Yokogawa UT520 Data sheet

<<Contents>> <<Index>>
General Specifications
MODEL UT520 Digital Indicating Controller
GS 05D01C02-02E
General
Model UT520 Digital Indicating Controller is an intelligent, micro-processor based digital indicating controller with powerful control capability and the user-friendly large numerical display. The UT520 features as standard many functions which are necessary for various control applica­tions, and all of these functions such as control function, control computation function, signal computation function, etc. can be configured by using the keys on the front panel. The instrument has eight types of control strategies and also an overshoot suppressing function "SUPER" and a hunting suppressing function "SUPER 2" as well as an auto-tuning function built in as standard. Panel size is small, 48 mm (width) saving space.
×
96 mm (height), and designed for
Main Features
• High resolution display of 5 digits. Since LEDs of 12 mm height are used for displaying measured values, the display is clearly read.
• The front panel size is 48 mm (width) × 96 mm (height) and the depth is 100 mm, designed for saving space.
• Eight types of control function, including single-loop control, cascade control, loop control with PV auto­selector, and loop control with PV-hold function, enabling the operator to start control operation immediately after simply entering the settings.
• Parameter can be easily set using a personal computer. ("Parameter setting tool (model LL100)" sold separately is required.)
• Universal input and output enables users to set or change freely the type of measured inputs, measurement input range, type of control output, etc. from the front panel.
• Contact inputs (up to 4 points) and contact outputs (up to 4 points) assigned to each contact (The maximum number of points varies depending on the specification code.)
• Various communication function are provided. Communication is possible with personal computer, programable logic controller, and other controllers.
Note
can be employed and functions can be
Note: See the Hardware Specifications and Contact Outputs
described later.
Functional Specifications
Control Functions
UT Mode
The following types of basic control structure can be set as the UT mode by the user.
Single-loop control (UT mode 1): Cascade primary-loop control (UT mode 2):
Cascade secondary-loop control (UT mode 3):
The most simple and basic control function.
Output tracking function and cascade control logic are provided. Suitable for primary-loop cascade control.
Setpoint output and the cascade control logic are provided. Suitable for secondary-loop cascade control.
UT520
UT520E
“E” indicates the model with expanded functions.
Cascade control (UT mode 4):
Dual control function for cascade control is available in a single instrument.
Loop control for back-up (UT mode 5):
Output tracking function is provided to back up another control instrument. The local and remote control outputs are switched by a contact input.
Loop control with PV switching (UT mode 6):
Two measured inputs are switched for control depending on the status of contact input or measured input.
Loop control with PV auto-selector (UT mode 7):
Two measured inputs are automatically selected for control with a high, low, or average, or temperature-difference value selector.
Loop control with PV-hold function (UT mode 8):
This control holds a PV input and a control output if an external sensor is switched.
Control Computation Functions
In each UT mode, the following control computation functions can be selected.
Continuous PID control, Time-proportional PID control, and Relay ON/OFF control.
Target setpoint and PID parameters:
Maximum eight sets of target setpoint and PID parameters can be set. These eight sets can be set for both the main and slave loops in cascade control.
Zone PID selection:
Dividing measuring range into maximum 7 zones by maximum 6-reference points, PID parameter set switching in up to 7 measured input zones.
Auto-tuning:
Available as standard. Possible to activate auto-tuning for both main and slave loops for cascade control.
GS 05D01C02-02E
© Copyright Feb. 2000 (YK)
<<Contents>> <<Index>>
2
Preset output function:
When the instrument is in STOP mode, measured input is burnt-out, or an abnormality is found in an input circuit, a preset value is output as a control output.
"SUPER" function:
Overshoots generated by abrupt changes in the target setpoint or by disturbances can be suppressed.
"SUPER 2" function:
The function stabilizes the state of control that is unstable due to hunting, etc. without requiring any change in PID constants, when the load and/or gain varies greatly, or when there is a difference between the characteris­tics of temperature zones.
Control cycle time
Each cycle time can be selected under the following conditions.:
50 ms: Available for model code UT520-00, when
UT mode is set to Single-loop control and the following functions are not used: "SUPER" function, "SUPER 2" function, PV input computation, setpoint rate-of­change limiter, MV output rate-of-change limiter, deviation alarm, sensor grounding alarm, fault diagnosis alarm, and FAIL output.
100 ms: Available when UT mode is not cascade
control. 200 ms: Available when UT mode is cascade control. (Set value on shipped from the factory: 200 ms)
Operation Mode Switching
(Note: Communication enables all the following
mode switching to be executed.)
AUTO/MANUAL switching:
Bumpless switching between automatic operation mode and manual control mode is available by using the front keys or contact input. The contact input has priority over front key input or switching by communica­tion. The contact input is invalid for Cascade secondary-loop control or Cascade control.
RUN/STOP switching:
Switching by contact input (bumpless for switching from STOP to RUN). The contact input has priority over switching by communi­cation. In RUN mode, control computation is activated. In STOP mode, control computa­tion ceases and a preset value is output as a control output while other functions operate normally.
REMOTE/LOCAL switching:
Switching between remote setpoint and local setpoint by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. For remote to local switch­ing, either bumpless tracking (employing the remote setpoint on switching as the local setpoint) or without tracking (directly switching the local setpoint) can be specified.
CASCADE/AUTO/MANUAL switching:
Switching by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. Valid for Cascade second-
Output tracking ON/OFF switching:
ary-loop control or Cascade control.
Provided for Cascade primary-loop control or Loop control for backup. External tracking signal and internal control output are switched by the contact input. The contact input has priority over the switching by communication.
