Yokogawa UT550 Data sheet

<<Contents>> <<Index>>
General Specifications
MODEL UT550 Digital Indicating Controller
GS 05D01C02-01E
General
Model UT550 Digital Indicating Controller is an intelligent, micro-processor based digital indicating controller with powerful control capability and the user-friendly large numerical display. The UT550 features as standard many functions which are necessary for various control applica­tions, and all of these functions such as control function, control computation function, signal computation function, etc. can be configured by using the keys on the front panel. The instrument has eight types of control strategies and also an overshoot suppressing function "SUPER" and a hunting suppressing function "SUPER 2" as well as an auto-tuning function built in as standard. It is suitable for a diverse range of applications, with position-proportional control model and heating/cooling control model also available.
Main Features
• Extra-large digital display allows the indicated values to be read even from a long distance. LEDs of 20 mm height are used for the process variable display. This is a five-digit display for higher resolution.
• Eight types of control function, including single-loop control, cascade control, loop control with PV auto­selector, and loop control with PV-hold function, enabling the operator to start control operation immediately after simply entering the settings.
• Parameters can be easily set using a personal computer. ("Parameter setting tool (model LL100)" sold separately is required.)
• Universal input and output enables users to set or change freely the type of PV inputs, PV input range, type of control output, etc. from the front panel.
• In addition to standard type (universal output), the position-proportional type (relay output) or the heating/ cooling type (universal output) can be specified.
• Contact inputs (up to 8 points) and contact outputs (up to 8 points) can be employed and functions can be assigned to each contact. (The maximum number of points varies the suffix code.)
Note: See Hardware Specifications and Contact Outputs
• Various communication function are provided.
described later.
Communication is possible with personal computer, programmable logic controller, and other controllers.
Functional Specifications
Control Functions
UT Mode
The following types of basic control structure can be set as the UT mode by the user.
Single-loop control (UT mode 1):
The most simple and basic control function.
UT550
UT550E
“E” indicates the model with expanded functions.
Cascade primary-loop control (UT mode 2):
Output tracking function and cascade control logic are provided. Suitable for cascade primary-loop control.
Cascade secondary-loop control (UT mode 3):
Setpoint output and cascade control logic are provided. Suitable for cascade secondary-loop control.
Cascade control (UT mode 4):
Dual control function for cascade control is available in a single instrument.
Loop control for back-up (UT mode 5):
Output tracking function is provided to back up another control instrument. The local and remote control outputs are switched by a contact input.
Loop control with PV switching (UT mode 6):
Two PV inputs are switched for control depending on the status of contact input or PV input.
Loop control with PV auto-selector (UT mode 7):
Two PV inputs are automatically selected for control with a high, low, average, or tempera­ture-difference value selector.
Loop control with PV-hold function (UT mode 8):
This control holds a PV input and a control output if an external sensor is switched.
Control Computation Functions
In each UT mode, the following control computation functions can be selected:
Continuous PID control, Time-proportional PID control, Relay ON/OFF control, Position­proportional PID control (for UT550-1, UT550-4)and Heating/Cooling control (for UT550-2).
Target setpoint and PID parameters:
Maximum eight sets of target setpoint and PID parameters can be set. These eight sets can be set for both the main and slave loops in cascade control.
GS 05D01C02-01E
© Copyright Feb. 2000 (YK)
<<Contents>> <<Index>>
2
Zone PID selection:
Dividing PV input range into maximum 7 zones by maximum 6 reference points, PID parameter set switching in up to 7 PV input zones.
Auto-tuning:
Available as standard. Possible to activate auto-tuning for both main and slave loops for cascade control.
"SUPER" function:
Overshoots generated by abrupt changes in the target setpoint or by disturbances can be suppressed.
"SUPER 2" function:
This function stabilizes the state of control that is unstable due to hunting, etc. without requiring any change in PID constants, when the load and/or gain varies greatly, or when there is a difference between the characteris­tics of temperature zones.
Preset output function:
When the instrument is in STOP mode, PV input is burnt-out, or an abnormality is found in an input circuit, a preset value is output as a control output.
Sampling period
Each sampling period can be selected under the following conditions:
50 ms: Available for model code UT550-00, when
UT mode is set to Single-loop control and the following functions are not used: "SUPER" function, "SUPER 2" function, heating/cooling control, PV input computa­tion, setpoint rate-of-change limiter, MV output rate-of-change limiter, deviation alarm, sensor grounding alarm, fault diagnosis alarm, and FAIL output.
100 ms: Available when UT mode is not cascade
control. 200 ms: Available when UT mode is cascade control. (Set value when shipped from the factory: 200 ms) 500 ms: Always available.
Operation Mode Switching
(Note: Communication enables all the following
mode switching to be executed.)
AUTO/MANUAL switching:
Bumpless switching between automatic operation mode and manual control mode is available by using the front keys or contact input. The contact input has priority over front key input or switching by communica­tion. The contact input is invalid for Cascade secondary-loop control or Cascade control.
RUN/STOP switching:
Switching by contact input (bumpless for switching from STOP to RUN). The contact input has priority over switching by communi­cation. In RUN mode, control computation is activated. In STOP mode, control computa­tion ceases and a preset value is output as a control output while other functions operate normally.
REMOTE/LOCAL switching:
Switching between remote setpoint and local setpoint by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. For remote to local switch­ing, either bumpless tracking (employing the remote setpoint on switching as the local setpoint) or without tracking (directly switching the local setpoint) can be specified.
CASCADE/AUTO/MANUAL switching:
Switching by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. Valid for Cascade second­ary-loop control or Cascade control.
Output tracking ON/OFF switching:
Provided for Cascade primary-loop control or Loop control for backup. External tracking signal and internal control output are switched by the contact input. The contact input has priority over the switching by communication.
Control Parameters Setting Range
Proportional band: 0.1 to 999.9%
0.0 to 999.9% (for heating/cooling PID
control), 0.0% available for ON/OFF control Integral time: 1 to 6,000 s, or OFF (for Manual reset) Derivative time: 1 to 6,000 s, or OFF ON/OFF control hysteresis: 0.0 to 100.0% of PV input
range span Preset output: -5.0 to 105.0% (0 mA or less cannot be
output) Output limiter:
Setting range: -5.0 to 105.0% for both high
and low limits
However, "low limit setpoint < high limit
setpoint" must be satisfied.
In case of heating/cooling PID control, upper
limiter for heating and upper limiter for
cooling. Shutdown function:
When manual control is carried out with 4 to
20 mA output, control output can be output
down to about 0 mA (shutdown is specified
for -5.0% or less). Rate-of-change limiter for output:
OFF or 0.1 to 100.0%/s Deadband for heating/cooling control:
-100.0 to 50.0% for output value
Deadband for position-proportional control:
1.0 to 10.0% for output
Configuration of Input/Output Signal
PV Input Computations
Input processing, Square root extraction (voltage input only, Input low cut 0.0 to 5.0%), Ten-segment linearizer function, Ten-segment bias, Bias addition (-100.0 to 100.0%), and First order lag filter (OFF, time constant 1 to 120 s)
Auxiliary Input Computations
(Applied to remote setting input only)
Input processing, Square root extraction (Input low cut 0.0 to
5.0%), Bias addition (-100.0 to 100.0%), Ratio multiplication (0.001 to 9.999), First order lag filter (OFF, time constant 1 to 120 s)
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E 2nd Edition Sept.18, 2000-00
<<Contents>> <<Index>>
3
Alarm Functions
Alarm types:
PV high limit, PV low limit, Deviation high limit, Deviation low limit, Deenergized on deviation high limit, Deenergized on deviation low limit, Deviation high and low limits, High and low limits within deviation, Deenergized on PV high limit, Deenergized on PV low limit, SP high limit, SP low limit, Output high limit, Output low limit.
