York DJ 150 User Manual

Page 1
GUIDE
GUIDE
MAGNUM
ULTRA HIGH EFFICIENCY
246695-YTG-C-0708
®
®

DESCRIPTION

YORK® Predator® Magnum is a convertible single package unit with a common footprint cabinet and common roof curb for 12­1/2 ton models. All units have two compressors with indepen­dent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.
SINGLE P ACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS
DJ 150 12-1/2 NOMINAL TONS
11.35 EER
®
All Predator on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
All units are convertible between side and down airflow. Inde­pendent economizer designs are used on side and down dis­charge applications, as well as all tonnage sizes.
Predator rations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or field-installed accessories.
Tested in accordance with:
Magnum units are self-contained and assembled
®
Magnum units are available in the following configu-
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
246695-YTG-C-0708

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . .5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . .6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . 26

LIST OF FIGURES

Fig. # 1 PREDATOR® MAGNUM COMPONENT LOCATION. .3
2 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . .16
3 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . .16
4 UNIT WITH 6 POINT LOAD . . . . . . . . . . . . . . . . . . . .16
5 UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . .17
6 PREDATOR® MAGNUM ROOF CURB
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7 SUNLINE™ TO PREDATOR® MAGNUM
TRANSITION ROOF CURBS . . . . . . . . . . . . . . . . . . .18
8 BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . .19
9 SIDEFLOW DUCT DIMENSIONS . . . . . . . . . . . . . . .19
10 DOWNFLOW ECONOMIZER HOOD DETAIL . . . . . . 20
11 FACTORY INSTALLED DOWNFLOW
ECONOMIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
12 FIELD INSTALLED DOWNFLOW ECONOMIZER
W/POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . .21
13 FIELD INSTALLED HORIZONTAL ECONOMIZER
W/POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . .21
14 SLAB ECONOMIZER DOWNFLOW W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
15 SLAB ECONOMIZER END RETURN W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
16 COOLING UNIT WITH GAS HEAT WIRING 230 V.
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
17 COOLING UNIT W/WO ELECTRIC HEAT WIRING
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
18 COOLING UNIT WITH GAS HEAT WIRING 460,
575 & 50 HZ DIAGRAM . . . . . . . . . . . . . . . . . . . . . . .25
Pg. #

LIST OF TABLES

Tbl. #
1 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 DJ 150 (12-1/2 TON) CAPACITY RATINGS . . . . . . . 10
4 UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . 10
5 DJ 150 (12 1/2 TON) COOLING CAPACITY . . . . . . . 11
6 ELECTRICAL DATA DJ150 (12-1/2 TON) W/O PWRD
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . 12
7 ELECTRICAL DATA DJ150 (12-1/2 TON) WITH PWRD
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . . 12
8 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . 12
9 BLOWER PERFORMANCE 12-1/2 TON SIDE
DUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 BLOWER PERFORMANCE 12-1/2 TON
DOWNSHOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11 ADDITIONAL STATIC RESISTANCE . . . . . . . . . . . . 15
12 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM . . . . 15
13 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . 15
14 POWER EXHAUST SPECIFICATIONS . . . . . . . . . . . 15
15 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 16
16 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 16
17 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
18 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . 17
19 ECONOMIZER USAGE . . . . . . . . . . . . . . . . . . . . . . . 20
Pg. #
2 Johnson Controls Unitary Products
Page 3
246695-YTG-C-0708
Second model
nameplate inside
hinged access panel
Dual stage cooling
for maximum comfort
Compressor #2 access
(high-efficiency compressor
w/crankcase heater)
Base rails
w/forklift slots
(three sides)
and lifting holes
Simplicity™ Control board
w/screw connectors for T-stat
wiring and Network Connection
Disconnect location
(optional disconnect switch)
Filter access
(2" throw-away)
Filter drier (solid core)
Condenser
Section
Belt-drive
blower motor
Slide out motor and
blower assembly
for easy adjustment
and service
Power ventor motor
20-gauge aluminized steel tubular heat exchanger for
long life (stainless steel option)
Roof curbs in eight-and
fourteen-inch heights.
Roof curbs for transitioning
from York Sunline™ footprint to
the DM/DH/DJ Series footprint
are available
(field-installed accessory)
Toolless
doorlatch
Side entry power
and control wiring
knockouts
Slide-out drain pan
with steel ¾" NPT, female connection
Compressor #1 access
(high-efficiency compressor
w/crankcase heater)

FIGURE 1 - PREDATOR® MAGNUM COMPONENT LOCATION

FEATURES

High Efficiency – High efficiency units are rated at 11.35 EER. Gas/electric units have electronic spark ignition and power vented combustion with steady state efficiencies of 80%. These efficiencies meet or exceed all legislated min­imum levels and provide low operating costs.
®
Service Friendly – The Predator
Magnum incorpo­rates a number of enhancements which improve service­ability.
The motor and blower slide out of the unit as a common assembly. This facilitates greater access to all the indoor airflow components, thus simplifying maintenance and adjustment.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unauthorized persons. It is recommended that the panels be secured with screws once service is complete.
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board uti­lize flash codes to aid in diagnosis of unit malfunctions. Unique alarm codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This standard­ization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to per­mit easy cleaning. The drain pan is accessed by remov­ing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
All Predator plate located inside the control access door . This is to pre­vent deterioration of the nameplate through weathering.
Two-stage gas heating
to maintain warm,
comfortable temperature
Intelligent control board
for safe and efficient operation
®
Magnum units have a second model name-
Johnson Controls Unitary Products 3
Page 4
246695-YTG-C-0708
Environmentally Aware – For improved Indoor Air Quality, foil faced insulation is used exclusively through­out the units.
Balanced Heating – The Predator® Magnum offers “Ultimate Heating Comfort” with a balance between 1 and 2nd stage gas heating. The first stage of a gas heat Predator® Magnum unit provides 60% of the heating capacity . Balanced heating allows the unit to better main­tain desired temperatures.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side supply/ return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection – Suction line freezestats are sup­plied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low-pressure switches. Internal compressor protection is standard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compres­sors do not require crankcase heaters. Phase monitors are standard on all units.
Advanced Controls - Simplicity control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to 0°F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air tem­perature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling fan delay times are independent of one ano ther. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit con­trol board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip
three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
st
trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable – From the beginning – All units undergo com­puter automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term – All Predator
®
units are painted with a long lasting, pow­der paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size and heating option after the internal loads have been determined.
To further simplify planning and installation, Predator Magnum cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” on-center joists or between 48” on-center joist s.
The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be fitted to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.
Easy Installation – Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connec­tions can be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to han­dle most airflow requirements. For high static applica­tions, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at a minimum of 1.5” ESP.
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and e lectric heater elements each carry a 5-year warranty. Aluminized steel and stainless steel tubular heat exchangers carry a 10­year warranty.
®
4 Johnson Controls Unitary Products
Page 5

