This user’s manual describes the communication functions of the UPM100 and UPM101
universal power monitors and contains information on how to create communication
programs.
Read the manual carefully to understand the communication functions of the UPM100 and
UPM101 universal power monitors.
In this manual, “UPM100 and UPM101 universal power monitors” are referred to as
“UPM100 universal power monitor” because the communication functions of UPM100
and UPM101 universal power monitors are common.
And the illustrations of “UPM100 universal power monitor with display function” are used
for description.
The UPM100 universal power monitor has the following communication protocols.
• PC link communication protocol
• MODBUS communication protocol
• UPM01 communication protocol
1
You are required to have background knowledge of the communication specifications
of higher-level devices, their communication hardware, language used for creating
communication programs, and so on.
1: The UPM01 communication protocol is the original communication protocol for the UPM01,
UPM02, and UPM03. The protocol can be used only for the UPM100 universal power monitor
with the optional measuring function “Integral resolution Wh” specified at ordering.
Intended Readers
This manual is intended for people familiar with the functions of the UPM100 universal
power monitor, control engineers and personnel in charge of maintaining instrumentation
and control equipment.
Related Documents
The following user’s manuals all relate to the communication functions of the UPM100
universal power monitor. Read them as necessary.
• Model UPM100 Universal Power Monitor User’s Manual
Document number: IM 77C01H01-00EN
• Model UPM100 Universal Power Monitor User’s Manual
(for 920 MHz Wireless Communication model)
Document number: IM 77C01H01-43EN
Note: 920 MHz wireless communication can be used only in the Republic of Korea.
• Model UPM101 Universal Power Monitor (With Dedicated CT) User’s Manual
Document number: IM 77C01J01-00EN
See AlsoGives reference locations for further information on the topic.
Symbols Used in Figures and Tables
Markings
[See Also]Gives reference locations for further information on the topic.
NoteDraws attention to information that is essential for understanding
the operation and/or features of the product.
TIPGives additional information to complement the present topic.
[NOTE]Draws attention to information that is essential for understanding
the features of the product.
[TIP]Gives additional information to complement the present topic.
Description of Displays
1. Some of the representations of product displays shown in this manual may be
exaggerated, simplified, or partially omitted for reasons of convenience when explaining
them.
2. Figures and illustrations representing the universal power monitor’s displays may differ
from the real displays in regard to the position and/or indicated characters (uppercase or lower-case, for example), the extent of difference does not impair a correct
understanding of the functions and the proper operations and monitoring of the system.
ii
IM 77C01H01-10EN
Notices
Regarding This User’s Manual
1. This manual should be passed on to the end user. Keep the manual in a safe place.
2. Read this manual carefully to gain a thorough understanding of how to operate this
product before you start using it.
3. This manual is intended to describe the functions of this product. Yokogawa Electric
Corporation (hereinafter simply referred to as Yokogawa) does not guarantee that these
functions are suited to the particular purpose of the user.
4. Under absolutely no circumstance may the contents of this manual, in part or in whole,
be transcribed or copied without permission.
5. The contents of this manual are subject to change without prior notice.
6. Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention however, please contact your
nearest Yokogawa representative or our sales office.
Regarding Protection, Safety, and Prohibition Against Unauthorized Modification
1. In order to protect the product and the system controlled by it against damage and
ensure its safe use, be certain to strictly adhere to all of the instructions and precautions
relating to safety contained in this document. Yokogawa does not guarantee safety if
products are not handled according to these instructions.
2. The following safety symbols are used on the product and/or in this manual.
Symbols Used on the Product and in This Manual
Markings
This symbol on the product indicates that the operator must refer
to an explanation in the user’s manual in order to avoid the risk
of injury or death of personnel or damage to the instrument. The
manual describes how the operator should exercise special care
to avoid electric shock or other dangers that may result in injury or
loss of life.
Protective
Grounding
Terminal
This symbol indicates that the terminal must be connected to
ground prior to operating the equipment.
IM 77C01H01-10EN
iii
Force Majeure
1. Yokogawa does not make any warranties regarding the product except those mentioned
in the WARRANTY that is provided separately.
