YOKOGAWA UPM100, UPM101 User Manual

User ’s Manual
Model UPM100, UPM101
Universal Power Monitor Communication Functions
Yokogawa Electric Corporation
IM 77C01H01-10EN
4th Edition

Introduction

This user’s manual describes the communication functions of the UPM100 and UPM101 universal power monitors and contains information on how to create communication programs.
Read the manual carefully to understand the communication functions of the UPM100 and UPM101 universal power monitors.
In this manual, “UPM100 and UPM101 universal power monitors” are referred to as “UPM100 universal power monitor” because the communication functions of UPM100 and UPM101 universal power monitors are common. And the illustrations of “UPM100 universal power monitor with display function” are used for description.
The UPM100 universal power monitor has the following communication protocols.
• PC link communication protocol
• MODBUS communication protocol
• UPM01 communication protocol
1
You are required to have background knowledge of the communication specifications of higher-level devices, their communication hardware, language used for creating communication programs, and so on.
1: The UPM01 communication protocol is the original communication protocol for the UPM01,
UPM02, and UPM03. The protocol can be used only for the UPM100 universal power monitor with the optional measuring function “Integral resolution Wh” specified at ordering.
Intended Readers
This manual is intended for people familiar with the functions of the UPM100 universal power monitor, control engineers and personnel in charge of maintaining instrumentation and control equipment.
Related Documents
The following user’s manuals all relate to the communication functions of the UPM100 universal power monitor. Read them as necessary.
• Model UPM100 Universal Power Monitor User’s Manual Document number: IM 77C01H01-00EN
• Model UPM100 Universal Power Monitor User’s Manual (for 920 MHz Wireless Communication model) Document number: IM 77C01H01-43EN Note: 920 MHz wireless communication can be used only in the Republic of Korea.
• Model UPM101 Universal Power Monitor (With Dedicated CT) User’s Manual Document number: IM 77C01J01-00EN
4th Edition: Mar. 8 All Rights Reserved, Copyright © 2005, Yokogawa Electric Corporation
IM 77C01H01-10EN

Documentation Conventions

Symbols
This manual uses the following symbols.
Symbols Used in the Main Text
Markings
See Also Gives reference locations for further information on the topic.
Symbols Used in Figures and Tables
Markings
[See Also] Gives reference locations for further information on the topic.
Note Draws attention to information that is essential for understanding
the operation and/or features of the product.
TIP Gives additional information to complement the present topic.
[NOTE] Draws attention to information that is essential for understanding
the features of the product.
[TIP] Gives additional information to complement the present topic.
Description of Displays
1. Some of the representations of product displays shown in this manual may be
exaggerated, simplified, or partially omitted for reasons of convenience when explaining them.
2. Figures and illustrations representing the universal power monitor’s displays may differ
from the real displays in regard to the position and/or indicated characters (upper­case or lower-case, for example), the extent of difference does not impair a correct understanding of the functions and the proper operations and monitoring of the system.
ii
IM 77C01H01-10EN