FACTORY INSTALLED OPTIONS

YORK® offers several equipment options factory installed, for the Predator® Magnum line.
Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed econo­mizers with low leak dampers. The outdoor air enthalpy sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module. See Table 19 to determine the correct econo­mizer for your application.
Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Pro­vided). The economizer has spring return, fully modu­lating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to econo­mizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the
economizer control accepts an optional CO demand ventilation. With single enthalpy input, the
economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the econ­omizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric
relief) - All features of the downflow economizer exist except you must order the duct mount baro­metric relief separately. You must order a 1EH0408
if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief)
- The economizer is provided with a Belimo actuator that requires a 0-10V DC input from an external source (i.e., field installed building automation sys­tem controller). Power exhaust options are avail­able. The economizer is 2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” pleated filters.
Slab Economizer for Energy Recovery Ventilators-
(With barometric relief and Fresh Air Hood) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air damp­ers close. The changeover from mechanical refrigera­tion to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional
input for
2
246695-YTG-C-0708
input for demand ventilation. With single enthalpy
CO
2
input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to mon­itor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For applica­tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof stain­less steel drain pan is available to provide years of trou­ble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 18kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
Disconnect Switch - For gas heat units and cooling units with electric heat, an HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This option locates a 120V single-phase GFCI o utl et with cover, on the corn er o f the un it housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase p ower sou r ce and wiring. The “Powered” option is powere d b y a ste p­down transformer in the unit. Factory installed option only .
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. Avail abl e for both the supply and/or return air.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Johnson Controls Unitary Products 5
Page 6
246695-YTG-C-0708
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on unit s wi th Scro ll Com-
pressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
T echni coat C ondense r Coil s - The condenser coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
BAS - Building Automation System Controls Simplic- ity™ Intelli-Comfort™ Control - The York® Simplicity™ Intelli-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor , an d an Outside Air IAQ sensor. Construc tion mode operation, 365-day real time clock with 7 day pro­gramming plus holiday scheduling is built-in. Two differ­ent modes of demand ventilation are achieved through the Intelli-Comfort™ using CO
sensors. It uses an
2
inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO
sensor to perform Differential
2
Demand Ventilation. It uses a Patented Comfort Ventila­tion algorithm to provide comfortable ventilation air tem­perature. The patented economizer-loading algorithm will protect the equipment when harsh operating condi­tions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the Intelli-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ Intelli­Comfort™ balances space temperature, ventilation air temperature, CO
and humidity for ultimate comfort.
2
Simplicity™ Intelli-Comfort™ with ModLINC Control - The York® Simplicity™ Intelli-Comfort™ with ModLINC control is factory installed. It includes all the features of the Intelli-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and change-over bypass systems.

FIELD INSTALLED ACCESSORIES

YORK® offers several equipment accessories for field instal­lation, for the Predator
Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo­mizer control accepts an optional CO ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit pro­vides a second input used to monitor the return air. With a dual input kit installed, the economizer control com­pares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible
Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator­(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the econo­mizer control accepts an optional CO
®
Magnum line.
input for demand
2
input for demand
2
6 Johnson Controls Unitary Products
Page 7
246695-YTG-C-0708
ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit pro­vides a second input used to monitor the return air. With a dual input kit installed, the economizer control com­pares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maxi­mum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a hori­zontal flow application.
Manual Outdoor Air Damper - Like the motorized out- door air damper , each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
CO
Sensor - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas heat units to perform in low ambient temperatures, a gas section heating kit is available. This kit provides electric heat in the gas heat controls section to ensure the gas valve and controls will continue to function properly at extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Conversion kits are available for natural gas and pro­pane.
Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It contains the main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.
Electric Heaters - The electric heaters range from 18 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
Low Limit / Compressor Lockout Kit
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security con­cerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) ­Roof curbs for transitioning from Sunline™ units to Pred-
®
Magnum. Fits 7.5 to 12.5 Sunlin e™ roof curbs only.
ator
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24- volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only ther­mostats, depending upon unit configuration.
Johnson Controls Unitary Products 7
Page 8
246695-YTG-C-0708

TABLE 1: ACCESSORIES

Part Number Description Weight
1RC0470 Roof Curb, 8" Height ­1RC0471 Roof Curb, 14" Height ­1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) ­1BD0408 Burglar Bars, Downflow ­2TP04521825 Electric Heat 18kW 230V ­2TP04522425 Electric Heat 24kW 230V ­2TP04523625 Electric Heat 36kW 230V ­2TP04525425 Electric Heat 54kW 230V ­2TP04521846 Electric Heat 18kW 460V ­2TP04522446 Electric Heat 24kW 460V ­2TP04523646 Electric Heat 36kW 460V ­2TP04525446 Electric Heat 54kW 460V ­2TP04521858 Electric Heat 18kW 575V ­2TP04522458 Electric Heat 24kW 575V ­2TP04523658 Electric Heat 36kW 575V ­2TP04525458 Electric Heat 54kW 575V ­1FA0411 Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­1FA0412 Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­2MD04702724 Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief) ­2MD04703324 Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief) 2EE04705024 Economizer, Downflow (Incl. Barometric Relief & All Hoods) 124 lbs. 2EE04705124 Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief) 97 lbs. 2EE04705224 Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief) 2PE04703225 Power Exhaust, Downflow, 230V (For Units with Economizer only) ­2PE04703246 Power Exhaust, Downflow, 460V (For Units with Economizer only) ­2PE04703258 Power Exhaust, Downflow, 580V (For Units with Economizer only) ­2EC04700924 Dual Enthalpy Control (Use with Single Enthalpy Economizer) ­1EH0407 Hood Kit, Downflow Economizer (Included with all Downflow Economizers) 1RD0411 Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood) 1EH0408 Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood) 25 lbs. 1EH0409 Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood) ­2AQ04700424 CO2 Detector Unit Mount ­2AQ04700324 CO2 Detector Space Mount ­2SD04700424 Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer) ­2MK04700624 Low Limit / Compressor Lockout Kit 1CG0424 Coil Guard (Electric / Electric & HP models) ­1CG0425 Coil Guard (Gas / Electric models) ­1HG0411 Hail Guard Kit ­1GP0404 Gas Piping Kit ­1NP0441 Propane Conversion Kit ­1HA0442 High Altitude Kit for Natural Gas ­1HA0443 High Altitude Kit for Propane ­1FE0411 Flue Exhaust Extension Kit ­2BC04700106 Gas Heat Kit, -60 deg F, 230V ­2BC04700151 Gas Heat Kit, -60 deg F, 460V ­2BC04700154 Gas Heat Kit, -60 deg F, 575V ­1FL0402 Permanent Filter Kit ­2DF0401 Dirty Filter Switch ­1FF0410 Filter Frame Kit, Metal -
8 Johnson Controls Unitary Products
Page 9

