Yokogawa UM331 Operating Manual

User’s Manual
Models UM351/UM331 Digital Indicator with Alarms User’s Manual
IM 05F01D12-41E
IM 05F01D12-41E
4th Edition
<Toc> <Rev>

Introduction

Thank you for purchasing the UM351/UM331 digital indicator with alarms.
How to Use the Manuals
Purpose Title Description
1. Installation
2.
Initial Settings
3. Operations
4.1 Troubleshooting
5. Parameters
Setup Describes the tasks (installation, wiring, and others) required
Basic operation
Operating procedures and troubleshooting
Brief operation and setpoint recording
Regarding This Users Manual
(1) This manual should be provided to the end user. Keep an extra copy or copies of the
manual in a safe place.
to make the indicator ready for operations. Describes examples of setting PV input types, and alarm
types. Making settings described herein allows you to carry out basic monitoring.
Describes examples of setting alarm setpoints, as well as key operation necessary to run the indicator.
Contains the parameter map used as a guideline for setting parameters and lists of parameters for recording user settings.
i
(2) Read this manual carefully to gain a thorough understanding of how to operate this
product before starting operation.
(3) This manual describes the functions of this product. Yokogawa Electric Corporation
(hereinafter simply referred to as Yokogawa) does not guarantee the application of these functions for any particular purpose.
(4) Under absolutely no circumstances may the contents of this manual, in part or in
whole, be transcribed or copied without permission. (5) The contents of this manual are subject to change without prior notice. (6) Every effort has been made to ensure that the details of this manual are accurate.
However, should any errors be found or important information be omitted, please
contact your nearest Yokogawa representative or our sales office.
Media No. IM 05F01D12-41E (CD) 4th Edition : May 2006 (YK) All Rights Reserved Copyright © 2003, Yokogawa Electric Corporation
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <Rev>
Safety Precautions
The following symbol is indicated on the indicator to ensure safe use.
This symbol on the indicator indicates that the operator must refer to an explanation in the user’s manual in order to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator should exercise special care to avoid
CAUTION
electric shock or other dangers that may result in injury or loss of life.
The following symbols are used in the hardcopy user’s manuals and in the user’s manual supplied on the CD-ROM.
NOTE
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
ii
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or features of the indicator.
Force Majeure
(1) Yokogawa assumes no liability to any party for any loss or damage, direct or indirect,
caused by the use or any unpredictable defect of the product. (2) No portion of the software supplied by Yokogawa may be transferred, exchanged,
leased or sublet for use by any third party without the prior permission of Yokogawa. (3) Be sure to use the spare parts approved by Yokogawa when replacing parts or
consumables. (4) Use this software with one specified computer only. You must purchase another copy
of the software for use on each additional computer. (5) Copying this software for purposes other than backup is strictly prohibited. (6) Store the floppy disk(s) (original medium or media) containing this software in a
secure place.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <Rev>
Regarding Protection, Safety, and Prohibition Against Unauthorized Modification
(1) In order to protect the product and the system controlled by it against damage and
ensure its safe use, make certain that all of the instructions and precautions relating to safety contained in this document are strictly adhered to. Yokogawa does not guaran-
tee safety if products are not handled according to these instructions. (2) Modification of the product is strictly prohibited. (3) Reverse engineering such as the disassembly or decompilation of software is strictly
prohibited.
iii
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Int> <Rev>
Models UM351/UM331 Digital Indicator with Alarms Users Manual

CONTENTS

Introduction........................................................................................................... i
1. Installation .............................................................................................. 1-1
1.1 Model and Suffix Codes.................................................................................. 1-1
1.2 How to Install................................................................................................... 1-2
1.3 How to Connect Wires .................................................................................... 1-5
1.4 Hardware Specifications ................................................................................ 1-7
1.5 Terminal Wiring Diagrams ............................................................................ 1-12
2. Initial Settings ......................................................................................... 2-1
Toc-i
IM 05F01D12-41E 4th Edition
2.1 Names and Functions of Front Panel Parts................................................... 2-2
2.2 Setting PV Input Type (Setting First at Power-on)......................................... 2-3
2.3 Changing PV Input Type ................................................................................. 2-7
2.4 Changing Alarm Type ..................................................................................... 2-9
2.5 Setting Hysteresis in Alarm Setpoint ............................................................2-11
2.6
2.7 Setting the High Limit and Low limit for PV Color change ......................... 2-13
Setting the PV display color changing function Active Color PV Display”...
2-12
3. Operations .............................................................................................. 3-1
3.1 Monitoring-purpose Operating Display Available during Operation ........... 3-1
3.2 Setting Alarm Setpoints .................................................................................. 3-2
4. Troubleshooting and Maintenance ........................................................ 4-1
4.1 Troubleshooting.............................................................................................. 4-1
4.2 Maintenance .................................................................................................... 4-4
4.2.1 Cleaning ........................................................................................... 4-4
4.2.2 Replacing Brackets ........................................................................... 4-4
4.2.3 Attaching Terminal Cover .................................................................. 4-4
4.2.4 Replacing Parts with a Limited Service Life ....................................... 4-6
5. Parameters.............................................................................................. 5-1
5.1 Parameter Map ................................................................................................ 5-1
5.2 Lists of Parameters ......................................................................................... 5-2
Revision Information ............................................................................................ i
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>

1. Installation

This chapter describes installation, wiring, and other tasks required to make the indicator ready for operation.

1.1 Model and Suffix Codes

Before using the indicator, check that the model and suffix codes match your order.
Model Suffix Code Description UM351 UM331
Type
Optional functions
-0 Standard type with three alarms
-3 Standard type with three alarms (with 24 V DC loop power supply)
Check that the following items are provided:
Digital indicator with alarms (of ordered model) .................... 1
Digital indicator with Alarms (provided with retransmission output and 15 V DC loop power supply as standard)
0 None 1 With communication and additional alarm-4 2 With additional alarm-4
1-1
Brackets (mounting hardware) ............................................. 1 pair
Unit label.............................................................................. 1
Users Manuals.................................................................... 3 (A2 size)
Users Manuals
Setting/Explanation of Active Color PV Display ................... 1 (A3 size)
Users Manual (Reference) (CD-ROM version)
(only for indicators with optional communication functions)... 1
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>

1.2 How to Install

NOTE
To install the indicator, select a location where:
1. no one may accidentally touch the terminals,
2. mechanical vibrations are minimal,
3. corrosive gas is minimal,
150 mm
1-2
4. temperature can be maintained at about 23C and the fluctuation is minimal,
150 mm150 mm
150 mm
5. no direct radiant heat is present,
6. no magnetic disturbances are caused,
7. no wind blows against the terminal board (reference junction compensation element),
8. no water is splashed,
9. no flammable materials are around,
Never place the indicator directly on flammable items or equipment. If the indicator has to be installed close to flammable items or equipment, be sure to pro-
vide shielding panels all around the indicator, at least 150 mm away from every side; the panels should be made of either 1.43 mm-thick metal-plated steel plates or 1.6 mm-thick uncoated steel plates.
NOTE
Never touch the opening at the bottom of the case. It is to be used in the factory at ship­ping.
Installation Position
Install the indicator at an angle within 30 from horizontal with the front panel facing up­ward. Do not install it facing downward. The position of right and left sides should be hori­zontal.
Front panel
of indicator
30
Must not exceed 30
Rear of indicator
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
External Dimensions and Panel Cutout Dimensions
1-3
UM351
(53)
+0.8
92
0
96
11
96
100
1 to 10 mm (Panel thickness)
Large bracket
112
91.8
Small bracket
General installation Side-by-side close installation
+0.8
0
145 min.
[(N-1)96+92]117 min.
0
+0.8
92
"N" stands for the number of indicators to be installed. However, the measured value applies if N 5.
Unit: mm
UM331
45
(25)
+0.6
+0.8
92
0
48
General installation
0
92
+0.8
0
(25)
96
145 min.
Small bracket
(53)
10011
70 min.
112
91.8
Front of indicator
Unit: mm
Small bracket
1 to 10 mm (Panel thickness)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
How to Install
Turn off the power to the indicator before installing it on the panel because there is a possi­bility of electric shock.
CAUTION
After opening the mounting hole on the panel, follow the procedures below to install the indicator:
1. Insert the indicator into the opening from the front of the panel so that the terminal board on the rear is at the far side.
2. Set the brackets in place on the top and bottom of the indicator as shown in the figure below, then tighten the screws of the brackets. Take care not to overtighten them.
1-4
Panel
Direction to insert the indicator
Insert the
indicator into the opening at the front of the panel.
Note: Right and left mounting for UM331.
Small bracket
(bottom mounting hardware)
Large bracket
(top mounting hardware)
Terminal board
Insert a screwdriver into the brackets to tighten the screws.
Recommended tightening torque :0.4N m
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>

