YOKOGAWA UM350, UM330 User Manual

Page 1
NOTE
User’s Manual
Models UM350 / UM330 Digital Indicator with Alarms User’s Manual
IM 05F01D02-01E
This manual describes installation, wiring, and other tasks required to make the indicator ready for operation.
1. Safety Precautions
2. Model and Suffix Codes
3. How to Install
4. How to Connect Wires
5. Hardware Specifications
Introduction
Thank you for purchasing the UM350/UM330 digital indicator with alarms. The indicator is shipped from the factory with 3 hardcopy user’s manuals (A2 size). T he 3 user’s man uals in hardcopy format describe the operating procedures required for basic use. It is recommended that you refer to these user’s manuals to understand [1] installation, [2] initial settings, and [3] operating procedures of the indicator.
How to Use the Manuals
Purpose Manual Title Description Media
Setup
Basic operation
Operating procedures and troubleshooting
Brief operation and setpoint recording
1. Safety Precautions
The following symbol is indicated on the indicator to ensure safe use.
CAUTION
This symbol on the indicator indicates that the operator must refer to an explanation in the user’ s manual in order to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes ho w the opera tor should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.
The following symbols are used in the hardcopy user’s manuals.
NOTE
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or features of the indicator.
Exemption from Responsibility
Make sure that all of the precautions are strictly adhered to. Yokogawa Electric Corporation assumes no liability for any damage resulting from use of the instrument in contradiction to the precautions. Also, Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect, caused by the use or any unpredictable defect of the instrument.
Regarding Protection, Safety, and Prohibition Against Unauthorized Modification
(1) In order to protect the product and the system controlled by it against damage and ensure its safe use, make certain that
all of the instructions and precautions relating to safety contained in this document are strictly adhered to. Yokogawa does not guarantee safety if products are not handled according to these instructions.
(2) Modification of the product is strictly prohibited.
2. Model and Suffix Codes
Before using the indicator, check that the model and suffix codes match your order.
Model Suffix Code Description UM350 UM330
Type
Optional functions
Check that the following items are provided:
• Digital indicator with alarms (of ordered model): .........................................1
• Brackets (mounting hardware): ......................................................................1 pair
• Unit label: .......................................................................................................1
• User’s Manuals:..............................................................................................3 (A2 size)
• User’s Manual (Reference) (CD-ROM Version)
(only for indicators with optional communication functions):....................... 1
-0 Standard type with three alarms
-3 Standard type with three alarms (with 24V DC loop power supply)
Installation
Contents
Installation
Initial Settings
Operations
Parameters
Describes the tasks (installation, wiring, and others) required to make the indicator ready for operations.
Describes examples of setting PV input types, and alarm types. Making settings described herein allows you to carry out basic monitoring.
Describes examples of setting alarm setpoints, as well as key operation necessary to run the indicator
Contains the parameter map used as a guideline for setting parameters and lists of parameters for recording user settings.
Digital indicator with Alarms (provided with retransmission output and 15 V DC loop power supply as standard)
0 None 1 With communication and additional alarm-4 2 With additional alarm-4
4th Edition: Jan 31, 2005
A2-size paper (Front and back)
A2-size paper (Front)
(Back)
A2-size paper (Front and back)
3. How to Install
NOTE
To install the indicator, select a location where: (1) no one may accidentally touch the terminals, (2) mechanical vibrations are minimal, (3) corrosive gas is minimal, (4) temperature can be maintained at about 23°C and the fluctuation is minimal, (5) no direct radiant heat is present, (6) no magnetic disturbances are caused, (7) no wind blows against the terminal board (reference junction compensation
element), (8) no water is splashed, (9) no flammable materials are around,
Never place the indicator directly on flammable items or equipment. If the indicator has to be installed close to flammable items or equipment, be sure to provide shielding panels all around the indicator, at least 150mm away from every side; the panels should be made of either 1.43mm-thick metal-plated steel plates or 1.6mm-thick uncoated steel plates.
NOTE
Never touch the opening at the bottom of the case. It is to be used in the factory at shipping.
Installation Position
Install the indicator at an angle within 30° from horizontal with the front panel facing upward. Do not install it facing down­ward. The position of right and left sides should be horizontal.
Front panel
of indicator
30
External Dimensions and Panel Cutout Dimensions
UM350
Large bracket
91.8
Small bracket
[(N-1)96+92]117 min.
UM330
45
(25)
92
+0.6
(53)
+0.8
0
92
48
General installation
0
92
96
11
96
100
1 to 10 mm (Panel thickness)
General installation Side-by-side close installation
0
+0.8
92
+0.8
145 min.
0
(25)
Small bracket
96
10011
"N" stands for the number of indicators to be installed. However, the measured value applies if N  5.
112
91.8
Front of indicator
145 min.
70 min.
+0.8
0
(53)
150mm
Unit: mm
112
+0.8
0
Small bracket
1 to 10 mm (Panel thickness)
150mm
Rear of indicator
Unit: mm
150mm150mm
Must not exceed 30
How to Install
CAUTION
Turn off the power to the indicator before installing it on the panel because there is a possibility of electric shock.
Panel
Direction to insert the indicator
Insert the
indicator into the opening at the front of the panel.
Note: Right and left mounting for UM330.
Small bracket
(bottom mounting hardware)
Large bracket
(top mounting hardware)
Terminal board
Insert a screwdriver into the brackets to tighten the screws.
Recommended tightening torque :0.4 Nm
After opening the mounting hole on the panel, follow the procedures below to in­stall the indicator:
1. Insert the indicator into the opening from the front of the panel so that the terminal board on the rear is at the far side.
2. Set the brackets in place on the top and bottom of the indicator as shown in the figure on the left, then tighten the screws of the brackets. Take care not to over­tighten them.
4. How to Connect Wires
CAUTION
1) Before carrying out wiring, turn off the po wer to the indicator and check that the cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
2) For the protection and safe use of the indicator, be sure to place a circuit breaker (conforms with IEC60947, 5A, 100V or 220V AC) near the indicator where the breaker can easily be operated. In addition, be sure to indicate that it is the instrument to cut the power supply of the indicator.
3) Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.
1) Provide po wer from a single-phase instrument power supply . If there is a lot of noise in the po wer line, insert an insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC2205-00U from TDK) on the secondary side. As a countermeasures against noise, do not place the primary and secondary power cables close to each other .
2) For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires. The cables to be used for wiring, terminal specifications, and recommended parts are as shown below.
3) Alarm output relays ha ve a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off a load.
4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
5) When there is possibility of being struck by external lightening sur ge, use the arrester to protect the instrument.
For DC Relay Wiring For AC Relay Wiring
UM350/UM330
Relay
External DC power supply
UM350/UM330
R
Diode
UM’s contact
(Use one with a relay coil rating
less than the UM’s contact rating.)
Relay
(Mount it directly to the relay coil terminal (socket).)
UM’s contact
(Use one with a relay coil
rating less than the UMs
contact rating.)
