General Specifications
Model UT150L Limit Controller
GS 05C01E22-01E
General
The UT150L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.
The UT150L features universal input, two alarm outputs, retransmission output, a timer to count the total time the setpoint is exceeded, and a register to retain the maximum temperature reached.
The RS485 communication interface is available optionally.
Model and Suffix Codes
Model UT150L
Control output Fixed code Option
Suffix Codes
–R N /AL /EX /RET /RS
Descriptions
Limit Controller (1/16 DIN size) Relay output Always N Alarm outputs (2 points) Digital input (1 point) PV retransmission output in 4 to 20 mA Communication function
Measured Value Input
The UT100 series allows you to freely change the input type by software.
Table 1. Measured Input Range
Input Typ
le
hermocou
Platinel
Pt1
Pt1
e
to100m
0 to 5
1 to 5
C volta
to 10
Range(C)Range Code(C
to
-199.9 to 400.
-199.9 to
to 17
-199.9 to
to 400.
to 1
to 400.
-199.9 to 200.
-199.9 to
to 100.
to 5.
Not
to 10.
Range(F
to
to 750.
-
to 750.
-
to 1
2 to 31
1
1
1
1
1
1
2
2
2 to 31
32 to 320
-
to 1
-
to 7
2 to 2
to 750.
-
to 4
4 range
-1999 to 9999, -199.9 to 999.9
-199.99 to 99.99, -1.999 to 9.99
4
4
4
4
4
Limit Control Function
When a measured value (PV) exceeds a setpoint (SP), “EXCEEDED” lamp lights, and “OUT” lamp turns ON (A). The limit output relay is de-energized then. “EXCEEDED” lamp turns off when PV goes into normal condition, while the output (OUT) display lamp stays on as it is (B). The output (OUT) display lamp turns off when a confirming operation is done by an operator (C). The way to confirm is pressing the “ ” key (or by an external contact, according to the setting of setup parameter DIS). The confirming operation is not accepted during PV exceeds SP (D) (during EXCEEDED lamp lights*). State of output relay is de­energized whenever “OUT” lamp is on. * Check the “HYS” value if the EXCEEDED lamp is not turn off when PV is lower than SP.
(A) (B) (C) (A) (D) (B)
SP
HYS
PV
EXCEEDED Lamp
OUT Lamp
Output relay
lit off
lit off
on off
Operation
confirmation
(accepted)
confirmation
(not accepted)
GS 05C01E22-01E
© Copyright Sep. 2005 (YK)
<<Contents>> <<Index>>
Hardware Specifications
2
Measured Value (PV) Input
Input: 1 point
Input type: Universal; can be selected by software
Input accuracy (at 23 ±2°C ambient temperature)
Thermocouple: ±2°C±1digit
However,
±4°C for thermocouple input –200 to –100°C
±3°C for thermocouple input –100 to 0°C
±5°C for type R and S (±9°C for 0 to 500°C)
±9°C for type B (accuracy is not guaranteed for 0 to 400°C)
RTD: ±1°C±1digit
Voltage (mV, V): ±0.3%±1digit
Sampling period for measured value input: 500ms
Burnout detection: Functions for thermocouple
or RTD input (burnout upscale only; cannot be switched off) Input resistance: 1M or greater for thermocouple or
DC mV input. Approx. 1M for DC V input Maximum allowable signal source resistance :
250 for thermocouple or DC mV input 2k
for DC V input
Maximum allowable wiring resistance for RTD input:
10/wire (The resistance values of three wires must be the same.) Allowable input voltage:
±10V DC for thermocouple or DC mV input ±20V DC for DC V input
Noise rejection ratio:
Normal mode noise: Min. 40dB (50/60Hz) Common mode noise: Min. 120dB (Min. 90dB for DC V input) Error of reference junction compensation:
±1.5°C (at 15-35°C) ±2.0°C (at 0-50°C)
The reference junction compensation cannot be switched off. Applicable standards:
Thermocouple and resistance temperature detector JIS/IEC/DIN (ITS90)
Response time:
2 second or less, 63% (10 - 90%) (The time required for transmission output to reach 63% of the maximum excursion when PV abruptly changes from 10% to 90%)
Control Output
Output: 1 point
Output type:
Relay contact output Contact capacity: 3A at 240V AC or 3A at 30V DC (with resistance load) Note: The control output relay cannot be replaced by users.
Alarm Functions
Alarm Functions (Option Code /AL)
Alarm types: 22 types
(waiting action can be set by software): PV high limit, PV low limit, Deviation high limit, Deviation low limit, De-energized on deviation high limit, De­energized on deviation low limit, Deviation high and low limits, High and low limits within deviation, De-energized on PV high limit, De-energized on PV low limit, Fault diagnosis output, FAIL output Alarm output: 2 relay contacts
Relay contact capacity: 1A at 240V AC or 1A at 30V DC (with resistance load) Note: The alarm output relays cannot be replaced by users.
Measurement
1
2
Retransmission Output
The retransmission output is provided only when the /RET option is specified.
Output signal: Measured value in 4-20mA DC
Maximum load resistance: 600
Output accuracy: ±0.3% of span
(at 23±2°C ambient temperature)
3
4
Contact Input
The contact inputs are provided only when the /EX option is specified.
