Yokogawa UT150 Operating Manual

Users Manual
Models UT150, UT152, UT155 Temperature Controller
Please read through this user's manual to ensure correct usage of the controller and keep it handy for quick reference.
Contents
1. Notice
2. What is on the Front Panel?
3. Installing the Controller
4. Panel Cutout Dimensions and External Dimensions
5. Wiring
6. Hardware Specifications
7. Key Operations
8. Troubleshooting
...........................................................
.................................
......................................
.....
..........................................................
.....................................
................................................
...............................................
1 1 1 1 2 2 3
Revision Record
IM 05C01E12-01E 1st Edition: Oct. 00 2nd Edition: Feb. ’01 3rd Edition: Jun. ’04
3
IM 05C01E12-01E
Jun. 2004 3rd Edition
Checking Package Contents
Before using the product, check that its model & suffix codes are as you ordered.
Model and Suffix Codes
Model
UT150 UT152 UT155
Control output for standard­type (or for heating)
Control output for cooling
Option
Note:When specifying the /RS option, be sure to order the required number of copies of Communication Functions Users Manual separeately.
Check the package contents against the list below.
• Temperature controller
• Mounting bracket
Suffix code Description
Temperature controller
–R –V –A
N R V A
..........................
................................
...................
Relay output (time-proportional PID or on/off control) Voltage pulse output (time-proportional PID) 4 to 20mA output (continuous PID)
No cooling output (standard type) Relay output (time-proportional PID or on/off control) Voltage pulse output (time-proportional PID) 4 to 20mA output (continuous PID)
/AL
Alarm outputs (2 points)
/HBA
Heater disconnection alarm (includes optional /AL function)
/EX
SP1/SP2 switching, starting of timer, and RUN/STOP switching by external contacts
/RET
PV retransmission output in 4 to 20mA
/RS
Communication function
/V24
Power Supply 24V DC / 24V AC
1 1 for UT150 2 for UT152, UT155 1
1. Notice
The following safety symbol is used both on the product and in this users manual.
This symbol stands for Handle with Care. When displayed on the product, the operator should refer to the corresponding explanation given in the users manual in order to avoid injury or death of personnel and/or damage to the product. In the manual the symbol is accompanied by an expla­nation of the special care that is required to avoid shock or other dangers that may result in injury or loss of life.
The following symbols are used in this manual only.
NOTE
IMPORTANT
Indicates that operating the hardware or software in a particular manner may lead to damage or result in system failure.
Draws attention to information that is essential for understanding the operation and/or features of the product.
Exemption from Responsibility
Make sure that all of the precautions are strictly adhered to. Yokogawa Electric Corporation assumes no liability for any damage resulting from use of the instrument in contradiction to the precautions. Also, Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect, caused by the use or any unpredictable defect of the instrument.
2. What is on the Front Panel ?
UT152 UT155UT150
a.
f.
b.
c.
f.
d.
h.
g.
e. d. c.
a. b.
g.
f.
h.
Name Function
a. PV display (red) b. SP display (green) c. Alarm 1 (AL1) lamp (red) d. Alarm 2 (AL2) lamp (red) e. SP2 lamp (green) f. Output (OUT) display lamps
UT150: (Left: orange; right: green) UT152, UT155: (Upper: orange; lower: green)
g. Data change keys
(Indicated as simply the and keys hereafter.)
SET/ENT key (data registering key)
h.
(Indicated as simply the key hereafter.)
e. c.
d.
h.
Indicates PV (measured value) and character information such as parameter codes and error codes. Indicates SP (target setpoint) and parameter values. Lit when alarm 1 is activated. Lit when alarm 2 is activated. Lit when SP2 is being used for control operation. Lit while control output is being output.
The left (upper) lamp is lit in orange during control output of standard type. In heating/cooling control, the left (upper) lamp lights up in orange when the heating-side output
is active; while the right (lower) lamp lights up in green when the cooling-side output is active.
Changes SP and the parameter values.
Pressing the key decreases the data value and pressing the key increases
it. Holding down the key will gradually increase the speed of the change.
Registers the data value changed using the data change keys.
Switches between operating display or parameter setting displays sequentially.
Pressing the key for 3 seconds or longer in the operating display retrieves the
operating parameter setting display.
Pressing the key for 3 seconds or longer in either an operating or setup parameter setting display transfers back to operating display 1. (See page 3.)
3. Installing the Controller
CAUTION
To prevent electric shock, the source of power to the controller must be turned off when mounting the controller on to a panel.
4. Panel Cutout Dimensions and External Dimensions
1. General Mounting
min. 70
UT150
25
min. 70
25
2. Side-by-side Close Mounting
[(N–1)×48+45]
0
+0.6
45
N is the number of controllers. If N>5, then measure the actual length.
0
+0.6
45
+0.6
45
0
+0.6
0
1. General Mounting
min. 70
a.
min. 145
e.
b.
25
2. Side-by-side Close Mounting
×48+
[(N–1)
53
0
+0.8
92
+0.6
45
0
+0.6
45]
0
g.
0
+0.8
92
N is the number of controllers. If N>5, then measure the actual length.
1. General Mounting
min. 117
+ 0.8 0
+ 0.8
53
0
92
min. 145
25
92
2. Side-by-side Close Mounting
×96+
92]
+0.8
0
[(N–1)
0
+0.8
92
N is the number of controllers. If N>5, then measure the actual length.
Unit: mm
UT152
Unit: mm
48
UT155
Unit: mm
96
48
48
Panel thickness
1 to 10
11
96
Panel thickness
1 to 10
96
Panel thickness
1 to 10
max. 47.8
max. 44.8
10012
max. 61
max. 44.8
max. 44.6max. 91.8
1-1021-301-20
100
max. 112
max. 91.8
1-1051-6041-5031-4021-3011-20
11
100
max. 112
max. 91.8
NOTE
To install the controller, select a location where:
1. No-one may accidentally touch the terminals; 6. There are no resulting magnetic disturbances;
2. Mechanical vibrations are minimal; 7. The terminal board (reference junction compen-
3. Corrosive gas is minimal; sation element, etc.) is protected from wind;
4. The temperature can be maintained at about 23°C with 8. There is no splashing of water; and
minimal fluctuation; 9. There are no flammable materials.
5. There is no direct heat radiation;
Never place the controller directly on flammable items.
If the controller has to be installed close to flammable items or equipment, be sure to enclose the controller in shielding panels positioned at least 150mm away from each side. These panels should be made of either 1.43mm thick metal-plated steel plates or 1.6mm thick uncoated steel plates.
Mount the controller at an angle within 30° from horizontal with
the screen facing upward. Do not mount it facing downward.
