Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
Before servicing, disconnect all
electrical power to the furnace.
More than one disconnect may be
provided.
When servicing controls, label all
wires prior to disconnecting.
Reconnect wires correctly.
Verify proper operation after
servicing. Secure all doors with
key-lock or nut and bolt.
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to turn on unit.
Shut off main gas supply.
Do not touch any electric switch.
Do not use any phone in the
building.
Never test for gas leaks with an
open flame.
Use a gas detection soap solution
and check all gas connections
and shut off valves.
CAUTION
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
QUALIFIED INSTALLER
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
6
7
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
Electric shock hazard. Before
servicing, shut off all electrical power
to the unit, including remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in
hand mode or manual bypass.
Damage to personnel or equipment
can occur if left unattended. When in
hand mode or manual bypass mode
VFDs will not respond to controls or
alarms.
WARNING
WARNING
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical components. Only a
qualified licensed electrician or
individual properly trained in handling
live electrical components shall
perform these tasks.
Standard NFPA-70E, an OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate Personal Protective
Equipment (PPE) be worn, should be
followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide proper unit ground in
accordance with these code
requirements.
WARNING
Electric motor over-current protection
and overload protection may be a
function of the Variable Frequency
Drive to which the motors are wired.
Never defeat the VFD motor overload
feature. The overload ampere setting
must not exceed 115% of the electric
motors FLA rating as shown on the
motor nameplate.
CAUTION
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
Always use a pressure regulator,
valves and gauges to control
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
WARNING
Door compartments containing
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
CAUTION
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
8
1. Startup and service must be performed
by a Factory Trained Service
Technician.
2. The unit is for outdoor use only. See
General Information section for more
information.
3. Use only with type of the gas approved
for the boiler. Refer to the boiler rating
plate.
4. Provide adequate combustion ventilation
air to the boiler.
5. Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
6. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
A = 500 MBH Modulating High Flow
B = 750 MBH Modulating High Flow
C = 1,000 MBH Modulating High Flow
D = 1,500 MBH Modulating High Flow
E = 500 MBH Modulating Low Flow
F = 750 MBH Modulating Low Flow
G = 1,000 MBH Modulating Low Flow
H = 1,500 MBH Modulating Low Flow
FEATURE 1: BLANK
1A, 1B, 1C, 1D: BLANK
0000 = Standard
FEATURE 2: BLANK
0 = Standard
FEATURE 3: BOILER ACCESSORIES
0 = Standard
A = Glycol Boiler
B = Thermometers and Pressure Gauges
C = Options A + C
0=Standard, No Boiler Pump
A = 1 Pump/Barrel - Std Eff, 1170 RPM
B = 2 Single Pumps/Barrel - Std Eff, 1170 RPM
C = dualArm Pump/Barrel - Std Eff, 1170 RPM
D = 1 Pump/Barrel - Prem Eff, 1170 RPM
E = 2 Single Pumps/Barrel - Prem Eff, 1170 RPM
F = dualArm Pump/Barrel - Premium Eff, 1170 RPM
G = 1 Pump/Barrel w/ VFD - 1170 RPM
H = 2 Single Pumps/Barrel w/ 2 VFDs - 1170 RPM
J = dualArm Pump/Barrel w/ 2 VFDs - 1170 RPM
K = 1 Pump/Barrel - Std Eff, 1760 RPM
L = 2 Single Pumps/Barrel - Std Eff, 1760 RPM
M = dualArm Pump/Barrel - Std Eff, 1760 RPM
N = 1 Pump/Barrel - Prem Eff, 1760 RPM
P = 2 Single Pumps/Barrel - Prem Eff, 1760 RPM
Q = dualArm Pump/Barrel - Prem Eff, 1760 RPM
R = 1 Pump/Barrel w/ VFD - 1760 RPM
S = 2 Single Pumps/Barrel w/ 2 VFDs - 1760 RPM
T = dualArm Pump/Barrel w/ 2 VFDs - 1760 RPM
Y = 1 Pump/Barrel - Prem Eff - 3520 RPM
Z = 2 Single Pumps/Barrel - Prem Eff, 3520 RPM
1 = dualArm Pump/Barrel - Prem Eff, 3520 RPM
2 = 1 Pump/Barrel w/ VFD - 3520 RPM
3 = 2 Single Pumps/Barrel w/ 2 VFDs - 3520 RPM
4 = dualArm Pump/Barrel w/ 2 VFDs - 3520 RPM
6B: BUILIDNG PUMP SIZE
0 = Standard, No Boiler Pump
A = Pump 4360 1.5B
B = Pump 4360 2B
C = Pump 4360 2D
D = Pump 4380 1.5x1.5x6
E = Pump 4380 2x2x6
F = Pump 4380/4382 3x3x6
G = Pump 4380/4382 4x4x6
H = Pump 4380 1.5x1.5x8
J = Pump 4380 2x2x8
K = Pump 4380/4382 3x3x8
L = Pump 4380/4382 4x4x8
M = Pump 4380 5x5x8
N = Pump 4380/4382 6x6x8
P = Pump 4380 2x2x10
Q = Pump 4380/4382 3x3x10
R = Pump 4380/4382 4x4x10
S = Pump 4380/4382 6x6x10
T = Pump 4380/4382 8x8x10
U = Pump 4380 4x4x11.5
V = Pump 4380 5x5x11.5
W = Pump 4380 6x6x11.5
Y = Pump 4380 8x8x11.5
Z = Pump 4380 4x4x13
1 = Pump 4380 6x6x13
2 = Pump 4380 8x8x13
3 = Pump 4382 6x6x6
4 = Pump 4382 8x8x8
5 = Pump 4360 3D
6C: BUILDING PUMP MOTOR
0 = Standard, No Building Pump
A = 0.50 hp
B = 0.75 hp
C = 1 hp
D = 1.5 hp
E = 2 hp
F = 3 hp
G = 5 hp
H = 7.5 hp
J = 10 hp
K = 15 hp
L = 20 hp
M = 25 hp
N = 30 hp
P = 40 hp
Q = 50 hp
R = 60 hp
S = 75 hp
0 = Standard
A = 115V Outlet, Factory Wired
B = 115V Outlet, Field Wired
FEATURE 8: BLANK
0 = Standard
FEATURE 9: BLANK
0 = Standard
FEATURE 10: POWER OPTIONS
0 = Standard Power Block
A = Power Switch (225 Amps)
B = Power Switch (400 Amps)
C = Power Switch (600 Amps)
D = Power Switch (800 Amps)
E = Power Switch (1200 Amps)
FEATURE 11: SAFETY OPTIONS
A = Standard, Boiler w/ UL/FM/CSD-1 Certification
B = Boiler w/ IRI Gas Train
C = Boiler w/ IRI Gas Train and Proof of Closure
D = Boiler w/ Low Water Cutoff
E = Options B + D
F = Options C + D
FEATURE 12: CONTROLS
0 = Standard
B = Phase and Brown Out Protection
FEATURE 13: SPECIAL CONTROLS
0 = MCS Controller
G = MCS Controller w/ Modem
P = w/ BACnet Connection
Q = w/ Modbus Connection
R = w/ N2 Connection
S = w/ LonTalk Connection
T = w/ Automated Logic Connection
U = w/ BACnet Connection and Modem
V = w/ Modbus Connection and Modem
W = w/ N2 Connection and Modem
Y = w/ LonTalk Connection and Modem
Z = w/ Automated Logic Connection and Modem
FEATURE 14: COMPRESSION TANK
14A: BLANK
0 = Standard
14B: BOILER COMPRESSION TANK
0 = Standard - No Compression Tank
A = AX-15V
B = AX-20V
C = AX-40V
D = AX-60V
E = AX-80V
F = AX-100V
G = AX-120V
H = AX-180V
J = AX-200V
K = AX-240V
L = AX-260V
M = AX-280V
N = 1000-L
P = 1200-L
Q = 1600-L
R = 2000-L
FEATURE 15: OPTION BOXES
0 = Standard
A = 2ft. Option Box
B = 4ft. Option Box
C = 6ft. Option Box
D = 8ft. Option Box
E = 10ft. Option Box
F = 12ft. Option Box
0 = Standard - ETL U.S.A. Listing
A = MEA New York
H = ETL U.S.A. + Canada Listing
FEATURE 20: BLANK
0 = Standard
FEATURE 21: BLANK
0 = Standard
FEATURE 22: BLANK
0 = Standard
FEATURE 23: TYPE
B = Standard Paint
U = Special Price Authorization and Special Paint
X = Special Price Authorization w/ Standard Paint
13
General Information
Sheet metal surfaces present sharp
edges and care must be taken when
working with equipment.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING
WARNING
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
AAON BL Series boiler outdoor mechanical
rooms are complete self contained liquid
heating units. They are factory assembled,
wired, and run-tested.
