TECHNICAL GUIDE CHAMPION® PLUS SINGLE PACKAGE GAS/ELECTRIC
036-21366-003-C-0405
®
FLEXIBLE LIGHT COMMERCIAL UNIT
GENERAL
YORK’s Champion®package units are designed to handle applications ranging from residential to light commercial and any in between. The Champion® is a unit that gives you the flexibility and choices you need in today’s market.
AIR COOLED AIR CONDITIONERS 2 THRU 4 NOMINAL TON
DNP024, 030, 036, 042 and 048 13 SEER
FEATURING
FACTORY MOUNTED TXV
COOLING/GAS HEATING UNITS (NATURAL GAS OR PROPANE)
LOW PROFILE
QUIET OPERATION
COMMON FOOTPRINT
OPTIONAL SLIDE IN MOTORIZED DAMPERS
OPTIONAL SLIDE IN ECONOMIZERS
OPTIONAL PROPANE CONVERSION KIT
OPTIONAL HIGH ALTITUDE CONVERSION KIT (NATURAL GAS/PROPANE)
OPTIONAL LOW NOx KIT
FULL PERIMETER BASE RAILS
BOTTOM AND SIDE UTILITY CONNECTIONS
1” OR 2” CLEANABLE FILTERS STANDARD ON ALL 3 PHASE MODELS. OPTIONAL ON 1 PHASE MODELS
WARRANTY - 1 PHASE
10 year compressor
20 year heat exchanger
5 year other parts
WARRANTY - 3 PHASE
5 year compressor
10 year heat exchanger
1 year other parts
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
TABLE OF CONTENTS
036-21366-003-C-0405
DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
STANDARD FEATURES/BENEFITS . . . . . . . . . . . . 3
FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4
TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . 28
MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 29
LIST OF FIGURES
Fig# Pg#
1 PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . .2
2 UNIT COMPONENT LOCATION . . . . . . . . . . . . . . . . .6
3 FIELD WIRING DIAGRAM CONTROL WIRING. . . . . 17
4 POWER WIRING FIELD DIAGRAM. . . . . . . . . . . . . .18
5 UNIT DIMENSIONS - FRONT . . . . . . . . . . . . . . . . . .19
6 UNIT DIMENSIONS - FRONT & BOTTOM . . . . . . . .20
7 UNIT DIMENSIONS - BACK & BOTTOM. . . . . . . . . .20
8 TYPICAL SLAB ON GROUND INSTALLATION. . . . . 21
9 TYPICAL ROOF CURB INSTALLATION . . . . . . . . . . 21
10 TYPICAL DUCT APPLICATIONS. . . . . . . . . . . . . . . .22
11 UNIT CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . 22
12 ROOF CURB DIMENSIONS. . . . . . . . . . . . . . . . . . . .23
13 ROOF CURB CROSS SECTION . . . . . . . . . . . . . . . .23
14 TYPICAL WIRING DIAGRAM D*NP 024
(208/230-1-60) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
15 TYPICAL WIRING DIAGRAM D*NP 030-048
(208/230-1-60 POWER SUPPLY). . . . . . . . . . . . . . . .25
16 TYPICAL WIRING DIAGRAM D*NP 030-048
(208/230-3-60 POWER SUPPLY . . . . . . . . . . . . . . . . 26
17 TYPICAL WIRING DIAGRAM D*NP 030-048
(460-3-60 POWER SUPPLY). . . . . . . . . . . . . . . . . . . 27
18 TYPICAL WIRING DIAGRAM LEGEND. . . . . . . . . . . 28
LIST OF TABLES
Tbl# Pg#
1 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 RATINGS COOLING/GAS HEATING. . . . . . . . . . . . . . 7
3 DNP024 COOLING CAPACITIES - 2 TON. . . . . . . . . . 8
4 DNP030 COOLING CAPACITIES - 2-1/2 TON. . . . . . 10
5 DNP036 COOLING CAPACITIES - 3 TON. . . . . . . . . 11
6 DNP042 COOLING CAPACITIES - 3-1/2 TON. . . . . . 12
7 DNP048 COOLING CAPACITIES - 4 TON. . . . . . . . . 13
8 TWO TON AIR PERFORMANCE . . . . . . . . . . . . . . . . 14
9 SIDE SUPPLY AIR BLOWER PERFORMANCE -
208/230 VOLTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10 BOTTOM SUPPLY AIR BLOWER PERFORMANCE -
208/230 VOLTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11 ADDITIONAL STATIC PRESSURE RESISTANCE -
2, 2-1/2, 3 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
12 ADDITIONAL STATIC PRESSURE RESISTANCE -
3-1/2 AND 4 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
13 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14 UNIT DIMENSIONS FRONT . . . . . . . . . . . . . . . . . . . . 19
15 UNIT MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 19
16 UNIT WEIGHTS AND CENTER OF GRAVITY. . . . . . 22
FIGURE 1 - PRODUCT NOMENCLATURE
2 Unitary Products Group
Page 3
036-21366-003-C-0405
DESCRIPTION
These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct con­nections are required at the point of installation.
The gas-fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are avail­able in natural gas with field conversion to propane.
STANDARD FEATURES/BENEFITS
OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of
13.0. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common,
compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper ton­nage unit on that curb after the internal load has been deter­mined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory.
LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds.
All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and tem­perature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance.
Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces.
UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
CONVERTIBLE AIRFLOW DESIGN - The bottom duct open­ings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.
CONDENSATE PAN - A non-corrosive, long-lasting, water­tight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62­89 standards (Ventilation for Acceptable Indoor Air Quality).
CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI cop­per connection is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.
DURABLE FINISH - With a heavy duty cabinet made of pow­der-painted, galvanized steel the neutral color blends into surrounding areas. The powdered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy finish insures less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 stan­dards for 1000 hours salt spray rating. The highest in the industry.
FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location.
MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area.
TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surround­ing the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
CONDENSER COIL GRILLE - A multi-piece totally enclosed, rigidly mounted condenser coil grille provides protection from objects after installation and provides protection duri ng transi t.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the liv­ing area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compres­sor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for opti­mum strength and rigidity.
Unitary Products Group 3
Page 4
036-21366-003-C-0405
FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. These models have 2 cooling speeds and a single heating speed. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input. It cannot be field adjusted. This allows maximum comfort conditions.
Two ton models operate over a wide range of design condi­tions with a 3-speed direct-drive fan motor. These single phase models have the Comfort-Match system that allows different speed taps for heating or cooling operations.
SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also pro­vided to simplify the field interface of external controls. Mate­n-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the com­pressor if undesirable operating conditions occur.
EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability.
HEAT EXCHANGERS - Are corrosion-resistant, aluminized­steel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cool­ing cycle. This adds to longer heat exchanger life and higher long term efficiencies.
POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon comple­tion of the heating cycle to prolong the heat exchanger life.
SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units.
HOT SURFACE TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and elimi­nates nuisance lockouts. Also assures starts in damp condi­tions.
MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are con­structed of high-grade corrosion-resistant, aluminized-steel.
LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip­Track slide-out blower assembly.
SECURED SERVICE ACCESS PORTS - Protected, exter­nally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required.
EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assem­bly to slide-out for easy removal for maintenance and ease of trouble shooting.
REPLACEMENT PARTS - The installer requires no special training to replace any of the components of these units and does not need to maintain an inventory of unique parts.
SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit.
FIELD-INSTALLED ACCESSORIES
LOW NOx KIT - Kit includes all the necessary hardware and instructions to field convert units to reduce emissions to less than 40 nanogram per Joule. California requirement on single phase models only.
PROPANE CONVERSION KIT - Kit includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane.
HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane)
- Kit includes all necessary labels and instructions to field alter units with natural gas/propane for installations above 2000 feet. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately.
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modu­lating integrated economizer provides simultaneous opera­tion between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided.
SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved econo­mizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.
DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air tempera­ture dry bulb and humidity in conjunction with the single
4 Unitary Products Group
Page 5
036-21366-003-C-0405
enthalpy to determine the most economical mix. Single Enthalpy sensor also required.
PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by fur­nished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out prevent­ing any further operation until reset or problem is corrected. Package agency approved.
HAIL GUARD KIT - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection.
ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.Not required if Thermostat 2ET07700224 and 2ET04700224 are used.
FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable stan­dard size filters are shipped in one kit. The filter rack is suit­able for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct applica­tion only. Standard in all 3 Phase models.
MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.
RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening.
ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also pro­vides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available.
MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Stan­dard unit operation 45º F.
TRANSFORMER KIT - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.)
Unitary Products Group 5
Page 6
BLOW-THROUGH DESIGN
WITH RELIABLE ALUMINIZED
STEEL TUBULAR HEAT EX HANGERS
LONG LASTING
POWDER PAINT
FINISH
C
DIRECT DRIVE
CONDENSER
FAN MOTOR
HIGHLY EFFICIENT ENHANCE
COPPER TUBE/ALUMINUM FIN
EVAPORATOR COIL
HIGHLY EFFICIENT
ENHANCED COPPER
TUBE/ALUMINUM FIN
CONDENSER COIL
D
DECORATIVE PROTECTIVE COIL GAURD
036-21366-003-C-0405
REAR AND BOTTOM
RET RUNAIR AND SUPPLY AIR DUCT OPENINGS
HEAVY GAUGE
REMOVABLE
BASE RAILS
DIRECT DRIVE
BLOWER MOTOR WITH
SLIDE-OUT BLOWER ASSEMBLY
POWER VENTER MOTOR
HIGH VOLTAGE
TERMINAL BLOCK
SELF-DIAGNOSTIC CONTROLS WITH
"COMFORT-MATCH" SPEED CONTROL
AUTOMATIC GAS VALVE (1/2" - 14 NPTI)
HIGH EFFICIENCY
COMPRESSOR
RIGIDLY
MOUNTED
HOT SURFACE PILOT
HIGH GRADE ALUMINIZED
LOW VOLTAGE
TERMINAL BLOCK
ASSEMBLY
IN-SHOT BURNERS
FIGURE 2 - UNIT COMPONENT LOCATION TABLE 1: PHYSICAL DATA
1/2
DNP
NPTI
3.3 / 20 x 12 (2 Reqd.)
1/2 NPTI
3.3/20x12 (2 Reqd.)