Alarm setting range:
PV/SP alarm: -100 to 100% of PV input range Deviation alarm: -100 to 100% of PV input range span Output alarm: -5.0 to 105.0% of output value Alarm hysteresis: 0.0 to 100.0% of PV input range span
Delay timer:
0.00 to 99.59 (minute, second) An alarm is output when the delay timer expires after the alarm setpoint is reached. Setting for each alarm is possible.
Stand-by action:
Stand-by action can be set to make PV/ deviation alarm OFF during start-up or after SP change until SP reaches the normal region.
Timer function (stabilization of control status notification
event) (Alarm 1 only): This function sets the alarm 1 output to ON when a preset time (timer setting) elapses after a PV has reached the control target setpoint hysteresis band to notify that control has reached its stabilized status. Restarted in RUN/STOP or SP switching.
Other alarm actions:
Sensor grounding alarm: Detects sensor deterioration and outputs an alarm. Fault-diagnosis alarm: For input burnout, A/D conversion error, or thermocouple reference junction compensation error. FAIL output: Abnormality in software or hardware.
Number of alarm settings: 8 (maximum)
The alarm status can be read via communica­tion in addition to output as the above alarm output.
Alarm output points (see also the item "Contact Outputs")
• Number of contact (relay) outputs: 3 (standard) or 4 (if a control output relay is used for the alarm 4 output relay.)
• Number of contact (transistor open collector) outputs: 4 (when optional function code is specified as 1 or 3)
From the above, up to 8 point outputs can be obtained (except for cascade control). Any of PV alarm, deviation alarm, SP alarm, output alarm, Fault-diagnosis alarm, sensor grounding alarm and FAIL output can be assigned to contacts for the above number of outputs. However, the timer delay alarm can be assigned to the alarm 1 output only. Also, the alarm 4 only can be assigned to the control output relay (if a relay is not used for control output).
Display and Operation Functions
PV Display
PV is displayed in the 5-digit display. PV1 or PV2 is displayed by switching them in cascade control. The number of display digits is 4 or 5. For thermocouple or RTD, data below the decimal point can be set not to display. The display range is -19999 to 30000 and the display span is 30000 or less. [550.00 appearing in the product photograph on page 1 cannot actually be displayed.]
Setpoint Display
A parameter name is displayed in the 3-digit display and data in the 5-digit display. There are four kinds of displays : operating display, operating parameter setting display, setup parameter setting display and SELECT display.
Operating display:
Data necessary for operations, such as setpoint or control output, are displayed depending on the UT mode.
Operating parameters setting display:
The Operating parameters, which are mainly changed during operations, such as PID constant, are displayed.
Setup parameters setting display:
The Setup parameters to configure the functions of the instrument before starting operation are displayed. UT mode is to be set in this display.
SELECT display:
Up to five displays which are frequently accessed can be selected from the Operating parameters setting display and Setup param­eters setting display to be displayed in the SELECT display.
Status Indicator Lamps
Alarm indicator lamps:
Four lamps, AL1, AL2, AL3, and AL4
Status indicator lamps:
REM (remote operation), MAN (manual mode operation), CAS (cascade operation), and LP2 (cascade secondary-loop control)
Deviation monitor:
Plus deviation, Minus deviation, and deviation in normal range
Operation Keys
, keys: Increase or decrease setpoints and other
parameters displayed in the setpoint display.
SET/ENT key: Used for setting or changing set data,
switching the displayed contents, and switching operation modes except for A/M.
A/M key: Operation mode switching (Auto/Manual)
Security Function
Key-lock by parameter setting and prohibiting operation by a password are available.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E 2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
4
Status indicator lamps
Deviation (,
, ) Cascade operation (CAS) and remote operation (REM) Manual operation (MAN) Lit for secondary parameter indication (LP2)
Light-loader interface
Parameters are set via communication from a personal computer.
Operation keys
Increase/decrease of the setting data (, ) Screen switching/parameter selection/entry of set data (SET/ENT) Auto/manual operation mode switching (A/M)
Communication Functions
(For optional function code 1 or 2 only)
This controller has four types of communication protocol with one communication interface. Communication is possible with personal computer, programmable logic controller, and other controllers.
Communication Protocol
Computer link communication:
Communication protocol with a personal
Ladder communication:
Coordinated operation:
computer
Communication protocol with the ladder program on some programmable logic controllers.
Protocol for coordinated operation with more than one GREEN SERIES controller. The UT550 controller can be connected as a master or slave station.
Measured value (PV) display
Displays PV and error codes when errors are detected.
Setpoint display
Displays setpoints (SP), output values, valve opening, or parameters.
Alarm indicator lamps
Displays alarms (AL1, AL2, AL3, or AL4).
MODBUS communication:
Communication protocol with a personal computer, or PLC.
RS-485 Communication Interface
The RS-485 communication interface (conforms to EIA RS485) can be used for personal computer link, MODBUS communication, ladder communication, or for coordinated operation.
Maximum number of connectable controllers:
31 GREEN SERIES controllers Maximum communication distance: 1200 m Communication method:
Two-wire half-duplex or four-wire half-
duplex, start-stop synchronization, and non-
procedural Baud rate:
600, 1200, 2400, 4800, or 9600 bps
Examples of Communication System Configuration Diagram
(1) Personal computer link communication/ MODBUS communication
Personal computer
PV
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
UT550, UT520 Digital indicating controller
(3) Coordinated operation
PV
PV2
UP750, UP550 Program controller
AL
REM MAN1 MAN2 STP CAS
or
A/M
DISP
SET/ENT
UT750, UT550, UT520 Digital indicating controller
PV
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
UT550, UT520 Digital indicating controller
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
(2) Ladder communication
MELSEC-A
Programmable logic controllor
PV
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
DISP
SET/ENT
UT550, UT520 Digital indicating controller
GS 05D01C02-01E 2nd Edition Sept. 18, 2000-00
PV
PV2
AL
1
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
<<Contents>> <<Index>>
5
Hardware Specifications
Input/Output Signal Specifications
PV Input Signal
Number of input points: 1 Input type, instrument input range, and measurement
Sampling period: 50, 100, 200, or 500 ms (selectable) Burnout detection:
Input bias current: 0.05 µA (for TC or RTD b-terminal) Measurement current(RTD): About 0.13 mA Input resistance: 1 M or more for TC or mV input
Unspecified (When shipped from the factory) Thermocouple
RTD
Standard signal
DC voltage
accuracy: The type of input and instrument input range can be specified from the instrument input range codes shown in the table below.
