York DM 240, DM 300 User Manual

TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS
DM 180, 240 & 300
15, 20 & 25 NOMINAL TONS
262259-YTG-B-0107

DESCRIPTION

YORK Sunline 2000™ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
All units include:
Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats
Scroll compressors (25T model only)
Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic
Permanently lubricated motors
Bottom or side air discharge configuration capability (field convertible)
Belt Drive Blower Motor with high static drive option
Constant supply air volume (CV) with optional variable air volume (VAV)
Manufactured under the quality standards of ISO9001
Simplicity® Control Board
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tooless latched doors
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units

WARRANTY

One-year parts warranty
A Five-year parts warranty on the compressors and electric heat elements
Ten-year parts warranty on the gas-fired heat exchangers
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TABLE OF CONTENTS

262259-YTG-B-0107
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 7
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 37
LIST OF FIGURES
Fig. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3 TYPICAL DM FIELD WIRING DIAGRAM . . . . . . . . 29
4 UNIT DIMENSIONS & CLEARANCES 15, 20 & 25
TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . 31
6 UNIT DIMENSIONS DM180, 240 & 300
(RAINHOOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . 33
8 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . 33
9 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . 34
10 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . 35
11 ROOF CURB DUCT OPENINGS DIMENSION . . . 35
12 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . 35
13 TYPICAL SIMPLICITY® CONTROL WIRING
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pg. #
LIST OF TABLES
Tbl. #
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . 9
2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . 9
3 GAS HEAT RATIINGS . . . . . . . . . . . . . . . . . . . . . . . 9
4 DM 180 COOLING CAPACITIES (15 TON) . . . . . . 10
5 DM 240 COOLING CAPACITIES (20 TON) . . . . . . 12
6 DM 300 COOLING CAPACITIES (25 TON) . . . . . . 14
7 ALTITUDE CORRECTION FACTORS . . . . . . . . . . 16
Pg. #
Tbl. # Pg. #
8 SUPPLY AIR BLOWER PERFORMANCE
(15 TON) - COOLING ONLY 180 MBH - BOTTOM
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . 18
9 SUPPLY AIR BLOWER PERFORMANCE
(20 TON) - COOLING ONLY 240 MBH - BOTTOM
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . 19
10 SUPPLY AIR BLOWER PERFORMANCE
(15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
11 SUPPLY AIR BLOWER PERFORMANCE
(20 TON) - GAS HEAT 240 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 SUPPLY AIR BLOWER PERFORMANCE
(25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . 23
14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . 23
15 POWER EXHAUST PERFORMANCE . . . . . . . . . . 23
16 DM 180, 240 ELECTRICAL DATA WITHOUT
POWERED CONVENIENCE OUTLET . . . . . . . . . 24
17 DM 300 ELECTRICAL DATA STANDARD
MOTOR WITHOUT POWERED CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
18 DM 300 ELECTRICAL DATA HIGH STATIC
MOTOR WITHOUT POWERED CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
19 DM 180, 240 ELECTRICAL DATA WITH POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . 26
20 DM 300 ELECTRICAL DATA STANDARD MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . 27
21 DM 300 ELECTRICAL DATA HIGH STATIC MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . 27
22 DM VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . 28
23 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 28
24 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . 29
25 ELECTRIC HEAT CORRECTION FACTORS . . . . 29
26 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . 30
27 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . 32
28 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . 34
2 Unitary Products Group
262259-YTG-B-0107

PRODUCT NOMENCLATURE

15-25 Ton Sunline 2000™ Model Number Nomenclature
D M 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category
D = A/C, Single Pkg., R-22
Product Style
A = Style A
Product Identifier
M = 8.5-9.0 EER A/C
Nominal Cooling Capacity
180 = 15 Ton 240 = 20 Ton 300 = 25 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed
electric heat
Gas Heat Options
N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel
Electric Heat Options
E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW
Airflow
A = Std. Drive B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only) D = Std. Drive/Motorized Damper N = Hi Static Drive P = Hi Static Drive/Single Input Econo. Q = Hi Static Drive/Single Input Econo./Power Exhaust
(Downflow Only) R = Hi Static Drive/Motorized Damper
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume (VFD) - Not Available with Factory Installed BAS Options
Variable Air Volume (VFD With Manual Bypass) - Not Available with Factory Installed BAS Options
Variable Air Volume (VFD-Ready for Customer Installed Drive)
2" Pleated filters
4" Pleated filters
BAS Ready Unit with Belimo Economizer
Double Wall Construction
Heat Reclaim Coil Options (2 or 3 Row, 1-5/8" or 2-1/8" Stub Out) (WJ and W R models only)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
1 = First Generation 2 = Second Generation
Standard Cabinet
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Configuration Options (not required for all units)
Additional Options
Hinged Filter Door & Toolless Access Cabinet
BA = Hinged Filter Door & Toolless Access Panels BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
Installation Options
A = No Options Installed B = Option 1 C=Option2 D = Options 1 & 2 E=Option3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M=Options1,2,3,&4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S=Option5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
Options
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5=Pwr'dConv.Outlet
Unitary Products Group 3
262259-YTG-B-0107

FEATURES

All models are available with a wide variety of factory­mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
All models are available with these “factory mounted” outdoor air damper options:
Single enthalpy economizer
Single enthalpy economizer with power exhaust
Motorized outdoor air damper A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo­mizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis­tance. Optionally, the control board can be pro­grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully pro­grammable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit con­trol board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air vol­ume (VAV) option using a variable frequency drive is avail­able for applications requiring a constant supply duct pressure. A differential pressure transducer is used to moni­tor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.
All compressors include scroll compressors and internal pres­sure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.
Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls.
4 Unitary Products Group
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
•Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger
262259-YTG-B-0107
LONG LASTING POWDER PAINT FINISH
ECONOMIZER HOOD
ELECTRIC HEATER LOCATION (OPTIONAL ELECTRIC/ELECTRIC UNITS)
20 GAUGE ALUMINIZED STEEL TUBULAR HEAT EXCHANGERS
HIGH EFFICIENCY COMPRESSORS WITH CRANKCASE HEATERS
COPPER TUBE/ALUMINUM FIN CONDENSER COILS
LOW VOLTAGE RELAY BOARD AND TERMINAL STRIP
ELECTRICAL DISCONNECT MOUNTING LOCATION (Field installed)
KNOCKOUT FOR SIDE CONTROL WIRING ENTRY
2" DISPOSABLE FILTERS
OUTDOOR AIR OPENING FOR SLIDE-IN/PLUG-IN INTERNAL ECONOMIZER(OPTION)
SIDE AND BOTTOM SUPPLY & RETURN AIR DUCT OPENINGS(SIDE X SIDE)
1" NPTI CONDENSATE DRAIN
FULL PERIMETER 14 GUAGE BASE RAILS WITH LIFTING HOLES
FIGURE 1 - UNIT CUTAWAY
with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
Electric Heat Operation - All electric heat models (fac­tory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to pro­vide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
BAS Controls - Y ork’ s Sunlin e™ series units o ffer factory mounted BAS controls such as Simplicity® INTELLI-Com- fort™, Novar, Honeywell , Johnson, and CPC.

FACTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
KNOCKOUT FOR SIDE POWER WIRING ENTRY SIDE
TERMINAL BLOCK (For Single Point Power Supply with Electric Heat) ELECTRIC\ELECTRIC UNITS
BOTTOM POWER & CONTROL WIRING ENTRY
KNOCKOUTS FOR SIDE GAS SUPPLY ENTRY
HOLE FOR BOTTOM GAS SUPPLY ENTRY
BELT-DRIVE BLOWER MOTOR
POWER VENTOR MOTOR WITH POST PURGE CYCLE
LOCATION OF VFD (Optional)
LOCATION OF VFD Bypass (Optional)
GAS/ELECTRIC
UNIT SHOWN
ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
POWER EXHAUST - Our single economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field.
The power exhaust option can only be used on bot­tom duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper­ating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection.
Unitary Products Group 5
262259-YTG-B-0107
ELECTRIC HEA T ERS wired for single point power sup­ply. These nickel chromium heater elements are pro­vided with limit and automatic reset capability to prevent operation at excessive temperatures.
VARIABLE AIR VOLUME (VAV) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A pressure transducer and VAV control board are mounted inside the control box. The drive comes completely wired and pre-programmed from the factory.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and oper­ate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.
Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus­tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus­tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depend­ing on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows:
For 5-hp motor applications........................ 10” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications ........13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted space, then it will have to be mounted within a NEMA-4 enclosure for outside installation or inside the building on a perpendicular wall not subjected to excessive tempera­ture, vibration, humidity, dust, corrosive gas, explosive gas, etc.
A terminal block located in the control box is provided for field connection of the VFD controls.
HOT GAS BYPASS - To allow for low cooling load oper- ation, a direct-acting pressure-modulating bypass control valve installed on the system #1 discharge line is used to divert high temperature, high pressure refrigerant around the TXV in order to maintain a desired minimum evapo­rator pressure. HGBP is standard on all units with VAV and optional with CV units.
FILTER OPTIONS - Standard units are shipped with 2” throw-away filters installed. 2” pleated and 4” pleated fil­ters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 vol t o ut le t ca n be “powered” by the unit with a stepdown transformer or
you may order the unit with a “non-powered” conve­nience outlet that can be wired in the field.
DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
BAS - Building Automation System Controls (avail­able on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York® Simplicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen­sor, and an outside air sensor . There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO
sensors. It uses an inside CO2 sensor to per-
2
form Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board con­nection for hot gas re-heat system. It uses the INTELLI­Start™ algorithm to maximize energy savings by recov­ering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLI-Comfort™ bal­ances space temperature, ventilation air temperature,
and humidity for ultimate comfort.
CO
2
Simplicity® INTELLI-Comfort™ with ModLINC CON- TROL - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi­tional control to translate communications from MOD­BUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system con­troller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air prov­ing switch.
CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes
6 Unitary Products Group
262259-YTG-B-0107
supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will hav e to be moved to prevent having false alarms.
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
ST AINLESS STEEL DRAIN PAN- An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of­phase condition.
HIGH SPEED DRIVE - Includes a belt and blower pulley upgrade to enhance blower performance.
ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti­tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
HINGED FILTER DOOR/”TOOLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance. NOTE:Knobs are shipped separately within the unit to
prevent shipping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa­for applications with a higher CFM and/or static pressure requirements.
Unitary Products Group 7
SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER - This damper acces­sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
HIGH SPEED DRIVE - A smaller blower pulley and a shorter belt increase the speed of the supply air blower
262259-YTG-B-0107
ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
WOOD SKID - Allows unit to be handled with 90” forks.
CO
SENSOR - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the present limits.
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of­phase condition.
8 Unitary Products Group
262259-YTG-B-0107
TABLE 1: SOUND POWER RATING
UNIT SIZE
180 6,000 1.00 1,080 4.60 99 99 89 82 84 77 72 67 89 56 240 8,000 1.00 1,120 6.65 102 102 92 85 87 80 75 70 92 59 300 10,000 1.30 1160 12.5 108 108 98 91 93 86 81 76 98 65
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
2. At a distance of 10 feet from the blower.
CFM
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
ESP BLOWER
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000
TABLE 2: CAPACITY RATINGS - (ARI 360)
MODEL MBH
COOLING ONLY
DM180C/E00 DM240C/E00 DM300C/E00
COOLING WITH GAS HEAT
DM180N/S DM240N/S DM300N/S
COOLING WITH ELECTRIC HEAT
DM180E18 DM180E36 DM180E54 DM180E72 DM240E18 DM240E36 DM240E54 DM240E72 DM300E18 DM300E36 DM300E54 DM300E72
1. Certified in accordance with the Unitary Large Equip­ment certification program which is based on ARI Stan­dard 340/360.
2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated Part Load Value.
176 8.7 9.2 234 8.6 8.05 272 8.5 9.2
176 8.5 9.0 232 8.5 8.05 272 8.5 9.0
176 8.7 9.2 176 8.6 9.1 174 8.5 8.7 174 8.5 8.7 234 8.5 8.05 234 8.5 8.05 232 8.5 8.05 232 8.5 8.05 272 8.5 9.1 272 8.5 9.1 270 8.5 9.0 270 8.5 9.0
1
EER
SOUND POWER (db 10
Octave Band Centerline Frequency (Hz)
1
2
IPLV
3
TABLE 3: GAS HEAT RATIINGS
MODEL MBH INPUT MBH OUTPUT
DM180N/S24 DM180N/S32
DM240N/S24 DM240N/S32
DM300N/S24 DM300N/S32
NOTE: All gas units are two-stage heating. First stage is 50% of total. S.S.E. = Steady State Efficiency (80%) - output divided by input.
-12
Watts)
300 240 400 320 300 240 400 320 300 240 400 320
SWL
dB(A)
For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.
If there are VAV boxes present in the duct sys­tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec­tric heating elements or gas heat exchanger tubes.
dB(A)
@
10Ft.
2
Unitary Products Group 9
TABLE 4: DM 180 COOLING CAPACITIES (15 TON)
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 223.2 16.6 116.8 95.5 74.1 - - - 212.0 17.5 110.9 89.5 68.2 - - ­72 206.6 15.9 143.3 121.9 100.5 79.2 - - 195.5 16.8 137.8 116.5 95.1 73.7 - -
4500
67 190.0 15.2 169.8 148.4 127.0 105.6 84.2 - 179.0 16.1 164.8 143.4 122.0 100.6 79.2 ­62 171.6 14.8 171.6 171.6 152.5 131.1 109.8 88.4 161.6 15.6 161.6 161.6 144.7 123.3 101.9 80.6 57 171.6 14.7 171.6 171.6 158.4 137.0 115.7 94.3 161.6 15.5 161.6 161.6 148.1 126.7 105.3 83.9 77 232.6 16.8 131.7 105.8 80.5 - - - 221.5 17.7 129.3 99.8 74.6 - - ­72 215.3 16.1 159.8 134.5 109.3 84.0 - - 204.3 17.0 154.6 129.3 104.0 78.8 - -
5250
67 198.0 15.4 187.9 163.3 138.0 112.7 87.5 - 187.0 16.3 179.9 158.8 133.5 108.2 83.0 ­62 178.8 15.0 178.8 178.8 165.8 140.5 115.2 89.9 168.8 15.8 168.8 168.8 158.4 133.1 107.8 82.5 57 178.8 14.9 178.8 178.8 172.2 146.9 121.7 96.4 168.8 15.7 168.8 168.8 162.0 136.8 111.5 86.2 77 242.0 17.0 146.6 116.2 87.0 - - - 231.0 17.9 147.6 110.2 81.0 - - ­72 224.0 16.3 176.3 147.2 118.0 88.8 - - 213.0 17.2 171.3 142.2 113.0 83.8 - -
6000
67 206.0 15.6 206.0 178.2 149.0 119.8 90.7 - 195.0 16.5 195.0 174.2 145.0 115.8 86.7 ­62 186.0 15.2 186.0 186.0 179.0 149.8 120.7 91.5 176.0 16.0 176.0 176.0 172.0 142.8 113.7 84.5 57 186.0 15.1 186.0 186.0 186.0 156.8 127.7 98.5 176.0 15.9 176.0 176.0 176.0 146.8 117.7 88.5 72 230.0 16.5 195.9 162.7 129.5 96.2 - - 217.9 17.4 189.6 156.3 123.1 89.9 - -
6750
67 211.5 15.8 211.5 197.6 163.5 130.3 97.1 - 199.5 16.7 199.5 189.1 158.0 124.8 91.6 ­62 191.0 15.4 191.0 191.0 187.5 154.3 121.0 87.8 180.1 16.2 180.1 180.1 178.1 144.9 111.6 78.4 57 191.0 15.3 191.0 191.0 191.0 157.8 124.5 91.3 180.1 16.1 180.1 180.1 180.1 146.9 113.6 80.4 72 236.0 16.7 215.4 178.2 140.9 103.6 - - 222.8 17.6 207.8 170.5 133.3 96.0 - -
7500
67 217.0 16.0 217.0 217.0 178.0 140.7 103.5 - 204.0 16.9 204.0 204.0 171.0 133.7 96.5 ­62 195.9 15.6 195.9 195.9 195.9 158.7 121.4 84.2 184.1 16.4 184.1 184.1 184.1 146.9 109.6 72.3 57 195.9 15.5 195.9 195.9 195.9 158.7 121.4 84.2 184.1 16.3 184.1 184.1 184.1 146.9 109.6 72.3
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
262259-YTG-B-0107
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 200.9 18.4 105.0 83.6 62.2 - - - 188.8 19.4 101.7 80.3 58.9 - - ­72 184.4 17.7 132.4 111.0 89.6 68.2 - - 173.2 18.6 128.2 106.8 85.5 64.1 - -
4500
67 168.0 17.0 159.8 138.4 117.0 95.6 74.2 - 157.5 17.8 153.4 133.4 112.0 90.6 69.2 ­62 151.6 16.4 151.6 151.6 136.9 115.5 94.1 72.8 143.7 17.3 143.7 143.7 129.0 107.6 86.2 64.9 57 151.6 16.3 151.6 151.6 137.7 116.4 95.0 73.6 143.7 17.3 143.7 143.7 129.4 108.0 86.7 65.3 77 210.4 18.6 126.8 93.9 68.6 - - - 196.9 19.6 126.7 90.3 65.0 - - ­72 193.2 17.9 149.4 124.1 98.8 73.5 - - 180.6 18.8 144.8 119.5 94.2 69.0 - -
5250
67 176.0 17.2 171.9 154.3 129.0 103.7 78.5 - 164.3 18.0 162.2 148.7 123.5 98.2 73.0 ­62 158.8 16.6 158.8 158.8 151.0 125.7 100.4 75.1 149.9 17.4 149.9 149.9 142.3 117.0 91.7 66.4 57 158.8 16.5 158.8 158.8 151.9 126.6 101.3 76.1 149.9 17.4 149.9 149.9 142.7 117.4 92.2 66.9 77 220.0 18.8 148.6 104.2 75.0 - - - 205.0 19.8 151.6 100.2 71.0 - - ­72 202.0 18.1 166.3 137.2 108.0 78.8 - - 188.0 19.0 161.3 132.2 103.0 73.8 - -
6000
67 184.0 17.4 184.0 170.2 141.0 111.8 82.7 - 171.0 18.2 171.0 164.1 135.0 105.8 76.7 ­62 166.0 16.8 166.0 166.0 165.0 135.8 106.7 77.5 156.0 17.6 156.0 156.0 155.5 126.3 97.2 68.0 57 166.0 16.7 166.0 166.0 166.0 136.8 107.7 78.5 156.0 17.6 156.0 156.0 156.0 126.8 97.7 68.5 72 205.8 18.3 183.2 150.0 116.8 83.6 - - 192.1 19.2 176.4 145.4 112.2 78.9 - -
6750
67 187.5 17.6 187.5 180.6 152.5 119.3 86.1 - 174.8 18.4 174.8 171.3 147.0 113.8 80.6 ­62 169.2 17.0 169.2 169.2 168.7 135.4 102.2 69.0 159.4 17.8 159.4 159.4 159.2 126.0 92.8 59.5 57 169.2 16.9 169.2 169.2 169.2 135.9 102.7 69.5 159.4 17.8 159.4 159.4 159.4 126.2 93.0 59.8 72 209.7 18.5 200.1 162.9 125.6 88.4 - - 196.2 19.4 191.5 158.6 121.3 84.0 - -
7500
67 191.0 17.8 191.0 191.0 164.0 126.7 89.5 - 178.5 18.6 178.5 178.5 159.0 121.7 84.5 ­62 172.3 17.2 172.3 172.3 172.3 135.1 97.8 60.5 162.9 18.0 162.9 162.9 162.9 125.6 88.3 51.1 57 172.3 17.1 172.3 172.3 172.3 135.1 97.8 60.5 162.9 18.0 162.9 162.9 162.9 125.6 88.3 51.1
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
10 Unitary Products Group
262259-YTG-B-0107
TABLE 4: DM 180 COOLING CAPACITIES (15 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM
4500
5250
6000
6750
7500
WB
°F
77 176.8 20.4 98.3 77.0 55.6 - - ­72 161.9 19.5 124.1 102.7 81.3 59.9 - ­67 147.0 18.6 147.0 128.4 107.0 85.6 64.2 ­62 135.8 18.1 135.8 135.8 121.1 99.7 78.3 56.9 57 135.8 18.2 135.8 135.8 121.1 99.7 78.3 56.9 77 183.4 20.5 126.5 86.6 61.3 - - ­72 167.9 19.6 140.2 114.9 89.6 64.4 - ­67 152.5 18.8 152.5 143.2 118.0 92.7 67.5 ­62 140.9 18.3 140.9 140.9 133.6 108.3 83.0 57.7 57 140.9 18.4 140.9 140.9 133.6 108.3 83.0 57.7 77 190.0 20.7 154.6 96.3 67.0 - - ­72 174.0 19.8 156.3 127.2 98.0 68.8 - ­67 158.0 18.9 158.0 158.0 129.0 99.8 70.7 ­62 146.0 18.4 146.0 146.0 146.0 116.8 87.7 58.5 57 146.0 18.5 146.0 146.0 146.0 116.8 87.7 58.5 72 178.4 20.1 169.6 140.7 107.5 74.3 - ­67 162.0 19.2 162.0 162.0 141.5 108.3 75.1 ­62 149.7 18.6 149.7 149.7 149.7 116.5 83.3 50.1 57 149.7 18.7 149.7 149.7 149.7 116.5 83.3 50.1 72 182.8 20.3 182.8 154.3 117.0 79.7 - ­67 166.0 19.4 166.0 166.0 154.0 116.7 79.5 ­62 153.4 18.9 153.4 153.4 153.4 116.1 78.9 41.6 57 153.4 19.0 153.4 153.4 153.4 116.1 78.9 41.6
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor­mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1.5 KW) and the compressor motors but not the supply air blower motor.
TEMPERATURE OF AIR ON CONDENSER COIL
MBH
1
POWER
INPUT
KW
2
TOTAL
CAP.
Nominal Rating
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