1/2
EVAPORATOR
BLOWER
MODEL
CENTRIFUGAL BLOWER (Dia. x W. in.) 10 x 8 10 x 8 11 x 10 12 x 11 12 x 11 FAN MOTOR HP 1/2 3/4 3/4 1 1
024 030 036 042 048
ROWS DEEP 2 3333
EVAPORATOR
COIL
FINS PER INCH 15 13 13 13 16 FACE AREA (Sq. Ft.) 3.5 3.5 3.5 4.5 4.5 PROPELLER DIA. (in.) 22 22 22 22 22
CONDENSER
FAN
FAN MOTOR HP 1/4 1/4 1/4 1/4 1/3 NOM. CFM TOTAL 2,200 2,400 2,400 2,400 3,000 ROWS DEEP 1 1222
CONDENSER
COIL
FINS PER INCH 20 20 20 20 20 FACE AREA (Sq. Ft.) 11.7 11.7 11.7 14.7 14.7
CHARGE REFRIGERANT 22 (lbs./oz.) 4 / 10 4 / 9 6 / 12 9 / 6 8 / 4
FILTER FACE AREA (Sq. Ft.) Size (Nominal) 2.6 / 20 x 20 2.6 / 20 x 20 2.6/20x20
FURNACE
SECTION
NATURAL GAS BURNER ORIFICE NO. (Drill Size)
PROPANE BURNER ORIFICE NO. (Drill Size)
43 43 43 40 40
55 55 55 53 53
GAS CONNECTION SIZE 1/2 NPTI 1/2 NPTI
COMPRESSOR HERMETIC TYPE, (Qty. = 1) Recip Scroll Scroll Scroll Scroll
NPTI
6 Unitary Products Group
Page 7
036-21366-003-C-0405
TABLE 2: RATINGS COOLING/GAS HEATING
NET COOLING CAPACITY
MODEL
DNP
024N03606 25.4 13.3 1 1.6 81 45 36 80.2 2 25 - 55 024N05606 25.4 13.3 1 1.6 81 70 56 80.2 3 30 - 60 030N03606 30.6 13.4 11.75 80 45 36 80.2 2 25 - 55 030N03625 30.6 13.4 11.75 80 45 36 80.2 2 25 - 55 030N03646 30.6 13.4 11.75 80 45 36 80.2 2 25 - 55 030N05606 30.6 13.4 11.75 80 70 56 80.2 3 30 - 60 030N05625 30.6 13.4 11.75 80 70 56 80.2 3 30 - 60 030N05646 30.6 13.4 11.75 80 70 56 80.2 3 30 - 60 036N03606 37.4 13.65 11.75 81 45 36 80.4 2 25 - 55 036N03625 37.4 13.65 11.75 81 45 36 80.4 2 25 - 55 036N03646 37.4 13.65 11.75 81 45 36 80.4 2 25 - 55 036N05606 37.4 13.65 11.75 81 70 56 80.2 3 25 - 55 036N05625 37.4 13.65 11.75 81 70 56 80.2 3 25 - 55 036N05646 37.4 13.65 11.75 81 70 56 80.2 3 25 - 55 036N07206 37.4 13.65 11.75 81 90 72 80.1 4 30 - 60 036N07225 37.4 13.65 11.75 81 90 72 80.1 4 30 - 60 036N07246 37.4 13.65 11.75 81 90 72 80.1 4 30 - 60 042N06506 44.0 13.7 11.65 80 80 64 80.6 3 25 - 55 042N06525 44.0 13.7 11.65 80 80 64 80.6 3 25 - 55 042N06546 44.0 13.7 11.65 80 80 64 80.6 3 25 - 55 042N09006 44.0 13.7 11.65 80 108 86 80.8 4 45 - 75 042N09025 44.0 13.7 11.65 80 108 86 80.8 4 45 - 75 042N09046 44.0 13.7 11.65 80 108 86 80.8 4 45 - 75 048N06506 48.0 13.20 11.7 84 80 64 80.8 3 25 - 55 048N06525 48.0 13.20 11.7 84 80 64 80.8 3 25 - 55 048N06546 48.0 13.20 11.7 84 80 64 80.8 3 25 - 55 048N09006 48.0 13.20 11.7 84 108 86 80.6 4 35 - 65 048N09025 48.0 13.20 11.7 84 108 86 80.6 4 35 - 65 048N09046 48.0 13.20 11.7 84 108 86 80.6 4 35 - 65 048N11006 48.0 13.20 11.7 84 135 107 80.5 5 45 - 75 048N11025 48.0 13.20 11.7 84 135 107 80.5 5 45 - 75 048N11046 48.0 13.20 11.7 84 135 107 80.5 5 45 - 75
1.
Net Cooling Capacity = ARI 210 standard rating conditions.
2.
(dbels) = ARI 270-95
3.
Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the
MBH
SEER
3
1
EER
SOUND RATING
4
(dbels)
INPUT
2
(MBH)
GAS HEAT CAPACITY / EFFICIENCIES
5
OUTPUT
(MBH)
AFUE
(%)
NUMBER OF
BURNERS
TEMP.
RISE
(°F) RANGE
total electric power input in watt-hours during the same period.
4.
Tested in accordance with ARI 210 Standard Rating Conditions.
5.
AFUE = Annual Fuel Utilization Efficiency.
Unitary Products Group 7
Page 8
TABLE 3: DNP024 COOLING CAPACITIES - 2 TON
036-21366-003-C-0405
AIR ON
EVAPORATOR
COIL
600
700
800
900
WB
°F
72 26.5 1.94 15.8 14.1 12.4 10.7 9.0 #N/A #N/A 24.7 2.07 15.8 14.1 12.4 10.7 9.0 #N/A #N/A 67 24.3 1.95 19.4 17.7 16.0 14.3 12.6 10.9 9.2 22.5 2.08 19.2 17.4 15.7 14.0 12.3 10.6 8.9 62 22.4 1.93 57 22.1 1.92 72 28.3 1.98 17.9 15.9 13.8 11.8 9.8 #N/A #N/A 26.3 2.12 17.6 15.6 13.6 11.6 9.5 #N/A #N/A 67 25.9 1.98 21.9 19.9 17.9 15.9 13.8 11.8 9.8 23.9 2.12 21.3 19.3 17.2 15.2 13.2 11.2 9.2 62 23.9 1.97 57 23.5 1.96 72 30.0 2.02 20.0 17.6 15.3 13.0 10.6 #N/A #N/A 27.9 2.17 19.5 17.1 14.8 12.5 10.1 #N/A #N/A 67 27.5 2.02 24.4 22.1 19.8 17.4 15.1 12.8 10.4 25.4 2.17 23.4 21.1 18.8 16.4 14.1 11.8 9.4 62 25.4 2.00 57 25.0 1.99 72 30.2 2.05 21.5 18.8 16.1 13.5 10.8 #N/A #N/A 28.1 2.20 20.9 18.3 15.6 13.0 10.3 #N/A #N/A 67 27.6 2.05 26.1 23.5 20.9 18.2 15.5 12.9 10.2 25.6 2.20 24.6 22.5 19.8 17.2 14.5 11.9 9.2 62 25.5 2.03 57 25.2 2.02 72 30.4 2.08 22.9 20.0 17.0 14.0 11.0 #N/A #N/A 28.4 2.22 22.4 19.4 16.5 13.5 10.5 #N/A #N/A 67 27.8 2.08 27.8 24.9 21.9 19.0 16.0 13.0 10.0 25.8 2.22 62 25.7 2.07 57 25.3 2.06
CFM
1000
TEMPERATURE OF AIR ON CONDENSER COIL TEMPERATURE OF AIR ON CONDENSER COIL
85°F 95°F
NET CAP. MBH
POWER
INPUT
KW
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
22.4 20.8 19.1 17.4 15.7 14.0 12.3 20.9 2.04 20.9 20.7 18.9 17.2 15.5 13.8 12.1
22.1 21.6 19.8 18.1 16.4 14.7 13.0 20.9 2.03 20.9 20.9 19.2 17.4 15.7 14.0 12.3
23.9 23.1 21.4 19.3 17.3 15.3 13.3 22.2 2.09 22.2 22.1 20.8 18.7 16.7 14.7 12.7
23.5 23.3 22.2 20.2 18.1 16.1 14.1 22.2 2.08 22.2 22.2 21.0 19.0 17.0 14.9 12.9
25.4 25.4 23.6 21.3 18.9 16.6 14.3 23.5 2.14 23.5 23.5 22.6 20.3 17.9 15.6 13.3
25.0 25.0 24.5 22.2 19.8 17.5 15.2 23.6 2.13 23.6 23.6 22.9 20.5 18.2 15.9 13.5
25.5 25.5 24.6 22.0 19.3 16.7 14.0 23.7 2.16 23.7 23.7 23.3 20.6 17.9 15.3 12.6
25.2 25.2 24.9 22.2 19.6 16.9 14.3 23.8 2.15 23.8 23.8 23.4 20.7 18.1 15.4 12.8
25.7 25.7 25.7 22.7 19.7 16.7 13.7 23.9 2.19 23.9 23.9 23.9 20.9 18.0 15.0 12.0
25.3 25.3 25.3 22.3 19.3 16.4 13.4 23.9 2.18 23.9 23.9 23.9 21.0 18.0 15.0 12.0
1
NET CAP. MBH
POWER
INPUT
KW
25.8 23.9 20.9 17.9 14.9 11.9 9.0
SENSIBLE CAPACITY
1
AIR ON
EVAPORATOR
COIL
CFM
1000
WB
°F
72 23.1 2.24 15.1 13.4 11.7 10.0 8.3 #N/A #N/A 21.4 2.41 14.5 12.8 11.1 9.3 7.6 #N/A #N/A
600
700
800
900
67 20.9 2.21 18.6 16.9 15.2 13.5 11.8 10.1 8.4 19.4 2.35 18.1 16.4 14.7 13.0 11.3 9.6 7.9 62 19.7 2.20 57 19.8 2.20 72 24.4 2.28 16.9 14.8 12.8 10.8 8.8 #N/A #N/A 22.6 2.45 16.1 14.1 12.0 10.0 8.0 #N/A #N/A 67 22.2 2.26 20.5 18.7 16.6 14.6 12.6 10.6 8.6 20.4 2.39 19.8 18.1 16.0 14.0 12.0 10.0 7.9 62 20.9 2.24 57 21.0 2.24 21.0 21.0 19.8 17.8 15.7 13.7 11.7 19.7 2.39 19.7 19.7 18.6 16.5 14.5 12.5 10.5 72 25.8 2.33 18.6 16.2 13.9 11.6 9.2 #N/A #N/A 23.7 2.48 17.7 15.4 13.0 10.7 8.4 #N/A #N/A 67 23.4 2.30 22.4 20.4 18.1 15.7 13.4 11.1 8.7 21.4 2.43 62 22.0 2.28 22.0 22.0 21.2 18.9 16.6 14.2 11.9 20.5 2.43 20.5 20.5 19.9 17.6 15.2 12.9 10.6 57 22.1 2.28 72 26.0 2.37 19.9 17.3 14.6 12.0 9.3 #N/A #N/A 23.9 2.53 19.0 16.3 13.7 11.0 8.3 #N/A #N/A 67 23.6 2.34 23.1 21.6 19.0 16.3 13.7 11.0 8.4 21.6 2.48 62 22.2 2.32 57 22.3 2.32 72 26.3 2.40 21.3 18.3 15.4 12.4 9.4 #N/A #N/A 24.2 2.58 20.2 17.3 14.3 11.3 8.3 #N/A #N/A 67 23.8 2.37 62 22.4 2.36 57 22.5 2.36
1.
