Model UT450 Digital Indicating Controller is a simple,
micro-processor based digital indicating controller with
basic control capability and the user-friendly large
numerical display. The UT450 features as standard many
functions which are necessary for various control applications, and all of these functions such as control function,
control computation function, signal computation function,
etc. can be configured by using the keys on the front panel.
The instrument has an Auto-tuning, an overshoot
suppressing function "SUPER" and a hunting suppressing
function "SUPER2" built in as standard. It is suitable for a
diverse range of applications, with position-proportional
control and heating/cooling control models also available.
■Main Features
• Extra-large digital display allows the indicated values to be
read even from a long distance. LEDs of 20 mm height are
used for the process variable display. This is a 5-digit
display for higher resolution.
• Enabling the operator to start control operation immediately after simply entering the settings.
• Parameters can be easily set using a personal computer.
("Parameter setting tool (model LL100)" sold separately is
required.)
• Universal input and output enables users to set or change
freely the type of measured inputs, measurement range,
type of control output, etc. from the front panel.
• In addition to general purpose models (universal output),
the position-proportional model (relay output) or the
heating/cooling control model (universal output) can be
specified.
• Contact inputs (up to 7 points) can be employed and
functions assigned to each contact (The maximum number
of points varies depending on the specification code.)
• Various communication function are provided.
Communication is possible with personal computer,
programable logic controller, and other controllers.
■Functional Specifications
● Control Computation Functions
The following control computation functions can be
selected:
Target setpoint and PID parameter:
Zone PID selection:
Auto-tuning:
"SUPER" function:
Continuous PID control, Time-proportional
PID control, Relay ON/OFF control, Positionproportional PID control (for UT450-1■■) and
Heating/Cooling control (for UT450-2■■).
Maximum eight sets of target setpoint and PID
parameter can be set.
PID parameter set switching in up to 7
measured input zones.
Available as standard.
Overshoots generated by abrupt changes in the
target setpoint or by disturbances can be
suppressed.
UT450
UT450E
“E” indicates the
model with expanded
functions.
"SUPER2" function:
The function stabilizes the state of control that
is unstable due to hunting, etc. without
requiring any change in PID constants, when
the load and/or gain varies greatly, or when
there is a difference between the characteristics of temperature zones.
Preset output function:
When the instrument is in STOP mode,
measured input is burnt-out, or an abnormality
is found in an input circuit, a preset setpoint is
output as a control output.
Control cycle time: 200 ms
Operation Mode Switching
(Note: Communication enables all the following
mode switching to be executed.)
AUTO/MANUAL switching:
Bumpless switching between automatic
operation mode and manual control mode is
available by using the front key or contact
input. The contact input has priority over
front key input or switching by communication.
RUN/STOP switching:
Switching by contact input (bumpless for
switching from STOP to RUN). The contact
input has priority over switching by communication. In RUN mode, control computation is
activated. In STOP mode, control computation ceases and a preset value is output as a
control output while other functions operate
normally.
REMOTE/LOCAL switching:
Switching between remote setpoint and local
setpoint by instrument operation or contact
input. The contact input has priority over
instrument operation or switching by
communication. For remote to local switching, either bumpless tracking (employing the
remote setpoint on switching as the local
setpoint) or without tracking (directly
switching the local setpoint) can be specified.
control) 0.0% available for ON/OFF control
Integral time: 1 to 6,000 s, or OFF (for Manual reset)
Derivative time: 1 to 6,000 s, or OFF
ON/OFF control hysteresis: 0.0 to 100.0% of measured
input range width
Preset output: -5.0 to 105.0% (0 mA or less cannot be
output)
Output limiter:
Setting range: -5.0 to 105.0% for both high
and low limits
However, "low limit setpoint < high limit
setpoint" must be satisfied.
In case of heating/cooling PID control, upper
limiter for heating and upper limiter for
cooling.