90 85 80 75 70 65
Unitary Products Group 11
TABLE 5: DM 240 COOLING CAPACITIES (20 TON)
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 322.5 22.3 159.6 131.1 102.6 - - - 298.6 23.9 154.3 125.8 97.3 - - ­72 291.2 21.6 194.3 165.8 137.3 108.8 - - 272.3 22.9 188.7 160.1 131.6 103.1 - -
6000
67 260.0 20.9 229.0 200.5 172.0 143.5 115.0 - 246.0 21.9 223.0 194.5 166.0 137.5 109.0 ­62 225.8 20.3 225.8 225.8 192.7 164.2 135.7 107.2 213.1 21.3 213.1 213.1 185.3 156.8 128.3 99.7 57 225.8 19.9 225.8 225.8 194.2 165.7 137.2 108.7 213.1 20.8 213.1 213.1 190.3 161.8 133.3 104.8 77 331.2 22.3 186.6 147.0 113.3 - - - 308.3 24.0 180.9 140.3 106.6 - - ­72 299.1 21.6 219.0 185.3 151.6 118.0 - - 281.1 23.0 211.7 178.0 144.3 110.6 - -
7000
67 267.0 20.9 251.5 223.7 190.0 156.3 122.6 - 254.0 22.0 242.5 215.7 182.0 148.3 114.6 ­62 231.9 20.3 231.9 231.9 212.8 179.2 145.5 111.8 220.1 21.4 220.1 220.1 203.1 169.4 135.7 102.1 57 231.9 19.9 231.9 231.9 214.6 180.9 147.2 113.5 220.1 20.9 220.1 220.1 208.7 175.0 141.3 107.6 77 340.0 22.3 213.5 162.9 124.0 - - - 318.0 24.1 207.5 154.9 116.0 - - ­72 307.0 21.6 243.8 204.9 166.0 127.1 - - 290.0 23.1 234.8 195.9 157.0 118.1 - -
8000
67 274.0 20.9 274.0 246.9 208.0 169.1 130.2 - 262.0 22.1 262.0 236.9 198.0 159.1 120.2 ­62 238.0 20.3 238.0 238.0 233.0 194.1 155.2 116.4 227.0 21.5 227.0 227.0 221.0 182.1 143.2 104.4 57 238.0 19.9 238.0 238.0 235.0 196.1 157.2 118.4 227.0 21.0 227.0 227.0 227.0 188.1 149.2 110.4 72 313.5 21.9 273.3 229.1 184.8 140.5 - - 297.7 23.5 264.6 220.3 176.0 131.8 - -
9000
67 279.8 21.2 279.8 266.2 231.5 187.2 142.9 - 269.0 22.5 269.0 256.4 222.0 177.7 133.4 ­62 243.0 20.6 243.0 243.0 240.5 196.2 151.9 107.7 233.1 21.8 233.1 233.1 230.1 185.8 141.5 97.2 57 243.0 20.2 243.0 243.0 241.5 197.2 152.9 108.7 233.1 21.3 233.1 233.1 233.1 188.8 144.5 100.2 72 320.0 22.2 302.9 253.2 203.5 153.9 - - 305.5 23.8 294.4 244.7 195.1 145.4 - -
10000
67 285.5 21.5 285.5 285.5 255.0 205.3 155.6 - 276.0 22.8 276.0 276.0 246.0 196.3 146.6 ­62 248.0 20.9 248.0 248.0 248.0 198.3 148.6 99.0 239.1 22.2 239.1 239.1 239.1 189.4 139.8 90.1 57 248.0 20.5 248.0 248.0 248.0 198.3 148.6 99.0 239.1 21.7 239.1 239.1 239.1 189.4 139.8 90.1
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
262259-YTG-B-0107
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 274.7 25.5 148.9 120.4 91.9 - - - 255.9 27.0 142.4 113.9 85.4 - - ­72 253.3 24.2 183.0 154.5 126.0 97.4 - - 236.4 25.6 177.2 148.7 120.2 91.7 - -
6000
67 232.0 22.9 217.0 188.5 160.0 131.5 103.0 - 217.0 24.2 209.5 183.5 155.0 126.5 98.0 ­62 200.4 22.3 200.4 200.4 177.9 149.4 120.8 92.3 192.0 23.5 192.0 192.0 172.2 143.7 115.1 86.6 57 200.4 21.7 200.4 200.4 186.4 157.9 129.4 100.8 192.0 23.0 192.0 192.0 179.5 151.0 122.4 93.9 77 285.3 25.7 175.2 133.7 100.0 - - - 266.2 27.1 171.7 126.2 92.5 - - ­72 263.2 24.4 204.4 170.7 137.0 103.3 - - 246.0 25.7 197.5 163.8 130.1 96.4 - -
7000
67 241.0 23.1 233.5 207.7 174.0 140.3 106.6 - 225.8 24.3 222.0 201.4 167.8 134.1 100.4 ­62 208.2 22.5 208.2 208.2 193.4 159.7 126.0 92.3 199.8 23.6 199.8 199.8 186.3 152.6 118.9 85.2 57 208.2 21.9 208.2 208.2 202.7 169.0 135.3 101.6 199.8 23.1 199.8 199.8 194.2 160.5 126.8 93.1 77 296.0 25.9 201.5 146.9 108.0 - - - 276.5 27.3 201.0 138.4 99.5 - - ­72 273.0 24.6 225.8 186.9 148.0 109.1 - - 255.5 25.9 217.8 178.9 140.0 101.1 - -
8000
67 250.0 23.3 250.0 226.9 188.0 149.1 110.2 - 234.5 24.5 234.5 219.4 180.5 141.6 102.7 ­62 216.0 22.7 216.0 216.0 209.0 170.1 131.2 92.4 207.5 23.8 207.5 207.5 200.5 161.6 122.7 83.9 57 216.0 22.1 216.0 216.0 219.0 180.1 141.2 102.4 207.5 23.2 207.5 207.5 209.0 170.1 131.2 92.4 72 282.0 25.0 255.8 211.6 167.3 123.0 - - 261.2 26.2 241.1 201.2 156.9 112.6 - -
9000
67 258.3 23.7 258.3 246.7 212.5 168.2 123.9 - 239.8 24.8 239.8 232.2 202.3 158.0 113.7 ­62 223.1 23.1 223.1 223.1 219.6 175.3 131.1 86.8 212.1 24.1 212.1 212.1 208.6 164.3 120.0 75.7 57 223.1 22.5 223.1 223.1 224.6 180.3 136.1 91.8 212.1 23.6 212.1 212.1 212.8 168.6 124.3 80.0 72 291.0 25.4 285.9 236.3 186.6 136.9 - - 267.0 26.6 264.4 223.5 173.8 124.1 - -
10000
67 266.5 24.1 266.5 266.5 237.0 187.3 137.6 - 245.0 25.2 245.0 245.0 224.0 174.3 124.6 ­62 230.3 23.5 230.3 230.3 230.3 180.6 130.9 81.2 216.7 24.5 216.7 216.7 216.7 167.0 117.3 67.6 57 230.3 22.9 230.3 230.3 230.3 180.6 130.9 81.2 216.7 23.9 216.7 216.7 216.7 167.0 117.3 67.6
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
12 Unitary Products Group
262259-YTG-B-0107
TABLE 5: DM 240 COOLING CAPACITIES (20 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM
6000
7000
8000
9000
10000
WB
°F
77 237.1 28.5 135.9 107.4 78.9 - - ­72 219.5 27.0 171.5 143.0 114.5 85.9 - ­67 202.0 25.5 202.0 178.5 150.0 121.5 93.0 ­62 183.6 24.7 183.6 183.6 166.5 138.0 109.4 80.9 57 183.6 24.2 183.6 183.6 172.5 144.0 115.5 87.0 77 247.0 28.5 168.2 118.6 85.0 - - ­72 228.8 27.0 190.6 156.9 123.2 89.5 - ­67 210.5 25.6 210.5 195.2 161.5 127.8 94.1 ­62 191.3 24.8 191.3 191.3 179.2 145.5 111.8 78.1 57 191.3 24.3 191.3 191.3 185.8 152.1 118.4 84.7 77 257.0 28.6 200.5 129.9 91.0 - - ­72 238.0 27.1 209.8 170.9 132.0 93.1 - ­67 219.0 25.6 219.0 211.9 173.0 134.1 95.2 ­62 199.0 24.8 199.0 199.0 192.0 153.1 114.2 75.4 57 199.0 24.3 199.0 199.0 199.0 160.1 121.2 82.4 72 240.4 27.5 226.3 190.8 146.5 102.2 - ­67 221.3 26.0 221.3 217.7 192.0 147.7 103.4 ­62 201.0 25.1 201.0 201.0 197.5 153.3 109.0 64.7 57 201.0 24.6 201.0 201.0 201.0 156.8 112.5 68.2 72 242.9 27.8 242.9 210.7 161.0 111.3 - ­67 223.5 26.3 223.5 223.5 211.0 161.3 111.6 ­62 203.1 25.5 203.1 203.1 203.1 153.4 103.7 54.0 57 203.1 25.0 203.1 203.1 203.1 153.4 103.7 54.0
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor­mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
TEMPERATURE OF AIR ON CONDENSER COIL
MBH
1
POWER
INPUT
KW
2
TOTAL
CAP.
Nominal Rating
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
90 85 80 75 70 65
Unitary Products Group 13
TABLE 6: DM 300 COOLING CAPACITIES (25 TON)
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 364.9 24.2 197.4 161.8 126.1 - - - 349.9 26.9 188.9 153.3 117.6 - - ­72 341.5 23.7 237.8 202.2 166.5 130.9 - - 326.3 26.4 230.5 194.8 159.2 123.6 - -
7500
67 318.1 23.2 278.2 242.5 206.9 171.2 135.6 - 302.8 25.9 272.1 236.4 200.8 165.1 129.5 ­62 290.0 23.1 290.0 290.0 259.7 224.1 188.4 152.8 279.5 25.4 279.5 279.5 247.5 211.8 176.2 140.5 57 287.2 22.7 287.2 287.2 259.1 223.5 187.8 152.2 276.6 25.4 276.6 276.6 251.1 215.5 179.8 144.2 77 367.6 24.2 214.3 173.3 131.2 - - - 355.6 27.0 209.9 165.4 123.3 - - ­72 344.0 23.7 257.4 215.3 173.2 131.0 - - 331.7 26.5 251.1 209.0 166.9 124.8 - -
8750
67 320.4 23.2 300.5 257.2 215.1 173.0 130.8 - 307.8 25.9 292.4 252.6 210.5 168.3 126.2 ­62 292.1 23.1 292.1 292.1 270.1 228.0 185.8 143.7 284.1 25.4 284.1 284.1 259.4 217.3 175.1 133.0 57 289.2 22.7 289.2 289.2 269.4 227.3 185.1 143.0 281.1 25.4 281.1 281.1 263.2 221.1 179.0 136.9 77 370.2 24.2 231.3 184.9 136.3 - - - 361.3 27.1 230.8 177.6 129.0 - - ­72 346.5 23.7 277.0 228.4 179.8 131.2 - - 337.0 26.5 271.8 223.2 174.6 126.0 - -
10000
67 322.7 23.2 322.7 271.9 223.3 174.7 126.1 - 312.7 26.0 312.7 268.7 220.1 171.5 122.9 ­62 294.1 23.1 294.1 294.1 280.4 231.8 183.2 134.6 288.6 25.5 288.6 288.6 271.3 222.7 174.1 125.5 57 291.3 22.7 291.3 291.3 279.7 231.1 182.5 133.9 285.6 25.5 285.6 285.6 275.3 226.7 178.1 129.5 72 348.9 23.5 301.9 246.6 191.2 135.9 - - 342.3 26.6 293.9 238.6 183.2 127.9 - -
11250
67 325.1 23.0 325.1 292.9 237.6 182.2 126.9 - 317.6 26.0 317.6 286.4 231.0 175.7 120.3 ­62 296.2 22.9 296.2 296.2 297.8 242.5 187.1 131.8 293.2 25.5 293.2 293.2 284.5 229.2 173.8 118.5 57 293.3 22.6 293.3 293.3 289.6 234.3 178.9 123.6 290.1 25.5 290.1 290.1 285.0 229.6 174.3 118.9 72 351.4 23.4 326.9 264.8 202.7 140.6 - - 347.6 26.6 316.0 253.9 191.8 129.7 - -
12500
67 327.4 22.9 327.4 314.0 251.9 189.8 127.7 - 322.6 26.1 322.6 304.0 241.9 179.8 117.7 ­62 298.2 22.8 298.2 298.2 315.2 253.1 191.0 128.9 297.7 25.6 297.7 297.7 297.7 235.6 173.5 111.4 57 295.3 22.4 295.3 295.3 299.6 237.5 175.4 113.3 294.6 25.6 294.6 294.6 294.6 232.5 170.4 108.3
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
262259-YTG-B-0107
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 334.8 29.7 180.4 144.8 109.1 - - - 316.8 32.8 162.5 126.9 91.3 - - ­72 311.2 29.1 223.2 187.5 151.9 116.3 - - 294.4 32.3 211.3 175.6 140.0 104.3 - -
7500
67 287.6 28.5 266.0 230.3 194.7 159.0 123.4 - 272.1 31.7 260.0 224.3 188.7 153.1 117.4 ­62 269.0 27.7 269.0 269.0 235.2 199.6 163.9 128.3 253.0 30.8 253.0 252.8 218.1 182.5 146.8 111.2 57 266.0 28.0 266.0 266.0 243.1 207.5 171.8 136.2 250.3 31.3 250.3 250.3 223.0 187.4 151.7 116.1 77 343.6 29.8 205.4 157.5 115.4 - - - 323.0 33.0 194.4 139.0 96.9 - - ­72 319.3 29.2 244.9 202.7 160.6 118.5 - - 300.2 32.4 232.9 190.8 148.7 106.5 - -
8750
67 295.1 28.7 284.3 248.0 205.8 163.7 121.6 - 277.4 31.8 271.4 242.6 200.5 158.4 116.2 ­62 276.1 27.8 276.1 276.1 248.7 206.6 164.5 122.3 258.0 30.9 258.0 257.9 231.7 189.5 147.4 105.3 57 273.0 28.1 273.0 273.0 257.1 214.9 172.8 130.7 255.3 31.4 255.3 255.3 236.8 194.7 152.6 110.5 77 352.4 29.9 230.4 170.2 121.6 - - - 329.2 33.1 226.3 151.1 102.5 - - ­72 327.5 29.3 266.5 217.9 169.3 120.7 - - 306.0 32.5 254.6 206.0 157.4 108.8 - -
10000
67 302.7 28.8 302.7 265.6 217.0 168.4 119.8 - 282.8 31.9 282.8 260.8 212.2 163.6 115.0 ­62 283.1 27.9 283.1 283.1 262.2 213.6 165.0 116.4 263.0 31.1 263.0 263.0 245.2 196.6 148.0 99.4 57 280.0 28.3 280.0 280.0 271.0 222.4 173.8 125.2 260.2 31.5 260.2 260.2 250.7 202.1 153.5 104.9 72 335.7 29.6 285.9 230.5 175.2 119.8 - - 311.8 32.8 272.1 216.8 161.4 106.1 - -
11250
67 310.2 29.0 310.2 279.8 224.5 169.1 113.8 - 288.2 32.2 288.2 271.3 217.6 162.3 106.9 ­62 290.2 28.1 290.2 290.2 271.2 215.9 160.5 105.2 267.9 31.3 267.9 267.9 251.5 196.2 140.8 85.5 57 286.9 28.5 286.9 286.9 280.4 225.0 169.7 114.3 265.1 31.7 265.1 265.1 257.2 201.8 146.5 91.1 72 343.9 29.9 305.2 243.1 181.0 118.9 - - 317.6 33.0 289.7 227.6 165.5 103.4 - -
12500
67 317.8 29.3 317.8 294.1 232.0 169.9 107.8 - 293.5 32.4 293.5 281.7 223.0 160.9 98.8 ­62 297.3 28.4 297.3 297.3 280.3 218.2 156.1 94.0 272.9 31.5 272.9 272.9 257.9 195.8 133.7 71.6 57 293.9 28.8 293.9 293.9 289.7 227.6 165.5 103.4 270.1 32.0 270.1 270.1 263.7 201.6 139.5 77.4
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
14 Unitary Products Group
262259-YTG-B-0107
TABLE 6: DM 300 COOLING CAPACITIES (25 TON) (CONTINUED)
AIR ON
EVAPORATOR
COIL
CFM
7500
8750
10000
11250
12500
WB
°F
77 298.7 36.0 144.7 109.0 73.4 - - ­72 277.7 35.4 199.3 163.7 128.1 92.4 - ­67 256.6 34.8 254.0 218.4 182.7 147.1 111.5 ­62 236.9 34.0 236.9 236.6 201.0 165.4 129.7 94.1 57 234.7 34.5 234.7 234.7 202.9 167.2 131.6 96.0 77 302.4 36.1 183.4 120.5 78.3 - - ­72 281.1 35.5 221.0 178.8 136.7 94.6 - ­67 259.8 34.9 258.5 237.2 195.1 153.0 110.9 ­62 239.9 34.1 239.9 239.7 214.6 172.5 130.4 88.2 57 237.6 34.6 237.6 237.6 216.6 174.5 132.4 90.3 77 306.1 36.3 222.2 131.9 83.3 - - ­72 284.5 35.7 242.6 194.0 145.4 96.8 - ­67 263.0 35.1 263.0 256.1 207.5 158.9 110.3 ­62 242.8 34.2 242.8 242.8 228.2 179.6 131.0 82.4 57 240.5 34.8 240.5 240.5 230.4 181.8 133.2 84.6 72 287.9 35.9 258.4 203.1 147.7 92.4 - ­67 266.1 35.3 266.1 262.7 210.8 155.4 100.1 ­62 245.7 34.5 245.7 245.7 231.8 176.5 121.1 65.8 57 243.3 35.0 243.3 243.3 234.0 178.7 123.3 68.0 72 291.3 36.1 274.2 212.1 150.0 87.9 - ­67 269.3 35.5 269.3 269.3 214.1 152.0 89.9 ­62 248.6 34.7 248.6 248.6 235.5 173.4 111.3 49.2 57 246.2 35.2 246.2 246.2 237.7 175.6 113.5 51.4
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor­mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.
TEMPERATURE OF AIR ON CONDENSER COIL
MBH
1
POWER
INPUT
KW
2
TOTAL
CAP.
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
90 85 80 75 70 65
Unitary Products Group 15
262259-YTG-B-0107
CFM, STATIC PRESSURE, AND POWER - ALTI­TUDE AND TEMPERATURE CORRECTIONS
The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
order to use the indoor blower tables for high altitude applica­tions, certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In
generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 7 and Figure 2.
TABLE 7: ALTITUDE CORRECTION FACTORS
AIR TEMP
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
The examples below will assist in determining the airflow per­formance of the product at altitude.
Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: At an elevation of 5,000 ft., the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 7 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 7 shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC Corrected BHP = 4.0 x 0.832 = 3.328
ALTITUDE (FEET)
blower tables to select the blower speed and the BHP requirement.
Solution: As in the example above, no temperature informa­tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
16 Unitary Products Group
262259-YTG-B-0107
  