These capacities are net capacities (the indoor fan heat is deducted).
TEMPERATURE OF AIR ON CONDENSER COIL TEMPERATURE OF AIR ON CONDENSER COIL
105°F 115°F
NET CAP. MBH
POWER
INPUT
KW
86 83 80 77 74 71 68 86 83 80 77 74 71 68
19.7 19.6 17.9 16.2 14.5 12.8 11.1 18.5 2.35 18.5 18.5 16.9 15.2 13.4 11.7 10.0
19.8 19.8 18.1 16.4 14.7 13.0 11.3 18.7 2.36 18.7 18.7 17.0 15.3 13.6 11.9 10.2
20.9 20.8 19.6 17.6 15.5 13.5 11.5 19.5 2.39 19.5 19.5 18.4 16.4 14.3 12.3 10.3
22.1 22.1 21.5 19.1 16.8 14.5 12.1 20.7 2.43 20.7 20.7 20.1 17.8 15.4 13.1 10.8
22.2 22.2 21.8 19.2 16.5 13.9 11.2 20.7 2.48 20.7 20.7 20.4 17.7 15.1 12.4 9.8
22.3 22.3 22.0 19.3 16.7 14.0 11.4 20.9 2.48 20.9 20.9 20.6 17.9 15.3 12.6 10.0
23.8 22.8 19.9 17.0 14.0 11.0 8.0 21.8 2.53 21.8 21.8 19.0 16.0 13.0 10.1 7.1
22.4 22.4 22.4 19.4 16.5 13.5 10.5 20.9 2.53 20.9 20.9 20.9 17.9 14.9 12.0 9.0
22.5 22.5 22.5 19.6 16.6 13.6 10.6 21.1 2.53 21.1 21.1 21.1 18.1 15.2 12.2 9.2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
ALL SENSIBLE CAPACITY
1
NET CAP. MBH
POWER
INPUT
KW
21.4 19.7 17.3 15.0 12.7 10.3 8.0
21.6 20.8 18.2 15.5 12.9 10.2 7.5
SENSIBLE CAPACITY
1
8 Unitary Products Group
Page 9
036-21366-003-C-0405
TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D)
AIR ON
EVAPORATOR
COIL
CFM
600
700
800
900
1000
1.
These capacities are net capacities (the indoor fan heat is deducted).
WB
°F
72 19.8 2.6 13.8 12.1 10.4 8.7 7.0 #N/A #NIA 67 17.8 2.5 17.6 15.9 14.2 12.5 10.8 9.1 7.4 62 17.4 2.5 57 17.6 2.5 72 20.7 2.6 15.3 13.3 11.3 9.2 7.2 #N/A #N/A 67 18.6 2.5 19.0 17.4 15.4 13.4 11.4 9.4 7.3 62 18.2 2.5 57 18.5 2.6 72 21.6 2.6 16.8 14.5 12.2 9.8 7.5 #N/A #N/A 67 19.4 2.6 20.4 19.0 16.6 14.3 12.0 9.6 7.3 62 19.0 2.6 57 19.3 2.6 72 21.8 2.7 18.0 15.3 12.7 10.0 7.4 #N/A #N/A 67 19.7 2.6 20.1 19.9 17.3 14.7 12.0 9.4 6.7 62 19.2 2.6 57 19.5 2.6 72 22.1 2.8 19.1 16.2 13.2 10.2 7.2 #N/A #N/A 67 19.9 2.7 62 19.4 2.7 57 19.7 2.7
NET CAP. MBH
POWER
INPUT
KW
TEMPERATURE OF AIR ON CONDENSER COIL
86 83 80 77 74 71 68
17.4 17.5 15.8 14.1 12.4 10.7 9.0
17.6 17.6 16.0 14.3 12.6 10.8 9.1
18.2 18.2 17.2 15.2 13.1 11.1 9.1
18.5 18.5 17.3 15.3 13.3 11.3 9.2
19.0 19.0 18.5 16.2 13.9 11.5 9.2
19.3 19.3 18.7 16.4 14.0 11.7 9.4
19.2 19.2 19.0 16.3 13.7 11.0 8.3
19.5 19.5 19.2 16.5 13.9 11.2 8.6
19.9 20.8 18.1 15.1 12.1 9.1 6.1
19.4 19.4 19.4 16.4 13.4, 10.5 7.5
19.7 19.7 19.7 16.7 13.7 10.8 7.8
ALL SENSIBLE CAPACITY
125°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
1
Unitary Products Group 9
Page 10
TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON
036-21366-003-C-0405
TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP.MBH
TOT AL POWER INPUT kW
86 83
Bulb °F
Entering Dry
Bulb °F
Entering Dry
Bulb °F
Entering Dry
Bulb °F
Entering Dry
Bulb °F
Entering Dry
80 77 74 71 68
86 83 80 77 74 71 68
86 83 80 77 74 71 68
86 83 80 77 74 71 68
86 83 80 77 74 71 68
85 °F
95 °F
105 °F
115 °F
125 °F
1.
These capacities are net capacities (the indoor fan heat is deducted)
1
MBH
Sensible Capacity
NET CAP. MBH
TOT AL POWER INPUT kW
1
MBH
Sensible Capacity
NET CAP.MBH
TOTAL POWERINPUT kW
1
MBH
Sensible Capacity
NET CAP.MBH
TOTAL POWER NPUT kW
1
MBH
Sensible Capacity
NET CAP. MBH
TOT AL POWER INPUT kW
1
MBH
Sensible Capacity
72 67 62 57 72 67 62 57
33.6 31.6 30.3 30.2 34.5 32.4 31.1 31.0
2.4 2.4 2.3 2.3 2.6 2.6 2.5 2.5
23.6 29.2
20.7 26.3
17.8 23.4 28.4 29.6 19.7 25.9
14.9 20.5 25.5 26.7 16.0 22.2 27.3 27.3
12.0 17.5 22.6 23.8 12.3 18.5 23.6 23.5 N/A 14.6 19.7 20.8 N/A 14.8 19.9 19.8 N/A 11.7 16.8 17.9 N/A 11.0 16.2 16.1
32.7 30.5 28.8 28.9 33.5 31.3 29.6 29.7
2.6 2.6 2.6 2.5 2.8 2.8 2.8 2.7
23.1 29.0
20.2 26.1
17.3 23.2 27.9 28.4 19.4 26.0
14.4 20.3 25.0 25.4 15.7 22.3 25.9 26.0
11.5 17.3 22.1 22.5 12.0 18.5 22.1 22.2 N/A 14.4 19.2 19.6 N/A 14.8 18.4 18.5 N/A 11.5 16.3 16.7 N/A 11.1 14.7 14.8
31.0 28.3 27.3 27.3 32.2 29.4 28.3 28.3
2.9 2.9 2.9 2.9 3.1 3.1 3.0 3.0
22.6 27.6
19.6 25.1
16.7 22.2 26.4 26.8 18.9 25.1
13.8 19.3 23.5 23.8 15.2 21.4 24.6 24.6
10.9 16.4 20.6 20.9 11.5 17.6 20.8 20.9 N/A 13.5 17.7 18.0 N/A 13.9 17.1 17.2 N/A 10.5 14.8 15.1 N/A 10.2 13.4 13.4
29.3 26.2 25.7 25.7 30.8 27.5 27.0 27.0
3.2 3.3 3.2 3.2 3.4 3.4 3.3 3.3
22.0
19.0 24.1
16.1 21.2 24.9 25.2 18.4 24.2
13.2 18.3 22.0 22.2 14.7 20.5 23.3 23.2
10.3 15.4 19.1 19.3 10.9 16.8 19.5 19.5 N/A 12.5 16.2 16.4 N/A 13.0 15.8 15.8 N/A 9.6 13.3 13.5 N/A 9.3 12.1 12.1
27.6 24.1 24.2 24.0 29.4 25.6 25.7 25.6
3.5 3.6 3.5 3.5 3.6 3.7 3.6 3.6
21.4 24.8
18.4 23.2
15.5 20.2 23.4 23.6 17.9 23.3
12.6 17.3 20.5 20.7 14.2 19.6 22.0 21.9
9.7 14.4 17.6 17.7 10.4 15.9 18.3 18.1 N/A 11.5 14.7 14.8 N/A 12.1 14.5 14.4 N/A 8.6 11.8 11.9 N/A 8.4 10.8 10.7
1,000 CFM 1,250 CFM
WB °F WB °F
26.2 25.7 25.7 25.8 27.5 27.0 27.0
ALL SENSIBLE CAPACITY
AIR ON EVAPORATOR COIL
30.3 30.2 27.2 32.4 31.1 31.0
30.3 30.2 23.5 29.7 31.1 31.0
31.1 31.0
28.8 28.9 26.9 31.3 29.6 29.7
28.8 28.9 23.1 29.7 29.6 29.7
29.6 29.7
27.3 27.3 26.4 29.4 28.3 28.3
27.3 27.3 22.6 28.6 28.3 28.3
28.3 28.3
25.7 25.7 22.1 27.5 27.0 27.0
27.0 27.0
24.2 24.0 25.3 25.6 25.7 25.6
24.2 24.0 21.6 26.4 25.7 25.6
25.7 25.6
10 Unitary Products Group
Page 11
036-21366-003-C-0405
TABLE 5: DNP036 COOLING CAPACITIES - 3 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP.
