and immediately before the
startup of the condenser be sure that these items
have been checked.
1. Verify that electrical power is available to the
unit.
2. Verify that any remote stop/start device is
requesting the condenser to start.
While performing the Startup, use the
Condensing Startup Form at the back of this
booklet to record motor amps and any other
comments.
Startup:
• Use the General Check List at the top of the
Startup Form to make a last check that all the
components are in place and the power supply is
energized.
Note: Condensing fan operation should start
with the first compressor.
• Cycle through all the compressors to confirm
that all are operating within tolerance.
• When unit is running, observe the system for a
complete operation cycle to verify that all
systems are functioning properly.
• While performing the check, use the Condenser
Startup Form to record observations of amps and
refrigerant pressures.
• When all is running properly, place the
controller in the Run mode and observe the
system until it reaches a steady state of operation.
Axial Flow Fans:
Multi-Wing Z Series Aluminum Fan Blade
Pitch Angle Setting Instructions:
Before You Begin, to maintain balance of fan:
• Mark the hub castings across a joint, so the fan
hub can be reassembled in the same orientation.
• Mark the location of any balancing weight.
Balancing weight will be on the outer bolt circle,
in the form of washers, and/or longer bolts, or an
additional balancing nut.
• Number the blades and blade sockets, so that
they are replaced into their original position.
• If possible, note the location of the pitch setting
pin in the blade socket, and whether pin is
located in the Hub or Retainer half of the fan.
Step 1. Determine Boss Location Code: “A” or
“B” The boss is the center section of the hub
through which the fan is mounted to the shaft,
and typically contains either setscrews or a
center-tapered hole where the bushing inserts.
Select boss location A or B:
A is the boss on air inlet, including AS
configurations.
B is the boss on air discharge, including BS.
For flange mounted fans, use boss location A for
R rotation fans, and boss location B for L
rotation fans.
note in which groove the pin is located. Refer to
groove number code diagram.
• Using diagrams in step 5, determine if the pin
was in the hub (HUB) or retainer side (RET) of
fan.
• Using table in step 4, find the possible blade
pitch.
• Using table in step 3, select your blade angle
based on whether your pin was in the HUB or
RET.
Step 3. Determine Hub/Retainer Code: “HUB”
or “RET”
Step 4. - Determine Groove Number: 1 or 2 or 3
or 4
Step 5. Final Assembly
Definition of HUB and RET for purposes of
instructions. For 2-piece hubset:
Using the HUB or RET code found in Step 3:
• If code is HUB, place the hub down on work
surface first (one or two pieces, depending on
above).
• If code is RET, place one retainer ring only
down on the work surface first. (A weighted
coffee can could be used to elevate the fan from
the work surface).
• Using the groove number, place the locking pin
in the groove number that was found in Step 4.
Insert Blades:
• Place the blade over the pin in the hub/retainer
blade socket, so that the pin also fits into the
appropriate pitch angle groove in the blade.
• Repeat for all blades.
• Assemble hub set together, aligning the match
marks that were made.
• Replace any balancing weight to its original
position.
14
STARTUP cont.
• To finish, tighten the bolts in a cross pattern to
5 to 6 ft-lbs of torque.
Multi-Wing W Series Black Glass Reinforced
Polypropylene Fan Blade Pitch Angle Setting
Instructions:
Step 1. Note original position of retaining plates,
center boss and all hardware including additional
hardware used for balancing.
Step 2. Remove all the bolts and nuts.
Step 3. Determine blade rotation – on the
concave side of the blade is a blade marking
showing 6WR, 6WL, 7WL, 7WR, or 9WR. The
“L” and “R” denote the rotation of the blade.
Step 4. Replace the pitch insert in the blade root
with an insert of the desired pitch.
Step 8. Tighten nuts and bolts to 14 ft-lbs of
torque.
SERVICING AND MAINTENANCE
General:
• Qualified technicians must perform routine
service checks and maintenance. This includes
reading and recording the condensing and
suction pressures and checking for normal subcooling and superheat (see charging information
beginning on page 14).
• Air-cooled and evaporative-cooled condenser
units require different maintenance
schedules/procedures. Unit specific instructions
for both types are included in this manual.
Compressors:
The scroll compressors are fully hermetic and
require no maintenance except keeping the shell
clean.
Refrigerant Filter Driers:
Each refrigerant circuit contains a replaceable
core filter drier. Replacement is recommended
when there is excessive pressure drop across the
assembly or moisture is indicated in a liquid line
sight glass.