Codes and Ordinances
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of BL Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes
and voltages have been received to match
the job requirements.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Outdoor Mechanical Room
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the
warranty.
Never turn off the main power supply to the
unit, except for complete shutdown.
Always control the system from the building
management system, or control panel, never
at the main power supply (except for
emergency or for complete shutdown of the
system).
14
Wiring Diagrams
A complete set of unit specific wiring
diagrams in both ladder and point-to-point
form are laminated in plastic and located
inside the control compartment door.
General Maintenance
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the boiler.
Boiler System
Boilers and pumping packages are factory
installed. The boiler system uses a
primary/secondary pumping package. There
can be 1-4 boilers in parallel and each boiler
has its own primary pump. The heating loop
must be designed to return at least 120°F
water to the boiler during normal operation.
Failure to return 120°F water to the boiler
will create condensation, which will reduce
the life of the heat exchanger and void the
boiler warranty. See unit submittal for unit
specific piping schematics. See the Thermal
Solutions Boiler “Installation, Operating,
and Service Instructions” that are included
with the unit for specific information about
the boiler.
Once the boiler is given a run signal, the
boiler secondary pump will be activated and
the controls package will stage boilers as
necessary to maintain the leaving water
temperature setpoint.
The controls package will also control the
speed of the secondary pump in the boiler
system to maintain differential pressure
across the pump.
Boiler Primary/Secondary Pumping
Water enters the unit through the return
water piping, and then travels through a
suction guide with strainer. The end of the
suction guide is removable for strainer
access. The strainer assembly is composed
of two parts, the operational strainer, and the
startup strainer, (located inside the
operational strainer) which is to be removed
24 hours after startup.
The pump is installed after the suction
guide, and before a combination valve (FloTrex). This combination valve acts as
isolation valve, check valve, and flow
balancing valve. The boiler is placed after
the combination valve in the water circuit.
The primary/secondary pumping package
provides variable flow to the system. It
consists of a constant flow pump for the
boiler, and a variable flow pump for the
building. The controls package senses
differential pressure across the pump with
pressure transducers installed at the suction
and discharge, and varies the speed of the
pump using a VFD in order to maintain a
given differential pressure across the pump.
The primary/secondary pumping package is
essentially composed of two piping loops
coupled together. The primary loop has a
constant flow rate in order to maintain water
temperature through the boiler, and the
secondary, variable flow loop, provides
water to the building. The two loops are
coupled via a water line that compensates
for excess flow in either loop. As the flow in
the secondary loop decreases below the flow
in the primary, excess flow bypasses the
building loop and circulates through the
primary loop. On the other hand, as the flow
in the secondary loop increases above the
primary loop, excess flow bypasses the
boiler and circulates through the bypass
water line.
The secondary pump includes suction guide,
combination valve, and isolation valve with
the addition of an air separator to remove
any air that is entrapped in the water.
15
See appendix for additional information on
the installation, operation and maintenance
of pumps.
Makeup Water
A city makeup water connection is provided
to replace water that is lost from the system.
Glycol units require a glycol feeder
(optional factory installed or field installed)
to replace fluid that is lost in the system.
Water should not be added to glycol
applications as this would dilute the glycol
concentration and thereby increase the
freezing temperature of the fluid.
The makeup water connection is provided
with a backflow preventer that has isolation
valves on the inlet and outlet for service.
Figure 1 shows the pressure drop versus
flow rate for the backflow preventer.
Figure 1 - Backflow Preventer
There is a pressure-reducing valve after the
backflow preventer. This valve reduces the
city water pressure to maintain the operating
pressure of the system. This valve is
adjustable from 10-35 psig with a factory
setting of 30 psig. The system pressure
varies with the height of the system. The
pressure-reducing valve setting should be set
so that the pressure at the high point in the
system is high enough to vent air from the
system (usually 4 psig). There should be air
vents at all parts in the system where air
could be trapped. If the pressure is not high
enough throughout the system, flashing
could occur in the piping or the pump could
cavitate. There is an isolation valve on the
inlet and outlet of the pressure-reducing
valve for service.
The pressure reducing valve fills the system
at a reduced rate. There is a bypass around
the pressure reducing valve for the initial fill
of the system to increase the initial fill
speed. After the initial system fill, this valve
should be closed.
Compression/Expansion Tank
As the water temperature in the system
increases, the volume that water displaces
increases. In order to compensate for these
expansion forces, a compression or
expansion tank must be used. The factory
installed tank option includes a prepressurized diaphragm compression tank
that is preset for 12 psig.
The factory pre-charge pressure may need to
be field adjusted. The tank must be precharged to system design fill pressure before
placing into operation. Remove the pipe
plug covering the valve enclosure. Check
and adjust the charge pressure by adding or
releasing air.
If the system has been filled, the tank must
be isolated from the system and the tank
emptied before charging. This ensures that
all fluid has exited the diaphragm area and
proper charging will occur.
If the pre-charge adjustment is necessary, oil
and water free compressed air or nitrogen
gas may be used. Check the pre-charge
using an accurate pressure gauge at the
charging valve and adjust as required. Check
the air valve for leakage. If evident, replace
the Schrader valve core. Do not depend on
the valve cap to seal the leak. After making
sure the air charge is correct, replace the
16
pipe plug over the charging valve for
protection.
Purge air from system before placing tank
into operation. All models have system
water contained behind the diaphragm.
It is recommended that the pre-charge be
checked annually to ensure proper system
protection and long life for the vessel.
Pressure Relief Valve
Required pressure relief valve is installed in
the unit. This valve is set at 125 psig. Figure
2 shows inlet pressure versus capacity for
this pressure relief valve. See appendix for
additional information.
Figure 2 - Pressure Relief Valve
Automatic Air Vent
There is an automatic air vent installed at the
high point of the system inside the pumping
package compartment. The air vent valve
must be in the proper position for operation.
Ensure that the small vent cap is loosened
two turns from the closed position, allowing
air to be vented from the system. It is
advisable to leave the cap on to prevent
impurities from entering the valve. See
appendix for additional information.
Dual Pumps
When redundant pumping is required,
factory installed dual pumps or two single
pumps can be ordered. A dual pump is a
pump with two independent motors and
pumps in a single casing. This dual pump
has a swing split-flapper valve in the
discharge port to prevent liquid recirculation
when only one pump is operating. Isolation
valves in the casing allow one pump to be
isolated and removed for service while the
other pump is still operating.
When redundant pumping is required with
high flow rates, two independent pumps
may be installed in parallel. Each pump will
have its own suction guide/strainer,
combination valve, and isolation valves.
The controls package will activate the pump
when the unit is given a run command. If the
controls do not recognize flow in 60
seconds, the second pump will be activated
and an alarm signal will be generated. If the
second pump does not activate, the cooling
will be locked out. See appendix for
additional information.
Pressure Gauges and Thermometers
Pressure gauges and thermometers are
available as a factory installed option.
Thermometers are installed on the inlet and
outlet of the unit. One pressure gauge is
installed at each pump. This pressure gauge
is connected in three places to the water
piping before the suction guide/strainer,
after the suction guide and before the pump,
and after the pump. There is also a needle
valve at each of these points to isolate the
pressure. To measure the pressure at any
given point, open the needle valve at that
point and close the other two needle valves.