1.3 How to Connect Wires

1) Before carrying out wiring, turn off the power to the indicator and check that the cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
CAUTION
2) Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.
NOTE
1) Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC2205-00U from TDK) on the secondary side. As a countermeasures against noise, do not place the primary and secondary power cables close to each other.
2) For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires. The cables to be used for wiring, terminal specifications, and recommended parts are as shown below.
1-5
3) Alarm output relays have a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off a load.
4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
5) When there is possibility of being struck by external lightening surge, use the arrester to protect the instrument.
For DC Relay Wiring For AC Relay Wiring
UM351/UM331
Relay
UMs contact
(Use one with a relay coil
rating less than the UMs
Relay
contact rating.)
External DC power supply
R
Diode (Mount it directly to the relay coil terminal (socket).)
UM351/UM331
UM’s contact
(Use one with a relay coil
rating less than the UMs
contact rating.)
External AC power supply
R
Relay
CR filter (Mount it directly to the relay coil terminal (socket).)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
Cable Specifications and Recommended Cables
Purpose Name and Manufacturer
Power supply, grounding, relay contact outputs
Thermocouple Shielded compensating lead wires, JIS C 1610, X- - -
RTD Shielded wires (three conductors), UL2482 (Hitachi Cable) Other signals Shielded wires
600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm2
(See Yokogawa Electric's GS 6B1U1-E.)
Recommended Terminal Lugs
1-6
Applicable wire size Tightening torque
0.3 to 1.65 mm
7 mm or less
2
3.7mm
or
7 mm or less
Terminal Covers (Optional parts)
Target Model Part Number Sales Unit UM351 T9115YD 1 UM331 T9115YE 1
0.8 N·m or less
3.7mm
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>

1.4 Hardware Specifications

PV Input Signals
Number of inputs: 1 (terminals 11-12-13)
Input type: Universal input system. The input type can be selected with the software.
Sampling period: 250 ms
Burnout detection: Functions at TC, RTD, standard signal (0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified. For standard signal, burnout is determined to have occurred if it is 0.1 V or less.
Input bias current: 0.05 A (for TC or RTD b-terminal)
Measurement current (RTD): About 0.13 mA
Input resistance: 1 M or more for thermocouple or mV input
About 1 M for DC voltage input
Allowable signal source resistance: 250  or less for thermocouple or mV input Effects of signal source resistance: 0.1 V/ or less 2 k or less for DC voltage input Effects of signal source resistance: About 0.01%/100 V
1-7
Allowable wiring resistance: for RTD input Maximum 150 /wire: Conductor resistance between three wires should be equal However, 10 /wire for a maximum range of -150.0 to 150.0C. Wire resistance effect: 0.1C/10 
Allowable input voltage: 10 V DC for thermocouple, mV, or RTD input20 V DC for DC voltage input
Noise rejection ratio: 40 dB (50/60 Hz) or more in normal mode 120 dB (50/60 Hz) or more in common mode
Reference junction compensation error: 1.0C (15 to 35C)1.5C (0 to 15C, 35 to 50C)
Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD
Loop Power Supply
Power is supplied to a two-wire transmitter. (15 V DC: terminals A resistor (10 to 250 ) connected between the indicator and transmitter converts a current signal into a voltage signal, which is then read via the PV input terminal. Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided with a protection circuit against a field short-circuit); 21.6 to 28.0 V DC, max. 30 mA (only for models with 24 V DC loop power supply)
16-17
; 24 V DC: terminals 21-22)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
Retransmission Output
Outputs the PV value. Either the retransmission output or the loop power supply can be used with terminals
16-17
.
1-8
Number of outputs: 1 (terminals
16-17
)
Output signal: 4-20 mA DC
Load resistance: 600 or less
Output accuracy: 0.3% of span under standard operating conditions (232C,
5510% RH, power frequency of 50/60 Hz)
Contact Inputs
Purpose: Resetting of PV peak and bottom values
Number of inputs: 1
Input type: Non-voltage contact or transistor open collector input
Input contact rating: 12 V DC, 10 mA or more
On/off determination: For non-voltage contact input, contact resistance of 1 k or less
is determined as on and contact resistance of 20 k or more as off. For transistor open collector input, input voltage of 2 V or less is determined as on and leakage current must not exceed 100 A when off.
Minimum status detection hold time: About 1 second
Contact Outputs
Purpose: Alarm output, FAIL output, and others
Number of outputs: 4 (Max).
Relay contact rating for Alarm 1 to 3: 240 V AC, 1 A, or 30 V DC, 1 A; 1a
Relay contact rating for Alarm 4: 250 V AC, 3 A, or 30 V DC, 3 A (resistance load)
3 terminals (NC, NO, Common); 1c, (FAIL output : 1b)
Display Specifications
PV display: 4-digit, 7-segment red LED display, character height of 20 mm (for both UM351 and UM331)
Setpoint display: 4-digit, 7-segment, red LEDs, character height of 9.3 mm (for both UM351 and UM331)
Status indicating lamps: LEDs
Safety and EMC Standards
Safety: Complies with IEC/EN61010-1 (CE), approved by C22.2 No.61010-1, ap­proved by UL508.
Installation category : CAT. II Pollution degree : 2 (IEC/EN61010-1, C22.2 No.61010-
1) Measurement category : I (CAT. I : IEC/EN61010-1) Rated measurement input voltage : 10V DC max.(across terminals), 300V AC
max.(across ground)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
Rated transient overvoltage : 1500V (Note) Note : It is a value on the safety standard which is assumed by IEC/EN61010-1 in
Measurement category I, and is not the value which guarantees an apparatus perfor­mance.
This equipment has Measurement category I, therefore do not use the equipment for measurements within Measurement categories II, III and IV.
CAUTION
1-9
Measurement category
1
2
3
4
CAT.1 CAT.2 CAT.3 CAT.4
Entrance Cable
Construction, Installation, and Wiring
Description For measurements performed on circuits not directly connected to MAINS. For measurements performed on circuits directly connected to the low voltage installation. For measurements performed in the building installation. For measurements performed at the source of the low-voltage installation.
Internal Wiring
3
4
Outlet
2
T
1
Appliances, portable equipments, etc. Distribution board, circuit breaker, etc. Overhead wire, cable systems, etc.
Remarks
EMC standards: Complies with EN61326, EN61000-3-2, EN61000-3-3 and EN55011 (CE). AS/NZS 2064 compliant (C-Tick). Class A Group 1.
The instrument continues to operate at a measuring accuracy of within 20% of the range during tests.
Construction: Dust-proof and drip-proof pront panel conforming to IP55. For side-by­side close installation the indicator loses its dust-proof and drip-proof protection.
Material: ABS resin and polycarbonate
Case color: Black
Weight: About 1 kg or less
Dimensions:
UM351 96 (W) 96 (H) 100 (depth from panel face) mm UM331 96 (W) 48 (H) 100 (depth from panel face) mm
Installation: Panel-mounting type. With top and bottom (or right and left) mounting hardware (1 each)
Panel cutout dimensions: UM351 92 UM331 92
+0.8
(W) 92
0 +0.8
(W) 45
0
+0.8
(H) mm
0 +0.6
(H) mm
0
Installation position: Up to 30 upward facing (not designed for facing downward)
Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
Power Supply Specifications
Power supply: Rated voltage of 100 to 240 V AC (10%), 50/60 Hz
Power consumption: Max. 20 VA (8.0 W max.)
Internal fuse rating: 250 VAC, 1.6A time-lug fuse
Data backup: Non-volatile memory (can be written to up to 100,000 times)
Withstanding voltage
- Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
- Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
- Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
- Between secondary terminals**:
At least 500 V AC for 1 minute * Primary terminals indicate power terminals and relay output terminals ** Secondary terminals indicate analog I/O signal, and contact input terminals
1-10
Insulation resistance: 20 M or more at 500 V DC between power terminals and grounding terminal
Grounding: Class D grounding (grounding resistance of 100  or less)
Signal Isolations
PV input terminals: Isolated from other input/output terminals. Not isolated from internal circuit.
15 V DC loop power supply terminals: Not isolated from 4-20 mA analog output. Isolated from other input/output terminals and internal circuit.
24 V DC loop power supply terminals: Isolated from 4-20 mA analog output terminals, other input/output terminals and internal circuit.
4-20 mA analog output terminals (for retransmission): Not isolated from 15 V DC loop power supply. Isolated from other input/output terminals and internal circuit.
Contact input terminals: Not isolated from communication terminals. Isolated from other input/output terminals and internal circuit.
Relay contact output terminals: Not isolated between relay contact output terminals. Isolated from other input/output terminals and internal circuit.
RS-485 communication terminals: Not isolated from contact input terminals. Isolated from other input/output terminals and internal circuit.
Power terminals: Isolated from other input/output terminals and internal circuit.
Grounding terminals: Isolated from other input/output terminals and internal circuit.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
Environmental Conditions
Normal operating conditions: Ambient temperature: 0 to 50C (40C or less for side-by-side close installation) 0 to 40C if the 24 V DC loop power supply of Model UM331 is used Temperature change rate: 10C/h or less Ambient humidity: 20 to 90% RH (no condensation allowed) Magnetic field: 400 A/m or less Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or less Continuous vibration at 14 to 150 Hz: 4.9 m/s Short-period vibration: 14.7 m/s Shock: 147 m/s
2
or less, 11 ms
2
, 15 seconds or less
Installation height: Height above sea level of 2000 m or less Warm-up time: 30 minutes or more after power on
Transportation and storage conditions: Temperature: -25 to 70C Temperature change rate: 20C/h or less Humidity: 5 to 95% RH (no condensation allowed)
Effects of changes in operating conditions
- Effects from changes in ambient temperature:
- On voltage or thermocouple input, 1 V/C or 0.01% of F.S./C, whichever is larger
2
or less
1-11
- On RTD input, 0.05C/C (ambient temperature) or less
- On analog output, 0.05% of F.S./C or less
- Effects from power supply fluctuation (within rated voltage range)
- On analog input, 1 V/10 V or 0.01% of F.S./10 V, whichever is larger
- On analog output, 0.05% of F.S./10 V or less
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>

