YOKOGAWA US1000 User's Manual

Setup Parameters (for building functions)
IM 5D1A01-81E 1st Edition Oct. 1998
Setup parameters are used to configure controller functions and cannot be changed during operation. (You must stop the control to change setup param­eters.)
Operation display
O.LP1
DISP
SET/ENT
Note: Initialization is required
(or MODE menu) Press the / keys to display STUP. Press SET/ENT key.
STUP
PS.IN
: Goes back to one-level higher in hierarchy.
: Returns to operation display when pressed for 3 seconds.
after settings are made.
Set the operation mode to MAN, then press SET/ENT key for 3 seconds.
(Input the password and press the SET/ENT key twice.)
S.LP1
SET/ENT
SV
ALM
SET/ENT
S.LP2
SET/ENT
CMLP AIN
C.CTL
RET
KLCK
MLCK R485
CONF
SET/ENT
C.SEL U.OPE
DO
DI
C.PYS
USMD
SET/ENT
MD
IN(See note)
OUT
VALV
INT
TEST
Scroll through the items using the SET/ENT key; set data with the
/ keys; and write the data with
the SET/ENT key.
CAS input, PV tracking,
SET/ENT
SV ramp rate
SET/ENT
Alarm type, mode
SET/ENT
Control function
Loop-2: the same as loop-1
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
Analog input computation Preset PID, power recovery,
pulse output Retransmission output 1-3
Key lock Menu lock RS-485 communication
SELECT display USER display
Contact output Contact input 10-seg. linearizer unit
Controller mode, control period
Analog input type, range, scale, and unit
MV output, analog output type Motor valve calibration Parameter initialization
(For adjustment at shipment only; not for operation.)
Setup Parameter List
Parameters marked with an asterisk (*): Be sure to check (and change) the settings. Other parameters: Use their default settings for general use, and change as necessary.
Code Description Setting range
SV
CMS Cascade input selection PVT PV tracking selection OFF, ON
TMU Time unit for ramp-rate setting 0 = 1 hour, 1 = 1 minute DVB Deviation display range EUS(0.0 to 100%)
AIN = analog input, CPT = communication
ALM
* AL1 Alarm 1 type * AL2 Alarm 2 type * AL3 Alarm 3 type * AL4 Alarm 4 type HY1 -
Alarm 1 to 4 hysteresis
HY4 PVR.T PV velocity alarm duration time 1 to 9999 seconds AMD Alarm mode 0 = Always enabled, 1 to 5
OFF, 1 to 29 (PV high limit = 1, PV low limit = 2. See the table overleaf for other alarms.)
MV alarm: 0 to 100.0%, EUS(0.0 to 100.0%)
MVR Output velocity limiter OFF, 0.1 to 100.0% per second * MOD PID control mode 0 = batch, 1 = fixed point AR Anti-reset windup AUTO, 50.0 to 200.0% FFS Feedforward input selection OFF = disabled, AIN = analog input
AIN
A.BS1 Analog Input-1(AIN1)bias EUS(-100.0 to 100.0%) A.FL1 AIN1 filter OFF, 1 to 120 seconds A.SR1 AIN1 square-root computation OFF, ON
AIN1 square-root low signal
A.LC1
cutoff
A.BO1 AIN1 burnout action OFF, UPS, DNS
AIN1 reference junction
A.RJ1
compensation A.BS2 to A.RJ2: Parameters for analog input-2 (the same as for AIN1) A.BS3 to A.BO3: Parameters for analog input-3 (the same as for AIN1), but without RJ
0.0 to 5.0%
OFF, ON
C.CTL
PPID Preset PID function selection 0 = disabled, 1 = SV no., 2 = zone PID
Restart mode (upon power
