MODEL UT750
Digital Indicating Controller
(with Custom Computation)
GS 05D01B02-01E
■ General
Model UT750 Digital Indicating Controller is an intelligent,
micro-processor based digital indicating controller with
powerful control capability, custom computation function
and the user-friendly large numerical display. The UT750
features many functions which are necessary for various
control application as standard, and all of these functions
such as control function, control computation function,
signal computation function, etc. can be configured by using
the keys on the front panel. The instrument specifies thirteen
types of control strategies built in and also the overshoot
suppressing function "SUPER" and a hunting suppressing
function "SUPER 2" as well as an auto-tuning as standard.
■ Main Features
• Extra-large digital display allows the indicated values to be
read even from a long distance. LEDs of 20 mm height are
used for the process variable display. This is a five-digit
display for higher resolution.
• User-friendly full dot LCD display. Not only the target
setpoint and other control related parameters but also a
deviation trend record or a deviation analogue bar can be
displayed.
• Thirteen types of control function, including single-loop
control, cascade control, loop control with PV autoselector, and custom computation control, enabling the
operator to start control operation immediately after simply
entering the settings.
• Custom Computation function, which allows users’ own
configuration for signals, enable them to realize such
functions as complicated computation for input compensation or sequence logic.
( “Custom Computation Building Tool <model name:
LL200> is necessary to use this function.)
• Universal input and output enable users to set or change
freely the type of measured inputs (thermocouple, RTD, or
DCV), measurement input range, type of control output (4
to 20mA current, voltage pulse, or relay contact), etc. from
the front panel.
• Equipped with seven contact inputs and outputs each,
which are further expandable up to 23 inputs and outputs
each by adding contact I/O signal expansion modules.
• Various communication function are provided.
Communication is possible with personal computer,
programable logic controller, and other controllers.
■ Functional Specifications
● Control Functions
UT mode
The following types of basic control structure can be set as
the UT mode by the user.
Single-loop Control (UT mode 1):
The most simple and basic control function.
UT750
UT750E
“E” indicates with the
model with expanded
functions.
Cascade primary-loop control (UT mode 2):
Output tracking function and cascade control
logic are provided. Suitable for the primaryloop cascade control.
Cascade secondary-loop control (UT mode 3):
Setpoint output and cascade control logic are
provided. Suitable for the secondary-loop
cascade control.
Cascade control (UT mode 4):
Dual control function for cascade control is
available in a single instrument.
Loop control for back up (UT mode 5):
Output tracking function is provided to backup another control instrument. The switching
between its control output and the control
output of the instrument to be backed-up can
be carried out by external contact.
Loop control with PV switching (UT mode 6):
Two measured inputs are switched for control
depending on the status of contact input or
measured input.
Loop control with PV auto-selector (UT mode 7):
Two measured inputs are automatically
selected for control with a high, low, average,
or temperature-difference value selector.
Dual-loop control (UT mode 11):
Dual control function is available in a single
instrument to control two loop.
Temperature and Humidity control (UT mode 12):
Temperature and Relative Humidity control is
available in a single instrument.
Cascade control with two universal inputs (UT mode 13):
Cascade control with using two universal
measured inputs.
Loop control with PV switching and two universal inputs
(UT mode 14):
Loop control with PV switching and two
universal inputs available as measured inputs.
Loop control with PV auto-selector and two universal
inputs (UT mode 15):
Process variable for loop control is automatically selected from two or three measured
inputs by an internal selector, with using two
universal inputs and an auxiliary analogue
input. When two universal inputs are
configured as measured input, auxiliary
analog input can be used for a remote setting
input.
Custom computation control (UT mode 21):
Can be provided by the user using the optional
LL200 custom computation building tool.
● Control Computation Functions
In each UT mode, the following control computation
functions can be selected.
Continuous PID control, Time-proportional
PID control, Position proportional PID
control(UT750-1 ■ position-proportional type
only), Relay ON/OFF control, Heating/
Cooling control.
Target setpoint and PID parameter:
Maximum eight sets of target setpoint and PID
parameters can be set and stored in a instrument. For Cascade control and Dual Loop
control type, eight sets for each main and
slave are available.
Zone PID selection:
Sets of PID parameters can be selected
according to PV zone. Maximum seven zones
can be set for selection.
Auto-tuning:
Available as standard.
Possible to activate auto-tuning for both loops
of Cascade control, Dual-loop control, and
Temperature and humidity control.
“SUPER” function:
Overshoots generated by abrupt changes in the
target setpoint or by disturbances can be
suppressed.