Step 5. Replace blades to their original location.
Step 6. Replace all nuts, bolts, and washers on
the fan hub.
Step 7. Replace retaining plates and center boss
to original location.
The filter driers are provided with pressure taps
and shutoff valves for isolation when changing
the core. For safety purposes a service manifold
must be attached prior to filter maintenance.
15
SERVICING AND MAINTENANCE
cont.
Evaporator/Heat Exchangers:
Normally no maintenance or service work will be
required for a matching direct expansion
evaporator with a thermal expansion valve to
regulate refrigerant.
Charging Refrigerant:
• Charging a system in the field must be based on
determination of liquid sub-cooling and
evaporator superheat. On a system with a
thermostatic expansion valve liquid sub-cooling
is more representative of the charge than
evaporator superheat but both measurements
must be taken.
Before Charging:
• Refer to the Unit Nameplate to determine the
proper refrigerant to charge the system with.
• The unit being charged must be at or near full
load conditions before adjusting the charge.
• Units equipped with hot gas bypass must have
the hot gas bypass valve closed to get the proper
charge.
• Units equipped with hot gas reheat must be
charged with the hot gas valve closed while the
unit is in cooling mode.
• After adding or removing charge the system
must be allowed to stabilize, typically 10-15
minutes, before making any other adjustments.
• The type of unit and options determine the
ranges for liquid sub-cooling and evaporator
superheat. Refer to Table 1 when determining
the proper sub-cooling.
• The vertical rise of the liquid line must be
known in order to adjust the sub-cooling range
for proper charge.
• Units equipped with low ambient (0°F) option
see special charging instructions at the end of the
charging instructions.
Checking Liquid Sub-cooling:
1. Measure the temperature of the liquid line as
it leaves the condenser coil.
2. Read the gauge pressure reading of the liquid
line close to the point where the temperature was
taken. You must use liquid line pressure as it
will vary from discharge pressure due to
condenser coil pressure drop.
3. Convert the pressure obtained in Step 2 to a
saturated temperature using the appropriate
refrigerant temperature-pressure chart.
4. Subtract the measured liquid line temperature
in Step 1 from the saturated temperature in Step
3 to determine the liquid sub-cooling.
5. Compare calculated sub-cooling to TABLE 1.
for the appropriate unit type and options.
Checking Evaporator Superheat:
1. Measure the temperature of the suction line
close to the compressor.
2. Read gauge pressure at the suction line close
to the compressor.
3. Convert the pressure obtained in Step 2 to a
saturated temperature using the appropriate
refrigerant temperature-pressure chart.
4. Subtract the saturated temperature in Step 3
from the measured suction line temperature in
Step 1 to determine the evaporator superheat.
5. Compare calculated superheat to TABLE 1 for
the appropriate unit type and options.
16
SERVICING AND MAINTENANCE
TABLE 1
Sub-
cooling
(°F)
Superheat
(°F)
Sub-cooling
W/Hot Gas
Reheat (°F)
Air Cooled
Condenser
12-18*
8-15**
15-22*
Evaporative
Cooled
Condenser
6-10*
8-15**
8-12*
Water
Cooled
Condenser
6-10*
8-15**
8-12*
cont.
* Sub-cooling must be increased by 3°F per 20
feet of vertical liquid line rise for R-22 and 2°F
for R-410A
** Superheat will increase with long suction line
runs.
Adjusting Sub-cooling and Superheat
Temperatures:
The system is overcharged if:
1. the sub-cooling temperature is too high and
2. the evaporator is fully loaded (low loads on
the evaporator result in increased sub-cooling)
and
3. the evaporator superheat is within the
temperature range as shown in TABLE 1 (high
superheat results in increased sub-cooling)
Correct an overcharged system by reducing the
amount of refrigerant in the system to lower the
sub-cooling.
The system is undercharged if:
1. the superheat is too high and
2. the sub-cooling is too low
• Correct an undercharged system by adding
refrigerant to the system to reduce superheat and
raise sub-cooling.
• If the sub-cooling is correct and the superheat is
too high, the TXV may need adjustment to
correct the superheat.
Special Charging Instructions:
• For units equipped with low ambient refrigerant
flood back option being charged in the summer
when the ambient temperature is warm:
Once enough charge has been added to get the
evaporator superheat and sub-cooling values to
the correct setting more charge must be added.
Add approximately 80% of the receiver tank
volume to the charge to help fill the receiver
tank. The additional charge is required for the
system when running in cold ambient conditions.