Cable Specifications and Recommended Cables
Purpose Name and Manufacturer
Power supply, grounding, relay contact outputs
Thermocouple Shielded compensating lead wires, JIS C 1610, X- - -
RTD Shielded wires (three conductors), UL2482 (Hitachi Cable) Other signals Shielded wires
600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm2
(See Yokogawa Electric's GS 6B1U1-E.)
Recommended T erminal Lugs
Applicable wire size Tightening torque
0.3 to 1.65 mm
7 mm or less
2
3.7mm
0.8 N·m or less
3.7mm
or
7 mm or less
Terminal Covers(Optional parts)
Target Model Part Number Sales Unit UM350 T9115YD 1 UM330 T9115YE 1
1. Before attaching the terminal cover, bend the side with the groove inward as shown in Fig. A. Be careful not to bend it backwards. This not only makes it harder to attach the cover but will also weaken its hold.
2. Fit the holes on the top and bottom (or left and right) of the terminal cover over the projections on the brackets (Fig. B) and lock in place. The figure right shows the attachment of a terminal cover to UM indicator.
Note:Right and left mounting for UM330.
Figure A
External AC power supply
R
Relay
Fold the cover in the direction of the arrow.
Fit the cover hold over the protrusion on the mounting bracket.
CR filter (Mount it directly to the relay coil terminal (socket).)
5. Hardware Specifications
PV Input Signals
Number of inputs: 1 (terminals 11-12-13)
Input type: Universal input system. The input type can be
selected with the software.
Sampling period: 250 ms
Burnout detection: Functions at TC, RTD, standard signal
(0.4 to 2 V or 1 to 5 V) Upscale, downscale, and off can be specified. For standard signal, burnout is determined to have occurred if it is 0.1 V or less.
Input bias current: 0.05 A (for TC or RTD b-terminal)
Measurement current (RTD): About 0.13 mA
Input resistance: 1 M or more for thermocouple or mV input
About 1 M for DC voltage input
Allowable signal source resistance: 250  or less for thermocouple or mV input Effects of signal source resistance: 0.1 V/ or less 2 k or less for DC voltage input Effects of signal source resistance: About 0.01%/100
Allowable wiring resistance: for RTD input Maximum 150 /wire: Conductor resistance between three wires should be equal However, 10 /wire for a maximum range of -150.0 to
150.0C. Wire resistance effect: 0.1C /10 
Allowable input voltage: 10 V DC for thermocouple, mV, or RTD input 20 V DC for DC voltage input
Noise rejection ratio: 40 dB (50/60 Hz or more in normal mode 120 dB (50/60 Hz) or more in common mode
Reference junction compensation error: 1.0C (15 to 35C)1.5C (0 to 15C, 35 to 50C)
Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD
Loop Power Supply
Power is supplied to a two-wire transmitter. (15 V DC: terminals
A resistor (10 to 250 ) connected between the indicator and transmitter converts a current signal into a voltage signal, which is then read via the PV input terminal . Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided with a protection circuit against a field short-circuit); 21.6 to 28.0 V DC, max. 30 mA (only for models with 24 V DC loop power supply)
Retransmission Output
Outputs the PV value. Either the retransmission output or the 15 VDC loop power
supply can be used with terminals
Number of outputs: 1 (terminals
Output signal: 4-20 mA DC
Load resistance: 600 or less
Output accuracy: 0.3% of span under standard operating
conditions (23 2C, 55 10% RH, power frequency of 50/60 Hz)
Contact Inputs
Purpose: Resetting of PV peak and bottom values
Number of inputs: 1
Input type: Non-voltage contact or transistor open collector input
Input contact rating: 12 V DC, 10 mA or more
On/off determination: For non-voltage contact input, contact
resistance of 1 k or less is determined as on and contact resistance of 20 k or more as “off. For transistor open collector input, input voltage of 2 V or less is determined as “on” and leakage current must not exceed 100 A when “off.
Minimum status detection hold time: About 1 second
Contact Outputs
Purpose: Alarm output, FAIL output, and others
Number of outputs: 4 (Max).
Relay contact rating for Alarm 1 to 3: 240 V AC, 1 A, or 30 V
DC, 1 A ; 1a (FAIL output ; 1b)
Relay contact rating for Alarm 4: 250 V AC, 3 A, or 30 V DC, 3 A (resistance load) 3 terminals (NC, NO, Common); 1c
Display Specifications
PV display: 4-digit, 7-segment red LED display, character height of 20 mm
Setpoint display: 4-digit, 7-segment, red LEDs, character height of 9.3 mm
Status indicating lamps: LEDs
Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE), approved by C22.2 No.61010-1, approved by UL508. Installation category : CAT. II Pollution degree : 2 (IEC/ EN61010-1, C22.2 No.61010-1) Measurement category : I (CAT. I : IEC/EN61010-1) Rated measurement input voltage : 10V DC max.(across terminals), 300V AC max.(across ground) Rated transient overvoltage : 1500V (Note) Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in Measurement category I, and is not the value which guarantees an apparatus performance.
CAUTION
This equipment has Measurement category I, there­fore do not use the equipment for measurements within Measurement categories II, III and IV.
Measurement category
CAT.1
1
CAT.2
2
CAT.3
3
CAT.4
4
Entrance Cable
14-15
; 24 V DC: terminals 21-22)
16-17
Description
For measurements performed on circuits not directly connected to MAINS. For measurements performed on circuits directly connected to the low voltage installation. For measurements performed in the building installation. For measurements performed at the source of the low-voltage installation.
Internal Wiring
3
4
1
Outlet
16-17
.
)
Remarks
Appliances, portable equipments, etc.
Distribution board, circuit breaker, etc. Overhead wire, cable systems, etc.
2
T
Construction, Installation, and Wiring
• Construction: Only the front panel is dust-proof and drip-proof (protection class IP55) For side-by-side close installation the indicator loses its dust-proof and drip-proof protection.
• Material: ABS resin and polycarbonate
• Case color: Black
• Weight: About 1 kg or less
• Dimensions: UM350 96 (W) 96 (H) 100 (depth from panel face)
UM330 96(W) 48 (H) 100 (depth from panel face)
• Installation: Panel-mounting type. With top and bottom (or right and left) mounting hardware (1 each)
• Panel cutout dimensions: UM350 92 UM330 92
• Installation position: Up to 30° upward facing (not designed for facing downward)
• Wiring: M3.5 screw terminals (for signal wiring and power/ ground wiring as well)
mm
mm
+0.8
0
+0.6
0
(W) 92 (W) 45
+0.8
(H) mm
0
+0.8
(H) mm
0
Power Supply Specifications
• Power supply: Rated voltage of 100 to 240 V AC (10%), 50/60 Hz
• Power consumption: Max. 20 VA (8.0 W max.)
• Internal fuse rating: 250 V AC, 1.6A time-lug fuse
• Data backup: Non-volatile memory (can be written to up to 100,000 times)
• Withstanding voltage
- Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
- Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
- Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
- Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay
output terminals
** Secondary terminals indicate analog I/O signal, and
contact input terminals
• Insulation resistance: 20 M or more at 500 V DC between power terminals and grounding terminal
• Grounding: Class D grounding (grounding resistance of 100 or less)
Signal Isolations
• PV input terminals: Isolated from other input/output terminals. Not isolated from internal circuit.