Shutdown function:
When manual control is carried out with 4 to
20 mA output, control output can be output
down to about 0 mA (shutdown is specified
for -5.0% or less).
Rate-of-change limiter for output:
OFF or 0.1 to 100.0%/s
Deadband for heating/cooling control:
-100.0 to 50.0% for output range
Deadband for position-proportional control:
1.0 to 10.0% for output
● Configuration of Input/Output Signal
Measured Input Computations
Input processing, Bias addition (-100.0 to 100.0%), and First
order lag filter (OFF, time constant 1 to 120 s)
Remote Input Computations
(Applied to remote input only)
Input processing, Bias addition (-100.0 to 100.0%), Ratio
multiplication (0.001 to 9.999), First order lag filter (OFF,
time constant 1 to 120 s)
● Alarm Functions
Alarm types:
PV high limit, PV low limit, Deviation high
limit, Deviation low limit, Deenergized on
deviation high limit, Deenergized on deviation
low limit, Deviation high and low limits, High
and low limits within deviation, Deenergized
on PV high limit, Deenergized on PV low
limit, SP high limit, SP low limit, Output high
limit, Output low limit.
Alarm setting range:
PV/SP alarm: -100 to 100% of measured input
range
Deviation alarm: -100 to 100% of measured
input range width
Output alarm: -5.0 to 105.0% of output range
Alarm hysteresis: 0.0 to 100.0% of measured
input range width
Stand-by action:
Stand-by action can be set to make PV/
deviation alarm OFF during start-up or after
SP change until SP reaches the normal region.
Delay timer:
0.00 to 99.59 (minute, second)
An alarm is output when the delay timer
expires after the alarm setpoint is reached.
Setting for each alarm is possible.
Timer function (stabilization of control status notification
event) (Alarm1 only)
This function sets the alarm 1 output to ON
when a preset time (timer setting) elapses after
a PV has reached the control target setpoint
hysteresis band to notify that control
processing has reached its stabilized status.
Restarted in RUN/STOP or target value
switching.
Other alarm actions
Sensor grounding alarm: Detects sensor
deterioration and outputs an alarm.
Falt-diagnosis alarm: For input burn-out, A/D
conversion error, or thermocouple reference
junction compensation error.
FAIL output: Abnormality in software or
hardware.
Number of alarm settings: 4 (maximum)
The alarm status can be read via communication in addition to output as the above alarm
output.
Alarm output points (see also the item "Contact output")
• Number of contact (relay) outputs:
3 (standard)
• Number of contact (transistor open collector)
outputs:
1 (when optional specification code is
specified as 1 or 3)
Any of PV alarm, deviation alarm, SP alarm, output
alarm, Falt-diagnosis alarm, sensor grounding alarm
and FAIL output can be assigned to contacts for the
above number of outputs. However, the timer delay
alarm can be assigned to the alarm 1 output only.
● Display and Operation Functions
PV Display
PV1 is displayed on the 5-digit display. The number of
display digits is 4 or 5. For thermocouple or RTD, data
below the decimal point can be set not to display. The
display range is -19999 to 30000 and the display span is
30000 or less. [450.00 appearing in the product photograph
on page 1 cannot actually be displayed.]
Setpoint Display
A parameter name is displayed in the 3-digit display and data
in the 5-digit display. There are four kind of displays of
operation, operating parameter setting, setup parameter
setting and SELECT display.
Operating display:
Setpoint, control output, etc. are displayed.
Operating parameters setting display:
The Operating parameters, which are mainly
changed during operating, such as PID
constant, are displayed.
Setup parameters setting display:
The Setup parameters to configure the
functions of the instrument before starting
operation are displayed.
Up to five displays which are frequently
accessed can be selected from the Operating
parameters setting display and Setup parameters setting display to be displayed in the
SELECT display.
