Yokogawa UP750 Data sheet

<<Contents>> <<Index>>
General Specifications
Model UP750 Program Controller (with Custom Computation)
GS 05E01B02-01E
General
Model UP750 Program Controller is an intelligent, micro­processor based program controller that has the capacity of 300 program patterns, powerful control capability, custom computation function and a user-friendly display. The UP750 has many control modes as standard, and all these functions such as program setting function, control function, control computation function, signal computation, etc. can be configured by using the keys on the front panel. The instrument includes eleven types of predecided control strategies including cascade, temperature/ humidity, and more in single or dual loops. Auto-tuning control, an overshoot suppressing function "SUPER" and a heating suppressing function "SUPER 2" are standard.
Main Features
• Extra-large digital display allows the indicated values to be read even from along distance. LEDs of 20mm height are used for the process variable display. This is a five-digit display for higher resolution.
• User-friendly full dot LCD display. Not only the target setpoint and control related parameters, but also a program pattern, deviation trend record or an analogue bargraph of control output value can be displayed on it.
• Huge capacity of 300 program patterns / 3000 segments. Applicable to a wide range of heat treatment , textile, environmental chamber and testing application.
•Eleven type of control function, including single-loop control, cascade control, loop control with PV auto­selector, and custom computation function, enabling the operator to start control operation immidiately after simply entering the settings.
• The program pattern-2 retransmission function outputs a program pattern (control setpoint) by way of the retrans­mission output. This function is used in combination with retransmission output setup parameter RET 1 or RET 2, for which target setpoint-2 (SP2) should be selected, and is used for pattern transmission to another instrumennt (available for UP mode 1, 2, or 6).
• Custom Computation capability, which allows users’ own configuration for signals, enables them to realize such functions as complicated computation for input compensa­tion or sequence logic for input/output. ( “PC-based Custom Computation Building Tool <model name: LL200> is necessary to use this function.)
• Universal input and output enable users to set or change freely the type of measured inputs(thermocouple, RTD, or DCV), measurement input range, type of control output(4 to 20 mA current, voltage pulse, or relay contact) etc. the front panel.
• Equipped with seven contact inputs and outputs each, which are further expandable up to 23 inputs and outputs each by adding contact I/O signal expansion modules.
• Various communication function are provided. Communi­cation is possible with personal computer, programable logic controller, and other controllers.
UP750
UP750E
“E” indicates with the model with expanded functions.
Functional Specifications
Program Setting Function
“Program setting” allows the setting of a setpoint versus time. The instrument can store program patterns and change the pattern according to the operating status. One program pattern consists of several broken line (segment). The length of each segment can be set by segment time. Users can also configure the number of Repeats, Start/Stop, event outputs, etc.
Program pattern setting capacity: 300 maximum Number of segment/pattern: 99 maximum Number of segment: 3000 maximum (sum of segments for
all program patterns)
Number of event: 4000 maximum (sum of events for all
Number of program repeat time: 0 to 999, or unlimited
Segment time: 0 minute 0 s to 59 m i n u t e 5 9 s , o r 0 h 0
Mode of program pattern operation:
Switching between program patterns:
Target setpoint (SP)
segment time
program patterns)
repeats.
minute to 59 h 59 minute.
Start (RUN), stop (RESET), paused (hold), advance, can be executed by an external contact or instrument operation.
Achieved by contact input or instrument operation.
1
t
2
t
segment time No.1
Example of program pattern
segment time No.2
t
3
t
4
segment time No.5
t
5
GS 05E01B02-01E
4th Edition Oct. 2007 (KP)
<<Contents>> <<Index>>
2
Wait Function
The function to delay the progress of the program pattern when Process variable (PV) does not reach the change of the target setpoint (SP). The wait function has to parameters: a wait zone and a wait time.
Wait zone is a range of the deviation, and wait time is the time to wait for PV to reach the wait zone. If PV reaches the wait zone within a certain time (wait time), then the program will advance to the next segment. If PV does not reach the wait zone even after the wait time pass, then the program will eventually advance to the next segment.
Wait time: OFF, 0 minute 1 s to 99 minute 59 s or 0 h 1
minute to 99 h 59 s.
Wait zone: 0 to 10 % of measured input range width.
UP mode and Program Setting Function
UP mode with one channel of control: Single-loop control,
Cascade primary-loop control, Loop control with PV switching, Loop control with PV auto selector, Loop control with 2 universal inputs switching , Cascade control, Cascade control with 2 universal inputs. Note that Program pattern setting function is only available with the cascade primary-loop when Cascade control with 2 universal inputs are used.
UP mode with two channels of control: Dual-loop control,
Temperature and humidity control. The following functions are common to dual program setting functions ( “Program pattern RUN/RESET”, “The total number of program segment”) and “Segment time”.
Program Setting Function and PID Parameters
Switching
Controller can switch between PID parameter sets as a program pattern progresses.
Segment PID selection: PID-parameter numbers being
used can be selected on a segment basis.
Zone PID selection: PID parameter sets are selected
depending on the value of the applied PV input. Either the reference point method (reference point: a setpoint for switching between PID parameter sets) or the reference deviation method is used for the switching.
Reference point method: Divides the measurement input
range into as many as seven zones using a maximum of six reference points, and switching between PID parameter sets is done on a zone basis.
Reference deviation method: Switches between PID
parameter sets depending on whether the control deviation (DV) is within the given reference deviation or exceeding the deviation. This method has priority over the reference point method during operation.
Time Events
Time event is selected based on time in the program pattern
Number of time events: 8 points max. per segment (Max. 8
points for per segment the instrument with two control channels)
Time event display: 4 points (TME1, TME2, TME3,
TME4) Time event setting point: Start and duration (user settable) Setting time: 0 minute 0 s to 99 h 59 minute.
