Yokogawa UT350L Data sheet

<<Contents>> <<Index>>
General Specifications
Model UT350L Limit Controller
GS 05D01D21-01E
Overview
The UT350L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.
The UT350L features universal input, two alarm outputs, retransmission output, a timer to count the total time the setpoint is exceeded, and a register to retain the maximum temperature reached.
The RS485 communication interface is available optionally.
Features
• The large LED display of measured value whose character is 20mm in height allows the good readability.
• Universal input is provided. The input type can be set and changed easily by software.
• Retransmission function is included in the standard features.
UT350L
SP
12
12
Function Specifications
Limit Control Function
Setpoint : 1 Control type : high limit or low limit Limit action : latching
When measured value (PV) exceeds the setpoint(SP), both the “Exceeded” lamp and “OUT” lamp turn on.(1) “Exceeded” lamp turns off when PV goes into normal status, however, “OUT” lamp remains lit.(2) “OUT” lamp turns off when the confirmation is done with pressing the “RESEST” key by the operator.(3) The confirmation(RESET) is not allowed while PV exceeds SP.(4)
State of Output Relay
State of output relay is de-energized whenever OUT lamp is lit. When PV has not exceeded SP since power-on, state of output relay is de-energized. (NC terminal : CLOSE, NO terminal : OPEN) and after confirmation is done, the state of output relay is energized. (NC terminal : OPEN, NO terminal : CLOSE) It is also possible to make the relay energized immediately after power-on by the software setting. At power-off, the relay is de-energized (NC terminal : CLOSE, NO terminal : OPEN).
Control parameter setting range:
ON/OFF hysteresis band : 0.0 to 100.0 of instrument range width.
Resrart mode:
Relay status at power-on can be selected.
EXCEEDED
Lamp
OUT
Lamp
PV
EXCEEDED
Lamp
OUT
Lamp
PV
SP
power off
power on
&
not over temp
(Settable as off, either)
3
(not accepted)
1
243
confir-
mation
43
confirmation
confirmation
(not accepted)
confirmationconfirmation
lit
off
lit
off
confir-
mation
lit
off
lit
off
GS 05D01D21-01E
© Copyright Apr. 1996 (YK)
<<Contents>> <<Index>>
2
Signal Computation Function
Measured input computation:
Bias addition (-100.0 to 100.0 % of measured input range width), and first-order lag filter (time constant off or 1 to 120 s)
Contact input function:
Limit output confirmation
Alarm Function
Types of alarm functions are provided. The alarm status is indicated by the alarm lamp on the front panel. Also, two points among them can be output as relay contact outputs. Alarm types:
PV high limit, PV low limit, Deviation high limit, Deviation low limit, De-energized on deviation high limit, De-energized on deviation low limit, Deviation high and low limits, Deviation within high and low limits, De-energized on PV high limit,
De-energized on PV low limit. Alarm output: 2 points. Setting ranges for PV alarm and deviation alarm:
PV alarm: -100.0 to 100.0% of measured input range Deviation alarm: -100.0 to 100.0% of measured input
range span
Alarm hysteresis width: 0.0 to 100.0% of measured
input range span
Waiting action:
Waiting action can be set to make PV/deviation alarm
stand-by during start-up until PV reaches the normal
region. Fault diagnostic alarm:
Input burnout, A/D conversion error, thermocouple
reference junction compensation error. FAIL output:
Software failure and/or hardware failure. When in fail, retransmission output and alarm output become 0% or OFF.
Display and Operation Function
PV display:
In 4-digit digital display of engineering unit
Setpoint display:
Various data, such as the setpoint (SP), are displayed by selection on the 4-digit digital display.
Status indicating lamps:
2 alarm indicator lamps: AL1, AL2
Exceeded lamp: Lit when PV exceeds SP
Output status lamp: Lit when output relay is de-
energized.
Operation keys:
and keys: Increase or decrease setpoints and
various parameters.
SET/ENT key: For data setting or call-up/selection of
various parameters.
RESET key: Confirms the limit status and resets the
output.
Security function:
An operation-inhibiting mode using a password is
provided.
Communication Specifications (op-
tional)
This controller has a communication function and can be connected to a personal computer, programmable controllers or other GREEN Series controllers. Communication protocol:
Computer link communication: Communication protocol
with a personal computer.
Ladder communication: Communication protocol with
programmable controller.