30° (MAX)
150mm
150mm
NOTE
Splash-proof construction is not available when the side-by-side close mounting method shown in the above figures, is chosen for any of the controllers.
Mounting the Controller
UT152, UT155UT150
1. Affix the bracket over the back end of the controller.
Panel
150mm150mm
UT150
Bracket
[ How to remove the bracket ] To move the bracket, push down the center of the upper and lower parts of the controller softly. The bracket is released from the latch.
2.
Push the bracket to the panel, and then secure the bracket into position.
Direction for mounting
Insert the controller into the opening with the terminal board facing the front. Set and tighten the top and bottom brackets on the controller to fix it on the panel.
1
Panel
Small bracket (bottom)
IM05C01E12-01E
Large bracket (top)
Terminal board
Insert a screwdriver into the brackets to tighten the screws.
y
y
v
quip
quip
g
.
g
.
O
t
ce
C
e
3
5. Wiring
1) Before you start wiring, turn off the power source and use a tester to check that the controller and cables are not receiving any power in order to prevent electric shock.
2) For safety, be sure to install a circuit breaker switch (of 5A and 100V AC or 220V AC, and that conforms to IEC60947) near the instrument so as to be operated easily, and clearly indicate that the device is used to de­energize the instrument.
3) Wiring should be carried out by personnel with appropriate electrical knowledge and experience.
1) Use a single-phase power source. If the source has a lot of noise, use an isolation transformer for the primary
CAUTION
NOTE
Cable Specifications and Recommended Products
Power supply and relay contact output Thermocouple input RTD input Other signals
600V vinyl insulated wire/cable, JIS C3307, 0.9 to 2.0mm Shielded compensating lead wire, JIS C1610 Shielded wire (3-wire), UL2482 (Hitachi cable) Shielded wire
2
Recommended Terminals
Use M3.5 screw-compatible crimp-on terminals with an insulating sleeve, as shown below.
ø 3.7mm ø 3.7mm
side and a line filter (we recommend TDKs ZAC2205-00U product) for the secondary side. When this noise-prevention measure is taken, keep the primary and secondary power cables well apart. Since the controller has no fuse, be sure to install a circuit breaker switch (of 5A and 100V AC or 220V AC, and that conforms to IEC standards) and clearly indicate that the device is used to de-energize the controller.
7mm or less
7mm or less
2) For thermocouple input, use shielded compensating lead wires. For RTD input, use shielded wires which have low resistance and no resistance difference between the 3 wires. See the table given later for the specifications of the cables and terminals and the recommended products.
3) The control output relay cannot be replaced even though it has a limited service life (100,000 relay contacts
Always fix a terminal cover bracket to the UT150 controller before wiring if an optional anti-electric-shock terminal cover (part number: L4000FB) is used.
IMPORTANT
for the resistance load). Thus, an auxiliary relay should be used so that the load can be turned on and off.
4)
When using an inductive load (L) such as an auxiliary relay and solenoid valve, be sure to insert a CR filter (for AC) or diode (for DC) in parallel as a spark-rejecting surge suppressor to prevent malfunctions or damage to the relay.
5)
When there is the possibility of being struck by external lightening surge, use the arrester to protect the instrument.
UT150 Terminal Arrangement (Standard type)
B b A
NOTE
+
AC/DC 24V
When /V24
is specified.
+
B b A
+
Universal input-selectable input type
DC mV or V Input
7
+
8
CAUTION
To prevent damage to the controller, never provide 100-240V AC power supply for power supply AC/DC 24V model (when /V24 is specified).
4 to 20 mA DC Output
+
14
15
Universal input-selectable input type
DC mV or V Input
12
+
13
4 to 20 mA DC Output
+
14
15
Alarm Outputs
16
ALM2
17
ALM1
18
COM
When /AL or /HBA is specified.
Retransmission Output
+
1
2
When /RET is specified.
RS-485
3
RSB(+)
4
RSA(–)
5
SG
When /RS is specified.
External Contact Inputs
TMR STOP
3
SP2 STOP
4
COM
5
When /EX is specified.
UT152/UT155 Terminal Arrangement
(Standard Type)
External Contact Inputs
21 22 23
When /EX is specified.
Heater Current Detection Input
26 27 28
Heater Current Detection Input
When /HBA is specified.
0 (Default)
Timer starts when DI=ON
TMR
Timer stops
STOP
when DI=OFF SP1/SP2
SP2
switching SP2
STOP
when DI=ON
TMR STOP
SP2 STOP
COM
24
25
RS-485
RSB(+) RSA(–) SG
CT
When /RET is specified.
TMR STOP
SP2 STOP
When /HBA is specified.
When /RS is specified.
Retransmission Output
1
2
(Note 1)
1 2 3 4
5
0 (Default)
Timer starts when DI=ON
Timer stops when DI=OFF
SP1/SP2 switching
SP2 when DI=ON
29
30
CT
Parameter DIS
+
Alarm Outputs
11 12 13 14 15
1
Timer starts when DI=ON
Timer stops when DI=OFF
RUN/STOP switching
STOP when DI=ON
Parameter DIS
1
Timer starts when DI=ON
Timer stops when DI=OFF
RUN/STOP switching
STOP when DI=ON
11
ALM2
12
ALM1
13
COM
When /AL or /HBA is specified.
6 7 8 9
10
2
RUN/STOP switching
STOP when DI=ON
SP1/SP2 switching
SP2 when DI=ON
2
RUN/STOP switching
STOP when DI=ON
SP1/SP2 switching
SP2 when DI=ON
1121
22
12
23
13
24
14
25
15
26
16
27
17
28
18
29
19
30
20
Power Supply
L
19
20
N
100-240V AC
Measured Value (PV) Input
TC Input
7
8
9
10
+
L
N
100-240V AC
RTD Input
6 7 8
Power Supply
9
10
Control Output
Relay Contact Output
Specify one for the output signal type.
Note: The terminal arrangements of the UT152 and
Voltage Pulse Output
NO
14
15
COM
14
15
UT155 are the same.
Measured Value (PV) Input
TC Input
12
13
+
RTD Input
11 12 13
Control Output
Relay Contact Output
Specify one for the output signal type.
NOTE
19
+
AC/DC 24V
20
When /V24
is specified.
Voltage Pulse Output
NO
14
15
COM
14
15
CAUTION
To prevent damage to the controller, never provide 100-240V AC power supply for power supply AC/DC 24V model (when /V24 is specified).
(Heating/coolin Type)
(Heating/cooling Type)
Two types of optional anti-electric-shock terminal covers (part numbers T9115YE and T9115YD) are available for the UT152 and UT155 controllers, respectively.
Cooling-side Control Output
Voltage Pulse Output
1
2
Specify one for the output signal type.