Status Lamps
Alarm indicating lamp:
Four lamps, AL1, AL2, AL3, and AL4
Operation mode indicating lamp:
REM (remote operation), MAN (manual mode
operation)
Deviation indicating lamp:
▲Plus deviation, ▼Minus deviation, and
deviation in normal range
Operation Keys
m, n keys:Increase or decrease setpoints and other
parameters displayed in the setpoint display.
SET/ENT key: Used for setting or changing set data,
switching the displayed contents, and
switching operation modes except for A/M.
A/M key: Operation mode switching (Auto/Man)
Security Function
Key-lock from parameters setting and
operation can be inhibited by a password.
Parameters are set via communication from a
personal computer.
UT450
Measured value (PV) display unit
Displays PV and error codes when
errors are detected.
Data display unit
Displays setpoints (SP), output
values, valve opening, or
parameters.
Operation keys
Increase/decrease of the setting data (m, n)
Screen switching/parameter selection/entry of set
data (SET/ENT)
Auto/manual operation mode switching (A/M)
● Communication Functions
(For optional specification code ■■1 or ■■2 only)
This controller has 4 types of communication protocol with
one communication interface. Communication is possible
with personal computer, programmable logic controller, and
other controllers.
Communication Protocol
Computer link communication:
Communication protocol with a personal
computer
Ladder communication:
Communication protocol with programmable
logic controllers.
MODBUS communication:
Communication protocol with a personal
computer or PLC.
Coordinated operation:
Protocol for coordinated operation with more
than one GREEN SERIES controller. The
UT450 controller can be connected as a
master or slave station.
Alarm indicating lamps
Displays alarms (AL1, AL2, AL3,
or AL4).
RS-485 Communication Interface
The RS-485 communication interface (conforms to EIA
RS485) can be used for personal computer link, ladder
communication, MODBUS communication, or for coordinated operation.
Maximum number of connectable controllers:
GREEN SERIES controller 31
Maximum communication distance: 1200 m
Communication method:
Examples of Communication System Configuration Diagram
(1)
Personal computer link communication/MODBUS communication
4
(2) Ladder communication
Personal computer
PV
PV
PV2
AL
REM
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
REM
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
UT450, UT420
Digital indicating controller
(3) Coordinated operation
PV
PV2
UP750, UP550 Program controller
AL
REM
MAN1
MAN2
STP
CAS
or
A/M
DISP
SET/ENT
UT750, UT550, UT520, UT450, UT420 Digital indicating controller
PV
PV
PV2
AL
REM
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
REM
REM
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
REM
MAN1
MAN2
STP
CAS
A/M
DISP
SET/ENT
UT450, UT420
Digital indicating controller
■Hardware Specifications
● Input/Output Signal Specifications
Measured Input Signal
Number of input points: 1
Input type, measurement range, and measurement
Sampling period: 200 ms
Burnout detection:
Input bias current: 0.05 µA (for TC or RTD b-terminal)
Specified current(RTD): about 0.13 mA
Input resistance: 1 MΩ or more for TC or mV input
Allowable signal source resistance:
Allowable leadwire resistance (for RTD input):
Allowable input voltage:
Noise rejection ratio:
accuracy:
The type of input and measurement range can
be specified using the input range code shown
in the table below.
Activated for thermocouple (TC) input, RTD
input, or standard signal of 0.4 to 2 V or 1 to
5 V.
Possible to specify a travel of upscale,
downscale, or off.
For standard signal input, set to burn out at
0.1 V or less.
Approx 1 MΩ for DC voltage input
250 Ω or less for TC or mV input
Signal source resistance effect 0.1 µV/Ω or
less
2 kΩ or less for DC voltage input
Signal source resistance effect
Approx. 0.01%/100 Ω
Maximum 150 Ω/one wire (Lead resistances
of three wires must be equal.)
However, it must be 10 Ω/one wire for the
range of -150.0 to 150.0°C.
Effect of wiring resistance: ±0.1°C/10Ω
±10 V DC for TC/mV/RTD input
±20 V DC for DC voltage input
Normal mode40 dB (50/60 Hz) or more
Common mode 120 dB (50/60 Hz) or more
Set the data item PV input type “IN” to the OFF option to leave the PV input type undefined.