Notices

Regarding This User’s Manual
1. This manual should be passed on to the end user. Keep the manual in a safe place.
2. Read this manual carefully to gain a thorough understanding of how to operate this
product before you start using it.
3. This manual is intended to describe the functions of this product. Yokogawa Electric
Corporation (hereinafter simply referred to as Yokogawa) does not guarantee that these functions are suited to the particular purpose of the user.
4. Under absolutely no circumstance may the contents of this manual, in part or in whole,
be transcribed or copied without permission.
5. The contents of this manual are subject to change without prior notice.
6. Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention however, please contact your nearest Yokogawa representative or our sales office.
Regarding Protection, Safety, and Prohibition Against Unauthorized Modification
1. In order to protect the product and the system controlled by it against damage and
ensure its safe use, be certain to strictly adhere to all of the instructions and precautions relating to safety contained in this document. Yokogawa does not guarantee safety if products are not handled according to these instructions.
2. The following safety symbols are used on the product and/or in this manual.
Symbols Used on the Product and in This Manual
Markings
This symbol on the product indicates that the operator must refer to an explanation in the user’s manual in order to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.
Protective
Grounding
Terminal
This symbol indicates that the terminal must be connected to ground prior to operating the equipment.
IM 77C01H01-10EN
iii
Force Majeure
1. Yokogawa does not make any warranties regarding the product except those mentioned
in the WARRANTY that is provided separately.
2. Yokogawa assumes no liability to any party for any loss or damage, direct or indirect,
caused by the use or any unpredictable defect of the product.
3. Be sure to use the spare parts approved by Yokogawa when replacing parts or
consumables.
4. Modification of the product is strictly prohibited.
5. Reverse engineering such as the disassembly or decompilation of software is strictly
prohibited.
6. No portion of the software supplied by Yokogawa may be transferred, exchanged,
leased, or sublet for use by any third party without the prior permission of Yokogawa.
iv
IM 77C01H01-10EN
Contents
Introduction ................................................................................................................................................ i
Documentation Conventions .................................................................................................................... ii
Notices ..................................................................................................................................................iii
Chapter 1 Setup
1.1 Setup Procedure .................................................................................................................1-1
1.2 Notes on Setting RS-485 Communication Conditions ........................................................1-2
Chapter 2 RS-485 Communication Specifications
Chapter 3 Procedures for Setting UPM100/UPM101 Functions
3.1 Basic Setting .......................................................................................................................3-2
3.1.1 Setting of VT Ratio .................................................................................................................3-2
3.1.2 Setting of CT Ratio .................................................................................................................3-3
3.1.3 Setting of Integral Low-cut Power ..........................................................................................3-4
3.2 Setting Pulse Output ...........................................................................................................3-5
3.2.1 Pulse Unit-1 of Electric Energy ..............................................................................................3-5
3.2.2 ON Pulse Width-1 of Electric Energy .....................................................................................3-6
3.2.3 Pulse Unit-2 of Electric Energy ..............................................................................................3-7
3.2.4 LAG/LEAD/Regenerative Selection for Pulse Output of Electric Energy ...............................3-8
3.2.5 ON Pulse Width-2 of Electric Energy .....................................................................................3-9
3.3 Executing Reset Operations .............................................................................................3-10
3.3.1 Remote Reset ......................................................................................................................3-10
3.3.2 Active Energy Reset ............................................................................................................. 3-11
3.3.3 Maximum/Minimum Values Reset ........................................................................................ 3-11
3.3.4 Regenerative Energy Reset .................................................................................................3-12
3.3.5 Reactive Energy Reset ........................................................................................................3-12
3.3.6 Apparent Energy Reset ........................................................................................................3-13
3.4 Other Settings ...................................................................................................................3-14
3.4.1 Start of Optional Integration .................................................................................................3-14
3.4.2 Stop of Optional Integration .................................................................................................3-14
3.4.3 Start/Stop of Integration .......................................................................................................3-15
3.4.4 Active Energy Writing ...........................................................................................................3-16
3.4.5 Apparent Energy Writing ......................................................................................................3-17
3.4.6 LEAD Reactive Energy Writing ............................................................................................3-18
3.4.7 LAG Reactive Energy Writing ..............................................................................................3-19
3.4.8 Regenerative Energy Writing ...............................................................................................3-20
1
2
3
4
5
6
7
8
App
Chapter 4 PC Link Communication
4.1 Overview .............................................................................................................................4-1
4.1.1 Configuration of Command ....................................................................................................4-2
4.1.2 Configuration of Response .....................................................................................................4-3
4.1.3 Response Error Codes ...........................................................................................................4-4
4.1.4 Specifying Broadcast .............................................................................................................4-5
4.2 Command and Response ...................................................................................................4-6
BRD Reads I relays on a bit-by-bit basis ...............................................................................................4-7
BWR Writes data into I relays on a bit-by-bit basis ...............................................................................4-8
BRR Reads I relays on a bit-by-bit basis in a random order .................................................................4-9
BRW Writes data into I relays on a bit-by-bit basis in a random order ................................................4-10
BRS Specifies I relays to be monitored on a bit-by-bit basis ............................................................... 4-11
BRM Monitors I relays on a bit-by-bit basis .........................................................................................4-12
WRD Reads D registers and I relays on a word-by-word basis ..........................................................4-13
WWR Writes data into D registers and I relays on a word-by-word basis ...........................................4-14
WRR Reads D registers and I relays on a word-by-word basis in random order ................................ 4-15
WRW Writes data into D registers and I relays on a word-by-word basis in random order .................4-16
WRS Specifies the D registers and I relays to be monitored on a word-by-word basis ......................4-17
WRM Monitors the D register and I relays on a word-by-word basis ..................................................4-18
INF6 Reads the model, suffix codes, and version information ............................................................4-19
INF7 Reads the maximum value of CPU.............................................................................................4-20
IM 77C01H01-10EN
v
Contents
4.3 Communication with Higher-level Devices ........................................................................ 4-21
4.3.1 Communication with FA-M3 (UT Link Module) .....................................................................4-21
4.3.2 Communication with Touch Panel ........................................................................................ 4-23
Chapter 5 MODBUS Communication
5.1 Overview .............................................................................................................................5-1
5.2 Message and Response ...................................................................................................5-10
5.1.1 Configuration of Message ......................................................................................................5-3
5.1.2 Specifying D Registers ...........................................................................................................5-4
5.1.3 Checking Errors .....................................................................................................................5-4
5.1.4 Responses from Slaves .........................................................................................................5-7
5.1.5 Specifying Broadcast .............................................................................................................5-9
03 Reads data from multiple D registers ............................................................................................. 5-11
06 Writes data into D register ..............................................................................................................5-12
08 Performs loop back test ..................................................................................................................5-13
16 Writes data into multiple D registers ...............................................................................................5-14
Chapter 6 Functions and Usage of D Registers
6.1 Overview of D Registers .....................................................................................................6-1
6.2 Interpretation of D Register Map Table ...............................................................................6-2
6.3 Configuration of D Registers ............................................................................................... 6-3
6.4 D Register Map ...................................................................................................................6-4
Chapter 7 Functions and Usage of I Relays
7.1 Configuration of I Relays ..................................................................................................... 7-2
7.2 I Relay Map ......................................................................................................................... 7-3
Chapter 8 UPM01 Communication (Original Communication Protocol)
8.1 Overview .............................................................................................................................8-1
8.2 Frame Configuration ...........................................................................................................8-2
8.3 Functions ............................................................................................................................. 8-5
8.3.1 Measured Items (Category A) ................................................................................................8-5
8.3.2 Statistical Items (Category B) .................................................................................................8-7
8.3.3 Set Items (Category C) ..........................................................................................................8-8
8.3.4 User Control Items (Category E) ..........................................................................................8-10
Appendix
Appendix 1 Table of ASCII Codes (Alphanumeric Codes) .................................................................App-1
Revision Information
vi
IM 77C01H01-10EN
010101E.EPS