One gauge is used so that the calibration of
the pressure gauge is irrelevant in the
calculation of the differential pressure.
17
Pipe Insulation
Location
All Sizes
Front
100”
Back
100”
Ends
100”
Top
Unobstructed
All roofing work should be performed
by competent roofing contractors to
avoid any possible leakage.
CAUTION
The water piping and components on units
with pumping packages are not insulated at
the factory. Insulation should be installed on
the water piping after the system has been
checked for leaks.
Installation
Outdoor Mechanical Room Placement
The AAON BL Series is designed for
outdoor applications and mounting at
ground level or on a rooftop. It must be
placed on a level and solid foundation that
has been prepared to support its weight.
Table 1 - Service Clearances
Units require rail support along all four sides
of the unit base.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is
1¼” wide and 1½” tall. It is recommended
that this or another similar gasket be used
between the curb and the unit to reduce
vibration from the unit to the building.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb and Steel Mount Installation
Make openings in the roof decking large
enough to allow for water piping, electrical,
and gas penetrations and workspace only.
Do not make openings larger than necessary.
Set the curb to coincide with the openings.
Make sure curb is level.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural Sheet Metal Manual for curb installation
details.
Figure 3 - Curb Mounting with Dimensions
18
Cabinet
Style
A B C
D
Standard
Narrow
100”
96”
92”
97”
Wide
142”
138”
134”
139”
Do not push, pull or lift the unit from
anything other than its base.
Figure 4 - Steel Mounting Rail with
Dimensions
Table 2 - Mounting Dimensions
Lifting and Handling
If cables or chains are used to hoist the unit
they must be the same length and care
should be taken to prevent damage to the
cabinet.
Before lifting unit, be sure that all shipping
material has been removed from unit.
Secure hooks and cables at all lifting points/
lugs provided on the unit.
Hoist unit to a point directly above the curb
or mounting rail. Be sure that the gasket
material has been applied to the curb or
mounting rail.
Carefully lower and align unit with utility
and duct openings. Lower the unit until the
unit skirt fits around the curb. Make sure the
unit is properly seated on the curb and is
level.
Figure 5 - Marked Lifting Points
NOTE: UNIT MUST BE RIGGED AT ALL
MARKED LIFTING POINTS
19
Figure 6 - BL, LL, RL, and CL Series Lifting Detail (General Configuration)
Lifting slot locations are unit specific.
Unit must be rigged at all marked lifting points.
20
Water Connection
Boiler Size
Rated Capacity (CFH)*
Natural
LP/Propane
500 MBH
500
200
750 MBH
750
300
1000 MBH
1000
400
1500 MBH
1500
600
Boilers must be operated only with
liquid flowing through boiler.
WARNING
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used with R-410A and other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
Connect the supply and return water lines.
The connection size is listed on the unit
rating sheet, along with the designed
volumetric flow rate. The maximum
operating pressure for AAON BL Series
units is 125 psi.
Gas Connection
Size the gas piping to supply the unit with
proper pressure when all gas consuming
devices in the building connected to the
same gas system are operating. The
maximum gas train inlet pressure for all
boiler sizes is 5 psig. The minimum gas train
inlet pressure for the 500 MBH boiler is 5
inches of water column, and for all other
boilers, 7 inches of water column.
Carefully consider all current and future gas
usage. Table 3 details the input rate for each
boiler unit.
Gas connection sizes are listed on the unit
rating sheet.
Table 3 - Boiler Rated Input Capacity
*Note: Rating is for sea level conditions.
For additional information regarding the gas
piping connection, see the Thermal
Solutions Boiler “Installation, Operating, and Service Instructions” that are included
with the unit.
Boiler Exhaust Connection
In addition to gas connection installation,
each boiler requires installation of the
exhaust vent piping and inlet vent hood. The
exhaust panel with chimney cutout is
removed for shipping, and replaced with a
shipping cover.
Remove the shipping cover and attach the
exhaust panel shipped with the unit. When
the exhaust panel is securely fastened with
sheet metal screws, locate the exhaust piping
that is also shipped along with the unit. The
exhaust piping that must be attached to the
internal exhaust vent piping includes the
vent length, 90 degree elbow and rain cap.
Examine all components prior to
installation. The female end of each vent
pipe component incorporates a sealing
gasket and a mechanical locking band.
21
Figure 7 - Boiler Vent Shipping Covers
Failure to follow proper joint
connection procedure may result in
carbon monoxide gas poisoning due
to flue gas leakage.
WARNING
Intake and exhaust covers are in place for
shipping. These must be removed and
external intake/exhaust components must be
installed prior to boiler operation.
Figure 8 - Boiler Vent Components
Gaskets must be in proper position or flue
gases could leak.
22
Securely fasten the vent pipe joints
according to the following procedure.
1. Insert the male end into the female
section. Push the units together and turn
them until the bead of the male end is
seated against the flared end of the
female section. This creates the
necessary airtight seal. Align the seams
on the vent lengths and orient them
upward in all horizontal applications.
2. Tighten the locking band with a nut
driver until snug plus 1/4 turn.
Before proceeding, recheck all joints and
ensure that all male sections extend to the
top of the flared female end and all clamps
are tightened.
Figure 9 - Correct Vent Pipe Connection
Stop bead on male end must be pushed
directly against the flared end of the female
end. When checking the inside of the joint,
the gasket is fully covered and out of sight.
Figure 10 - Incorrect Vent Pipe Connection
Boiler Intake Connection
Remove the intake shipping cover. The
round collar on the back of the intake vent
passes through the cabinet wall and slides
over the crimped end of the air intake pipe
inside the unit. This joint should be secured
with aluminum foil tape. The outer flange of
the wall vent is fastened to the outer wall of
the cabinet using sheet metal screws.
Mounting Isolation
For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Doors
Lockable access door is provided to the
electrical and control compartment. A
separate access door is also provided to the
boiler and pumping package compartment.
A light switch is on the wall of the control
compartment.
Electrical
The single point electrical power
connections are made in the electrical
control compartment.
The microprocessor control furnished with
the unit is supplied with its own power
supply factory wired to the main power of
the outdoor mechanical room.
23
Verify the unit nameplate voltage agrees
Electric shock hazard. Before
attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death or property damage.
WARNING
with the power supply. Connect power and
control field wiring as shown on the unit
specific wiring diagram provided with the
unit.
Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 167°F (75°C).
Route power and control wiring, separately,
through the utility entry. Do not run power
and signal wires in the same conduit.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Power wiring is to the unit terminal block or
main disconnect. All wiring beyond this
point has been done by the manufacturer and
cannot be modified without effecting the
unit's agency/safety certification.
Figure 11 - Terminal Block
Startup technician must check motor
amperage to ensure that the amperage listed
on the motor nameplate is not exceeded.
Motor overload protection may be a function
of the variable frequency drive and must not
be bypassed.
Note: All units are factory wired for
208/230V, 460V, or 575V. If unit is to be
connected to a 208V supply, the transformer
must be rewired to 208V service. For 208V
service interchange the yellow and red
conductor on the low voltage control
transformer.
Red-Black for 208V
Yellow-Black for 230V
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 221°F (105°C)
type AWM insulated conductors.
24
Startup
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Improper installation, adjustment,
alteration, service or maintenance
can cause property damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
Rotation must be checked on all
MOTORS of three phase units. All
motors, to include and not be limited
to pump motors motors, should all be
checked by a qualified service
technician at startup and any wiring
alteration should only be made at the
unit power connection.
CAUTION
Before completing installation, a
complete operating cycle should be
observed to verify that all
components are functioning properly.
CAUTION
(See back of the manual for startup form)
Before the startup of the boiler be sure that
the following items have been checked.
1. Verify that electrical power is available
to the unit.
2. Verify that any remote stop/start device
connected to the boiler controller is
requesting the boiler to start.