Heater Current Detection Input
When /HBA is specified.
RS-485
3
RSB(+)
4
RSA(–)
5
SG
When /RS is specified.
When /HBA is specified.
Heater Current Detection Input
RS-485
26
RSB(+)
27
RSA(–)
28
SG
Cooling-side Control Output
Relay Contact Output
Specify one for the output signal type.
+
3
4
(Note 1)
24
25
29
30
CT
CT
NO
COM
4 to 20 mA DC Output
1
2
External Contact Inputs
3 4 5
When /EX is specified.
External Contact Inputs
When /EX is specified.
When /RS is specified.
Voltage Pulse Output
29
30
+
TMR STOP
SP2 STOP
COM
21 22 23
+
TMR STOP
SP2 STOP
COM
Relay Contact Output
TMR STOP
SP2 STOP
4 to 20 mA DC Output
29
30
TMR STOP
SP2 STOP
NO
1
COM
2
0 (Default)
Timer starts when DI=ON
Timer stops when DI=OFF
SP1/SP2 switching
SP2 when DI=ON
Timer starts when DI=ON
Timer stops when DI=OFF
SP1/SP2 switching
SP2 when DI=ON
+
1 2 3 4
0 (Default)
5
Parameter DIS
Timer starts when DI=ON
Timer stops when DI=OFF
RUN/STOP switching
STOP when DI=ON
Parameter DIS
Timer starts when DI=ON
Timer stops when DI=OFF
RUN/STOP switching
STOP when DI=ON
6. Hardware Specifications
Measured Value (PV) Input Alarm Functions
Input: 1 point
Input type: Universal; can be selected by software
Input accuracy (at 23 ±2°C ambient temperature)
Thermocouple: ±2°C
However,
±4°C for thermocouple input –200 to 100°C
±3°C for thermocouple input –100 to 0°C
±5°C for type R and S (±9°C for 0 to 500°C)
±9°C for type B
RTD: ±1°C ±1digit
Voltage(mV, V) : ±0.3%
Sampling period for measured value input: 500ms
Burn-out detection: Functions for thermocouple or RTD input
(burn-out upscale only; cannot be switched off) Input resistance: 1M or greater for thermocouple
or DC mV input. Approx. 1M for DC V input Maximum allowable signal source resistance :
Maximum allowable wiring resistance for RTD input:
10/wire (The resistance values of three wires must be the same.) Allowable input voltage: ±10V DC for thermocouple or DC mV input
Noise rejection ratio:
(50/60Hz) (Min. 90dB for DC V input) Error of reference junction compensation:±1.5°C (at 15-35°C)
The reference junction compensation cannot be switched off. Applicable standards:
Thermocouple and resistance temperature detector JIS/IEC/DIN (ITS90)
(accuracy is not guaranteed for 0 to 400°C)
250
for thermocouple or DC mV input
2k
for DC V input
±20V DC for DC V input
Normal mode noise: Min. 40dB
Common mode noise: Min. 120dB
±2.0°C (at 0-50°C)
Control Output
Output: 1 point (for standard type) or
2 points (for heating/cooling type)
Output type: Choose one from (1) to (3) below:
(1) Relay contact output Contact capacity: 3A at 240V AC or 3A at 30V DC (with resistance load) Note: The control output relay cannot be replaced by users. (2) Voltage pulse output On voltage: 12-18V DC load resistance: 600 or greater Off voltage: 0.1V DC or less short-circuit current: approx. 30mA (3) Current output Output signal: 4 to 20mA Maximum load resistance: 600 Output accuracy: ±0.3% of span (at 23±2°C ambient temperature)
Alarm Functions (Option Code /AL or /HBA)
Alarm types: 22 types
(waiting action can be set by software): PV high limit, PV low limit, Deviation high limit, Deviation low limit, De-energized on deviation high limit, De-energized on deviation low limit, Deviation high and low limits, High and low limits within deviation, De-energized on PV high limit, De-energized on PV low limit, Fault diagnosis output, FAIL output Alarm output: 2 relay contacts
Relay contact capacity: 1A at 240V AC or 1A at 30V DC (with resistance load) Note: The alarm output relays cannot be replaced by users.
Heater Disconnection Alarm (Option Code /HBA)
The heater disconnection alarm is available when time­proportional PID control or on/off control is selected.
Heater current setting range: 1 to 80A
Alarm output: 1 relay contact
(The terminals are the same as those of the /AL option.) On time of burn-out detection: Min. 0.2 second
Sensor:
CTL-6-S-H or CTL-12-S36-8
(URD Co., Ltd.)
To be purchased separately.
Timer Function (Option Code /AL/EX or /HBA/EX)
The output contact status changes when the preset time has passed since external contact (TMR) turned on. The contact action can be selected by software from: (1)
Make contact–the contact closes upon time-up.
(2)
Break–the contact opens upon time-up.
Input contact type: See Contact Inputs below.
Retransmission Output
The retransmission output is provided only when the /RET option is specified, but is not available for the heating/cooling type.
Output signal: Measured value in 4-20mA DC
Maximum load resistance: 600
Output accuracy: ±0.3% of span
(at 23±2°C ambient temperature)
Entran
abl
Measurement category
1 2 3 4
CAT.1
For measurements performed on circuits not directly connected to MAINS For measurements performed on circuits directly connected to the low voltage installation.
CAT.2
For measurements performed in the building installation.
CAT.3
For measurements performed at the source of the low-voltage installation.
CAT.4
utle
Description
IM05C01E12-01E
Contact Inputs
The contact inputs are provided only when the /EX option is specified.
Functions: (1) SP1/SP2 switching
(2)
Starting a timer (See the (3) RUN/STOP switching Can be selected by parameter DIS.
Input: 2 points (with the shared common terminal)
Input type: Non-voltage contact or transistor contact input
Contact capacity: At least 12V/10mA
On/off judgment: On state for 1k or less; off state
for 20kΩ or greater
Alarm Functions .)
Communication Function
The communication function is provided only when the /RS option is specified. (For details, read the instruction manual of the communications functions IM 05C01E12-10E.)
Communication Protocol
Personal computer link: Used for communication with a
personal computer, or UT link module of the FA-M3 controller (from Yokogawa Electric Corporation). Ladder communication: Used for communication with a
ladder communication module of the FA-M3, or a programmable controller of other manufacturers. MODBUS communication: Used for communication with
equipment featuring the MODBUS protocol.