Chapter 1 Setup

1 Setup
This chapter describes the setup procedure required to use the communication functions and the communication specifications of the UPM100 universal power monitor.
Hereafter, the UPM100 universal power monitor is simply referred to as the UPM100.

1.1 Setup Procedure

Set up the communication functions on the UPM100 as follows:
Set up the communication function parameters of the UPM100. For the UPM100 with display function, set up the communication conditions using the front panel keys. For the UPM100 without display function, set up the communication conditions using the front DIP switches. (See the user's manual of Model UPM100 Power Monitor <Initial Setup Operations>.)
Connect a higher-level device and a UPM100. (See the user's manual of Model UPM100 Power Monitor <Installation>.)
1
Setup
Create communication programs for the higher-level device to perform communication. (See "4. PC Link Commnication" or "5. MODBUS Communication" for the communication protocol. See "6. Functions and Usage of D Registers", "7. Functions and Usage of I Relays" and "8. UPM01 Communication" for the data storing.)
To avoid an electric shock, be sure to turn off the power supply source to the equipment involved before you start wiring.
Note
• In the case of PLC (MELSEC:Mitsubishi Electric Corporation’s sequencer), “B” is for (-), and “A” is for (+).
• Do not share the grounding wire with another instrument. Doing so may result in a failure of the instrument. Use crimp terminals at cable ends.
Note Create communication programs referring to the documentation of each higher-level device.
Higher-level devices : PCs, PLCs (sequencers), touch panels, and others.
IM 77C01H01-10EN
1-1