MBH
TOTAL POWER
INPUT kW
86 29.5 35.8 37.4 36.7 31.8 38.4 38 37.2
85 °F
1
MBH
Sensible Capacity
TOTAL POWER
95 °F
1
MBH
Sensible Capacit y
TOTAL POWER
105 °F
1
MBH
Sensible Capacity
TOTAL POWER
115 °F
1
MBH
Sensible Capacity
TOTAL POWER
125 °F
1
MBH
Sensible Capacity
1.
These capacities are net capacities (the indoor fan heat is deducted).
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
83 26 32.3 80 22.5 28.8 34.8 35.6 23.8 30.4 36.7 36.7 77 19 25.3 31.3 32.1 19.9 26.4 32.7 32.7 74 15.5 21.8 27.8 28.6 15.9 22.5 28.7 28.7
Bulb °F
71 - 18.3 24.3 25.1 - 18.5 24.7 24.7 68 - 14.8 20.8 21.6 - 14.5 20.7 20.7
86 28.5 34.8 35.7 35.3 31 36.9 36.6 36.2 83 25 31.3 80 21.5 27.8 33.5 33.9 23 29.7 25.5 35.5 77 18 24.3 30 30.4 19 25.7 31.5 31.5 74 14.5 20.8 26.5 26.9 15 21.7 17.6 27.5
Bulb °F
71 - 17.3 23 23.4 - 17.7 23.6 23.5 68 - 13.8 19.5 19.9 - 13.8 19.6 19.5
86 27.6 33.6 33.9 33.6 29.9 35.1 34.8 34. 5 83 24.1 30.1 33.9 33.6 26 32.4 34.8 34.5 80 20.6 26.6 32 32.2 22 28.4 33.9 33.8 77 17.1 23.1 28.5 28.7 18 24.4 29.9 29.8 74 13.6 19.6 25 25.2 14 20.5 25.9 25.8
Bulb °F
71 - 16.1 21.5 21.7 - 16.5 21.9 21.8 68 - 12.6 18 18.2 - 12.5 18 17.9
86 26.6 32.4 32.2 31.9 28.9 33.4 33.1 32.8 83 23.1 28.9 32.2 31.9 24.9 31.1 33.1 32.8 80 19.6 25.4 30.6 30.6 21 27.1 32.3 32.1 77 16.1 21.9 27.1 27.1 17 23.2 28.3 28.1 74 12.6 18.4 23.6 23.6 13 19.2 24.3 24.1
Bulb °F
71 - 14.9 20.1 20.1 - 15.2 20.3 20.2 68 - 11.4 16.6 16.6 - 11.2 16.3 16.2
86 25.6 31.2 30.4 30.1 27.9 31.6 31.3 31 83 22.1 27.7 80 18.6 24.2 19.1 28.9 19.9 25.9 30.6 30.4 77 15.1 20.7 25.6 25.4 15.9 21.9 26.6 26.4 74 11.6 17.2 22.1 21.9 12 17.9 22.7 22.5
Bulb °F
71 - 13.7 18.6 18.4 - 13.9 18.7 18.5 68 - 10.2 15.1 14.9 - 9.9 14.7 14.5
ALL SENSIBLE CAPACITY
72 67 62 57 72 67 62 57
43.3 39.9 37.4 36.7 44 40.5 38 37.2
2.932.89 2.9 2.883.083.053.063.04
41.4 37.1 35.7 35.3 42.5 38 36.6 36.2
3.22 3.27 3.18 3.15 3.32 3.37 3.28 3.25
38.5 34.8 33.9 33.6 39.6 35.8 34.8 34.5
3.613.61 3.5 3.483.733.723.613.59
35.6 32.6 32.2 31.9 36.7 33.5 33.1 32.8
4.01 3.95 3.82 3.8 4.14 4.07 3.93 3.92
32.8 30.2 30.4 30.1 33.7 31.2 31.3 30
4.4 4.3 4.1 4.1 4.5 4.4 4.3 4.2
AIR ON EVAPORATOR COIL
1,200 CFM 1,350 CFM
WB °F WB °F
37.4 36.7 27.8 34.4 38 37.2
35.7 35.3 27 33.7 36.6 36.2
30.4 30.1 23.9 29.9 31.3 31
Unitary Products Group 11
Page 12
TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON
036-21366-003-C-0405
TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP. 48.4 44.5 40.9 41.2 54.0 49.6 45.6 46.0
TOTAL POWER 3.4 3.3 3.3 3.3 3.8 3.7 3.6 3.7
86 33.0 39.9 40.9 41.2 36.8 44.4 45.6 46.0 83 29.1 36.0
85 °F
95 °F
105 °F
115 °F
125 °F
1.
These capacities are net capacities (the indoor fan heat is deducted)
1
MBH
Sensible Capacity
TOTAL POWER 3.8 3.6 3.8 3.6 4.2 4.0 4.2 4.0
1
MBH
Sensible Capacity
TOTAL POWER 4.2 4.1 4.1 4.0 4.6 4.5 4.6 4.5
1
MBH
Sensible Capacity
TOTAL POWER 4.6 4.5 4.5 4.5 5.1 5.0 5.1 5.0
1
MBH
Sensible Capacity
TOTAL POWER 5.0 5.0 4.9 4.9 5.6 5.5 5.5 5.5
1
MBH
Sensible Capacity
Entering Dry
NET CAP. 46.1 42.4 39.6 39.1 51.3 47.3 44.1 43.5
Entering Dry
NET CAP. 43.5 40.0 37.2 37.2 48.5 44.6 41.4 41.5
Entering Dry
NET CAP. 41.0 37.6 34.7 35.4 45.7 41.9 38.7 39.4
Entering Dry
NET CAP. 38.5 35.2 32.3 33.6 43.0 39.2 36.0 37.4
Entering Dry
80 25.2 32.0 38.1 40.4 28.1 35.7 42.4 45.0 77 21.3 28.1 34.2 36.5 23.7 31.3 38.1 40.7 74 17.3 24.2 30.2 32.6 19.3 27.0 33.7 36.3
Bulb °F
71 N/A 20.3 26.3 28.7 N/A 22.6 29.3 31.9 68 N/A 16.4 22.4 24.7 N/A 18.2 25.0 27.6
86 32.2 38.8 39.6 39.1 35.9 43.3 44.1 43.5 83 28.3 34.9 80 24.4 31.0 37.6 38.7 27.2 34.5 41.9 43.1 77 20.5 27.1 33.7 34.8 22.8 30.2 37.6 38.7 74 16.6 23.1 29.8 30.8 18.5 25.8 33.2 34.4
Bulb °F
71 N/A 19.2 25.9 26.9 N/A 21.4 28.8 30.0 68 N/A 15.3 21.9 23.0 N/A 17.1 24.5 25.6
86 31.3 38.0 37.2 37.2 34.9 42.3 41.4 41.5 83 27.4 34.1 80 23.5 30.2 36.2 36.7 26.2 33.6 40.3 40.9 77 19.6 26.2 32.3 32.8 21.8 29.2 36.0 36.5 74 15.7 22.3 28.3 28.8 17.4 24.9 31.6 32.2
Bulb °F
71 N/A 18.4 24.4 24.9 N/A 20.5 27.2 27.8 68 N/A 14.5 20.5 21.0 N/A 16.1 22.8 23.4
86 30.4 37.2 34.7 35.4 33.9 41.4 38.7 39.4 83 26.5 33.3 34.7 35.4 29.5 37.1 38.7 39.4 80 22.6 29.3 77 18.7 25.4 30.8 30.8 20.8 28.3 34.3 34.3 74 14.7 21.5 26.9 26.8 16.4 24.0 30.0 29.9
Bulb °F
71 N/A 17.6 23.0 22.9 N/A 19.6 25.6 25.6 68 N/A 13.7 19.0 19.0 N/A 15.2 21.2 21.2
86 29.5 36.3 32.3 33.6 32.9 40.5 36.0 37.4 83 25.6 32.4 32.3 33.6 28.5 36.1 36.0 37.4 80 21.7 28.5 33.3 32.7 24.1 31.8 37.1 36.4 77 17.7 24.6 29.4 28.8 19.8 27.4 32.7 32.1 74 13.8 20.7 25.4 24.9 15.4 23.0 28.3 27.7
Bulb °F
71 N/A 16.7 21.5 20.9 N/A 18.7 24.0 23.3 68 N/A 12.8 17.6 17.0 N/A 14.3 19.6 19.0
72 67 62 57 72 67 62 57
ALL SENSIBLE CAPACITY
AIR ON EVAPORATOR COIL
1,350 CFM 1,500 CFM
WB °F WB °F
40.9 41.2 32.4 40.1 45.6 46.0
39.6 39.1 31.6 38.9 44.1 43.5
37.2 37.2 30.6 38.0 41.4 41.5
34.7 34.7 25.2 32.7 38.7 38.7
12 Unitary Products Group
Page 13
036-21366-003-C-0405
TABLE 7: DNP048 COOLING CAPACITIES - 4 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP.
MBH
TOTAL POWER
INPUT kW
86 35.8 43.7 45.6 45.9 39.1 47.7 46.6 46.9
85 °F
1
MBH
Sensible Capacity
TOTAL POWER
95 °F
1
MBH
Sensible Capacity
TOTAL POWER
105 °F
1
MBH
Sensible Capacity
TOTAL POWER
115 °F
1
MBH
Sensible Capacity
TOTAL POWER
125 °F
1
MBH
Sensible Capacity
1.
These capacities are net capacities (the indoor fan heat is deducted).
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
NET CAP.