• 15 V DC loop power supply terminals: Not isolated from 4-20 mA analog output. Isolated from other input/output terminals and internal circuit.
• 24 V DC loop power supply terminals: Isolated from 4-20 mA analog output terminals, other input/output terminals and internal circuit.
• 4-20 mA analog output terminals (for retransmission): Not isolated from 15 V DC loop power supply. Isolated from other input/output terminals and internal circuit.
• Contact input terminals: Not isolated from communication terminals. Isolated from other input/output terminals and internal circuit.
• Relay contact output terminals: Not isolated between relay contact output terminals. Isolated from other input/output terminals and internal circuit.
• RS-485 communication terminals: Not isolated from contact input terminals. Isolated from other input/output terminals and internal circuit.
• Power terminals: Isolated from other input/output terminals and internal circuit.
• Grounding terminals: Isolated from other input/output terminals and internal circuit.
Environmental Conditions
• Normal operating conditions:
Ambient temperature: 0 to 50C (40C or less for side-by-side
close installation) 0 to 40C if the 24V DC loop power supply of Model UM330 is used
Temperature change rate: 10C/h or less Ambient humidity: 20 to 90% RH (no condensation allowed) Magnetic field: 400 A/m or less Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or
less
Continuous vibration at 14 to 150 Hz: 4.9 m/s2 or less Short-period vibration: 14.7 m/s2, 15 seconds or less Shock: 147 m/s2 or less, 11 ms Installation height: Height above sea level of 2000 m or less Warm-up time: 30 minutes or more after power on
• Transportation and storage conditions:
Temperature: -25 to 70C Temperature change rate: 20C/h or less Humidity: 5 to 95% RH (no condensation allowed)
• Effects of changes in operating conditions
- Effects from changes in ambient temperature:
- On voltage or thermocouple input, 1 V/C or 0.01%
of F.S./C, whichever is larger
- On RTD input, 0.05C /C (ambient temperature) or less
- On analog output, 0.05% of F.S./C or less
- Effects from power supply fluctuation (within rated voltage range)
- On analog input,  1 V/10 V or  0.01% of F.S. /10 V, whichever is larger
- On analog output, 0.05% of F.S./ 10 V or less
Figure B
EMC standards: Complies with EN61326, EN61000-3-2, EN61000-3-3 and EN55011 (CE). Class A Group 1. The instrument continues to operate at a measuring accuracy of within 20% of the range during tests.
IM 05F01D02-01E (1)
Page 2
6. Terminal Wiring Diagrams
NOTE
Do not use unassigned terminals as relay terminals.
UM350 Standard Type (Model UM350-䊐䊐)
* Wiring can only be carried out for indicators with communication functions. Maximum baud rate: 9600 bps
1 2 3 4 5 6 7 8 9
10
UM
6 5 4
peak and bottom values
when DI1 is changed
7
Alarm 4 output
Relay contact output
NC
1
NO
2
COM
3
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Power supply
Power supply
L
N
* Wiring can only be carried out for
Before carrying out wiring, turn off the power to the indicator and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
8 9
10
Allowable range: 100 to 240 V AC (10%)
(free voltage) 50/60 Hz shared
RS-485 communication
SDB(+)
23
SDA(-)
24
RDB(+)
25
RDA(-)
26
SG
27
UM350-1 or UM350-ⵧ2.
CAUTION
Alarm output
Alarm 1 output
Relay
Alarm 2 output
Alarm 3 output
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
AL1
AL2 AL3
COM
21 22 23 24
25 26 27
Resets the PV
from OFF to ON
Common
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
24 V DC loop power supply
+
21
21.6-28.0VDC (30 mA DC max.)
-
22
11 12 13
Retransmission output
16 17
19
15 V DC loop power supply
20
Contact input
Contact
UM DI1
.
19
20
COM
Contact rating: 12 V DC, 10 mA or more
+5V
16 17
16 17
DI1
COM
PV input
+
4-20 mA DC
-
+
14.5-18.0VDC (21 mA DC max.)
-
Transistor contact
19
20
* Not configured at factory before shipment See ,
Initial Settings Users Manual
for more information.
12 13
TC input
+
-
11 12 13
RTD input A b
B
mV/V input
+
12
-
13
* PV retransmission is configured at factory before shipment.
Load resistance: 600
or less
* If 15 V DC loop power supply is used, retransmission output cannot be used.
Receiving 4-20 mA DC Current
Signals with the Indicator
* When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint 41”).
12
+
250
4-20mA
-
13
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
UM330 Standard Type (Model UM330-䊐䊐)
Receiving 4-20 mA DC Current
Signals with the Indicator
* When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint 41).
12
+
250
4-20mA
-
13
Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
24 V DC loop power supply
21.6-28.0VDC (30 mA DC max.)
Alarm 4 output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
PV input
TC input
+
12
-
13
+
21
-
22
* Wiring can only be carried out for 1 2 3
30 V DC, 3 A (resistance load)
UM330-1 or UM330-2.
* Not configured at factory before shipment See ,
Initial Settings Users Manual
for more information.
RTD input A
11
b
12 13
B
mV/V input
+
12
-
13
Alarm output
Alarm 1 output
Relay
Alarm 2 output
Alarm 3 output
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
AL1
AL2 AL3
COM
112113
12
23
22
1
2 8
6
3
UM
25
24
5
4
5 4 7
Retransmission output
+
16
4-20 mA DC
-
17
15 V DC loop power supply
+
16
14.5-18.0VDC (21 mA DC max.)
-
17
19
17
16
27
26
9
7
6
Power supply
Power supply
L
N
Allowable range: 100 to 240 V AC (10%)
(free voltage) 50/60 Hz shared
* PV retransmission is configured at factory before shipment.
Load resistance: 600
or less
* If 15 V DC loop power supply is used, retransmission output cannot be used.
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
Common
20
RS-485 communication
SDB(+)
23
SDA(-)
10
8 9
10
24
RDB(+)
25
RDA(-)
26
SG
27
CAUTION
Before carrying out wiring, turn off the power to the indicator and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
UM DI1
.
COM
Contact rating: 12 V DC, 10 mA or more
* Wiring can only be carried out for indicators with communication functions. Maximum baud rate: 9600 bps
Contact input
Contact
19
20
+5V
DI1
COM
Transistor contact
19
20
15 V DC Power Supply Wiring to Two-wire Sensor
External resistor (Note)
Two-wire transmitter
4-20mADC
Note: Connecting a 100 resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
12
100
0.4 to 2.0 V DC signal
13
16
17
PV input
Loop power
supply
14.5 to
18.0 V DC
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
24 V DC Power Supply Wiring to Two-wire Sensor
250
12
PV input
1 to 5 V DC signal
13
21
Loop power
supply
21.6 to
28.0 V
22
DC
External resistor (Note)
Two-wire transmitter
4-20mADC
Note: Connecting a 250 resistor to the terminals is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
IM 05F01D02-01E (2)
Page 3
NOTE
1.
Bring the operating display into view (appears at power-on).