2. Yokogawa assumes no liability to any party for any loss or damage, direct or indirect,
caused by the use or any unpredictable defect of the product.
3. Be sure to use the spare parts approved by Yokogawa when replacing parts or
consumables.
4. Modification of the product is strictly prohibited.
5. Reverse engineering such as the disassembly or decompilation of software is strictly
prohibited.
6. No portion of the software supplied by Yokogawa may be transferred, exchanged,
leased, or sublet for use by any third party without the prior permission of Yokogawa.
iv
IM 77C01H01-10EN
Contents
Introduction ................................................................................................................................................ i
Documentation Conventions .................................................................................................................... ii
8.3.1 Measured Items (Category A) ................................................................................................8-5
8.3.2 Statistical Items (Category B) .................................................................................................8-7
8.3.3 Set Items (Category C) ..........................................................................................................8-8
8.3.4 User Control Items (Category E) ..........................................................................................8-10
Appendix
Appendix 1 Table of ASCII Codes (Alphanumeric Codes) .................................................................App-1
Revision Information
vi
IM 77C01H01-10EN
010101E.EPS
Chapter 1 Setup
1 Setup
This chapter describes the setup procedure required to use the communication functions
and the communication specifications of the UPM100 universal power monitor.
Hereafter, the UPM100 universal power monitor is simply referred to as the UPM100.
1.1 Setup Procedure
Set up the communication functions on the UPM100 as follows:
Set up the communication function parameters of the UPM100.
For the UPM100 with display function, set up the communication conditions using the
front panel keys.
For the UPM100 without display function, set up the communication conditions using
the front DIP switches. (See the user's manual of Model UPM100 Power Monitor
<Initial Setup Operations>.)
Connect a higher-level device and a UPM100.
(See the user's manual of Model UPM100 Power Monitor <Installation>.)
1
Setup
Create communication programs for the higher-level device to perform communication.
(See "4. PC Link Commnication" or "5. MODBUS Communication" for the communication
protocol. See "6. Functions and Usage of D Registers", "7. Functions and Usage of I
Relays" and "8. UPM01 Communication" for the data storing.)
To avoid an electric shock, be sure to turn off the power supply source to the
equipment involved before you start wiring.
Note
• In the case of PLC (MELSEC:Mitsubishi Electric Corporation’s sequencer), “B” is for (-), and “A”
is for (+).
• Do not share the grounding wire with another instrument. Doing so may result in a failure of the
instrument. Use crimp terminals at cable ends.
Note Create communication programs referring to the documentation of each higher-level device.
Higher-level devices : PCs, PLCs (sequencers), touch panels, and others.
IM 77C01H01-10EN
1-1
1.2 Notes on Setting RS-485 Communication Conditions
This section describes the setting parameters for using the communication functions
and their setting ranges.
Note
The details of the UPM100 communication conditions need to be the same as those of the
communication conditions of the higher-level device to be connected.
• UPM100 without display function (UPM100-xx0xx-20 or UPM100-xx2xx-20): Set up
the communication conditions using the front DIP switches. (See the user’s manual of Model
UPM100 Universal Power Monitor <Initial Setup Operations>.)
• UPM100 with display function (UPM100-xx1xx-20 or UPM100-xx3xx-20): Set up
the communication parameters using the front panel keys. (See the user’s manual of Model
UPM100 Universal Power Monitor <Initial Setup Operations>.)
Table 1-1 Parameters to be Set for Communication Functions
Initial Setting
Parameter
Name
RS-485
communication
protocol
Parameter
Symbol
(COMM)
Setting Range
PC link without checksum PCLK1
PC link with checksumPCLK2
MODBUS (ASCII mode) M ASC
MODBUS (RTU mode)M RTU
UPM01UPM01
Without 920
MHz Wireless
Communication
PCLK2M RTU
2
With 920 MHz
Wireless
Communication
3
RS-485
station number
RS-485
communication
baud rate
(ST-NO)
(B-RT)
1 to 99 (1 to 31 recommended)11
2400 bps
9600 bps
960019200
19200 bps
NoneNONE
Parity
Stop bit
Data length
(PRI)
(STP)
1
(DLN)
EvenEVEN
OddODD
1
2
7
8
NONENONE
11
88
3
3
1: When “MODBUS (ASCII mode)” is selected in protocol selection, select “7” or “8” for the data
length. When “MODBUS (RTU mode)” is selected, select “8.” Otherwise, communication cannot
be achieved.