Control Parameters Setting Range
Proportional band: 0.1 to 999.9% Integral time: 1 to 6,000 s, or OFF (for Manual reset) Derivative time: 1 to 6,000 s, or OFF ON/OFF control hysteresis:
0.0 to 100.0% of measured input range width
Preset output: -5.0 to 105.0% of the output (0 mA or less
cannot be output)
Output limiter:
Setting range: -5.0 to 105.0% for both high and low limits However, "low limit setpoint < high limit setpoint" must be satisfied.
Shutdown function:
When manual control is carried out with 4 to 20 mA output, control output can be output down to about 0 mA (shutdown is specified for -5.0% or less).
Rate-of-change limiter for output:
OFF or 0.1 to 100.0%/s
Configuration of Input/Output Signal
Measured Input Computations
Input processing, Square root extraction (voltage input only, Input low cut 0.0 to 5.0%), Ten-segment linearizer function, Ten-Segment bias, Bias addition (-100.0 to 100.0%), and First order lag filter (OFF, time constant 1 to 120 s)
Auxiliary Input Computations
(Applied to remote setting input only)
Input processing, Square root extraction (Input low cut 0.0 to
5.0%), Bias addition (-100.0 to 100.0%), Ratio multiplication (0.001 to 9.999), and First order lag filter (OFF, time constant 1 to 120 s)
Alarm Functions
Alarm types:
PV high limit, PV low limit, Deviation high limit, Deviation low limit, Deenergized on deviation high limit, Deenergized on deviation low limit, Deviation high and low limits, High and low limits within deviation, Deenergized on PV high limit, Deenergized on PV low limit, SP high limit, SP low limit, Output high limit, Output low limit.
Alarm setting range:
PV/SP alarm: -100 to 100% of measured input range Deviation alarm: -100 to 100% of measured input range span Output alarm: -5.0 to 105.0% of output value Alarm hysteresis: 0.0 to 100.0% of measured input range span
Delay timer:
0.00 to 99.59 (minute, second) An alarm is output when the delay timer expires after the alarm setpoint is reached. Setting for each alarm is possible.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E 1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
3
Stand-by action:
Stand-by action can be set to make PV/ deviation alarm OFF during start-up or after SP change until SP reaches the normal region.
Timer function (stabilization of control status notification
event) (Alarm 1 only): This function sets the alarm 1 output to ON when a preset time (timer setting) elapses after a PV has reached to the control target setpoint hysteresis band to notify that processing has completed. Restarted in RUN/STOP or SP switching.
Other alarm actions:
Sensor grounding alarm: Detects sensor deterioration and
outputs an alarm. Fault-diagnosis alarm: For input burnout, A/D conver-
sion error, or thermocouple reference
junction compensation error. FAIL output: Abnormality in software or hardware.
Number of alarm settings: 4
The alarm status can be read via communica­tion in addition to output as the above alarm output.
Alarm output points (see also the item "Contact Outputs")
Number of contact (relay) outputs: 3 (stan­dard) or 4 (if a control output relay is used for
the alarm 4 output relay.) Any of PV alarm, deviation alarm, SP alarm, output alarm, Fault-diagnosis alarm, sensor grounding alarm and FAIL output can be assigned to contacts for the above number of outputs. However, the timer delay alarm can be assigned to the alarm 1 output only. Also, the alarm 4 only can be assigned to the control output relay (if a relay is not used for control output).
Display and Operation Functions
PV Display
PV is displayed on the 5-digit display. PV1 and PV2 are displayed by switching them in cascade control. The number of display digits is 4 or 5. For thermocouple or RTD, data below the decimal point can be set not to display. The display range is -19999 to 30000 and the display span is 30000 or less. [520.00 appearing in the product photograph on page 1 cannot actually be displayed.]
Setpoint Display
A parameter name is displayed in the 3-digit display and data in the 5-digit display. There are four kinds of displays : operating display, operating parameter setting display, setup parameter setting display and SELECT display.
Operating display:
Data necessary for operations, such as setpoint or control output, are displayed depending on the UT mode.
Operating parameters setting display:
The Operating parameters, which are mainly changed during operation, such as PID constant, are displayed.
Setup parameters setting display:
The Setup parameters to configure the functions of the instrument before starting operation are displayed. UT model is to be set in this display.
SELECT display:
Up to five displays which are frequently accessed can be selected from the Operating parameters setting display and Setup param­eters setting display to be displayed in the SELECT display.
Status Lamps
Alarm indicating lamp:
Four lamps, AL1, AL2, AL3, and AL4
Operation mode indicating lamp:
REM (remote operation), MAN (manual mode operation), CAS (cascade operation), and LP2 (cascade secondary-loop control)
Operation Keys
n, , keys: Increases or decreases setpoints and other
parameters displayed in the setpoint display.
SET/ENT key: Used for setting or change set data,
switching the displayed contents, and switching operation modes except for A/M.
A/M key: Operation mode switching (Auto/Man)
Security Function
Key-lock by parameters setting and prohibit­ing operation are available by a password
Measured value (PV) display unit
Displays PV and error codes when errors are detected.
Status lamps
Cascade operation(CAS) and
Data display unit
Displays setpoints (SP), output values, valve opening,or parameters.
Communication port for light loader
Parameters are set via communication from a personal computer.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E 1st Edition Mar. 31, 2000-00
remote operation(REM) Manual operation (MAN) Lit for secondary parameter indication (LP2)
Alarm indicating lamps
Displays alarms (AL1, AL2, AL3, or AL4).
Operation keys
Increase/decrease of the setting data (n, ,) Screen switching/parameter selection/entry of set data (SET/ENT) Auto/manual operation mode selection (A/M)
<<Contents>> <<Index>>
4
Communication Functions
(For optional function code h7 only) This controller has four types of communication protocol with one communication interface. Communication is possible with personal computer, programmable logic controller, and other controllers.