recovery for power failures of
R.MD
no less than 2 seconds) R.TM Restart timer 0 to 60 seconds * CT1, 2 Cycle time of MV1, MV2 1 to 1000 seconds
Cycle time of cooling-side MV1, CTc1, 2
MV2
HOT = continues the operation prior to power failure, COLD = starts in MAN mode
1 to 1000 seconds
RET
RET1 Retransmission output-1 type
Max. value of retransmission RTH1
output-1 scale
OFF=disabled,1=PV1, 2=SV1, 3=MV1, 4=PV2, 5=SV2, 6=MV2
RTL1<RTH1(EU(100.0%)
Default
EUS(1.65%)
1= PV high
2= PV low
1= PV high
2= PV low
EUS or MV alarm
0.5%
1 second
AUTO
EUS(0.0%)
1.0%
COLD
0 seconds
30 seconds 30 seconds
3=(MV1)
100.0
AIN OFF
OFF
OFF
OFF OFF
OFF OFF
Min. value of retransmission
RTL1
output-1 scale RET2 Retransmission output-2 type OFF=disabled, 1 to 6 RTH2,
Max./min. values of RTL2
retransmission output-2 scale * RET3 Retransmission output-3 type OFF=disabled, 1 to 6
RTH3,
Max/min values of RTL3
retransmission output-3 scale
EU(0.0%)(RTL1<RTH1
The same as RTH1 and RTL1
The same as for RTH1 andRTL1
0.0
2=(SV1)
P.RL to P.RH
1=(PV1)
P.RL to P.RH
KLCK
SVC SV setting keylock OFF, ON
/ Data setting keylock OFF, ON
0
< / > MV operation keylock OFF, ON C CAS mode keylock OFF, ON A AUTO mode keylock OFF, ON M MAN mode keylock OFF, ON
OFF OFF OFF
ON OFF OFF
MLCK
MODE MODE menu lock OFF, ON O.LP1 O.LP1 menu lock OFF, ON O.LP2 O.LP2 menu lock OFF, ON PID PID menu lock OFF, ON USR USR menu lock OFF, ON
0
1
PYS1,
PYS1/2 menu lock OFF, ON
PYS2 PWD Password setting 0 = no password, 1 to 30000
R485
0 = MODBUS(ASCII),
PSL Protocol selection
BPS Baud rate 600 to 38400bps PARI Parity N = none, E = even, O = odd STP Stop bit 1, 2 DLN Data length 7, 8 ADR Controller address 1 to 99 RSP.T Minimum response time
1 = MODBUS(RTU), 2 = PC-link communication 3 = As above (but with sum check)
0 to 10 ( x 10ms)
OFF OFF OFF OFF OFF
OFF
0
0
9600
E 1 8 1 0
C.SEL and U.OPE
C.S1 -
Registration for the
C.S5
SELECT display 1 to 5 U.1AL USER display of loop-1 alarm OFF, ON U.2AL USER display of loop-2 alarm OFF, ON
0
U.SVN USER display of SV number OFF, ON
USER display of U.1PI
loop-1 PID group No.
USER display of U.2PI
loop-2 PID group No.
USER display of AIN1 to 3 U.AI1 - 3
measured values U.PV1 - 2
USER display of PV1, 2 OFF, ON
USER display of sampling error U.SMP
counter
OFF, 201 to 773
OFF, ON
OFF, ON
OFF, ON
OFF, ON
OFF OFF
OFF OFF
OFF
OFF
OFF OFF OFF
DO
DO1 -
Output flag registration for DO7
DO1 to 7
(Refer to the instruction manual)IM5D1A01-01E
Code Description Setting range Default
DI
CAS1
Loop-1 mode switchover to CAS Loop-1 mode switchover to AUTO
AUT1 MAN1 Loop-1 mode switchover to MAN CAS2 -
Loop-2 mode switchover to
MAN2
CAS/AUTO/MAN Open/Close switchover of
O/C
internal cascade loop R/S RUN/STOP switchover TRF1,
Loop-1,2 tracking flags TRF2
SV.B0 -
Bit 0-3 of SV number setting SV.B3
Operation display for DP1, DP2
interruption 1, 2 MG1 -
Message interruption display 1 to 4 MG4
Set the I-relay number of the contact input to be connected. DI1= 5161, DI2= 5162 DI3= 5163, DI4= 5164 DI5= 5165, DI6= 5166 DI7= 5167
Depends upon the mode of the controller.