-270.0 to 1370.0°C
-270.0 to 1000.0°C
-200.0 to 500.0°C
-200.0 to 1200.0°C
-270.0 to 400.0°C
0.0 to 400.0°C
0.0 to 1800.0°C
0.0 to 1700.0°C
0.0 to 1700.0°C
-200.0 to 1300.0°C
-270.0 to 1000.0°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 2300.0°C
0.0 to 1390.0°C
0.0 to 1900.0°C
0.0 to 2000.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
-200.0 to 850.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-450.0 to 2500.0°F
-450.0 to 2300.0°F
-200.0 to 1000.0°F
-300.0 to 2300.0°F
-450.0 to 750.0°F
-200.0 to 750.0°F
32 to 3300°F
32 to 3100°F
32 to 3100°F
-300.0 to 2400.0°F
-450.0 to 1800.0°F
-300.0 to 1600.0°F
-300.0 to 750.0°F
-200.0 to 1000.0°F
32 to 4200°F
32.0 to 2500.0°F
32 to 3400°F
32 to 3600°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
-300.0 to 1560.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
Display range
-19999 to 30000
Display span 30000 or
less (Decimal point
position changeable)
±0.1% ±1 digit of instrument range at 0°C or more
±0.2% ±1 digit of instrument range at less than 0°C
• However, ±2% ±1 digit of instrument range for type K
at temperatures less than -200°C.
However, ±1% ± 1 digit of instrument range for type T
•
at temperatures less than -200°C.
±0.15% ±1 digit of instrument range at 400°C or more
±5% ±1 digit of instrument range at less than 400°C
±0.15% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range
±0.25% ±1 digit of instrument range for temperature at less than 0°C
±0.1% ±1 digit of instrument range at 0°C or more
±0.2% ±1 digit of instrument range at less than 0°C
• However, ±1.5% ±1 digit of instrument range for
type E at temperature less than -200°C.
±0.2% ±1 digit of instrument range
±0.1% ± 1 digit of instrument range
±0.5% ±1 digit of instrument range at 800°C or more
Accuracy not guaranteed for temperature less than
800°C
±0.2% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range (Note1) (Note2)
±0.2% ± 1 digit of instrument range (Note1)
±0.1% ± 1 digit of instrument range (Note1) (Note2)
±0.2% ± 1 digit of instrument range (Note1)
±0.1% ± 1 digit of instrument range
-10.00 to 20.00 mV
0.0 to 100.0 mV
Note1:The accuracy is ±0.3°C of instrument range ±1 digit for a temperature range from 0 to 100°C.
Note2:The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from –100 to 200°C.
*1:Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60Hz power frequency)
Instrument accuracy
*1
Remote Input Signal
(UT450-■■1, -■■2, or -■■4 only)
Functions: Remote input (analog input) for setting SP
Input type: Settable within the range of voltage input
1 to 5 V DC, 0 to 2 V DC, 0 to 10 V DC or
0.4 to 2.0 V DC.
Number of inputs: 1 point
Sampling period: 200 ms
Input resistance: Approx. 1 MΩ
Input accuracy: ±0.3% ± 1 digit of F.S. for 0 to 2 V DC
input
24V DC Loop Power Supply for Sensor
Supplies power to the 2-wire transmitter. The current signal
is converted to a voltage signal by placing a resistor
(arbitrary from 10 to 250 Ω) and is read by the measured
input block.
Supply voltage 21.6 to 28.0 V DC, maximum supply current
about 30 mA (only for models with 24 V DC loop power
supply)
■24 V DC Power Supply Wiring to Two-wire Sensor
±0.2% ± 1 digit of F.S. for 0 to 10 V DC input
±0.375% ± 1 digit of F.S. for 0.4 to 2.0 V DC
range
±0.3% ± 1 digit of F.S. for 1 to 5 V DC range
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
Feedback Resistance Input Signal
Provided for UT450-1■■ only. Valid for position propor-
tional PID control.