1.2 Notes on Setting RS-485 Communication Conditions

This section describes the setting parameters for using the communication functions and their setting ranges.
Note
The details of the UPM100 communication conditions need to be the same as those of the communication conditions of the higher-level device to be connected.
• UPM100 without display function (UPM100-xx0xx-20 or UPM100-xx2xx-20): Set up the communication conditions using the front DIP switches. (See the user’s manual of Model UPM100 Universal Power Monitor <Initial Setup Operations>.)
• UPM100 with display function (UPM100-xx1xx-20 or UPM100-xx3xx-20): Set up the communication parameters using the front panel keys. (See the user’s manual of Model UPM100 Universal Power Monitor <Initial Setup Operations>.)
Table 1-1 Parameters to be Set for Communication Functions
Initial Setting
Parameter
Name
RS-485 communication protocol
Parameter
Symbol
(COMM)
Setting Range
PC link without checksum PCLK1
PC link with checksum PCLK2
MODBUS (ASCII mode) M ASC
MODBUS (RTU mode) M RTU
UPM01 UPM01
Without 920
MHz Wireless
Communication
PCLK2 M RTU
2
With 920 MHz
Wireless
Communication
3
RS-485 station number
RS-485 communication baud rate
(ST-NO)
(B-RT)
1 to 99 (1 to 31 recommended) 1 1
2400 bps
9600 bps
9600 19200
19200 bps
None NONE
Parity
Stop bit
Data length
(PRI)
(STP)
1
(DLN)
Even EVEN
Odd ODD
1
2
7
8
NONE NONE
1 1
8 8
3
3
1: When “MODBUS (ASCII mode)” is selected in protocol selection, select “7” or “8” for the data
length. When “MODBUS (RTU mode)” is selected, select “8.” Otherwise, communication cannot be achieved.
2: The UPM01 communication is selectable only when the optional measuring function “Integral
resolution Wh” is specified at ordering.
3: When using 920 MHz Wireless Communication, please use the default value above. Note: 920 MHz wireless communication can be used only in the Republic of Korea.
3
3
1-2
IM 77C01H01-10EN
1.2 Notes on Setting RS-485 Communication Conditions
Use the DIP switches to enter the settings on UPM100 without display function. Referring to the diagram below, set the binary values, with the first bit on the left.
When using 920 MHz Wireless Communication, please use the factory setting values except for the address. Note: 920 MHz wireless communication can be used only in the Republic of Korea.
<Address (station number)>
0: Usage prohibited
1 to 99 can be set (1 to 31 recommended) (Initial setting: 1)
<UPM01 protocol>
0: None 1: With protocol
denotes initial settings.
1
0
<Parity>
00: None 01: Even 10: Odd
11: Usage prohibited
<Data length>
0: 8 bits 1: 7 bits
<Stop bit>
0: 1 bit 1: 2 bits
<Communication protocol>
00: PC link without SUM 01: PC link with SUM 10: MODBUS ASCII 11: MODBUS RTU
<Baud rate>
00: 2400 bps 01: 9600 bps 10: 19200 bps
RS-485 communication protocol (COMM)
Set the communication protocol identical to that of the higher-level device to be connected.
1
Setup
RS-485 communication baud rate (B-RT)
Set the baud rate identical to that of the higher-level device to be connected. (Otherwise, proper communication cannot be achieved.)
Parity (PRI)
Set the handling of parity to be carried out when data is sent or received. Set the parity bit state identical to that of the higher-level device to be connected.
Stop bit (STP)
Set the stop bit identical to that of the higher-level device to be connected.
Data length (DLN)
Set the data length identical to that of the higher-level device to be connected. (When “MODBUS (RTU mode)” is selected in protocol selection, select “8” for the data length. When “MODBUS (ASCII mode)” is selected, select “7” or “8.”)
RS-485 station number (ST-NO)
Set the station number of the UPM100 itself. A station number of 1 to 99 may be assigned in any order. However, there is a limitation - the number of UPM100 to be connected to a single communication port is limited to 31.
When connecting two or more power monitors to a single communication port, make sure none of the station numbers 1 to 31 is set twice.
IM 77C01H01-10EN
1-3
PC
010202E.EPS
1.2 Notes on Setting RS-485 Communication Conditions
Example of connecting four UPM100 to a higher-level device by setting station numbers of 01, 05, 10, and 20
Maximum overall cable length of 1200 m for a maximum of 31 slave stations
ST-NO=01 ST-NO=05 ST-NO=10 ST-NO=20
<Binary Number Quick Reference Chart> The following table is a binary number quick reference chart for use in setting addresses (station numbers) with DIP switches.
1 0000001 21 0010101 41 0101001 61 01111 01 81 1010001 2 0000010 22 0010110 42 0101010 62 011111 0 82 1010010 3 0000011 23 0010111 43 0101011 63 0 111111 83 1010011 4 0000100 24 0011000 44 0101100 64 1000000 84 1010100 5 0000101 25 0011001 45 0101101 65 1000001 85 1010101 6 0000110 26 0011010 46 0101110 66 1000010 86 1010110 7 0000111 27 0011011 47 01 0 1111 67 1000011 87 1010111 8 0001000 28 0011100 48 0110000 68 1000100 88 1011000 9 0001001 29 0011101 49 0110001 69 1000101 89 1011001 10 0001010 30 0 011110 50 0110010 70 1000110 90 1011010 11 0001011 31 0 0 11111 51 0110011 71 1000111 91 1011011 12 0001100 32 0100000 52 0110100 72 1001000 92 1011100 13 0001101 33 0100001 53 0110101 73 1001001 93 1011101 14 0001110 34 0100010 54 0110110 74 1001010 94 1 0 1111 0 15 0 0 0 1111 35 0100011 55 0 11 0 111 75 1001011 95 10 11111 16 0010000 36 0100100 56 0111000 76 1001100 96 1100000 17 0010001 37 0100101 57 0111001 77 1001101 97 1100001 18 0010010 38 0100110 58 0111010 78 1001110 98 1100010 19 0010011 39 0100111 59 0111011 79 1 001111 99 1100011 20 0010100 40 0101000 60 0111100 80 1010000
1-4
IM 77C01H01-10EN