1.5 Terminal Wiring Diagrams

NOTE
Do not use unassigned terminals as relay terminals.
Terminal wiring diagrams are shown on and after the next page.
1-12
IM 05F01D12-41E 4th Edition: May 31, 2006-00
UM351 Standard Type (Model UM351-0 or UM351-3䊐)
Power supply
Relay contact output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
* Wiring can only be carried out for indicators with communication functions. Maximum baud rate: 9600 bps
Allowable range: 100 to 240 V AC (
10%) (free voltage) 50/60 Hz shared
PV input
* Not configured at factory before shipment See “2.
Initial Settings,” for more
information.
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
16
17
Retransmission output
4-20 mA DC
16
17
15 V DC loop power supply
14.5-18.0 V DC (21 mA DC max.)
* PV retransmission is configured at factory before shipment.
Load resistance: 600
or less
* If 15 V DC loop power supply is used, retransmission output cannot be used.
-
+
-
+
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
8
9
10
L
N
12
13
11
12
13
12
13
21
22
21.6-28.0 V DC (30 mA DC max.)
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
6
5
4
7
AL1
AL2
AL3
COM
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
1
2
3
Alarm 4 output
NC
NO
COM
A
b
B
UM
+
-
* Wiring can only be carried out for
UM351-1 or UM351-
2.
-
+
-
+
TC input
RTD input
mV/V input
12
13
+
-
Note: Connecting a 250
resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
* When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint
41).
䊏 Receiving 4-20 mA DC Current
Signals with the Indicator
250
19
20
DI1
COM
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
.
Common
UM
Contact input
Contact
Contact rating: 12 V DC, 10 mA or more
DI1
COM
+5V
Transistor contact
19
20
RS-485 communication
Alarm output
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Power supply
24 V DC loop
power supply
4-20mA
CAUTION
Before carrying out wiring, turn off the power to the indicator and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
<Toc> <1. Installation>
IM 05F01D12-41E 4th Edition: May 31, 2006-00
1-13
UM331 Standard Type (Model UM331-0 or UM331-3䊐)
24 V DC Power Supply Wiring to Two-wire Sensor
15 V DC Power Supply Wiring to Two-wire Sensor
12
13
+
-
Note: Connecting a 250
resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
* When receiving 4-20 mA DC current signals, set the PV input type to 1-5 V DC (setpoint
41).
䊏 Receiving 4-20 mA DC Current
Signals with the Indicator
250
4-20 mA
12
13
11
12
13
12
13
A
b
B
-
+
-
+
TC input
RTD input
mV/V input
6
5
4
7
AL1
AL2
AL3
COM
UM
16
17
Retransmission output
4-20 mA DC
16
17
15 V DC loop power supply
14.5-18.0 V DC (21 mA DC max.)
* PV retransmission is configured at factory before shipment.
Load resistance: 600
or less
* If 15 V DC loop power supply is used, retransmission output cannot be used.
-
+
-
+
11
21
13
23
3
15
25
5
19
29
9
1
17
27
7
12
22
14
24
4
16
26
6
20
30
10
2
18
28
8
8
9
Power supply
10
L
N
Power supply
23
24
RS-485 communication
* Wiring can only be carried out for indicators with communication functions. Maximum baud rate: 9600 bps
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
19
20
DI1
COM
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
.
Common
1
2
Relay contact output
3
Alarm 4 output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
* Wiring can only be carried out for
UM331-1 or UM331-
2.
CAUTION
Before carrying out wiring, turn off the power to the indicator and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
UM
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
12
13
16
17
Two-wire transmitter
PV input
0.4 to 2.0 V DC signal
Loop power
supply
14.5 to
18.0 V DC
External resistor (Note)
4-20 mA DC
Note: Connecting a 100
resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
100
12
13
21
22
Two-wire transmitter
PV input
1 to 5 V DC signal
Loop power
supply
21.6 to
28.0 V
DC
External resistor (Note)
4-20 mA DC
Note: Connecting a 250
resistor to the terminals is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
250
Contact input
Contact
Contact rating: 12 V DC, 10 mA or more
DI1
COM
+5V
Transistor contact
19
20
* Wiring can only be carried out for indicators with 24 V DC loop power supply.
21
22
21.6-28.0 V DC (30 mA DC max.)
+
-
24 V DC loop
power supply
Alarm output
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Allowable range: 100 to 240 V AC (
10%) (free voltage) 50/60 Hz shared
PV input
* Not configured at factory before shipment See 2.
Initial Settings,” for more
information.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <1. Installation>
1-14
<Toc> <2. Initial Settings>