Function: Resetting “exceeded status”
Input: 1 point
Input type: Non-voltage contact or transistor
contact input Contact capacity: At least 12V/10mA
On/off judgment: On state for 1k or less; off state
for 20k or greater
Communication Function
The communication function is provided only when the /RS option is specified. (For details, read the user’s manual of the communication functions IM 05C01E22-10E.)
Communication Protocol
Personal computer link: Used for communication with a
personal computer, or UT link module of the FA-M3 controller (from Yokogawa Electric Corporation). Ladder communication: Used for
communication with a ladder communication module of the FA-M3, or a programmable controller of other manufacturers. MODBUS communication: Used for communication
with equipment featuring the MODBUS protocol.
Communication Interface
Applicable standards: Complies with EIA RS-
485 Number of controllers that can be connected:
Up to 31 Maximum communication distance: 1,200m
Communication method: Two-wire half-duplex,
start-stop synchronization, non-procedural
Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE),
approved by C22.2 No.61010-1, approved by UL508. Certified by FM-3810 and FM-3545. Installation category : CAT. II Pollution degree : 2 (IEC/EN61010-1, C22.2 No.61010-1) Measurement category : I (CAT. I : IEC/EN61010-1)
Rated measurement input voltage : 10V DC
max.(across terminals), 300V AC max.(across ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in Measurement category I, and is not the value which guarantees an apparatus performance. Caution: This equipment has Measurement category I, therefore do not use the equipment for measurements within Measurement categories II, III and IV.
Internal Wiring
T
3
4
Entrance Cable
Description
category
For measurements performed on
CAT.1
circuits not directly connected to MAINS. For measurements performed on
CAT.2
circuits directly connected to the low voltage installation.
For measurements performed in
CAT.3
the building installation. For measurements performed at
CAT.4
the source of the low-voltage installation.
EMC standards: Complies with EN61326,
EN61000-3-2, EN61000-3-3 and EN55011 (CE). The instrument continues to operate at a measuring accuracy of within ±20% of the range during tests.
1
Outlet
Remarks
Appliances, portable equipments, etc.
Distribution board, circuit breaker, etc.
Overhead wire, cable systems, etc.
Power Supply and Isolation
Power Supply
Voltage
Power supply
Frequency Maximum power consumption Memory
Between primary terminals Withstanding
and secondary terminals voltage
(See note 1.)
Between primary terminals
Insulation
and secondary terminals
resistance
(See note 1.)
Note 1: The primary terminals are the power supply
terminals and relay output terminals.
The secondary terminals are the analog input and
output terminals, the voltage pulse output terminals, and the contact input terminals.
Isolation
The bold lines below indicate reinforced isolation, and the broken line indicates functional isolation.
Power supply terminals
(100-240V AC)
Control output terminals
(relay contacts)
Alarm output terminals
(2 relay contacts)
Note: Neither the measured value input terminals
nor input terminals for the /EX option are isolated from the internal circuit.
Rated at 100-240VAC (±10%) 50 or 60Hz 8VA max. (4W max.) Non-volatile memory
1500V AC for 1 minute
20M or more at 500V DC
Measured value input terminals
1 input terminals for /EX
Internal circui
PV transmission output terminals for /RET
RS-485 terminals for /RS
t
Construction, Mounting, and Wiring
Construction: Dust-proof and drip-proof front
panel conforming to IP65. For side-by-side close installation the controller loses its dust-proof and drip-proof protection. Casing: ABS resin and polycarbonate
Case color: Black
Mounting: Flush panel mounting
Terminals: Screw terminals
Environmental Conditions
Normal Operating Conditions
Warm-up time: At least 30 minutes
Ambient temperature:0-50°C (0-40°C when
mounted side-by-side) Rate of change of temperature: 10°C/h or less
Ambient humidity: 20-90% RH (no
condensation allowed) Magnetic field: 400A/m or less
Continuous vibrations of 5 to 14Hz: Amplitude
of 1.2mm or less Continuous vibrations of 14 to 150Hz: 4.9m/s2
2
(0.5G) or less Short-period vibrations: 14.7m/s2 (1.5G) for 15
seconds or less Shock: 98m/s2 (10G) for 11 milliseconds or less
Mounting angle: Upward incline of up to 30
degrees; downward incline is not allowed. Altitude: 2000m or less above sea level
Maximum Effects from Operating Conditions
(1) Temperature effects
Thermocouple, DC mV and DC V input: ±2µV/°C or
±0.02% of F.S./°C, whichever is the larger Resistance temperature detector: ±0.05°C/°C
Analog output: ±0.05% of F.S./°C
(2) Effect from fluctuation of power supply voltage (within rated voltage range)
Analog input: ±0.2µV/V or ±0.002% of F.S./V,
whichever is the larger Analog output: ±0.05% of F.S./V
Transportation and Storage Conditions
Temperature: –25 to 70°C
Humidity: 5 to 95% RH (no condensation allowed)
Shock: Package drop height 90cm (when packed in the
dedicated package)
All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation
GS 05C01E22-01E 2nd Edition Apr.02, 2007-00