MBH
INPUT kW
Entering Dry
83 31.7 39.6 44.6 45.3 34.5 43 46.6 46.9 80 27.7 35.6 42.4 43.6 29.8 38.3 45.7 46.9 77 23.6 31.6 38.4 39.5 25.1 33.7 41 42.3 74 19.6 27.5 34.3 35.5 20.5 29 36.3 37.6
Bulb °F
71 - 23.5 30.3 31.4 - 24.3 31.7 32.9 68 - 19.4 26.2 27.4 - 19.7 27 28.3
86 35.4 42.9 43.8 44.0 38.4 46.4 43.9 44.2 83 31.4 38.9 42.8 43.2 33.8 41.7 80 27.4 34.9 40.9 41.5 29.1 37.1 43.5 44.2 77 23.3 30.8 36.8 37.5 24.4 32.4 38.8 39.5 74 19.3 26.8 32.8 33.4 19.8 27.7 34.1 34.8
Bulb °F
71 - 22.7 28.7 29.4 - 23.1 29.5 30.2 68 - 18.7 24.7 25.4 - 18.4 24.8 25.5
86 34.1 41.3 41.4 41.7 37.1 4.44 41.8 42.1 83 30.0 37.7 40.7 41.1 32.4 40.6 80 26.0 33.6 38.9 39.4 27.8 35.9 41.6 77 22.0 29.6 34.9 35.3 23.1 31.3 36.9 37.4 74 17.8 25.6 30.8 31.3 18.4 26.6 32.3 32.7
Bulb °F
71 - 21.5 26.8 27.3 - 21.9 27.6 28.1 68 - 17.5 22.8 23.2 - 17.3 22.9 23.4
86 32.7 39.7 39.1 39.4 35.8 42.5 39.7 40 83 28.7 36.5 38.7 38.9 31.1 39.5 80 24.6 32.4 37.0 37.2 26.4 34.8 77 20.6 28.4 32.9 33.2 21.8 30.1 35 35.3 74 16.6 24.4 28.9 29.1 17.1 25.5 30.4 30.6
Bulb °F
71 - 20.3 24.9 25.1 - 20.8 25.7 26 68 - 16.3 20.8 21.1 - 16.2 21 21.3
86 31.4 38.0 36.8 37.0 34.5 40.5 37.6 37.9 83 27.3 35.3 36.7 36.8 29.8 38.4 37.6 37.9 80 23.3 31.2 35.1 35.1 25.1 33.7 77 19.2 27.2 31.0 31.0 20.5 29 33.2 33.2 74 15.2 23.1 27.0 27.0 15.8 24.4 28.5 28.5
Bulb °F
71 - 19.1 22.9 23.0 - 19.7 23.8 23.9 68 - 15.1 18.9 18.9 - 15 19.2 19.2
ALL SENSIBLE CAPACITY
72 67 62 57 72 67 62 57
54.0 49.2 45.6 45.9 55.2 50.4 46.6 46.9
3.69 3.66 3.62 3.57 3.85 3.83 3.79 3.73
51.8 46.8 43.8 44.0 51.9 46.9 43.9 44.2
4.07 4.04 4.01 3.99 4.21 4.18 4.15 4.12
48.7 44.3 41.4 41.7 49.2 44.7 41.8 42.1
4.49 4.45 4.38 4.34 4.63 4.59 4.51 4.48
45.7 41.8 39.1 39.4 46.4 42.5 39.7 40
4.91 4.86 4.74 4.70 5.05 5 4.87 4.83
42.7 39.3 36.8 37.0 43.6 40.2 37.6 37.9
4.3 5.3 5.1 5.0 5.5 5.4 5.2 5.2
AIR ON EVAPORATOR COIL
1,400 CFM 1,600 CFM
WB °F WB °F
43.9 44.2
41.8 42.1
42.1
39.7 40
39.7 40
37.6 37.9
Unitary Products Group 13
Page 14
036-21366-003-C-0405
WATTS
1
EXTERNAL STAIC PRESSURE - IWG
CFM
TABLE 8: TWO TON AIR PERFORMANCE
MODEL #
DNH (Cooling/ Heating)
MTR SPD
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10
CFM
WATTS
CFM
WATTS
CFM
SIDE SUPPLY AIR PERFORMANCE - 208 VOLT
HI----------984443894422751390608358----
024
MED 994 333 947 321 901 309 854 297 774 280 695 263 615 246 - - - - - - - ­LOW743243700235657226614218--------------
SIDE SUPPLY AIR BLOWER PERFORMANCE - 230 VOLT
HI------------929491809473688454----
024
MED - - - - 999 353 944 338 865 319 785 299 706 280 - - - - - - - ­LOW998372906333813294721255651241------------
BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208 VOLT
HI----------886398805380676351547322----
024
MED 895 300 853 289 811 278 769 267 697 252 625 237 554 221 - - - - - - - ­LOW669219630211591204553196--------------
BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 VOLTS
HI------------836442728425620409----
024
1.
MED - - - - 899 318 850 304 778 287 707 269 635 252 - - - - - - - ­LOW898335815300732265649230586217------------
Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to Table 11 and 12.
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
14 Unitary Products Group
Page 15
036-21366-003-C-0405
TABLE 9: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS
EXTERNAL STATIC PRESSURE - IWG
MODEL #
DNP
030
030
030
030
036
036
036
036
036
042
042
042
042
048
048
048
048
048
1.
Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 and 12.
MODE
(COOLING / HEATING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (2 TUBE)
(FACTORY SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (2 TUBE)
(FACTORY SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
HEATING (5 TUBE)
(FACTORY SETTING)
CFM
1000 248 298 325 365 385 411 470 498 500
1250 342 385 431 474 510 562 614 657 694
850 169 217 237 278 302 334 374 401 431
1100 300 338 378 416 447 493 539 576 609
1200 354 396 436 511 548 599 641 677 721
1350 442 503 563 606 648 685 721 774 826
700 207 231 254 298 320 349 ~ ~ ~
1250 383 432 478 543 581 628 ~ ~ ~
1350 442 503 563 606 648 685 ~ ~ ~
1350 410 457 504 575 646 687 729 780 830
1500 450 500 553 641 729 798 830 872 939
1500 450 500 553 641 729 798 830 872 939
1275 388 433 478 545 612 652 691 739 787
1400 427 476 525 599 673 716 759 812 865
1600 476 532 587 687 786 872 958 994 1030
1525 458 511 564 654 744 814 ~ ~ ~
1600 476 532 587 687 786 872 ~ ~ ~
1600 476 532 587 687 786 872 ~ ~ ~
.20 .30 .40 .50 .60 .70 .80 .90 1.0
WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS
1
Unitary Products Group 15
Page 16
036-21366-003-C-0405
TABLE 10: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS
EXTERNAL STATIC PRESSURE - IWG
MODEL #
DNP
030
030
030
030
036
036
036
036
036
042
042
042
042
048
048
048
048
048
1.
Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 and 12.
MODE
(COOLING / HEATING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (2 TUBE)
(FACTORY SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (2 TUBE)
(FACTORY SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
COOLING
(FACTORY SETTING)
COOLING
(FIELD SETTING)
HEATING (3 TUBE)
(FACTORY SETTING)
HEATING (4 TUBE)
(FACTORY SETTING)
HEATING (5 TUBE)
(FACTORY SETTING)
CFM
1000 248 298 325 365 385 411 470 498 500
1250 342 385 431 474 510 562 614 657 694
850 169 217 237 278 302 334 374 401 431
1100 300 338 378 416 447 493 539 576 609
1200 354 396 436 511 548 599 641 677 721
1350 442 503 563 606 648 685 721 774 826
700 207 231 254 298 320 349 ~ ~ ~
1250 383 432 478 543 581 628 ~ ~ ~
1350 442 503 563 606 648 685 ~ ~ ~
1350 410 457 504 575 646 687 729 780 830
1500 450 500 553 641 729 798 830 872 939
1500 450 500 553 641 729 798 830 872 939
1275 388 433 478 545 612 652 691 739 787
1400 427 476 525 599 673 716 759 812 865
1600 476 532 587 687 786 872 958 994 1030
1525 458 511 564 654 744 814 ~ ~ ~
1600 476 532 587 687 786 872 ~ ~ ~
1600 476 532 587 687 786 872 ~ ~ ~
.20 .30 .40 .50 .60 .70 .80 .90 1.0
WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS
1
16 Unitary Products Group
Page 17
036-21366-003-C-0405
*
TABLE 11: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON
RESISTANCE, IWG
DESCRIPTION
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600
WET EVAPORATOR COIL .01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09
ECONOMIZER
FILTER FRAME KIT .01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20
1.
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
1
.00 .00 .00 .01 .01 .01 .01 .02 .03 .04 .05 .06
CFM
TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2 AND 4 TON
RESISTANCE, IWG
DESCRIPTION
1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
WET EVAPORATOR COIL .02 .03 .04 .05 .06 .07 .07 .08 .09 .09
ECONOMIZER
FILTER FRAME KIT .04 .04 .05 .05 .06 .07 .08 .09 .10 .11
1.
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
1
.02 .02 .02 .03 .03 .04 .04 .04 .05 .05
CFM
NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.
THERMOSTAT
*=Minimumwiresizeof18AWG
wire should be used for all field installed 24 volt wire.
PROGRAMMABLE
R
G
W
C
UNIT TERMINAL STRIP
**
R
G
YY
W
C
24 VOLT TRANSFORMER
THERMOSTAT ONLY
FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING
Unitary Products Group 17
Page 18
036-21366-003-C-0405
L U G
C O N T A C T O R
F I E L D - S U P P L I E D
D I S C O N N E C T
R E F E R T O E L E C T R I C A L D A T A T A B L E S T O S I Z E
G R O U N D
L U G
C O N T A C T O R
R E F E R T O E L E C T R I C A L D A T A T A B L E S T O S I Z E T H E D I S C O N N E C T
F I E L D - S U P P L I E D
D I S C O N N E C T
S I N G L E
H A S E
P P O W E R S U P P L Y
G R O U N D
T H E D I S C O N N E C T
FIGURE 4 - POWER WIRING FIELD DIAGRAM
TABLE 13: ELECTRICAL DATA
VOLTAGE
MODEL
DNP
024 208/230-1-60 187 253 8.1 57 1.1 2.6 15.7 25 25 0.96 40
030 208/230-1-60 187 253 13.6 67 1.1 6.8 24.9 35 35 0.96 40
030 208/230-3-60 187 253 8.6 55 1.1 6.8 18.7 25 25 0.96 75
030 460-3-60 414 504 5.7 39 0.6 6.8 13.4 20 20 0.96 75
036 208/230-1-60 187 253 17.2 88 1.1 6.8 29.4 45 45 0.96 40
036 208/230-3-60 187 253 11.4 77 1.1 6.8 22.2 30 30 0.96 75
036 460-3-60 414 504 5.7 39 0.6 6.8 14.8 20 20 0.96 75
042 208/230-1-60 187 253 20 104 1.3 9.1 35.4 50 50 0.96 40
042 208/230-3-60 187 253 13.9 88 1.3 9.1 27.8 40 40 0.96 75
042 460-3-60 414 504 6.4 44 0.7 9.1 18.5 25 25 0.96 75
048 208/230-1-60 187 253 23.4 126 1.9 9.1 39.5 60 60 0.96 40
048 208/230-3-60 187 253 13 93 1.9 9.1 26.5 35 35 0.96 75
048 460-3-60 414 504 6.4 46.5 1.0 9.1 18.4 25 25 0.96 75
1.