2. Initial Settings

This chapter describes examples of setting the types of PV input and alarm. Carry­ing out settings described herein allows you to perform basic monitoring. Refer to examples of various settings to understand how to set parameters required. Refer to 5.1 Parameter Map for an easy to understand explanation of setting various parameters. If you cannot remember how to carry out an operation during setting, press the ing display) that appears at power-on.
Setup Procedure
SET/ENT
key for more than 3 seconds. This brings you to the display (operat-
2-1
Power-on
Set PV input.
See 2.2 Setting PV Input Type (Setting First at Power-on), or 2.3 Changing PV Input Type.
Set the alarm
type and other setup
parameters.
See “2.4 Changing the Alarm Type.”
Set the alarm
setpoints and other
operating parameters.
See “3.2 Setting Alarm Setpoints.”
Indicator operation
(Factory-set to Unspecified.)
Denotes a step that must always be followed.
Denotes a step that should be followed as necessary.
The following explanation of operation for the UM351s panel, shown in the figure, is the same as that of the UM331s panel.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>

2.1 Names and Functions of Front Panel Parts

2-2
4. SET/ENT key
Name of Part
Process variable (PV)
1. display
Parameter setpoint display
2.
3. Alarm indicator lamps SET/ENT
4. key
and
5. keys
SET/ENT
IMPORTANT
1. Process variable (PV) display
2. Parameter Setpoint display
3.
Alarm indicator
lamps
5. and keys
Displays a PV value during operation.
Displays a parameter symbol when you set a parameter.
Displays an error code in red if the indicator fails.
Displays the setpoint of a parameter when it is configured. If any of alarms 1 to 4 occurs, the respective alarm indicator lamp (AL1 to AL4) is lit (in orange). Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch
between the operating display and the menu for operating parameter setting display alternately. Used to change numerical values. On setting displays for various parameters, you can change parameters.
Pressing the key decreases a numerical value, while pressing the key causes it to increase. You can hold down a key to gradually increase the speed of change.
2. Parameter Setpoint display
Function
4. SET/ENT key
1. Process variable (PV) display
3. Alarm indicator lamps
5. and keys
The indicator automatically returns to the display at the time of power-on (i.e., Operating display) if no key is operated for at least one minute.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>

2.2 Setting PV Input Type (Setting First at Power-on)

NOTE
The indicator displays the operating display when the power is turned on. However, if PV input type has not been set, IN appears. In this case, first use the display the input range code to use, then press the the maximum value (RH) and minimum value (RL) of the PV input range (for voltage input, set the maximum value (SH) and minimum value (SL) of the PV input scale).
The indicator is configured to the initial value of each parameter at the factory before shipment. First check the initial values shown in 5.2 Lists of Parameters, and change param­eter values as necessary.
Example of Temperature Input Example of Voltage Input
1V 5V (Input signal)
-200°C 1370°C
0°C 800°C
Minimum value of
PV input range (RL)
Parameters to be set for temperature input
1. PV input type (IN): Set according to a sensor
2. Maximum value of PV input range (RH): Set the maximum value of the range to be displayed.
3. Minimum value of PV input range (RL): Set the minimum value of the range to be displayed.
Instrument input range
PV input range
Maximum value of
PV input range (RH)
Set the actual read-out range.
Parameters to be set for voltage input
1. PV input type (IN): Set according to an input signal
2. Maximum value of PV input range (RH): Set the maximum value of an input signal.
3. Minimum value of PV input range (RL): Set the minimum value of an input signal.
4. Position of PV input decimal point (SDP): Set the position of the decimal point for PV input display.
5. Maximum value of PV input scale (SH): Set the maximum value of the scale to be displayed.
6. Minimum value of PV input scale (SL): Set the minimum value of the scale to be displayed.
2V 4V
PV input range
RL
PV input scale
0.0m3/h 50.0m3/h
Minimum value of
PV input scale (SL)
SET/ENT
Instrument input range
Maximum value of
PV input scale (SH)
key to register it. Then, set
RH
Set the actual read-out range.
2-3
key to
The following operating procedure describes an example of setting a K-type thermocouple (-199.9C to 500.0C) and a measurement range of 0.0C to 200.0C.
Display screen at power-on
1.
The parameter IN for setting the PV input type appears.
PV
AL1234
SET/ENT
Displays
parameter
IN.
Press the or key to display the
2.
required setpoint. The figure below shows an example of setting a K-type thermocouple (-199.9 to
500.0C). See the Instrument Input Range Codes.
PV
AL1234
SET/ENT
Blinks during
change.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
2-4
3.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
4.
Press the
SET/ENT
key once to display the
parameter UNIT (PV input unit).
PV
AL1234
SET/ENT
5.
Press the
SET/ENT
key once to display the parameter RH (maximum value of PV input range).
PV
AL1234
Displays
parameter
UNIT.
Displays
parameter
RH.
8.
Press the
SET/ENT
key once to display the parameter RL (minimum value of PV input range).
PV
AL1234
SET/ENT
Press the or key to display the
9.
required setpoint. The figure below shows an example of setting the minimum value of PV input range to 0.0C.
PV
AL1234
SET/ENT
10.
Press the
SET/ENT
key once to register the setpoint.
PV
Displays
parameter
RL.
Blinks during
change.
SET/ENT
Press the or key to display the
6.
required setpoint. The figure below shows an example of setting the maximum value of PV input range to 200.0C.
PV
AL1234
SET/ENT
7.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
Blinks during
change.
AL1234
SET/ENT
If the type of input is voltage, also config­ure the PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH), and Minimum Value of PV Input Scale (SL) parameters that are displayed after this.
11.
Press the
SET/ENT
key for more than 3 sec­onds. This returns you to the display shown at power-on (figure below).
PV
AL1234
SET/ENT
Displays PV.
The PV display in the figure above shows the error code for input burnout ( ) if PV input wiring is not yet complete. The error code disappears when you wire the PV input terminals correctly.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
Instrument Input Range Codes
Selected the unit from UNIT parameter.
Input Type
Unspecified
Thermocouple
RTD
Standard signal
DC voltage
K
J4
T
B7
S8
R9
N10
E11
L(DIN) 12
U(DIN)
W15
Platinel 2 16
PR20-40 17
W97Re3­W75Re25
JPt100
Pt100
0.4 to 2 V 1 to 5 V 41 0 to 2 V 50 0 to 10 V 51
-10 to 20 mV 0 to 100 mV
Instrument Input
Range Code
OFF
1
2
3
5
6
13
14
18
30
31
35
36
37
40
55 -10.00 to 20.00 mV 56 0.0 to 100.0 mV
* Performance in the standard condition (at 232C, 5510%RH, and 50/60 Hz power frequency. Note 1: The accuracy is 0.3C of instrument range 1 digit for a temperature range from 0C to 100C. Note 2: The accuracy is 0.5C of instrument range 1 digit for a temperature ranges from -100C to 0C and 100C to
200C.
* To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 resistor. This
resistor is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Instrument
Input Range
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
Set the data item PV Input Type "IN" to the OFF option to leave the PV input type undefined.
type undefined.
-200 to 1370C
-300 to 2500F
-199.9 to 999.9C 0 to 2300F
-199.9 to 500.0C
-199.9 to 999.9F
-199.9 to 999.9C
-300 to 2300F
-199.9 to 400.0C
-300 to 750F
0.0 to 400.0C
-199.9 to 750.0F
0 to 1800C
32 to 3300F
0 to 1700C
32 to 3100F
0 to 1700C
32 to 3100F
-200 to 1300C
-300 to 2400F
-199.9 to 999.9C
-300 to 1800F
-199.9 to 900.0C
-300 to 1300F
-199.9 to 400.0C
-300 to 750F
0.0 to 400.0C
-199.9 to 750.0F 0 to 2300C
32 to 4200F
0 to 1390C
32 to 2500F
0 to 1900C
32 to 3400F
0 to 2000C
32 to 3600F
-199.9 to 500.0C
-199.9 to 999.9F
-150.0 to 150.0C
-199.9 to 300.0F
-199.9 to 850.0C
-300 to 1560F
-199.9 to 500.0C
-199.9 to 999.9F
-150.0 to 150.0C
-199.9 to 300.0F
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
0.1% of instrument range 1 digit for temperatures equal to or higher than 0°C 0.2% of instrument range 1 digit for temperatures below 0°C
0.15% of instrument range 1 digit for temperatures equal to or higher than 400°C 5% of instrument range 1 digit for temperatures below 400°C
0.15% of instrument range 1 digit
0.1% of instrument range 1 digit0.25% of instrument range 1 digit for temperatures
below 0°C
0.1% of instrument range 1 digit for temperatures equal to or higher than 0°C 0.2% of instrument range 1 digit for temperatures below 0°C
0.2% of instrument range 1 digit
0.1% of instrument range 1 digit
0.5% of instrument range 1 digit for temperatures
equal to or higher than 800°C No guarantee of accuracy for temperatures below 800°C
0.2% of instrument range 1 digit
0.1% of instrument range 1 digit (Note 1) (Note 2)
0.2% of instrument range 1 digit (Note 1)
0.1% of instrument range 1 digit (Note 1) (Note 2)
0.2% of instrument range 1 digit (Note 1)
0.1% of instrument range 1 digit
The read-out range can be scaled between -1999 and
9999.
Measurement Accuracy
2-5
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
NOTE
The indicator may automatically initialize the registered operating parameter setpoints if any change is made to the data item PV Input Type (IN), Maximum Value of PV Input Range (RH), Minimum Value of PV Input Range (RL), PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH) or Minimum Value of PV Input Scale (SL). After a change has been made to any of these data items, be sure to verify the registered operating parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a required value.
2-6
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>

