<<Contents>> <<Index>>
General
Specifications
Model UT150L
Limit Controller
GS 05C01E22-01E
■ General
The UT150L is an FM approved limit controller that can be
configured either as a high limit or as a low limit controller
by a user.
The UT150L features universal input, two alarm outputs,
retransmission output, a timer to count the total time the
setpoint is exceeded, and a register to retain the maximum
temperature reached.
The RS485 communication interface is available optionally.
■ Model and Suffix Codes
Model
UT150L
Control output
Fixed code
Option
Suffix Codes
–R
N
/AL
/EX
/RET
/RS
Descriptions
Limit Controller (1/16 DIN size)
Relay output
Always N
Alarm outputs (2 points)
Digital input (1 point)
PV retransmission output in 4 to 20 mA
Communication function
■ Measured Value Input
The UT100 series allows you to freely change the input type
by software.
Table 1. Measured Input Range
Input Typ
le
hermocou
Platinel
Pt1
Pt1
e
to100m
0 to 5
1 to 5
C volta
to 10
Range(C)Range Code(C
to
-199.9 to 400.
-199.9 to
to 17
-199.9 to
to 400.
to 1
to 400.
-199.9 to 200.
-199.9 to
to 100.
to 5.
Not
to 10.
Range(F
to
to 750.
-
to 750.
-
to 1
2 to 31
1
1
1
1
1
1
2
2
2 to 31
32 to 320
-
to 1
-
to 7
2 to 2
to 750.
-
to 4
4 range
-1999 to 9999, -199.9 to 999.9
-199.99 to 99.99, -1.999 to 9.99
4
4
4
4
4
■ Limit Control Function
When a measured value (PV) exceeds a setpoint (SP),
“EXCEEDED” lamp lights, and “OUT” lamp turns ON (A).
The limit output relay is de-energized then. “EXCEEDED”
lamp turns off when PV goes into normal condition, while
the output (OUT) display lamp stays on as it is (B). The
output (OUT) display lamp turns off when a confirming
operation is done by an operator (C). The way to confirm is
pressing the “ ” key (or by an external contact, according
to the setting of setup parameter DIS). The confirming
operation is not accepted during PV exceeds SP (D) (during
EXCEEDED lamp lights*). State of output relay is deenergized whenever “OUT” lamp is on.
* Check the “HYS” value if the EXCEEDED lamp is not
turn off when PV is lower than SP.
(A) (B) (C) (A) (D) (B)
SP
HYS
PV
EXCEEDED
Lamp
OUT
Lamp
Output
relay
lit
off
lit
off
on
off
Operation
confirmation
(accepted)
confirmation
(not accepted)
GS 05C01E22-01E
© Copyright Sep. 2005 (YK)
2nd Edition Apr. 2007 (KP)
<<Contents>> <<Index>>
■ Hardware Specifications
2
Measured Value (PV) Input
Input: 1 point
•
Input type: Universal; can be selected by software
•
Input accuracy (at 23 ±2°C ambient temperature)
•
Thermocouple: ±2°C±1digit
•
However,
• ±4°C for thermocouple input –200 to –100°C
• ±3°C for thermocouple input –100 to 0°C
• ±5°C for type R and S (±9°C for 0 to 500°C)
• ±9°C for type B (accuracy is not guaranteed for 0 to 400°C)
RTD: ±1°C±1digit
•
Voltage (mV, V): ±0.3%±1digit
•
Sampling period for measured value input: 500ms
•
Burnout detection: Functions for thermocouple
•
or RTD input (burnout upscale only; cannot be
switched off)
Input resistance: 1MΩ or greater for thermocouple or
•
DC mV input. Approx. 1MΩ for DC V input
Maximum allowable signal source resistance :
•
250Ω for thermocouple or DC mV input
2k
Ω
for DC V input
Maximum allowable wiring resistance for RTD input:
•
10Ω/wire (The resistance values of three wires
must be the same.)
Allowable input voltage:
•
±10V DC for thermocouple or DC mV input
±20V DC for DC V input
Noise rejection ratio:
•
Normal mode noise: Min. 40dB (50/60Hz)
Common mode noise: Min. 120dB (Min. 90dB
for DC V input)
Error of reference junction compensation:
•
±1.5°C (at 15-35°C)
±2.0°C (at 0-50°C)
The reference junction compensation cannot be
switched off.
Applicable standards:
•
Thermocouple and resistance temperature
detector JIS/IEC/DIN (ITS90)
Response time:
•
2 second or less, 63% (10 - 90%)
(The time required for transmission output to
reach 63% of the maximum excursion when
PV abruptly changes from 10% to 90%)
Control Output
Output: 1 point
•
Output type:
•
Relay contact output
Contact capacity: 3A at 240V AC or 3A at 30V DC
(with resistance load)
Note: The control output relay cannot be
replaced by users.
Alarm Functions
■Alarm Functions (Option Code /AL)
Alarm types: 22 types
•
(waiting action can be set by software):
PV high limit, PV low limit, Deviation high limit, Deviation
low limit, De-energized on deviation high limit, Deenergized on deviation low limit, Deviation high and low
limits, High and low limits within deviation, De-energized
on PV high limit, De-energized on PV low limit, Fault
diagnosis output, FAIL output
Alarm output: 2 relay contacts
•
Relay contact capacity: 1A at 240V AC or 1A at 30V DC
(with resistance load)
Note: The alarm output relays cannot be
replaced by users.
Measurement
1
2
Retransmission Output
The retransmission output is provided only when
the /RET option is specified.
Output signal: Measured value in 4-20mA DC
•
Maximum load resistance: 600Ω
•
Output accuracy: ±0.3% of span
•
(at 23±2°C ambient temperature)
3
4
Contact Input
The contact inputs are provided only when the /EX
option is specified.