PV Events
PV event is the PV/DV alarm function which is configured in relation with the program pattern.
Number of PV event: max. 8 points per segment PV event display: 2 points ( PVE1, PVE2 )
The status of all the setting events can be seen in the operating display.
Event types: PV high limit, PV low limit, Deviation high
limit, Deviation low limit, Deenergized on deviation high limit, Deenergized on deviation low limit, Deviation high and low limits, High and low limits within deviation, Deenergized on PV high limit, Deenergized on PV low limit, SP high limit, SP low limit, Output high limit, Output low limit.
Configurable ranges of PV events:
PV alarm: –100 to 100% of measured input range DV alarm: –100 to 100% of measured input width Alarm hysteresis: 0.0 to 100% of measured input renge
width
Instrument Alarm Functions
The instrument alarm function outputs PV, deviation, SP, and other alarm without regards to the program pattern. Controller has four instrument alarm outputs.
Alam types: PV high limit, PV low limit, Deviation high
limit, Deviation low limit, Deenergized on deviation high limit, Deenergized on deviation low limit, Deviation high and low limits, High and low limits within deviation, Deenergized on PV high limit, Deenergized on PV low limit, SP high limit, SP low limit, Output high limit, Output low limit.
Alarm setting range:
PV/SP alarm: –100 to 100 % of measured input range. Deviation alarm: –100 to 100 % of measured input range
width. Output alarm: –5.0 to 105.0 % of output value. Alarm hysteresis: 0.0 to 100.0 % of measured input
range width.
Stand-by action: Stand-by action can be set to make PV/
deviation alarm OFF during start-up or after SP change until SP reaches the normal region.
Other alarm actions:
Sensor grounding alarm: Detects sensor deterioration and
outputs an alarm. Fault diagnostic alarm: Input burnout, A/D conversion
error, RJC error FAIL output: Abnormality in Software, Abnormality in
Hardware
Number of Instrument Alarm Settings: 4 points Number of Instrument Alarm Outputs: Max. 4 points
One of PV alarm/Deviation alarm, Fault diagnostic alarm, Sensor grounding alarm and Fail output can be output with contact output.
(Note): Refer to the later "Contact Outputs" in
Hardware Specifications.
Event Output Functions
Output contact: Max. 7 points of contact output can be used
to output the event/alarm (See ‘Contact output’) The following number are pre-configured as an initial setting upon shipment.
Time event: 4 points PV event: 2 points
Instrument alarm: 1 point Max. 23 points outputs are available when Expanssion Digital I/O connected.
Time events, PV events and Instrument alarm can be assigned for any contact output. Event and alarm status can be read by communication.
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
3
Control Functions
UP mode
The following types of basic control structure can be set as the UP mode by the user.
Single-loop Control (UP mode 1): The most simple and
basic control function.
Cascade primary-loop control (UP mode 2): Output
tracking function and cascade control logic are provided. Suitable for the primary- loop cascade control.
Cascade control (UP mode 4): Dual control functions.
Whole Cascade control can be executed with a single instrument.
Loop control with PV switching (UP mode 6): Two
measured inputs are switched for control depending on the status of contact input or measured input.
Loop control with PV auto-selector (UP mode 7): Two
measured inputs are automatically selected for control with a high, low, average, or tempera­ture-defference value selector.
Dual-loop control (UP mode 11): Dual control function is
available in a single instrument to control two loops.
Temperature and Humidity control (UP mode 12):
Temperature control and Relative Humidity control are available in a single instrument.
Cascade control with two universal inputs (UP mode 13):
Cascade control with using two universal measured inputs.
Loop control with PV switching and two universal inputs
(UP mode 14): Loop control with PV switching and two universal inputs available as mesured inputs.
Loop control with PV auto-selector and two universal
inputs (UP mode 15): Process variable for loop control is automatically selected from two or three measured inputs by an internal selector, using two universal inputs and an auxiliary analog input. When two universal inputs are configured as measured input, auxiliary analog input can be used for a remote setpoint input.
Custom computation control (UP mode 21): Can be
provided by the user using the optional LL200 custom computation building tool.
Control Computation Functions
In each UP mode, the following control types can be selected.
Continuous PID control, Time-proportional PID control, Relay ON/OFF control, Heating/Cooling control.
Target setpoint and PID parameter: Maximum eight sets of
target setpoint and PID parameters can be set and stored in a instrument. For Cascade control and Dual-Loop control type, eight sets for each main and slave are available.
Auto-tuning: standard
Possible to activate auto-tuning for both loops of Cascade control, Dual-loop control and Temperature and humidity control.
“SUPER” function: Overshoots generated by abrupt
changes in the target setpoint or by distur­bances can be suppressed.
“SUPER 2” function: This function stabilizes the state of
control that is unstable due to hunting, etc.
without requiring any change in PID con­stants, when the load and/or gain varies greatly, or when there is a difference between the characteristics of temperature zones.
Preset output function: When the instrument is in reset
mode, measured input is burnout, or abnor­mality is found in an input circuit, users’ preconfigurable preset value is output as a control output.
Control cycle time: Each cycle time can be selected under
the following conditions
100 ms: Available when model code is UP750-0 .
200 ms: Available with UP750-5 , or when the
amount of computation module of Custom computation function is less than 30.
500 ms: Available when the amount of computation
module is 50 or more.
(Set value on shipped from the factory: 200 ms)
Operation Mode Switching
(Note:Communication enables all the following mode
switching to be excuted.)
AUTO/MANUAL switching: Bump-less switching is
available. Switching between AUTO and MANUAL mode can be realized by instrumment operation or by external contact, and external contact switching has priority to instrumment operation.