2.3 Changing PV Input Type

The following operating procedure describes an example of changing the setting of K-type thermocouple (-199.9 to 500.0C) to RTD Pt100 (-199.9 to 500.0C) and a measurement range of 0.0 to 200.0C.
2-7
PV input terminal Thermocouple/mV/V input
RTD input .................................................. - -
Bring the operating display into view
1.
(display appears at power on).
PV
AL1234
SET/ENT
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu OP.PA”.
PV
AL1234
SET/ENT
..............................
Displays PV.
Displays
menu OP.PA.
1312
-
131211
5.
Press the
SET/ENT
key once to display the
menu FUNC”.
Displays
PV
AL1234
SET/ENT
Press the key once to display the
6.
menu FUNC”.
menu I/O”.
Displays
PV
AL1234
SET/ENT
menu “I/O”.
Press the key once to display the
3.
menu STUP”.
PV
AL1234
SET/ENT
4.
Press the
SET/ENT
key once to display the
parameter PWD”.
PV
AL1234
SET/ENT
Displays
menu STUP.
Displays
parameter
PWD.
7.
Press the
SET/ENT
key once to display the
parameter IN (PV input type).
PV
AL1234
SET/ENT
Press the or key to display the
8.
required setpoint. The figure below shows an example of changing to RTD Pt100 (-199.9 to 500.0C).
PV
AL1234
SET/ENT
Blinks during
Displays
parameter
IN.
change.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
2-8
9.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
10.
Press the
SET/ENT
key once to display the
parameter UNIT (PV input unit).
PV
AL1234
SET/ENT
11.
Press the
SET/ENT
key once to display the parameter RH (maximum value of PV input range).
PV
AL1234
Displays
parameter
UNIT.
Displays
parameter
RH.
14.
Press the
SET/ENT
key once to display the parameter RL (minimum value of PV input range).
PV
AL1234
SET/ENT
Press the or key to display the
15.
required setpoint. The figure below shows an example of setting the minimum value of PV input range to 0.0C.
PV
AL1234
SET/ENT
16.
Press the
SET/ENT
key once to register the setpoint.
PV
Displays
parameter
RL.
Blinks during
change.
SET/ENT
Press the or key to display the
12.
required setpoint. The figure below shows an example of setting the maximum value of PV input range to 200.0C.
PV
AL1234
SET/ENT
13.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
Blinks during
change.
AL1234
SET/ENT
17.
Press the
SET/ENT
key for more than 3 sec­onds. This returns you to the display shown at power-on (figure below).
PV
AL1234
SET/ENT
Displays PV.
* If the type of input is voltage, also config-
ure the PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH), and Minimum Value of PV Input Scale (SL) parameters that are displayed after this.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>

2.4 Changing Alarm Type

The following operating procedure describes an example of changing alarm-1 (factory-set default: PV high limit alarm) to PV low limit alarm.
When you have changed alarm type, the alarm setpoint will be initialized; set the alarm setpoint again.
2-9
Alarm output terminals Factory-set defaults
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers )......PV low limit alarm
Bring the operating display into view
1.
(appears at power-on).
PV
AL1234
SET/ENT
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu OP.PA”.
PV
AL1234
6 7
-
5 7
-
4 7
-
2 31
--
-
Displays PV.
Displays
menu OP.PA.
5.
Press the
SET/ENT
key once to display the menu FUNC”.
PV
SET/ENT
6.
Press the
SET/ENT
key once to display the parameter AL1 (alarm-1 type).
PV
Displays
menu FUNC”.
AL1234
Displays
parameter
AL1.
AL1234
SET/ENT
Press the key once to display the
3.
menu STUP”.
PV
AL1234
SET/ENT
4.
Press the
SET/ENT
key once to display the
parameter PWD”.
PV
AL1234
SET/ENT
Displays
menu STUP.
Displays
parameter
PWD.
SET/ENT
Press the or key to display the
7.
required setpoint. The figure below shows an example of setting PV low limit alarm.
PV
AL1234
SET/ENT
Blinks during
change.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
2-10
8.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
You can take the same steps for alarm-2 type (AL2), alarm-3 type (AL3), and alarm-4 type (AL4) that are displayed after this.
List of Alarm Types
The table below shows the alarm types and alarm actions. In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with stand-by actions.
Alarm action
Alarm type
Open/close shows status of relay contact, and lit and unlit shows status of lamp
No alarm OFF
Hysteresis
PV high limit
PV low limit
Open (unlit)
Closed (lit)
Alarm setpoint
PV
Hysteresis
Alarm setpoint PV
Closed (lit)
Open (unlit)
Contact
closes
if alarm
occurs
1
11
2
12
Contact
opens
if alarm
occurs
Press the
9.
onds. This returns you to the display shown at power-on (figure below).
See 3.2 Setting Alarm Setpoints when setting an alarm setpoint.
Alarm type
De-energized
on PV high limit
De-energized
on PV low limit
SET/ENT
key for more than 3 sec-
PV
AL1234
SET/ENT
Alarm action
Open/close shows status of relay contact, and lit and unlit shows status of lamp
Hysteresis
Closed
(unlit)
Open (lit)
Alarm setpoint
PV
Hysteresis
Open (lit)
Alarm setpoint
Closed
PV
(unlit)
Displays PV.
Alarm type codeAlarm type code
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
9
19
10
20
Fault diagnosis output (Note 1) FAIL output (Note 2)
Note 1: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
Note 2: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
Stand-by Action
C
Treated
Normal
as normal
It is effective in the following cases where;
- the power is turned on
- the alarm type is changed
The alarm output does not turn on in this region even if the PV value is below the low limit of the alarm setpoint.
Power-on
Abnormal
The alarm
output turns on.
Low limit of alarm setpoint
Time
IM 05F01D12-41E 4th Edition: May 31, 2006-00
2221
<Toc> <2. Initial Settings>