“SUPER 2” function:
The function stabilizes the state of control that
is unstable due to hunting, etc. without
requiring any change in PID constants, when
the load and/or gain varies greatly, or when
there is a difference between the characteristics of temperature zones.
Preset output function:
When the instrument is in STOP mode,
measured input is burnout, or abnormality is
found in an input circuit, users’
preconfigurable preset value is output as a
control output.
Control cycle time:
Each cycle time can be selected under the
following coditions
50ms:Available when model code is "UT750-00",
UT mode is set to Single-loop control, and
the following function is not used. “SUPER” function, “SUPER 2” function,
Heating/Cooling control, measured input
computations, setpoint rate of change
limiter, output rate of change limiter,
deviation alarm, sensor grounding alarm,
fault-diagnosis alarm, FAIL output.
100ms:Available when model code is UT750-0 ■,
UT750-1 ■, (Without Cascade control)
200ms:Available when model code is UT750-5 ■
and the amount of computation module of
Custom computation function is less than
30.
500ms:Available when the amount of computation
module of Custom computation function is
more than 30.
(Set value on shipped from the factory: 200ms)
Operation Mode Switching
(Note: Communication enables all the
following mode switching to be excuted.)
AUTO/MANUAL switching:
Bump-less switching is available. Switching
between AUTO and MANUAL mode can be
realized by using front key or by external
contact, and external contact switching has
priority to a front key operation.
When UT mode is set to “Cascade secondaryloop control” or “Cascade control”, switching
can not be realized by external contact.
RUN/STOP switching:
Switching of RUN/STOP can be realized by
external contact. Bump-less switching from
STOP to RUN is available. In RUN mode,
control computation is activated. In STOP
mode, control computation is ceased and
preset output value is output as a control
output, while other functions are operated
normally.
REMOTE/LOCAL switching:
Switching between local setpoints and remote
setpoint can be realized by instrument
operation or external contact, and external
contact switching is prior to instrument
operation. For remote to local switching,
either with bump-less tracking ( to make the
local setpoint value equivalent to the Remote
setpoint value upon switching.) or without
tracking(to switch directly to local setpoint in
the instrument) can be specified by the
parameter.
CASCADE/AUTO/MANUAL switching:
Switching can be realized by instrument
operation or external contact, and external
contact switching is prior to instrument
operation. Available when UT mode is set to
“Cascade secondary-loop control” or
“Cascade control” .
Output tracking ON/OFF switching:
Available when UT mode is set to “Cascade
primary-loop control” or “ Loop control for
back-up”. Switching between External
tracking signal and internal control output can
be realized by external contact.
Control Parameter Setting Range
Proportional band: 0.1 to 999.9%
0.0 to 999.9% (for heating/cooling control.),
0.0% available for ON/OFF control
Integral time: 1 to 6,000 s, or OFF (for Manual reset)
Derivative time: 1 to 6,000 s, or OFF
ON/OFF control hysteresis:
0.0 to 100.0% of measured input range width
Preset output value: -5.0 to 105.0% of Output range
Setting range: -5.0 to 105.0% for both high
and low limits.
However, “low limit setpoint < high limit
setpoint” must be satisfied.
When heating/cooling PID control, upper
limiter for heating and upper limiter for
cooling.
Shutdown function(For 4 to 20 mA control output only):
In manual mode operation, up to approx. 0mA
can be output.
Rate of change limiter for output:
OFF, or 0.1 to 100.0%/s
Dead band of heating/cooling control:
-100.0 to 50.0% of Output value
Dead band of position-proportional control:
1.0 to 10.0 % of Output value
● Configuration of Input/Output Signal
Measured Input Computations
Bias(-100.0 to 100.0% of measuring input range), First lag
filter(OFF, 1 to 120 s), Square root extraction(for voltage
input only, Input low cut 0.0 to 5.0%), 10-segment linearizer
function, 10-segment bias function, relative humidity
calculation by wet/dry bulb(for Temperature & Humidity
control type)
Auxiliary Input Computations
Applicable for remote setting input only.
Bias(-100.0 to 100.0%), First lag filter (OFF, 1 to 120s),
Square root extraction (Input low cut 0.0 to 5.0%),
Ratio multiplication (0.001 to 9.999)
Custom Computations
LL200 Building tool is necessary to use Custom computation
function.
Combining computation function modules allows such
functions as users’ own configuration of input/output signals,
operation mode switching via contact input, and status output
via contact output.