Two-wire transmitter
4-20mADC
External
resistor
(Note)
250Ω
12
PV input
1 to 5 V DC signal
13
Sensor power
43
44
supply
21.6 to
28.0 V DC
Slidewire resistance:
Total resistance 100 Ω to 2.5 kΩ (with
detection of slidewire breakage)
Note : Connecting a 250Ω resistor to the terminals is optional.
Model : X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Any of the PV, target setpoint or control output is output. Or
this can be used for 15 V DC sensor power supply.
Number of output points: 1
Output signal: 4 to 20 mA DC
Load resistance: 600 Ω or less
Output accuracy: ±0.1% of span
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
When using for 15 V DC sensor power supply:
Supply voltage 14.5 to 18.0 V DC, maximum supply
current about 21 mA (with the protection circuit at field
shortcircuit)
Control Outputs
Select 1 or 2 points (UT450-2■■) from the following output
types depending on the product model. Relay contact output
for position proportional PID control (UT450-1■■).
Current output
Number of output points: 1 or 2 (for heating/cooling
type) (switchable to voltage pulse output)
Output signal: 4 to 20 mA DC
Load resistance: 600 Ω or less
Output accuracy:
±0.1% of span
Performance in the standard operating
conditions (at 23±2°C, 55±10% RH, and 50/
60Hz power frequency)
Voltage pulse output
Number of output points: 1 or 2 (for heating/cooling
model) (switchable to current output)
Output signal:
ON voltage 12 V DC or more (load
resistance 600 Ω or more; current on shortcircuiting about 30 mA)
OFF voltage 0.1 V DC or less
Resolution: 10 ms or 0.1% of output value, whichever is
greater.
Relay contact output
Number of output points: 1 or 2 (for heating/cooling
model)
Output signal: At three terminals of NC, NO, and
Common
Contact rating: 250 V AC, 3 A or 30 V DC, 3 A
(resistive load)
Resolution: 10 ms or 0.1% of output value, whichever is
greater.
Contact Inputs
Usage:Target setpoint switching, REMOTE/LOCAL
switching, or RUN/STOP switching
Number of input points:
Varies with optional codes (as shown below):
Model and Suffix Code Number of Input Points
UT450- ■ 02
■
UT450UT450UT450UT450-
17
■
23
■
36
■
43
Input type: Non-voltage contact input or transistor open
collector input
Input contact rating: 12 V DC, 10 mA or more (for non-
voltage contact input)
On/off detection:
For non-voltage contact input,
On contact resistance 1 k Ω or less;
Off contact resistance 20 k Ω or more
For transistor contact input,
On 2 V or less;
Off leak current 100 µA or less
Minimum retention time for status detection: 0.6 s
Contact Outputs
Usage:Alarm output, FAIL output
Number of output points:
Varies with optional codes (as shown below):
Model and Suffix Code Number of Output Points
UT450- ■ 03
■
UT450UT450UT450UT450-
14
■
23
■
34
■
43
Relay contact rating: 240 V AC, 1 A or 30 V DC, 1 A
Transistor contact rating: 24 V DC, 50 mA
● Display Specifications
Measured value (PV) display:
Data display:3 digits + 5 digits, seven-segment red color
Status indicating lamps: LEDs
5-digit seven-segment red color LED display;
height of letters 20 mm
LED display; height of letters 9.3 mm
● Conformance to Safety and EMC Standards
Safety standard:
EMC standard:
Conforms to IEC1010-1: 1990 and EN610101: 1992
Certified for CSA1010
The overvoltage category of each input is
CAT II (IEC1010-1)
Certified for UL508 application
To the following EMC standards. During test,
the controller continues to operate with the
measurement accuracy within ±20% of the
range:
For EMI (emission), EN55011, Class A Group 1
For EMS (immunity), EN50082-2: 1995
● Construction, Installation, and Wiring
Construction: Dust-proof and Drip-proof front panel
Material of the body: ABS resin and polycarbonate
Case color: Black
Weight:Approx. 1 kg or less
External dimensions: 96W × 96H × 100D (from the panel
Mounting: Direct panel mounting; mounting bracket, one
Panel cutout dimensions:
Mounting attitude:
conforming to IP55.