2.5 Setting Hysteresis in Alarm Setpoint

The following operating procedure describes an example of setting a 5.0°C hysteresis level in the alarm setpoint.
2-11
Bring the operating display into view
1.
(appears at power-on).
PV
AL1234
SET/ENT
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu OP.PA”.
PV
AL1234
SET/ENT
Press the key once to display the
3.
menu STUP”.
Displays PV.
Displays
menu OP.PA.
6.
Press the
SET/ENT
key several times to display the parameter HY1 (alarm-1 hysteresis).
PV
AL1234
SET/ENT
Press the or key to display the
7.
required setpoint.
PV
AL1234
SET/ENT
8.
Press the
SET/ENT
key once to register the setpoint.
Displays
parameter
HY1.
Blinks during
change.
Press the
4.
parameter PWD”.
Press the
5.
menu FUNC”.
PV
AL1234
SET/ENT
SET/ENT
key once to display the
PV
AL1234
SET/ENT
SET/ENT
key once to display the
PV
AL1234
Displays
menu STUP.
Displays
parameter
PWD.
Displays
menu FUNC.
PV
AL1234
SET/ENT
You can take the same steps for alarm-2 hysteresis (HY2), alarm-3 hysteresis (HY3), and alarm-4 hysteresis (HY4) that are displayed after this.
9.
Press the
SET/ENT
key for more than 3 sec­onds. This returns you to the display shown at power-on (figure below).
PV
Displays PV.
AL1234
SET/ENT
SET/ENT
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
2-12

2.6 Setting the PV display color changing function Active Color PV Display

The following operating procedure describes an example of changing PV color mode (factory-set default: Fixed in red mode) to Link to alarm 1 mode.
Bring the operating display into view (appears at
(1)
power on).
PV
AL1234
SET/ENT
Press the key for more than 3 seconds to
(2)
call up the menu OP.PA.
SET/ENT
Displays PV.
Displays
PV
AL1234
SET/ENT
Press the key once to display the menu
(3)
STUP.
PV
AL1234
SET/ENT
Press the key once to display the parameter
(4)
PWD.
Press the key once to display the menu
(5)
FUNC.
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
PV
menu OP.PA
Displays
menu STUP
Displays
menu PWD
Displays
menu FUNC
Press the key several times to display the
(6)
menu PCMD (PV color mode).
Press the key or key to display the
(7)
required setpoint. The figure below shows an
SET/ENT
SET/ENT
PV
AL1234
parameter PCMD
example of setting Link to alarm 1 mode.
PV
during change
AL1234
SET/ENT
Press the key once to register the setpoint.
(8)
SET/ENT
If PCMD = 6, 7, 8 or 9,
PV
also set the relating paraemters PCCH
AL1234
SET/ENT
Press the key for more than 3 seconds.
(9)
This returns you to the display shown at power-on
SET/ENT
(High limit for PV color change) and PCCL (Low limit for PC color change).
(figure blow).
PV
AL1234
SET/ENT
Displays PV.
Displays
Blinks
SET/ENT
AL1234
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <2. Initial Settings>
2-13

2.7 Setting the High Limit and Low limit for PV Color change

The following operating procedure describes an example of changing PV display color by linking to PV. Set High limit and Low limit for PV color change. Setting for both of High limit and Low limit is required.
Bring the operating display into view (appears at
(1)
power-on).
PV
AL1234
SET/ENT
Press the key for more than 3 seconds to
(2)
call up the menu OP.PA.
Press the key several times to display the
(3)
parameter PCCH.
SET/ENT
PV
AL1234
SET/ENT
SET/ENT
PV
AL1234
SET/ENT
Displays PV.
menu OP.PA
Displays parameter
PCCH.
Displays
Press the key or key to display the
(4)
required setpoint.
PV
AL1234
SET/ENT
Press the key once to register the
(5)
setpoint.
SET/ENT
PV
AL1234
SET/ENT
Blinks during
PCCL (Low limit for PV color change parameter) that is displayed after this can be
Press the key for more than 3 seconds.
(6)
This returns you to the display shown at power-
SET/ENT
on (figure below).
PV
AL1234
SET/ENT
change.
Displays PV.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <3. Operations>

3. Operations

3-1
This chapter describes key entries for operating the indicator. If you cannot remem­ber how to carry out an operation during setting, press the seconds. This brings you to the display (operating display) that appears at power­on.
SET/ENT
key for more than 3
NOTE
Do not use the instrument generating strong magnetic field such as radio equipment and the like near the indicator. This may cause the fluctuation of the PV value.

3.1 Monitoring-purpose Operating Display Available during Operation

The following is the monitoring-purpose operating display available during operation.
Power On
SET/ENT
PV
AL1234
Displays PV.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <3. Operations>

3.2 Setting Alarm Setpoints

The following operating procedure describes an example of setting a value of 160.0 in the alarm-1 setpoint parameter. Before setting the alarm setpoint, check the alarm type. To change the alarm type, see 2.4 Changing Alarm Type.
3-2
Alarm output terminals
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers ).......PV low limit alarm
Bring the operating display into view
1.
(display appears at power on).
PV
AL1234
SET/ENT
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu OP.PA”.
PV
AL1234
SET/ENT
6 7 5 7 4 7 1
Factory-set defaults
-
-
-
2
3
--
Displays PV.
Displays
menu OP.PA”.
5.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
You can take the same steps for alarm-2 setpoint (A2), alarm-3 setpoint (A3), and alarm-4 setpoint (A4) that are displayed after this.
6.
Press the
SET/ENT
key for more than 3 sec­onds. This returns you to the display shown at power-on (figure below).
PV
Displays PV.
3.
Press the
SET/ENT
key once to display the
parameter A1”.
PV
AL1234
SET/ENT
Press the or key to display the
4.
required setpoint.
PV
AL1234
SET/ENT
AL1234
SET/ENT
Displays
parameter
A1.
Blinks during
change.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>