Communication Protocol
Computer link communication:
Communication protocol with a personal computer
Ladder communication:
Communication protocol with the ladder program on some programmable logic controllers.
Coordinated operation:
Protocol for coordinated operation with more than one GREEN SERIES controller. The UT520 controller can be connected as a master or slave station.
MODBUS communication:
Communication protocol with a personal computer, or PLC.
Examples of Communication System Configuration Diagram
(1)Personal computer link communication/
MODBUS communication
Personal computer
RS-485 Communication Interface
The RS485 communication interface (conforms to EIA RS485) can be used for personal computer link, ladder communication, MODBUS communication or for coordi­nated operation.
Maximum number of connectable controllers:
GREEN SERIES controller 31 Maximum communication distance: 1200 m Communication method:
Two-wire half-duplex or four-wire half-
duplex, start-stop synchronization, and non-
procedural Communication rate:
600, 1200, 2400, 4800, or 9600 bps
(2) Ladder communication
MELSEC-A
Programmable logic controller
PV
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
UT550, UT520 Digital indicating controller
(3) Coordinated operation
PV
PV2
UP750, UP550 Program controller
AL
REM MAN1 MAN2 STP CAS
or
A/M
DISP
SET/ENT
UT750, UT550, UT520 Digital indicating controller
PV
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
UT550, UT520 Digital indicating controller
PV
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
SET/ENT
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
DISP
SET/ENT
UT550, UT520 Digital indicating controller
PV
PV2
AL
REM MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E 1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
5
Hardware Specifications
Input/Output Signal Specifications
Measured Input Signal
Number of input points: 1 Type of input, measurement range, and measurement
Sampling period: 50, 100, 200 or 500 ms (selectable) Burnout detection:
Input bias current: 0.05 µA (for TC or RTD b-terminal) Measurement current(RTD): about 0.13 mA Input resistance:
Unspecified (When shipped from the factory)
Thermocouple
RTD
Standard signal
DC voltage
accuracy: The type of input and measurement range can be specified from the input range code shown in the table below.
Activated for thermocouple (TC) input, RTD input, or standard signal of 0.4 to 2 V DC or 1 to 5 V DC. Possible to specify a travel of upscale, downscale, or off. For standard signal input (see the table below), set to burn out at 0.1 V or less.
1 M or more for TC or mV input About 1 M for DC voltage input
Input type
K
J T
B
S R N
E L (DIN) U (DIN)
W (DIN) Platinel 2 PR20-40
W97Re3-W75Re25 JPt100
Pt100
0.4 to 2V 1 to 5V 0 to 2V 0 to 10V
-10 to 20mV 0 to100mV
Input range
code
OFF
1 2 3 4 5 6
7
8 9
10
11 12 13 14 15 16
17
18 30 31 35 36 37 40 41 50 51 55 56
Set the data item PV input type “IN 1” to the OFF option to leave the PV input type undefined.
-10.00 to 20.00 mV
Instrument
range (°C)
-270.0 to 1370.0°C
-270.0 to 1000.0°C
-200.0 to 500.0°C
-200.0 to 1200.0°C
-270.0 to 400.0°C
0.0 to 400.0°C
0.0 to 1800.0°C
0.0 to 1700.0°C
0.0 to 1700.0°C
-200.0 to 1300.0°C
-270.0 to 1000.0°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 2300.0°C
0.0 to 1390.0°C
0.0 to 1900.0°C
0.0 to 2000.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
-200.0 to 850.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.0 to 100.0 mV
Allowable signal source resistance:
250 or less for TC or mV input
Signal source resistance effect
0.1 µV/ or less
2 k or less for DC voltage input
Signal source resistance effect
Approx. 0.01%/100 Allowable leadwire resistance (for RTD input):
Maximum 150 /one wire (Lead resistances
of three wires must be equal.)
However, it must be 10 /one wire for the
range of -150.0 to 150.0°C.
Effect of wiring resistance: ±0.1°C/10 Allowable input voltage:
±10 V DC for TC/mV/RTD input
±20 V DC for DC voltage input Noise rejection ratio:
Normal mode 40 dB (50/60 Hz) or more
Common mode 120 dB (50/60 Hz) or more Reference junction compensation error:
±1.0°C (15 to 35°C), ±1.5°C (0 to 15°C and
35 to 50°C) Applicable standards: JIS, IEC, and DIN (ITS-90) for TC
and RTD
Instrument
range (°F)
-450.0 to 2500.0°F
-450.0 to 2300.0°F
-200.0 to 1000.0°F
-300.0 to 2300.0°F
-450.0 to 750.0°F
-200.0 to 750.0°F 32 to 3300°F
32 to 3100°F 32 to 3100°F
-300.0 to 2400.0°F
-450.0 to 1800.0°F
-300.0 to 1600.0°F
-300.0 to 750.0°F
-200.0 to 1000.0°F
32 to 4200°F
32.0 to 2500.0°F 32 to 3400°F
32 to 3600°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
-300.0 to 1560.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
Display range
-19999 to 30000 Display span 30000 or less (Decimal point position changeable)
±0.1% ±1 digit of instrument range at 0°C or more ±0.2% ±1 digit of instrument range at less than 0°C
• However, ±2% ±1 digit of instrument range for type K at temperatures less than -200°C. However, ±1% ± 1 digit of instrument range for type T
• at temperatures less than -200°C.
±0.15% ±1 digit of instrument range at 400°C or more ±5% ±1 digit of instrument range at less than 400°C
±0.15% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range ±0.25% ±1 digit of instrument range for temperature at less than 0°C
±0.1% ±1 digit of instrument range at 0°C or more ±0.2% ±1 digit of instrument range at less than 0°C
• However, ±1.5% ±1 digit of instrument range for type E at temperature less than -200°C.