3. Verify that liquid flow is present through
the boiler from the building.
4. There should be a building load of at
least 25% of the boiler capacity in order
to properly check operation.
5. With the main power switch off, review
the MCS Controller Manual provided
with the boiler. Understand the keypad
functions, how to set the leaving water
temperature setpoint and how to initiate
the Run State.
Use the general check list at the top of the
startup form to make a last check that all the
components are in place, water flow is
present, and the power supply is energized.
Using the controller keypad, individually set
the outputs in “Manual On” to confirm relay
closure.
Cycle on all the boilers to confirm that all
are operating within tolerance.
While performing the check, use the startup
form to record observations of boiler amps
When all is running properly, place the
controller in the Run mode and observe the
system until it reaches a steady state of
operation.
Note: For more information on
programming the controller refer to the
MCS Controller manual provided with the
boiler.
25
Maintenance
General
Qualified technicians must perform routine
service checks and maintenance.
Lubrication
All original motors and bearings are
furnished with an original factory charge of
lubrication. Certain applications require
bearings be re-lubricated periodically. The
schedule will vary depending on operating
duty, temperature variations, or severe
atmospheric conditions.
Bearings should be re-lubricated at normal
operating temperatures, but not when
running. Rotate the motor shaft by hand and
add only enough grease to purge the seals.
DO NOT OVERLUBRICATE.
Service
If the unit will not operate correctly and a
service company is required, only a
company with service technicians qualified
and experienced in both boilers and
pumping systems are permitted to service
the systems to keep warranties in effect. If
assistance is required, the service technician
must contact AAON.
Replacement Parts
Parts for AAON equipment may be obtained
from AAON at www.aaonparts.com. When
ordering parts, reference the unit serial
number and part number.
AAON Warranty, Service, and Parts
Department
2424 S. Yukon Ave.
Tulsa, OK 74107
Ph: 918-583-2266
Fax: 918-382-6364
www.aaon.com
Note: Before calling, technician should have
model and serial number of the unit
available for the service department to help
answer questions regarding the unit.
26
Appendix - Water Piping Component Information
Water Pressure Reducing Valve
Water Pressure Reducing Valves are
designed to reduce incoming water pressure
to protect plumbing system components and
reduce water consumption.
Overview
Standard construction includes Z3 sealed
spring cage and corrosion resistant adjusting
cage screws for outdoor/waterworks pit
installations.
Integral stainless steel strainer
Replaceable seat module
Bronze body construction
Serviceable in line
High temperature resistant reinforced
Meets requirements of ASSE Standard
1003; (ANSI A112.26.2); CSA Standard
B356; Southern Standard Plumbing Code
and listed by IAPMO.
Teflon® is a registered trademark of E.I.
Dupont de Nemours & Company.
27
Capacity
Maintenance Instructions
To clean strainer remove the bottom plug
and pull out strainer.
Adjustment
To adjust pressure setting, loosen the lock
nut and turn the adjusting bolt clockwise to
increase pressure, counter clockwise to
decrease pressure.
Dimensions-Weights:
Note: Use a pressure gauge downstream to
adjust and verify the pressure setting.
Troubleshooting
High System Pressure
If the downstream system pressure is higher
than the set pressure under no flow
conditions, the cause could be thermal
expansion, pressure creep or dirt/debris on
the seat. Thermal expansion occurs
whenever water is heated in a closed system.
The system is closed when supply pressure
exceeds 150 psi, or a check valve or
backflow preventer is installed in the supply
piping. To determine if this is the result of
thermal expansion, try briefly opening the
cold water tap. If the increased pressure is
caused by thermal expansion, the pressure
will immediately be relieved and the system
will return to the set pressure.
28
Water Pressure Relief Valve
Overview
ASME Rated, Design Certified and Listed
by C.S.A.
Used for protection against excessive
pressure on domestic storage tanks or
tankless water heaters, the pressure relief
valve has no temperature relieving element.
Standard setting, 125 psi Size 3⁄4" x 3⁄4"
(20mm x 20mm).
ASME construction and is tested, listed and
certified by the National Board of Boiler and
Pressure Vessel Inspectors.
seals and prevents any water from escaping
from the system.
The float vent can also operate as an antivacuum device since it will permit air to
enter the system when it must be drained. It
can also be installed to permit the separation
and dispersal of air while fluid is actually
circulating in the system.
Overview
Body and cover are brass construction.
Air vent with silicone rubber seal.
Impurities do not usually affect function
as maximum float line of water is always
lower than the valve seal.
Float is high temperature resistant
polyethylene.
Suitable for use with glycol systems.
Can be disassembled for inspection and
cleaning.
ANSI Z21.22 “Relief Valves for Hot Water
Supply Systems.”
DESIGN CERTIFIED and listed by C.S.A.
Automatic Air Vent Valves
Automatic Air Vent Valves provide
automatic air venting for hot or cold water
distribution systems. These vents purge air
that may be in the water system.
The vent valve utilizes a float to actuate the
valve plug which is located at the top of the
valve. Once the air is displaced and the
system pressure is sustained, the valve plug
29
Operating Range
Minimum working pressure: 1.45psi (10
kPa)
Maximum working pressure: 150psi (10
bars)
Temperature Range: 33°F – 240°F (5°C –
116°C)
Performance:
The figure below shows the installation of
the vent valve for the venting of air while
the fluid is circulating in the system and the
required increase in pipe size in order to
obtain proper separation of air from water.
Performance curve details the quantity of air
vented by the “Float Vent” according to the
pressure in the system.
Note: In order to get the best results in
venting air from risers, use connecting pipes
of at least 1⁄2" diameter between the “Float
Vent” valves and installation.
Installation
When the air vent valve is installed as
shown, the air will not be vented while the
fluid is circulating in the system, but it can
vent when the system is shut off.
The valve should be mounted only in a
vertical position as its operation is based on
the vertical movement of the float.
While the air vent valve is in operation, back
off the small vent cap two turns. This is the
proper operating setting which will allow air
to be vented from the system. It is advisable
to leave the cap on to prevent impurities
from entering the valve.
30
No Installation of this equipment
should take place unless this
document has been read and
understood.
CAUTION
Dimensions – Weights:
Maintenance
No maintenance is normally necessary.
However, if the FV-4M1 is disassembled for
inspection or cleaning it is important that
when re-assembling to ensure that the spring
loaded lever properly engages under the
float collar
Pumps - Installation and Operating
Instructions
Introduction
This document contains specific information
regarding the safe installation, operating and
maintenance of Vertical In-Line pumps and
should be read and understood by installing,
operating and maintenance personnel. The
equipment supplied has been designed and
constructed to be safe and without risk to
health and safety when properly installed,
operated and maintained. The instructions
following must be strictly adhered to. If
clarification is needed on any point please
contact Armstrong quoting the equipment
serial number.
31
Where under normal operating conditions
the limit of 68°C/155°F (Restricted Zone)
for normal touch, or 80°C/176°F
(Unrestricted Zone) for unintentional touch,
may be experienced, steps should be taken
to minimize contact or warn operators/users
that normal operating conditions will be
exceeded. In certain cases where the
temperature of the pumped liquid exceeds
the above stated temperature levels, pump
casing temperatures may exceed
100°C/212°F and not withstanding pump
insulation techniques appropriate measures
must be taken to minimize risk for operating
personnel.
Storage
Pumps removed from service and stored,
must be properly prepared to prevent
excessive rusting. Pump port protection
plates must not be removed until the pump is
ready to connect to the piping. Rotate the
shaft periodically (At least monthly) to keep
rotating element free and bearings fully
functional.
For long term storage, the pump must be
placed in a vertical position in a dry
environment. Internal rusting can be
prevented by removing the plugs at the top
and bottom of the casing and drain or air
blow out all water to prevent rust buildup or
the possibility of freezing. Be sure to
reinstall the plugs when the unit is made
operational. Rust-proofing or packing the
casing with moisture absorbing material and
covering the flanges is acceptable. When
returning to service be sure to remove the
drying agent from the pump.