NOMENCLATURE

D J 150 N15 A 2 A AA 4 0 1 2 4 A
246695-YTG-C-0708
12.5 Ton Model Number Nomenclature
Product Category
D = A/C, Single Pkg., R-22
Product Identifier
J = 12.5 Ton 11.3 EER A/C
Nominal Cooling Capacity
150 = 12.5 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Gas Heat Options
N15 = 150 MBH Output Aluminized Steel N20 = 200 MBH Output Aluminized Steel S15 = 150 MBH Output Stainless Steel S20 = 200 MBH Output Stainless Steel
Electric Heat Options
E18 = 18 KW E24 = 24 KW E36 = 36 KW E54 = 54 KW
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only) D = Std. Motor/Motorized Damper (Downflow Only) E = Std. Motor/Horizontal Economizer (No Baro.) F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only) N = Hi Static Mtr. P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only) Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only) R = Hi Static Mtr./Motorized Damper (Downflow Only) S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only) U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Product Style
A = Style A B = Style B C = Style C
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
2" Pleated filters
BAS Ready Unit with Belimo Economizer
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
4 = Fourth Generation
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
Configuration Options (not required for all units)
Additional Options
RC = Coil Guard, Shipping Bag & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
Options
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products 9
Page 10
246695-YTG-C-0708

TABLE 2: PHYSICAL DATA

Component
Model
DJ 150 (12-1/2)
Evaporator
Blower
Evaporator
Coil
Condenser
Fan
(4 per Unit)
Condenser
Coil
(2 per unit)
Refrigerant
Charge
Compressors
Air Filters
Blower, Centrifugal (Dia. X Wd. in.) 15 x 15
Motor, Standard (HP) 3
Motor, Optional (HP) 5
Rows 4
Fins per Inch 15
Height (in.) 40
2
Face Area (ft.
Propeller Dia. (in., each) 24
Motor (HP, each) 1/3
CFM, Nominal (each) 3500
Rows (each) 2 Fins per Inch 15
Height (in., each) 36
Face Area (ft.
System 1 (lb./oz.) 2/0 System 2 (lb./oz.) 20/8
Quantity 2
Size (Wd. x Ht. x Thickness in.) 25x20x2
Number Per Unit 4
each)
2
each)
Type Scroll
13.2
11.88

TABLE 3: DJ 150 (12-1/2 TON) CAPACITY RATINGS

Cooling Capacity
Size
(Tons)
Model
ARI Ratings
MBH EER IPLV
Cooling
Only
150
(12-1/2)
Electric
Heat Gas Heat - 180 144 80 10-40 3/4 Gas Heat - 240 192 80 25-55 3/4
1 Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb. 2 Rated in accordance with ARI 270 standard. 3 See Table 8.
150 11.35 12.3 3750 86
1
CFM
Sound
Rating
2
(dB)
Capacity

TABLE 4: UNIT VOLTAGE LIMITATIONS

POWER RATING MIN. MAX.
208/230-3-60
460-3-60 575-3-60
187 252 432 504 540 630
Nominal
Electric
Heat
3
Input
(kW)
--- - --
18, 24, 36
54
(MBH)
-- - - -
Gas Heat Capacity
Output
(MBH)
Seasonal
Efficiency (%)
Temp.
Rise (°F)
Gas Line Size
(in. OD)
10 Johnson Controls Unitary Products
Page 11
TABLE 5: DJ 150 (12 1/2 TON) COOLING CAPACITY
Air On
Evap. Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
72 173 10.9 102 92 81 70 60 49 38 168 11.8 101 90 79 69 58 47 37 67 160 10.6 127 116 105 95 84 73 63 154 11.6 124 114 103 92 81 71 60 62 148 10.5 148 141 131 120 109 99 88 143 11.4 143 138 127 116 106 95 84 57 147 10.5 147 144 133 123 112 101 91 141 11.5 141 137 126 116 105 94 84 72 177 10.9 112 100 87 74 62 49 37 170 11.8 111 98 85 73 60 47 35 67 163 10.7 138 126 113 101 88 75 63 156 11.7 136 123 110 98 85 72 60 62 151 10.6 151 148 141 128 115 103 90 145 11.5 145 142 136 124 111 98 86 57 150 10.5 150 149 143 131 118 106 93 143 11.5 143 141 136 123 110 98 85 72 180 11.0 122 108 93 79 64 49 35 173 11.9 120 106 91 76 62 47 33 67 167 10.7 150 136 121 107 92 77 63 158 11.8 147 132 118 103 89 74 60 62 154 10.6 154 154 150 136 121 107 92 147 11.6 147 147 146 131 116 102 87 57 154 10.6 154 154 154 139 124 110 95 145 11.6 145 145 145 130 116 101 87 72 184 11.0 133 116 100 83 66 50 33 176 12.0 131 114 98 81 65 48 31 67 170 10.8 162 146 129 113 96 80 63 161 11.8 155 143 127 110 93 77 60 62 157 10.7 157 157 155 139 122 106 89 150 11.7 150 150 149 132 116 99 83 57 157 10.6 157 157 157 140 123 107 90 147 11.7 147 147 147 131 114 98 81 72 188 11.1 143 125 106 87 69 50 32 179 12.1 142 123 105 86 67 49 30 67 173 10.8 173 156 138 119 101 82 63 164 11.9 164 154 135 117 98 79 61 62 161 10.7 161 161 161 142 123 105 86 152 11.7 152 152 152 134 115 96 78 57 160 10.6 160 160 160 141 122 104 85 150 11.8 150 150 150 131 113 94 75
72 158 13.0 99 88 77 67 56 45 34 148 14.3 96 86 75 64 54 43 32 67 145 12.9 120 110 99 88 78 67 56 136 14.2 116 106 95 84 74 63 52 62 134 12.7 134 129 119 108 97 87 76 125 14.0 125 121 110 100 89 78 67 57 134 12.8 134 130 119 109 98 87 77 128 14.2 128 123 112 102 91 80 70 72 160 13.1 109 96 83 71 58 45 33 150 14.4 107 94 81 69 56 43 31 67 147 13.0 132 119 107 94 81 69 56 138 14.2 128 116 103 90 78 65 52 62 136 12.8 136 134 128 115 103 90 77 127 14.1 127 125 120 107 94 82 69 57 136 12.9 136 134 129 116 103 91 78 130 14.2 130 127 122 109 97 84 71 72 162 13.2 119 104 89 75 60 46 31 152 14.4 117 102 88 73 58 44 29 67 149 13.0 144 129 114 100 85 71 56 140 14.3 140 126 111 96 82 67 53 62 138 12.8 138 138 137 123 108 93 79 129 14.1 129 129 129 114 100 85 70 57 138 12.9 138 138 138 124 109 94 80 131 14.3 131 131 131 117 102 88 73 72 165 13.2 129 112 96 79 63 46 29 155 14.5 127 111 94 77 61 44 28 67 152 13.1 149 139 123 106 90 73 56 143 14.3 143 135 119 102 86 69 53 62 140 12.9 140 140 140 123 107 90 74 131 14.1 131 131 131 114 98 81 65 57 141 13.0 141 141 141 124 107 91 74 134 14.3 134 134 134 117 100 84 67 72 168 13.3 140 121 102 84 65 47 28 157 14.5 138 119 100 82 63 44 26 67 154 13.1 154 150 131 113 94 75 57 145 14.3 145 145 127 108 90 71 53 62 143 12.9 143 143 143 124 106 87 68 133 14.2 133 133 133 115 96 77 59 57 143 13.0 143 143 143 124 106 87 68 136 14.3 136 136 136 117 99 80 61
72 137 15.6 94 83 73 62 51 41 30 67 127 15.5 112 102 91 80 70 59 48 62 116 15.3 116 113 102 91 81 70 59 57 121 15.5 121 116 105 95 84 73 63 72 139 15.7 105 92 79 67 54 41 29 67 129 15.5 125 112 99 87 74 61 49 62 118 15.3 118 116 111 99 86 73 61 57 123 15.5 123 120 115 102 90 77 64 72 141 15.7 115 100 86 71 57 42 28 67 131 15.5 131 122 108 93 78 64 49 62 120 15.3 120 120 120 106 91 77 62 57 125 15.6 125 125 125 110 95 81 66 72 144 15.7 125 109 92 75 59 42 26 67 133 15.5 133 131 115 99 82 65 49 62 122 15.4 122 122 122 106 89 72 56 57 127 15.6 127 127 127 110 94 77 60 72 146 15.7 135 117 98 80 61 42 24 67 136 15.6 136 136 123 104 86 67 48 62 124 15.4 124 124 124 105 87 68 49 57 129 15.6 129 129 129 110 92 73 54
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
Cap.
(MBH)
Tot.
1
Input
2
(kW)
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
Sensible Capacity (MBH)
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
246695-YTG-C-0708
1
Tot.
Cap.
(MBH)
Tot.
1
Input
2
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
1 These capacities are gross ratings. For net
capacity, deduct air blower motor , MBh = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
2 These ratings include condenser fan motors
(total 1 kW) and the compressor motors but not the supply air blower motor.
1
Johnson Controls Unitary Products 11
Page 12
246695-YTG-C-0708
A
A