Function: Resetting “exceeded status”
•
Input: 1 point
•
Input type: Non-voltage contact or transistor
•
contact input
Contact capacity: At least 12V/10mA
•
On/off judgment: On state for 1kΩ or less; off state
•
for 20kΩ or greater
Communication Function
The communication function is provided only
when the /RS option is specified. (For details,
read the user’s manual of the communication
functions IM 05C01E22-10E.)
■Communication Protocol
Personal computer link: Used for communication with a
•
personal computer, or UT link module of the FA-M3
controller (from Yokogawa Electric Corporation).
Ladder communication: Used for
•
communication with a ladder communication
module of the FA-M3, or a programmable
controller of other manufacturers.
MODBUS communication: Used for communication
•
with equipment featuring the MODBUS protocol.
■Communication Interface
Applicable standards: Complies with EIA RS-
•
485
Number of controllers that can be connected:
•
Up to 31
Maximum communication distance: 1,200m
•
Communication method: Two-wire half-duplex,
•
start-stop synchronization, non-procedural
Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE),
•
approved by C22.2 No.61010-1, approved by
UL508.
Certified by FM-3810 and FM-3545.
Installation category : CAT. II
Pollution degree : 2 (IEC/EN61010-1, C22.2
No.61010-1)
Measurement category : I (CAT. I :
IEC/EN61010-1)
Rated measurement input voltage : 10V DC
max.(across terminals), 300V AC max.(across
ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safety standard
which is assumed by IEC/EN61010-1 in
Measurement category I, and is not the value
which guarantees an apparatus performance.
Caution: This equipment has Measurement
category I, therefore do not use the equipment
for measurements within Measurement
categories II, III and IV.
Internal Wiring
T
3
4
Entrance
Cable
Description
category
For measurements performed on
CAT.1
circuits not directly connected to MAINS.
For measurements performed on
CAT.2
circuits directly connected to the
low voltage installation.
For measurements performed in
CAT.3
the building installation.
For measurements performed at
CAT.4
the source of the low-voltage installation.
EMC standards: Complies with EN61326,
•
EN61000-3-2, EN61000-3-3 and EN55011
(CE).
The instrument continues to operate at a
measuring accuracy of within ±20% of the
range during tests.
1
Outlet
Remarks
Appliances,
portable equipments,
etc.
Distribution board,
circuit breaker, etc.
Overhead wire,
cable systems,
etc.
Power Supply and Isolation
■ Power Supply
Voltage
Power
supply
Frequency
Maximum power consumption
Memory
Between primary terminals
Withstanding
and secondary terminals
voltage
(See note 1.)
Between primary terminals
Insulation
and secondary terminals
resistance
(See note 1.)
Note 1: The primary terminals are the power supply
terminals and relay output terminals.
The secondary terminals are the analog input and
output terminals, the voltage pulse output
terminals, and the contact input terminals.
■ Isolation
The bold lines below indicate reinforced
isolation, and the broken line indicates functional
isolation.
Power supply terminals
•
(100-240V AC)
Control output terminals
•
(relay contacts)
Alarm output terminals
•
(2 relay contacts)
Note: Neither the measured value input terminals
nor input terminals for the /EX option are
isolated from the internal circuit.
Rated at 100-240VAC (±10%)
50 or 60Hz
8VA max. (4W max.)
Non-volatile memory
1500V AC for 1 minute
20MΩ or more at 500V DC
Measured value input terminals
•
1 input terminals for /EX
•
Internal circui
•
PV transmission output terminals for /RET
•
RS-485 terminals for /RS
•
t
Construction, Mounting, and Wiring
Construction: Dust-proof and drip-proof front
•
panel conforming to IP65.
For side-by-side close installation the
controller loses its dust-proof and drip-proof
protection.
Casing: ABS resin and polycarbonate
•
Case color: Black
•
Mounting: Flush panel mounting
•
Terminals: Screw terminals
•
Environmental Conditions
■Normal Operating Conditions
Warm-up time: At least 30 minutes
•
Ambient temperature:0-50°C (0-40°C when
•
mounted side-by-side)
Rate of change of temperature: 10°C/h or less
•
Ambient humidity: 20-90% RH (no
•
condensation allowed)
Magnetic field: 400A/m or less
•
Continuous vibrations of 5 to 14Hz: Amplitude
•
of 1.2mm or less
Continuous vibrations of 14 to 150Hz: 4.9m/s2
2
•
(0.5G) or less
Short-period vibrations: 14.7m/s2 (1.5G) for 15
•
seconds or less
Shock: 98m/s2 (10G) for 11 milliseconds or less
•
Mounting angle: Upward incline of up to 30
•
degrees; downward incline is not allowed.
Altitude: 2000m or less above sea level
•
■Maximum Effects from Operating
Conditions
(1) Temperature effects
Thermocouple, DC mV and DC V input: ±2µV/°C or
•
±0.02% of F.S./°C, whichever is the larger
Resistance temperature detector: ±0.05°C/°C
•
Analog output: ±0.05% of F.S./°C
•
(2) Effect from fluctuation of power supply voltage (within
rated voltage range)
Analog input: ±0.2µV/V or ±0.002% of F.S./V,
•
whichever is the larger
Analog output: ±0.05% of F.S./V
•
■
Transportation and Storage Conditions
Temperature: –25 to 70°C
•
Humidity: 5 to 95% RH (no condensation allowed)
•
Shock: Package drop height 90cm (when packed in the
•
dedicated package)
All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation
GS 05C01E22-01E 2nd Edition Apr.02, 2007-00