2: The UPM01 communication is selectable only when the optional measuring function “Integral
resolution Wh” is specified at ordering.
3: When using 920 MHz Wireless Communication, please use the default value above.
Note: 920 MHz wireless communication can be used only in the Republic of Korea.
3
3
1-2
IM 77C01H01-10EN
1.2 Notes on Setting RS-485 Communication Conditions
Use the DIP switches to enter the settings on UPM100 without display function.
Referring to the diagram below, set the binary values, with the first bit on the left.
When using 920 MHz Wireless Communication, please use the factory setting values except
for the address.
Note: 920 MHz wireless communication can be used only in the Republic of Korea.
<Address (station number)>
0: Usage prohibited
1 to 99 can be set (1 to 31
recommended)
(Initial setting: 1)
<UPM01 protocol>
0: None
1: With protocol
denotes initial settings.
1
0
<Parity>
00: None
01: Even
10: Odd
11: Usage prohibited
<Data length>
0: 8 bits
1: 7 bits
<Stop bit>
0: 1 bit
1: 2 bits
<Communication protocol>
00: PC link without SUM
01: PC link with SUM
10: MODBUS ASCII
11: MODBUS RTU
<Baud rate>
00: 2400 bps
01: 9600 bps
10: 19200 bps
RS-485 communication protocol (COMM)
Set the communication protocol identical to that of the higher-level device to be connected.
1
Setup
RS-485 communication baud rate (B-RT)
Set the baud rate identical to that of the higher-level device to be connected. (Otherwise,
proper communication cannot be achieved.)
Parity (PRI)
Set the handling of parity to be carried out when data is sent or received. Set the parity bit
state identical to that of the higher-level device to be connected.
Stop bit (STP)
Set the stop bit identical to that of the higher-level device to be connected.
Data length (DLN)
Set the data length identical to that of the higher-level device to be connected. (When
“MODBUS (RTU mode)” is selected in protocol selection, select “8” for the data length.
When “MODBUS (ASCII mode)” is selected, select “7” or “8.”)
RS-485 station number (ST-NO)
Set the station number of the UPM100 itself. A station number of 1 to 99 may be assigned
in any order. However, there is a limitation - the number of UPM100 to be connected to a
single communication port is limited to 31.
When connecting two or more power monitors to a single communication port, make sure
none of the station numbers 1 to 31 is set twice.
IM 77C01H01-10EN
1-3
PC
010202E.EPS
1.2 Notes on Setting RS-485 Communication Conditions
Example of connecting four UPM100 to a higher-level device by setting station numbers of
01, 05, 10, and 20
Maximum overall cable length of 1200 m for a maximum of 31 slave stations
ST-NO=01ST-NO=05ST-NO=10ST-NO=20
<Binary Number Quick Reference Chart>
The following table is a binary number quick reference chart for use in setting addresses
(station numbers) with DIP switches.
The RS-485 communication interface has the PC link communication, MODBUS
communication, and UPM01 communication protocols.
Table 2-1 UPM100 Communication Specifications
Communication Hardware2-wire RS-485 communication system
PC link communication without checksum
Communication Protocol Specifications
Maximum Baud Rate19200 bps
Maximun Communication Distance1200 m
Communication Cable
*1 The UPM01 communication is selectable only when the optional measuring function “Integral
resolution Wh” is specified at ordering.
Table 2-2 Communication Protocols and Types of Devices to be Connected
Communication ProtocolExample of Connected Devices
PCs and the like which are installed with a MODBUS communication
MODBUS communication
PC link communication
UPM01 communication
driver and SCADA software.
PLCs which support MODBUS
PCs and the like which are installed with a PC-link communication
driver and SCADA software.
Touch panel (GP series)
PLCs (FA-M3’s UT link module)
PCs and the like which are installed with the PR970 which supports
the UPM01 protocol.
PCs and the like which are installed with SCADA software which
supports the UPM01 protocol.