4. Troubleshooting and Maintenance

4.1 Troubleshooting

Troubleshooting Flow
If the operating display does not appear after turning on the indicators power, try to solve the problem by following the procedure below.
If the problem seems to be complex, contact the vendor from which you purchased the instrument.
Is the instrument
defective?
Yes
Totally
inoperable?
Yes
No
Is key
operation
faulty?
Yes
No
Is display
faulty?
Yes
No
Is I/O
signal faulty?
Yes
No
Is
communication
link faulty?
Yes
4-1
Check wiring on the power supply terminals.
Check the supply voltage.
Normal?
Ask the vendor for repair.
No
No
Yes
Check the key lock setting.
No
Correct
errors.
Correct?
Yes
Find the cause.
Is key lock enabled?
Disable key lock.
Yes
Turn off power, and then turn it on again.
Check the instruments I/O specifications.
Check the specifications of I/O counterpart for wrong polarity.
No communication
capability.
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
Check the instrument's suffix code.
No
Does the code
include a communication
option?
Check the communication-related parameters.
Check communication wiring.
Check the specifications of communication counterpart.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>
Errors at Power on
The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.
4-2
Error indication
(on PV display unit)
(E000)
(E001)
(E002)
PV decimal point blinks.
(E400)
Description
of error Faulty RAM
Faulty ROM
System data error
Faulty calibration value
Parameter error
PV
None
0% Normal action
(out of accuracy)
0%
Possible Errors during Operation
The following shows possible errors occurring during operations.
Error indication
(on PV display unit)
Displays RJC and PV alternately
PV value blinks.
(E300)
(B.OUT)
(OVER) or
(-OVER)
SP decimal point blinks. (on setpoint display unit)
All indications off Faulty if power off/on does
All indications off Check for abnormal power.
Description
of error
RJC error
EEPROM error
A/DC error
PV burnout error
Excessive PV Out of -5 to 105%
Faulty communi­cation line
Runaway (due to defective power or noise)
Power off
PV
Measured with RJC=OFF
Normal action
105
%
Dependent on the BSL parameter Up-scale: 105% Down-scale: -5%
-5% or 105%
Normal action
None
None
Control
output
0% or less or OFF
Normal action (out of accuracy)
Preset value
Control
output
Normal action
Normal action
Preset value
Preset value
Normal action
Normal action
0% or less or OFF
0
Normal action
Normal action
Normal action
Normal action
Normal action
Normal action
OFF
OFF
%
Alarm
output
OFF
Normal action (out of accuracy)
OFF 0%
Retransmis-
Alarm
sion output
output
Normal action
Normal action
Normal action
Normal action
Normal action
Normal action
0% or less
0
%
Retransmission
output
0% or less Stopped
0% Normal action
(out of accuracy)
Commu-
Normal action
Normal action
Normal action
Normal action
Normal action
Normal action
Stopped
Stopped
Communi-
cation
Normal action
nication
Faulty Contact us for repair.
Faulty Contact us for repair.
Check wires and sensor.
Check process.
Check wires and communication parameters, and make resetting. Recovery at normal receipt
not reset start the unit. Contact us for repair.
Remedy
Faulty Contact us for repair.
Check and set the parameters, as they have been set to the limited values.
Remedy
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>
If a Power Failure Occurs during Operation
Momentary Power Failures shorter than 20 ms
The indicator is not affected at all and continues normal operation.
Momentary Power Failures of 20 ms or longer
The alarm function of the indicator continues to work normally. (Alarms with the stand­by feature temporarily return to their stand-by state, however.)
Setting parameters that have already been configured retain their settings.
4-3
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>

4.2 Maintenance

This section describes the cleaning and maintenance of the UM351/UM331.

4.2.1 Cleaning

The front panel and operation keys should be gently wiped with a dry cloth.
NOTE
Do not use alcohol, benzine, or any other solvents.

4.2.2 Replacing Brackets

When the brackets are broken or lost, purchase the following brackets for replacement.
4-4
Target Model Part No. UM351 T9115NL UM331 T9115NK
SEE ALSO
1.2 How to Install, for how to replace brackets.

4.2.3 Attaching Terminal Cover

When a terminal cover is necessary, purchase the following part.
Target Model Part No. UM351 T9115YD UM331 T9115YE
Sales Unit A large bracket and small bracket in pair Small brackets in pair
Sales Unit 1 1
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>
Attaching Terminal Cover
The procedure for attaching the terminal cover is as follows.
Do not touch the terminals on the rear panel when power is being supplied to the indicator. Doing so may result in electric shock.
4-5
CAUTION
1.
Before attaching the terminal cover, turn off the source circuit breaker and use a tester to check that the power cable is not conducting any electricity.
Before attaching the terminal cover, fold it once or twice so that the side which has the Handle With Care symbol ( ), is on the outside.
Fold over.
Grooved
Fold over.
Grooved
Folding Direction of Terminal Cover
Alert symbol on the back
NOTE
Do not fold the terminal cover the wrong way, doing so not only reduces the cover’s strength but may also cause the hinge to crack, thereby disabling attachment.
With the cover properly folded, fit its top and bottom holes to the protrusions of the
2.
mounting brackets.
Fit the hole of the terminal cover to the protrusion on the mounting bracket.
Attaching Terminal Cover
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <4. Troubleshooting and Maintenance>

4.2.4 Replacing Parts with a Limited Service Life

The following UM351/UM331 parts have a limited service life. The service life given in the table assume that the indicator is used under normal operating conditions.
4-6
Part Aluminum electrolytic condenser EEPROM About 100,000 times of writings Alarm 4 output relays About 100,000 more ON-OFF operations or with resistance load
About 10 years (rated)
Service life
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>

5. Parameters

This chapter contains a parameter map as a guideline for setting parameters, and lists of parameters for recording User Settings.

5.1 Parameter Map

5-1
UM351/UM331 Parameter Map
Operating Display
PV display
SET3S
A1 A2 A3 A4
PEAK
BOTM
FL
BS
PCCH
PCCL
SET
SET3S
SET3S
To switch the parameter display, press the key.
Displayed only for UM351-1, UM351-2, UM331-1, UM331-䊐2
Displayed when PCMD (PV color mode parameter) = 6 or 7
Menu
SET/ENT
SET
SET
SET
SET3S
Press the key once.
Press the key for 3 seconds.
Press the or key once.
STUPOP.PA
SET
Password
check display
Password input
(No password is required when PWD = 0.)
SET
Setup Parameter
Alarm/
Communication
related Input related
Setting Display
FUNC
SET SET
PCMD
AL1
AL2
AL3 AL4
HY1
Displayed only for UM351-1, UM351-2, UM331-1, UM331-䊐2
HY2 HY3 HY4 DY1
Displayed only for UM351-1, UM351-2, UM331-1, UM331-䊐2
DY2 DY3 DY4 P.SL
Displayed only for UM351-1, UM351-2, UM331-1, UM331-䊐2
BPS
PRI
STP
Displayed only for indicators with communication function.
DLN ADR RP.T
TEST
This parameter is not to be set.
SET/ENT
SET/ENT
IN
UNIT
RH
RL
SDP
SH
SL
RJC
ERJC
BSL RET RTH RTL
DIS C.S1 C.S2 C.S3 C.S4
LOCK
PWD
I/O
When shipped from the factory, the indicator is configured so that this parameter appears first after power-on.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>