C.PYS
10- segment linearizer-1 input PY1X
unit
10- segment linearizer-1 output PY1Y
unit PY2X,
10- segment linearizer-2 PY2Y
input/output unit
0 to 15 12=EU(PV1), 13=EUS(PV1) 14=EU(PV2), 15=EUS(PV2)
14/15
MD
1 to 21
* USM Controller mode (US mode)
SMP Control period 50, 100, 200, 500 ms
(See "Controller Mode (USMD-MD) and ApplicableController Type.")
IN
* TYP1 Analog input-1 (AIN1) type * UNT1 AIN1 unit ˚C (Celsius),˚ F (Fahrenheit) * RH1 Max. value of AIN1 range Within instrument range
* RL1 Min. value of AIN1 range Within instrument range * SDP1 AIN1 decimal point position 0 to 4
* SH1 Max. value of AIN1 scale -19999 to 30000 * SL1 Min. value of AIN1 scale -19999 to 30000 TYP2 to SL2 : Parameters for analog input-2 (the same as AIN1 parameters) TYP3 to SL3 : Parameters for analog input-3 (the same as AIN1 parameters except for the unit) P.DP1** PV1 decimal point position 0 to 4 P.RH1** Max. value of PV1 range -19999 to 30000 P.RL1** Min. value of PV1 range -19999 to 30000 P.DP2, P.RH2, P.RL2: Parameters for PV2 (the same as PV1 parameters)
** P.DPn, P.RHn, P.RLn are used for loop control with PV switching/auto-selector.
1 to 56 (See "Analog Input Type List (for setting IN-TYPn).")
Max. value of
instrument range
Min. value of
instrument range
100.0
100.0
OUT
* MVS1,
MV1, MV2 selection * MVS2
AO1 -
Analog output 1/2/3 type AO3
Reverse display and operation of RVOP
MV
1 to 12 (See "MV Output Types (for setting OUT-MVS1,MVS2).") 2 = current
0 = 4 to 20 mA, 1 = 0 to 20 mA, 2 = 20 to 4 mA, 3 = 20 to 0 mA
OFF, ON
12
13
200
41 ˚C
0.0
0.0
OFF
VALV (US1000-21 only)
V.RS Reset valve position
V.L Valve in fully-closed position
V.H Valve in fully-opened position
Auto-calibration for valve
V.AT
positioning
0 = normal position, 1 = reset position data
Close the valve completely using the key, then press SET/ENT to save the position.
Open the valve completely using the key, then press SET/ENT to save the position.
OFF, ON
0
OFF
INT
* INIT Parameter initialization OFF, ON
OFF
Analog Input Type List (for setting IN-TYPn)
Type Range (˚F )
Thermocouple
1
Platinel 2 16
PR20-40 17
W97Re3 W75Re25
JPt100
RTD
1
Standard signal
1
2
0
DC voltage
Pt100 (ITS90)
0.4 to 2.0 V 40 1 to 5 V 41 0 to 2 V 50
0 to 10 V 51
-10 to 20 mV 55 0 to 100 mV 56
Setting Range (˚C)
K
J4
T
B7 S8 R9 N10 E11 L12
U
W15
1 2 3
5 6
13 14
18 30
31 35 36 37
-270.0 to 1370.0 ˚C
-270.0 to 1000.0 ˚C
-200.0 to 500.0 ˚C
-200.0 to 1200.0 ˚C
-270.0 to 400.0 ˚C
0.0 to 400.0 ˚C
0.0 to 1800.0 ˚C
0.0 to 1700.0 ˚C
0.0 to 1700.0 ˚C
-200.0 to 1300.0 ˚C
-270.0 to 1000.0 ˚C
-200.0 to 900.0 ˚C
-200.0 to 400.0 ˚C
0.0 to 400.0 ˚C
0.0 to 2300.0 ˚C
0.0 to 1390.0 ˚C
0.0 to 1900.0 ˚C
0.0 to 2000.0 ˚C
-200.0 to 500.0 ˚C
-150.00 to 150.00 ˚C
-200.0 to 850.0 ˚C
-200.0 to 500.0 ˚C
-150.00 to 150.00 ˚C
0.400 to 2.000