Communication interface:
Communication protocol: Computer link or ladder
communication Standards: EIA RS485 Maximum number of connectable controllers: 31
GREEN Series controllers Maximum communication distance: 1,200 m Communication method: Two-wire half duplex or four-
wire half duplex, start-stop synchronization,
non-procedural. Communication rate: 600, 1200, 2400, 4800, 9600 bps
Hardware Specifications
PV Input Signal
Number of input points : 1 Input system:
The types of input/measurement ranges can be set
using software from a list of inputs. Types of inputs, measurement ranges and measurement accuracy: Refer to the table on page 4. Burnout detection:
Functions with a thermocouple (TC), RTD, standard signal 0.4 to 2 V, and 1 to 5 V. Can be specified as upscale, downscale, and off. For
standard signal, judged as burnout at 0.1 V or less. Input bias current : 0.05 µA (for TC/RTD) Input resistance:
1 M or more for TC/mV About 1 M for DC voltage input
Allowable signal source resistance:
250 or less; effect of permissible signal source
resistance 0.1 µV/ or less for TC/mV
2 k or less; effect of permissible signal source
resistance 0.01%/100 or less for DC voltage
Allowable leadwire resistance:
Max. of 150 /wire (resistance in each of three wires
must be equal) for RTD.
However, 10 /wire in the range of -150.0 to 150.0°C. Effect of permissibe leadwire resistance:
0.1°C/10 or less
Allowable input voltage:
± 10 V DC for TC/mV/RTD ± 20 V DC for DC voltage
Noise rejection ratio:
Normal mode 40 dB (50/60 Hz) or more Common mode 120 dB (50/60 Hz) or more
Reference-junction compensation error:
± 1.0°C (15 to 35°C), ± 1.5°C (0 to 15°C, 35 to 50°C) Applicable standards : JIS, IEC, or DIN for TC and RTD Response time: 2 second or less, 63% (10 - 90%)
(The time required for transmission output to reach 63% of the maximum excursion when PV abruptly changes from 10% to 90%)
All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation
GS 05D01D21-01E 4th Edition Apr. 02, 2007-00
<<Contents>> <<Index>>
3
Retransmission Output
Either PV or target setpoint is output.
Number of output points: 1 Output signal: 4 to 20 mA DC Load resistance: 600 Ω or less Output accuracy: ± 0.3% of span
Control Output
The control output is a relay output.
Number of output points : 1 Output signal: Three terminals for NC, NO, and
Common transfer-contacts
Contact rating: 250 V AC, 3 A or 30 V DC, 3A (resistive
load)
Resolution: 10 ms
Contact Input
Usage: Confirmation of limit output Number of input points: 1 Input type: Voltage-free contact input or transistor contact
input Input contact rating: 12 V DC, 10 mA or more On/off determination:
For contact input,
ON = contact resistance of 1 kΩ or less, OFF = contact resistance of 20 k or more.
For transistor contact input,
ON = 2 V or less, OFF = leakage current of 100 µA or less.
Minimum retention time for status detection: 1 s
Contact Output
Usage: Alarm output and FAIL output Number of relay contact output points: 2 Relay contact rating: 240 V AC, 1 A or 30 V DC, 1 A
Display Specifications
PV display: 4-digit, 7-segment red LED; character height -
20 mm Setpoint display: 4-digit, 7-segment red LED; character
height - 9.3 mm Status indicating lamps : LEDs
Conformance to Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE), approved by
C22.2 No.61010-1, approved by UL508. Certified for FM-3810 and FM-3545. Installation category : CAT. II Pollution degree : 2 (IEC/EN61010-1, C22.2 No.61010-1) Measurement category : I (CAT. I : IEC/ EN61010-1) Rated measurement input voltage : 10V DC max.(across terminals), 300V AC max.(across ground) Rated transient overvoltage : 1500V (Note) Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in Measurement category I, and is not the value which guarantees an apparatus performance.
EMC standards:Complies with EN61326, EN61000-3-2,
EN61000-3-3 and EN55011 (CE). Class A Group 1. During test, the controller continues to operate with the measurement accuracy within ±20% of the range.
Construction, Mounting, and Wiring
Construction: Front panel drip-proof (IP55 compatible) Material: ABS resin and polycarbonate Case color: Black Weight: Approx. 1 kg or less External dimensions: 96 (width) x 96 (height) x 100
Mounting: Direct panel mounting; mounting bracket, one
Panel cutout dimensions:
Mounting attitude: Up to 30 degrees above the horizontal.
Wiring: M3.5 (ISO 3.5 mm) screw terminals (signal wiring
(depth) mm
each for upper and lower mounting
92
+0.8
(width) x
0
92
+0.8
0
mm
No downward tilting allowed.
and power/ground wiring as well)
(height)
Status lamps
Alarm(AL1, 2), EXCEEDED, OUT
LED display unit (for PV)
Displays PV, and error code when error is detected.
LED display unit (for SP)
Displays setpoint (SP) and setting item/value of parameters.
Operational keys
Increase/Decrease the setting data (,) Select parameter/Enter the setting data (SET/ENT) Confirm and reset the output (RESET)
All Rights Reserved. Copyright © 1996, Yokogawa Electric Corporation GS 05D01D21-01E 4th Edition Apr. 02, 2007-00
Loading...
+ 4 hidden pages