Activated for thermocouple (TC) input, RTD input, or standard signal of 0.4 to 2 V DC or 1 to 5 V DC. Possible to specify a travel of upscale, downscale, or off. For standard signal input, set to burn out at
0.1 V or less.
About 1 M for DC voltage input
Input Type
K
J T
B
S R N
E L (DIN) U (DIN)
W (DIN) Platinel 2 PR20-40
W97Re3-W75Re25 JPt100
Pt100
0.4 to 2V 1 to 5V 0 to 2V 0 to 10V
-10 to 20mV 0 to100mV
Instrument Input
Range Code
OFF
1 2 3 4 5 6
7
8 9
10
11 12 13 14 15 16
17
18 30 31 35 36 37 40 41 50 51 55 56
Set the data item PV input type IN 1 to the OFF option to leave the PV input type undefined.
-10.00 to 20.00 mV
Instrument Input
Range (°C)
-270.0 to 1370.0°C
-270.0 to 1000.0°C
-200.0 to 500.0°C
-200.0 to 1200.0°C
-270.0 to 400.0°C
0.0 to 400.0°C
0.0 to 1800.0°C
0.0 to 1700.0°C
0.0 to 1700.0°C
-200.0 to 1300.0°C
-270.0 to 1000.0°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 2300.0°C
0.0 to 1390.0°C
0.0 to 1900.0°C
0.0 to 2000.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
-200.0 to 850.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.0 to 100.0 mV
Allowable signal source resistance:
250 or less for TC or mV input
Signal source resistance effect
0.1 µV/ or less
2 k or less for DC voltage input
Signal source resistance effect About 0.01%/100 Allowable wiring resistance (for RTD input):
Maximum 150 /wire (Conductor resistance
between three wires must be equal.)
However, it must be 10 /wire for a
maximum range of -150.0 to 150.0°C.
Effect of wiring resistance: ±0.1°C/10Ω Allowable input voltage:
±10 V DC for TC/mV/RTD input
±20 V DC for DC voltage input
Noise rejection ratio:
Normal mode 40 dB (50/60 Hz) or more
Common mode 120 dB (50/60 Hz) or more Reference junction compensation error:
±1.0°C (15 to 35°C), ±1.5°C (0 to 15°C and
35 to 50°C) Applicable standards:
JIS, IEC, and DIN (ITS-90) for TC and RTD
Instrument Input
Range (°F)
-450.0 to 2500.0°F
-450.0 to 2300.0°F
-200.0 to 1000.0°F
-300.0 to 2300.0°F
-450.0 to 750.0°F
-200.0 to 750.0°F 32 to 3300°F
32 to 3100°F 32 to 3100°F
-300.0 to 2400.0°F
-450.0 to 1800.0°F
-300.0 to 1600.0°F
-300.0 to 750.0°F
-200.0 to 1000.0°F
32 to 4200°F
32.0 to 2500.0°F 32 to 3400°F
32 to 3600°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
-300.0 to 1560.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
Display range
-19999 to 30000 Display span 30000 or less (Decimal point position changeable)
±0.1% ±1 digit of instrument range at 0°C or more ±0.2% ±1 digit of instrument range at less than 0°C
However, ±2% ±1 digit of instrument range for type K at temperatures less than -200°C. However, ±1% ± 1 digit of instrument range for type T
at temperatures less than -200°C.
±0.15% ±1 digit of instrument range at 400°C or more ±5% ±1 digit of instrument range at less than 400°C
±0.15% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range ±0.25% ±1 digit of instrument range for temperature at less than 0°C
±0.1% ±1 digit of instrument range at 0°C or more ±0.2% ±1 digit of instrument range at less than 0°C
However, ±1.5% ±1 digit of instrument range for type E at temperature less than -200°C.
±0.2% ±1 digit of instrument range ±0.1% ± 1 digit of instrument range
±0.5% ±1 digit of instrument range at 800°C or more
Accuracy not guaranteed for temperature less than 800°C
±0.2% ± 1 digit of instrument range ±0.1% ± 1 digit of instrument range (Note 1) (Note 2) ±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range (Note 1) (Note 2)
±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range
Note 1: The accuracy is ±0.3°C of instrument range ±1 digit for a temperature range from 0 to 100°C. Note 2: The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from -100 to 200°C. *1: Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60Hz power frequency)
Measurement Accuracy
*1
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
6
Auxiliary Analog Input Signal
(UT550-1, -2, or -4 only) Functions: Remote setting input, tracking input, cascade
control secondary loop PV input, etc.
Input type: Settable within the range of voltage input 0 to
2 V DC, 0 to 10 V DC, 0.4 to 2.0 V DC or
1 to 5 V DC. Number of inputs: 1 point Sampling period: 100, 200 or 500 ms
Auxiliary analog input sampling period is
linked with PV input sampling period.
(If PV input period is 50 ms , auxiliary analog
input period is 100 ms.) Input resistance: Approx. 1 M Input accuracy: ±0.3% ± 1 digit of input span for 0 to 2 V
DC input
±0.2% ± 1 digit of input span for 0 to 10 V
DC input
±0.375% ± 1 digit of input span for 0.4 to 2.0
V DC range
±0.3% ± 1 digit of input span for 1 to 5 V DC
range
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
Feedback Resistance Input Signal
(UT550-1 only) Valid for position proportional PID control.
Slidewire resistance:
Total resistance 100 to 2.5 k (with burnout detection of slidewire)
Measuring resolution ±0.1% of total resistance
24 V DC Loop Power Supply for Sensor
Supplies power to the 2-wire transmitter. The current signal is converted to a voltage signal by placing a resistor (arbitrary from 10 to 250 ) and is read by the PV input terminal.
21.6 to 28.0 V DC, maximum supply current about 30 mA (only for models with 24 V DC loop power supply for sensor).
24 V DC Power Supply Wiring to Two-wire Sensor
250
12
PV input
1 to 5 V DC signal
13
Loop power
43
44
supply
21.6 to
28.0 V DC
External resistor (Note)
Two-wire transmitter
4-20mADC
Note : Connecting a 250 resistor to the terminals is optional. Model : X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Retransmission Output
Any of the PV, target setpoint or control output is output. Or this can be used for 15 V DC loop power supply.
Number of output points: 1 or 2
Retransmission output 2 is available only when
relay is selected as the control output type. Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to 4
mA DC or 20 to 0 mA DC (0 mA or less
cannot be output)
Load resistance: 600 or less Output accuracy: ±0.1% of span (±5% for 1 mA or less)
Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/ 60Hz power frequency)
When using for 15 V DC loop power supply: Supply voltage 14.5 to 18.0 V DC, maximum supply current about 21 mA (with the protection circuit at field short-circuit).
Control Outputs
Select 1 or 2 points (UT550-2) from the following output types depending on model type and UT mode. Relay contact output for position proportional PID control (UT550-1 UT550-4).