 
 



 

      
 
FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

   
  

Unitary Products Group 17
262259-YTG-B-0107
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (15 TON) -
COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
208 VOLT AND STANDARD DRIVE
850 6.0** 0.9 2.4 2.2 0.7 3.0 2.7 0.5 3.2 2.9 - - - - - ­870 5.5 1.0 2.5 2.3 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - ­915 4.5 1.1 2.6 2.4 0.9 3.4 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0 965 3.5 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 4.9 4.4
980 3.0 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8. 4.3 0.5 5.1 4.6 1010 2.0 1.4 3.1 2.8 1.2 3.8 3.4 1.0 4.2 3.8 0.7 5.0 4.5 0.6 5.4 4.8 1040 1.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.2 4.7 0.7 5.7 5.1
208 VOLT AND HIGH SPEED DRIVE
965 6.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4
980 5.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1025 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.8 5.1 4.6 0.7 5.6 5.0 1065 3.5 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - ­1095 3.0 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - ­1130 2.0 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - ­1170 1.0 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - -
230/460/575 VOLT AND STANDARD DRIVE
870 6.0** 1.0 2.4 2.2 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -
915 5.0 1.1 2.6 2.4 0.9 3.3 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0
965 4.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4
980 3.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1040 2.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1 1065 1.0 1.6 3.3 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -
230/460/575 VOLT AND HIGH SPEED DRIVE
980 6.0 1.3 2.9 2.6 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6 1040 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1 1065 4.0 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - ­1095 3.5 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - ­1130 2.5 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - ­1170 1.5 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - ­1190 1.0 2.2 4.0 3.6 2.1 4.8 4.3 2.0 5.7 5.1 - - - - - -
MOTOR
PULLEY
(TURNS
OPEN)*
4500 5250 6000 6750 7200
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
CFM
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure availa ble for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT ** Factory setting.
close the pulley below 1 turn open.
18 Unitary Products Group
262259-YTG-B-0107
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
208 VOLT AND STANDARD DRIVE
8706.0**0.42.11.80.12.32.0--------­900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - ­930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - ­950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - ­980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1
1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9
208 VOLT AND HIGH SPEED DRIVE
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7 1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0 1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3 1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - ­1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - ­1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - -
230/460/575 VOLT AND STANDARD DRIVE
8706.0**0.42.11.80.12.32.0---------
900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - -
930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -
950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9 1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3
230/460/575 VOLT AND HIGH SPEED DRIVE
950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -
980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1 1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9 1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3 1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - ­1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - ­1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - ­1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - - - - -
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
MOTOR PULLEY (TURNS
OPEN)*
2. Refer to Table 13 for additional static resistances. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT ** Factory setting.
close the pulley below 1 turn open.
6000 7000 8000 9000 9400
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
CFM
Unitary Products Group 19
262259-YTG-B-0107
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT
180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
208 VOLT AND STANDARD DRIVE
850 6.0** 0.9 2.4 2.1 0.6 2.9 2.6 0.3 3.4 3.0 - - - - - ­870 5.5 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - ­915 4.5 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - ­965 3.5 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.0 0.2 5.0 4.5
980 3.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1010 2.0 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8 1040 1.0 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0
208 VOLT AND HIGH SPEED DRIVE
965 6.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5
980 5.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1025 4.5 1.4 3.1 2.8 1.2 3.6 3.2 0.9 4.1 3.7 0.7 4.8 4.3 0.4 5.5 4.9 1065 3.5 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - ­1125 2.0 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - ­1170 1.0 2.1 3.9 3.5 1.9 4.7 4.2 1.6 5.5 4.9 - - - - - -
230/460/575 VOLT AND STANDARD DRIVE
870 6.0** 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - -
915 5.0 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -
965 4.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5
980 3.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1015 2.5 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8 1050 1.5 1.5 3.1 2.8 1.2 3.7 3.3 0.9 4.2 3.8 0.7 4.9 4.4 0.5 5.7 5.1 1065 1.0 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -
230/460/575 VOLT AND HIGH SPEED DRIVE
980 6.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6 1045 4.5 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0 1065 4.0 1.7 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - ­1125 2.5 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - ­1170 1.5 2.1 3.9 3.5 1.8 4.7 4.2 1.6 5.5 4.9 - - - - - ­1190 1.0 2.2 4.0 3.6 1.9 4.8 4.3 1.7 5.6 5.0 - - - - - -
MOTOR
PULLEY
(TURNS
OPEN)*
4500 5250 6000 6750 7200
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
CFM
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table. ESP = External Static Pressure availa ble for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT ** Factory setting.
close the pulley below 1 turn open.
20 Unitary Products Group
262259-YTG-B-0107
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT
240 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
208 VOLT AND STANDARD DRIVE
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - ­900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - ­930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - ­950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - ­980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1 995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3
1015 1.0 2.2 4.8 4.0 1.7 4.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 - - -
208 VOLT AND HIGH SPEED DRIVE
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - ­980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 4.5 2.1 4.5 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - ­1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - ­1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - ­1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - - - - -
230/460/575 VOLT AND STANDARD DRIVE
870 6.0** 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - -
900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - -
930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -
950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - ­1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -
230/460/575 VOLT AND HIGH SPEED DRIVE
950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -
980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1
995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3 1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - ­1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - ­1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - ­1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - ­1100 1.5 2.9 5.6 4.7 2.3 6.8 4.7 1.8 7.9 6.6 - - - - - ­1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - - - -
MOTOR PULLEY (TURNS
OPEN)*
6000 7000 8000 9000 9400
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
CFM
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT ** Factory setting.
close the pulley below 1 turn open.
Unitary Products Group 21
262259-YTG-B-0107
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT
300 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
208 VOLT AND STANDARD DRIVE
975 6.01.25.94.95.07.36.0--------­1005 5.01.46.25.10.77.76.3--------­1040 4.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0 - - - - - ­1070 3.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3 - - - - - ­1100 2.0 2.0 7.3 6.0 1.3 8.9 7.3 0.6 10.6 8.7 - - - - - ­1135 1.0 2.2 7.7 6.3 1.6 9.3 7.6 0.8 11.1 9.1 - - - - - ­1165 0.0 2.4 8.0 6.6 1.8 9.7 8.0
208 VOLT AND HIGH SPEED DRIVE
1140 6.0 2.2 7.7 6.3 1.6 9.4 7.7 0.9 11.2 9.2 - - - - - ­1180 5.0 2.5 8.2 6.7 1.9 9.9 8.1 1215 4.0 2.7 8.6 7.0 2.1 10.4 8.5 1255 3.0 3.0 9.1 7.4 2.4 11.0 9.0 1290 2.0 3.2 9.5 7.8 2.7 11.5 9.4 1330 1.0 3.5 10.0 8.2 1365 0.0 3.7 10.5 8.6
230/460/575 VOLT AND STANDARD DRIVE
975 6.0* 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2 - - - - - ­1005 5.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6 0.1 10.9 8.9 - - ­1040 4.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0 0.3 11.4 9.4 - - ­1070 3.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3 1100 2.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7 1135 1.0 2.4 7.7 6.3 2.0 9.3 7.6 1.6 11.1 9.1 1165 0.0 2.6 8.0 6.6 2.2 9.7 8.0