Communication Interface
Applicable standards: Complies with EIA RS-485
Number of controllers that can be connected: Up to 31
Maximum communication distance: 1,200m
Communication method: Two-wire half-duplex,
start-stop synchronization, non-procedural Baut rate: 2400, 4800, or 9600 bps
Safety and EMC Standards
Safety: Compliant with IEC/EN61010-1: 2001, approved
by CSA1010, approved by UL508. Installation category : CAT. II (IEC/EN61010, CSA1010) Pollution degree : 2 (IEC/EN61010, CSA1010) Measurement category : I (CAT. I : IEC/EN61010)
Rated measurement input voltage : 10V DC max.(across
terminals), 300V AC max.(across ground)
Rated transient overvoltage : 1500V (Note)
Note : It is a value on the safet b
IEC/EN61010-1 in measurement category I, and is not
the
alue which guarantees an apparatus performance. Caution: This e therefore do not use the e within measurement cate
EMC standards: Complies with EN61326.
The instrument continues to operate at a measurin accuracy of within ±20% of the range during tests.
standard which is assumed
ment has Measurement category I,
ment for measurements
ories II, III and IV
Remarks
Appliances, portable equipments, etc. Distribution board, circuit breaker, etc. Overhead wire, cable systems, etc.
2
Power Supply and Isolation
Power Supply
Voltage
Power supply
Frequency
Maximum power consumption Memory
Between primary terminals
Withstanding
and secondary terminals
voltage
(See notes 1 and 2.) Between primary terminals
Insulation
and secondary terminals
resistance
(See notes 1 and 2.)
Note 1:
The primary terminals are the power supply terminals and
relay output terminals. The secondary terminals are the analog input and output terminals, the voltage pulse output terminals, and the contact input terminals.
Note 2: AC/DC 24V terminals are secondary terminals.
Isolation
The bold lines below indicate reinforced isolation, and the broken line indicates functional isolation.
Power supply
terminals (100-240V AC)
Control output
terminals (relay contacts)
Alarm output
terminals (2 relay contacts)
Note: Neither the measured value input terminals, CT input
terminals for the /HBA option, nor 2 input terminals for the /EX option are isolated from the internal circuit.
IMPORTANT
Alarm Outputs
11
ALM2
12
ALM1
13
COM
When /AL or /HBA is specified.
6
11
7
12
8
13
9
14
10
15
1
2
RUN/STOP switching
STOP when DI=ON
SP1/SP2 switching
SP2 when DI=ON
1
2
RUN/STOP switching
STOP when DI=ON
SP1/SP2 switching
SP2 when DI=ON
1121
22
12
23
13
24
14
25
15
26
16
27
17
28
18
29
19
30
20
Power Supply
L
19
20
N
100-240V AC
Rated at 100-240VAC (±10%) AC/DC 24V when /V24 is specified.
50 or 60Hz 8VA max. (4W max.)
3W max. when /V24 is specified.
Non-volatile memory 1500V AC
for 1 minute 20M or more at
500V DC
Power supply
terminals AC/DC 24V (When /V24 is specified)
Measured value input
terminals CT input terminals
for /HBA 2 input terminal
for /EX Internal circuit
Control output terminals:
4-20 mA/Voltage pulse RS-485 terminals
for /RS
Note 1: The heater current detection input terminals (option code: /HBA)
are defined as terminals and for a standard type and as
3 4
terminals and for a heating/cooling type.
Measured Value (PV) Input
TC Input
7
+
8
9
10
100-240V AC
Power Supply
L
N
1 2
RTD Input
6
B
7
b
8
A
9
+
10
Universal input-selectable input type
NOTE
AC/DC 24V
When /V24
is specified.
DC mV or V Input
7
+
8
CAUTION
To prevent damage to the controller, never provide 100-240V AC power supply for power supply AC/DC 24V model (when /V24 is specified).
Heating-side Control Output
+
B b A
4 to 20 mA DC Output
+
14
15
Universal input-selectable input type
DC mV or V Input
12
+
13
Relay Contact Output
Specify one for the output signal type.
Note: The terminal arrangements of the UT152 and
Voltage Pulse Output
NO
14
15
COM
14
15
UT155 are the same.
Measured Value (PV) Input
TC Input
12
13
+
RTD Input
11 12 13
Heating-side Control Output
Relay Contact Output
NO
14
COM
15
Specify one for the output signal type.
NOTE
To prevent damage to
19
+
20
the controller, never provide 100-240V AC power supply
AC/DC 24V
for power supply AC/DC 24V model (when /V24 is
When /V24
specified).
is specified.
Voltage Pulse Output
14
15
CAUTION
4 to 20 mA DC Output
+
14
15
Alarm Outputs
When /AL or /HBA is specified.
NOTE
The and stand for the polarity
+
for DC 24V power supply.
+
16
ALM2
17
ALM1
18
COM
Construction, Mounting, and Wiring
Construction: Dust-proof and drip-proof front
panel conforming to IP65 [Model UT150] and IP55 [Models UT152 and UT155]. For side-by-side close installation the controller loses its dust-proof and drip-proof protection. Casing: ABS resin and polycarbonate
Case color: Black
Mounting: Flush panel mounting
Terminals: Screw terminals
Environmental Conditions
Normal Operating Conditions
Warm-up time: At least 30 minutes
Ambient temperature:0-50°C (0-40°C when
mounted side-by-side) Rate of change of temperature: 10°C/h or less
Ambient humidity: 20-90% RH (no condensation allowed)
Magnetic field: 400A/m or less
Continuous vibrations of 5 to 14Hz: Amplitude of 1.2mm or less
Continuous vibrations of 14 to 150Hz: 4.9m/s
Short-period vibrations: 14.7m/s2 (1.5G) for 15 seconds or less
Shock: 98m/s2 (10G) for 11 milliseconds or less
Mounting angle: Upward incline of up to 30
degrees; downward incline is not allowed. Altitude: 2000m or less above sea level
Maximum Effects from Operating Conditions
(1) Temperature effects
Thermocouple, DC mV and DC V input: ±2µV/°C
or ±0.02% of F.S./°C, whichever is the larger Resistance temperature detector: ±0.05°C/°C
Analog output: ±0.05% of F.S./°C
(2) Effect from fluctuation of power supply voltage
(within rated voltage range)
Analog input: ±0.2µV/V or ±0.002% of F.S./V,
whichever is the larger Analog output: ±0.05% of F.S. /V
Transportation and Storage Conditions
Temperature: 25 to 70°C
Humidity: 5 to 95% RH (no condensation allowed)
Shock: Package drop height 90cm (when packed in
the dedicated package)
2
(0.5G) or less
7. Key Operations
CAUTION
To prevent electric shock, the controller should be mounted on the panel so that you do not accidentally touch the terminals when power is being applied.
IMPORTANT
The temperature controller is shipped with the parameters set at the factory-set defaults. Check the default values against the Parameter Lists in the following page, and change the parameter settings that need to be changed.