PC link communication with checksum
MODBUS communication (ASCII mode)
MODBUS communication (RTU mode)
UPM01 communication*1
Shielded twisted-pair cable
(wire size equivalent to AWG24)
2
RS-485 Communication Specifications
Table 2-3 RS-485 Communication Interface
ItemSpecifications
StandardConforms to EIA, RS-485
Maximum number of devices to be connected31
Communication system2-wire, half duplex
SynchronizationStart-stop synchronization
Communication protocolNo protocol
Maximum communication distance1200 m
Baud rate2400, 9600 and 19200 bps
IM 77C01H01-10EN
2-1
Blank
Chapter 3 Procedures for Setting UPM100/UPM101 Functions
3
Procedures for Setting UPM100/UPM101 Functions
To set the functions of the UPM100, use the protocols described in “4. PC Link
Communication,” “5. MODBUS Communication,” or “8. UPM01 Communication” according
to the instructions in this chapter.
For details of each function, refer to the standard manuals that come with the UPM100.
For set value ranges, initial values, and data backup for registers, refer to “6. Functions and
Usage of the D Register.” D Register numbers are explained in this chapter, but refer to
Chapter 6 also for reference numbers for MODBUS communications.
The UPM100 offers registers for floating-point data. To perform settings via communication
starting from larger digits, floating-point data is displayed by IEEE754 (single precision).
Note
• The UPM100 has data (D register) the unit of which is two words. When 2-word data need to
be written or read, writing or reading operations must be performed for the 2- word data at the
same time.
• Even if data written to the D register is out of the effective range, a normal response is returned.
The part of the written data within the effective range becomes effective on the UPM100 when
the equivalent setting change status is written for that data.
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-1
3.1 Basic Setting
3.1.1 Setting of VT Ratio
[Procedure]
1. Write a VT ratio to the two D registers in the table below. The data type is 4-byte floating
point.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No.H No.DescriptionEffective Range
• The pulse unit-1 of electric energy value can be set for the UPM100 with pulse outputs.
• To set the pulse unit-1 of electric energy value using the UPM100 with the integral resolution
(kWh) option via communication, set it to 1/10th the value of the displayed (true) value (e.g., set
it to 5 when setting the pulse unit-1 of electric energy value to 50 Wh/pls).
The value of the UPM100 with the integral resolution (Wh) option should be the same as that of
the displayed value.
IM 77C01H01-10EN
3-5
3.2 Setting Pulse Output
3.2.2 ON Pulse Width-1 of Electric Energy
[Procedure]
1. Write an ON pulse width-1 of electric energy value to the D register in the table below.
The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
Note
When the value to be set for the ON pulse width-1 is greater than the value calculated by the
following equation, the value cannot be set:
ON pulse width (ms) ≤
D Register Reference No.H No.DescriptionEffective Range
D0052400520033
D0072400720047Setting change status
Default value of ON pulse width-1 of electric energy: 5 (50 ms)
Secondary rated power [W] x VT ratio x CT ratio x 1.2 x 2
Pulse unit [Wh/pls] x 60 x 60 x 1000
ON pulse width-1 of electric
energy value
1 to 127
Unit: x 10 ms
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the ON pulse width-1 of electric energy value to 100 ms, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
• The pulse unit-2 of electric energy value can be set for the UPM100 with pulse outputs and the
one with the reactive power/reactive energy measuring function.
• To set the pulse unit-2 of electric energy value using the UPM100 with the integral resolution
(kWh) option via communication, set it to 1/10th the value of the displayed (true) value (e.g., set
it to 5 when setting the pulse unit-2 of electric energy value to 50 varh/pls).
The value of the UPM100 with the integral resolution (Wh) option should be the same as that of
the displayed value.