±0.2% ±1 digit of instrument range ±0.1% ± 1 digit of instrument range
±0.5% ±1 digit of instrument range at 800°C or more
Accuracy not guaranteed for temperature less than 800°C
±0.2% ± 1 digit of instrument range ±0.1% ± 1 digit of instrument range (Note 1) (Note 2) ±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range (Note 1) (Note 2)
±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range
Note 1 : The accuracy is ±0.3°C of instrument range ±1 digit for a temperature range from 0 to 100°C. Note 2 : The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from –100 to 200°C. *1: Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60Hz power frequency)
Instrument accuracy
*1
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
6
Auxiliary Analog Input Signal
(UT520-h7 or -h8 only) Functions: Remote setting input, tracking input, cascade
control secondary-loop PV input, etc.
Input type: Settable within the range of voltage input 0 to
2 V DC, 0 to 10 V DC, 0.4 to 2.0 V DC or
1 to 5 V DC. Number of inputs: 1 point Sampling period: 100, 200 or 500 ms
Auxiliary analog input period is linked with
PV sampling period.
(when PV input period is 50ms , auxiliary
analog input period is 100ms) Input resistance: Approx. 1 M Input accuracy: ±0.3% ± 1 digit of input span for 0 to 2 V
DC input
±0.2% ± 1 digit of input span for 0 to 10 V
DC input
±0.375% ± 1 digit of input span for 0.4 to 2.0
V DC range
±0.3% ± 1 digit of input span for 1 to 5 V DC
range
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
Retransmission Output
Any of the PV, target setpoint or control output is output. Or this can be used for 15 V DC loop power supply.
Number of output points: 1 or 2 Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to 4 mA
DC or 20 to 0 mA DC (0 mA or less cannot be
output) Load resistance: 600 or less Output accuracy: ±0.1% of span (±5% for 1 mA or less)
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
When using for 15 V DC loop power supply: Supply voltage 14.5 to 18.0 V DC, maximum supply
current about 21 mA (with the protection circuit at field short-circuit)
Control Outputs
Select the control output from the following output types depending on the product model and UT mode.
Current output
Number of output points: 1 (switchable to voltage pulse
output)
Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to
4 mA DC or 20 to 0 mA DC (0 mA or less cannot be output)
Load resistance: 600 or less Output accuracy: ±0.1% of span (±5% for 1 mA or less)
Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/ 60Hz power frequency)
Voltage pulse output
Number of output points:
1 (switchable to current output)
Output signal:
ON voltage 12 V DC or more (load resistance 600 or more; current on short­circuiting about 30 mA) OFF voltage 0.1 V DC or less
Resolution: 10 ms or 0.1% of output value, whichever is
greater
Relay contact output
Number of output points: 1 Output signal: At three terminals of NC, NO, and
Common
Contact rating: 250 V AC, 3 A or 30 V DC, 3 A
(resistive load)
Resolution: 10 ms or 0.1% of output value, whichever is
greater
Contact Inputs
Usage: Target setpoint switching, C/A/M mode
switching, REMOTE/LOCAL switching, RUN/STOP switching, or Measured input switching
Number of input points:
Varies with optional codes (as shown below):
UT520-■0: 2 points UT520-■7: 4 points UT520-■8: 4 points
Input type: Non-voltage contact input or transistor open
collector input Input contact rating: 12 V DC, 10 mA or more ON/OFF detection:
For non-voltage contact input,
On .. contact resistance 1 k or less;
Off.. contact resistance 20 k or more
For transistor contact input,
On .. 2 V or less;
Off.. leak current 100 µA or less Minimum retention time for status detection: PV input
sampling period ×3
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
7
Contact Outputs
Usage: Alarm output, FAIL output Number of output points:
3 (relay output) However, when a relay is not used for control output, the relay for control output can be used for the alarm 4. For this reason, the number of relay output points can be changed to 4 by adding to the above 3.
Relay contact rating: 240 V AC, 1 A or 30 V DC, 1 A
Display Specifications
Measured value (PV) display:
5-digit seven-segment red color LED display; height of letters 12 mm
Data display:
3 digits + 5 digits, seven-segment red color LED display; height of letters 9.3 mm
Status indicating lamps: LEDs
Conformance to Safety and EMC Standards
Safety standard:
Conforms to IEC1010-1: 1990 and EN61010­1: 1992 Certified for CSA 1010 The overvoltage category of each input is CAT II (IEC1010-1) Certified for UL508 application
EMC standard:
To the following EMC standards. During test, the controller continues to operate with the measurement accuracy within ±20% of the range: For EMI (emission), EN55011: Class A Group 1 For EMS (immunity), EN50082-2: 1995
Construction, Installation, and Wiring
Construction: Dust-proof and Drip-proof front panel
conforming to IP55. For side-by-side close installation, controller
loses its dust-proof and drip-proof protection. Material of the body: ABS resin and polycarbonate Case color: Black Weight: Approx. 1 kg or less External dimensions:
48W × 96H × 100D (from the panel face)
(mm) Mounting: Direct panel mounting; mounting bracket, one
each for upper and lower mounting Panel cutout dimensions:
Mounting attitude:
Wiring connection:
45
+0.6
0
W ×
92
+0.8
H (mm)
0
Up to 30 degrees from horizontal; Must not
face downward.