2.
Press the key for more than 3 seconds to call up the menu OP.PA.
3.
Press the key once to display the menu STUP.
7.
Press the or key to display the required setpoint. The figure below shows an example of setting PV low limit alarm.
9.
Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
See 1. Setting Alarm Setpoints in
Operations
Users Manual
when setting an alarm setpoint.
4.
Press the key once to display the parameter PWD.
8.
Press the key once to register the setpoint.
5.
Press the key once to display the menu FUNC.
6.
Press the key once to display the parameter AL1 (alarm-1 type).
You can take the same steps for alarm-2 type (AL2), alarm-3 type (AL3), and alarm-4 type (AL4) that are displayed after this.
SET/ENT
SET/ENTSET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
PV
AL1 2 3 4
SET/ENT
Displays menu
OP.PA.
Display menu
STUP.
Displays menu
FUNC”.
Displays
parameter
PWD.
Displays
parameter
AL1.
Blinks during
change.
Displays
PV.
Displays
PV.
User’s Manual
Models UM350 / UM330 Digital Indicator with Alarms Users Manual
IM 05F01D02-02E
This manual describes examples of setting the types of PV input and alarm. Carrying out settings described herein allows you to perform basic monitoring. Refer to examples of various settings to understand how to set parameters required. Refer to “1. Par ameter Map” in
eters. If you cannot remember how to carry out an operation during setting, press the This brings you to the display (operating display) that appears at power-on.
1. Names and Functions of Front Panel Parts
2. Setting PV Input Type (Setting First at Power-on)
3. Changing PV Input Type
4. Changing Alarm Type
5. Setting Hysteresis in Alarm Setpoint
1. Names and Functions of Front Panel Parts
4. SET/ENT key
Name of Part Process variable (PV)
1. display
Parameter setpoint display
2.
3. Alarm indicator lamps
4.
5.
SET/ENT key
and keys
SET/ENT
The following explanation of operation for the UM350’s panel, shown in the figure, is the same as that of the UM330’s panel.
IMPORTANT
The indicator automatically returns to the display at the time of power-on (i.e., Operating display) if no key is operated for at least one minute.
2. Setting PV Input Type (Setting First at Power-on)
NOTE
The indicator displays the operating display when the power is turned on. However, if PV input type has not been set, “IN” appears. In this case, first use the key to
display the input range code to use, then press the to register it. Then, set the maximum value (RH) and minimum
value (RL) of the PV input range (for voltage input, set the maximum value (SH) and minimum value (SL) of the PV input scale).
The indicator is configured to the initial value of each param­eter at the factory before shipment. First check the initial values shown in 2. Lists of Parameters, in parameter values as necessary.
Example of Temperature Input Example of Voltage Input
-200°C 1370°C
Minimum value of
PV input range (RL)
Parameters to be set for temperature input
1. PV input type (IN): Set according to a sensor
2. Maximum value of PV input range (RH): Set the maximum value of the range to be displayed.
3. Minimum value of PV input range (RL): Set the minimum value of the range to be displayed.
The following operating procedure describes an example of setting a K-type thermocouple (-199.9°C to 500.0°C) and a measurement range of 0.0°C to 200.0°C.
1.
Instrument input range
PV input range
0°C800°C
PV input range (RH)
Display screen at power-on The parameter IN for setting the PV input type appears.
Initial Settings
4th Edition: Jan 31, 2005
Parameters User’s Manual
• Displays a PV value during operation.
• Displays a parameter symbol when you set a parameter.
• Displays an error code in red if the indicator fails. Displays the setpoint of a parameter when it is configured. If any of alarms 1 to 4 occurs, the respective alarm indicator lamp (AL1 to AL4) is lit (in orange). Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch
between the operating display and the menu for operating parameter setting display alternately. Used to change numerical values. On setting displays for various parameters, you can change parameters,
setpoint. Pressing the key decreases a numerical value, while pressing the key causes it to increase. You can hold down a key to gradually increase the speed of change.
Set the actual read-out range.
Maximum value of
PV
AL1234
SET/ENT
Displays
parameterIN.
for an easy to understand explanation of setting various param-
SET/ENT
key for more than 3 seconds.
Contents
1. Process variable (PV) display
3. Alarm indicator lamps
5. and keys
NOTE
Blinks during
change.
1. Process variable (PV) display
2. Parameter Setpoint display
3.
Alarm indicator
lamps
5. and keys
2. Parameter Setpoint display
4. SET/ENT key
Function
SET/ENT
key
PV
SET/ENT
AL1234
Parameters Users Manual
If the display is as shown on the left, press the key to show the range code for the PV input type you use. Then, register the range code setting by pressing the key.
1V 5V (input signal)
2V 4V
RL
0.0m3/h 50.0m3/h
Minimum value of
PV input scale (SL)
Parameters to be set for voltage input
1. PV input type (IN): Set according to an input signal
2. Maximum value of PV input range (RH): Set the maximum value of an input signal.
3. Minimum value of PV input range (RL): Set the minimum value of an input signal.
4. Position of PV input decimal point (SDP): Set the position of the decimal point for PV input display.
5. Maximum value of PV input scale (SH): Set the maximum value of the scale to be displayed.
6. Minimum value of PV input scale (SL): Set the minimum value of the scale to be displayed.
Instrument input range
PV input range
PV input scale
Maximum value of PV input scale (SH)
RH
Set the actual read-out range.
Press the or key to display the required
2.
setpoint. The figure below shows an example of setting a K-type thermocouple (-199.9 to 500.0°C). See the Instrument Input Range Codes.
PV
SET/ENT
AL1234
SET/ENT
and change
Press the key once to register the setpoint.
3.
SET/ENT
Press the key once to display the parameter
8.
RL (minimum value of PV input range).
SET/ENT
Displays
PV
AL1234
SET/ENT
Press the key once to display the parameter
4.
UNIT (PV input unit).
SET/ENT
PV
AL1234
SET/ENT
Press the or key to display the required
9.
setpoint. The figure below shows an example of
parameter
RL.
setting the minimum value of PV input range to
Displays
PV
AL1234
SET/ENT
Press the key once to display the parameter
5.
RH (maximum value of PV input range).
SET/ENT
parameter
UNIT.
0.0°C.
PV
AL1234
SET/ENT
Press the key once to register the setpoint.
10.
SET/ENT
Blinks during
change.
Displays
PV
AL1234
SET/ENT
SET/ENT
PV
AL1234
parameter
RH.
If the type of input is voltage, also configure the PV Input Decimal Point Position (SDP), Maximum value of PV Input Scale (SH), and Minimum value of PV Input Scale (SL) parameters that are displayed after this.
Press the or key to display the required
6.
setpoint. The figure below shows an example of setting the maximum value of PV input range to
Press the key for more than 3 seconds. This
11.
returns you to the display shown at power-on (figure below).
SET/ENT
200.0°C.
PV
AL1234
SET/ENT
Press the key once to register the setpoint.
7.
SET/ENT
Blinks during
change.