2.
POWER
SUPPLY
Rated in accordance with ARI Standard 110, utilization range “A”. Dual element, time delay type.
LIMITATIONS
MIN MAX RLA LRA
COMPRESSOR
1
COND.
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX FUSE SIZE
AMPS
2
MAX HACR
BREAKER
SIZE
AMPS
UNIT
POWER
FACTOR
T H R E E P H A S E P O W E R S U P P L Y
TRANS
FORMER
SIZE (VA)
18 Unitary Products Group
Page 19
036-21366-003-C-0405
L
GASSUPPLY1-1/4"DIA. HOLE(1/2"NPTI
ECTION)
CONN
VENTAIROUTLETHOOD
BLOWERSERVICE
ACCESSCOMPARTMENT PANEL
CONDENSERCOIL
UNITCONDENSATE CONNECTION3/4"NPTI (TRAPRECOMMENDED)
B
HIGHVOLTAGE CONN.1-3/8"DIA.
3-3/4
KNOCKOUT
HIGHVOLTAGE CONN.7/8"DIA. KNOCKOUT
2-1/2
GASSUPPLY1-1/4"DIA. KNOCKOU
T(1/2"NPTI
CONNECTION)
LOWVOLTAGECONN. 1-3/8"DIA.KNOCKOUT X7/8"HOLE
47-1/4
(OVERALL)
FIGURE 5 - UNIT DIMENSIONS - FRONT
1-1/2
3-1/3
5-3/8
2-5/8
11
2-3/8
12-3/4
49-1/8
(OVERALL)
GAS/ELECTRICCONTRO
COMPARTMENTPANEL
All dimensions are in inches. They are subject to change with­out notice. Certified dimensions will be provided upon request.
A
REFRIGERANT CONNECTIONS
COMBUSTIONAIR INLETLOUVERS
FRONT
SERVICEACCESS
TABLE 14: UNIT DIMENSIONS FRONT
UNIT SIZE
024, 030, 036 33-1/2 18-1/4
042, 048 41-1/2 23-1/8
DIMENSION
“A” “B”
TABLE 15: UNIT MINIMUM CLEARANCES1
CLEARANCES
FRONT 36”
BACK 0”
LEFT SIDE (Filter-Access) 24”
RIGHT SIDE 12” BELOW UNIT ABOVE UNIT
1.
A 1” clearance must be provided between any combus-
3
4
36” (For Condenser Air Discharge)
2
0”
tible material and the supply air ductwork.
2.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3.
Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
4.
Units must be installed outdoors. Overhanging struc­tures or shrubs should not obstruct condenser air dis­charge outlet.
Unitary Products Group 19
Page 20
HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT
CONDENSATE DRAIN 3/4"' NPTI
26-3/4
8-7/8
036-21366-003-C-0405
19-1/4
11-7/8
FRONT
6
GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2" NPTI CONNECTION)
LOW VOLTAGE CONN.
/87
" DIA. KNOCKOUT
4-5/8
FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM
S I D E S U P P L Y A I R O P E N I N G
C O N D E N S E R
C O I L
B O T T O M S U P P L Y
A I R O P E N I N G
1 - 3 / 4
1 5
1 5
2 9 - 9 / 1 6
3 - 1 / 2
1 4 - 1 / 2
1 - 3 / 4
1 - 3 / 4
2 8 - 3 / 8
1 4 - 1 / 2
1 5
B O T
T O M R E T U R N
A I R O P E N I N G
B A C K
3 - 3 / 8
S I D E R E T U R N
A I R O P E N I N G
1 4 - 1 / 2
3 - 1 / 2
4
FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM
20 Unitary Products Group
Page 21
036-21366-003-C-0405
S
R
F I E L D S U P P L I E D
D I S C O N N E C T S W I T C H
L O C A T E D T O R E A R O F U N I T
T O G A S
U P P L Y L I N E
M A N U A L G A S
S H U T - O F F V A L V E
T O P O W E R S U P P Y
FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION
C O N T R O L W I R I N G
T O I N D O O R
T H E R M O S T A T
R E T U R N A I R
D U C T
S U P P L Y A I
D U C T
M A N U A L G A S
S H U T - O F F V A L V E
F I E L D
S U P P L I E D
D I S C O N N E C T
S W I T C H
M O U N T E D
O N U N I T
T O P O W E R
S U P P L Y
T O G A S
S U P P L Y L I N E
C O N T R O L W I R I N G
T O I N D O O R T H E R M O S T A T
R E T U R N A I R
D U C T
S U P P L Y A I R
D U C T
FIGURE 9 - TYPICAL ROOF CURB INSTALLATION
Unitary Products Group 21
Page 22
R O O F C U R B I N S T A L L A T I O N R E A R D U C T
FIGURE 10 - TYPICAL DUCT APPLICATIONS
036-21366-003-C-0405
R O O F C U R B I N S T A L L A T I O N B O T T O M D U C T
S L A B O N G R O U N D I N S T A L L A T I O N
TABLE 16: UNIT WEIGHTS AND CENTER OF GRAVITY
UNIT SIZE
024, 030, 036 400 395 100 96 98 101
042, 048 475 470 133 130 102 104
SHIPPING
WEIGHT
(lbs.)
OPERATING
WEIGHT
(lbs.)
FRONT
OF
UNIT
"A"
49-1/8
25
CORNER WEIGHTS
(location, lbs.)
“A” “B” “C” “D”
"D"
CENTER OF
GRAVITY
"B"
25
"C"
47-1/4
ECONOMIZER
(lbs.)
40
ROOF CURB
(lbs.)
8” - 70
14” - 75
FIGURE 11 - UNIT CENTER OF GRAVITY
22 Unitary Products Group
Page 23
036-21366-003-C-0405
R E C O M M E N D E D
D U C T S I Z E
1 7 - 1 / 2 " X 1 6 - 3 / 4 "
4 2 - 2 / 3
4 0 - 3 / 4
1 7 - 5 / 8
3 - 1 / 2
1 4
FIGURE 12 - ROOF CURB DIMENSIONS
3 / 4 " X 1 " W I D E G A S K E T I N G F O R C U R B F R A M E
A N D A L L D U C T S U P P O R T S U R F A C E S
O P E N I N G F O R
R E T U R N A I R D U C T
1
1 7 - 1 / 4
O P E N I N G F O R
S U P P L Y A I R D U C T
1 "
4 5 - 1 / 8
4 3 - 1 / 4
2 2
1
R E C O M M E N D E D
D U C T S I Z E
1 7 - 1 / 8 " X 2 1 - 1 / 2 "
U N I T B A S E
W O O D N A I L E R
8 " M I N . A B O V E
F I N I S H E D R O O F
C U R B F R A M E
I N S U L A T I O N
FIGURE 13 - ROOF CURB CROSS SECTION
1. 8” Roof curb also available
U N I T B A S E R A I L
C O U N T E R F L A S H I N G
1 4 "
C A N T S T R I P
I N S U L A T I O N A N D R O O F I N G M A T E R
R O O F D E C T A N D R O O F I N G M A T E R I A L
I A L
Unitary Products Group 23
Page 24
036-21366-003-C-0405
FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60)
24 Unitary Products Group
Page 25
036-21366-003-C-0405
3H,5H
17H
10G
15H
LKJHGFEDCBA
2
ASCT
31
(SEE NOTE 5)
805/BL
FSHP LP
801/BL (SEE NOTE 5)
(OPTIONAL ACCESSORIES - SEE NOTE 5)
B
806/BR
LR
A
807/BL
M1
802/BK 803/BK 804/BK
800/Y
LR
72
220/O
224/R
202/Y
203/BR
BOARD
100/BK
107/PR
GND
90 SEC60 SEC
110/BK
LUG
101/BK
M1-1
180 SEC120 SEC
RC1
T1
L1
FACTORY
COMPR
1
230-1-60
RSC
102/Y
103/BR
T2
M1-2
L2
208/230-1-60
POWER SUPPLY
SETTING
HEAT/BK
MOTOR
OD FAN
BRN
BLK
RC2
104/R
SEE DETAIL "A"
COOL/BLU
230-1-60
108/PR
1
PRP
CONTROL
12S
DELAY
Y
C
ON
213/R
"SPEED" CONNECTIONS
FOR COOLING BLOWER
SEE TABLE 1
R/RED
OFF
B
A
TB2
INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER COOL ON DELAY: 3 SEC
CONTROL BOARD SETTINGS:
COMBUSTION BLOWER POSTPURGE: 5 SEC
* BLACK SQUARE INDICATES SWITCH POSITION
Y
AUTO
ON
G
THERMOSTAT
BLK
T1
M2
L1
108/PR
240V/BLK
LUG
A
110/BK
220/O
203/BR
R
102/Y
104/R
T2
B
L2
108/PR
ELEMENTARY DIAGRAM
ROOM
2
1
PRP
CONTROL BOX
C2/BRN
T2
B
L2
221/BR
CONNECTION DIAGRAM
240V/PRP
GND
COOL
M1
107/PR
76543
101/BK
110/BK
OFF
T1
L1
HEAT
W
8
BLK
A
202/Y
100/BK
CGYWR
TB1
9
10
(SEE NOTE 5)
BRN
L1
BLK
BLK
CCH
OPTIONAL CCH
S/P CONFIGURATION
12
11
103/BR
FAN
T1
RC1/RC2
COOLING UNIT WITH GAS HEAT
M2-2
PRP
108/PR
DRAFT
M2
DI
MOTOR
UNUSED
HUM
L1
BLK
BLK
CCH
D/P CONFIGURATION
15
14
13
PRP
HERM
C
104/R
110/BK
L2
M2-1
T2
BLK
MOTOR
1
230-1-60
LEADS
1
N
EAC
+/-CLOSE+/-OPEN
------
12
200
CONTROL SETPOINT (DEG F)
RS
TEMPERATURE CONTROLS
2 TUBE
UNIT SIZE DEVICE
L2
T2L2
M1-2
DETAIL "A"
17
16
C230
100/BK107/PR
208
"SPEED" CONNECTIONS
COOLING BLOWER
FOR HEATING AND
SEE TABLES 1 AND 2
L1
T1
221/BR
N
9
6
LS 140 110
030
T1
P4/S4
HEAT/BLK
------
------