Handling Large VIL Units
One effective way of lifting a large pumping
unit is to place lifting hooks through the
motor lifting rings or straps around the
upper part of the motor. The pump and
motor unit will free-stand on the casing ribs.
Remove the coupling guard and place (2)
lifting straps through the pump/motor
pedestal, one on each side of the motor shaft
and secure to the lifting device.
With the straps in place, using a spacer bar if
necessary to protect the motor fan cover, the
whole assembly can now be lifted securely.
Note:Handling, transportation and
installation of this equipment should only
undertaken by trained personnel with proper
use of lifting equipment.
Remove coupling guard and place lifting
straps on each side of coupling, use spacer
bar if necessary to protect motor fan cover.
Vertical Inline Pump Lifting Strap
Positioning
Note: All split-coupled pumps contain a
tapped hole in the motor bracket above the
discharge flange for draining the well. Pipe
this drain hole to a floor drain to avoid
overflow of the cavity caused by collecting
chilled water condensate or from seal
failure.
32
Pump Piping - General
Do not run pumps with discharge
valve closed or under very low flow
conditions.
Use Caution. Piping may carry high
temperature fluid.
Discharge valve only is to be used to
throttle pump flow.
CAUTION
CAUTION
CAUTION
The discharge valve only is to be used to
throttle pump flow, not the suction valve.
Care must be taken in the suction line layout
and installation, as it is usually the major
source of concern in centrifugal pump
applications
Alignment
Alignment is unnecessary on close-coupled
pumps as there is no shaft coupling.
Split-coupled units are accurately aligned at
the factory prior to being shipped and do not
need re-aligning when installed.
Operation
Starting Pump
Ensure that the pump turns freely by hand,
or with some mechanical help such as a
strap and lever on larger pumps. Ensure that
all protective guarding is securely fixed in
position.
The pump must be fully primed on startup.
Fill the pump casing with liquid and rotate
the shaft by hand to remove any air trapped
in the impeller. On split coupled units, any
air trapped in the casing as the system is
filled must be removed by the manual air
vent in the seal flush line. Close-coupled
units are fitted with seal flush/vent lines
piped to the pump suction area. When these
units operate residual air is drawn out of the
pump towards the suction piping.
“Bump” or energize the motor momentarily
and check that the rotation corresponds with
the directional arrow on the pump casing. To
reverse rotation of a three phase motor,
interchange any two power leads.
Start the pump with the discharge valve
closed and the suction valve open, and then
gradually open the discharge valve when the
motor is at operating speed. The discharge
valve may be cracked” or open slightly at
start up to help eliminate trapped air.
When stopping the pump: Close the
discharge valve and de-energize the motor.
DO NOT run the pump against a closed
discharge valve for an extended period of
time. (A few minutes maximum)
Star-Delta motor starters should be fitted
with electronic/mechanical interlocks that
have a timed period of no more than 40
milliseconds before switching from star
(Starting) to delta (Run) connection yet
allow the motor to reach full star (Starting)
speed before switching to delta (Run).
Should the pump be noisy or vibrate on
start-up a common reason is overstated
system head. Check this by calculating the
pump operating head by deducting the
suction pressure gauge value from the
discharge gauge reading. Convert the result
33
into the units of the pump head as stated on
Check rotation arrow prior to
operating the unit.
CAUTION
Electric shock hazard. Before
attempting to perform any service or
maintenance on pumping unit,
disconnect power source to the
driver, LOCK IT OFF and tag with the
reason.
WARNING
the pump nameplate and compare the
values. Should the actual pump operating
head be significantly less than the nameplate
head value it is typically permissible to
throttle the discharge isolation valve until
the actual operating head is equal to the
nameplate value.
Any noise or vibration usually disappears.
The system designer or operator should be
made aware of this soon as some adjustment
may be required to the pump impeller
diameter or drive settings, if applicable, to
make the pump suitable for the system as
installed.
Check rotation arrow prior to operating the
unit. The rotation of all Vertical In-Line
units is “clockwise” when viewed from the
drive end. (Looking from on top of / behind
the motor)
General Care
Vertical In-Line pumps are built to operate
without periodic maintenance, other than
motor lubrication on larger units. A
systematic inspection made at regular
intervals, will ensure years of trouble-free
operation, giving special attention to the
following:
Keep unit clean.
Keep moisture, refuse, dust or other
loose particles away from the pump and
ventilating openings of the motor.
Avoid operating the unit in overheated
surroundings (Above 100ºF/40ºC).
Any possibility of the unit starting while
being serviced must be eliminated.
If mechanical seal environmental
accessories are installed, ensure water is
flowing through the sight flow indicator and
that filter cartridges are replaced as
recommended.
Lubrication
Pump
Lubrication is not required. There are no
bearings in the pump that need external
lubrication service.
Large Series split-coupled units are installed
with a shaft bushing located beneath the
impeller that is lubricated from the pump
discharge. This bearing is field removable
for service on the 20x20x19 size without
disturbing the motor or other major pump
components.
Motor
Follow the lubrication procedures
recommended by the motor manufacturer.
Many small and medium sized motors are
permanently lubricated and need no added
lubrication. Generally if there are grease
fittings evident the motor needs periodic
lubrication, and if there are no grease fittings
evident, no periodic lubrication is required.
34
Check the lubrication instructions supplied
Double Check Prior to Startup
CAUTION
with the motor for the particular frame size
indicated on the motor nameplate.
Mechanical Seal
Mechanical seals require no special
attention. The mechanical seal is fitted with
a flush line. The seal is flushed from
discharge of the pump casing on splitcoupled pumps and is flushed/vented to the
suction on close coupled pumps.
The split-coupled pump is flushed from the
pump discharge because the mechanical seal
chamber is isolated from the liquid in the
pump by a throttle bushing. Because the seal
chamber is isolated, seal environmental
controls such as filters and separators, when
installed in the split-coupled flush line are
very effective, as only the seal chamber
needs cleansing, and will prolong seal life in
HVAC systems.
Do not run the pump unless properly filled
with water as the mechanical seals need a
film of liquid between the faces for proper
operation.
Mechanical seals may ‘weep’ slightly at
start-up. Allow the pump to continue
operating for several hours and the
mechanical seal to ‘seat’ properly prior to
calling for service personnel.
System Cleanliness
Before starting the pump the system must be
thoroughly cleaned, flushed and drained and
replenished with clean liquid.
Welding slag and other foreign materials,
“Stop Leak” and cleaning compounds and
improper or excessive water treatment are
all detrimental to the pump internals and
sealing arrangement.
Proper operation cannot be guaranteed if the
above conditions are not adhered to.
Note
Particular care must be taken to check the
following before the pump is put into
operation:
1. Pump primed?
2. Rotation OK?
3. Lubrication OK?
4. Pipe work properly supported?
5. Voltage supply OK?
6. Overload protection OK?
7. Is the system clean?
8. Is the area around the pump clean?
Warranty
Does not cover any damages to the
equipment resulting from failure to observe
the above precautions.
35
Noise Levels
Estimated Pumping Unit Sound Power Level, Decibels, A-Weighted, at 1 m (3 ft.) from unit.
Vibration Levels
Vertical In-Line pumps are designed to meet vibration levels set by Hydraulic Institute Standard
HI Pump Vibration 9.6.4. Standard levels are as detailed below:
Dual Pump Specific Information
Dual Pump Flapper Valve Operating
Instructions
This unit is fitted with internal valves to
allow isolation of one pump for service and
to automatically prevent recirculation of the
flow when only one pump is running.
Procedure for Parallel or Stand-By
Pumping
Discharge and suction valve stems should be
locked in the center position. This is
indicated by both locking handles in the
vertical position and the center pin of the
locking arms (4) locked by the handles. This
procedure allows the discharge flapper
valves to pivot freely and locks the suction
valve firmly in the center position.