The PV display in the figure above shows the error code for input burnout ( ) if PV input wiring is
SET/ENT
PV
AL1234
Displays
PV.
not yet complete. The error code disappears when
PV
AL1234
SET/ENT
you wire the PV input terminals correctly.
Instrument Input Range Codes
Select the unit from the UNIT parameter.
Input Type
Unspecified
Instrument Input
Range Code
OFF
1
K
2
3
J4
5
T
6
B7
S8
R9
Thermocouple
N10
E11
L(DIN) 12
13
U(DIN)
14
W15
Platinel 2 16
PR20-40 17
W97Re3­W75Re25
18 30
JPt100
31
RTD
Pt100
35
36
37
Standard signal
0.4 to 2 V 40 1 to 5 V 41 0 to 2 V 50
DC voltage
0 to 10 V 51
-10 to 20 mV 0 to 100 mV
55 -10.00 to 20.00 mV 56 0.0 to 100.0 mV
* Performance in the standard condition (at 23⫾2⬚C, 5510%RH, and 50/60Hz power frequency. Note1: The accuracy is ⫾0.3⬚C of instrument range 1 digit for a temperature range from 0⬚C to 100⬚C. Note2: The accuracy is ⫾0.5⬚C of instrument range ⫾1 digit for a temperature range from -100⬚C to 200⬚C. * To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 resistor. This resistor is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Instrument
Input Range
Measurement Accuracy
Set the data item PV Input Type "IN" to the OFF option to leave the PV input type undefined.
-200 to 1370C
-300 to 2500F
-199.9 to 999.9⬚C 0 to 2300⬚F
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-199.9 to 999.9⬚C
-300 to 2300F
0.1% of instrument range 1 digit for temperatures
equal to or higher than 0
C
0.2% of instrument range 1 digit for temperatures
C
below 0
-199.9 to 400.0⬚C
-300 to 750⬚F
0.0 to 400.0⬚C
-199.9 to 750.0⬚F 0 to 1800⬚C
32 to 3300⬚F
0.15% of instrument range 1 digit for temperatures
equal to or higher than 400
C
5% of instrument range 1 digit for temperatures
below 400
C
0 to 1700⬚C
32 to 3100⬚F
0 to 1700⬚C
0.15% of instrument range 1 digit
32 to 3100⬚F
-200 to 1300⬚C
-300 to 2400⬚F
0.1% of instrument range 1 digit0.25% of instrument range 1 digit for temperatures
C
below 0
-199.9 to 999.9⬚C
-300 to 1800⬚F
-199.9 to 900.0⬚C
-300 to 1300⬚F
-199.9 to 400.0⬚C
-300 to 750⬚F
0.1% of instrument range 1 digit for temperatures
equal to or higher than 0
C
0.2% of instrument range 1 digit for temperatures
C
below 0
0.0 to 400.0⬚C
-199.9 to 750.0⬚F 0 to 2300⬚C
32 to 4200⬚F
0 to 1390⬚C
32 to 2500⬚F
0 to 1900⬚C
32 to 3400⬚F
0 to 2000⬚C
32 to 3600⬚F
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
-199.9 to 300.0⬚F
0.2% of instrument range 1 digit
0.1% of instrument range 1 digit0.5% of instrument range 1 digit for temperatures
equal to or higher than 800
C
No guarantee of accuracy for temperatures below 800
0.2% of instrument range 1 digit0.1% of instrument range 1 digit (Note1) (Note2)
0.2% of instrument range 1 digit (Note1)
-199.9 to 850.0⬚C
-300 to 1560⬚F
-199.9 to 500.0⬚C
0.1% of instrument range 1 digit (Note1) (Note2)
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
-199.9 to 300.0⬚F
0.2% of instrument range 1 digit (Note1)
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.1% of instrument range 1 digit (Note) The read-out range can be scaled between -1999 and
9999.
4. Changing Alarm Type
Alarm output terminals Factory-set defaults
6 7
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers )......PV low limit alarm
-
5 7
-
4 7
-
---
2 31
The indicator may automatically initialize the registered operating parameter setpoints if any change is made to the data item PV Input T ype (IN), Maximum Value of PV Input Range (RH), Minimum Value of PV Input Range (RL), PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH) or Minimum Value of PV Input Scale (SL). After a change has been made to any of these data items, be sure to verify the registered operating parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a required value.
The following operating procedure describes an example of changing alarm-1 (factory-set value: PV high limit alarm) to PV low limit alarm. When you have changed alarm type, the alarm setpoint will be initial­ized; set the alarm setpoint again.
3. Changing PV Input Type
The following operating procedure describes an example of changing the setting of K-type thermocouple (-199.9 to 500.0C) to RTD Pt100 (-199.9 to 500.0C) and a measurement range of 0.0 to 200.0C.
Bring the operating display into view (display
1.
appears at power on).
PV
AL1234
SET/ENT
Press the key for more than 3 seconds to
2.
call up the menu OP.PA.
SET/ENT
Displays
PV.
Displays
PV
AL1234
SET/ENT
Press the key once to display the menu
3.
STUP.
PV
AL1234
SET/ENT
Press the key once to display the parameter
4.
PWD.
SET/ENT
menu OP.PA.
Displays menu
STUP.
Displays
PV
AL1234
SET/ENT
Press the key once to display the menu
5.
FUNC.
Press the key once to display the menu I/O.
6.
Press the key once to display the parameter
7.
IN (PV input type).
SET/ENT
PV
AL1234
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
parameter
PWD
Displays
“FUNC”.
menu
Displays
menu “I/O”.
Displays
PV
AL1234
SET/ENT
Press the or key to display the required
8.
setpoint. The figure below shows an example of
parameter IN.
changing to RTD Pt100 (-199.9 to 500.0°C).
PV
AL1234
SET/ENT
Press the key once to register the setpoint.
9.
C
SET/ENT
PV
AL1234
SET/ENT
Blinks during
change.
10.
11.
12.
13.
.
14.
15.
16.
17.
PV input terminal Thermocouple/mV/V input
..............................
RTD input .................................................. - -
Press the key once to display the parameter
SET/ENT
UNIT (PV input unit).
Displays
PV
AL1234
SET/ENT
Press the key once to display the parameter
SET/ENT
parameter
UNIT”.
RH (maximum value of PV input range).
Displays
PV
AL1234
SET/ENT
parameter
RH.
Press the or key to display the required setpoint. The figure below shows an example of setting the maximum value of PV input range to
200.0°C.
PV
AL1234
Blinks during
SET/ENT
Press the key once to register the setpoint.
Press the key once to display the parameter
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
change.
RL (minimum value of PV input range).
Displays
PV
AL1 2 3 4
SET/ENT
parameter
RL.
Press the or key to display the required setpoint. The figure below shows an example of setting the minimum value of PV input range to
0.0°C.
PV
AL1234
Blinks during
SET/ENT
Press the key once to register the setpoint.
Press the key for more than 3 seconds.
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
change.
This returns you to the display shown at power-on (figure below).
PV
AL1234
SET/ENT
If the type of input is voltage, also configure the
*
PV Input Decimal Point Position (SDP), Maximum
Displays
PV.
value of PV Input Scale (SH), and Minimum value of PV Input Scale (SL) parameters that are displayed after patameter RL.