With M3.5 screw terminals (for signal, power
and grounding wiring)
Power Supply and Isolation
Power supply: Rated voltage 100 to 240 V AC (±10%),
50/60 Hz Power consumption: MAX. 20 VA or less (MAX. 8.0W) Memory backup: Non-volatile memory. Service life
approx. 100000 times of writings. Withstanding voltage:
1500 V AC for 1 min.
between primary terminals and secondary terminals
1500 V AC for 1 min.
between primary terminals and ground terminal
1500 V AC for 1 min.
between ground terminal and secondary terminals
500 V AC for 1 min.
between secondary terminals
where primary terminals stand for power and relay output terminals and secondary terminals stand for analog input and output signal terminals, voltage pulse output terminals, and contact input terminals.
Note: The withstanding voltage is specified as
2300 V AC per minute to provide a mar gin of safety.
Isolation resistance:
20 M or more for 500 V DC applied
between power terminals and ground terminal Grounding: Class 3 grounding (grounding resistance of
100 or less)
Isolation Specifications
Measured input terminal : Isolated from other input/output
terminals but not isolated from internal
circuits. Auxiliary analog input terminal: Isolated from other input/
output terminals and internal circuits. Control output (current output or voltage pulse output) and
retransmission output: Not isolated between
controll outputs and retransmission output, but
isolated from other input/output terminals and
internal circuits. Relay contact control output terminals: Isolated from other
input/output terminals and internal circuits. Contact input terminals: Not isolated from other contact
input terminals, and communication terminals,
but isolated from other input/output terminals
and internal circuits. Relay contact alarm output terminals: Not isolated from
other relay contact alarm outputs, but isolated
from other input/output terminals and internal
circuits. RS-485 communication terminals: Not isolated from
contact input terminals, but isolated from
other input/output terminals and internal
circuits. Power terminals: Isolated from other input/output
terminals and internal circuits. Ground terminal: Isolated from other input/output
terminals and internal circuits.
(Note)
(Note)
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Environmental Conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C (40°C or less in close
Temperature change rate limit: 10°C/h or less Ambient humidity: 20 to 90% RH (no condensation) Magnetic field: 400 A/m or less Continuous vibration (5 to 14 Hz):
Continuous vibration (14 to 150 Hz):
Short period vibration: 14.7 m/s Shock: 147 m/s Installation altitude: 2000 m or less above sea level Warm-up time: 30minutes or more
Transportation and storage conditions:
Temperature: -25 to 70°C Temperature change rate limit: 20°C/h or less Humidity: 5 to 95% RH (no condensation)
Effects of operating conditions
Effect of ambient temperature:
Effect of power supply fluctuation (within rated voltage
mounting side-by-side) However, 0 to 45°C (35°C or less in close mounting side-by-side) if two analog current output points and the control relay output are used simultaneously.
Peak-to-peak amplitude 1.2 mm or less
2
or less
4.9 m/s
2
or less, 11 ms
2
, 15 s or less
Whichever is greater, ±1 µV/°C or ±0.01% of F.S./°C for voltage or thermocouple inputs. ±0.02% of F.S./°C for Auxiliary input ±0.05°C/°C (ambient temperature) or less for RTD inputs. ±0.05% of F.S./°C or less for analog outputs.
range): Whichever is greater, ±1 µV/10 V or ±0.01% of F.S./10 V for analog inputs. ±0.05% of F.S./10 V or less for analog outputs.
8
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Single-loop Control
9
PV input terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
Remote input
terminals and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
Remote setting filter
Ratio/bias calculation
2221
CommunicationAux. Input RMS=COMRMS=RSP
R/L
Target setpoint ramp-rate function
Communication
terminals to
RS485
2723
SPN
Target setpoints 1 to 8
LOCALREMOTE
REMOTE(ON)/LOCAL(OFF) switching
Contact input
DI1 DI2 DI8INPUT1 INPUT3
Manual operation
Preset output Output limiter
Control computation
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
RUNSTOP
S/R
OT1
Control output
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or pulse
terminals and
STOP(ON)/RUN(OFF) switching
15V loop power supply Retransmission output
Relay terminals
, and
1716
2 31
terminals
and
* Unavailable when control output is current or pulse.
RT2 RT1
Current*
Alarm function
DO3DO2DO1
Current
terminals
1716
and
Alarm 1 Alarm 2 Alarm 3
1514
Legend
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Cascade Control
10
Cascade primary PV
input terminals
, and
12 1311
INPUT1 INPUT3
Communication
terminals
2723
to
RS485
Input selection Ratio/bias
Unit selection
calculation
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
Secondary PV input terminals
2221
and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
RMS=COM
R/L
SPN
Primary target setpoint
LOCALREMOTE
Target setpoint ramp-rate function
Control computation 1
Cascade
(OFF➝ON)
If receives the FAIL signal (burnout or A/D converter error) from primary PV input, operation is switched to AUTO.
SPN
Secondary target setpoint
Contact inputs
DI8DI1 DI2
Manual
(OFF➝ON)
Automatic
(OFF➝ON)
Output limiter
Tracking in
C/A/M
AUTO or MAN
Tracking signal
Preset output
Output limiter
RUNSTOP
S/R
15V loop
OT2
power supply
Control
output
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
1716
and
Relay
terminals
2 31
, and
RT2 RT1
Current*1
terminals
and
*1 Unavailable when control output is current or pulse.
AUTO, MANCAS
Cascade switching
Manual operation
Retransmission
output
Current
terminals
1716
and
1514
Control computation 2
CAS, AUTOMAN
C/A/M
A/M
MAN switching
Alarm function
DO3DO2DO1
Alarm 1 Alarm 2 Alarm 3
Legend
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Loop Control for Backup
11
PV input
Communication
terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias PV input filter
terminals
to
RS485
(Manipulated output from host)
2723
terminals and
Input selection
Unit selection
Analog input range conversion
Analog input bias
Tracking signal
Ratio/bias
calculation
RMS=COM
Analog input filter
Target setpoints
1 to 8
R/L
LOCALREMOTE
Target setpoint ramp-rate function
SPN
2221
Contact inputs
DI1 DI2 DI8INPUT1 INPUT3
Tracking switching signal
Manual operation
Control output can not be changed when contact input 8 (DI8) is set to ON.