Procedure for Isolation of One Side
1. Stop the pump to be serviced.
2. Close and lock the suction and discharge
valves: as per instructions below.
3. Ensure seal flush line interconnection
valve is closed and drain the isolated
casing.
4. Service isolated pump as required.
Procedure for Starting the Pump after
Servicing
1. Ensure serviced pump is fully re-
assembled including all seal flush lines
and drain plugs.
36
2. Fill the dry casing with system fluid by
opening the seal flush line
interconnecting valve and the air vent
fitting.
3. Allow the pressure to equalize in the two
casings, if necessary, by opening seal
flush line interconnected valve.
4. Unlock the discharge valve as per
instructions below.
5. Unlock the suction valve as per
instructions below.
NOTE: Keep hands and tools away from
locked suction valve arm, as the differential
pressure may cause the arm to rotate quickly
with force when unlocked.
6. Close the seal flush line interconnect
valve and restart pump.
Valve Operation - Refer to following 3”, 4”
& 6” valve illustration and the 8” valve
illustration.
Discharge Valve
This valve performs the dual function of
automatically sealing the discharge of the
inactive pump when one pump is running
and can manually be closed and locked to
isolate one pump for service.
Automatic Flapper Operation
In the flapper mode the two halves of the
discharge valve are free to pivot
independently under normal operating
conditions. The locking handle (3) should be
secured with the set screw (11) in the
vertical position with the center pin of the
locking arm (4) trapped by the locking
handle (3).
Manual Valve Locking
The locking feature of this valve is to ensure
a positive seal (leak proof) of the discharge
port on the pump to be serviced.
Note: Ensure the pump to be isolated is not
operating before attempting to release the
locking mechanism. Failure to do so may
result in injury to the operator and/or
damage to the pump.
Locking
1. Loosen discharge side set screw (11) to
release the locking handle (3).
2. Rotate the discharge side locking handle
(3) so that the handle points toward the
pump to be serviced and secure in the
horizontal position, using set screw (11).
This releases the discharge locking arm
(4).
3. Rotate discharge valve shaft (16)
towards the pump to be isolated. The
orientation of the shaft is indicated by
the center pin on the locking arm (4).
4. Raise the locking handle (3) so that the
cam on the base of the handle forces the
pin of the locking arm (4) towards the
pump to be isolated. The locking handle
(3) should be raised to between 45
degrees and the vertical position.
5. Tighten set screw (11) to lock the
locking handle (3) in position.
This handle should not be rotated past the
vertical position.
Note: Ensure the isolated pump is not
operating before attempting to release the
locking mechanism. Failure to do so may
result in injury to the operator and/or
damage the pump.
Unlocking:
1. Open the interconnecting valve on the
seal flush line to pressurize the serviced
pump and vent air through bleeder valve
on series 4302.
2. Close these valves once the pressure is
equalized and air removed.
37
3. Loosen set screw (11) and lower locking
Care should be taken when
performing procedures 3 and 4. Read
instructions carefully.
WARNING
handle (3) to the horizontal position,
secure with set screw (11).
4. Rotate valve to center position so that
the center pin of the locking arm (4)
locates in the recess on the locking
handle (3).
5. Loosen set screw (11) and raise locking
arm (3) to the vertical position, locking
the center pin in the locking arm recess,
secure with set screw (11).
Suction Valve
Manual Operation
The suction side valve is designed for use as
a manually operated isolation valve. This
valve is not designed to automatically pivot
as the discharge flappers do.
Locking
1. Loosen suction side set screw (11) to
release the locking handle (3).
2. Rotate the suction side locking handle
(3) so that the handle points towards the
pump to be serviced and secure in the
horizontal position, using set screw (11).
This releases the suction locking arm
(4).
Note: The locking handle (3) should only be
rotated towards the pump stopped for
service. The suction valve is designed to
prevent the locking handle (1) from rotating
towards the running pump, as the suction of
the running pump could cause the valve to
slam shut with sufficient force to injure the
operator and/or cause damage to the pump.
Do not attempt to circumvent this safety
feature.
3. Rotate the suction valve towards the
pump to be isolated. The orientation of
the shaft is indicated by the center pin on
the locking arm (4).
4. Loosen set screw (11) and raise the
locking handle (3) so that the cam on the
base on the handle forces the pin of the
locking arm (4) towards the pump to be
isolated. The locking handle (3) should
be raised to between 45 degrees and the
vertical position.
This handle should not be rotated past the
vertical position.
5. Tighten set screw (11) to secure the
locking handle (3) in position.
38
Care should be taken when
performing procedures 3 and 4. Read
instructions carefully.
WARNING
Unlocking:
1. Open the interconnecting valve on the
seal flush line to pressurize the serviced
pump and vent air through bleeder valve
on series 4302. Close these valves once
the pressure is equalized and air
removed.
2. Loosen set screw (11) and lower locking
handle (3) to the horizontal position,
secure with set screw (11).
NOTE: Keep hands and tools away from
suction valve locking arm when freed by
locking handle as differential pressure may
cause arm to rotate quickly with force when
unlocked.
3. Rotate valve to center position so that
the center pin of the locking arm (4) is
located in the recess on the locking
handle (3).
4. Loosen set screw (11) and raise locking
arm (3) to the vertical position, locking
the center pin in the locking arm recess,
secure with set screw.
39
40
41
Horizontal and Vertical Expansion Tanks
ASME PRE-PRESSURIZED
DIAPHRAGM EXPANSION TANKS
FOR HEATING & COOLING SYSTEMS
Vessel Description
Tanks are ASME constructed and precharged. They are designed to absorb the
expansion forces and control the pressure in
heating/cooling systems.
The system’s expanded water (is contained
behind a heavy-duty diaphragm fully
compatible with water/glycol mixtures)
preventing tank corrosion and water logging
problems.
The factory set pre-charge for these tanks is
12 psig (83 kPa).
Materials
Shell – Carbon Steel
Diaphragm – Heavy Duty Butyl
Operating Conditions
Maximum Working Temperature - 240°F
(115°C)
Maximum Working Pressure – 125 psi (862
kPa)
Maintenance Steps & Procedure
Visually inspect tank for damage, which
may occur during transit.
Factory pre-charge pressure may not be
correct for the installation. Tank MUST be
pre-charged to system design fill pressure
BEFORE placing into operation. Remove
pipe plug covering the valve enclosure.
Check and adjust the charge pressure by
adding or releasing air for each application.
Note: If the system has been filled, the tank
must be isolated from the system and the
tank emptied before charging. This ensures
all fluid has exited the diaphragm area and
proper charging will occur.
If the pre-charge adjustment is necessary, oil
and water free compressed air or nitrogen
gas may be used. Check the pre-charge
using an accurate pressure gauge at the
charging valve and adjust as required. Check
air valve for leakage. If evident, replace the
Schrader-type tire valve core.
Do not depend on the valve cap to seal the
leak.
After making sure air charge is correct,
replace pipe plug over the charging valve for
protection.
Set tank in place and pipe system connection
to system. Be sure to include isolation
valve(s) and drain.
Purge air from system BEFORE placing
tank into operation. All models have system
water contained behind diaphragm.
When filling the system with water, open
valves to tank to ensure that any residual air
in the tank is displaced by water.
It is recommended that the pre-charge be
checked annually to ensure proper system
protection and long life for the vessel.
42
Installation
The Suction Guides may be installed in any
arrangement feasible the arrangement of the
pump flange bolt-holes.
Suction Guides
Introduction
Suction Guides are designed for bolting
directly onto the suction flange of horizontal
or vertical shaft centrifugal pumps.
Operating Limits
The suction guide is designed to be a fourfunction fitting. Each Suction Guide is a 90º
elbow, a Pipe Strainer and a Flow Stabilizer.
It may also be used as a Reducing Elbow,
should the suction piping be larger than the
pump inlet.
Inspection
Suction Guides are thoroughly tested and
inspected before shipment to assure they
meet with your order requirements. All units
must be carefully examined upon arrival for
possible damage during transit. Any
evidence of mishandling should be reported
immediately to the carrier and noted on the
freight bill.