Computation function module:
Addition/subtraction/multiplication/division,
Processing absolute value/reciprocal,
Selecting maximum/minimum/average,
Keeping maximum/minimum value, Keeping
value, Rate of change limiter, Switch, Limiter,
Constant, AND, OR, Exclusive OR, NOT,
Latch, Comparison (=,<,>,,), Not
equivalent, Within range, AND(word),
OR(word), Shift word, Sum, Timer, Tensegment linearizer 1/2, Inverse ten-segment
linearizer 1/2, Curve linearizer 1/2, Ratio,
First order lag filter, Conversion to industrial
unit, Selection of PV from two inputs,
Temperature and humidity calculation, MV
selection1/2, Conversion of display value,
Parameter setting, Data display1/2, Special
contact output calculation, Assignment of
output terminals 1/2, etc.
PV high limit, PV low limit, Deviation high
limit, Deviation low limit, Deenergized on
deviation high limit, Deenergized on deviation
low limit, Deviation high and low limits, High
and low limits within deviation, Deenergized
on PV high limit, Deenergized on PV low
limit, SP high limit, SP low limit, Output high
limit, Output low limit.
Alarm setting range:
PV/SP alarm: -100 to 100 % of measured
input range
Deviation alarm: -100 to 100 % of measured
input range width
Output alarm: -5.0 to 105.0% of output value
Alarm hysteresis: 0.0 to 100.0 % of measured
input range width
Delay timer:
0.00 to 99.59 (minute, second)
An alarm is output when the delay timer
expires after the alarm setpoint is reached.
Setting for each alarm is possible.
Stand-by action:
Stand-by action can be set to make PV/
deviation alarm OFF during start-up or after
SP change unitl SP reaches the normal region.
Timer function (stabilization of control status notification
event) (Alarm 1 only):
The timer function sets alarm 1 output to ON/
OFF when preset time is elapsed after PV has
reached to the SP and its hysteresis band.
Activated again by RUN/STOP switching or
SP switching.
Other alarm actions:
Sensor grounding alarm: Detects sensor
deterioration and outputs an alarm.
Fault diagnostic alarm: Input burnout, A/D
conversion error, RJC error.
FAIL output: Abnormality in software, or
Abnormality in hardware.
Number of alarm settings: 4 points (for each loop)
Alarm output points: 4 points
Up to 4 points can be selected among PV,
deviation, SP, output sensor grounding, fault
diagnosis and FAIL alarms and output.
Timer function is available with alarm 1
output only.
Note: See the Hardware Specifications and the contents of
Contact Outputs described later.
● Display and Operation Functions
PV Display Unit
Either PV1 or PV2 can be displayed on 5 digit digital display
unit and switched one from the other.
Digit of display is 4 or 5 digit. For Thermocouple and RTD
input, Lower digit than decimal point can be turned off.
The display range is -19999 to 30000 and the display span is
30000 or less. [750.00 appearing in the product photograph
on page 1 cannot actually be displayed.]
Some data are displayed on LCD display unit. Each screen is
called “display”.
Four types of displays are provided. Operating display,
Operating parameter setting display, setup parameter setting
display, and SELECT display.
Each screen of LCD display unit
Operating display:
Necessary data for operation is displayed
according to UT mode. Such items as
Setpoint, Control output, Control output bargraph, deviation trend, and deviation analogue
bar-graph are displayed. Memorable time of
deviation trend is 120 s to 20 h.
Operating parameters setting display:
The Operating parameters, which are mainly
changed during operation, such as PID
constant, are displayed.
Setup parameter setting display:
The Setup parameters to configure the
functions of the instrument before starting
operation are displayed.
UT mode is set in this display.
ceased), CAS (Cascade operation)
Deviation indicating lamp:
䉱 Plus deviation , 䉲 Minus deviation, and
deviation in normal range
Deviation band for the display can be set.
LED display unit (for PV)
Display PV, and error code when
error is detected.
LCD display unit
Display setpoint (SP), output value,
deviation bargraph, deviation value,
deviation trend, valve opening and
setting item/value of parameters.
Operation keys
Increase/Decrease the setting data (䉭, 䉮)
Switching the display (DISP)
Select parameter/Enter the setting data (SET/ENT)
A/M mode switching of Loop 1 (A/M).
Examples of Communication System Configuration Diagram
(1) Computer link communication/
MODBUS communication
Personal computer
PV
PV
PV2
AL
123
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
1
1
2
2
3
3
REM
REM
4
4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
123
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
UT750 Digital indicating controller
(3) Coordinated operation
PV
PV2
AL
12
UP750 Program controller
3
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
or UT750 Digital indicating controller
PV
PV
PV2
AL
123
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
1
1
2
2
3
3
REM
REM
4
4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
123
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
UT750 Digital indicating controller
(2) Ladder communication
MELSEC-A
PV
PV2
AL
1
2
3
REM
4
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
UT750 Digital indicating controller
(4) Digital I/O Expansion Module (µ-BUS communication)
䉭, 䉮 key: Increases/decreases the value of Setpoints or
other parameters which appear on LCD display.