• For units equipped with low ambient refrigerant
flood back option being charged in the winter
when the ambient temperature is cold:
1. Once enough charge has been added to get the
evaporator superheat and sub-cooling values to
the correct setting more charge may need to be
added. If the ambient temperature is 0°F no
more charge is required. If the ambient
temperature is around 40°F add approximately
40% of the receiver tank volume.
2. The unit will have to be checked for proper
operation once the ambient temperature is above
80°F.
Lubrication:
• All original motors and bearings are furnished
with an original factory charge of lubrication.
Certain applications require bearings be relubricated periodically. The schedule will vary
depending on operating duty, temperature
changes, or severe atmospheric conditions.
• Bearings should be re-lubricated at normal
operating temperatures, but not when running.
17
SERVICING AND MAINTENANCE
cont.
Rotate the fan shaft by hand and add only enough
grease to purge the seals. DO NOT
OVERLUBRICATE.
Service Information:
If the unit will not operate correctly and a service
company is required, only a company with
service technicians qualified and experienced in
both condensing units and air conditioning are
permitted to service the systems to keep
warranties in effect. If assistance is required, the
service technician must contact AAON.
Replacement Parts
Parts for AAON equipment may be obtained
from your local AAON representative. When
ordering parts reference the unit serial number
and part number.
AAON Warranty, Service and Parts
Department
2424 S. Yukon Ave.
Tulsa, OK 74107
Ph: 918-583-2266
Fax: 918-382-6364
www.aaon.com
Note: Before calling, technician should have
model and serial number of the unit available for
the service department to help answer questions
regarding the unit
EVAPORATIVE-COOLED
CONDENSER
• Evaporative cooling equipment rejects heat by
evaporating a portion of the recirculated water
spray and discharging it from the unit with the
hot, saturated air. As the spray water evaporates,
it leaves behind the mineral content and
impurities of the supply water. If these residuals
are not purged from the water distribution
system, they will become concentrated and lead
to scaling, corrosion, sludge build-up and
biological fouling.
• A water treatment monitoring and control
system has been furnished with this unit. Be sure
to read the complete manual that has been
furnished. All water treatment is a combination
of bleed water and chemical treatment for proper
control of the residuals and to prevent any
biological contamination.
GENERAL INFORMATION
Severe Service:
The following recommended maintenance
procedures are basic requirements for normal
operating environments. For severe operating
conditions, the frequency of inspection and
service should be increased. Air containing
industrial and chemical fumes, salt, dust, or other
airborne contaminates and particulates will be
absorbed by the recirculating water system and
may form solutions and deposits harmful to the
products and personnel.
Safety:
The recirculating water system contains chemical
additives for water quality control and biological
contaminants removed from the air by the
washing action of the water. Personnel exposed
to the saturated effluent, drift, or direct contact
should use proper precaution. Proper location of
the evaporative-cooled condenser requires good
judgment to prevent the air discharge from
entering fresh air intakes or to avoid allowing
contaminated building exhaust from entering the
condenser.
18
EVAPORATIVE-COOLED
CONDENSER cont.
Follow local and national codes in locating the
evaporative-cooled condenser but as minimum
the evaporative-cooled condenser sump must be
15 feet from the nearest intake.
Performance:
Improper location of the evaporative-cooled
condenser may seriously degrade the capacity of
the equipment. Make sure the equipment is
located such that discharge air from the
condenser does not enter the condenser air inlet.
Warranties:
Please refer to the limitation of warranties in
effect at the time of purchase.
Condenser Tube Inspection:
The coil is leak tested at 450 P.S.I.G. before
shipment. AAON will not be responsible for loss
of refrigerant. It is the responsibility of the
installer to verify that the system is sealed before
charging with refrigerant. If the unit is operated
during low ambient temperature conditions,
freeze protection for the recirculating water
system must be provided.
Freeze Protection:
In order to prevent water temperatures from
dropping below 50°F, this unit is equipped with a
variable frequency drive (VFD) on the fan
motors when the refrigeration system is
operating.
Recirculating Water System:
Electric sump heaters are available to keep the
sump water from freezing when the refrigeration
system is not operating. An electric resistance
heater is supplied in the vestibule when sump
heaters are selected.
Note: The condenser should not be operated
with the fan on and the pump cycled on and
off to maintain head pressure control under
any conditions. The unit is equipped with a
water temperature controller which varies fan
speed to maintain sump water temperature.
This unit is not equipped with a compressor
discharge pressure controller for fan speed
modulation and therefore can not be operated
without water flow.
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.