RUN (PRG)/STOP (RESET) switching: Switching can be
realized by the front key or external contact, and external contact switching takes priority to the front key. Bump-less switching for RESET to PROG is available. In PRG mode, control computation is activated. In RESET mode, control computation ceases and preset output value is output as a control output, while other functions operates normally.
CASCADE/Local SP switching: Switching can be realized
by instrument operation or external contact, and external contact switching takes priority to instrument operation. Available when UP mode is set to “Cascade control” .
Control Parameter Setting Range
Proportional Band: 0.1 to 999.9%
0.0 to 999.9% (for heating/cooling PID
control), 0.0% available for ON/OFF control. Integral time: 1 to 6,000 s, or OFF(for Manual reset) Derivative time: 1 to 6,000 s, or OFF ON/OFF control hysteresis: 0.0 to 100.0% of measured
input range width Preset output value: –5.0 to 105.0% of output range (0mA
or less cannot be output) Output limiter:
Setting range: –5.0 to 105.0% for both high and low
limits. However “low limit setpoint < high limit setpoint” must be satisfied. In case of heating/cooling PID control, upper limiter for heating and upper limiter for cooling.
Shutdown function: In manual mode operation, up to
approx. 0mA can be output. (For 4 to 20 mA
control output only) Rate of change limiter for output: OFF, or 0.1 to 100.0%/s Dead band for heating/cooling control: –100.0% to 50.0%
of output value
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
4
Configuration of Input/Output Signal
Measured Input Computations
Bias (–100.0 to 100.0%), First lag filter (OFF, time constant 1 to 120 s), Square root extraction (for voltage input only, Input low cut 0.0 to 5.0%), 10-segment line linearizer/bis function, relative humidity calculation for wet/dry bulb (for Temperature & Humidity control type only)
Auxiliary Input Computaitons
Bias (-100.0 to 100.0%), Filter (off, time constant 1 to 120 s), Square root extraction (Input low-cut 0.0 to 5.0%).
Custom Computations
LL200 Building tool is necessary for using Custom computa­tion function.
Combining computation function modules allows such functions as user configuration of input/output signals, operation mode switching via discrete input, status output via discrete output, and so on.
Computation function module: Addition/substruction/
multiplication/division, Processing absolute value/reciprocal, Selecting maximum/ minimum/average, Keeping maximum/ minimum value, Keeping value, Rate of change limiter, Switch, Limiter, Constant, AND, OR, Exclusive OR, NOT, Latch, Comparison(=, <, >, , ), Not equivalent, Within range, AND(word), OR(word), Shift word, Sum, Timer, Ten-segment linearizer 1/ 2, Inverse ten-segment linearizer 1/2, Curve linearizer 1/2, Ratio, First order lag filter, Conversion to engineering unit, Selection of PV from two inputs, Temperature and humidity calculation, Fluid Temperature/ Pressure compensation, MV selection1/2, Conversion of display value, Parameter setting, Data display1/2, Special discrete output calculation, Assignment of output terminals 1/2, etc.
Maximum Number of Module to be used:
50 for input Custom computation, 50 for output Custom computation
Display and Operation Function
PV Display Unit
Either PV1 or PV2 can be displayed on 5 digit digital display unit and switched one from the other.
(Digit of display: 4 or 5 digit) For Thermocouple and RTD input, the display of the digits lower than decimal point can be off.
The display range is -19999 to 30000 and the display span is 30000 or less. [750.00 appearing in the product photograph on page 1 cannot actually be displayed.]
LCD Display Unit
Some data are displayed on LCD display unit. Each screen is called “display”.
Five types of display are provided; Operating display, Operating parameter setting display, Program parameter setting dispiay, Setup parameter setting display and SELECT display.
Each screen of LCD display unit contains:
Operating display: Necessary data for operation is
displayed according to UP mode. Such items as Program pattern, Setpoint, Control output, control output bar, deviation trend, is displayed. Time base of deviation trend is 120 s to 20 h.
Operating parameters setting display: The Operating
parameters, which are mainly changed during operation, such as PID constant, are displayed. The explanation of each param­eters is provided.
Program Parameters Setting display:
Generation of Program pattern, and parameters for Wait Function and Repeat Function are displayed.
Setup parameter setting display: The Setup parameters to
configure functions of the instrument before starting operation are displayed. The explanation of each parameters is provided.
SELECT display: Up to 5 displays which are frequently
accessed can be selected from Operating parameter setting display and Setup parameters setting display.
Status Lamps
Event indicating lamp: 7 points (TME1, TME2, TME3,
TME4, PVE1, PVE2, AL) Operation mode indicating lamp: PRG (Program opera-
tion), RST (Program operation reset), HLD
(Program operation hold), LOC (Local
operation), MAN1 (Loop1 in Manual mode),
MAN2 (Loop2 in Manual mode), CAS
(Cascade operation).
Operation Key
, key: Increase/decrease the value of Setpoint or
other parameters which appear on LCD display. DISP key: Switch data to be showed on LCD display SET/ENT key: Set/change the setting value, switch
information to be showed on LCD display,
switch operation mode other than AUTO/
MAN. PT No. key: Select program pattern No. RUN key: Start the program operation RESET key: Stop and reset the program operation.
Security Function
Key lock from parameters setting and, operation can be inhibited by a password.
Communication Functions
( For UP750- 1 only )
The instrument allows two communication ports and five types of communication protocols, and allows the simulta­neous communication with two different instruments. The instruments to communicate are such as a personal computer, a programmable logic controller, other UT750/UP750, and Digital I/O expansion module.
Communication Protocol
Computer link communication: Communication protocol
with a personal computer, PLC communica-
tion modules, and more. Ladder communication (BCD serial communication):
Communication protocol with the ladder
program on some programmable logic
controllers. MODBUS communication: Communication protocol with
a personal computer or PLC. Coordinated operation protocol: Protocol to realize
Coordinated operation with other GREEN
SERIES controller. UP750 is always
configured as a master unit.