Current output
Number of output points: 1 or 2 (for heating/cooling
type) (switchable to voltage pulse output)
Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to 4
mA DC or 20 to 0 mA DC
Load resistance: 600 or less Output accuracy:
±0.1% of span (±5% for 1 mA or less) Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/ 60Hz power frequency)
Voltage pulse output
Number of output points: 1 or 2 (for heating/cooling
control) (switchable to current output)
Output signal:
ON voltage-12 V DC or more (load resistance 600 or more) OFF voltage- 0.1 V DC or less
Resolution: 10 ms or 0.1% of output value, whichever is
greater
Relay contact output
Number of output points: 1 or 2 (for heating/cooling
control)
Output signal: At three terminals of NC, NO, and
Common
Contact rating: 250 V AC, 3 A or 30 V DC, 3 A
(resistance load)
Resolution: 10 ms or 0.1% of output value, whichever is
greater
Contact Inputs
Usage: Target setpoint switching, C/A/M mode
switching, REMOTE/LOCAL switching, RUN/STOP switching, or PV input switching
Number of input points:
Varies with optional codes (as shown below):
UT550-0: 2 points UT550-1: 8 points UT550-2: 3 points UT550-3: 7 points UT550-4: 3 points
Input type: Non-voltage contact input or transistor open
collector input Input contact rating: 12 V DC, 10 mA or more On/off detection:
For non-voltage contact input,
On .. contact resistance 1 k or less;
Off.. contact resistance 20 k or more
For transistor contact input,
On .. 2 V or less;
Off.. leak current 100 µA or less Minimum status detection hold time: PV input sampling
period ×3
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
7
Contact Outputs
Usage: Alarm output, FAIL output Number of output points:
Varies with optional codes (as shown below):
UT550-0: Relay output 3 points UT550-1: Relay output 3 points, transistor output 4
points
UT550-2: Relay output 3 points UT550-3: Relay output 3 points, transistor output 4
points
UT550-4: Relay output 3 points
However, when a relay is not used for control output, the relay for control output can be used for the alarm 4. For this reason, the number of relay output points can be
changed to 4 by adding to the above 3. Relay contact rating: 240 V AC, 1 A or 30 V DC, 1 A Transistor contact rating: 24 V DC, 50 mA
Display Specifications
Measured value (PV) display:
Data display: 3 digits + 5 digits, 7-segment red color
Status indicator lamps: LEDs
5-digit 7-segment red color LED display; height of letters 20 mm
LED display; height of letters 9.3 mm
Conformance to Safety and EMC Standards
Safety standard:
EMC standards:
Conforms to IEC1010-1: 1990 and EN61010­1: 1992 Certified for CSA1010 The overvoltage category of each input is CAT II (IEC1010-1) Certified for UL508 application
To the following EMC standards. During test, the controller continues to operate with the measurement accuracy within ±20% of the range: For EMI (emission), EN55011, Class A Group 1 For EMS (immunity), EN50082-2: 1995
Construction, Installation, and Wiring
Construction: Dust-proof and Drip-proof front panel
Material of the body: ABS resin and polycarbonate Case color: Black Weight: About1 kg or less External dimensions: 96W × 96H × 100D (from the panel
Mounting: Direct panel mounting; mounting bracket, one
Panel cutout dimensions: Mounting attitude:
Wiring connection:
conforming to IP55. For side-by-side close installation, the controller loses its dust-proof and drip-proof protection.
face) (mm)
each for upper and lower mounting
92
+0.8
0
W ×
92
+0.8
H (mm)
0
Up to 30 degrees from horizontal; Must not face downward.
With M3.5 screw terminals (for signal, power and grounding wiring)
Power Supply and Isolation
Power supply: Rated voltage 100 to 240 V AC (±10%),
Power consumption: Max. 20 VA (Max. 8.0 W) Data backup: Non-volatile memory. Service life about
Withstanding voltage:
Isolation resistance:
Grounding: Class 3 grounding (grounding resistance of
Isolation Specifications
PV input terminal:
Auxiliary analog input terminal:
15 V DC loop power supply terminal:
24 V DC loop power supply terminal:
Control output (current output or voltage pulse output) and
Relay contact control output terminals:
Contact input terminals:
Relay contact output terminals:
50/60 Hz
100,000 times of writings 1500 V AC for 1 min.
(Note)
between primary terminals and secondary terminals
1500 V AC for 1 min.
(Note)
between primary terminals and ground terminal
1500 V AC for 1 min.
between ground terminal and secondary terminals
500 V AC for 1 min.
between secondary terminals
where primary terminals stand for power and relay output terminals and secondary terminals stand for analog input and output signal terminals, voltage pulse output terminals, and contact input terminals.
Note: The withstanding voltage is specified as
2300 V AC per minute to provide a margin of safety.
20 M or more for 500 V DC applied between power terminals and ground terminal
100 or less)
Isolated from other input/output terminals, but not isolated from internal circuit.
Isolated from other input/output terminals and internal circuit.
Not isolated from analog current output and voltage pulse control output, but isolated from other input/output terminals and internal circuit.
Isolated from 4-20mA analog ouptut, other input/output terminals and internal circuit.
retransmission output: Not isolated between control output and retransmission output, but isolated from other input/output terminals and internal circuit.
Isolated between contact output terminals, and from other input/output terminals and internal circuit.
Not isolated between contact input terminals and from communication terminals, but isolated from other input/output terminals and internal circuit.
Not isolated between relay contact outputs, but isolated from other input/output terminals and internal circuit.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
8
Transistor contact output terminals:
Not isolated between transister contact outputs, but isolated from other input/output terminals and internal circuit.
RS-485 communication terminals:
Not isolated from contact input terminals, but isolated from other input/output terminals and internal circuit.
Feedback slidewire resistance input terminals:
Not isolated from control output terminals (current or voltage pulse output) and retransmmision output, but isolated from other input/output terminals and internal circuit.
Power terminals:
Isolated from other input/output terminals and internal circuit.
Ground terminal:
Isolated from other input/output terminals and internal circuit.
Environmental Conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C (40°C or less for side­Temperature change rate limit: 10°C/h or less
Ambient humidity: 20 to 90% RH (no condensation) Magnetic field: 400 A/m or less Continuous vibration (5 to 14 Hz):
Continuous vibration (14 to 150 Hz): Short-period vibration: 14.7 m/s
Shock: 147 m/s2 or less, 11 ms Installation altitude: 2000 m or less above sea level Warm-up time: 30minutes or more after power on
Transportation and storage conditions:
Temperature: -25 to 70°C Temperature change rate: 20°C/h or less Humidity: 5 to 95% RH (no condensation)
Effects of operating conditions
Effect of ambient temperature:
Effect of power supply fluctuation (within rated voltage
by-side close mounting )
Peak-to-peak amplitude 1.2 mm or less
2
or less
4.9 m/s
2
, 15 s or less
Whichever is greater, ±1 µV/°C or ±0.01%
of F.S./°C for voltage or thermocouple
inputs.
±0.02% of F.S./°C for Auxiliary input
±0.05°C/°C (ambient temperature) or less
for RTD inputs.
±0.05% of F.S./°C or less for analog
outputs.
range):
Whichever is greater, ±1 µV/10 V or
±0.01% of F.S./10 V for analog inputs.