TABLE 6: ELECTRICAL DATA DJ150 (12-1/2 TON) W/O PWRD CONVENIENCE OUTLET

Voltage
Compressors
RLALRAFL
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
20.0 146.0 1.5
208
230
8.4 73.0
460
6.7 60.0 0.6 4.1 6.0 1.8
575
Maximum HACR breaker of the same AMP size is applicable.
1
OD Fan Motors
Supply Blower
Motor FLA
35 3 5 3 5353 5
10.9 16.1 5.5 0.0
1.5 10.9 16.120.0 146.0
0.8 5.3 8.1 2.2 0.0
Pwr Exh
Motor
FLA
5.5 0.0
Pwr
Conv
Electric Heater
Outlet
Model No.
FLA
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90 2TP04521825 13.5 37.5 61.9 67.1 67.4 73.8 80 80 80 90 2TP04522425 18.0 50.0 76.1 82.6 83.0 89.5 80 90 90 90 2TP04523625 25.5 70.8 102.1 108.6 109.0 115.5 110 110 110 125
2TP04525425 40.6 112.7 154.5 161.0 161.4 167.9 175 175 175 175
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90 2TP04521825 18.0 43.3 67.8 74.3 74.6 81.1 80 80 80 90 2TP04522425 24.0 57.7 85.8 92.3 92.7 99.2 90 100 100 100 2TP04523625 34.0 81.8 115.9 122.4 122.7 129.2 125 125 125 150
2TP04525425 54.0 129.9 143.5 150.0 150.4 156.9 175 175 175 175
None -- -- 27.4 30.2 29.6 32.4 35 35 35 40 2TP04521846 18 22.6 33.7 37.2 36.4 39.9 35 40 40 40 2TP04522446 24 30.1 42.7 46.2 45.5 49 45 50 50 50 2TP04523646 34 42.7 57.7 61.2 60.5 64 60 70 70 70
2TP04525446 54 67.8 71.6 75.1 74.3 77.8 80 90 80 90
None -- -- 21.6 23.5 23.4 25.3 25 30 30 30 2TP04521858 18 18.1 26.8 29.2 29 31.4 30 30 30 35
0.0
2TP04522458 24 24.1 34 36.4 36.2 38.6 35 40 40 40 2TP04523658 34 34.1 46 48.4 48.3 50.6 50 50 50 60
2TP04525458 54 54.2 57.1 59.5 59.3 61.7 70 70 70 70
Actual
KW
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA w/Power Exhaust
(Amps)

TABLE 7: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH PWRD CONVENIENCE OUTLET

MCA w/Power Exhaust
(Amps)
Voltage
Compressors
RLALRAFL
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
20.0 146.0
208
20.0 146.0
230
8.4
460
6.7 60.0 0.6 4.1 6.0 1.8 4.0
575
1
Maximum HACR breaker of the same AMP size is applicable.
OD Fan Motors
73.0 0.8 5.3 8.1
Supply Blower
Motor FLA
35 3 5 3 5353 5
1.5 10.9 16.1 5.5 10.0
1.5 10.9 16.1 5.5 10.0
Pwr Exh
Motor
FLA
2.2 5.0
Pwr
Conv
Electric Heater
Outlet
FLA
Model No.
2TP04521825 13.5 37.5 73.0 79.5 79.8 86.3 90 90 90 100 2TP04522425 18.0 50.0 88.6 95.1 95.5 102.0 90 100 100 110 2TP04523625 25.5 70.8 114.6 121.1 121.5 128.0 125 125 125 150 2TP04525425 40.6 112.7 167.0 173.5 173.9 180.4 175 175 175 200
2TP04521825 18.0 43.3 80.3 86.8 87.1 93.6 90 90 90 100 2TP04522425 24.0 57.7 98.3 104.8 105.2 111.7 100 110 110 125 2TP04523625 34.0 81.8 128.4 134.9 135.2 141.7 150 150 150 150 2TP04525425 54.0 129.9 156.0 162.5 162.9 169.4 175 175 175 175
2TP04521846 18 22.6 39.9 43.4 42.7 46.2 40 45 45 50 2TP04522446 24 30.1 49 52.5 51.7 55.2 50 60 60 60 2TP04523646 34 42.7 64 67.5 66.7 70.2 70 70 70 80 2TP04525446 54 67.8 77.8 81.3 80.6 84.1 90 90 90 90
2TP04521858 18 18.1 31.8 34.2 34 36.4 35 35 35 40 2TP04522458 24 24.1 39 41.4 41.2 43.6 40 45 45 45 2TP04523658 34 34.1 51 53.4 53.3 55.6 60 60 60 60 2TP04525458 54 54.2 62.1 64.5 64.3 66.7 70 70 70 70