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
5
Digital input/output expansion(-Bus): Protocol to connect
Digital I/O expansion module to increase the number of Discrete Input and Output.
RS-485 Communication Interface
Two types of RS-485 communication interface(conforms to EIA RS485) are available; High performance interface and general purpose interface. Both interfaces are available simultaneously according to usage.
High Performance Interface:
High performance RS-485 communication is available with Computer link, Ladder, Digital I/O expansion module, and Coordinated operation communication.
Specification (Common for Computer link, Ladder, and
Coordinated operation):
Maximum number of connectable controllers:
31 units max. Maximum communication distance: 1,200 m max. Communication method: 2 wire, half duplex, Start-stop
synchronization system, Protocol free Communication rate: 600, 1200, 2400, 4800, 9600bps,
19.2k, 38.4kbps.
Status lamps
Second PV(PV2) Time event(TME1 to 4), PV event(PVE1/2), alarm(AL1), Program operation(PROG), Reset(RST), Hold(HLD), Local operation(LOC), Loop 1 in Manual operation (MAN1), Loop 2 in Manual operation(MAN2), Cascade operation(CAS)
Digital I/O Expansion Module Communication (애-Bus): Digital I/O Expansion module communicaiton
terminals are same as high performance communication terminals.
Digital I/O Expansion module: P2ER1-20J,
P2ET1-20J Units to be connected: 2 units max. Maximum communication distance: 15m max. Communication rate: 1.25Mbps
General Purpose Interface:
General purpose communication is interface available with Computer link, Ladder or Coordinated operation.
Specification (Common for Computer link, Ladder, and Coordinated operation)
Maximum number of connectable controllers:
31 units max. Maximum communication distance: 1200 m Communication method: Two-wire half duplex or four-
wire half duplex Start-stop synchronizations
system, Protocol free Communication rate: 600, 1200, 2400, 4800, 9600 bps
PV display unit
Display PV. Error code is displayed when error is detected.
Communication port for light loader
Communicate with personal computer to transfer the parameter/program setting data and Custom computation data.
LCD display unit
Display setting item and setting data of Setpoint(SP), program pattern, output opening,deviation bar-graph, deviation value, deviation trend,
Operational keys
parameter, etc.
Increase/Decrease the setting data(, ) Transfer the display(DISP), Operation mode selection(MODE), Setting Parameters/values(SET/ENT) Program pattern selection( PT No.), Program operation Start(RUN), Program operation reset(RESET)
Examples of Communication System Configuration Diagram
(1) Computer link communication/MODBUS communication (2) Ladder communication
Personal computer
PV
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
1
1
2
2
3
3
REM
REM
4
4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
UP750 Program controller
(3) Coordinated operation (4) Digital I/O expansion module (µ-bus communication)
PV
PV2
AL
1 2
UP750 Program controller or
3 REM 4 MAN1 MAN2 STP CAS
A/M
UT750 Digital indicating controller
DISP
SET/ENT
MELSEC-A
PLC
PV
PV2
AL
1 2 3 4
PV
PV2
AL
1 2 3
REM
REM 4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
SET/ENT
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
SET/ENT
DISP
SET/ENT
UP750 Program controller
DISP
PV
PV2
AL
1 2 3 REM 4 MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV
PV2
AL
1 2 3 REM 4 MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
PV
PV2
PV2
AL
AL
1
1
2
2
3
3
REM
REM
4
4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
UT750 Digital indicating controller
PV
PV2
AL
1 2 3 REM 4 MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
Digital I/O expansion module
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
6
Hardware specifications
Input/Output Signal Specifications
Measured Input Signal
Number of input:1 or 2 points Input type, measurement input range and measurement
Sampling period: 100, 200 or 500 ms (selectable)
Burnout detection: Available with Thermocouple, RTD,
Unspecified (When shipped from the factory)
Thermocouple
RTD
Standard signal
DC voltage
accuracy: Refer to the table below. Possible to select input type/measurement range by software.
(default: 200 ms)
standard signal 0.4 to 2 V DC and 1 to 5 V DC input. Possible to specify a travel of upscale, downscale or off. For DC voltage input, 0.1 V or less are regarded as burnout.
Input type
K
J T
B
S R N
E L (DIN) U (DIN)
W (DIN) Platinel 2 PR20-40
W97Re3-W75Re25 JPt100
Pt100
0.4 to 2V 1 to 5V 0 to 2V 0 to 10V
0.0 to 1.2 V (Note 3)
-10 to 20mV 0 to100mV
Input range
code
OFF
typeK1 (1) typeK2 (2) typeK3 (3) typeJ (4) typeT1 (5) typeT2 (6)
typeB (7)
typeS (8) typeR (9) typeN (10)
typeE (11) typeL (12) typeU1 (13) typeU2 (14) typeW (15) plati2 (16)
PR2040 (17)
W97Re3 (18) JPt1 (30) JPt2 (31) Pt1 (35) Pt2 (36) Pt3 (37)
0.4 to 2V (40) 1 to 5V (41) 0 to 2V (50) 0 to 10V (51)
0.00 to 1.25 V(52) mV1 (55) mV2 (56)
Set the data item PV input type “IN 1” or “IN 2” to the OFF option to leave the PV input type undefined.