Chapter 2 RS-485 Communication Specifications

2 RS-485 Communication Specifications
The RS-485 communication interface has the PC link communication, MODBUS communication, and UPM01 communication protocols.
Table 2-1 UPM100 Communication Specifications
Communication Hardware 2-wire RS-485 communication system
PC link communication without checksum
Communication Protocol Specifications
Maximum Baud Rate 19200 bps
Maximun Communication Distance 1200 m
Communication Cable
*1 The UPM01 communication is selectable only when the optional measuring function “Integral
resolution Wh” is specified at ordering.
Table 2-2 Communication Protocols and Types of Devices to be Connected
Communication Protocol Example of Connected Devices
PCs and the like which are installed with a MODBUS communication
MODBUS communication
PC link communication
UPM01 communication
driver and SCADA software.
PLCs which support MODBUS
PCs and the like which are installed with a PC-link communication driver and SCADA software.
Touch panel (GP series)
PLCs (FA-M3’s UT link module)
PCs and the like which are installed with the PR970 which supports the UPM01 protocol. PCs and the like which are installed with SCADA software which supports the UPM01 protocol.
PC link communication with checksum MODBUS communication (ASCII mode) MODBUS communication (RTU mode) UPM01 communication*1
Shielded twisted-pair cable (wire size equivalent to AWG24)
2
RS-485 Communication Specifications
Table 2-3 RS-485 Communication Interface
Item Specifications
Standard Conforms to EIA, RS-485
Maximum number of devices to be connected 31
Communication system 2-wire, half duplex
Synchronization Start-stop synchronization
Communication protocol No protocol
Maximum communication distance 1200 m
Baud rate 2400, 9600 and 19200 bps
IM 77C01H01-10EN
2-1
Blank

Chapter 3 Procedures for Setting UPM100/UPM101 Functions

3
Procedures for Setting UPM100/UPM101 Functions
To set the functions of the UPM100, use the protocols described in “4. PC Link Communication,” “5. MODBUS Communication,” or “8. UPM01 Communication” according to the instructions in this chapter.
For details of each function, refer to the standard manuals that come with the UPM100.
For set value ranges, initial values, and data backup for registers, refer to “6. Functions and Usage of the D Register.” D Register numbers are explained in this chapter, but refer to Chapter 6 also for reference numbers for MODBUS communications.
The UPM100 offers registers for floating-point data. To perform settings via communication starting from larger digits, floating-point data is displayed by IEEE754 (single precision).
Note
• The UPM100 has data (D register) the unit of which is two words. When 2-word data need to be written or read, writing or reading operations must be performed for the 2- word data at the same time.
• Even if data written to the D register is out of the effective range, a normal response is returned. The part of the written data within the effective range becomes effective on the UPM100 when the equivalent setting change status is written for that data.
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-1

3.1 Basic Setting

3.1.1 Setting of VT Ratio

[Procedure]
1. Write a VT ratio to the two D registers in the table below. The data type is 4-byte floating point.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No. H No. Description Effective Range
D0043 40043 002A VT ratio (float, lower 2 bytes)
D0044 40044 002B VT ratio (float, upper 2 bytes)
D0072 40072 0047 Setting change status
Default VT ratio: 1 (4-byte floating-point data: 3F800000)
[Example]
To set the VT ratio to 10.0:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
If 10.0 is converted into a 4-byte floating-point value, the value is 4120 0000.
1 to 6000
If other than 1: Invalid If 1: Writing is executed
[Command]
[STX] 01010WRW03D0043, 0000, D0044, 4120, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
• When the VT ratio is changed, already integrated values of active energy, reactive energy,
apparent energy, optional electric energy, and regenerative energy will return to 0.
• Set the VT and CT ratios so that [Secondary rated power] x [VT ratio] x [CT ratio] is smaller than
10 GW.
3-2
IM 77C01H01-10EN

3.1.2 Setting of CT Ratio

[Procedure]
1. Write a CT ratio to the two D registers in the table below. The data type is 4-byte floating point.
2. After writing that value, write “1” to the setting change status register, D0072.
3.1 Basic Setting
D Register Reference No. H No. Description Effective Range
D0045 40045 002C CT ratio (float, lower 2 bytes) 0.05 to 32000
D0046 40046 002D CT ratio (float, upper 2 bytes)
D0072 40072 0047 Setting change status
Default CT ratio: 1 (4-byte floating-point data: 3F800000)
(with 5 signicant digits;
can be set to the second place of a decimal point.)
If other than 1: Invalid If 1: Writing is executed
[Example]
To set the CT ratio to 10.0:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
If 10.0 is converted into a 4-byte floating-point value, the value is 4120 0000.
[Command]
[STX] 01010WRW03D0045, 0000, D0046, 4120, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
• When the CT ratio is changed, already integrated values of active energy, reactive energy,
apparent energy, optional electric energy, and regenerative energy will return to 0.
• Set the VT and CT ratios so that [Secondary rated power] x [VT ratio] x [CT ratio] is smaller than
10 GW.
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-3
3.1 Basic Setting