TABLE 8: ELECTRIC HEAT MULTIPLIERS

VOLTAGE
NOMINAL RATING
240 480
600
208 0.75 230 0.92 460 0.92 575 0.92
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for heaters supplied at lower voltages.
kW Cap. Multiplier
Min. Circuit
Actual
Heater
KW
Amps
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
None -- -- 32.4 35.2 34.6 37.4 40 40 40 45
None -- -- 25.6 27.5 27.4 29.3 30 30 30 35
Ampacity
(Amps)

NOTES FOR TABLES 9 AND TABLE 10:

Blower performance includes dry coil and 2” throwaway filters.
Blower performance for gas heat includes the maximum number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.
Max
Fuse
Size
(Amps)
Max
Fuse
Size
(Amps)
Max Fuse Size
1
w/Power
Exhaust
(Amps)
Max Fuse Size
1
w/Power Exhaust
(Amps)
1
1
12 Johnson Controls Unitary Products
Page 13
246695-YTG-C-0708
External Static Pressure
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP Watts RPM BHP Watts RPM BHP Wa tts RPM BHP Watts RPM BHP W atts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
CFM
3700 ---- ---- ---- ---- ---- ---- ---- ---- ---- 874 1.93 1801 927 2.04 1906 984 2.27 2113 1037 2.41 2245 1089 2.57 2399 1138 2.68 2499 1178 2.82 2628
3800 ---- ---- ---- ---- ---- ---- 840 1.82 1699 888 2.01 1871 941 2.14 1993 997 2.36 2202 1048 2.50 2334 1099 2.67 2485 1146 2.77 2586 1186 2.93 2728
3900 ---- ---- ---- ---- ---- ---- 855 1.92 1786 903 2.09 1947 954 2.24 2085 1009 2.46 2295 1060 2.60 2427 1109 2.76 2576 1155 2.88 2680 1195 3.04 2834
4000 ---- ---- ---- ---- ---- ---- 870 2.01 1877 917 2.18 2028 968 2.34 2182 1022 2.57 2392 1071 2.71 2524 1120 2.87 2672 1163 2.98 2780 1204 3.16 2947
4100 ---- ---- ---- ---- ---- ---- 885 2.12 1973 932 2.27 2115 982 2.45 2283 1035 2.68 2494 1083 2.82 2626 1130 2.98 2774 1171 3.10 2887 1212 3.29 3066
4200 ---- ---- ---- 834 2.11 1970 900 2.22 2072 946 2.37 2207 996 2.56 2390 1048 2.79 2601 1094 2.93 2733 1140 3.09 2881 1179 3.22 3000 1221 3.42 3192
4300 ---- ---- ---- 851 2.19 2042 915 2.33 2175 961 2.47 2305 1009 2.68 2501 1061 2.91 2712 1106 3.05 2844 1150 3.21 2993 1188 3.35 3119 1230 3.57 3324
4400 ---- ---- ---- 868 2.28 2121 931 2.45 2283 975 2.58 2409 1023 2.81 2616 1074 3.03 2828 1117 3.18 2960 1160 3.34 3111 1196 3.48 3245 1239 3.71 3462
4500 822 2.13 1990 885 2.37 2208 946 2.57 2395 990 2.70 2518 1037 2.94 2736 1087 3.16 2948 1129 3.30 3080 1171 3.47 3234 1204 3.62 3377 1247 3.87 3607
4600 838 2.23 2083 901 2.47 2301 961 2.69 2511 1004 2.82 2633 1051 3.07 2862 1099 3.30 3072 1141 3.44 3204 1181 3.61 3362 1212 3.77 3515 1256 4.03 3758
4700 854 2.34 2184 918 2.58 2401 976 2.82 2631 1019 2.95 2753 1064 3.21 2991 1112 3.43 3201 1152 3.58 3333 1191 3.75 3496 1221 3.93 3659 1265 4.20 3916
4800 870 2.46 2291 935 2.69 2508 991 2.96 2755 1033 3.09 2879 1078 3.35 3126 1125 3.58 3335 1164 3.72 3467 1201 3.90 3635 1229 4.09 3810 1273 4.38 4080
4900 887 2.58 2406 952 2.81 2622 1007 3.09 2883 1048 3.23 3011 1092 3.50 3265 1138 3.73 3473 1175 3.87 3605 1211 4.05 3779 1237 4.26 3967 1282 4.56 4250
5000 903 2.71 2527 968 2.94 2744 1022 3.24 3016 1062 3.38 3148 1105 3.66 3409 1151 3.88 3616 1187 4.02 3748 1222 4.21 3929 1245 4.43 4131 1291 4.75 4427
5100 919 2.85 2656 985 3.08 2872 1037 3.38 3152 1077 3.53 3291 1119 3.82 3558 1164 4.04 3763 1198 4.18 3895 1232 4.38 4083 1254 4.61 4301 1300 4.95 4610
5200 936 2.99 2791 1002 3.23 3007 1052 3.53 3293 1091 3.69 3439 1133 3.98 3711 1177 4.20 3914 1210 4.34 4046 1242 4.55 4244 1262 4.80 4477 1308 5.15 4800
5300 952 3.15 2934 1018 3.38 3149 1067 3.69 3438 1106 3.85 3593 1147 4.15 3869 1189 4.37 4070 1221 4.51 4202 1252 4.73 4409 1270 5.00 4660 1317 5.36 4996
5400 968 3.31 3083 1035 3.54 3298 1083 3.85 3587 1120 4.03 3753 1160 4.33 4032 1202 4.54 4231 1233 4.68 4363 1262 4.91 4580 1278 5.20 4848 ---- ---- ----
5500 984 3.48 3240 1052 3.71 3455 1098 4.01 3740 1135 4.20 3918 1174 4.51 4200 1215 4.72 4396 1244 4.86 4528 1273 5.10 4757 1286 5.41 5044 ---- ---- ----
5600 1001 3.65 3403 1069 3.88 3618 1113 4.18 3897 1149 4.39 4089 1188 4.69 4372 1228 4.90 4566 1256 5.04 4698 1283 5.30 4938 ---- ---- ---- ---- ---- ----
5700 1017 3.83 3574 1085 4.06 3788 1128 4.35 4058 1164 4.58 4265 1201 4.88 4549 1241 5.08 4740 1267 5.23 4872 1293 5.50 5125 ---- ---- ---- ---- ---- ----
5800 1033 4.02 3751 1102 4.25 3965 1143 4.53 4224 1178 4.77 4447 1215 5.07 4731 1254 5.28 4918 1279 5.42 5050 ---- ---- ---- ---- ---- ---- ---- ---- ----
5900 1050 4.22 3936 1119 4.45 4149 1159 4.71 4393 1193 4.97 4635 1229 5.27 4917 1267 5.47 5101 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6000 1066 4.43 4127 1136 4.66 4341 1174 4.90 4567 1207 5.18 4828 1243 5.48 5108 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6100 1082 4.64 4326 1152 4.87 4539 1189 5.09 4745 1222 5.39 5027 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6200 1098 4.86 4531 1169 5.09 4744 1204 5.29 4927 1236 5.61 5231 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