±0.05% of F.S./10 V or less for analog
outputs.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E 2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Single-loop Control (Model UT550-0,UT550-2■ or UT550-3■)
9
PV input terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
Remote input
terminals and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
Remote setting filter
Ratio/bias calculation
2221
CommunicationAux. Input RMS=COMRMS=RSP
REMOTE
R/L
Target setpoint ramp-rate function
Communication
terminals to
RS485
LOCAL
2723
DI3 DI4 DI5 DI6 DI1 DI2 DI8INPUT1 INPUT3
Target setpoint selection
SPN
Target setpoints 1 to 8
REMOTE(ON)/LOCAL(OFF) switching
Contact input
Manual operation
Preset output Output limiter
24V loop power supply
LPS
Terminals and
4443
Legend
Control computation
MAN
A/M
AUTO
AUTO(ON)/MAN(OFF) switching
RUNSTOP
S/R
OT1
Control output
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
and
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
STOP(ON)/RUN(OFF) switching
15V loop power supply
Relay terminals
, and
1716
2 31
RT2 RT1
Current*
terminals
and
* Unavailable when control output is current or pulse.
Retransmission output
Current
terminals
1716
and
1514
Alarm function
ON in normal condition
DO7DO4DO3DO2DO1
Alarm 1 Alarm 2 Alarm 3 Alarm 4 FAIL output
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
■Function Block Diagram for Single-loop Heating/Cooling Control (Model UT550-2)
10
PV input terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
Remote input
terminals and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
Remote setting filter
Ratio/bias calculation
2221
CommunicationAux. Input
RMS=COMRMS=RSP
R/L
Target setpoint ramp-rate function
Communication
terminals to
RS485 DI3 DI4 DI5 DI6 DI1 DI2 DI8INPUT1 INPUT3
2723
LOCALREMOTE
REMOTE(ON)/LOCAL(OFF) switching
Contact input
Target setpoint selection
SPN
Target setpoints 1 to 8
Heating-side preset output
OUTPUT1 OUTPUT1
Current or
pulse terminals
Control computationManual operation
AUTOMAN
A/M
Heating/cooling computation
Heating-side output limiter Cooling-side output limiter
OT1
Heating-side
output
Relay
terminals
and
1716
2 31
, and
* Unavailable when heating-side output is current output or pulse.
AUTO(ON)/MAN(OFF) switching
OT1
Cooling-side
output
OUTPUT2 OUTPUT2
Current or pulse
terminals
and
4746
Relay
terminals
, and
49 5048
Cooling-side preset output
15V loop
power supply
RT2 RT1
OUTPUT1 OUTPUT3
Current*
terminals
and
1716
S/R
STOP(ON)/RUN(OFF) switching
Retransmission
output
Current
terminals
and
Alarm function
ON in normal condition
DO7DO4DO3DO2DO1
Alarm1Alarm2Alarm3Alarm4FAIL
output
1514
Legend
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Single-loop Position-proportional Control (Model UT550-1or UT550-4■)
PV input terminals
12 1311
, and
Remote input
terminals and
2221
Communication
terminals to
RS485 DI3 DI4 DI5 DI6 DI1 DI2 DI8INPUT1 INPUT3
2723
Contact input
11
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
In MAN operation, relay is ON when or key is hold down.
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
Remote setting filter
CommunicationAux. Input
RMS=RSP
Ratio/bias calculation
RMS=COM
R/L
Target setpoint ramp-rate function
Control computationManual operation
Output limiter
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
Target setpoint selection
SPN
Target setpoints 1 to 8
LOCALREMOTE
REMOTE(ON)/LOCAL(OFF) switching
Preset output
RUNSTOP
FEEDBACK
and
45
47
terminals ,
46
Feed-back input
Signal comparison
L relay
( key)
terminals ,
S/R
OUTPUT
49 50
and
M
STOP(ON)/RUN(OFF) switching
15V loop power supply
H relay
( key)
48
Relay output Direct/reverse signal
Motor-driven valve
Retransmission output
RT2 RT1
OUTPUT1 OUTPUT3
1716
OUTPUT3
terminals
and
OUTPUT1
terminals
and
Alarm1Alarm2Alarm3Alarm4FAIL
1514
Valve position sliding resistor
Legend
43 44
- terminals : 24VDC loop power supply
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
Alarm function
ON in normal condition
DO7DO4DO3DO2DO1
output
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Cascade Control
12
Cascade primary PV
Communication
input terminals
, and
12 1311
Input selection Ratio/bias
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
terminals
2723
to
RS485
calculation
Secondary PV input terminals
2221
and
DI3 DI4 DI5 DI6INPUT1 INPUT3
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
RMS=COM
R/L
SPN
Primary target setpoint
LOCALREMOTE
Target setpoint ramp-rate function
Control computation 1
Contact inputs
Cascade
ON)
(OFF
Target setpoint selection
If receives the FAIL signal (burnout or A/D converter error) from primary PV input, operation is switched to AUTO.
SPN
Secondary target setpoint
Automatic
(OFF
ON)
Manual
(OFF
DI8 DI7DI1 DI2
ON)
Output limiter
Tracking in
C/A/M
AUTO or MAN
Tracking signal
Preset output
Output limiter
RUNSTOP
S/R
OT2
STOP(ON)/RUN(OFF) switching
24V loop
power supply
15V loop
power supply
Control
output
OUTPUT1 LPSOUTPUT1 OUTPUT1 OUTPUT3
Current or pulse
terminals
1716
and
Relay
terminals
2 31
, and
Terminals
4443
and
RT2 RT1
Current*1
terminals
and
*1 Unavailable when control output is current or pulse.
AUTO, MANCAS Cascade switching
Manual operation
Retransmission
output
Current
terminals
1716
and
1514
Control computation 2
MAN
C/A/M
A/M
CAS, AUTO
MAN switching
Alarm function
DO7DO4DO3DO2DO1
Alarm 1 Alarm 2 Alarm 3 Alarm 4 FAIL output
ON in normal
condition
Legend
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Loop Control for Backup
13
PV input
Communication
terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
Target setpoint ramp-rate function
terminals
2723
to
RS485
Ratio/bias
calculation
RMS=COM
R/L
Tracking signal
(Manipulated output from host)
terminals and
2221
DI3 DI4 DI5 DI6 DI1 DI2 DI8INPUT1 INPUT3
Input selection
Unit selection
Analog input range conversion
Analog input bias
Analog input filter
SPN
Target setpoints
1 to 8
LOCALREMOTE
Contact inputs
Target setpoint selection
Tracking switching signal
Manual operation
Control output can not be changed when contact input 8 (DI8) is set to ON.
Preset output
24V loop
power supply
LPS
Terminals
4443
and
Control computation
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
Tracking (ON)
Output limiter
RUNSTOP
S/R
OT1
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
and
STOP(ON)/RUN(OFF) switching
Control
output
Relay
terminals
1716
2 31
, and
15V loop
power supply
RT2 RT1
Current *1
terminals
and
Retransmission
1716
*1 Unavailable when control output is current or pulse.
output
Current
terminals
and
Alarm function
ON in normal
condition
DO3DO5DO4DO2DO1
Alarm 1 Alarm 2 Alarm 4 Alarm 3 FAIL output
1514
Legend
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
2nd Edition Sept. 18 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Loop Control with PV Switching
14
PV input 1
terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input range conversion
Analog input bias
Square root extraction
Square root extraction
Analog input filter
PV input 2
terminals
22
21
and
Input selection
Unit selection
Analog input bias
Analog input filter
Communication
10-seg. linearizer approx./bias 10-seg. linearizer approx./bias PV input Switching (Temp. range, Temp. upper limit, or DI)
Burnout occurs when the burnout of PV input 1 or PV input 2 occurs.