Preset output
Control computation
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
Tracking (ON)
Output limiter
RUNSTOP
S/R
OT1
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
and
STOP(ON)/RUN(OFF) switching
Control
output
Relay
terminals
1716
2 31
, and
15V loop
power supply
RT2 RT1
Current *1
terminals
and
Retransmission
1716
*1 Unavailable when control output is current or pulse.
output
Current
terminals
and
Alarm function
DO4DO2DO1
Alarm 1 Alarm 2 Alarm 3
1514
Legend
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Function Block Diagram for Loop Control with PV Switching
12
PV input 1
terminals
12 1311
, and
Input selection
Unit selection
Analog input range conversion
Analog input range conversion
Analog input bias
Square root extraction
Square root extraction
Analog input filter
PV input 2
terminals
22
21
and
Input selection
Unit selection
Analog input bias
Analog input filter
Communication
10-seg. linearizer approx./bias 10-seg. linearizer approx./bias PV input Switching (Temp. range, Temp. upper limit, or DI)
Burnout occurs when the burnout of PV input 1 or PV input 2 occurs.
PV input bias PV input filter
RMS=COM
R/L
Target setpoint ramp-rate function
Control computationManual operation
AUTOMAN
A/M
AUTO(ON)/MAN(OFF) switching
terminals
2723
to
RS485
Ratio/bias
calculation
U1
Upper limit
U2
Lower limit
U3
Operation
SPN
Target setpoints 1 to 8
LOCALREMOTE
Contact inputs
DI1 DI2 DI8INPUT1 INPUT3
PV input switching (U3=2)
PV input 1(OFF)/ PV input 2(ON)
Preset output
Output limiter
RUNSTOP
S/R
OT1
OUTPUT1 OUTPUT1 OUTPUT1 OUTPUT3
Current or
pulse terminals
and
STOP(ON)/RUN(OFF) switching
Control
output
Relay
terminals
1716
2 31
, and
15V loop
power supply
RT2 RT1
Current *1
terminals
and
Retransmission
terminals
1716
*1 Unavailable when control output is current or pulse.
Legend
Terminal Parameter Function
Analog Signal Contact Signal Front Panel Key
output
Current
and
Alarm function
DO3DO2DO1
Alarm 1 Alarm 2 Alarm 3
1514
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
1
2
3
4
5
6
789
10
21
22232425262728
29
30
111213141516171819
20
19
18
20
29
28
30
DI1
DI2
COM
DI3
COM
DI8
No function
Common
Common
19
18
20
DI1
DI2
COM
+5V
+5V
29
28
30
DI3
DI8
COM
+5V
+5V
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
12
13
11
12
13
A
b
B
8
9
10
L
N
1
2
3
NC
NO
COM
6
5
4
7
DO1
DO2
DO3
COM
RS-485 communication
* Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Relay contact output
Control output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact
output is configured at factory
before shipment.
Note: Select this option from the
OT1 parameter.
External contact outputs
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
* The functionality of a contact input can be varied by changing the setting of
the contact input registration parameter.
+
-
TC input
RTD input
Installation category (overvoltage category): II (IEC1010-1)
NOTE
Contact
Transistor contact
External contact inputs
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Contact rating: 12 V DC, 10 mA or more
Remote when DI8=ON
Local when DI8=OFF
* Wiring can only be carried out for
controllers with remote input.
21
22
Remote input
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
j
15 V DC Power Supply Wired to Sensor in
Two-wire System Configuration
12
13
14
15
100V
Two-wire
transmitter
PV input
0.4-2.0 V DC
signal
Loop power
supply
14.5-
18.0 V DC
External
resistor
(Note)
4-20mADC
OT1=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT1=1
Correspondence between parameter OT1 and control output types
Time proportional control
Voltage pulse output (terminals and )
OT1=2
Current output
(terminals and )
OT1=3
On-off control
Relay output (terminals , and )
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to change the control output type.
1 2 3
16 17
16 17
1 2 3
Default: 1-5 V DC
UT
UT
12
13
+
-
mV/V input
* Factory-set to
PV retransmission.
* Retransmission output 1
is not available if a
15 V DC loop power
supply is used.
Control output
14
15
Retransmission output 1*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply*
14.5-18.0 V DC
(21 mA DC max.)
* Retransmission output 2 is available
only when relay is selected as the
type of control output.
Default: 4-20 mA DC
-
+
-
+
PV input
16
17
Continuous/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
* Not configured at factory before shipment
12
13
Note: Connecting a 250 resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41 ).
j
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Load resistance: 600 or less
A
llowable range: 100-240 V AC (610%)
(free voltage)
50/60 Hz shared
Note: Connecting a 100 V resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
Note: Select this option from the OT1 parameter.
Note: External Contact Input
If the power is turned on when
the external contact input is OFF,
the mode (SPN, R/L, or A/M)
existing before the power is turned
off will be continued.
(except for RUN/STOP)
13
UT520 Single-loop Control (Factory-set to Single-loop Control), Terminal Arrangements
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
1
2
3
4
5
6
789
10
21
22232425262728
29
30
111213141516171819
20
19
18
20
29
28
30
DI1
DI2
COM
DI3
COM
DI8
No function
Common
Common
19
18
20
DI1
DI2
COM
+5V
+5V
29
28
30
DI3
DI8
COM
+5V
+5V
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
12
13
11
12
13
A
b
B
8
9
10
L
N
1
2
3
NC
NO
COM
6
5
4
7
DO1
DO2
DO3
COM
RS-485 communication
* Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Relay contact output
Control output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact
output is configured at factory
before shipment.