3.1.3 Setting of Integral Low-cut Power

[Procedure]
1. Write an integral low-cut power value to the two D registers in the table below. The data type is 4-byte floating point.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No. H No. Description Effective Range
D0047 40047 002E
D0048 40048 002F
D0072 40072 0047 Setting change status
Default integral low-cut power value: 0.05 (4-byte floating-point data: 3D4CCCCD)
[Example]
To set the integral low-cut power value to 10.0:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
If 10.0 is converted into a 4-byte floating-point value, the value is 4120 0000.
Integral low-cut power value (float, lower 2 bytes)
Integral low-cut power value (float, upper 2 bytes)
0.05 to 20.00 Unit: %
If other than 1: Invalid If 1: Writing is executed
[Command]
[STX] 01010WRW03D0047, 0000, D0048, 4120, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
3-4
IM 77C01H01-10EN

3.2 Setting Pulse Output

3.2.1 Pulse Unit-1 of Electric Energy

[Procedure]
1. Write a pulse unit-1 of electric energy value to the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No. H No. Description Effective Range
D0049 40049 0030
D0072 40072 0047 Setting change status
Default value of pulse unit-1 of electric energy: 100 (1000 Wh/pls)
[Example]
To set the pulse unit-1 of electric energy value to 100 Wh/pls, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
1: The data written when the integral resolution (kWh) option is specified.
Pulse unit-1 of electric energy value
3
Procedures for Setting UPM100/UPM101 Functions
1 to 50,000 Unit: x 10 Wh/pls
If other than 1: Invalid If 1: Writing is executed
1
[Command]
[STX] 01010WRW02D0049, 000A, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
• The pulse unit-1 of electric energy value can be set for the UPM100 with pulse outputs.
• To set the pulse unit-1 of electric energy value using the UPM100 with the integral resolution
(kWh) option via communication, set it to 1/10th the value of the displayed (true) value (e.g., set it to 5 when setting the pulse unit-1 of electric energy value to 50 Wh/pls).
The value of the UPM100 with the integral resolution (Wh) option should be the same as that of
the displayed value.
IM 77C01H01-10EN
3-5
3.2 Setting Pulse Output

3.2.2 ON Pulse Width-1 of Electric Energy

[Procedure]
1. Write an ON pulse width-1 of electric energy value to the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
Note
When the value to be set for the ON pulse width-1 is greater than the value calculated by the following equation, the value cannot be set:
ON pulse width (ms) ≤
D Register Reference No. H No. Description Effective Range
D0052 40052 0033
D0072 40072 0047 Setting change status
Default value of ON pulse width-1 of electric energy: 5 (50 ms)
Secondary rated power [W] x VT ratio x CT ratio x 1.2 x 2
Pulse unit [Wh/pls] x 60 x 60 x 1000
ON pulse width-1 of electric energy value
1 to 127 Unit: x 10 ms
If other than 1: Invalid If 1: Writing is executed
[Example]
To set the ON pulse width-1 of electric energy value to 100 ms, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW02D0052, 000A, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
• The ON pulse width-1 of electric energy value can be set for the UPM100 with pulse outputs.
• To set the ON pulse width-1 of electric energy value via communication, set it to 1/10th the
value of the displayed (true) value (e.g., set it to 5 when setting the ON pulse width-1 of electric energy value to 50 ms).
3-6
IM 77C01H01-10EN

3.2.3 Pulse Unit-2 of Electric Energy

[Procedure]
1. Write a pulse unit-2 of electric energy value to the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
3.2 Setting Pulse Output
D Register Reference No. H No. Description Effective Range
D0085 40085 0054
D0072 40072 0047 Setting change status
Default value of pulse unit-2 of electric energy: 100 (1000 varh/pls)
Pulse unit-2 of electric energy value
1 to 50,000 Unit: x 10 varh/pls
If other than 1: Invalid If 1: Writing is executed
[Example]
To set the pulse unit-2 of electric energy value to 100 varh/pls, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
1: The data written when the integral resolution (kWh) option is set.
[Command]
[STX] 01010WRW02D0085, 000A, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
1
Note
• The pulse unit-2 of electric energy value can be set for the UPM100 with pulse outputs and the
one with the reactive power/reactive energy measuring function.
• To set the pulse unit-2 of electric energy value using the UPM100 with the integral resolution
(kWh) option via communication, set it to 1/10th the value of the displayed (true) value (e.g., set it to 5 when setting the pulse unit-2 of electric energy value to 50 varh/pls).
The value of the UPM100 with the integral resolution (Wh) option should be the same as that of
the displayed value.
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-7
3.2 Setting Pulse Output