230/460/575 VOLT AND HIGH SPEED DRIVE
1140 6.0 2.4 7.7 6.3 2.1 9.4 7.7 1.6 11.2 9.2 1180 5.0 2.7 8.2 6.7 2.3 9.9 8.1 1215 4.0 2.9 8.6 7.0 2.6 10.4 8.5 1255 3.0 3.2 9.1 7.4 2.9 11.0 9.0 1290 2.0 3.4 9.5 7.8 3.1 11.5 9.4 1330 1.0 3.7 10.0 8.2 1365 0.0 3.9 10.5 8.6
MOTOR
PULLEY
(TURNS
OPEN)*
7500 8750 10000 11250 12500
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
3.0 12.0 9.9 2.3 14.1 11.6 1.5 16.4 13.4---
3.2 12.6 10.3 2.6 14.7 12.1 1.8 17.0 13.9---
3.4 12.0 9.9 3.0 14.1 11.6 2.6 16.4 13.4---
3.7 12.6 10.3 3.3 14.7 12.1 2.9 17.0 13.9---
CFM
1.0 11.6 9.5 0.2 13.5 11.0---
1.2 11.8 9.7 0.3 13.7 11.2---
1.4 12.3 10.1 0.6 14.3 11.7---
1.7 12.9 10.6 0.9 15.0 12.3---
2.0 13.5 11.1 1.2 15.6 12.8---
0.6 11.9 9.8---
0.8 12.4 10.2 0.2 14.3 11.7
1.0 13.0 10.6 0.4 14.9 12.2
1.8 11.6 9.5 1.3 13.5 11.0 0.7 15.5 12.7
1.1 13.1 10.7 0.5 15.0 12.3
1.9 11.8 9.7 1.4 13.7 11.2 0.8 15.8 12.9
2.2 12.3 10.1 1.7 14.3 11.7 1.1 16.4 13.5
2.5 12.9 10.6 2.0 15.0 12.3 1.4 17.2 14.1
2.7 13.5 11.1 2.2 15.6 12.8---
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table. ESP = External Static Pressure availa ble for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT ** Factory setting.
close the pulley below 1 turn open.
15 HP Motor is required.
22 Unitary Products Group
262259-YTG-B-0107
TABLE 13: BLOWER MOTOR AND DRIVE DATA
DESIG-
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
1
MODEL
SIZE
Standard 850/1065
15 TON
Standard 870/1025
20 TON
Standard 950/1120 10 215 T 89.5 1VP68 6.75 5.5-6.5
25 TON
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heat ing device.
2. Do NOT
BLOWER
DRIVE
Speed
Access
Speed
Access
Speed
Access
RANGE
(RPM)
High
965/1190 BK80 7.75 7.4 1 BX68 69.8 1
High
950/1120 BK110 10.75 10.4 1-3/16 BX81 82.8 1
High
1140/1365 15 254 T 91 1VP75X 7.5 6.2-7.4 1-5/8 1B5V94 9.7 9.5 1-7/16 5VX840 84.0 1
close this pulley below 1 turn open.
MOTOR
HP FRAME
5 184 T 83 1VP5 6 5.35 4.3-5.3
7.5 213 T 89 1VP68 6.7 5 5.5-6.521-3/8
EFF.
(%)
ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY
DESIG-
NATION
OUTSIDE
DIA. (IN.)
PITCH
DIA. (IN.)
BORE
(IN.)
NATION
2
1-1/8
2
1-3/8 1B5V110 11.3 11.1 1-7/16 BX81 82.8 1
OUTSIDE
DESIG-
BK90 8.75 8.4 1 BX81 82.8 1
BK120 11.75 11.4 1-3/16 BX83 84.8 1
DIA. (IN.)
PITCH
DIA. (IN.)
BORE
(IN.)
NATION
TABLE 14: STATIC RESISTANCES
1
RESISTANCE, IWG
DESCRIPTION
15 TON 20 TON 25 TON
CFM
4500 6000 7200 6000 8000 9400 7500 10000 12500
WET INDOOR COIL 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
18 KW 0.3 0.4 0.4 0.4 0.4 0.5 0.4 0.5 0.6
ELECTRIC HEAT OPTIONS
36 KW 0.3 0.4 0.5 0.4 0.5 0.5 0.5 0.5 0.6 54 KW 0.4 0.5 0.5 0.5 0.5 0.6 0.5 0.6 0.7 72 KW 0.4 0.5 0.5 0.5 0.5 0.6 0.5 0.6 0.7
ECONOMIZER OPTION 0.1 0.1 0.1 0.1 0.1 0.2 0.1 0.2 0.3 HORIZONTAL DUCT CONNECTIONS
1. Deduct these resistance values from the available external static pressures shown in the respecti ve Blo w er Pe r fo r m a nce Table (See Note 2 for exception.)
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the respective unit’s blower performance table.
2
0.1 0.2 0.3 0.2 0.3 0.5 0.3 0.5 0.6
QTY.
TABLE 15: POWER EXHAUST PERFORMANCE
MOTOR SPEED
2
HIGH
MEDIUM
LOW
1
CFM kW CFM kW CFM kW CFM kW CFM kW
5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - -
4400 0.72 3700 0.74 3000 0.78 - - - -
0.2 0.3 0.4 0.5 0.6
1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.
Unitary Products Group 23
STATIC RESISTANCE OF RETURN DUCTWORK, IWG
262259-YTG-B-0107
TABLE 16: DM 180, 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TON-
NAGE)
180 (15)
240 (20)
VOLTAGE
208 19.2 124 4.5 14.0 0.0
230 19.2 124 4.3 14.0 0.0
460 9.6 62 2.2 7.0 0.0
575 7.7 50 1.7 5.3 0.0
208 19.2 124 4.5 19.6 0.0
230 19.2 124 4.3 19.6 0.0
460 9.6 62 2.2 9.8 0.0
575 7.7 50 1.7 8.2 0.0
RLA
EACH
NOTE 1: HACR Type per NEC.
LRA
EACH
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MODEL KW STAGES AMPS
None 0.0 - - 85.4 100
E18 13.5 1 37.5 85.4 100 E36 27.0 2 75.1 111.2 125 E54 40.6 2 112.6 158.4 175 E72 54.1 2 150.1 167.7 200
None 0.0 - - 85.0 100
E18 18.0 1 43.3 85.0 100 E36 36.0 2 86.6 125.8 150 E54 54.0 2 129.9 147.4 175 E72 72.0 2 173.2 190.7 225
None 0.0 - - 42.6 50
E18 18.0 1 21.7 42.6 50 E36 36.0 2 43.3 62.9 70 E54 54.0 2 65.0 73.7 90 E72 72.0 2 86.6 95.4 110
None 0.0 - - 33.7 40
E18 18.0 1 17.3 33.7 40 E36 36.0 2 34.6 49.9 50 E54 54.0 2 52.0 58.6 70 E72 72.0 2 69.3 75.9 90
None 0.0 - - 110.3 125
E18 13.5 1 37.5 110.3 125 E36 27.0 2 75.1 118.2 125 E54 40.6 2 112.6 165.4 175 E72 54.1 2 150.1 174.7 200
None 0.0 - - 109.9 125
E18 18.0 1 43.3 109.9 125 E36 36.0 2 86.6 132.8 150 E54 54.0 2 129.9 154.4 175 E72 72.0 2 173.2 197.7 225
None 0.0 - - 55.1 60
E18 18.0 1 21.7 55.1 60 E36 36.0 2 43.3 66.4 70 E54 54.0 2 65.0 77.2 90 E72 72.0 2 86.6 98.6 110
None 0.0 - - 44.5 50
E18 18.0 1 17.3 44.5 50 E36 36.0 2 34.6 53.6 60 E54 54.0 2 52.0 62.2 70 E72 72.0 2 69.3 79.5 90
AMPACITY
MIN.
CIRCUIT
(AMPS)
MAX.
FUSE/
BRKR
SIZE
(AMPS)
1
24 Unitary Products Group
262259-YTG-B-0107
T ABLE 17: DM 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TON-
NAGE)
300 (25)
VOLTAGE
208 41.0 255 4.5 28.0 0.0
230 41.0 255 4.3 26.0 0.0
460 20.5 145 2.2 13.0 0.0
575 17.3 102 1.7 10.0 0.0
RLA
EACH
NOTE 1: HACR Type per NEC.
LRA
EACH
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
MODEL KW STAGES AMPS
AMPACITY
(AMPS)
None - - - 129.3 150
E18 13.5 1 37.5 129.3 150 E36 27.0 2 74.9 129.3 150 E54 40.6 2 112.7 175.9 200 E72 54.1 2 150.2 185.2 200
None - - - 126.9 150
E18 18.0 1 43.3 126.9 150 E36 36.0 2 86.6 140.8 150 E54 54.0 2 129.9 162.4 175 E72 72.0 2 173.2 205.7 225
None - - - 63.5 80
E18 18.0 1 21.7 63.5 80 E36 36.0 2 43.3 70.4 80 E54 54.0 2 65.0 81.2 90 E72 72.0 2 86.6 102.9 110
None - - - 52.3 60
E18 18.0 1 17.3 52.3 60 E36 36.0 2 34.6 55.8 60 E54 54.0 2 52.0 64.5 70 E72 72.0 2 69.3 81.8 90
MAX.
FUSE/
BRKR
SIZE
(AMPS)
1
T ABLE 18: DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET
MAX.
FUSE/
BRKR
SIZE
(AMPS)
MODEL
(TON-
NAGE)
300 (25)
COMPRESSORS
OD FAN
VOLTAGE
208 41.0 255 4.5 38.6 0.0
230 41.0 255 4.3 38.6 0.0
460 20.5 145 2.2 19.3 0.0
575 17.3 102 1.7 15.4 0.0
RLA
EACH
LRA
EACH
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
MODEL KW STAGES AMPS
AMPACITY
(AMPS)
None - - - 139.9 175
E18 13.5 1 37.5 139.9 175 E36 27.0 2 74.9 141.9 175 E54 40.6 2 112.7 189.1 200 E72 54.1 2 150.2 198.4 225
None - - - 139.5 175
E18 18.0 1 43.3 139.5 175 E36 36.0 2 86.6 156.5 175 E54 54.0 2 129.9 178.2 200 E72 72.0 2 173.2 221.5 250
None - - - 69.8 90
E18 18.0 1 21.7 69.8 90 E36 36.0 2 43.3 78.3 90 E54 54.0 2 65.0 89.1 100 E72 72.0 2 86.6 110.7 125
None - - - 57.7 70
E18 18.0 1 17.3 57.7 70 E36 36.0 2 34.6 62.6 70 E54 54.0 2 52.0 71.2 80 E72 72.0 2 69.3 88.5 100
NOTE 1: HACR Type per NEC.
1
Unitary Products Group 25
TABLE 19: DM 180, 240 ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
HEATER OPTION
MODEL KW STAGES AMPS
None 0.0 - - 95.4 110
E18 13.5 1 37.5 95.4 110 E36 27.0 2 75.1 123.7 125 E54 40.6 2 112.6 170.9 175 E72 54.1 2 150.1 180.2 200
None 0.0 - - 95.0 110
E18 18.0 1 43.3 95.0 110 E36 36.0 2 86.6 138.3 150 E54 54.0 2 129.9 159.9 175 E72 72.0 2 173.2 203.2 225
None 0.0 - - 47.6 50
E18 18.0 1 21.7 47.6 50 E36 36.0 2 43.3 69.1 70 E54 54.0 2 65.0 80.0 90 E72 72.0 2 86.6 101.6 110
None 0.0 - - 37.7 45
E18 18.0 1 17.3 37.7 45 E36 36.0 2 34.6 54.9 60 E54 54.0 2 52.0 63.6 70 E72 72.0 2 69.3 80.9 90
None 0.0 - - 120.3 125
E18 13.5 1 37.5 120.3 125 E36 27.0 2 75.1 130.7 150 E54 40.6 2 112.6 177.9 200 E72 54.1 2 150.1 187.2 200
None 0.0 - - 119.9 125
E18 18.0 1 43.3 119.9 125 E36 36.0 2 86.6 145.3 150 E54 54.0 2 129.9 166.9 175 E72 72.0 2 173.2 210.2 225
None 0.0 - - 60.1 70
E18 18.0 1 21.7 60.1 70 E36 36.0 2 43.3 72.6 80 E54 54.0 2 65.0 83.5 90 E72 72.0 2 86.6 105.1 110
None 0.0 - - 48.5 50
E18 18.0 1 17.3 48.5 50 E36 36.0 2 34.6 58.6 60 E54 54.0 2 52.0 67.2 70 E72 72.0 2 69.3 84.5 90
MODEL
(TON-
NAGE)
180 (15)
240 (20)
COMPRESSORS
OD FAN
VOLTAGE
208 19.2 124 4.5 14.0 10.0
230 19.2 124 4.3 14.0 10.0
460 9.6 62 2.2 7.0 5.0
575 7.7 50 1.7 5.3 4.0
208 19.2 124 4.5 19.6 10.0
230 19.2 124 4.3 19.6 10.0
460 9.6 62 2.2 9.8 5.0
575 7.7 50 1.7 8.2 4.0
RLA
EACH
LRA
EACH
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
NOTE 1: HACR Type per NEC.
262259-YTG-B-0107
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
SIZE
(AMPS)
1
26 Unitary Products Group
262259-YTG-B-0107
TABLE 20: DM 300 ELECTRICAL DATA STANDARD MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
(TON-
NAGE)
300 (25)
VOLTAGE
208 41.0 255 4.5 28.0 10.0
230 41.0 255 4.3 26.0 10.0
460 20.5 145 2.2 13.0 5.0
575 17.3 102 1.7 10.0 4.0
RLA
EACH
NOTE 1: HACR Type per NEC.
LRA
EACH
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
MODEL KW STAGES AMPS
AMPACITY
(AMPS)
None - - - 139.3 175
E18 13.5 1 37.5 139.3 175 E36 27.0 2 74.9 141.2 175 E54 40.6 2 112.7 188.4 200 E72 54.1 2 150.2 197.7 200
None - - - 136.9 175
E18 18.0 1 43.3 136.9 175 E36 36.0 2 86.6 153.3 175 E54 54.0 2 129.9 174.9 175 E72 72.0 2 173.2 218.2 225
None - - - 68.5 80
E18 18.0 1 21.7 68.5 80 E36 36.0 2 43.3 76.6 80 E54 54.0 2 65.0 87.5 90 E72 72.0 2 86.6 109.1 110
None - - - 56.3 70
E18 18.0 1 17.3 56.3 70 E36 36.0 2 34.6 60.8 70 E54 54.0 2 52.0 69.5 70 E72 72.0 2 69.3 86.8 90
MAX.
FUSE/
BRKR
(AMPS)
1
SIZE
TABLE 21: DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET
MAX.
FUSE/
BRKR
SIZE
(AMPS)
MODEL
(TON-
NAGE)
300 (25)
COMPRESSORS
OD FAN
VOLTAGE
208 41.0 255 4.5 38.6 10.0
230 41.0 255 4.3 38.6 10.0
460 20.5 145 2.2 19.3 5.0
575 17.3 102 1.7 15.4 4.0
RLA
EACH
LRA
EACH
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
MODEL KW STAGES AMPS
AMPACITY
(AMPS)
None - - - 149.9 175
E18 13.5 1 37.5 149.9 175 E36 27.0 2 74.9 154.4 175 E54 40.6 2 112.7 201.6 225 E72 54.1 2 150.2 210.9 225
None - - - 149.5 175
E18 18.0 1 43.3 149.5 175 E36 36.0 2 86.6 169.0 175 E54 54.0 2 129.9 190.7 225 E72 72.0 2 173.2 234.0 250
None - - - 74.8 90
E18 18.0 1 21.7 74.8 90 E36 36.0 2 43.3 84.5 90 E54 54.0 2 65.0 95.3 110 E72 72.0 2 86.6 117.0 125
None - - - 61.7 70
E18 18.0 1 17.3 61.7 70 E36 36.0 2 34.6 67.6 70 E54 54.0 2 52.0 76.2 90 E72 72.0 2 69.3 93.5 100