This section explains how to set and register parameter values. The procedure for changing SP (target setpoint) and A1 (alarm 1 setpoint) can be found on Changing Target Setpoint (SP) and Changing Alarm 1 Setpoint (A1), respectively. You can set the other parameters in the same way.
There are no setup displays for parameters specific to functions, such as the optional alarm output functions or heating/cooling control, if they were not selected at ordering. The setting of some parameters (such as the control mode parameter CTL) determines whether the other parameters are displayed or not.
The flowchart below will help you understand how this works.
NOTE
At power-on, the temperature controller displays the operating display 1 , but if the measured input range setting remains OFF, then “IN” appears. In this case, press the key to display the measured input range code you want to use, then press the key to register it. (Refer to the flowchart below.)
Changing Target Setpoint (SP) Changing Alarm 1 Setpoint (A1)
(This setpoint appears only if the /AL or /HBA option is specified.)
The following instructions assume that the controller is already receiving power.
Step 1:
Confirm that the controller shows the operating display 1 during normal operation (PV and SP are displayed on the indicators).
Step 2:
Press the or key to change the displayed SP value to the required value. In this example, SP is changed to 200°C.
The period flashes while the value is being changed.
Step 3:
Press the key once to register the setting. The period goes out. SP is now changed.
Step 1:
Confirm that the controller shows the operating display 1 during normal operation (PV and SP are displayed on the indicators).
Step 2:
To enter the operating parameter setting display, press the key for at least 3 seconds. If your controller has the /AL or /HBA option, the display for the Alarm 1 setpoint (A1) appears. {If not, control mode (CTL) appears.}
Press for at least 3 seconds.
Step 3:
Press the or key to change the current A1 value to a required value. In this example, A1 is changed to 200°C.
The period flashes while the value is being changed.
(1) You can move between parameter setting displays using the (2) To change the set value,
(i)
Change the display value with the or key (the period flashes).
(ii) Press the key to register the setting.
(3)
At the operating display 1 or 2 , pressing the
(4)
At the operating parameter setting display, pressing the
key for at least 3 seconds retrieves the operating parameter setting display.
key for at least 3 seconds transfers back to the oper-
key.
Note: If you cannot change the
parameter setting value, check the key-lock param­eter (LOC) setting.
ating display 1 . Registering the key-lock parameter LOC to “–1” retrieves the setup parameter setting display.
(5)
At the setup parameter setting display, pressing the
A
When measured input range code has been already set, the operating display 1 shown below appears.
key for at least 3 seconds transfers back to the operating display
Power ON
is displayed
YesNo
?
Operating display
Measured input value (PV) Target setpoint (SP1 or SP2)
Press the
key
to move between items.
T1 T2
1
SP1 or SP2 value can be changed at operating display 1
Operating display
Displayed only for the /AL/EX option with AL1, AL2 = 23 or 24.
NOTE
In STOP mode, or PV value is displayed on PV
2
display alternately.
Note:
If no key is pressed for a period of two minutes or more while in the operating or setup parameter setting display, the controller automatically returns to operating display 1 .
When In appears, press the key to display the measured input range code you want to use, then press the key to register it. After this operation, the controller shows the operating display 1 .
NOTE
NoteNote
Press the
key
for at least
3 seconds.
Press the
key
to move between items.
CTL
CTL
=SLF (Dynamic Auto Tune)
Note
CTL=SLF is not permitted for heating/cooling type.
FL BS
LOC
LOC=
Press the
key for
at least 3 seconds.
(To operating
display 1 )
key for
at least 3 seconds.
(To operating
display 1 )
Operating parameter setting display
Displayed only for the /AL or
A1 A2
HC
AT
MR
COL
DB
CT
CTC
SP1 SP2
When –1
Set -1 to enter the setup parameter setting display. But if LOC=1 or 2 is already set, the parameter value can not be changed by setting LOC=-1 only. To change the parameter value, set LOC=0 at first (for disabling keylock), then set LOC=-1 once again.
/HBA option
Not displayed when AL1, AL2 = OFF
Not displayed when AL1, AL2 = 21 or 22
Displayed only for the /HBA option and when AL1 = 25
CTL=PID
(PID control)
P
I
D
Displayed when I=OFF Displayed for heating/
cooling type
Displayed for heating/ cooling type
Displayed for time­proportional PID control
Displayed for time­proportional PID control of heating/cooling type
Displayed for the /EX option
When LOC=–1
transfers to the
setup parameter
setting display
NOTE
HYS
CTL=ONF (on/off
control)
Press the
to move between items.
,
Press the
Setup parameter setting display
IN
key
SPH SPL UPR DNR TMU
SC DR
Changing certain setup parameters may automatically initialize the operating parameters. Therefore, after you change the setup parameters, always check the operating parameter settings to find out if appropriate values have been set for them. If the operating parameters have been initialized, set them to their appropriate values.
DP
Displayed when DC voltage
RH
input range code is set
RL
DIS
Displayed for
RTL
the /EX option
Displayed for the /AL/EX or /HBA/EX option
Displayed for the /RET option
EOT
TTU
RTH
AL1 AL2
Displayed for the /AL or
HY1
/HBA option
HY2
Not displayed when CTL=ONF (on/off control) Not displayed for heating/cooling type
PSL ADR BPS
Displayed for the /RS option
PRI
STP DLN
1 .
A
NOTE
3
The period goes out.
Step 4:
Press the key once to register the setting. The period goes out. A1 is now changed. Another press of the
key calls up the Alarm 2
setpoint(A2) display.
The period goes out.
To return to the operating
display 1 , press the key for at least 3 seconds.
UT150/UT152/UT155 Measured Input Ranges
Input type Range (°C
K
J T E R S
Thermocouple
B N L U
Platinel 2
Pt100
RTD
JPt100
0 to 100mV
0 to 5V 1 to 5V
0 to 10V
DC voltage
–270 to 1370 °C
0.0 to 600.0°C
0.0 to 400.0°C
199.9 to 200.0 °C 199.9 to 999.9 °C 199.9 to 400.0 °C 199.9 to 999.9 °C
200 to 1300 °C 199.9 to 900.0 °C 199.9 to 400.0 °C
199.9 to 850.0 °C
0.0 to 400.0°C
199.9 to 200.0 °C
19.9 to 99.9 °C 199.9 to 500.0 °C
0.0 to 100.0
0.000 to 5.000
1.000 to 5.000
0.00 to 10.00
0 to 1700°C 0 to 1700°C 0 to 1800°C
0 to 1390°C
User-scalable
)
Range code (°C
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
)
199.9 to 999.9 °F
199.9 to 999.9 °F
)
Range (°F
–300 to 2500 °F
32.0 to 999.9°F
32.0 to 750.0°F
300 to 400 °F
300 to 2100 °F
300 to 750 °F
300 to 1800 °F
32 to 3100°F 32 to 3100°F 32 to 3200°F
300 to 2400 °F 300 to 1600 °F
300 to 750 °F
32 to 2500°F
32.0 to 750.0°F –300 to 400 °F
Range code (°F
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
)
For example, to select thermocouple type E (°F), set the range code to 37.