For side-by-side close installation, controller
loses its dust-proof and drip-proof protections.
face) (mm)
each for upper and lower mounting
92
+0.8
0
W ×
92
+0.8
H (mm)
0
Up to 30 degrees from horizontal; Must not
face downward.
With M3.5 screw terminals (for signal, power
and grounding wiring)
● Power Supply and Isolation
Power supply: Rated voltage 100 to 240 V AC (±10%),
50/60 Hz
Power consumption: MAX. 20 VA (MAX. 8.0 W)
Memory backup: EEPROM. Service life approx. 100000
times of writings
Withstanding voltage:
1500 V AC for 1 min.
between primary terminals and secondary
terminals (Note)
1500 V AC for 1 min.
between primary terminals and ground
terminal (Note)
1500 V AC for 1 min.
between ground terminal and secondary
terminals
500 V AC for 1 min.
between secondary terminals
where primary terminals stand for power
and relay output terminals and secondary
terminals, analog input and output signal
terminals, voltage pulse output terminals,
and contact input terminals.
Note. The withstanding voltage is specified as 2300 V AC
per minute to provide a margin of safety.
Isolation resistance:
20 MΩ or more for 500 V DC applied
between power terminals and ground terminal
Grounding: Class 3 grounding (grounding resistance of
100 Ω or less)
Isolation Specifications
Measured input terminal :
Isolated from other input/output terminals, but
not isolated from internal circuits.
Remote input terminal:
Isolated from other input/output terminals and
internal circuits.
24 V DC loop power supply terminal:
Isolated from other input/output terminals and
internal circuits.
Terminals for control output (current or voltage pulse) and
retransmission output:
Not isolated between control output and
retransmission output terminal, but isolated
from other input/output terminals and internal
circuits.
Relay contact control output terminals:
Isolated from other contact output terminals,
other input/output terminals and internal
circuits.
Contact input terminals:
Not isolated from other contact input
terminals mutually and communication
terminals, but isolated from other input/output
terminals and internal circuits.
Relay contact alarm output terminals:
Not isolated from contact input terminals, but
isolated from other input/output terminals and
internal circuits.
Feedback slidewire resistance input terminals:
Not isolated from control output terminals
(current or voltage pulse) and retransmission
output, but isolated from other input/output
terminals and internal circuits.
Power terminals:
Isolated from other input/output terminals and
internal circuits.
Ground terminal:
Isolated from other input/output terminals and
internal circuits.
● Environmental Conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C (40°C or less in close
Temperature change rate limit:10°C /h or less
Ambient humidity: 20 to 90% RH (no condensation)
Magnetic field: 400 A/m or less
Continuous vibration (5 to 14 Hz):
Continuous vibration (14 to 150 Hz):
Short period vibration: 14.7 m/s
Shock: 147 m/s
Installation altitude: 2000 m or less above sea level
Warm-up time: 30minutes or more
Transportation and storage conditions:
Temperature: -25 to 70°C
Temperature change rate limit:20°C /h or less
Humidity: 5 to 95% RH (no condensation)
Effects of operating conditions
Effect of ambient temperature:
Effect of power supply fluctuation (within rated voltage
mounting side-by-side)
Peak-to-peak amplitude 1.2 mm or less
2
or less
4.9 m/s
2
or less, 11 ms
2
, 15 s or less
Whichever is greater, ±1 µV/°C or ±0.01%
of F.S./°C for voltage or thermocouple
inputs.
±0.02% of F.S./°C for remote input
±0.05°C/°C (ambient temperature) or less
for RTD inputs.