NOTE 1: HACR Type per NEC.
1
Unitary Products Group 27
262259-YTG-B-0107
TABLE 22: DM VOLTAGE LIMITATIONS
VOLTAGE LIMITATIONS
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1. Utilization Range “A” in accordance with ARI Standard
110.
208/230-3-60
460-3-60 575-3-60
VOLTAGE
MIN. MAX.
187 253 414 506
518 630
TABLE 23: PHYSICAL DATA
MODELS DM180 DM240 DM300
EVAPORATOR
BLOWER
EVAPORATOR COIL
CONDENSER FAN
(Two Per Unit)
CONDENSER
COIL
COMPRESSOR
(Qty. Per Unit)
FILTERS
CHARGE
OPERATING
WEIGHTS
(LBS.)
1. This compressor will be energized first.
CENTRIFUGAL BLOWER (Dia. x Wd.) 15x15 18x15 18x15 FAN MOTOR HP, STANDARD/HI STATIC 5.0 7.5 10/15 ROWS DEEP 3 3 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 15.5 20 20.52 PROPELLER DIA. (In.) (Each) 30 FAN MOTOR HP (Each) 1 NOM. CFM TOTAL (Each) 6,500 7,200 7,200 ROWS DEEP 2 2 2 FINS PER INCH 13 20 20 FACE AREA (Sq. Ft.) 36 43.3 43.3 5 TON HERMETIC (RECIP.) 1 - -
10 TON TANDEM (RECIP.)
12.5 TON (SCROLL) - - 2 QUANTITY PER UNIT (12" X 24" X 2" or 4”) - - ­QUANTITY PER UNIT (16" X 20" X 2" or 4”) - 4 4 QUANTITY PER UNIT (16" X 25" X 2" or 4”) - 4 4 QUANTITY PER UNIT (18" X 24" X 2" or 4”) 5 - ­TOTAL FACE AREA (Sq. Ft.) 15 20 24 REFRIGERANT 22 (Lb./Oz.)
BASIC UNIT
OPTIONS
ACCESSORIES
SYSTEM No.1 17/8 18/0 18/0 SYSTEM No. 2 8/8 18/0 18/0 COOLING ONLY 1900 2100 2291
GAS / ELECTRIC ECONOMIZER 160
ECONOMIZER WITH POWER EXHAUST
MOTORIZED DAMPER 150
ELECTRIC HEATER
HOT GAS BYPASS 10 SUPPLY FAN VFD See Table 24 ROOF CURB 175 185 185 BAROMETRIC DAMPER 45 ECONOMIZER / MOTORIZED
DAMPER RAIN HOOD ECONOMIZER / POWER
EXHAUST RAIN HOOD WOOD SKID 200 220 220
1
1
1
N24 2100 2300 2491 N32 2140 2340 2531
18 KW 25 36 KW 30 54 KW 35 72 KW 40
2-
245
55
90
28 Unitary Products Group
262259-YTG-B-0107
TABLE 24: SUPPLY FAN VFD WEIGHTS, IN LBS.
SUPPLY FAN MOTOR 230V 460V 575V
W/O MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp
25 25 30 30 30 30 30 30 35 30 30 40
W/MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp
30 30 35 35 35 35 35 35 40 40 35 45
CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
RC RH
Y1
ADD JUMPER
Y2
W1 W2
G
B
LED1 LED2
NOT USED
COM
ADD JUMPER
A1
A2
T
T
TO REMOTE SENSOR
1
Electronic programmable thermostat 2ET04700224 (includes subbase).
2
Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3
Second stage heating is not required on units with a single stage electric heater.
4
Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
2THO4702224 IF USED
when the thermostat switches to the set-back position.
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
3
4
UNIT TERMINAL
BLOCK 1 TB
4
2
R
Y1 Y2
W1
W2
G
B X
24 VOLT
A1
TRANSFORMER
A2
TABLE 25: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208 240 480 600
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
ADD JUMPER
1
24 Volt Thermostat 2TH04701024 or 2TH04701524
(with Subbase 2TB04700324).
2
Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
3
Second stage heating is not required on units with a single stage
electric heater.
1
RH
RC
Y1
Y2
W1
W2
G
208 1.00 230 0.92 460 0.92 575 0.92
UNIT TERMINAL
3
BLOCK 1TB
R Y1 Y2 W1
W2
G
B
X A1 A2 Y3
2
24 VOLT TRANSFORMER
POWER WIRING
LINE VOLTAGE TERMINAL BLOCK 2TB IN CONTROL BOX
GROUND LUG
L1
L2 L3
Refer to the ELECTRICAL DATA tables to size the power wiring, the fuses and the disconnect switch.
FIGURE 3 - TYPICAL DM FIELD WIRING DIAGRAM
Unitary Products Group 29
BLOWER ACCESS (Location Of Optional VFD)
BLOWER MOTOR ACCESS (Location Of Optional VFD Bypass)
BLOWER COMPARTMENT ACCESS (Auxiliary)
DOT PLUG (For pressure Drop Reading)
ELECTRIC/
GAS HEAT ACCESS
VENT AIR OUTLET HOODS
COMBUSTION AIR INLET HOOD
(C) GAS SUPPLY ENTRY
125-1/4"(15 TON)
136-1/4” (20, 25 TON)
FIELD-SUPPLIED DISCONNECT SWITCH LOCATION
CONTROL BOX ACCESS
FRONT VIEW
12-1/4"(15 TON)
35-1/4” (20, 25 TON)
UNIT BASE WITH RAILS Shown separately to illustrate
Bottom Duct openings, Power and Gas Piping Connection locations
NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for the proper size of the supply and return air duct connections.
(D) GAS SUPPLY ENTRY
6-3/8"
35"
11-1/8"
7-1/8"
)
33"
2-3/4" 21-1/2"
46-5/8"
21"
5"
9-3/4"
5-7/8"
46-5/8"
RETURN
AIR
12-1/2"
ECONOMIZER / MOTORIZED DAMPER, FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail "Y")
92"
11-1/2"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
SUPPLY
AIR
(B) POWER WIRING ENTRY
(A)
8-1/8"
9-1/4"
9-3/4"
CONTROL WIRING ENTRY
262259-YTG-B-0107
COMPRESSOR ACCESS
COIL GUARD
48-5/8"(15 TON) 52-5/8" (20, 25 TON)
CONDENSER COILS
(A) CONTROL WIRING ENTRY
(B) POWER WIRING ENTRY
3-3/4"
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
FIGURE 4 - UNIT DIMENSIONS & CLEARANCES 15, 20 & 25 TON
TABLE 26: UTILITIES ENTRY DATA
HOLE
30 Unitary Products Group
OPENING SIZE
(DIA.)
A
B
C D
1-1/8” KO
3/4” NPS (Fem.) Bottom
3-5/8” KO
3” NPS (Fem.) Bottom
2-3/8” KO
1-11/16” Hole Gas Piping (Bottom)
Control Wiring
Power Wiring
USED FOR
Gas Piping (Front)
1. One-inch gas piping NPT required.
2. Opening in the bottom of the unit can be located by the slice in the insulation.
NOTE:
All entry holes should be field sealed to prevent rain water entry into the building.
Side
Side
1
,
1
2
262259-YTG-B-0107
40-3/8"
COMPRESSOR ACCESS
SUPPLY AIR ACCESS
Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit.
FIGURE 5 - REAR VIEW DIMENSIONS
RETURN AIR ACCESS
REAR
VIEW
SUPPLY AIR
18-5/8"
5-1/8"
RETURN AIR
27-3/4"
28-5/8” (15 TON) 39-5/8" (20, 25 TON)
OUTDOOR AIR
40-1/2"
OUTDOOR AIR COMPARTMENT ACCESS
EVAPORATOR SECTION
DOT PLUG (For pressure drop reading)
FILTER ACCESS
1" NPT FEMALE COND. DRAIN CONNECTION
NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for connecting side ducts.
For bottom duct applications:
1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers.
2. Remove and discard the bo ttom duct covers. Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.
3. Replace the side supply and return air compartment panels.
For side duct applications:
1. Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels.
2. Connect ductwork to the flanges on those panels.
Unitary Products Group 31
262259-YTG-B-0107
TABLE 27: MINIMUM CLEARANCES
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
Above Unit
1
2
CLEARANCE
36”
24” (Less Economizer)
49” (With Economizer)
24” (Less Economizer) 36” (With Economizer)
36”
0”
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
1. Units may be installed on combustib le floors made f rom wood or class A, B, or C roof covering material.
2. Units must be installed out doors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hoo d must be removed from its ride along position in front of evapora­tor coil, or in the outdoor air compartment, prior to final installa­tion.
ECONOMIZER MOTORIZED
SUPPLY AIR COMPARTMENT
POWER EXHAUST RAIN HOOD (on Return Air Compartment)
DAMPER RAIN HOOD (on Outdoor Air Compartment)
NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material when equipped with electric heaters.
GAS / ELEC Models
: A 1” clearance must be
provided between any combustible material and the
3
supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) fe et above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).
• Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.
• Four (4) feet fro m el ectric and gas meters, regulators and relief equipment.
ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS
36-5/8
16-1/8
5
28-3/16”
REAR VIEW
DETAIL “Y”
UNIT WITH RAIN HOODS
FIGURE 6 - UNIT DIMENSIONS DM180, 240 & 300 (RAINHOOD)
FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)
92”
LH VIEW
1“ CONDENSATE DRAIN (Must be trapped)
32 Unitary Products Group
262259-YTG-B-0107
FIGURE 7 - CENTER OF GRAVITY
FIGURE 8 - TYPICAL UNIT APPLICATIONS
Unitary Products Group 33
262259-YTG-B-0107
B
A
F R O N T
D
C
A
F
B
E
C
FIGURE 9 - FOUR AND SIX POINT LOADS
TABLE 28: FOUR AND SIX POINT LOADS
Total
Unit Size
Shipping
Weight
ABC D
180 Gas 2300 539 563 612 586 240 Gas 2500 538 563 715 684
300 Gas 2531 593 645 674 619 180 Elec 2100 492 514 558 536 240 Elec 2300 295 517 658 630 300 Elec 2331 546 594 621 570
Total
Unit Size
Shipping
Weight
ABC D E F
180 Gas 2300 351 367 392 416 399 375
240 Gas 2500 334 350 426 502 481 407
300 Gas 2531 390 412 436 456 430 407 180 Elec 2100 320 335 358 380 364 343 240 Elec 2300 307 322 392 462 442 375 300 Elec 2331 359 379 402 420 396 375
4 Point Loads (lbs)
6 Point Loads (lbs)
D
F R O N T
34 Unitary Products Group
262259-YTG-B-0107
SUPPLY AIR*
BACK OF UNIT
RETURN AIR*
DUCT SUPPORT RAILS
2"
35-7/8"
84"
DUCT SIZES: Supply Air = 22-1/2" x 35-5/8" Return Air = 32-7/8" x 35-5/8"
4"
14-1/4" (15 Ton) 25-1/4" (20, 25 Ton)
FIGURE 10 -UNIT ROOF CURB DIMENSIONS
4"
MIN. ROOF OPENING: 39-7/8" WIDE X 61-7/8" Long
OUTDOOR COIL END OF UNIT
4"
2"
22-3/4"
33-1/8"
115-5/16" (15 Ton) 126-1/4" (20, 25 Ton)
*Supply and Return Air (including duct support rails)
FRONT
OF
UNIT
as shown, are typical for bottom duct applications.
For location of horizontal duct applications (on back of unit), refer to Unit Dimension details.
2. The 58-1/2” overa ll dimension of the ducts allows duct­work penetration between roof joists that are spaced on 72” centers.
NOTE: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made inside the curb.
FIGURE 11 -ROOF CURB DUCT OPENINGS
DIMENSION
1. The 2” space between the ducts allows for “jumping” an existing roof joist.
Unitary Products Group 35
262259-YTG-B-0107
THERMOSTAT
TERMINALS
W1
1
W2
Y1
2
Y2
G
R
C
4
RC
5
OCC
6
X
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
1
Second stage heating not required on single stage heating units.
2
Second stage cooling not required on single stage cooling units.
3
Jumper is required if there is no Smoke Detector circuit.
4
Jumper is required for any combination of R, RC, or RH.
5
OCC is an output from the thermostat to indicate the Occupied condition.
6
X is an input to the thermostat to display Error Status conditions.
CONTROL TERMINAL
BLOCK
W1
W2
Y1
G
OCC
P
P1
Y2
X
R
SD
C
SD
SD
Smoke
Detector
Jumper
3
24 VAC Class 2
R
C
FIGURE 13 -TYPICAL Simplicity® CONTROL WIRING DIAGRAM
36 Unitary Products Group
262259-YTG-B-0107

GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility.
York's Sunline 2000™ units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cool­ing with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessori e s to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installa­tion and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For hori­zontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.
Each unit shall have 2 condenser fan motors. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement. All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line fil­ter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an addi­tional set of pin connectors to simplify the interface of addi­tional field controls. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models are CSA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, DM***N Electric Cooling/Gas Heat, DM***C/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted instal­lation. The 15, 20 and 25 ton units shall have minimum EER ratings of 8.5.
They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship-
ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CGA listed, classified to ANSIZ21.47 standards, UL 1995/ CAN/CSA No. 236-M90 conditions.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, wi th exterior surfaces coated with a non-chalking, powd ere d paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower section sha ll be insula ted with a min­imum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace comp artment and be fastened with ridged fasteners to prevent insu lat io n from entering the air stream. Cabinet pa nel s sha ll be "l arg e" size, easily removable for servicing and maintenance . Fu ll perimeter base rails shall be provided to assure reliable tra nsit of equipment, overhead rigging and p ro pe r sea li ng on roof curb applications. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed air­tight. Units filter track shall be designed to accommodate either 2" or 4" filters. Fan performance measuring ports shall be provided on the outside of the cabine t to allow accura te air measurements of evaporator fan pe rforma nce without remov­ing panels or creating air by-p a s s of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 1" I.D. female and be a ridged mou nt connecti on. Unit shall incorporate a fixed outdoor air damper with an out­door air intake opening covered with a bi rd screen an d a rain hood painted to match the exterior of the unit.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable­pitch motor pulley. Job site selected (B.H.P.) brake horse­power shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency drive (VFD) is available for applications requiring a constant supply duct static pressure. Units equipped for VAV shall be controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC output signal to a VAV control board which, in turn shall provide a 2 - 10 VDC speed reference signal to the VFD. Units equipped with VFD’s shall have factory-installed man­ual bypass as an option.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor­rosion resistant steel spider brackets and shall be dynami­cally balanced for smooth operation. The 2 outdoor fan motors shall be totally enclosed with permanently lubricated
Unitary Products Group 37
262259-YTG-B-0107
bearings, internally protected against overload conditions and staged independently.