1.000 to 5.000
0.000 to 2.000
0.00 to 10.00
-10.00 to 20.00
0.0 to 100.0
-450.0 to 2500.0 ˚F
-450.0 to 2300.0 ˚F
-200.0 to 1000.0 ˚F
-300.0 to 2300.0 ˚F
-450.0 to 750.0 ˚F
-200.0 to 750.0 ˚F 32 to 3300 ˚F 32 to 3100 ˚F 32 to 3100 ˚F
-300.0 to 2400.0 ˚F
-450.0 to 1800.0 ˚F
-300.0 to 1600.0 ˚F
-300.0 to 750.0 ˚F
-200.0 to 1000.0 ˚F 32 to 4200 ˚F
32.0 to 2500.0 ˚F 32 to 3400 ˚F
32 to 3600 ˚F
-300.0 to 1000.0 ˚F
-200.0 to 300.0 ˚F
-300.0 to 1560.0 ˚F
-300.0 to 1000.0 ˚F
-200.0 to 300.00 ˚F
Alarm Type List (for setting ALM-AL1 to AL4)
Alarm type Setting
PV high limit 1 PV high limit 11 PV low limit 2 PV low limit 12 High limit deviation 3 High limit deviation 13 Low limit deviation 4 Low limit deviation 14 Deviation of high limit passive 5 Deviation of high limit passive 15 Deviation of low limit passive 6 Deviation of low limit passive 16 Deviation of high and low limits 7 Deviation of high and low limits 17 Deviation within high and low limits 8 Deviation within high and low limits 18 PV high limit passive 9 PV high limit passive 19 PV low limit passive 10 PV low limit passive 20 SV high limit 21 PV velocity alarm 25 SV low limit 22 PV velocity alarm passive 26 MV high limit 23 Self-diagnostic alarm 27 MV low limit 24 Self-diagnostic alarm passive 28
FAIL passive 29
Alarm type
(11 to 20: with waiting action)
Setting
Controller Mode (USMD-MD) and Applicable Controller Type
Controller mode Setting
Single-loop control 1 Cascade primary-loop control 2 Cascade secondary-loop control 3 Cascade control 4 Loop control for backup 5 Loop control with PV switching 6 Loop control with PV auto-selector 7 Loop control with PV-hold function 8 Dual-loop control 11 Temperature and humidity control 12 Cascade control with two universal inputs 13 Loop control with PV switching and two universal inputs Loop control with PV auto-selector and two universal
inputs Custom computation control 21
= Applicable
14
15
Type of US1000
-00 -11 -21
✔✔✔ ✔✔ ✔✔✔ ✔✔✔ ✔✔✔ ✔✔✔ ✔✔✔ ✔✔✔
MV Output Types (for setting OUT-MVS1,MVS2)
MV output Setting MV output
Time proportional PID with relay output
Time proportional PID with voltage pulse output
Continuous PID with current output
On/off control with relay output0
Position proportional PID1–
2
• Single-loop/cascade control with heating and cooling output (H = heating output, C = cooling output)
4=(H=relay, C=rela y), 5=(H=pulse, C=relay), 6=(H=current, C=relay), 7=(H=relay, C=pulse), 8=(H=pulse, C=pulse), 9=(H=current, C=pulse),
Setting
– –
✔ ✔
✔ ✔
3
10=(H=relay, C=current), 11=(H=pulse, C=current), 12=(H=current, C=current)
• Dual-loop/temperature & humidity control with heating and cooling output (H = heating output, C = cooling output)
4=(H=pulse, C=relay), 5=(H=relay, C=pulse), 6=(H=current, C=relay), 7=(H=relay, C=current)