Note: Select this option from the
OT2 parameter.
External contact outputs
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
* The functionality of a contact input can be varied by changing the setting of
the contact input registration parameter.
* The functionality of a contact output can be
varied by changing the setting of the contact
output registration parameter.
+
-
TC input
RTD input
Installation category (overvoltage category): II (IEC1010-1)
NOTE
Contact
Transistor contact
External contact inputs
Cascade switching when
DI1 changes to on
Automatic switching when
DI2 changes to on
Contact rating: 12 V DC, 10 mA or more
Manual switching when
DI8 changes to on
Secondary PV input
21
22
Auxiliary input
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
j
15 V DC Power Supply Wired to Sensor in
Two-wire System Configuration
12
13
14
15
100V
Two-wire
transmitter
PV input
0.4-2.0 V DC
signal
Loop power
supply
14.5-
18.0 V DC
External
resistor
(Note)
4-20mADC
OT2=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT2=1
Correspondence between parameter OT2 and control output types
Time proportional control
Voltage pulse output (terminals and )
OT2=2
Current output
(terminals and )
OT2=3
On-off control
Relay output (terminals , and )
* OT2 is a setup parameter.
You can change the settings of the parameter OT2 to change the control output type.
1 2 3
16 17
16
17
1 2 3
Default: 1-5 V DC
UT
UT
12
13
+
-
mV/V input
* Factory-set to
PV retransmission.
* Retransmission output 1
is not available if a
15 V DC loop power
supply is used.
Control output
14
15
Retransmission output 1*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply*
14.5-18.0 V DC
(21 mA DC max.)
* Retransmission output 2 is available
only when relay is selected as the
type of control output.
Default: 4-20 mA DC
-
+
-
+
Primary PV input
16
17
Continuous/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
* Not configured at factory before shipment
12
13
Note: Connecting a 250 resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41 ).
j
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Load resistance: 600 or less
A
llowable range: 100-240 V AC (610%)
(free voltage)
50/60 Hz shared
Note: Connecting a 100 V resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
Note: Select this option from the OT2 parameter.
Note: External Contact Input
If the power is turned on when
the external contact input
(either of Cascade, Automatic,
and Manual) is ON,the controller
judges that the external contact
input is changed to ON.
14
UT520 Cascade Control, Terminal Arrangements
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
1
2
3
4
5
6
789
10
21
22232425262728
29
30
111213141516171819
20
19
18
20
29
28
30
DI1
DI2
COM
DI3
COM
DI8
No function
Common
Common
19
18
20
DI1
DI2
COM
+5V
+5V
29
28
30
DI3
DI8
COM
+5V
+5V
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
12
13
11
12
13
A
b
B
8
9
10
L
N
1
2
3
NC
NO
COM
6
5
4
7
DO1
DO2
DO3
COM
RS-485 communication
* Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Relay contact output
Control output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact
output is configured at factory
before shipment.
Note: Select this option from the
OT1 parameter.
External contact outputs
Relay
Alarm 1 output
Alarm 2 output
FAIL output
(ON when normal)
Common
* The functionality of a contact input can be varied by changing the setting of
the contact input registration parameter.
* The functionality of a contact output can
be varied by changing the setting of the
contact output registration parameter.
+
-
TC input
RTD input
Installation category (overvoltage category): II (IEC1010-1)
NOTE
Contact
Transistor contact
External contact inputs
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Contact rating: 12 V DC, 10 mA or more
Output of tracking signal when DI8=ON
Output of PID computation when DI8=OFF
Tracking Signal
(host device operation output)
21
22
Auxiliary input
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
j
15 V DC Power Supply Wired to Sensor in
Two-wire System Configuration
12
13
14
15
100V
Two-wire
transmitter
PV input
0.4-2.0 V DC
signal
Loop power
supply
14.5-
18.0 V DC
External
resistor
(Note)
4-20mADC
OT1=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT1=1
Correspondence between parameter OT1 and control output types
Time proportional control
Voltage pulse output (terminals and )
OT1=2
Current output
(terminals and )
OT1=3
On-off control
Relay output (terminals , and )
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to change the control output type.
1 2 3
16 17
16 17
1 2 3
Default: 1-5 V DC
UT
UT
12
13
+
-
mV/V input
* Factory-set to
PV retransmission.
* Retransmission output 1
is not available if a
15 V DC loop power
supply is used.
Control output
14
15
Retransmission output 1*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply*
14.5-18.0 V DC
(21 mA DC max.)
* Retransmission output 2 is available
only when relay is selected as the
type of control output.
Default: 4-20 mA DC
-
+
-
+
PV input
16
17
Continuous/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
* Not configured at factory before shipment
12
13
Note: Connecting a 250 resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41 ).
j
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Load resistance: 600 or less
A
llowable range: 100-240 V AC (610%)
(free voltage)
50/60 Hz shared
Note: Connecting a 100 V resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
Note: Select this option from the OT1 parameter.
Note: External Contact Input
If the power is turned on when
the external contact input is OFF,
the mode (SPN, R/L, or A/M)
existing before the power is turned
off will be continued.