TABLE 9: BLOWER PERFORMANCE 12-1/2 TON SIDE DUCT

High Horsepower Option Required
Johnson Controls Unitary Products 13
Page 14
246695-YTG-C-0708
1258 3.52 3280
1233 3.48 3245 1271 3.66 3414
1247 3.63 3381 1285 3.81 3550
1223 3.59 3348 1261 3.78 3520 1298 3.96 3690
1198 3.56 3315 1237 3.74 3490 1275 3.93 3662 1311 4.11 3832
1173 3.52 3281 1212 3.71 3459 1251 3.90 3634 1289 4.08 3807 1325 4.27 3977
1148 3.48 3247 1188 3.68 3428 1227 3.87 3606 1266 4.06 3782 1303 4.24 3955 1338 4.43 4125
1164 3.64 3396 1204 3.84 3578 1242 4.03 3758 1280 4.22 3933 1316 4.40 4106 1352 4.59 4275
External Static Pressure
1139 3.61 3364 1180 3.81 3549 1219 4.00 3732 1257 4.20 3912 1294 4.39 4088 1330 4.57 4260 1365 4.75 4429
1115 3.57 3331 1156 3.78 3520 1196 3.98 3707 1234 4.17 3891 1272 4.37 4071 1309 4.56 4246 1344 4.74 4417 1379 4.92 4585
1090 3.54 3297 1132 3.74 3491 1172 3.95 3682 1211 4.15 3870 1250 4.35 4054 1287 4.54 4233 1323 4.73 4407 1358 4.91 4577 1392 5.09 4744
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
1103 3.87 3603 1144 4.08 3805 1184 4.29 4003 1222 4.50 4196 1259 4.70 4384 1296 4.90 4566 1331 5.09 4742 ---- ---- ---- ---- ---- ---- ---- ---- ----
1122 4.06 3784 1162 4.28 3987 1201 4.49 4185 1238 4.70 4378 1275 4.90 4565 1311 5.09 4745 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1141 4.26 3971 1180 4.48 4175 1218 4.69 4373 1255 4.90 4564 1291 5.10 4750 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1160 4.47 4166 1198 4.69 4369 1235 4.90 4566 1271 5.10 4756 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1178 4.69 4368 1216 4.90 4569 1253 5.11 4765 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
CFM
3700 ---- ---- ---- ---- ---- ---- 908 1.99 1853 957 2.12 1976 1004 2.27 2112 1050 2.42 2258 1094 2.59 2412 1136 2.76 2571 1177 2.93 2733 1217 3.11 2895
3800 ---- ---- ---- 875 1.96 1831 926 2.09 1946 974 2.23 2077 1020 2.38 2220 1065 2.54 2372 1108 2.71 2530 1151 2.89 2693 1191 3.06 2856 1231 3.24 3021
3900 ---- ---- ---- 893 2.06 1918 943 2.19 2044 990 2.34 2183 1036 2.50 2332 1080 2.67 2489 1123 2.84 2652 1165 3.02 2817 1205 3.20 2983 1244 3.38 3149
4000 ---- ---- ---- 911 2.16 2012 960 2.30 2147 1007 2.46 2294 1052 2.63 2449 1096 2.80 2611 1138 2.98 2777 1179 3.16 2945 1219 3.34 3113
4100 878 2.13 1984 929 2.27 2113 977 2.42 2256 1023 2.59 2410 1068 2.76 2571 1111 2.94 2737 1153 3.12 2906 1194 3.30 3076
4200 897 2.23 2080 947 2.38 2219 995 2.54 2371 1040 2.72 2531 1084 2.89 2697 1127 3.08 2867 1168 3.26 3039 1208 3.44 3211
4300 915 2.34 2184 965 2.50 2332 1012 2.67 2491 1056 2.85 2657 1100 3.03 2828 1142 3.22 3001 1183 3.41 3175
4400 934 2.46 2294 983 2.63 2451 1029 2.81 2617 1073 2.99 2788 1116 3.18 2963 1157 3.37 3139
4500 953 2.59 2411 1001 2.76 2577 1046 2.95 2749 1090 3.14 2925 1132 3.33 3103
4600 972 2.72 2536 1019 2.91 2708 1063 3.10 2886 1106 3.29 3066
4700 991 2.86 2667 1036 3.05 2846 1081 3.25 3029 1123 3.45 3212

TABLE 10: BLOWER PERFORMANCE 12-1/2 TON DOWNSHOT

4800 1009 3.01 2806 1054 3.21 2990 1098 3.41 3177
4900 1028 3.17 2951 1072 3.37 3141
5000 1047 3.33 3103
1066 3.50 3263 1108 3.71 3460 1149 3.92 3656 1189 4.13 3848 1227 4.33 4037 1265 4.53 4221 1302 4.72 4399 1338 4.91 4572 1372 5.09 4740 ---- ---- ----
5100
1084 3.68 3430 1126 3.89 3629 1167 4.11 3827 1205 4.31 4020 1243 4.51 4208 1281 4.71 4391 1317 4.90 4569 1352 5.09 4740 ---- ---- ---- ---- ---- ----
5200
5500
5400
5300
1197 4.91 4576 1234 5.12 4776 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1216 5.14 4792 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5800
5700
5600
6000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
6100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
5900
6200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
High Horsepower Option Required
Motor Efficiency0.8
Std HP Motor3
14 Johnson Controls Unitary Products
Page 15
246695-YTG-C-0708