Operation
No special attention need be paid to the
Suction Guide at start-up. The fitting is
stationary and will strain the pumped fluid
and stabilize the flow into the pump
automatically.
43
Temporary strainer must be removed
following system clean up.
After all debris has been removed from the
system, or a maximum of 24 running hours,
stop the pump and close the pump isolation
valves. Drain the Suction Guide by
removing the drain plug or opening the
blowdown valve, if installed
Remove the Suction Guide cover and
remove the strainer assembly from the valve
body.
A temporary fine-mesh start-up strainer is
tack-welded to the permanent stainless steel
strainer. This temporary strainer should now
be removed from the permanent strainer.
The fine-mesh strainer is designed to
remove small particulate from new piping
systems and could easily clog with debris if
left in place. This will be detrimental to the
operation of the pump.
Inspect the cover O-ring and replace if
necessary.
Replace the permanent strainer into the
fitting body, once the temporary strainer is
removed.
Replace the cover into the body. Ensuring
that the strainer is properly seated, tighten
the cover bolts diagonally, evenly and
firmly.
Glycol Auto Fill Unit
The glycol auto fill unit (GLA) is designed
to maintain the HVAC system pressure by
adding the appropriate mix of glycol and
water to the system. During the normal
operation of the HVAC system, fluid is lost
causing a drop in the system pressure.
Standard Unit
When the system pressure drops below the
set point on the pressure switch, the GLA
pump is started adding fluid from the GLA
tank into the HVAC system. When the
system pressure returns to normal operating
conditions, the pump stops. As the tank
empties, a level switch is actuated
preventing the pump from running dry.
Ultra Unit
When the system pressure drops below the
set point on the pressure switch, the GLA
pump is started adding fluid from the GLA
tank into the HVAC system. When the
system pressure returns to normal operating
conditions, the pump stops. As the tank
empties, a level switch is actuated lighting
the low level pilot light. If the system is not
filled, a second level switch stops the
pump(s) preventing the pump(s) from
running dry. Should the system be
overfilled, a high level alarm is actuated by
level switch. Dry contacts can be provided
for remote indication of the above
conditions.
A manual “push to mix” switch is provided
for agitation of the contents of the GLA unit.
The switch starts the pump and opens the
return line solenoid valve circulating the
fluid.
Duplex units are equipped with a manual
alternator to equalize wear on the pumps.
Essential Safety Requirements
Glycol is toxic and the glycol supplier’s
safety instructions must be adhered to. In
critical areas a retaining wall should be used
to contain any spillage or leakage.
Overflows should be arranged not to
contaminate drainage systems.
It is recommended that initial
commissioning be carried out with water.
44
The flow rates from the unit are designed for
make-up rates. It is therefore suggested that
the system is back-filled with due
precautions taken to avoid contamination.
Glycol is sometimes subject to bacterial
attack and can become slimy as a result.
AAON recommend the addition of a suitable
biocide. The dosage should be calculated on
the amount of water glycol mixture added
and not the total tank contents. If bacterial
attack occurs on untreated mixtures the unit
should be drained, flushed and refilled with
fresh mixture and dosed with biocide.
Check that the supply voltage and overload
protection is correct.
Guards and covers must not be removed
during operation.
The pipework from the system to the
expansion vessels should not be insulated.
For systems operating above 200°F (93°C),
an anti-gravity loop with a minimum height
of 6 feet, (or an intermediate vessel) should
be installed to provide thermal protection to
the expansion tanks.
The ball float valve is fitted with a lowpressure seat; a high-pressure seat is
attached to the float valve and should be
fitted if required.
Pressure Switch Adjustment
Low system pressure - PS1
High system pressure - PS2
Duty pump control switch - PS3
Standby pump control switch (where fitted)
- PS4
For each switch, set the delivery to the
required pressure. Then very slowly turn the
adjusting screw on the switch until the
contacts change.
The high system pressure switch should first
be set higher than the required pressure by
turning the screw clockwise and the setting
then made by turning the screw counterclockwise until the switch contacts
changeover.
The other switches should first be set lower
than the required pressure by turning the
screw counter-clockwise and the setting then
made by turning the screw clockwise until
the switch contacts changeover.
A pipe plug is provided on the outlet to
allow connection of a test pump to simulate
differing system pressures to check switch
settings.
The Ultra versions of the GLA have the
capability of controlling duty and standby
pumps from a single pressure switch.
GLA Ultra Settings
The extra functionality of Ultra units is
integral. The only selectable option is
Manual or Automatic reset of alarm
conditions. DIP switch 1, on the display
board should be set to OFF for auto reset
(Factory setting), and ON for manual reset.
On alarm conditions, the MUTE switch will
mute the buzzer. In manual reset mode this
MUTE switch will reset the alarms after the
fault condition has been cleared. Other
switches change the mode of the printed
circuit board for use with other products. For
GLA application, all switches except 1 and 7
must be set to OFF.
Priming the makeup pumps
1. Close suction isolating valve.
2. Fill the glycol-mixing tank.
3. Remove the upper vent plug from the
makeup pump.
4. Open suction isolation valve until water
flows out of this tapping.
5. Close valve and replace plug.
45
6. Repeat for standby pump (where fitted).
7. Close the system-isolating valve.
8. Open suction isolating valve.
9. Switch on unit, initially both pumps will
run. As the pressure reaches the pump
control switch threshold, the pumps will
switch off.
10. Check all piping for leaks following
shipping.
11. Crack open system valve. The pressure
will fall and the pump will start and
maintain pressure.
Powered agitation (Ultra model only)
A solenoid valve is fitted to provide
powered agitation of the mixture.
Automatically this valve is periodically
opened and the duty pump starts creating
circulation through the pump and mixing
tank. Automatic mixing is inhibited when
there is a system demand for make-up.
A switch is provided for manual agitation
when adding glycol to the mixing tank.
Topping up with glycol
The mixing tank is calibrated in liters and
US gallons. The normal top up level is 53
US gallons (200 liters).
1. Calculate the amount of water needed
and add or drain to the correct level.
2. Add the required amount of glycol.
3. Operate the manual-agitating switch.
4. Check the mixture percentage. The unit
is now ready for service.
Flo-Trex Combination Valve
Introduction
The Flo-Trex combination valves are
designed for installation on the discharge
side of centrifugal pumps, and incorporate
three functions in one valve:
1. Drip-tight shut-off valve
2. Spring closure design, Non-slam check
valve
3. Flow throttling valve
Armgrip Flange Adapter Installation
1. Position the two halves of the Armgrip
flange adapter on the valve body
ensuring that the lugs on each half of the
flange adapters are located between the
anti-rotation lugs on the valve body (as
shown).
Insert two bolts of specified size (Table A1)
to secure the halves of the flange adapter to
the valve body (as shown).
46
Table A1. Armgrip Flange Adapter Details
Valve Size
125 psi/150 psi
250 psi/300 psi
Ductile Iron Bolt
Ductile Iron Bolt
No.
Size
No.
Size
2-1/2
4
5/8 8 3/4
3
4
5/8 8 3/4
4
8
5/8 8 3/4 5 8
3/4 8 3/4 6 8
3/4
12
3/4 8 8
3/4
12
7/8
10
12
7/8
16 1 12
12
7/8
16
1-1/8
The gasket cavity should face out to the
adjoining flange.
2. Lubricate the inner and outer diameter of
the gasket with the lubricant provided or
a similar non-petroleum based water
soluble grease.
3. Press the gasket firmly into the flange
cavity ensuring that the sealing lip is
pointed outward. When in place, the
gasket should not extend beyond the end
of the pipe (as shown).
5. Tighten remaining nuts evenly by
following bolting instructions, so that the
flange faces remain parallel (as shown in
the figure labeled Recommended Bolt
Tightening Procedure). Flange bolts
should be tightened to 70 ft-lbs torque
minimum to assure firm metal to metal
contact. When raised face flanges are
sued, there will be a gap between the
faces of the outer diameter.