DISP key: Switch data to be showed on LCD display
SET/ENT key: Set/change the setting value, switch
contents to be showed on LCD display, switch
operation mode other than AUTO/MAN.
A/M key:Switch operation mode (AUTO/MAN)
Security Function
Key lock from parameter setting and operation
can be inhibited by a password.
● Communication Functions
( For UT750-■1 only )
The instrument has two communication port and five types
of communication protocols, and allows the simultaneous
communication with two different instruments.
The instruments to communicate are a personal computer, a
programmable logic controller, and other UT750/UP750.
Input type
Unspecified (When shipped from the factory)
Thermocouple
0.4 to 2V(40)
1 to 5V(41)
0 to 2V(50)
0 to 10V(51)
0.0 to 1.2 V
mV1(55)
mV2(56)
OFF
Instrument
range (°C)
Set the data item PV input type “IN 1” to the OFF option to leave the PV input type undefined.
-270.0 to 1370.0°C
-270.0 to 1000.0°C
-200.0 to 500.0°C
-200.0 to 1200.0°C
-270.0 to 400.0°C
0.0 to 400.0°C
0.0 to 1800.0°C
0.0 to 1700.0°C
0.0 to 1700.0°C
-200.0 to 1300.0°C
-270.0 to 1000.0°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 2300.0°C
0.0 to 1390.0°C
0.0 to 1900.0°C
0.0 to 2000.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
-200.0 to 850.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.000 to 1.200 V
-10.00 to 20.00 mV
0.0 to 100.0 mV
Communication Protocol
Computer link communication:
Ladder communication:
Coordinated operation protocol:
MODBUS communication:
Digital input/output expansion (µ-Bus):
Instrument
-450.0 to 2500.0°F
-450.0 to 2300.0°F
-200.0 to 1000.0°F
-300.0 to 2300.0°F
-450.0 to 750.0°F
-200.0 to 750.0°F
-300.0 to 2400.0°F
-450.0 to 1800.0°F
-300.0 to 1600.0°F
-300.0 to 750.0°F
-200.0 to 1000.0°F
32.0 to 2500.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
-300.0 to 1560.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
Display range
-19999 to 30000
Display span 30000 or
less (Decimal point
position changeable)
Communication protocol with a personal
computer.
Communication protocol with the ladder
program on some programmable logic
controllers.
Protocol to realize Coordinated operation
with other GREEN SERIES controller.
UT750 can be configurated as either master
or slave unit.
Communication protocol with a personal
computer or PLC.
Protocol to connect Digital I/O expansion
module to increase the number of Discrete
Input and Output.
range (°F)
32 to 3300°F
32 to 3100°F
32 to 3100°F
32 to 4200°F
32 to 3400°F
32 to 3600°F
Instrument accuracy
±0.1% ±1 digit of instrument range at 0°C or more
±0.2% ±1 digit of instrument range at less than 0°C
• However, ±2% ±1 digit of instrument range for type K
at temperatures less than -200°C.
However, ±1% ± 1 digit of instrument range for type T
•
at temperatures less than -200°C.
±0.15% ±1 digit of instrument range at 400°C or more
±5% ±1 digit of instrument range at less than 400°C
±0.15% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range
±0.25% ±1 digit of instrument range for temperature at less than 0°C
±0.1% ±1 digit of instrument range at 0°C or more
±0.2% ±1 digit of instrument range at less than 0°C
• However, ±1.5% ±1 digit of instrument range for
type E at temperature less than -200°C.
±0.2% ±1 digit of instrument range
±0.1% ± 1 digit of instrument range
±0.5% ±1 digit of instrument range at 800°C or more
Accuracy not guaranteed for temperature less than
800°C
±0.2% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range (Note 1) (Note 2)
±0.2% ± 1 digit of instrument range (Note 1)
±0.1% ± 1 digit of instrument range (Note 1) (Note 2)
±0.2% ± 1 digit of instrument range (Note 1)
±0.1% ± 1 digit of instrument range
*1
Numbers in ( ) are the measurement input range codes that
apply when the communication function is used.
*1:Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60Hz power frequency)
Note 1: The accuracy is ±0.3°C of instrument range ±1 digit for a temperature range from 0 to 100°C
Note 2: The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from –100 to 200°C.
Note 3: 0.0 to 1.2 V DC range is for universal input 2 (41, 42 and 43 terminals) only.