3.2.4 LAG/LEAD/Regenerative Selection for Pulse Output of Electric Energy

[Procedure]
1. Write a value for LAG/LEAD/regenerative selection for pulse output of electric energy to the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
D Register Reference No. H No. Description Effective Range
D0087 40087 0056
D0072 40072 0047 Setting change status
Default value for LAG/LEAD/regenerative selection for output pulse of electric energy: With the optional reactive power/reactive energy measuring function: 0 (LAG PULSE) Without the optional reactive power/reactive energy measuring function: 2 (Regenerative PULSE)
Value for LAG/LEAD/ regenerative selection for output pulse of electric energy
[Example]
To set a value for LAG/LEAD/regenerative selection to 1 (LEAD):
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
0: LAG PULSE 1: LEAD PULSE 2: Regenerative PULSE
If other than 1: Invalid If 1: Writing is executed
[Command]
[STX] 01010WRW02D0087, 0001, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
The value for LAG/LEAD/regenerative selection for output pulse of electric energy value can be set for the UPM100 with pulse outputs and the one with the reactive power/reactive energy measuring function. For the UPM100 without the reactive power/reactive energy measuring function, only the regenerative PULSE is available.
3-8
IM 77C01H01-10EN

3.2.5 ON Pulse Width-2 of Electric Energy

[Procedure]
1. Write an ON pulse width-2 of electric energy value to the D register in the table below. The data type is integer.
2. After writing that value, write “1” to the setting change status register, D0072.
3.2 Setting Pulse Output
Note
When the value to be set for the ON pulse width-2 is greater than the value calculated by the following equation, the value cannot be set:
ON pulse width (ms) ≤
D Register Reference No. H No. Description Effective Range
D0085 40085 0054
D0072 40072 0047 Setting change status
Default value of ON pulse width-2 of electric energy: 5 (50 ms)
Secondary rated power [W] x VT ratio x CT ratio x 1.2 x 2
[Example]
To set the ON pulse width-2 of electric energy value to 100 ms, write “000A.”
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW02D0088, 000A, D0072, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Pulse unit [Wh/pls] x 60 x 60 x 1000
ON pulse width-2 of electric energy value
1 to 127 Unit: x 10 ms
If other than 1: Invalid If 1: Writing is executed
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
Note
• The ON pulse width-2 of electric energy value can be set for the UPM100 with pulse outputs
and the one with the reactive power/reactive energy measuring function.
• To set the ON pulse width-2 of electric energy value via communication, set it to 1/10th the
value of the displayed (true) value (e.g., set it to 5 when setting the ON pulse width-2 of electric energy value to 50 ms).
3-9

3.3 Executing Reset Operations

3.3.1 Remote Reset

[Procedure]
1. To execute remote reset, write data to the D register or the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0059 40059 003A I0010 Remote reset
Note
• By executing remote reset, the maximum, minimum, and instantaneous voltage and current
values are reset. Remote reset stops while the optional electric energy measuring function is in operation.
• Even if remote reset is executed, data on active energy, reactive energy, and apparent energy
and the values set to their parameters will be saved.
• The D register and the I relay in the table above have the same functions.
[Example]
To execute remote reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
If other than 1: Invalid If 1: UPM100 is reset
[Command]
[STX] 01010WRW01D0059, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
After remote reset is executed, the micro-computer of the UPM100 is reset. Wait for more than 5 seconds before executing another command.
3-10
IM 77C01H01-10EN

3.3.2 Active Energy Reset

[Procedure]
1. To execute active energy reset, write data to the D register or the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0060 40060 003B I0011
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute active energy reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0060, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
3.3 Executing Reset Operations
Reset the active energy (D0001 and D0002)
If other than 1: Invalid If 1: Active energy is reset
3
Procedures for Setting UPM100/UPM101 Functions

3.3.3 Maximum/Minimum Values Reset

[Procedure]
1. To execute maximum/minimum values reset, write data to the D register or the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0061 40061 003C I0012
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute maximum/minimum values reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0061, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the maximum/ minimum values (D0023 to D0040)
If other than 1: Invalid If 1: Maximum/minimum values are reset
IM 77C01H01-10EN
3-11
3.3 Executing Reset Operations