PV input bias PV input filter
RMS=COM
R/L
Target setpoint ramp-rate function
Control computationManual operation
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
terminals
2723
to
RS485
Ratio/bias
calculation
DI3 DI4 DI5 DI6 DI1 DI2 DI8INPUT1 INPUT3
U1
Upper limit
U2
Lower limit
U3
Operation
SPN
Target setpoints 1 to 8
LOCALREMOTE
Contact inputs
Target setpoint selection
PV input switching (U3=2)
PV input 1(OFF)/ PV input 2(ON)
Preset output
24V loop
power supply
LPS
Terminals
4443
and
Output limiter
RUNSTOP
S/R
OT1
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
and
STOP(ON)/RUN(OFF) switching
Control
output
Relay
terminals
1716
2 31
, and
15V loop
power supply
RT2 RT1
Current *1
terminals
and
Retransmission
1716
*1 Unavailable when control output is current or pulse.
Legend
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
output
Current
terminals
and
Alarm function
ON in normal
condition
DO7DO4DO3DO2DO1
Alarm 1 Alarm 2 Alarm 3 Alarm 4 FAIL output
1514
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
1 2 3 4 5 6 7 8 9
10
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
8 9
Power supply
10
L
N
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
Power supply
12 13
TC input
11 12
RTD input
13
12 13
mV/V input
21 22
Remote input
*
Wiring can only be carried out for
controllers with remote input.
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
23 24
RS-485 communication
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
* Factory-set to PV retransmission.
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
24 V DC loop
power supply
*Wiring can only be carried out for controllers with 24 V DC loop power supply.
1 2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact output is configured at factory before shipment.
Note: Select this option from the OT1 parameter.
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Installation category (overvoltage category): II (IEC1010-1)
A b
B
NOTE
-
+
-
+
-
+
21.6-28.0VDC
(30 mA DC max.)
43 44
+
-
Default: 1-5 V DC
OT1=0 (factory-set default) OT1=1
Correspondence between parameter OT1 and control output types
OT1=2
OT1=3
* OT1 is a setup parameter. You can change the settings of the parameter OT1 to change the control output type.
Time proportional control
Relay output
(terminals , and )
1
2
3
Time proportional control
Voltage pulse output (terminals and )
16
17
Current output
(terminals and )
16
17
On-off control Relay output
(terminals , and )
1
2
3
PV input
* Not configured at factory before shipment
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF DI5 DI6
OFF OFF
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON OFF
ON
OFF
OFF
ON
Common
Remote when DI8=ON Local when DI8=OFF
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3 DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
No function
16 17
Current/voltage
pulse output
0-20mADC, 4-20mADC Voltage pulse (12 V)
Control output
14 15
Retransmission output 1*
4-20 or 0-20 mA DC
14 15
15 V DC loop power supply*
14.5-18.0 V DC (21 mA DC max.)
* Retransmission output 2 is available only when “relay” is selected as the type of control output.
16 17
Retransmission
output 2*
Default: 4-20 mA DC
Default: 4-20 mA DC
0-20mADC, 4-20mADC
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
-
+
-
+
-
+
-
+
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
Relay Transistor
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
Load resistance: 600
or less
12
13
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Note: Select this option from the OT1 parameter.
Note: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP)
*Alarm 4 output is available only when "current/voltage pulse" is selected as the type of control output.
UT550 Single-loop Control (Model UT550-0, UT550-2or UT550-3), Terminal Arrangements
<<Contents>> <<Index>>
2nd Edition Sept. 18, 2000-00
15
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
1 2 3 4 5 6 7 8 9
10
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
Heating-side control output
Current/voltage pulse output
Cooling-side control output
Cooling-side control output
12 13
11 12 13
12 13
A
b
B
23 24 25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
8 9
10
L
N
1 2 3
NC
NO
COM
48 49 50
NC
NO
COM
+
-
+
-
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Power supply
Power supply
Relay contact output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact output is configured at factory before shipment.
*Time proportional PID relay contact output is configured at factory before shipment.
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
*
Wiring can only be carried out for
controllers with remote input.
TC input
RTD input
mV/V input
Installation category (overvoltage category): II (IEC1010-1)
21 22
Remote input
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
-
+
RS-485 communication
Relay contact output
NOTE
Default: 1-5 V DC
OT1=4 (factory-set default) OT1=5
Correspondence between parameter OT1 and heating side output types/cooling side output types
OT1=6
OT1=7 OT1=8 OT1=9 OT1=10 OT1=11 OT1=12
The types of control output, relay output and voltage pulse output shown in the table above refer to those of time proportional control. To change to a relay output for on-off control, select Relay Terminals and change the setpoint of the proportional band to 0.
Heating side: Relay output (terminals , and ) Cooling side: Relay output (terminals , and )
1
2
3
Heating side: Voltage pulse output (terminals and ) Cooling side: Relay output (terminals , and )
16 17
Heating side: Current output (terminals and ) Cooling side: Relay output (terminals , and )
16
17
Heating side: Relay output (terminals , and ) Cooling side: Voltage pulse output (terminals and )
1
2
3
Heating side: Relay output (terminals , and ) Cooling side: Current output (terminals and )
1
2
3
Heating side: Voltage pulse output (terminals and ) Cooling side: Voltage pulse output (terminals and )
16 17
Heating side: Current output (terminals and ) Cooling side: Voltage pulse output (terminals and )
16 17
Heating side: Voltage pulse output (terminals and ) Cooling side: Current output (terminals and )
16
17
Heating side: Current output (terminals and ) Cooling side: Current output (terminals and )
16 17
* Factory-set to PV retransmission.
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
Heating-side control output
14 15
Retransmission output 1*
4-20 or 0-20 mA DC
14 15
15 V DC loop power supply*
14.5-18.0 V DC (21 mA DC max.)
* Retransmission output 2 is available only when “relay” is selected as the type of control output.
Default: 4-20 mA DC
-
+
-
+
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
* OT1 is a setup parameter. You can change the settings of the parameter OT1 to change the control output type.
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF DI5 DI6
OFF OFF
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Common
Remote when DI8=ON
Local when DI8=OFF
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3 DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
No function
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
48
47
46
47
46
47
46
47
46
47
46
47
46
49
50
48
49
50
48
49
50
46
47
+
-
0-20 mA DC 4-20 mA DC,
voltage pulse (12 V)
PV input
16 17
Current/voltage
pulse output
0-20mADC, 4-20mADC Voltage pulse (12 V)
16 17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC, 4-20mADC
-
+
-
+
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
Load resistance: 600
or less
12
13
Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
* Not configured at factory before shipment
Default: Unspecified
retransmission type
Note: Select this option from the OT1 parameter.
Note: Select this option from the OT1 parameter.
Note: Select this option from the OT1 parameter.
Note: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP)
Relay Transistor
*Alarm 3 output is available only when "current/voltage pulse" is selected as the type of cooling-side control output.
*Alarm 4 output is available only when "current/voltage pulse" is selected as the type of heating-side control output.