0.000 to 1.250 V
-10.00 to 20.00 mV
Instrument
range (°C)
-200.0 to 1370.0°C
-200.0 to 1000.0°C
-200.0 to 500.0°C
-200.0 to 1200.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 1800.0°C
0.0 to 1700.0°C
0.0 to 1700.0°C
-200.0 to 1300.0°C
-200.0 to 1000.0°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0.0 to 400.0°C
0.0 to 2300.0°C
0.0 to 1390.0°C
0.0 to 1900.0°C
0.0 to 2000.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
-200.0 to 850.0°C
-200.0 to 500.0°C
-150.00 to 150.00°C
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.0 to 100.0 mV
Input bias current: 0.05 A( For T/C and RTD b-terminal) Specified current (RTD): about 0.13 mA Input resistance: TC/mV input 1 M or more
DC Voltage input approx. 1 M (approx. 8 M for ramge 0.0 to 1.2 V of measuring input 2)
Allowable signal source resistance:
TC/mV input: 250 Ω or less: Effect from allowable
signal source resistance 0.1 µV/ or less
DC Voltage input: 2 kΩ or less: Effect from allowable
signal source resistance 0.01%/100 or less
Allowable leadwire resistance (for RTD input): Maximum
150 /one wire (Lead resistances of three wires must be equal.) However, it must be 10 /one wire for the range of -150.0 to 150.0˚C.
Effect of wiring resistance: ±0.1˚C/10
Instrument
range (°F)
-300.0 to 2500.0°F
0.0 to 2300.0°F
-200.0 to 1000.0°F
-300.0 to 2300.0°F
-300.0 to 750.0°F
-200.0 to 750.0°F 32 to 3300°F
32 to 3100°F 32 to 3100°F
-300.0 to 2400.0°F
-300.0 to 1800.0°F
-300.0 to 1600.0°F
-300.0 to 750.0°F
-200.0 to 1000.0°F
32 to 4200°F
32.0 to 2500.0°F 32 to 3400°F
32 to 3600°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
-300.0 to 1560.0°F
-300.0 to 1000.0°F
-200.0 to 300.0°F
Display range: -19999 to 30000 Display span: 30000 or less (Decimal point position changeable)
Instrument accuracy
±0.1% ±1 digit of instrument range at 0°C or more ±0.2% ±1 digit of instrument range at less than 0°C
±0.15% ±1 digit of instrument range at 400°C or more ±5% ±1 digit of instrument range at less than 400°C
±0.15% ± 1 digit of instrument range
±0.1% ± 1 digit of instrument range ±0.25% ±1 digit of instrument range for temperature at less than 0°C
±0.1% ±1 digit of instrument range for temperature at 0°C or more ±0.2% ±1 digit of instrument range for temperature at 0°C or more
±0.2% ±1 digit of instrument range ±0.1% ± 1 digit of instrument range
±0.5% ±1 digit of instrument range at 800°C or more
Accuracy not guaranteed for temperature less than 800°C
±0.2% ± 1 digit of instrument range ±0.1% ± 1 digit of instrument range (Note 1) (Note 2) ±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range (Note 1) (Note 2)
±0.2% ± 1 digit of instrument range (Note 1) ±0.1% ± 1 digit of instrument range
*1
Numbers in ( ) are the measurement input range codes that apply when the communication function is used.
*1: Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60Hz power frequency) Note 1 : The accuracy is ±0.3°C of instrument range ±1 digit for a temperature range from 0 to 100°C Note 2 : The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from -100 to 200°C. Note 3 : Av ailable for only measurement input 2.
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
7
Allowable input voltage:
TC/mV/RTD: ±10VDC DC Voltage: ±20VDC
Noise rejection ratio:
Normal mode: 40dB(50/60Hz) or more Common mode: 120dB(50/60Hz) or more
RJC Error: ±1.0°C (15 to 35°C),
±1.5°C (0 to 15°C, 35 to 50°C )
Applicable standard:
TC/RTD: JIS/IEC/DIN (ITS-90)
Response time: 1 second or less, 63% (10 - 90%)
(The time required for transmission output to reach 63% of the maximum excursion when PV abruptly changes from 10% to 90%)
Auxiliary Analog Input
(For UP750- 1 only) Functions: Remote setpoint input, compensatory input,
PV input of Cascade secondary-loop, etc.
Input type: DC voltage input 0 to 2 V DC, 0 to 10 V DC,
0.4 to 2.0 V DC or 1 to 5 V DC (Settable
within the range) Number of input: 1 point Sampling period: 100, 200 or 500 ms
auxiliary analog input period is linked with
PV sampling period. Input resistance: Approx. 1M Input accuracy: ±0.3%±1 digit of F.S.
for 0 to 2 V DC range
±0.2%±1 digit of F.S. for 0 to 10 V DC range
±0.375%±1 digit of F.S. for 0.4 to 2.0 V DC
range.
±0.3%±1 digit of F.S. for 1 to 5 V DC range.
Performance in the standard operating
conditions (at 23± 2°C, 55± 10% RH, and 50/
60 Hz power frequency)
Retransmission Output
Any of the PV, target setpoint or control output is output. Can be used as the 15 V DC loop power supply.
Number of output points: 1 or 2
Retransmission output 2 is available only
when “relay” is selected as the control output
function. Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to 4
mA DC or 20 to 0 mA DC (0 mA or less
cannot be output) Load resistance: 600 Ω or less Output accuracy: ±0.1% of span (±5% for 1 mA or less)
Performance in the standard operating
conditions (at 23± 2°C, 55± 10% RH, and 50/
60 Hz power frequency)
When using for 15 V DC loop power supply:
Supply voltage 14.5 to 18.0 V DC, maximum supply
current about 21 mA (with the protection
circuit at field short-circuit)
15 V DC Power Supply Wiring to Two-wire Sensor
12
100
13
14
15
PV input
0.4 to 2.0 V DC signal
Loop power
supply
14.5 to
18.0 V DC
Two-wire transmitter
4-20mADC
External resistor (Note)
Control Outputs
One or two points can be selected from the following types, according to the model codes and specified UP mode.