3.3.4 Regenerative Energy Reset

[Procedure]
1. To execute regenerative energy reset, write data to the D register in the table below. The data type is integer.
D Register Reference No. H No. Description Effective Range
D0064 40064 003F
[Example]
To execute regenerative energy reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0064, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the regenerative energy (D0067 and D0068)
If other than 1: Invalid If 1: Regenerative energy is reset

3.3.5 Reactive Energy Reset

Note
Data can be written to the UPM100 with the optional reactive power/reactive energy measuring function.
[Procedure]
1. To execute reactive energy reset, write data to the D register or the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0093 40093 005C I0015
Note
The D register and the I relay in the table above have the same functions.
[Example]
To execute reactive energy reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0093, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the reactive energy (D0077 to D0080)
If other than 1: Invalid If 1: Reactive energy is reset
3-12
IM 77C01H01-10EN

3.3.6 Apparent Energy Reset

[Procedure]
1. To execute apparent energy reset, write data to the D register in the table below. The data type is integer.
D Register Reference No. H No. Description Effective Range
D0097 40097 0060
[Example]
To execute apparent energy reset:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0097, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Reset the apparent energy (D0083 and D0084)
3.3 Executing Reset Operations
If other than 1: Invalid If 1: Apparent energy is reset
3
Procedures for Setting UPM100/UPM101 Functions
IM 77C01H01-10EN
3-13

3.4 Other Settings

3.4.1 Start of Optional Integration

[Procedure]
1. To start optional integration, write data to the D register or the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0062 40062 003D I0013
Note
The D register and the I relay in the table above have the same functions.
[Example]
To start optional integration:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0062, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Start of optional integration (D0003 to D0006)
If other than 1: Invalid If 1: Optional integration is started

3.4.2 Stop of Optional Integration

[Procedure]
1. To stop optional integration, write data to the D register or to the I relay in the table below. The data type is integer.
D Register Reference No. H No. I relay Description Effective Range
D0063 40063 003E I0014
Note
The D register and the I relay in the table above have the same functions.
[Example]
To stop optional integration:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
[Command]
[STX] 01010WRW01D0063, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Stop of optional integration (D0003 and D0004)
If other than 1: Invalid If 1: Optional integration is stopped
3-14
IM 77C01H01-10EN

3.4.3 Start/Stop of Integration

[Procedure]
1. To start/stop integration, write data to the D register in the table below. The data type is integer.
D Register Reference No. H No. Description Effective Range
D0053 40053 0034
[Example]
To start/stop integration:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
<Start>
[Command]
[STX] 01010WRW01D0053, 0000 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Active energy (D0001 and D0002) Apparent energy (D0083 and D0084) Regenerative energy (D0067 and D0068) Reactive energy (D0077 to D0080)
3.4 Other Settings
0: Integration is started 1: Integration is stopped
3
Procedures for Setting UPM100/UPM101 Functions
<Stop>
[Command]
[STX] 01010WRW01D0053, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
IM 77C01H01-10EN
3-15
3.4 Other Settings

3.4.4 Active Energy Writing

[Procedure]
1. Write an active energy value to the two D registers in the table below. The data type is integer.
2. After writing that value, write “1” to the write status register, D0073.
D Register Reference No. H No. Description Effective Range
D0057 40057 0038
D0058 40058 0039
D0073 40073 0048
[Example]
To set the active energy value to 12345:
For station number 01, use PC link communication (without checksum) and the random write command as shown below:
If 12345 is converted into a hexadecimal value, the value is 0000 3039. Then the order of the upper two bytes and the lower two bytes is reversed → 3039 0000.
Set active energy value (lower 2 bytes)
Set active energy value (upper 2 bytes)
Set active energy value write status
Refer to the "Note" below.
If other than 1: Invalid If 1: Writing is executed
[Command]
[STX] 01010WRW03D0057, 3039, D0058, 0000, D0073, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
The set active energy value range of the UPM100 with the integral resolution (kWh) option changes depending on the values of the VT and CT ratios. The table below shows the set value range.
[Secondary Rated Power] x [VT Ratio] x [CT Ratio] Possible Set Value Range
Below 1 MW 0 to 999999 kWh
1 MW to 10 MW 0.00 to 9999.999 MWh
10 MW or above 0.0 to 99999.999 MWh
Regardless of the value of [Secondary rated power] x [VT ratio] x [CT ratio], the set active energy value range of the UPM100 with the integral resolution (Wh) option can be set within the range below:
Possible set value range: 0 to 99999999 Wh
Note
The secondary rated power of the UPM100 changes depending on its model and suffix codes.
3-16
IM 77C01H01-10EN
Loading...
+ 74 hidden pages