8. Troubleshooting
Is the controller defective?
Yes
Completely inactive?
Yes Yes
Check the terminal connection of the power supply
Check the power supply voltage
Normal?
Yes
Contact us for repair Problem solved
Error Display during Operation
(1) If the controller displays one of the following, carry out the appropriate remedy for the particular error.
Display
Flashing period on PV display
(2)
The controller needs to be repaired if any of the indications in the table below appear.
In these cases, do not try to repair the controller yourself. Order a new controller or contact us for repair.
Display
Unknown (at power-on) All extinguished (at power-on) Err (at power-on)
When Power Failure Occurred during Operation
Momentary power failures of less than 20ms(or less than 1ms when /V24 is specified)
have no effect on the controller operation (i.e., normal operation continues).
For power failures longer than 20ms(or longer than 1ms when ⬙/V24 is specified), however
the status will be as follows. (The controller action at power recovery is the same as at power-on.)
Alarm action: Continues (but alarms with a waiting action enter the waiting state once)
Setting parameters: Maintained
Auto-tuning: Canceled
In the event of an abnormality, perform the following checks as outlined by the flowchart.
No
No
No
No
Correct it
Normal?
Yes
Key operation failure?
Check key-lock setting
Is the key
Cancel the setting
Error content Remedy
The parameter is abnormal
P.Er
Input burnout
B.o
PV over-scale (PV exceeds its effective range.)
OOO
PV under-scale (PV falls below its effective range.)
UUU
Communication failure (for /RS option only)
Error content
CPU failure Power source failure Calibration abnormal
No No No
Display failure? I/O signal failure?
Yes Yes Yes
Turn the power off, then on
locked?
Yes
Check the settings of all the parameters and set them at their proper values.
Check the sensor wiring and correct it.
Check the input type and range settings and correct them.
Press any key to stop the flashing.
Display
Flashing Err” (at power-on) Flashing Err
(during operation)
Verify the I/O spec. of controller
Verify the spec. of I/O destinations
No communication capability
Error content
RAM or ROM failure A/D converter failure,
RJC failure, or EEPROM failure
IM05C01E12-01E
Communication
failure?
Check the model and suffix codes
No
Communication
function included?
Check the communication­related parameters
Check the communication wiring
Verify the spec. of communicating partner
Alarm Function List
Alarm type
Opn and Cls indicate that the relay contact is opened and closed; (on) and (off) indicate that the lamp is on and off; and white triangles indicate temperature control setpoints.
No alarm
PV
high limit
Opn (off)
Measured value
PV
low limit
Deviation high limit
Deviation
Measured value
Cls (on)
low limit
De-energized
on deviation
high limit
Measured value
Fault
diagnosis
alarm
The output contact is opened in the following events:
FAIL
output
Program error
ROM error
RAM error
power failure
External contact (TMR) Opn
Timer
function
The output contact closes when the timer setting has passed since external contact was closed. Then, the output contact opens immediately when external contact is opened.
Note: The alarms numbered 1 to 10 have no waiting
action, while alarms 11 to 20 have a waiting action. The waiting action turns off the PV and deviation alarms that occur from the start of the control operation until a stable state is reached.
Action
Hysteresis
Cls (on)
Alarm setting
Hysteresis
Opn (off)Cls (on)
Alarm setting
Hysteresis
Opn (off)
Temperature setpoint
Deviation setting
Temperature setpoint
The contact is closed at input burnout.
Opn (off)
Time
Measured value
Deviation setting
Hysteresis
Opn (off)
Measured value
Temperature setpoint
Hysteresis
Opn (on)Cls (off)
Deviation setting
A/D converter error
RJC error
EEPROM error
Cls
Cls (on)
Blinking
Timer setting
Cls (on)
Description of Parameters
type code
Closed contact
during alarm
11
(See note.)
12
(See note.)
13
(See note.)
14
(See note.)
21
Opn
Opn (off)
23
Alarm
Alarm type
Open contact
during alarm
OFF
1
De-energized
on deviation
low limit
2
Deviation
high and low
3
Deviation
within high-
and -low-
4
De-energized
high limit
5
De-energized
15
(See note.)
low limit
Break timer
function
22
disconnection
Waiting action
Action
Hysteresis
Opn (off)
Cls (on)
Hysteresis
Alarm setting
Measured value
Temperature setpoint
Hysteresis Hysteresis
Temperature setpoint
Hysteresis Hysteresis
Temperature setpoint
Hysteresis
Measured value
Measured value
Opn (on)
limit
limit
on PV
Opn and Cls indicate that the relay contact is opened and closed; (on) and (off) indicate that the lamp is on and off; and white triangles indicate temperature control setpoints.
Opn (on) Cls (off)
Deviation setting
Cls
(on)
Deviation setting
Deviation setting
Cls
(off)
Measured value
on PV
Alarm setting
External contact
(TMR) Opn
Cls (off)
Time
The output contact opens when the timer setting has passed since the contact was closed. Then, the output contact closes immediately when external contact is opened.
Heater
alarm
°C
Power-on
Opn (off)
Heater current Alarm setting
The controller starts measuring the current from the heater disconnection detector when 100 milliseconds have passed after turning on the output.
Taken as
normal.
In this area, the alarm output is turned off even when a measured value falls below the low limit alarm setpoint.
Blinking
Timer setting
Normal
Measured value
Cls
Opn (on)
Abnormal
Alarm output = ON
Opn (off)Opn (off)
Cls (off)Opn (on)
This section describes the parameter functions specific to the UT150/UT152/UT155 temperature controllers. (The functions described in other sections of this manual and the general functions are not discussed.)
Parameter Function Parameter Function
Control mode
CTL
Manual reset
MR
Cooling-side gain
COL
Deadband
DB
Hysteresis for on/off control
HYS
Control output / cooling-side control output cycle time
CT CTC
PV input filter
FL
Select one from the following: a. Dynamic auto tune control (SLF) b. PID control (PID) c. On/off control (ONF) Note: Dynamic auto tune control is not available
for heating/cooling control. Read the section below this table to find out more about dynamic auto tune control.