Current output:
Number of output: 1 or 2 points (for heating/cooling type)
(selected between voltage pulse output)
Output signal: 4 to 20 mA DC, 0 to 20 mA DC, 20 to 4 mA
DC or 20 to 0 mA DC
Load resistance: 600 Ω or less Output accuracy: ±0.1% of output span(±5% for 1 mA or
less) Performance in the standard operating conditions (at 23± 2°C, 55± 10% RH, and 50/60 Hz power frequency)
Voltage pulse output:
Number of output: 1 or 2 points (for heating/cooling
type) (selected between current output)
Output signal: ON voltage 12 V DC or more (lead
resistance 600 or less), OFF voltage 0.1 V DC or less
Resolution: 10ms or 0.1% of output value, whichever is
greater
Relay contact output:
Number of output: 1 or 2 points (for heating/cooling
type) Output signal: Three terminals (NC, NO, and common) Contact rating: 250 V AC 3 A or 30 V DC 3 A (Load
resistance) Resolution: 10ms or 0.1% of output value, whichever is
greater
Contact Inputs
Usage: Program pattern switching, Local/Remote
switching, HOLD, ADVANCE selection, RUN/RESET switching, measured input selection, and message interruption display.
Number of input: 7 points (23 points max. when using
Digital I/O expansion module).
Input type: Non-voltage contact input or transistor open
collector input Input contact rating: 12 V DC, 10mA or more ON/OFF detection:
For non-voltage contact contact input:
ON=contact resistance 1 k or less, OFF=contact resistance 20 k or more
For transistor input:
ON=2 V or less, OFF=leak current 100 A or less
Minimum detecting time: PV input sampling period ×3
Contact Outputs
Usage: Instrument alarm output, Cooling side output
for Heating/Cooling control (Transistor
contact output), Event output. Number of output: 7 points (Relay output 3 points, Open
collector output 4 points), (23 points max.
when using Digital I/O expansion module). Relay contact rating: 240 V AC 1 A or 30 V DC 1 A
(Common to COM terminal) Transistor contact rating: 24 V DC 50 mA (Common to
COM terminal)
Expansion Digital I/O
Up to two Digital I/O expansion modules can be connected to increase the number of Digital I/O.
Each 8 points of input/output per one module can be accessed from the instrument.
Note: Connecting a 100 Ω resistor to the terminals is optional. Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
8
Display Specifications
Measured value (PV) display: 5 digit seven segment red Data display: 32 × 128 dot LCD display with back-light
Status indicating lamp: LED
color LED display, height of a letter: 20 mm
Conformance to Safety and EMC standards
Safety:Compliant with IEC/EN61010-1: 2001, approved
by CSA1010, approved by UL508. Installation category : CAT. II (IEC/EN61010, CSA1010) Pollution degree : 2 (IEC/ EN61010, CSA1010) Measurement category : I (CAT. I : IEC/ EN61010) Rated measurement input voltage : 10V DC max.(across terminals), 300V AC max.(across ground) Rated transient overvoltage : 1500V (Note) Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in measurement category I, and is not the value which guarantees an apparatus performance.
EMC standards:Complies with EN61326
During test, the controller continues to operate with the measurement accuracy within ±20% of the range.
Construction, Installation, and Wiring
Structure: Dust-proof and Drip-proof front panel
conforming to IP55. For side-by-side close installation, controller
loses its dust-proof and drip-proof protection. Material of the body: ABS resin and polycarbonate Case color: Black Weight: Approx. 1 kg or less Dimensions: 96W×96H×100D (From the front panel
surface) (mm) Mounting: Direct panel mounting; mounting bracket, one
each for upper and lower mounting Panel cutout dimensions:
92
+0.8
0
W ×
92
+0.8
H (mm)
0
Mounting position: 0° to +30° with respect to vertical
panel surface. Wiring: M3.5 screw terminal (signals, power supply/
ground)
Power Supply and Isolation
Power supply: Rated voltage 100 to 240V AC, (±10%),
Power consumption: MAX. 20VA (MAX. 8.0W) Memory backup: Litium Battery, Life Time approx.
Withstanding voltage:
Between primary terminal and secondary terminal:
Between primary terminal and ground terminal:
Between ground terminal and secondary terminal:
Between two secondary terminal:
primary terminal: Power supply, Relay output secondary terminal: Analogue input/output, Voltage
50/60Hz
10years
1500V AC for 1 min.
1500V AC for 1 min.
1500V AC for 1 min.
500V AC for 1 min.
pulse output, contact input.
Isolation Resistance:
Between power supply terminal and ground 500V DC 20M or more
Grounding: Class D grounding (grounding registance of
100 or less)
Isolation Specifications
Measured input terminal 1: Isolated from Measured input
terminal 2 and other input/output terminals. Not isolated from internal circuits.
Measured input terminal 2: Isolated from Measured input
terminal 1, other input/output terminals and internal circuits.
Auxiliary analogue input terminal: Isolated from other
input/output terminals and internal circuits.
Control output (current output or voltage pulse output) and
retransmission output: Not isolated between control output and retransmission output terminals. Isolated from other input/output terminals and internal circuits.
Relay contact control output terminals: Isolated from other
input/output terminals and input circuits.
Contact input terminals: Not isolated from other contact
input and communication terminals. Isolated from other input/output terminals and internal circuits.
Relay contact event output terminals: Isolated from other
input/output terminals and internal circuits.
Transistor contact event output terminals: Not isolated
between other open collector output terminals mutually. Isolated from other input/output terminals and internal circuits.
RS-485 communication terminals: Not isolated between
other communication terminals, and from contact input terminals. Isolated from other input/output terminals and internal circuits.
Power supply terminals: Isolated from other input/output
terminals and internal circuits.