12
12160
270
RS
ALS
7
S5/P5
3 TUBE
18
GRN
11
9
6
LS 160 130
030
SEC
240V/BK
240V/PR
543
5
3
C2/BRN
COOL/BLU
NEUTRAL
9
------
------
6
12160
12
200
LS 140 110
ALS
RS
2 TUBE
19
224/R 214/BR
BATB2
R/RED
213/R
C1/BRN
036
201/BR200/R
ID FAN
GRN
Y1/YEL
432
------
------
12
12160
270
ALS
107/PR
MOTOR
9
6
036
3 TUBE
20
213/R
1
DELAY
230-1-60
R/RED
COOL
------
12160
ALSRSLS 160 130
224/R
S
OFF
208V
12
------
12
270
RS
2
1
261
W1/WHT
HEAT
9
6
LS 160 130
036
4 TUBE
21
100/BK
T1
C
PRI
75 VA
SEC 24V
230V
201/BR
ID MOTOR CONTROLLER
214/BR
201/BR
200/R
XFMR
X
C
9
9
9
------
------
------
------
------
------
------
6
12
12160
6
12
12160
6
12160
12
12160
200
270
200
LS 150 120
ALS
RS
LS 140 110
ALS
RS
LS 140 110
ALS
ALS
RS
048
3 TUBE
042
3 TUBE
042
4 TUBE
24
23
22
220/O
LEADS
MOTOR
DI
UNUSED
N
EAC
HUM
COOL
CONTROL BOARD
Y
C
202/Y
203/BR
224/R
CN1
------
12
270
RS
1
N
Y1/YEL
4 TUBE
25
HEAT
9
6
LS 175 145
048
653214
------
12160
ALS
221/BR
W1/WHT
TB1
BLU
P3
1
S3S2
2
P2
210/BL
P1
9
------
------
6
12
12160
270
LS 160 130
ALS
RS
048
5 TUBE
LEGEND:
27
26
C1/BRN
214/BR
432
204/O
207/Y
G/GRA
HSP
BLU
GAS
211/PR
PS
208/PR
ALS AUXILARY LIMIT SWITCH
(OPTIONAL ACCESSORY)
ASCT ANTI-SHORT CYCLE TIMER
28
CN1
432
VALVE
134
AFTER SERVICING.
CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION
IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT
IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED,
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
NOTES:
CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL
4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.
3. MOTORS ARE INHERENTLY PROTECTED.
MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1.
6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION
PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL.
ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE
IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT
5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.
LS
205/R
ALS
206/R
209/BK
207/Y
COOL/BLU TO:
WIRE
CONNECT
TB2-A
213/R
1250 TB2-B
(CFM)
AIRFLOW
RS
204/O
CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD
COMPR COMPRESSOR
HSP HOT SURFACE TO PILOT
ON CONTROL BOARD, 24-1-60, 18VA MAX
EAC ELECTRONIC AIR CLEANER RELAY OUTPUT
29
200/R
201/BR
XFMR
C
X
654
321
208/PR
LS LIMIT SWITCH
BOARD, 24-1-60, 18VA MAX
HUM HUMIDIFIER RELAY OUTPUT ON CONTROL
ACCESSORY) OPENS @ 380 PSIG
HP HIGH PRESSURE SWITCH (OPTIONAL
OPEN @ 26 DEGREE F
FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)
OPEN @ 7 PSIG
LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)
LR LOCK OUT RELAY (OPTIONAL ACCESSORY)
30
209/BK
802/BK
800/Y
202/Y
210/BL
206/R
2A
7B
(SEE NOTE 5)
LR
RWYGC
800/Y
801/BL
801/BL
805/BL
806/BR
3
21
807/BL
(SEE NOTE 5)
ASCT
S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
M1 CONTACTOR, COMPR & OD FAN
GAS HEAT SECTION
205/R
FOR COOLING
1000 (ARI RATING)
UNIT SIZE
-030
-030
FOR COOLING AIRFLOW
BLOWER CONNECTIONS
TABLE 1
S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL
S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL
S5
FIELD WIRING
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES
ROOM THERMOSTAT 24V CONNECTIONS
TB1 ON CONTROL BOARD
T1 TRANSFORMER, 24V, 40 VA
RC1/RC2 COMP. START & OUTDOOR FAN RUN CAPACITOR
.193 IWC NOM (.33 IWC MAX)
PS PRESSURE SWITCH - MAKES @
RS ROLLOUT SWITCH
MOTOR "SPEED" CONNECTIONS
TB2 TERMINAL BLOCK, 24V, ID
M2 CONTACTOR, DRAFT INDUCER MOTOR
BLUBLK
GAS VALVE
213/R
213/R
ALS
IDENTIFIED TERMINAL ON CAPACITOR
HSP
BLU
CLEAR
MOTOR
DRAFT
PRP
CLEAR
BLU
BLU
432
1
S3
210/BL
209/BK
207/Y
211/PR
432
1
S2
211/PR
206/R
204/O
208/PR
205/R
PS
LS
RS
CCH CRANKASE HEATER (OPTIONAL)
YEL
Y1/
/BLU
COOL
BRN
C2/
WHT
W1/
BRN
C1/
BLK
803/BK
103/BR101/BK
035-18578D000 REV. C
BEFORE SERVICING THIS UNIT
CAUTION - OPEN ALL DISCONNECTS
7. SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)
TB2-A
TB2-A
TB2-A
1350 TB2-B
1600 TB2-B
1500 TB2-B
1200 (ARI RATING)
1350 (ARI RATING)
1400 (ARI RATING)
-042
-042
-036
-036
-048
-048
MOTOR
ID FAN
240V/BLK
GND/GRN
240V/PRP
54321
S4ID MOTOR CONTROLLER
87654321
16
1514131211109
R/RED
/BLK
HEAT
BLK
PRP
FAN
BRN
MOTOR
OUTDOOR
CCH
BLK
804/BK
804/BK
802/BK
805/BL
803/BK
FS
LP
HP
SC
R
102/Y
COMPR
FIGURE 15 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-1-60 POWER SUPPLY)
Unitary Products Group 25
Page 26
3H,5H
036-21366-003-C-0405
17H
10G
15H
LKJHGFEDCBA
2
ASCT
31
(SEE NOTE 5)
805/BL
FSHP LP
801/BL (SEE NOTE 5)
(OPTIONAL ACCESSORIES - SEE NOTE 5)
806/BR
B
LR
A
807/BL
M1
802/BK 803/BK 804/BK
800/Y
LR
72
224/R
220/O
DI
202/Y
203/BR
BOARD
100/BK
107/PR
GND
90 SEC60 SEC
110/BK
LUG
M1-1
180 SEC120 SEC
L1
121/BK
T1
L1
COMPR
230-3-60
L2
123/BL
T2
M1-2
L2
108/PR
208/230-3-60
POWER SUPPLY
SETTING
FACTORY
3
M1-3
L3
126/Y
T3
L3
HEAT/BK
BLK
COOL/BLU
OD FAN
RC2
MOTOR
BRN
105/BL
230-1-60
1
PRP
CONTROL
12S
DELAY
Y
C
ON
R/RED
213/R
"SPEED" CONNECTIONS
FOR COOLING BLOWER
SEE TABLE 1
TB2
INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER COOL ON DELAY: 3 SEC
CONTROL BOARD SETTINGS:
COMBUSTION BLOWER POSTPURGE: 5 SEC
* BLACK SQUARE INDICATES SWITCH POSITION
AUTO
ON
G
ELEMENTARY DIAGRAM
THERMOSTAT
ROOM
BLK
PRP
CONTROL BOX
C2/BRN
T2
T1
B
A
M2
L2
L1
220/O
221/BR
CONNECTION DIAGRAM
110/BK
108/PR
240V/BLK
240V/PRP
LUG
GND
COOLING UNIT WITH GAS HEAT
OFF
B
A
Y
R
105/BL
126/Y
T3
COOL
T2
OFF
123/BL
HEAT
W
121/BK
BK
T1
CGYWR
TB1
TEMPERATURE CONTROLS
987654321
11
10
9
9
+/-CLOSE+/-OPEN
------
------
------
12
12160
6
12
6
200
270
CONTROL SETPOINT (DEG F)
ALS
RS
LS 140 110
RS
LS 160 130
030
2 TUBE
3 TUBE
UNIT SIZE DEVICE
13
12
M1
L3
L2
L1
B
A
110/BK
100/BK
107/PR
203/BR
108/PR
(SEE NOTE 5)
202/Y
BRN
RC2
100/BK
T1
C
PRI
208V
75 VA
SEC 24V
107/PR
HSP
230V
MOTOR
ID FAN
GRN
316122
R/RED
Y1/YEL
C1/BRN
1
230-1-60
ID MOTOR CONTROLLER
214/BR
W1/WHT
201/BR
BLU
BLU
200/R
P3
3.2 AMP
CB
432
1
S3S2
GAS
VALVE
134
2
035-18845D000 REV.C
BEFORE SERVICING THIS UNIT
CAUTION - OPEN ALL DISCONNECTS
P2
211/PR
PS
AFTER SERVICING.
CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION
IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT
IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED,
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
NOTES:
224/R
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL
4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.
3. MOTORS ARE INHERENTLY PROTECTED.
CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.
MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1.
6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION
PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL.
ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE
IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT
5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.
108/PR
M2-2
PRP
DRAFT
L2
T2
MOTOR
230-1-60
110/BK
L1
M2-1
T1
240V/BLK
240V/PRP
BLK
543
1
5
11
P4/S4
C2/BRN
COOL/BLU
HEAT/BLK
LS
M2
------
12160
ALS
030
------
12
200
RS
UNUSED
HUM
9
6
LS 140 110
036
2 TUBE
14
221/BR
LEADS
MOTOR
1
NEUTRAL
N
N
EAC
9
9
9
9
9
------
------
------
------
------
12
6
12160
270
ALS
036
3 TUBE
15
------
------
------
------
------
12
12160
12160
12
6
6
12
12160
6
12
12160
6
270
200
200
270
ALS
RS
ALSRSLS 160 130
RS
LS 160 130
LS 150 120
ALS
RS
LS 140 110
ALS
RS
LS 140 110
036
4 TUBE
3 TUBE
042
3 TUBE
042
4 TUBE
19
181716
201/BR
212/R
XFMR
432
C
HEAT
COOL
9
9
------
------
------
------
------
12
12160
12
12160
12160
6
6
270
270
ALS
RS
ALS
RS
ALS
LS 160 130
LS 175 145
LEGEND:
048
5 TUBE
048
4 TUBE
048
224/R
213/R
ALS AUXILARY LIMIT SWITCH
23
222120
220/O
210/BL
X
P1
CN1
653214
CB CIRCUIT BREAKER
COMPR COMPRESSOR
ON CONTROL BOARD, 24-1-60, 18VA MAX
EAC ELECTRONIC AIR CLEANER RELAY OUTPUT
HP HIGH PRESSURE SWITCH (OPTIONAL
OPEN @ 26 DEGREE F
FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)
(OPTIONAL ACCESSORY)
ASCT ANTI-SHORT CYCLE TIMER
25
24
214/BR
221/BR
GRN
1
LEADS
MOTOR
DI
UNUSED
201/BR200/R
S
1
2
DELAY
OFF
EAC
HUM
CONTROL BOARD
C
203/BR
N
N
207/Y
HEAT
COOL
W1/WHT
Y1/YEL
Y
TB1
202/Y
200/R
G/GRA
105/BL
100/BK107/PR
PRP
C230
T1
SEC
208
A
TB2
R/RED
"SPEED" CONNECTIONS
COOLING BLOWER
FOR HEATING AND
SEE TABLES 1 AND 2
B
213/R 214/BR
205/R
ALS
206/R
209/BK
207/Y
208/PR
213/R
RS
204/O
S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD
M1 CONTACTOR, COMPR & OD FAN
HSP HOT SURFACE TO PILOT
BOARD, 24-1-60, 18VA MAX
HUM HUMIDIFIER RELAY OUTPUT ON CONTROL
ACCESSORY) OPENS @ 380 PSIG
LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)
29
282726
212/R
201/BR
C1/BRN
XFMR
432
C
X
204/O
654
321
CN1
208/PR
RWYGC
224/R
CB
212/R
RC2 OUTDOOR FAN RUN CAPACITOR
LS LIMIT SWITCH
.193 IWC NOM (.33 IWC MAX)
PS PRESSURE SWITCH - MAKES @
M2 CONTACTOR, DRAFT INDUCER MOTOR
OPEN @ 7 PSIG
LR LOCK OUT RELAY (OPTIONAL ACCESSORY)
30
209/BK
802/BK
800/Y
202/Y
210/BL
206/R
2A
7B
(SEE NOTE 5)
LR
800/Y
801/BL
801/BL
805/BL
806/BR
3
21
807/BL
(SEE NOTE 5)
ASCT
TB2-A
TB2-A
TB2-A
TB2-A
COOL/BLU TO:
WIRE
CONNECT
1350 TB2-B
1600 TB2-B
1250 TB2-B
1500 TB2-B
(CFM)
AIRFLOW
FOR COOLING
1200 (ARI RATING)
1000 (ARI RATING)
1350 (ARI RATING)
-030
-030
-036
-036
ID FAN
S5
FIELD WIRING
YEL
Y1/
/BLU
COOL
BRN
C2/
WHT
W1/
BRN
C1/
804/BK
803/BK
FS
211/PR
123/BL121/BK
1400 (ARI RATING)
-042
-042
-048
-048
MOTOR
240V/BLK
240V/PRP
GND/GRN
S4ID MOTOR CONTROLLER
87654321
16
1514131211109
R/RED
HEAT
PRP
BRN
FAN
MOTOR
OUTDOOR
BLK
804/BK
802/BK
805/BL
803/BK
LP
HP
L2L1
L3
COMPR
54321
/BLK
126/Y
FOR COOLING AIRFLOW
BLOWER CONNECTIONS
TABLE 1
UNIT SIZE
S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL
S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL
ROOM THERMOSTAT 24V CONNECTIONS
TB1 ON CONTROL BOARD
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES
T1 TRANSFORMER, 24V, 75 VA
RS ROLLOUT SWITCH
MOTOR "SPEED" CONNECTIONS
TB2 TERMINAL BLOCK, 24V, ID
IDENTIFIED TERMINAL ON CAPACITOR
HSP
BLU
BLUBLK
CLEAR
MOTOR
DRAFT
PRP
CLEAR
BLU
BLU
432
1
S3
210/BL
209/BK
207/Y
211/PR
GAS VALVE
GAS HEAT SECTION
432
1
S2
206/R
204/O
213/R
208/PR
205/R
213/R
205/R
PS
LS
RS
ALS
FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-3-60 POWER SUPPLY
26 Unitary Products Group
Page 27
036-21366-003-C-0405
FIGURE 17 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460-3-60 POWER SUPPLY)
Unitary Products Group 27
Page 28
036-21366-003-C-0405
TYPICAL WIRING DIAGRAM NOTES
1. All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit.
2. Caution: Label all wires prior to disconnection when ser­vicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105°C, 600V wire or equivalent clearly renumbered for identification. Verify proper operation after servicing.
3. Motors are inherently protected.
4. See unit nameplate for maximum fuse size and minimum circuit ampacity.
LEGEND :
ALS ASCT
COMPR EAC
FS
HP
HSP HUM
LP
LR LS M1 M2 PS
RC1/RC2 RS T1 T2 TB2
AUXILLARY LIMIT SWITCH ANTI-SHORT CYCLE TIMER (OPTIONAL ACCESSORY) COMPRESSOR ELECTRIC AIR CLEANER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. FREEZESTAT SWITCH (OPTIONAL ACCESSORY)
OPEN @ 25 HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 380 PSIG HOT SURFACE TO PILOT HUMIDIFER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG LOCK OUT RELAY (OPTIONAL ACCESSORY) LIMIT SWITCH CONTACTOR, COMPR. & O.D.FAN CONTACTOR, DRAFT INDUCER MOTOR PRESSURE SWITCH MAKES @ .193 IWC NOM. (.33 IWC MAX.) COMPR. START & OUTDOOR FAN RUN CAPACITOR ROLL OUT SWITCH TRANSFORMER, 24V, 40VA TRANSFORMER, 480/240 VOLT TERMINAL BLOCK, 24V, I.D. MOTOR "SPEED" CONNECTION IDENTIFIED TERMINAL ON CAPACITOR ROOM THERMOSTAT 24V CONNECTIONS TB1 ON CONTROL BOARD FACTORY WIRING AND DEVICES OPTIONAL WIRING AND DEVICES FIELD WIRING
0
F
5. Select indoor blower cooling speed from unit wirin g dia­gram Table 1. Heating speed is preset at the factory.
6. If both LR and ASCT are present, wire 801/BL and 805/ BL are connected to ASCT-3 if LR only is present wire 801/BL and 805/BL are connected to M1 coil. If ASCT only is present wire 202/Y is connected to ASCT-3. If neither LR or ASCT are present, Wire 202/Y is connect to M1 coil.
7. Shunt contact also used with crankcase heater. (Optional).
Open all disconnects before servicing this unit.
DNP LEGEND WIRING DIA.
FIGURE 18 - TYPICAL WIRING DIAGRAM LEGEND
28 Unitary Products Group
Page 29
036-21366-003-C-0405
MECHANICAL SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s Champion® package units are designed to handle applica­tions ranging from residential to light commercial and any in between. The Champion® is a unit that gives you the flexibil­ity and choices you need in today’s market. These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The gas fired heaters have alumi­nized steel tubular heat exchangers and hot surface to pilot ignition. They are available in natural gas with field conver­sion to propane.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heating units, designed for outdoor mounted installation. For SEER ratings, refer to technical literature. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility cer­tified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce­dures. The heating performance shall be rated to DOE and GAMA test procedures. Units shall be CSA listed and classi­fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/ CAN/CSA No. 236-M90 conditions.
UNIT CABINET
tight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams without modification to building structure, duct work and base unit. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4” NPTI copper, ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be direct drive, multi-speed design. Job site selected (BHP) brake horsepower shall not exceed the motors nameplate horsepower rating. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bear­ings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor­rosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTM­B117 standards. The unit top shall be a single piece “Water Shed” design, with drip edges and no-seam corners to pro­vide optimum water integrity. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with up to 3/4” thick, aluminum, foil faced insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily remov­able for servicing and maintenance, with built-in lift handles. Unit shall be built on a formed, “Super-Structure” design base pan, with embossments at critical points to add strength, rigidity and aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be removable, when required, to lower unit height. Filters shall be furnished and be accessible through a removable access door, sealed air-
Unitary Products Group 29
b. Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally iso­lated on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion,
blow through design, while condenser coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components:
a. Shall include independent thermal expansion
devices (TXV).
b. Shall include filter/strainer to eliminate any foreign
matter.
Page 30
036-21366-003-C-0405
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125º F out­door temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor tempera­ture. Accessory low ambient kit shall be available for opera­tion to 0º F.
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modification s. Separate side and bottom openings shall be provided for the control wiring.
30 Unitary Products Group
Page 31
036-21366-003-C-0405
Unitary Products Group 31
Page 32
Subject to change without notice. Printed in U.S.A. 036-21366-003-C-0405 Copyright © 2005 by Unitary Products Group. All rights reserved. Supersedes: 036-21366-003-B-1004