1312
-
131211
5. Setting Hysteresis in Alarm Setpoint
The following operating procedure describes an example of setting a 5.0°C hysteresis level in the alarm setpoint.
Bring the operating display into view (appears at
1.
power-on).
Displays
PV
AL1234
SET/ENT
Press the key for more than 3 seconds to
2.
call up the menu OP.PA”.
Press the key once to display the menu
3.
STUP.
Press the key once to display the parameter
4.
PWD.
Press the key once to display the menu
5.
FUNC.
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
PV
AL1234
PV
AL1234
PV
AL1234
PV
AL1234
Displays menu
Display menu
Displays menu
PV.
OP.PA”.
STUP”.
Displays
parameter
PWD”.
FUNC”.
Press the key several times to display the
6.
parameter HY1 (alarm-1 hysteresis).
Press the or key to display the required
7.
setpoint.
Press the key once to register the setpoint.
8.
You can take the same steps for alarm-2 hysteresis (HY2), alarm-3 hysteresis (HY3), and alarm-4 hysteresis (HY4) that are displayed after this.
Press the key for more than 3 seconds.
9.
This returns you to the display shown at power-on (figure below).
SET/ENT
SET/ENT
SET/ENTSET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
Displays
PV
AL1 2 3 4
PV
AL1 2 3 4
parameter
HY1.
Blinks during
change.
PV
AL1 2 3 4
PV
AL1 2 3 4
Displays
PV.
IM 05F01D02-02E (1)
Page 4
2. Troubleshooting
User’s Manual
Models UM350 / UM330 Digital Indicator with Alarms User’s Manual
IM 05F01D02-02E
This manual describes key entries for operating the indicator. If you cannot remember how to carry out an operation during setting, press the power-on.
SET/ENT
1. Setting Alarm Setpoints
2. Troubleshooting
NOTE
Do not use the instrument generating strong magnetic field such as radio equipment and the like near the indicator . This may cause the fluctuation of the PV value.
1. Setting Alarm Setpoints
The following operating procedure describes an example of setting a value of 160.0 in the alarm-1 setpoint parameter. Before setting the alarm setpoint, check the alarm type. To change the alarm type, see “4. Changing Alarm Type” in
Manual
.
Bring the operating display into view (display
1.
appears at power on).
Press the key for more than 3 seconds to call
2.
up the menu “OP.PA”.
Press the key once to display the parameter
3.
“A1”.
SET/ENT
SET/ENT
Operations
4th Edition: Jan 31, 2005
key for more than 3 seconds. This brings you to the display (operating display) that appears at
Contents
SET/ENT
SET/ENT
Alarm output terminals Factory-set defaults
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Initial Settings User's
4.
PV
AL1234
Displays PV.
5.
PV
AL1234
Displays menu
“OP.PA”.
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers ).......PV low limit alarm
Press the or key to display the required setpoint.
PV
SET/ENT
Press the key once to register the setpoint.
SET/ENT
PV
SET/ENT
You can take the same steps for alarm-2 setpoint (A2), alarm-3 setpoint (A3), and alarm-4 setpoint (A4) that are displayed after this.
Press the key for more than 3 seconds.
6.
This returns you to the display shown at power-on
SET/ENT
(figure below).
Displays
PV
AL1234
parameter
“A1”.
PV
6 7 5 7 4 7 1
AL1234
AL1234
AL1234
-
-
-
2
--
3
Blinks during
change.
Displays PV.
Troubleshooting Flow
If the operating display does not appear after turning on the indicator's power, try to solve the problem by following the procedure below. If the problem seems to be complex, contact the vendor from which you purchased the instrument.
Is the instrument
defective?
Yes
Totally
inoperable?
Yes
Check wiring on the power supply terminals.
Check the supply voltage.
No
Normal?
No
Yes
Ask the vendor for repair.
No
Correct
errors.
Correct?
Yes
Find the cause.
Is key
operation
faulty?
Yes
Check the key lock setting.
Is
No
key lock
enabled?
Yes
Disable
key lock.
No
Is display
Turn off power, and then turn it on again.
faulty?
Yes
No
Is I/O
signal faulty?
Check the instruments I/O specifications.
Check the specifications of I/O counterpart for wrong polarity.
No
Yes
No communication
capability.
Is
communication
link faulty?
Yes
Check the instrument's suffix code.
No
Does the code
include a communication
option?
Check the communication-related parameters.
Check communication wiring.
Check the specifications of communication counterpart.
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
Errors at Power On
The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.
Error indication
(on PV display unit)
(E000) (E001) (E002)
PV decimal point blinks.
(E400)
Description
of error Faulty RAM Faulty ROM System data error
Faulty calibration value
Parameter error
PV
None
0% Normal action
(out of accuracy)
0%
Control
output
0% or less or OFF
Normal action (out of accuracy)
Preset value
Alarm output
OFF
Normal action (out of accuracy)
OFF 0%
Retransmission
output
Communi-
cation
0% or less Stopped
0% Normal action
(out of accuracy)
Normal action
Remedy
Faulty Contact us for repair.
Check and set the parameters, as they have been set to the limited values.
Possible Errors during Operation
The following shows possible errors occurring during operations.
Error indication (on PV display unit)
Displays RJC and PV alternately
PV value blinks.
Description of error
RJC error
EEPROM error
PV
Measured with RJC=OFF
Normal action
Control output
Normal action
Normal action
Alarm output
Normal action
Normal action
Retransmis­sion output
Normal action
Normal action
Commu-
nication
Normal action
Normal action
Remedy
Faulty Contact us for repair.
Faulty Contact us for repair.
SET/ENT
SET/ENT
(E300)
(B.OUT)
A/DC error
PV burnout error
105
%
Dependent on the BSL parameter Up-scale: 105%
Preset value
Preset value
Normal action
Normal action
Normal action
Normal action
Normal action
Normal action
Check wires and sensor.
Down-scale: -5%
(OVER) or
(-OVER)
SP decimal pont blinks (on setpoint display unit).
All indications off Faulty if power off/on does
Excessive PV Out of -5 to 105%
Faulty communi­cation line
Runaway (due to defective power or
-5% or 105%
Normal action
None
Normal action
Normal action
0% or less or OFF
Normal action
Normal action
OFF
Normal action
Normal action
0% or less
Normal action
Normal action
Stopped
Check process.
Check wires and communication parameters, and make resetting. Recovery at normal receipt
not reset start the unit. Contact us for repair.
noise)
All indications off Check for abnormal power.
Power off
None
0
%
OFF
0
%
Stopped
If a Power Failure Occurs during Operation
Momentary power failures shorter than 20 ms
The indicator is not affected at all and continues normal operation.
Momentary power failures of 20 ms or longer
• The alarm function of the indicator continues to work normally. (Alarms with the stand-by feature temporarily return to their stand-by state, however.)
• Setting parameters that have already been configured retain their settings.