Ground terminal: Isolated from other input/output
terminals and internal circuits.
Environmental Conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C 40°C or less in close
Temperature change rate limit: 10°C/h or less Mbient humidity: 20 to 90%RH (no condensation) Ambient humidity: 20 to 90%RH (no condensation) Magnetic field: 400 A/m or less Continuous vibration (5 to 14Hz): amplitude 1.2mm or
Continuous vibration (14 to 150Hz): 4.9m/ s Vibration in short period: 14.7m/ s Shock: 147m/s Installation altitude: 2000m above the sea level or less Warm-up time: 30 minutes or more
Transit/storage conditions:
Temperature: -25 to 70°C Temperature change rate limit: 20°C/h or less Humidity: 5 to 95%RH (non-condensing)
Effects of operating conditions:
Effect of ambient temperature:
For Voltage/TC input: Within (±1V/°C or ±0.01% of
For Auxiliary input: Within ±0.02% of F.S./°C For RTD input: Within ±0.05°C/°C (ambient tempera-
For analog output: Within ±0.05% of F.S./°C
mounting side-by-side.
less
2
2
or less, 11ms
, 15sec or less
F.S./°C, whichever is greater.)
ture)
2
or less
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
Function Block Diagram for Single-loop Control
PV input
12
terminals , and
11
INPUT1
Input selection
Unit selection
Analog input range conversion
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
13
Contact Input
Contact input
Expansion
DI1
DI2
DI3
RDI104 to 108
DI4
Program
pattern selection
Program operation
Local
setpoint 1
Program
operation
Local
operation
Control computationManual operation
AUTOMAN
A/M
AUTO (ON)/MAN (OFF) switching (RDI103)
DI5
DI6
Start of program operation
when DI changes from OFF to ON
DI7
Stop of program operation
when DI changes from OFF to ON
Start of local-mode operation
when DI changes from OFF to ON
Start of hold operation when RDI101 changes from OFF to ON.
Advance operation when RDI102 changes from OFF to ON.
9
Contact Input
Expansion
RDI101 to 103
Preset output
Output limiter
RUNSTOP
STOP/RUN switching
15 V loop
OT1
Control
output
OUTPUT1
Current or pulse
17
16
terminals and
OUTPUT1
Relay
terminals
2
1
, and
R151 to 158
power supply
3
RET2 RET1
OUTPUT1
Current*
terminals
17
16
and
R251 to 258
Contact Output Expansion
* Unavailable when control output is current or pulse.
Retransmission
output
OUTPUT3
Current
terminals
15
14
and
Instrument alarm output
DO1
PV
event 1PVevent 2
PV event output
Time event output
DO2
DO3
Instrument
alarm 1
DO4
Time
event 1
DO5
Time
event 2
DO6
Time
event 3
DO7
Time
event 4
Legend
Terminal Parameter Function
Analog signal Contact signal
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
Function Block Diagram for Custom Computation
The UP750 controller comes with built-in control functions and various controller modes (UP modes) that provide different I/O computing functions. These modes are designed to support their
respective control applications. From these choices, you can choose one that best meets your applica­tion needs. In some control applications, however, you may want to execute special computations based upon specific input data or have a contact output of a specific data item in a specific control sequence. To be able to meet these needs, the UP750 controller provides a separate controller mode with which you can freely program your own computations. Computing functions available in these modes are referred to as custom computations.
Custom computations allow you to perform a variety of calculations based on input and output signals. These calculations include not only the four arithmetic operations and logical operations but also ten­segment linear approximations, temperature and humidity computations, temperature-based correction coefficient computations, pressure-based correction coefficient computations, and so on. For example, you can use the four arithmetic operations to apply the desired type of correction to input signals, or use a logical operation to program a sequencing process that works between input and output contacts.
Custom computations are configured using the given methods of block connection, as shown in Figures below.
10
Flowrate
Temperature-based
flowrate correction
Manual output
Temperature
Fluid pressure correction
Square-root computation
Control and computing section
Pressure
A/M switching
Contact input 1
Custom Computations Applied to Input Signals
Control and computing section
Alarm 1
Alarm 2 Alarm 3 Alarm 4 Alarm 5 Alarm 6
Contact input 2 Contact input 3
OR
AND
Control output processing
MV output
Custom Computations Applied to Output Signals
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
OR
Contact output 1
OR
Contact output 2
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
1
2
3
4
5
6
7
8
9
10
41
42
43
44
45
46
47
48
49
50
31
32
33
34
35
36
37
38
39
40
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
28
29
High performance
RS-485 communication
* Wiring can only be carried out
for controllers with
communication functions.
30
RSB(+)
RSA(-)
SG
* The functions of the external contact inputs are the defaults for single-loop control.
To change the functions, reconfigure the Contact Input Registration setup parameter.
* The functions of the external contact outputs are the defaults for single-loop control.
To change the functions, reconfigure the Contact Output Registration setup parameters.
Communication 1
(PSL1)
Communication 2
(PSL2)
1
2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*
Time proportional PID relay contact
output is configured at factory
before shipment.
Note: Select this option from
the OT1 parameter.
8
9
Power supply
10
L
N
A
llowable range: 100-240 V AC (
10%)
(free voltage)
50/60 Hz shared
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
23
24
RS-485 communication
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
21
22
Auxiliary analog input
*
Wiring can only be carried out for
controllers with remote input.
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
Default: 1-5 V DC
12
13
TC input
11
12
RTD input
13
12
13
mV/V input
A
b
B
-
+
-
+
PV input
*
Not configured at factory before shipment
12
13
Note:Connecting a 250
resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
Receiving 4-20 mA DC Current
Signals with the Controller
250
4-20mA
-
+
* Factory-set to “PV retransmission.”