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-7
3.2 Setting Pulse Output
3.2.4 LAG/LEAD/Regenerative Selection for Pulse Output of Electric Energy
[Procedure]
1. Write a value for LAG/LEAD/regenerative selection for pulse output of electric energy to
the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No.H No.DescriptionEffective Range
D0087400870056
D0072400720047Setting change status
Default value for LAG/LEAD/regenerative selection for output pulse of electric energy:
With the optional reactive power/reactive energy measuring function: 0 (LAG PULSE)
Without the optional reactive power/reactive energy measuring function: 2 (Regenerative PULSE)
Value for LAG/LEAD/
regenerative selection for
output pulse of electric energy
[Example]
To set a value for LAG/LEAD/regenerative selection to 1 (LEAD):
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
0: LAG PULSE
1: LEAD PULSE
2: Regenerative PULSE
If other than 1: Invalid
If 1: Writing is executed
The value for LAG/LEAD/regenerative selection for output pulse of electric energy value can be set
for the UPM100 with pulse outputs and the one with the reactive power/reactive energy measuring
function. For the UPM100 without the reactive power/reactive energy measuring function, only the
regenerative PULSE is available.
3-8
IM 77C01H01-10EN
3.2.5 ON Pulse Width-2 of Electric Energy
[Procedure]
1. Write an ON pulse width-2 of electric energy value to the D register in the table below.
The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
3.2 Setting Pulse Output
Note
When the value to be set for the ON pulse width-2 is greater than the value calculated by the
following equation, the value cannot be set:
ON pulse width (ms) ≤
D Register Reference No.H No.DescriptionEffective Range
D0085400850054
D0072400720047Setting change status
Default value of ON pulse width-2 of electric energy: 5 (50 ms)
Secondary rated power [W] x VT ratio x CT ratio x 1.2 x 2
[Example]
To set the ON pulse width-2 of electric energy value to 100 ms, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
If other than 1: Invalid
If 1: Writing is executed
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
Note
• The ON pulse width-2 of electric energy value can be set for the UPM100 with pulse outputs
and the one with the reactive power/reactive energy measuring function.
• To set the ON pulse width-2 of electric energy value via communication, set it to 1/10th the
value of the displayed (true) value (e.g., set it to 5 when setting the ON pulse width-2 of electric
energy value to 50 ms).
3-9
3.3 Executing Reset Operations
3.3.1 Remote Reset
[Procedure]
1. To execute remote reset, write data to the D register or the I relay in the table below.
The data type is integer.
D Register Reference No.H No.I relayDescriptionEffective Range
D005940059003AI0010Remote reset
Note
• By executing remote reset, the maximum, minimum, and instantaneous voltage and current
values are reset. Remote reset stops while the optional electric energy measuring function is in
operation.
• Even if remote reset is executed, data on active energy, reactive energy, and apparent energy
and the values set to their parameters will be saved.
• The D register and the I relay in the table above have the same functions.
[Example]
To execute remote reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
If other than 1: Invalid
If 1: UPM100 is reset
[Command]
[STX] 01010WRW01D0059, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
After remote reset is executed, the micro-computer of the UPM100 is reset. Wait for more than 5
seconds before executing another command.
3-10
IM 77C01H01-10EN
3.3.2 Active Energy Reset
[Procedure]
1. To execute active energy reset, write data to the D register or the I relay in the table
below. The data type is integer.
D Register Reference No. H No. I relayDescriptionEffective Range
D006040060003BI0011
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute active energy reset:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
[Command]
[STX] 01010WRW01D0060, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
3.3 Executing Reset Operations
Reset the active energy
(D0001 and D0002)
If other than 1: Invalid
If 1: Active energy is reset
3
Procedures for Setting UPM100/UPM101 Functions
3.3.3 Maximum/Minimum Values Reset
[Procedure]
1. To execute maximum/minimum values reset, write data to the D register or the I relay in
the table below. The data type is integer.
D Register Reference No. H No. I relayDescriptionEffective Range
D006140061003CI0012
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute maximum/minimum values reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0061, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the maximum/
minimum values
(D0023 to D0040)
If other than 1: Invalid
If 1: Maximum/minimum
values are reset
IM 77C01H01-10EN
3-11
3.3 Executing Reset Operations
3.3.4 Regenerative Energy Reset
[Procedure]
1. To execute regenerative energy reset, write data to the D register in the table below.
The data type is integer.
D Register Reference No. H No.DescriptionEffective Range
D006440064003F
[Example]
To execute regenerative energy reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0064, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the regenerative energy
(D0067 and D0068)
If other than 1: Invalid
If 1: Regenerative energy
is reset
3.3.5 Reactive Energy Reset
Note
Data can be written to the UPM100 with the optional reactive power/reactive energy measuring
function.