IM 05F01D02-02E (2)
Page 5
User’s Manual
Models UM350 / UM330 Digital Indicator with Alarms User’s Manual
IM 05F01D02-03E
This manual contains a parameter map as a guideline for setting parameters, and lists of parameters for recording User Settings.
1. Basic Key Operation Sequence and Parameter Map
2. Lists of Parameters
1. Basic Key Operation Sequence and Parameter Map
Parameters
4th Edition: Jan 31, 2005
Contents
?
If you become unsure of key operation during parameter
setting, hold down the key for more than
3 seconds. This returns you to the display at
power-on (i.e., operating display).
SET/ENT
Basic Key Operation Sequence
1. Setting display can be switched (moved) using the key.
2. A numerical value is changed by (1) Using the or key to change a displayed value (decimal point blinking) and (2) Pressing the key to register it.
3. Pressing the key on an operating display (for more than 3 seconds) brings you to the
SET/ENT
SET/ENT
operating parameter setting display.
4. Pressing the key on the operating parameter setting display (for more than 3 seconds)
SET/ENT
returns you to the operating display.
5. Pressing the key on the setup parameter setting display (for more than 3 seconds)
SET/ENT
returns you to the operating display. You cannot return to the operating parameter setting display from the setup parameter setting display.
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
key
Press this key for more
than 3 seconds to
move to the operating
parameter setting
display.
SET/ENT
key
SET/ENT
key
Power on
Display? IN = OFF
Operating Display
Displays PV.
Menu
Operating Parameter Setting Display
Alarm-1 setpoint
Alarm-2 setpoint
Alarm-3 setpoint
Alarm-4 setpoint
PV peak value
PV bottom value
PV input filter
PV input bias
Displayed only for UM350-1, UM350-2, UM330-1, UM330-2
Settings herein are described in “
Determine PV input type first.
(Setting First at Power-on)
Display example
PV
AL1 2 3 4
YesNo
SET/ENT
PV
AL1 2 3 4
SET/ENT
Blinks during
change.
Use the or key to set a numerical value. See
Instrument Input Range Codes
in
Initial Settings User’s Manual
.
2. Setting PV Input Type
” in
Initial Settings User’s Manual
Display example
PV
AL1 2 3 4
SET/ENT
SET/ENT
Press the key to register
2.1.
the value.
.
A
After PV input type (IN), input parameters such as PV input unit (UNIT), maximum value of PV input range (RH), and minimum value of PV input range (RL) will be displayed.
C
B C
SET/ENT
Press this key for
more than 3 seconds
to move to the
operating display.
key
NOTE
Changing the registered value of a setup parameter may cause the registered value of an operating pa­rameter to be initialized automatically. Thus, when you have changed a setup parameter, always check that the registered value of the operating parameter is appropriate. If it is initialized to default, reset it to the required value.
Displayed first after power on.
A
Setup Parameter Setting Display
SET/ENT
key
Press this key for
more than 3 seconds
to move to the
operating
display.
or key
To switch the parameter display, press the key.
SET/ENT
SET/ENT
SET/ENT
B
Menu
key
Password input
(No password is required when PWD = 0.)
key
Description of Operating Parameter Menu Display
Displays the
operating
parameter menu
symbol “OP.PA.”
PV
AL1234
SET/ENT
Description of Operating Parameter Setting Display
Displays a
parameter
symbol.
PV
AL1234
SET/ENT
Nothing is displayed.
Displays a setpoint.
Menu
Alarm/Communication
related
SET/ENT
or key
key
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
Protocol selection
Baud rate
Parity
Stop bit
Data length
Address
Displayed only for UM350-1, UM350-2, UM330-1, UM330-2.
Displayed only for UM350-1, UM350-2, UM330-1, UM330-2.
Displayed only for UM350-1, UM350-2, UM330-1, UM330-2.
Displayed only for indicators with communication functions
Input related
SET/ENT
key
PV input type
(PV INPUT terminals)
PV input unit
Maximum value of PV input range
Minimum value of PV input range PV input decimal point position
(displayed at voltage input)
Maximum value of PV input scale
(displayed at voltage input)
Minimum value of PV input scale
(displayed at voltage input)
Presence/absence of PV input
reference junction compensation
Selection of
PV input burnout action
Retransmission output type
Maximum value of
retransmission output scale
Minimum value of
retransmission output scale
DI function selection
SELECT display-1 registration
SELECT display-2 registration
SELECT display-3 registration
SELECT display-4 registration
Key lock
Description of Setup Parameter Menu Display
Displays a menu, such as FUNC or I/O.
PV
AL1234
SET/ENT
Nothing is displayed.
Description of Setup Parameter Setting Display
Displays a parameter.
PV
AL1 2 3 4
SET/ENT
Displays a setpoint.
SET/ENT
Minimum response time
key
This parameter is not to be set.
SET/ENT
Password setting
key
IM 05F01D02-03E (1)
Page 6
2. Lists of Parameters
* Parameters relating to PV should all be set in real numbers.
For example, use temperature values to define alarm setpoints for temperature input.
Operating Parameters
Parameter
Symbol
(A1)
(A2)
(A3)
(A4)
(PEAK)
(BOTM)
(FL)
(BS)
Name of Parameter Setting Range and Description Initial Value User setting
Alarm 1-setpoint
PV alarm: -100.0 to 100.0% of PV input range PV high limit
Alarm 2-setpoint
Alarm 3-setpoint
Alarm 4-setpoint
PV peak value
Displays the maximum value of PV input during operation. This parameter is not to be set.
PV bottom value
Displays the minimum value of PV input during operation. This parameter is not to be set.
PV input filter OFF, 1 to 120 second
Used when the PV input fluctuates.
PV input bias -100.0% to 100.0% of PV input range span
Used to correct the PV input value.
Setup Parameters
Alarm/Communication-related Parameters
Parameter
Symbol
(AL1)
(AL2)
(AL3)
(AL4)
(HY1)
(HY2)
(HY3)
(HY4)
(DY1)
(DY2)
(DY3)
(DY4)
(P.SL)
(BPS)
(PRI)
(STP)
(DLN)
(ADR)
(RP.T)
(TEST)
Name of Parameter Setting Range and Description User setting
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
Protocol selection
OFF 1: PV high limit (energized, no stand-by action) 2: PV low limit (energized, no stand-by action) 9: PV high limit (de-energized, no stand-by action) 10: PV low limit (de-energized, no stand-by action) 11: PV high limit (energized, stand-by action) 12: PV low limit (energized, stand-by action) 19: PV high limit (de-energized, stand-by action) 20: PV low limit (de-energized, stand-by action) 21: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
22: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
See List of Alarm Types on the right side of this manual for details on how these Alarm Type parameters behave.
0.0 to 100.0% of PV input range span Hysteresis can be set in the alarm setpoint.
Setting hysteresis prevents relays from chattering.