UT550 Single-loop Heating/Cooling Control (Model UT550-2), Terminal Arrangements
<<Contents>> <<Index>>
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
16
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
1
2 3 4 5 6 7 8 9
10
41 42 43 44 45
46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25
26 27 28 29 30
11 12 13 14 15
16 17 18 19 20
Feedback input
Resistance: 100to 2.5 k
Position proportional control output
48 49
Relay contact output
50
H
(Direct)
L
(Reverse)
COM
Con
ta
ct
ra
tin
g: 250 V AC, 3 A
30 V DC, 3 A (resista
n
c
e
loa
d
)
8 9
10
L
N
23 24
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
12
13
11 12 13
12 13
14 15
14 15
A b
B
24 V DC loop
power supply
*Wiring can only be carried out for controllers with 24 V DC loop power supply.
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
+
-
+
-
+
-
+
-
Retransmission output 1
15 V DC loop power supply
14.5-18.0VDC (21 mA DC max.)
* PV retransmission is configured at factory before shipment.
* If 15 V DC loop power supply is used, retransmission output 1 cannot be used.
Installation category (overvoltage category): II (IEC1010-1)
NOTE
21 22
Remote input
* Wiring can only be carried out for controllers with remote input.
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
-
+
RS-485 communication
TC input
RTD input
mV/V input
21.6-28.0VDC
(30 mA DC max.)
43 44
+
-
Default: 1-5 V DC
0%
100%
47 46
45
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF
DI5
DI6
OFF OFF
OFF OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF ON
Common
Remote when DI8=ON
Local when DI8=OFF
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3
DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
No function
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
Relay Transistor
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
PV input
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
* Not configured at factory before shipment
12
13
Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
W
h
en receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
16 17
Retransmission
output 2
Default: 4-20 mA DC
0-20mADC, 4-20mADC
Default: 4-20 mA DC
4-20 mA DC, 0-20 mA DC
-
+
Default: Unspecified
retransmission type
Load resistance: 600
or less
24 V DC Power Supply Wired to Sensor in Two-wire System Configuration
12
13
43
44
250
Two-wire transmitter
PV input
1-5 V DC
signal
Loop power
supply
21.6-
28.0 V DC
External resistor (Note)
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
* The following method of wiring is only possible when the controller is equipped with a 24 V DC loop power supply.
4-20mADC
Note: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP)
UT550 Single-loop Position Proportional Control (Model UT550-1or UT550-4), Terminal Arrangements
<<Contents>> <<Index>>
2nd Edition Sept. 18, 2000-00
17
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
1 2 3 4 5 6 7 8 9
10
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
8 9
Power supply
10
L
N
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
Power supply
12 13
TC input
11 12
RTD input
13
12 13
mV/V input
21 22
Auxiliary input
Secondary PV input
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
23 24
RS-485 communication
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
*
The functionality of a contact output can be varied by changing the setting of the contact output registration parameter.
* Factory-set to PV retransmission.
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
24 V DC loop
power supply
*Wiring can only be carried out for controllers with 24 V DC loop power supply.
1 2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact output is configured at factory before shipment.
Note: Select this option from the OT2 parameter.
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Installation category (overvoltage category): II (IEC1010-1)
A
b
B
NOTE
-
+
-
+
-
+
21.6-28.0VDC
(30 mA DC max.)
43 44
+
-
Default: 1-5 V DC
OT2=0 (factory-set default) OT2=1
Correspondence between parameter OT2 and control output types
OT2=2
OT2=3
* OT2 is a setup parameter. You can change the settings of the parameter OT2 to change the control output type.
Time proportional control
Relay output
(terminals , and )
1
2
3
Time proportional control
Voltage pulse output (terminals and )
16
17
Current output
(terminals and )
16
17
On-off control
Relay output
(terminals , and )
1
2
3
Primary PV input
* Not configured at factory before shipment
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
Cascade switching when
DI1 changes to on
Automatic switching when
DI2 changes to on
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF DI5 DI6
OFF OFF
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Common
Manual switching when
DI8 changes to on
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3 DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
STOP when DI7=ON RUN when DI7=OFF
16 17
Continuous/voltage
pulse output
0-20mADC, 4-20mADC Voltage pulse (12 V)
Control output
14 15
Retransmission output 1*
4-20 or 0-20 mA DC
14 15
15 V DC loop power supply*
14.5-18.0 V DC (21 mA DC max.)
* Retransmission output 2 is available only when “relay” is selected as the type of control output.
16 17
Retransmission
output 2*
Default: 4-20 mA DC
Default: 4-20 mA DC
0-20mADC, 4-20mADC
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
-
+
-
+
-
+
-
+
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
Relay Transistor
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
Load resistance: 600
or less
12
13
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Note: Select this option from the OT2 parameter.
Note: External Contact Input If the power is turned on when the external contact input (either of Cascade, Automatic, and Manual) is ON, the controller judges that the external contact input is changed to ON.
UT550 Cascade Control, Terminal Arrangements
<<Contents>> <<Index>>
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
18
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E
1 2 3 4 5 6 7 8 9
10
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24
25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
8 9
Power supply
10
L
N
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
Power supply
12 13
TC input
11 12
RTD input
13
12 13
mV/V input
21 22
Auxiliary input
Tracking Signal (host device operation output)
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
23 24
RS-485 communication
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
*
The functionality of a contact output can be varied by changing the setting of the contact output registration parameter.
* Factory-set to PV retransmission.
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
24 V DC loop
power supply
*Wiring can only be carried out for controllers with 24 V DC loop power supply.
1 2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact output is configured at factory before shipment.
Note: Select this option from the OT1 parameter.
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Installation category (overvoltage category): II (IEC1010-1)
A b
B
NOTE
-
+
-
+
-
+
21.6-28.0VDC
(30 mA DC max.)
43 44
+
-
Default: 1-5 V DC
OT1=0 (factory-set default) OT1=1
Correspondence between parameter OT1 and control output types
OT1=2
OT1=3
* OT1 is a setup parameter. You can change the settings of the parameter OT1 to change the control output type.
Time proportional control
Relay output
(terminals , and )
1
2
3
Time proportional control
Voltage pulse output (terminals and )
16
17
Current output
(terminals and )
16
17
On-off control Relay output
(terminals , and )
1
2
3
PV input
* Not configured at factory before shipment
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF DI5 DI6
OFF OFF
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Common
Output of tracking signal when DI8=ON
Output of PID computation when DI8=OFF
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3 DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
No function
16 17
Current/voltage
pulse output
0-20mADC, 4-20mADC Voltage pulse (12 V)
Control output
14 15
Retransmission output 1*
4-20 or 0-20 mA DC
14 15
15 V DC loop power supply*
14.5-18.0 V DC (21 mA DC max.)
* Retransmission output 2 is available only when “relay” is selected as the type of control output.
16 17
Retransmission
output 2*
Default: 4-20 mA DC
Default: 4-20 mA DC
0-20mADC, 4-20mADC
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
-
+
-
+
-
+
-
+
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
Relay Transistor
Alarm 3 output
Alarm 1 output
Alarm 2 output
FAIL output
(ON when normal)
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
No function
Common
UT
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
Load resistance: 600
or less
12
13
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Note: Select this option from the OT1 parameter.