TABLE 11: ADDITIONAL STATIC RESISTANCE

CFM
3700 0.20 0.04 0.18 0.21 0.22 0.26 3900 0.23 0.04 0.20 0.23 0.24 0.28 4100 0.25 0.04 0.22 0.25 0.26 0.31 4300 0.28 0.05 0.24 0.28 0.29 0.34 4500 0.30 0.05 0.26 0.30 0.31 0.37 4700 0.33 0.05 0.29 0.33 0.34 0.40 4900 0.36 0.05 0.31 0.35 0.37 0.43 5100 0.39 0.06 0.34 0.38 0.40 0.46 5300 0.42 0.06 0.37 0.41 0.43 0.49 5500 0.45 0.06 0.40 0.44 0.46 0.53 5700 0.48 0.06 0.43 0.47 0.49 0.56 5900 0.52 0.07 0.46 0.50 0.53 0.59 6100 0.56 0.07 0.49 0.53 0.56 0.62 6300 0.60 0.07 0.53 0.56 0.59 0.65
1 Add these resistance values to the available static resistance in the respective Blower Performance Tables. 2 Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table. 3 The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Cooling Only
1
Economizer2
3
18 24 36 54
Electric Heat KW
2

TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM

HEATER
kW
18 24 36 54 18 24 36 54 18 24 36 54
VOLTAGE
208/230 3750
480 3750
600 3750
UNIT NOMINAL TONS
12.5
MINIMUM SUPPLY AIR CFM

TABLE 13: INDOOR BLOWER SPECIFICATIONS

MODEL
DJ150
HP RPM Eff. SF Frame Datum Dia. (in.) Bor e (in.) Model Datum Dia. (in.) Bore (in.) Model
3 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54 5 1725 87% 1.15 184T 4.3 - 5.3 1 1/8 1VP56 6.7 1 BK77 BX55
MOTOR MOTOR SHEAVE BLOWER SHEAVE
BELT

TABLE 14: POWER EXHAUST SPECIFICATIONS

POWER EXHAUST
MODEL
2PE0473125 208/230 1
2PE0473158 575 1 1050 1.5 1.9 4
1 Motors are multi-tapped and factory wired for high speed.
VOLT PHASE
HP
0.75
MOTOR ELECTRICAL
RPM
1075
1
QTY LRA FLA MCA
24.9 5.0 6.3 10
1
N/A
2.2 2.8 5
Johnson Controls Unitary Products 15
FUSE
SIZE
CFM@
0.1 ESP
3,8002PE0473146 460 1
Page 16
246695-YTG-C-0708
FRONT
LEFT
A
B
D

FIGURE 2 - UNIT 4 POINT LOAD

TABLE 15: 4 POINT LOAD WEIGHT

Model
ABCD
DJ150
282 359 468 371
60"
LEFT
Location (lbs.)
25-½"
FRONT

FIGURE 3 - UNIT CENTER OF GRAVITY

C
LEFT
A
B
C
F
FRONT
D
E

FIGURE 4 - UNIT WITH 6 POINT LOAD

TABLE 16: 6 POINT LOAD WEIGHT

Model
DJ150
ABCDEF
184 210 246 323 275 242
Locations (lbs.)

TABLE 17: UNIT WEIGHTS

Model DJ150
Cooling Unit Only
w/Economizer
w/Power Exhaust
w/Gas Heat
w/Electric Heat
1
2
1 8 Tube Heat Exchanger 2 54 kW heater
Shipping
Weight (lb.)
1495 1480
85 84
150 148 110 110
49 49
Operating
Weight
(lb.)
16 Johnson Controls Unitary Products
Page 17
246695-YTG-C-0708
119-7/16
For Gas Pipe Entry
see DETAIL A
Convenience
Outlet
Convenience
Outlet Power
Entry 7/8
11-1/2
50-3/4
4-1/4
30-11/32
Power
Entry
2-1/2
Control
Entry
7/8
LEFT
59
30-3/16
24-3/16
17-3/16
6-3/16
27
FRONT
89
For Drain Dimensions
see DETAIL C
For Baserail Dimensions
see
DETAIL B

FIGURE 5 - UNIT DIMENSIONS

DETAIL A
5 - 1 / 4

TABLE 18: UNIT CLEARANCES

1
Top
Front
2
Rear
1 Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
2 To remove the slide-out drain pan, a rear clearance of 60” is
required. If space is unavailable, the drain pan can be removed through the front by separating the corner wall.
3 Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
G a s P i p e I n l e t
1 7 - 1 3 / 1 6
V i e w o f W a l l A c r o s s f r o m C o i l
72” 36” 36”
Right
Left
Bottom
3
B a s e P a n
12” 36”
0”
DETAIL B
DETAIL C
2 - 3 / 8
3 - 3 / 4
3 - 9 / 1 6
5 - 3 / 8
Johnson Controls Unitary Products 17
Page 18
246695-YTG-C-0708
R I G H T
8 0 - 5 / 8
2 0
S U P P L Y
8 o r 1 4
2 T Y P .
5 0 - 1 / 2
2 0
6
R E T U R N
3 0

FIGURE 6 - PREDATOR® MAGNUM ROOF CURB DIMENSIONS

2 T Y P
I N S U L A T E D D E C K U N D E R
C O N D E N S E R S E C T I O N
I N S U L A T E D D E C K U N D E R
C O M P R E S S O R S E C T I O N
F R O N T
2 3
5 0 - 1 / 2
3 0 - 1 / 2
4
2 6
R E T U R N
S U P P L Y
7 6 - 5 / 8
9 4
F R O N T
5 9 - 1 / 4
6 4 - 1 / 4

FIGURE 7 - SUNLINE™ TO PREDATOR® MAGNUM TRANSITION ROOF CURBS

8 0 - 5 / 8
1 0
R I G H T
18 Johnson Controls Unitary Products
Page 19
6-13/16
LEFT
32-11/16
6-13/16
Return
Air
27-1/2
Supply
Air
246695-YTG-C-0708
6-13/16
24
21
21-3/16
19-3/16
17-3/16
7-1/8
14-23/32
16-3/8
18-1/16
19-5/8
18
Bottom
Condensate
Drain
63-1/2
FRONT

FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)

Bottom
Power, Control and
Convenience Outlet
Wiring Entries
Dot
Plugs
Bottom
Gas Supply Entry
18-1/4
12-5/16
Return
Air
28-1/4
Supply
Air
18-1/4
18-1/16
2-31/32
5-5/32
28-1/4
31-11/16