±0.05% of F.S./°C or less for analog
outputs.
range):
Whichever is greater, ±1 µV/10 V or
±0.01% of F.S./10 V for remote inputs.
±0.05% of F.S./10 V or less for analog
outputs.
* Wiring can only be carried out for controllers with 24 V
DC sensor power supply.
Power supply
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Alarm output
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
Common
Alarm-1 output
Alarm-2 output
Alarm-3 output
Common
Alarm-4 output
*
DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
Correspondence between parameter DIS and external contact input functions
When DIS=4
STOP
when DI3=ON
RUN when DI3=OFF
AUTO when DI4=ON
MAN when DI4=OFF
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=3
STOP
when DI1=ON
RUN when DI1=OFF
2.SP when DI2=ON
1.SP when DI2=OFF
AUTO when DI3=ON
MAN when DI3=OFF
No function
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=2
AUTO when DI1=ON
MAN when DI1=OFF
2.SP when DI2=ON
1.SP when DI2=OFF
STOP
when DI3=ON
RUN when DI3=OFF
No function
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=1 (Factory-shipped setting)
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=0
No function
No function
No function
No function
No function
No function
No function
Remote when R/L=ON
Local when R/L=OFF
Common
When switching target
SP 1 to 4:
Contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
+
-
+
-
+
-
+
-
Retransmission output
4-20 mA DC
15 V DC sensor power supply
14.5-18.0VDC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
* If 15 V DC sensor power supply is used,
retransmission output cannot be used.
Installation category (overvoltage category): II (IEC1010-1)
NOTE
21
22
Remote input
* Wiring can only be carried out for
controllers with remote input.
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
RS-485 communication
TC input
RTD input
mV/V input
21.6-28.0VDC
(30 mA DC max.)
43
44
+
-
Default: 1-5 V DC
UT
UT
12
13
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41 ).
j
Receiving 4-20 mA DC Current
Signals with the Controller
250 Ω
4-20mA
-
+
Load resistance: 600
Ω or less
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
Allowable range: 100 to 240 V AC (610%)
(free voltage)
50/60 Hz shared
* Alarm-4
output is
optional
specification
PV input
* Not configured at factory before shipment
0%
100%
47
46
45
Relay
Transistor
DI3
DI4
1.SP2.SP 3.SP4.SP
ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP
ON
ONOFF
OFF
ON
ON OFF
OFF
DI5
DI6
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
When switching target SP 1 to 8:
* If all of the contact inputs are set to OFF,
the controller uses the immediately
preceding target setpoint.
Note: External Contact Input
If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued.
(except for RUN/STOP)
j
Receiving 4-20 mA DC Current
Signals with the Controller
13
■UT450 Position Proportional Type (Model UT450-1m or UT450-4m)
General installationSide-by-side close installation
Large bracket
112
91.8
Small bracket
[(N-1)396+92]117 min.
+0.8
0
14
Unit: mm
(53)
145 min.
"N" stands for the number of controllers to be
installed.
92
+0.8
0
92
+0.8
0
(25)
However, the measured value applies if N $ 5.
■Model and Suffix Codes
ModelSuffix CodeDescription
UT450
Type
Optional functions
-0Standard type
-1Position proportional type
-2Heating/cooling type
-3Standard type (with 24 V DC sensor power supply)
-4Position proportional type (with 24 V DC sensor power supply)
Digital indicating controller (provided with retransmission output and 15 V
DC sensor power supply as standard)
0None
1
With communication, remote input, 5 additional DIs, and 1 additional Alarm
2With communication, remote input, and 1 additional DI
3With 4 additional DIs and 1 additional Alarm
4With remote input and 1 additional DI
Standard accessories: Brackets (mounting hardware), unit label, User’s Manuals, and User’s Manual Reference (CD-ROM
version).
■Items to be Specified When Ordering
Model and suffix codes, necessary/unnecessary of User’s Manual or QIC.