REFRIGERANT COMPONENTS

Compressors:
a. Shall be Scroll (25T only) compressors internally
protected with internal high-pressure relief and over temperature protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter­nally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Fi lter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions. e. All mode ls shall have two independent circuits. f. Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.

UNIT CONTROLS

a. Unit shall be co mplete with self-contained low-volt-
age control circuit protected by a resettable circuit
breaker on the 24-volt transformer side. b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor. c. Loss-of-charge/Low-pressure switch.
1. High-pressure switch.
2. Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a
diagnostic code that indicates which safety switch has tripped.
d. Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.
e. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics
and fault code display.
g. Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation down to 0 °F.
h. Contro l board shall monitor each refrigerant safety
switch independently.
i. Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of a power loss.

GAS HEA TING SECTION (DM***N MODELS)

Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun­dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25° F. Burners shall be of the in­shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol­lowing minimum protection:
a. Primary and auxiliary high-temperature limit
switches. b. Induced draft motor speed sensor. c. Flame roll out switch (automatic reset). d. Flame proving controls. Unit shall have two inde-
pendent stages of capacity.

ELECTRIC HEATING (DM***C/E MODELS)

Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor , with standard controls, shall be capable of operation down to 0° F outdoor
38 Unitary Products Group
262259-YTG-B-0107
temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER - Outdoor and return air dampers that are inter­locked and positioned by a fully-modulating, spring­return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti­ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi­tioned space during normal operation. During econo­mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper­ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out­door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil­ters shall be provided. Simultaneous economizer/com­pressor operation is also possible. Dampers shall fully close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maxi­mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi­tions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14" high, full perimeter curb with wood nailer (shipped knocked-down).
100% BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mount­ing hardware. Used to relieve internal air pressure through the unit.
PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.
HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
BURGLAR BARS - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings.
SIDE DUCT FLANGE - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust.
HIGH SPEED DRIVE - Includes blower pulley and belt for higher CFM and/or static pressure requirements.
WOOD SKID - Allows unit to be handled with 90" forks.
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (DMN/E/C300 only) - Contains all hood panels and the hardware for assembling.
ANTI-RECYCLE TIMER - Assures 5-minute off time between compressor cycles.
COIL GUARD KIT - Guard for cooling coil.

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION - To work in conjunction with economizers.
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
BAS CONTROLS (Simplicity® INTELLI-Comfort™ CPC,
JOHNSON, HONEYWELL, NOVAR)
BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER)
Unitary Products Group 39
HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS
HIGH SPEED DRIVE
•2" THROW AWAY FILTERS
4" PLEATED FILTERS
DISCONNECT SWITCH
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
Subject to change without notice. Printed in U.S.A. 262259-YTG-B-0107 Copyright © 2007 by Unitary Products. All rights reserved. Supersedes: 262259-YTG-A-0706