FIGURE 9 - SIDEFLOW DUCT DIMENSIONS

Johnson Controls Unitary Products 19
Page 20
246695-YTG-C-0708

FIGURE 10 - DOWNFLOW ECONOMIZER HOOD DETAIL

TABLE 19: ECONOMIZER USAGE

Application Description Model
Bottom Return Downflow economizer with barometric relief 2EE04705424
Side Return Horizontal economizer without barometric relief
ERV or End Return Slab Economizer, 50” tall cabinet
1 Barometric relief must be ordered separately and installed in duct work. 2 Barometric relief or fresh air hood not included. Must be ordered separately.
2EE04705524 2EE04705224
1
2
2EE04705424
Fresh Air Hood
2EE04705424
Fresh Air Damper
2EE04705424
Return Air Damper
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood

FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER

20 Johnson Controls Unitary Products
Page 21
246695-YTG-C-0708
2EE04705424
Fresh Air Hood
2EE04705424
Fresh Air Damper
2EE04705424
Return Air Damper
2PE047032XX Power Exhaust
2EE04705424
Barometric Relief Damper

FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST

2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705424
Barometric Relief Hood
2EE04705524
Fresh Air Hood

FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST

Johnson Controls Unitary Products 21
Page 22
246695-YTG-C-0708
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper

FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST

2EE04705X24
Slab Economizer
1EH0409 Barometric
Relief Hood
1EH0409
Fresh Air Hood
Field Installed
Duct Work
1EH0409
Barometric Relief Hood
1EH0409
Barometric Relief Damper
2PE047032XX Power Exhaust

FIGURE 15 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST

22 Johnson Controls Unitary Products
Page 23
246695-YTG-C-0708

FIGURE 16 - COOLING UNIT WITH GAS HEAT WIRING 230 V. DIAGRAM

Johnson Controls Unitary Products 23
Page 24
246695-YTG-C-0708

FIGURE 17 - COOLING UNIT W/WO ELECTRIC HEAT WIRING DIAGRAM

24 Johnson Controls Unitary Products
Page 25
246695-YTG-C-0708

FIGURE 18 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 & 50 HZ DIAGRAM

Johnson Controls Unitary Products 25
Page 26
246695-YTG-C-0708

MECHANICAL SPECIFICATIONS

SINGLE PACKAGE AIR COOLED GAS/ELECTRIC UNITS FOR 12.5 NOMINAL TONS

PREDATOR® MAGNUM - DJ 150

11.35 EER

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® Predator® Magnum units are convertible single packages with a common footprint cabinet and common roof curb for all 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial appli­cations and can be easily installed on a roof curb, slab, or frame. All Predator on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent Predator num Economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Preda-
®
Magnum units are available in the following
tor configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as fac­tory-installed options or field-installed accessories.
®
units are self-contai n ed and assembled
®
Mag-

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, Gas/Elec), designed for outdoor installation. Units shall have a minimum EER of 11.35. They shall have built in field con­vertible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with fac­tory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-22 refriger­ant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and ARI test proce­dures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with 1/2” thick insulation coated on the airside. Aluminum foil faced insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be fur­nished and be accessible through hinged access door. Fan performance measuring ports shall be provided on the out­side of the cabinet to allow accurate air measurements of
evaporator fan performance without removing panels or cre­ating bypass of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Con­densate connection shall be a minimum of ¾” I.D. female and be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with for­ward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out design.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically bal­anced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.

REFRIGERANT COMPONENTS

Compressors: a. Shall be scroll type, direct drive, internally protected with
internal high-pressure relief and over temperature pro­tection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit name­plate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils
:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
26 Johnson Controls Unitary Products
Page 27
246695-YTG-C-0708
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Independent fixed-orifice or thermally operated expan-
sion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servi ci n g or troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments. Unit Controls a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resetable circuit breaker on
the 24-volt transformer side. b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor:
(1) loss-of-charge/Low-pressure switch,
:
ing temperature of 40 °F . Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be pro­vided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches. b. Induced draft pressure sensor. c. Flame roll out switch (manual reset). d. Flame proving controls. Unit shall have two independent
stages of capacity (60% 1
st
stage, 100% 2nd stage).

ELECTRIC HEATING SECTION (IF EQUIPPED)

An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two stages of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heat­ing element system from operating at an excessive tempera­ture. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
(2) high-pressure switch,
(3) freeze-protection thermostat, evaporator coil. c. If any of the above safety devices trip, a LED (light-emit-
ting diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped. d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection. e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up. f. Unit control board shall have on-board diagnostics and
fault code display. g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 °F. h. Control board shall monitor each refrigerant safety
switch independently. i. Control board shall retain last 5 fault codes in non vola-
tile memory, which will not be lost in the event of a power
loss.

GAS HEATING SECTION (IF EQUIPPED)

Heat exchanger and exhaust system shall be constructed of aluminized steel or optional stainless steel. Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel (or optional 304 stainless steel) for corrosion resistance and allowing minimum mixed air enter-

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125 °F out­door temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 °F outdoor tempera­ture. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor – 5 Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years, Part s – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO­MIZER – Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring­return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti­ometer shall be provided to adjust the outdoor and return air damper assembly to take in outdoor air to meet the minimum ventilation requirement of the conditioned
Johnson Controls Unitary Products 27
Page 28
space during normal operation. During economizer oper­ation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 °F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy con­trol that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief or power exhaust.
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and posi­tioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of
0.5 IWG . A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventila­tion requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi­tions – regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high­pressure drop across the filters.
BREAKER – An HACR breaker can be factory installed on the gas heat units or cooling units with electric heater.
DISCONNECT SWITCH - A disconnect can be factory installed on cooling only units, sized for the largest elec­tric heat available.
ELECTRIC HEAT - The electric heaters range from 18 kW to 54 kW and are available in all the voltage options of the base units.
STAINLESS STEEL HEAT EXCHANGER – For applica- tions in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.
STAINLESS STEEL DRAIN PAN - Provides years of trouble free operation in corrosive environments.
SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air com­partments.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL­ABLE
ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.

ADDITIONAL FACTORY INSTALLED OPTIONS

ALTERNATE INDOOR BLOWER MOTOR – For appli- cations with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.
CONVENIENCE OUTLET (POWERED/NON-POW- ERED) – Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.
PHASE MONITOR - Designed to prevent damage in out­of-phase condition.
COIL GUARD - Designed to prevent condenser coil damage.
BAS CONTROLS - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.
Subject to change without notice. Printed in U.S.A. 246695-YTG-C-0708 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 246695-YTG-B-0606
BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Sideflow) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.
PROPANE CONVERSION KIT – Contains new orifices and gas valve springs to convert from natural to L.P. gas.
–60 °F GAS HEAT KIT – Provides an electric heat kit for the gas compartment for use in extreme low ambient conditions.
ECONOMIZER (Downflow and Sideflow)
POWER EXHAUST – (Unit mount – Downflow, Duct mount – Sideflow)
DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.
Johnson Controls Unitary Products