You can set this parameter only for control without an integral action (when registered as CTL=PID and I=OFF). The controller outputs the manual reset (MR) value when PV=SP. For example, if you set MR=50%, the controller outputs (OUT) 50% when PV=SP.
For heating/cooling control, you can set the ratio between the cooling-side output and heating-side output. For example, if you set COL=2.0 and the heating­side output is 10% at a certain deviation (SP-PV), then the cooling-side output will be 20% when the cooling-side also reaches that deviation.
You can only set a deadband for heating/cooling control. In a positive deadband, there are neither heating-side nor cooling-side outputs. In a negative deadband, there are both heating-side and cooling-side outputs, which overlap each other.
1.
When the deadband of a heating/ cooling type is positive (Proportional band [P] control)
100%
Deadband
DB (+)
Cooling
side
0%
PV
For on/off control (CTL=ONF), you can set a hysteresis around the on/off point (SP) to prevent chattering.
The cycle time is the period of on/off repetitions of a relay or voltage pulse output in time proportional PID control. The ratio of the ON time to the cycle time is proportional to the control output value.
This function should be used when the PV display value may fluctuate greatly, for example, when the measured input signal contains noise. The filter is of the first­order lag type, and FL sets the time constant. If a larger time constant is set, the filter can remove more noise.
Input
OFF
ON
Heating
side
100
100%
On/off point (SP)
2-seconds filter
(See note)
2.
When both the heating and cooling sides are under on-off control
HYS HYS
ON
Deadband
DB (+)
OFF
0SP
PV
100%
Hysteresis
Cycle time
t ON
t OFF
10-seconds filter
ON
OFF
1000SP
PV input bias
BS
Decimal point of measurement input
DP
Maximum/minimum value of input scale
measured
RH, RL
Maximum/minimum value of target setpoint range
SPH, SPL
Setpoint ramp up/ramp-down rate
UPR, DNR
Hysteresis for alarm 1 and 2
HY1, HY2
SUPER function selection
SC
This function adds a bias value to the measured input value, and the result is used for display and control computation.
PV value inside the controller
This function is useful for carrying out fine adjustment when the PV value is within the required accuracy but it differs from the value obtained by other equipment.
For DC voltage input, the input signal can be scaled for the particular engineering unit. For example, if you set the input type (IN) at range code 22, the initial range is 0.0 to 100.0.
Using DP, set the decimal point position fit for the
a.
engineering unit you want to use. (In the example below, the 2 digits to the right of the decimal point)
b.
Next, register the scale values of the measured input scale using RH and RL. (In the example below, RH=10.00 and RL=0.00)
Using the SPH and SPL parameters, you can limit the setting range of the target setpoint (SP) within the measured input range(scale).
This function prevents SP from being mistakenly set at too large or too small a value (beyond the setting range).
To prevent a sudden change in SP, or to change SP at a constant rate, ramp-up and ramp-down rates can be set separately. This function operates at the following events. a. SP change b. SP1/SP2 switching c. Power-on At power-on, SP starts from the current PV value.
measured input value
Initial scale
Measured input scale
(after being scaled)
R
egister the decimal point position using DP.
Set the ramp-rate time unit using parameter TMU.
The alarms are output as relay outputs. Since a relay has a limited life, excessive on/off actions will shorten the life of the alarm. To prevent this, you can set a hysteresis to prevent excessive on/off actions for both alarm 1 and alarm 2.
The SUPER function is effective in the following cases: a. An overshoot must be suppressed. b. The rise-up time needs to be shortened. c. The load often varies. d. SP is changed frequently. Note 1: The SUPER function will not work when
on/off control is selected, or I or D constants is set at OFF in PID control.
Note 2: For some types of systems, the SUPER
function may not be so useful. If this is the case, turn off the function.
Closed contact
during alarm
Cls (on)
(See note.)
(See note.)
Opn
Cls (off)
Cls (on)
Time
Alarm
type code
Open contact
during alarm
16
(See note.)
7
17
8
18
19
(See note.)
10
20
(See note.)
24
25
Low limit alarm setpoint
PV bias+=
100.0 (5V)0.0 (1V)
10.00 (RH)0.00 (RL)
Ramp-rate for n°C/min. or n°C/h.
6
9
What is Dynamic Auto Tune Control?
Dynamic auto tune control is one of the features offered by the temperature controller. When the controller is turned on or the measured input value (PV) starts “hunting”, this mode of control monitors the behavior of the PV and/or OUT (control output value) to automatically determine the optimum PID constants. This means that the PID constants may be changed automatically. If this is not desirable for your system, operate the controller in the normal PID control”. If you want to automatically determine the PID constants at the initial startup of the controller, first define the target setpoint (SP) and then turn the controller off once and then back on again. Do not use dynamic auto tune control for a system where there is interference or continual disturbances.
Parameter Lists
(1) Target Setpoint (SP) and Timer Setting 1 and 2
Code Name Setting range and unit Default User setting
(SP value display)
T1
T2
Target setpoint
Timer setting 1
Timer setting 2
Minimum value (SPL) to maximum value (SPH) of target setpoint range Unit: °C/°F
0.0 to 99.59 Unit: minutes and seconds or hours and minutes Set the timer time unit using parameter TTU.
For example, 15.25 sets 15 minutes and 25 seconds. (T1 is for AL1, and T2 is for AL2)
Numbers in ( ) are the parmeter setpoints that apply when the communication function is used. Ex. OFF(0), ON(1)
SPL
0.00
0.00
(2) Operating Parameters : Parameters changed rather frequently during operation.
Code Setting range and unit Default User setting
A1
A2
HC
CTL
AT
P
I
D
MR
COL
DB
HYS
CT
CTC
SP1
SP2
FL
BS
LOC
Name
Alarm 1 setpoint
Alarm 2 setpoint
Heater disconnection current measured value
Control mode
Auto-tuning
Proportional band
Integral time
Derivative time
Manual reset –100 to 100%
Cooling-side gain
Deadband
Hysteresis for on/off control
Control output cycle time
Cooling-side control output cycle time
Target setpoint 1
Target setpoint 2
PV input filter
PV input bias
Key lock
PV alarm Unit: °C/°F
Setting range: minimum value to maximum value of measured input range (scale)
Deviation alarm Unit: °C/°F
Setting range: –100 to 100% of the measured input range (scale) span
Heater disconnection alarm Unit: A (ampere)
Setting range: OFF(0), 1 to 80 (can be set for the alarm 1 setpoint only)
HC is not a parameter to be set. The current value (0 to 80) of heater disconnection detector is displayed. Unit: A (ampere) Settings: When the display value is ––––, the heater current is not being measured.