6. Flange gaskets are not interchangeable
with other mechanical pipe couplings or
flange gaskets.
4. Position the adjoining flange or the pipe
to the Armgrip flange adapter and install
the remaining bolts. The two locking
bolts should be tightened first in order to
position the flange correctly.
Note: Care should be taken to ensure that
the gasket is not pinched or bent between
flanges.
Recommended Bolt Tightening Procedure
Field Conversion (Straight to Angle
Pattern Valve
1. Open valve at least one complete turn.
2. Remove the body bolts from valve body
using Allen Key.
3. Rotate one half of the valve body 180°
making sure the lower valve seat and O
ring stay in position. Inspect the O ring
for any cuts or nicks and replace if
necessary.
4. Replace body bolts and torque evenly to
70 ft-lbs.
47
Flow Measurement with the valve in the
Valve Size
2-1/2
3 4 5 6 8
10
12
Number of
Rings
5 5 6 9 10
12
18
28
(valve fully
open)
Safety glasses should be worn.
Probes should not be left inserted
into fittings for long periods of time as
leakage may result.
CAUTION
Wide Open position
Where approximate indication of flow is
acceptable the Flo-Trex valve can be used.
Step 1. Measure and record the differential
pressure across the valve.
Step 2. With valve in fully open position,
locate the differential pressure on the
Performance curve, and for the given valve
size in use, read the corresponding flow rate.
Flow Measurement with the valve in the
throttled position
Step 1. The valve stem with its grooved
rings and positioning sleeve is the flow
indicator scale for the throttled position of
the valve.
The quarter turn graduations on the sleeve,
with the scribed line on the stem provide an
approximate flow measurement.
Note: The valve is shipped in closed
position. The indicator on the plastic
sleeve is aligned with the vertical scribed
line on the stem.
Step 2. Record the size of the valve and
stem position using the flow indicator scale.
Calculate the percentage of valve opening
based on the number of rings at the fully
open position.
Step 3. Measure and record the differential
pressure across the valve in the throttled
position.
Step 4. Locate percentage of valve opening
on the flow characteristic curve. For the
given valve, record the percentage of
maximum flow rate.
Step 5. Locate the differential pressure
determined for the valve in the throttled
position on the Flo-Trex Performance
Curve. Determine the flow rate for the
given valve size at this differential pressure.
Step 6. Calculate the flow rate of the valve
in the throttled position by multiplying the
flow rate (Step 5) by the percentage of
maximum flow rate (Step 4).
Example:
Valve size: 4 in.
Differential pressure is 5.4 ft
Number of open rings is 3.
From the table, the number of rings for the 4
in valve fully open is 6.
Divide open rings by total, 3/6 = 50%
throttled
48
100
34) x (400
100
34) x (25.2
Safety glasses should be worn.
CAUTION
From the Flo-Trex performance curve, a 4
in. valve with 5.4 ft of pressure drop
represents a flow of 400 USgpm
From the flow characteristic curve, a 4 inch
valve at 50% open represents 34% of
maximum flow.
The approximate flow of a 4 inch valve with
a 5.4 ft pressure drop when 50% throttled is:
= 136 USgpm
=8.57 L/s
Note: To prevent premature valve failure
it is not recommended that the valve
operate in the throttled position with
more than 25 ft pressure differential.
Instead the pump impeller should be
trimmed or valves located elsewhere in
the system to partially throttle the flow.
Operation
To assure tight shut-off, the valve must be
closed using a wrench with 25 to 30 ft-lbs of
torque.
To assure trouble free check valve operation
and shut-off operation, the valve should be
periodically opened and closed to keep valve
seat and valve disc guide stem free of
buildup of system contaminants.
Repacking of Flo-Trex valve under full
system pressure
If it is necessary, the stem O ring can be
changed under full system pressure.
Step 1. Record the valve setting.
Step 2. Turn the valve stem
counterclockwise until the valve is fully
open and will not turn any further. Torque
to a maximum of 45 ft-lbs. This will ensure
good metal to metal contact and minimal
leakage.
Step 3. The valve bonnet may now be
removed. There may be a slight leakage, as
the metal to metal backseating does not
provide a drip-tight seal.
Step 4. Clean exposed portion of valve stem
being careful not to leave scratches.
Step 5. Remove and replace the O ring
gasket.
Step 6. Install the valve bonnet.
Step 7. Tightening the valve bonnet is
necessary to stop any leaks.
Step 8. Open valve to balance set point as
recorded in Step 1.
Note: On valve sizes of 2-1/2 inch and 3
inch, the full open position is 5 turns,
though the valve will open to 5-1/2 turns
which is just back of seating of valve.
Seat Replacement
Step 1. Drain the system and remove valve
from piping.
Step 2. Remove the body bolts from the
body using an Allen Key.
Step 3. Remove seat and O Ring. O rings
are not used on valves of 8 inches or larger.
49
Step 4. Inspect and clean O ring cavity and
install new O ring and seat. Valve disc stem
should be inspected and replaced if worn.
Pressure-Temperature Limits
Flo-Trex Cross Section
Valve stem O ring should be replaced at this
time as discussed under Repacking of FloTrex section.
Installing contractor should verify the following items.
1. Is there any visible shipping damage?
Yes No
2. Is the unit level?
Yes No
3. Are the unit clearances adequate for service and operation?
Yes No
4. Do all access doors open freely and are the handles operational?
Yes No
5. Have all electrical connections been tested for tightness?
Yes No
6. Does the electrical service correspond to the unit nameplate?
Yes No
7. On 208/230V units, has transformer tap been checked?
Yes No
8. Has overcurrent protection been installed to match the unit nameplate
requirement?
Yes No
9. Does the field water piping to the unit appear to be correct per design
parameters?
Yes No
Ambient Dry Bulb Temperature ________°F
Ambient Wet Bulb Temperature ________°F
Pre Startup Checklist
BL Series Startup Form
Ambient Temperature
51
Water/Glycol System
1. Has the entire system been flushed and pressure checked?
Yes No
2. Have isolation valves to the boiler been installed?
Yes No
3. Has the entire system been filled with fluid?
Yes No
4. Has air been bled from the heat exchangers and piping?
Yes No
5. Is there a minimum load of 50% of the design load?
Yes No
6. Has the water piping been insulated?
Yes No
7. Is the glycol the proper type and concentration (N/A if water)?
Yes No
8. What is the freeze point of the glycol (N/A if water)? ______________________________
No Water Leaks
Boiler Water Flow ________ gpm
Boiler Safety Check
Boiler Building Water Flow ________ gpm
hp
L1
L2
L3
Flow (gpm)
Boiler Building Pump #1
Boiler Building Pump #2
Boiler Water In Temperature ________°F
Boiler Water Out Temperature ________°F
Boiler
Amps
Boiler
Amps 1 3 2 4
Boiler Configuration
Pumping Package
Boilers
52
Maintenance Log
Entry Date
Action Taken
Name/Tel.
This log must be kept with the unit. It is the responsibility of the owner and/or
maintenance/service contractor to document any service, repair or adjustments. AAON Service
and Warranty Departments are available to advise and provide phone help for proper operation
and replacement parts. The responsibility for proper start-up, maintenance and servicing of the
equipment falls to the owner and qualified licensed technician.
53
Literature Change History
June 2010
Revision of the IOM adding PVC and CPVC piping Caution.
April 2012
Update of the IOM correcting the minimum inlet gas pressure for the 500 MBH boiler to 5” w.c
and the 750, 1000, and 1500 MBH boiler to 7” w.c., adding the electronic startup form, adding
the index of tables and figures, and updating the table of contents.
July 2013
Update of the feature string nomenclature options.
AAON
2425 South Yukon Ave.
Tulsa, OK 74107-2728
Phone: 918-583-2266
Fax: 918-583-6094
www.aaon.com
BL Series
Installation, Operation &
Maintenance
R53480 · Rev. A · 130725
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.