Note: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP)
UT550 Loop Control for Backup, Terminal Arrangements
<<Contents>> <<Index>>
2nd Edition Sept.18, 2000-00
19
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
1 2 3 4 5 6 7 8 9
10
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21
22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
8 9
Power supply
10
L
N
A
llowable range: 100-240 V AC (10%)
(free voltage) 50/60 Hz shared
Power supply
12 13
TC input
11 12
RTD input
13
12 13
mV/V input
21 22
Auxiliary input
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC.
23 24
RS-485 communication
* Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 9600 bps
25 26 27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
*
The functionality of a contact output can be varied by changing the setting of the contact output registration parameter.
* Factory-set to PV retransmission.
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
24 V DC loop
power supply
*Wiring can only be carried out for controllers with 24 V DC loop power supply.
1 2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact output is configured at factory before shipment.
Note: Select this option from the OT1 parameter.
CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Installation category (overvoltage category): II (IEC1010-1)
A b
B
NOTE
-
+
-
+
-
+
21.6-28.0VDC
(30 mA DC max.)
43 44
+
-
Default: 1-5 V DC
OT1=0 (factory-set default) OT1=1
Correspondence between parameter OT1 and control output types
OT1=2
OT1=3
* OT1 is a setup parameter. You can change the settings of the parameter OT1 to change the control output type.
Time proportional control
Relay output
(terminals , and )
1
2
3
Time proportional control
Voltage pulse output (terminals and )
16
17
Current output
(terminals and )
16
17
On-off control Relay output
(terminals , and )
1
2
3
PV input 1
PV input 2
* Not configured at factory before shipment
19 18
External contact inputs
40 39 38 37
20
28 30
DI1
DI2
DI3 DI4 DI5 DI6
COM
COM
DI8
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3 DI4
1.SP2.SP 3.SP4.SP ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP ON
ONOFF
OFF
ON
ON OFF
OFF DI5 DI6
OFF OFF
OFF OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
ON OFF
OFF
ON
Common
PV input 2 when DI8=ON
PV input 1 when DI8=OFF
(NOTE 1)
Common
When switching among target setpoints 1 to 8:
19 18 40 39 38 37
20
28 30
DI1 DI2 DI3 DI4
DI5 DI6
COM
COM
DI8
+5V +5V +5V +5V +5V +5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
NOTE 1: When operating paramter U3 set to "2", effective to contact input.
No function
16 17
Current/voltage
pulse output
0-20mADC, 4-20mADC Voltage pulse (12 V)
Control output
14 15
Retransmission output 1*
4-20 or 0-20 mA DC
14 15
15 V DC loop power supply*
14.5-18.0 V DC (21 mA DC max.)
* Retransmission output 2 is available only when “relay” is selected as the type of control output.
16 17
Retransmission
output 2*
Default: 4-20 mA DC
Default: 4-20 mA DC
0-20mADC, 4-20mADC
UT
* If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint.
-
+
-
+
-
+
-
+
6 5
External contact outputs
4 7
34 33
DO1
DO2 DO3
COM
DO4
DO5
Relay Transistor
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
Load resistance: 600
or less
12
13
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Note: Select this option from the OT1 parameter.
Note: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP)
UT550 Loop Control with PV Switching, Terminal Arrangements
<<Contents>> <<Index>>
GS 05D01C02-01E
2nd Edition Sept. 18, 2000-00
20
<<Contents>> <<Index>>
External Dimensions and Panel Cutout Dimensions
11
96
A/M
SET/ENT
96
PV
CAS REM MAN
LP2
AL1 2 3 4
General installation Side-by-side close installation
100
1 to 10 mm
0
+0.8
92
(Panel thickness)
Large bracket
112
91.8
Small bracket
[(N-1)96+92]117 min.
+0.8
21
Unit: mm
0
92
(53)
+0.8
0
145 min.
N stands for the number of controllers to be installed. However, the measured value applies if N 5.
+0.8
92
0
(25)
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-01E 2nd Edition Sept. 18, 2000-00
<<Contents>> <<Index>>
Model and Suffix Codes
Model Suffix Code Description
UT550
Type
Optional functions
Digital indicating controller (provided with retransmission output and 15 V DC loop power supply as standard)
-0 Standard type
-1 Position proportional type
-2 Heating/cooling type
-3 Standard type (with 24 V DC loop power supply)
-4 Position proportional type (with 24 V DC loop power supply) None
0
With communication, auxiliary analog (remote) input, 6 additional DIs and 4 additional DOs
1
With communication, auxiliary analog (remote) input, and 1 additional DI
2
With 5 additional DIs and 4 additional DOs
3 4
With auxiliary analog (remote) input and 1 additional DI
22
Standard accessories: Brackets (mounting hardware), unit label, Users Manuals, and Users Manual (reference) (CD-ROM
version).
Specify the required optional function codes according to the UT mode to be used.
Correspondence between UT mode and suffix code
Suffix code
UT mode
Single-loop control
Cascade primary loop control
Cascade secondary loop control Cascade control Loop control for backup
Loop control with PV switching
Loop control with PV auto-selector
Loop control with PV-hold function
(UT mode 1)
(UT mode 2)
(UT mode 3) (UT mode 4) (UT mode 5) (UT mode 6) (UT mode 7) (UT mode 8)
App.: Function available, Cond.: Function available conditionally , N/A: Function not av ailable
00, 03, 20, 23, 30, 33
Cond.
N/A
N/A N/A N/A N/A N/A
Cond.
01, 02,
10, 13,
04,
40, 43 31, 32, 34
App. Cond.
App. N/A
App. N/A App. N/A App. N/A App. N/A App. N/A App. Cond.
11, 12, 14, 41, 42, 44
App.
N/A
App. App. App. App. App. App.
21, 22, 24
Remarks
Cond.: Remote target setting not available
App.
The remote target setting function requires the auxiliary analog input (optional function) to be specified.
Cond.: UT mode 2 not available
Cond.
UT mode 2 can be used if one output is specified without employing heating/cooling (two outputs) functions.
App. App.
Auxiliary analog input is used for the cascade input.
App.
Auxiliary analog input is used for the tracking input.
App.
Auxiliary analog input is used for the PV input 2.
App.
Auxiliary analog input is used for the PV input 2. Cond.: Remote target setting not available
App.
The remote target setting function requires the auxiliary analog input (optional function) to be specified.
Correspondence between the Model and Suffix Codes, and the Contact Input/Output
Terminals Provided
Check the model ordered and the presence/absence of contact inputs and outputs in the following table.
indicate that the contacts are available.
Model and Suffix Codes
UT550- 0 UT550- 1 UT550- 2 UT550- 3 UT550- 4
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DO1 DO2 DO3
✓ ✓ ✓ ✓ ✓
Contact input terminals Contact output terminals
DI8
✓ ✓ ✓ ✓✓✓✓✓✓✓✓✓ ✓
✓✓
DO4
DO5 DO6 DO7
✓✓✓✓✓✓✓
Items to be Specified When Ordering
Model and suffix codes, necessary/unnecessary of Users Manual or QIC.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-01E 2nd Edition Sept. 18, 2000-00
Loading...