Hysteresis setting for PV high limit alarm
Output
An alarm is output when the delay timer expires after the alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm­1 type AL1 is 1, 2, 9, 10, 11, 12, 19, and 20)
Alarm setpoint
Alarm output
0.00 to 99.59 (min, sec.) (enabled when alarm­2 type AL2” is
0.00 to 99.59 (min, sec.) (enabled when alarm­3 type AL3” is
0.00 to 99.59 (min, sec.) (enabled when alarm­4 type AL4” is
0: PC link communication 1: PC link communication (with checksum) 2: Ladder communication 7: MODBUS (ASCII) 8: MODBUS (RTU)
Point of on-off action
(Alarm setpoint)
On
Off
Delay timer
off
1, 2, 9, 10, 11, 12, 19, and 20
1, 2, 9, 10, 11, 12, 19, and 20
1, 2, 9, 10, 11, 12, 19, and 20
Baud rate 0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
Parity 0: None
1: Even 2: Odd
Stop bit 1, 2
Data length
Address 1 to 99
Minimum response time
7, 8 Fixed at 7, when the P.SL parameter is set to MODBUS (ASCII). Fixed at 8, when the P.SL parameter is set to MODBUS (RTU) or Ladder Communication.
However, the maximum number of stations connectable is 31.
0 to 10 ( 10 ms)
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu. Caution: Do not change the setpoint of the TEST parameter, otherwise the indicator will be disabled.
Hysteresis
PV value
PV
Delay timer
Hysteresis
Time
* The User Setting column in the table below is provided for the customer to record setpoints.
List of Alarm Types
The table below shows the alarm types and alarm actions.
Input-/Output-related Parameters
Parameter
Symbol
alarm:
(IN)
100.0% of PV input range PV low limit
(UNIT)
alarm:
0.0% of PV input range
(RH)
(RL)
(SDP)
OFF
0.0% of PV input range
(SH)
span
(SL)
(BSL)
(RJC)
Initial Value
1
2
1
2
(RET)
(RTH)
(RTL)
(DIS)
(C.S1)
(C.S2)
(C.S3)
(C.S4)
0.5% of PV input range span
0.00
on
(LOCK)
(PWD)
Name of Parameter Setting Range and Description Initial Value User Setting
PV input type (PV INPUT terminals)
131211
- - terminals PV input unit °C: degree Celsius
Max. value of PV input range
Min. value of PV input range
PV input decimal point position (displayed at voltage input)
Max. value of PV input scale (displayed at voltage input)
Min. value of PV input scale (displayed at voltage input)
Selection of PV input burnout action
Presence/absence of PV input reference junction compensation
Retransmission output type
Max. value of retransmission output scale
Min. value of retransmission output scale
DI function selection 1
SELECT display-1 registration
SELECT display-2 registration
SELECT display-3 registration
SELECT display-4 registration
Key lock
Password setting 0: Password not set
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56 See Instrument Input Range Codes in
Settings
Users Manual .
Initial
°F: Fahrenheit Set the PV input range, however RL < RH
-Temperature input Set the range of temperature that is actually indicated.
- Voltage input Set the range of a voltage signal that is applied. The scale across which the voltage signal is actually indicated should be set using the parameters Maximum Value of PV Input Scale (SH) and Minimum Value of PV Input Scale (SL). 0 to 3 Set the position of the decimal point of voltage­mode PV input. 0: No decimal place 1: One decimal place 2, 3: Two, three decimal places
-1999 to 9999, however SL < SH Set the read-out scale of voltage-mode PV input.
OFF 1: Up scale 2: Down scale
OFF, ON ON
OFF: Does not work. 1: PV 4: Loop power supply for sensor (15 V)
RET=1: RTL + 1 digit to 100.0% of PV input range
RET=1: 0.0% of PV input range to RTH - 1 digit
OFF: The external contact input is disabled. 1: Resets the values of the PEAK and BOTM
operating parameters to an off-to-on transition of the DI1 input.
OFF, 201 to 1015 For example, registering 231 for C.S1 allows you to
change alarm-1 setpoint in operating display. Numbers for registering alarm SP parameter for
operating display: Alarm-1 setpoint: 231 Alarm-2 setpoint: 232 Alarm-3 setpoint: 233 Alarm-4 setpoint: 234
OFF: No key lock 1: Change to any parameter prohibited
Prohibits any operating parameter or setup parameter from being changed. The setpoint of the LOCK parameter itself can be changed, however.
2: Change to and display of operating parameters
prohibited Turns off the display for setting operating parameters, thus prohibiting any change to the parameter settings. (Press the SET/ENT key for more than 3 seconds to show the password check display.)
1 to 9999
OFF
°C
Max. value of instrument input range
Min. value of instrument input range
1
100.0
0.0
1
1
100.0% of PV input range
0.0% of PV input range
OFF
OFF
0
In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with stand-by actions.
Alarm type codeAlarm type code
Contact
Contact
closes
opens
if alarm
if alarm
occurs
occurs
9
19
10
20
2221
Low limit of alarm setpoint
Closed
(unlit)
Open (lit)
Alarm setpoint
Alarm action
PV
Hysteresis
Hysteresis
Open (lit)
Alarm setpoint
PV
Closed
(unlit)
Alarm type
No alarm OFF
PV high limit
PV low limit
Fault diagnosis output (Note1) FAIL output (Note2)
Open/close shows status of relay contact, and “lit” and “unlit” shows status of lamp
Open (unlit)
Closed (lit)
Alarm action
Hysteresis
Alarm setpoint
PV
Hysteresis
Alarm setpoint PV
Closed (lit)
Open (unlit)
Contact
closes
if alarm
occurs
1
11
2
12
Contact if alarm
opens occurs
Alarm type
De-energized
on PV high limit
De-energized
on PV low limit
Open/close shows status of relay contact, and “lit” and unlit shows status of lamp
Note1: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
Note2: FAIL output
Turns off in case of program failure, R OM f ailure, RAM failure, or power failure. This output is on during normal operation. If it turns off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
Stand-by Action
It is effective in the following cases where;
C
Treated
as normal
Normal Abnormal
The alarm
output turns on.
- the power is turned on
- the alarm type is changed The alarm output does not
turn on in this region even if the PV value is below the low limit of the alarm setpoint.
Power-on
Time
Behavior of the PV High-limit Alarm Parameter (Alarm Type Code: 1)
PV value
Alarm hysteresis
Alarm
setpoint
Alarm
OffOff On
contact output
Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to change settings easily. A maximum of four displays can be registered.
Useful
operating display
SET/ENT
key
SET/ENT
key
(SELECT display)
PV
AL1234
SET/ENT
Alarm-1 setting
display (example)
Setting method: Set the parameter numbers (D register numbers) you wish to register for setup parameters C.S1 to C.S4.
Ordinary operating
displays (example)
PV
AL1 2 3 4
SET/ENT
PV display
Numbers for Registration with SELECT Display
)
)
)
0
4
1
1
8
1
0
Operating Parameter Registration Number Alarm-1 setpoint (A1) Alarm-2 setpoint (A2) Alarm-3 setpoint (A3) Alarm-4 setpoint (A4) Bias (BS) 243 Filter (FL) 244
231 232 233 234
Setup Parameter Registration Number Alarm-1 hysteresis Alarm-2 hysteresis Alarm-3 hysteresis Alarm-4 hysteresis
919 920 921 922
IM 05F01D02-03E (2)
Loading...