ONF(0): On/off control PID(1): PID control
Dynamic auto tune control (cannot be set for heating/cooling control)
SLF(2): OFF(0): Stop auto-tuning
ON(1): Start auto-tuning 1°C/°F to the temperature that corresponds to 100% of the
measured input range (scale) span 1 to 3600 seconds;
OFF(0): no integral action
1 to 3600 seconds; OFF(0): no derivative action
0.01 to 9.99 times
PID control Unit: °C/°F
Setting range: –(proportional band setting) to +(proportional band setting)
On/off control Unit: °C/°F
Setting range: –50 to +50% of measured input range (scale)span
0°C/°F to the temperature that corresponds to 100% of the measured input range (scale) span
1 to 240 seconds
1 to 240 seconds 30 seconds
Minimum value (SPL) to maximum value (SPH) of target setpoint range Unit: °C/°F
There are also optional engineering units for voltage input.
OFF(0), 1 to 120 seconds
–100 to 100% of measured input range (scale) span
0: No key lock 1: Prevents operations from being changed except for the
changing of SP in the operating display 2: Prevents all parameter changing operations –1: Set -1 to enter the setup parameter setting display. But if LOC=1 or 2 is already set, the parameter value can
not be changed by setting LOC=-1 only. To change the
parameter value, set LOC=0 at first (for disabling keylock),
then set LOC=-1 once again.
Max. value of measured input range (scale) (PV alarm)
Min. value of measured input range (scale) (PV alarm)
SLF(2) :for standard type; PID(1) : for
heating/cooling type
OFF(0)
5% of measured input range (scale) span
240 seconds
60 seconds
50.0%
for standard type
0.0% for heating/cooling type
1.00 times
0% of measured input range (scale) span
0.5% of measured input range (scale) span
30 seconds
SPL
SPL
OFF(0)
0% of measured input range (scale) span
0
;
(3) Setup Parameters : Parameters rarely changed in normal use after once having been set.
Code Name Setting range and unit Default User setting
Measured
IN
DP
RH
RL
SPH
SPL
UPR
DNR
TMU
DIS
EOT
TTU
RTH
RTL
AL1
AL2
HY1
HY2
SC
DR
PSL
ADR
BPS
PRI
STP
DLN
input type
Decimal point position of measured input
Maximum value of measured input scale
Minimum value of measured input scale
Maximum value of target setpoint range
Minimum value of target setpoint range
Setpoint ramp­up-rate
Setpoint ramp­down-rate
Setpoint ramp­rate time unit
DI-function selection
Output in STOP mode
Timer time unit Maximum value
of retransmission output Minimum value of retransmission output
Alarm 1 type
Alarm 2 type
Alarm 1 hysteresis
Alarm 2 hysteresis
SUPER function
Direct/reverse action
Protocol selection
Controller address
Baud rate
Parity
Stop bit
Data length
1 to 23, 31 to 48 (See input range code list.) OFF(0): No input (If no input type is specified at the time of ordering, you must set the input type.)
0: No decimal place (nnnn) 1: One decimal place (nnn.n) 2: Two decimal places (nn.nn) 3: Three decimal places (n.nnn)
(RL + 1) to 9999 100.0
–1999 to (RH –1) 0.0
(SPL+1°C) to the maximum value of the measured input range (scale) ; Unit: °C/°F
Minimum value of measured input range (scale) to (SPH –1°C) Unit: °C/°F
OFF(0) or a value from the minimum to the maximum value of the measured input range (scale) Unit: °C/min or °C/hour, °F/min or °F/hour Set the ramp-rate time unit using parameter TMU.
0 : °C or °F / hour 1 : °C or °F / min
External Contact Inputs
UT152
UT150
UT155
TMR STOP
21
3
SP2 STOP
22
4
COM
23
5
In STOP mode by contact input, fixed control output can be generated. 0 : 0%, 1 : 100%
0 : hour.minute 1 : minute.second
Temperature input : Within measured input range Voltage input : RTL+1digit to max. value of measured input
(scale)(RH) Min. value of measured input (scale)(RL) to RTH-1digit However, RTL<RTH
OFF(0) or a value from 1 to 22 (see the table of alarm function list), and either 23 or 24 (if the timer function [/EX option] is included), and 25 (if the heater disconnection function [/HBA option] is included) OFF(0) or a value from 1 to 22 (see the table of alarm function list), and either 23 or 24 (if the timer function [/EX option]) is included)
0 to 100% of measured input range (scale) span Unit: °C/°F
ON(1): Uses the SUPER function OFF(0): Does not use SUPER function Note: Not displayed when on/off control
0: Reverse action 1: Direct action Note: Not displayed for heating/cooling type
0: PC-link communication 1: PC-link communication with sum check 2: Ladder communication 3: MODBUS in ASCII mode 4: MODBUS in RTU mode
1 to 99 However, the number of controllers that can be connected per host device is 31 at the maximum.
2.4(0): 2400 bps
4.8(1): 4800 bps
9.6(2): 9600 bps NON(0): Disabled
EVN(1); Even parity ODD(2): Odd parity
1 or 2 bits 7 or 8 bits
8 bits when ladder, MODBUS (RTU)
7 bits when MODBUS (ASCII)
(Displayed at voltage input)
(Displayed at voltage input)
(Displayed at voltage input)
0
Timer starts when DI=ON
TMR
Timer stops
STOP
when DI=OFF
SP1/SP2
SP2
switching SP2
STOP
when DI=ON
Parameter DIS
1
Timer starts when DI=ON Timer stops when DI=OFF
RUN/STOP switching STOP when DI=ON
2
RUN/STOP switching STOP when DI=ON
SP1/SP2 switching SP2 when DI=ON
OFF(0), or the input range code specified with order
1
Maximum value of measured input range (scale)
Minimum value of measured input range (scale)
OFF(0)
OFF(0)
1
0
0
1 Maximum value of
measured input range (scale)
Minimum value of measured input range (scale)
1 (PV high limit alarm)
2 (PV low limit alarm)
0.5% of measured input range (scale) span
OFF(0)
0
0
1
9.6(2)
EVN(1)
1 bit
8 bits
IMPORTANT
To use dynamic auto tune control, (1) be sure to turn on the final control element, such as a heater, before starting the control, and (2) make sure the controlled loop is a closed loop. If you do not follow these precautions, improper PID constants may be written into the controller. If this occurs, carry out the following:
Set the parameter CTL at PID.
Set the PID constants at the factory-set defaults (P = (upper range-limit - lower range-limit) × 5%; I = 240 s.; and D = 60 s.)
Set the parameter CTL at SLF. If the control still doesnt work properly, stop using the dynamic auto tune control function. Change the param-
eter CTL setting to PID and execute auto-tuning to obtain the PID constants.
IM05C01E12-01E
4
Loading...