(except for RUN/STOP)
15
UT520 Loop Control for Backup, Terminal Arrangements
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
1
2
3
4
5
6
789
10
21
22232425262728
29
30
111213141516171819
20
19
18
20
29
28
30
DI1
DI2
COM
DI3
COM
DI8
No function
Common
Common
19
18
20
DI1
DI2
COM
+5V
+5V
29
28
30
DI3
DI8
COM
+5V
+5V
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
12
13
11
12
13
A
b
B
8
9
10
L
N
1
2
3
NC
NO
COM
6
5
4
7
DO1
DO2
DO3
COM
RS-485 communication
* Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Relay contact output
Control output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact
output is configured at factory
before shipment.
Note: Select this option from the
OT1 parameter.
External contact outputs
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
* The functionality of a contact input can be varied by changing the setting of
the contact input registration parameter.
* The functionality of a contact output
can be varied by changing the
setting of the contact output
registration parameter.
+
-
TC input
RTD input
Installation category (overvoltage category): II (IEC1010-1)
NOTE
Contact
Transistor contact
External contact inputs
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Contact rating: 12 V DC, 10 mA or more
NOTE 1: When operating paramter U3 set to "2", effective
to contact input.
PV input 2 when DI8=ON
PV input 1 when DI8=OFF
(NOTE 1)
21
22
Auxiliary input
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
j
15 V DC Power Supply Wired to Sensor in
Two-wire System Configuration
12
13
14
15
100V
Two-wire
transmitter
PV input
0.4-2.0 V DC
signal
Loop power
supply
14.5-
18.0 V DC
External
resistor
(Note)
4-20mADC
OT1=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT1=1
Correspondence between parameter OT1 and control output types
Time proportional control
Voltage pulse output (terminals and )
OT1=2
Current output
(terminals and )
OT1=3
On-off control
Relay output (terminals , and )
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to change the control output type.
1 2 3
16 17
16 17
1 2 3
Default: 1-5 V DC
UT
UT
12
13
+
-
mV/V input
* Factory-set to
PV retransmission.
* Retransmission output 1
is not available if a
15 V DC loop power
supply is used.
Control output
14
15
Retransmission output 1*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply*
14.5-18.0 V DC
(21 mA DC max.)
* Retransmission output 2 is available
only when relay is selected as the
type of control output.
Default: 4-20 mA DC
-
+
-
+
PV input 1
PV input 2
16
17
Continuous/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
* Not configured at factory before shipment
12
13
Note: Connecting a 250 resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41 ).
j
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
Default: Unspecified
retransmission type
Load resistance: 600 or less
A
llowable range: 100-240 V AC (610%)
(free voltage)
50/60 Hz shared
Note: Connecting a 100 V resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
Note: Select this option from the OT1 parameter.
Note: External Contact Input
If the power is turned on when
the external contact input is OFF,
the mode (SPN, R/L, or A/M)
existing before the power is turned
off will be continued.
(except for RUN/STOP)
16
UT520 Loop Control with PV Switching, Terminal Arrangements
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E
1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
External Dimensions and Panel Cutout Dimensions
PV
AL1 2 3 4
A/M
SET/ENT
LP2 CAS
REM MAN
11
96
10048
1 to 10 mm
(Panel thickness)
Small bracket
112
91.8
Small bracket
17
Unit: mm
General installation
70 min.
Side-by-side close installation
[(N-1)348+45]
0
+0.8
+0.6
0
92
(53)
145 min.
“N” stands for the number of controllers to be installed.
+ 0.8
92
0
+ 0.6
45
(25)
0
However, the measured value applies if N $ 5.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation GS 05D01C02-02E 1st Edition Mar. 31, 2000-00
<<Contents>> <<Index>>
Model and Suffix Codes
Model Suffix Code Description UT520 Type
Optional functions
Standard accessories: Brackets (mounting hardware), unit label, User’s Manuals, and User’s Manual (reference) (CD-ROM
version).
Specify the required optional function codes according to the UT mode to be used.
Correspondence between UT mode and suffix code
Digital indicating controller (provided with retransmission output and 15 V DC loop power supply as standard)
-0 Standard type 0 None
7 Communication, auxiliary analog (remote) input, and 2 additional DIs 8 Auxiliary analog (remote) input and 2 additional DIs
18
Single-loop control (UT mode 1)
Cascade primary loop control (UT mode 2) Cascade secondary loop control (UT mode 3) Cascade control (UT mode 4) Loop control for backup (UT mode 5) Loop control with PV switching (UT mode 6) Loop control with PV auto-selector (UT mode 7) Loop control with PV-hold function (UT mode 8)
00 07 08UT mode Specification code
Cond.
N/A N/A N/A N/A N/A N/A
Cond.
App.
App. App. App. App. App. App. App.
Cond.: Remote target setting not available
App.
App. App. App. App. App. App. App.
The remote target setting function requires the auxiliary analog input (optional function) to be specified.
Auxiliary analog input is used for the cascade input. Auxiliary analog input is used for the tracking input. Auxiliary analog input is used for the PV input 2. Auxiliary analog input is used for the PV input 2. Cond.: Remote target setting not available
The remote target setting function requires the auxiliary analog input (optional function) to be specified.
Remarks
App.: Function available, Cond.: Function available conditionally, N/A: Function not available
Correspondence between the Model and Suffix Codes, and the Contact Input/Output
Terminals Provided
Check the model ordered and the presence/absence of contact inputs and outputs in the following table.
indicate that the contacts are available.
Model and Suffix Codes
UT520-00 UT520-07 UT520-08
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DO1 DO2 DO3 DO4
✓ ✓ ✓
Contact input terminals Contact output terminals
DI8 DO5
✓ ✓ ✓✓✓
DO6 DO7
Items to be Specified When Ordering
Model and suffix codes, necessary/unnecessary of User’s Manual or QIC.
All Rights Reserved. Copyright © 2000, Y okogawa M&C Corporation
GS 05D01C02-02E 1st Edition Mar. 31, 2000-00
Loading...