[Procedure]
1. To execute reactive energy reset, write data to the D register or the I relay in the table
below. The data type is integer.
D Register Reference No. H No. I relayDescriptionEffective Range
D009340093005CI0015
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute reactive energy reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0093, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the reactive energy
(D0077 to D0080)
If other than 1: Invalid
If 1: Reactive energy is
reset
3-12
IM 77C01H01-10EN
3.3.6 Apparent Energy Reset
[Procedure]
1. To execute apparent energy reset, write data to the D register in the table below.
The data type is integer.
D Register Reference No. H No.DescriptionEffective Range
D0097400970060
[Example]
To execute apparent energy reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0097, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the apparent energy
(D0083 and D0084)
3.3 Executing Reset Operations
If other than 1: Invalid
If 1: Apparent energy is reset
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-13
3.4 Other Settings
3.4.1 Start of Optional Integration
[Procedure]
1. To start optional integration, write data to the D register or the I relay in the table below.
The data type is integer.
D Register Reference No. H No. I relayDescriptionEffective Range
D006240062003DI0013
Note
The D register and the I relay in the table above have the same functions.
[Example]
To start optional integration:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0062, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Start of optional integration
(D0003 to D0006)
If other than 1: Invalid
If 1: Optional integration
is started
3.4.2 Stop of Optional Integration
[Procedure]
1. To stop optional integration, write data to the D register or to the I relay in the table
below. The data type is integer.
D Register Reference No. H No. I relayDescriptionEffective Range
D006340063003EI0014
Note
The D register and the I relay in the table above have the same functions.
[Example]
To stop optional integration:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0063, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Stop of optional integration
(D0003 and D0004)
If other than 1: Invalid
If 1: Optional integration is
stopped
3-14
IM 77C01H01-10EN
3.4.3 Start/Stop of Integration
[Procedure]
1. To start/stop integration, write data to the D register in the table below. The data type is
integer.
D Register Reference No. H No.DescriptionEffective Range
D0053400530034
[Example]
To start/stop integration:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
<Start>
[Command]
[STX] 01010WRW01D0053, 0000 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Active energy (D0001 and D0002)
Apparent energy (D0083 and D0084)
Regenerative energy (D0067 and D0068)
Reactive energy (D0077 to D0080)
3.4 Other Settings
0: Integration is started
1: Integration is stopped
3
Procedures for Setting UPM100/UPM101 Functions
<Stop>
[Command]
[STX] 01010WRW01D0053, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
IM 77C01H01-10EN
3-15
3.4 Other Settings
3.4.4 Active Energy Writing
[Procedure]
1. Write an active energy value to the two D registers in the table below. The data type is
integer.
2. After writing that value, write “1” to the write status register, D0073.
D Register Reference No. H No.DescriptionEffective Range
D0057400570038
D0058400580039
D0073400730048
[Example]
To set the active energy value to 12345:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
If 12345 is converted into a hexadecimal value, the value is 0000 3039. Then the order of
the upper two bytes and the lower two bytes is reversed → 3039 0000.
Set active energy value
(lower 2 bytes)
Set active energy value
(upper 2 bytes)
Set active energy value write
status
Refer to the "Note" below.
If other than 1: Invalid
If 1: Writing is executed
The set active energy value range of the UPM100 with the integral resolution (kWh) option changes
depending on the values of the VT and CT ratios. The table below shows the set value range.
[Secondary Rated Power] x [VT Ratio] x [CT Ratio]Possible Set Value Range
Below 1 MW 0 to 999999 kWh
1 MW to 10 MW 0.00 to 9999.999 MWh
10 MW or above 0.0 to 99999.999 MWh
Regardless of the value of [Secondary rated power] x [VT ratio] x [CT ratio], the set active
energy value range of the UPM100 with the integral resolution (Wh) option can be set within
the range below:
Possible set value range: 0 to 99999999 Wh
Note
The secondary rated power of the UPM100 changes depending on its model and suffix codes.
3-16
IM 77C01H01-10EN
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.