* Retransmission output 1 is not available
if a 15 V DC loop power supply is used.
14
15
Retransmission output 1*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply*
14.5-18.0 V DC
(21 mA DC max.)
Default: 4-20 mA DC
-
+
-
+
Load resistance: 600
or less
16
17
Current/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
Control output
* Retransmission output 2 is available
only when “relay” is selected as the
type of control output.
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
Default: Unspecified
retransmission type
Note: Select this option from the OT1 parameter.
OT1=0 (factory-set default)
OT1=1
Correspondence between parameters OT1 and control output types
OT1=2
OT1=3
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to change the control output type.
Time proportional control
Relay output
(terminals
1
,
2
and
3
)
Time proportional control
Voltage pulse output
(terminals
16
and
17
)
Current output
(terminals
16
and
17
)
On-off control
Relay output
(terminals
1
,
2
and
3
)
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
External contact inputs
Common
Start of local-mode operation when
DI7 changes from OFF to ON
Stop of program operation when
DI6 changes from OFF to ON
Start of program operation when
DI5 changes from OFF to ON
DI1
DI2
1234
ON
ON OFF
OFF
ON
ON
OFF
OFF
5678
ON
ON OFF
OFF
ON
ON
OFF
OFF
DI3
DI4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
9101112
ON
ON OFF
OFF
ON
ON
OFF
OFF
13 14 15
ON
ON OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
Switch between the ON and OFF states of the DI1 to DI4
contact inputs to select from program pattern numbers 1 to 15.
(Select a number during a RESET state.)
19
18
40
39
38
37
20
DI1
DI2
DI3
DI4
DI5
DI6
COM
19
18
40
39
38
37
20
DI1
DI2
DI3
DI4
DI5
DI6
COM
+5V
+5V
+5V
+5V
+5V
+5V
36
DI7
36
DI7
+5V
Contact Transistor contact
UP
6
5
External contact outputs
4
7
34
33
DO1
DO2
DO3
COM
DO4
DO5
Relay Transistor
Time event 2
output
PV event 1 output
PV event 2 output
Instrument alarm
1 output
Common
Time event 1
output
32
DO6
31
DO7
35
COM
Time event 3
output
Common
Time event 4
output
UP
Contact rating: 12 V DC, 10 mA or more
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
UP750 Single-loop Control (Model UP750-0 or UP750-5첸)
11
<<Contents>> <<Index>>
Effect of power supply fluctuation (within rating voltage):
For analog input: Within (±1µV/10V or ±0.01% of F.S./10V, whichever is greater.) For analog output: Within ±0.05% of F.S./10V
External Dimensions and Panel Cutout Dimension
12
Unit: mm
92
(53)
+0.8
96
PVE1 PVE2
11
100
96
Small bracket
1 to 10 mm (Panel thickness)
General installation Side-by-side close installation
[(N-1)96+92]117 min.
0
+0.8
92
145 min.
“N” stands for the number of controllers to be installed.
0
However, the measured value applies if N  5.
Large bracket
112
91.8
+0.8
0
92
+0.8
0
(25)
Normal Allowable Deviation=± (Value of JIS B 0401-1999 tolerance grade IT18) /2
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation
GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
<<Contents>> <<Index>>
Model and Suffix codes
Model suffix code Discription
UP750 Type Optional
Functions
Note: Using an optional custom computation building tool (Model LL200-E10) that runs on a personal computer, you can b uild a v ariety
of computation (e.g., four arithmetic operations, logical operations, ten-segment linearizer computations, temperature compensation factor computations, and pressure compensation factor computations) to be applied to the controller’ s I/O signals.
-0
-5
Program controller (provided with Custom Computating Function Single-loop type Dual-loop type
0
None
1
With communication, auxiliary analog input
Standard accessories: Brackets (mounting hardware), unit label, User’s Manuals, and User’s Manual (reference) (CD-
ROM version).
Specify suffix code according to the designated UP mode.
Correspondence between UP mode and suffix code
00 01 50 51UP mode suffix code
Single-loop control (UP mode 1) Cascade primary-loop control (UP mode 2) Cascade control (UP mode 4) Loop control with PV switching (UP mode 6) Loop control with PV auto-selector (UP mode 7) Dual-loop control (UP mode 11) Temperature and humidity control (UP mode 12) Cascade control with two universal inputs (UP mode 13) Loop control with PV switching and two universal intputs (UP mode 14) Loop control with PV auto-selector and two universal intputs (UP mode 15)
App.
N/A N/A N/A N/A N/A N/A N/A N/A
N/A
App. App. App. App. App.
N/A N/A N/A N/A
N/A
App.
N/A N/A N/A
N/A App. App. App. App.
Cond.
App. App. App. App. App. App. App. App. App.
App.
"Note"
)
An auxiliary analog innput is used as cascade input. An auxiliary analog input is used as PV input 2. An auxiliary analog input is used as PV input 2.
Cond.=Two PV inputs are available. App.=Three PV inputs are available.
13
Custom computation control (UP mode 21)
App: Function available, Cond: Function av ailable conditionally, N/A: Function not available
App.
App.
App.
Digital I/O expansion module
Model Description
P2ER1-20J*A P2ET1-20J*A
Note 1: Digital I/O expansion modules manufactured by Yokaga w a Electric Corporation.
Note 2: Digital I/O expansion modules do not have CE/UL marking.
AC power supply Inputs (8 points) and relay outputs (8 points) AC power supply Inputs (8 points) and transistor outputs (8 points)
Please order to Yokagawa Electric Corporation.
Items to be specified when ordering
Model & suffix code, necessary/unnecessary of User’s Manual or QIC
App.
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 05E01B02-01E 4th Edition Oct. 01, 2007-00
Loading...