5.2 Lists of Parameters

* Parameters relating to PV should all be set in real numbers.
For example, use temperature values to define alarm setpoints for temperature input. * The “User Setting” column in the table is provided for the customer to record setpoints. * Numbers in ( ) are the parameter setpoints that apply when the communication func-
tion is used. ex. OFF (0), ON(1)
Operating Parameters
5-2
Parameter
Symbol
(A1)
(A2)
(A3)
(A4)
(PEAK)
(BOTM)
(FL)
(BS)
(PCCH)
(PCCL)
Name of Parameter Setting Range and Description
Alarm 1-setpoint
Alarm 2-setpoint
Alarm 3-setpoint
Alarm 4-setpoint
PV peak value
PV bottom value
PV input filter OFF (0), 1 to 120 sec.
PV input bias -100.0% to 100.0% of PV input range span
High limit for PV color change
Low limit for PV color change
PV alarm: -100.0 to 100.0% of PV input range
Displays the maximum value of PV input during operation. This parameter is not to be set.
Displays the minimum value of PV input during operation. This parameter is not to be set.
Used when the PV input fluctuates.
Used to correct the PV input value.
When PCMD (PV color mode parameter) = 6 or 7 :
-100.0 to 100.0 % of PV input range
Initial Value User setting
PV high limit alarm:
100.0% of PV input range PV low limit alarm:
0.0% of PV input range
OFF (0)
0.0% of PV input range span
When PCMD = 6 or 7 : PCCH = 100.0%, PCCL = 0.0 %
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
Setup Parameters
Alarm/Communication Related Parameters
5-3
Parameter
Symbol
(PCMD)
(AL1)
(AL2)
(AL3)
(AL4)
(HY1)
(HY2)
(HY3)
(HY4)
(DY1)
Name of Parameter
PV color mode
Alarm-1 type
Alarm-2 type
Alarm-3 type
Alarm-4 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
Alarm-1 delay timer
Setting Range and Description Initial Value
0: Fixed in green 1: Fixed in red
1
2: Link to alarm 1 (Alarm OFF:green, Alarm ON:red) 3: Link to alarm 1 (Alarm OFF:red, Alarm ON:green) 4: Link to alarm 1 and 2 (Alarm OFF:green, Alarm ON:red) 5: Link to alarm 1 and 2 (Alarm ON:red, Alarm OFF:green) 6: PV limit (Within PV range:green, Out of PV range:red) 7: PV limit (Within PV range:red, Out of PV range:green)
OFF (0)
1 1: PV high limit (energized, no stand-by action) 2: PV low limit (energized, no stand-by action) 9: PV high limit (de-energized, no stand-by action) 10: PV low limit (de-energized, no stand-by action) 11: PV high limit (energized, stand-by action) 12: PV low limit (energized, stand-by action)
2 19: PV high limit (de-energized, stand-by action)
20: PV low limit (de-energized, stand-by action) 21: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
1
22: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns off, the retransmission output is set to 0%, the alarm
2
output is set to OFF, and the indicator stops.
See List of Alarm Types for details on how these Alarm Type parameters behave.
0.0 to 100.0% of PV input range span
0.5% of PV input range span
Hysteresis can be set in the alarm setpoint. Setting hysteresis prevents relays from chattering.
Hysteresis setting for PV high limit alarm
Output
An alarm is output when the delay timer expires
Point of on-off action
On
Off
(Alarm setpoint)
Hysteresis
PV value
Output alarms
0.5%
0.00
after the alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm­1 type AL1 is 1, 2, 9, 10, 11, 12, 19, and 20)
User Setting
(DY2)
(DY3)
(DY4)
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 delay timer
PV
Alarm setpoint
Hysteresis
onoff
Time
Alarm output
Delay timer
Delay timer
0.00 to 99.59 (min, sec.) (enabled when alarm­2 type AL2 is
1, 2, 9, 10, 11, 12, 19, and 20
)
0.00 to 99.59 (min, sec.) (enabled when alarm­3 type AL3 is
1, 2, 9, 10, 11, 12, 19, and 20
)
0.00 to 99.59 (min, sec.) (enabled when alarm­4 type AL4 is
1, 2, 9, 10, 11, 12, 19, and 20
)
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
5-4
Parameter
Symbol
(P.SL)
(BPS)
(PRI)
(STP)
(DLN)
(ADR)
(RP.T)
(TEST)
Name of Parameter
Protocol selection
Baud rate
Parity 0: None
Stop bit 1, 2
Data length
Address 1 to 99
Minimum response time
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
Caution: Do not change the setpoint of the TEST parameter, otherwise the indicator will be disabled.
Setting Range and Description Initial Value
0: PC link communication 1: PC link communication (with sum check) 2: Ladder communication 7: MODBUS (ASCII) 8: MODBUS (RTU)
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
1: Even 2: Odd
7, 8 Fixed at 7, when the P.SL parameter is set to MODBUS (ASCII). Fixed at 8, when the P.SL parameter is set to MODBUS (RTU) or Ladder Communication.
However, the maximum number of stations connectable is 31.
0 to 10 ( 10 ms)
User Setting
0
4
1
1
8
1
0
Input-/Output-related Parameters
Parameter
Symbol
(IN)
(UNIT)
(RH)
(RL)
(SDP)
(SH)
(SL)
(BSL)
(RJC)
(ERJC)
Name of Parameter Setting Range and Description Initial Value
PV input type (PV INPUT terminals)
131211
- - terminals PV input unit °C (0): degree Celsius
Max. value of PV input range
Min. value of PV input range
PV input decimal point position (displayed at voltage input)
Max. value of PV input scale (displayed at voltage input)
Min. value of PV input scale (displayed at voltage input)
Selection of PV input burnout action
Presence/absence of PV input reference junction compensation
External RJC setpoint -50.0 to 50.0 C
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56 See Instrument Input Range Codes in 2. Initial Settings.
°F (5): Fahrenheit
Set the PV input range, however RL < RH
-Temperature input Set the range of temperature that is actually indicated.
- Voltage input Set the range of a voltage signal that is applied. The scale across which the voltage signal is actually indicated should be set using the parameters Maximum Value of PV Input Scale (SH) and Minimum Value of PV Input Scale (SL).
0 to 3 Set the position of the decimal point of voltage­mode PV input. 0: No decimal place 1: One decimal place 2, 3: Two, three decimal places
-1999 to 9999, however SL < SH Set the read-out scale of voltage-mode PV input.
OFF (0) 1: Up scale 2: Down scale
OFF (0), ON (1) ON (1)
-58.0 to 122.0 F
OFF (0)
°C (0)
Max. value of instrument input range
Min. value of instrument input range
1
100.0
0.0
1
0.0 C
32.0 F
User Setting
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
5-5
Parameter
Symbol
(RET)
(RTH)
(RTL)
(DIS)
(C.S1)
(C.S2)
(C.S3)
(C.S4)
(LOCK)
(PWD)
Name of Parameter Setting Range and Description Initial Value
Retransmission output type
Max. value of retransmission output scale
Min. value of retransmission output scale DI function selection 1
SELECT display-1 registration
SELECT display-2 registration
SELECT display-3 registration
SELECT display-4 registration
Key lock
Password setting 0: Password not set
1: PV 2, 3: Do not use 4: Loop power supply for sensor (15 V)
RET=1: RTL + 1 digit to 100.0% of PV input range
RET=1: 0.0% of PV input range to RTH - 1 digit
OFF (0): The external contact input is disabled. 1: Resets the values of the PEAK and BOTM
operating parameters to an off-to-on transition of the DI1 input.
OFF (0), 201 to 1015 For example, registering 231 for C.S1 allows you to change alarm-1 setpoint in operating display.
Numbers for registering alarm SP parameter for operating display: Alarm-1 setpoint: 231 Alarm-2 setpoint: 232 Alarm-3 setpoint: 233 Alarm-4 setpoint: 234
OFF (0): No key lock 1: Change to any parameter prohibited
Prohibits any operating parameter or setup parameter from being changed. The setpoint of the LOCK parameter itself can be changed, however.
2: Change to and display of operating parameters
prohibited Turns off the display for setting operating parameters, thus prohibiting any change to the parameter settings. (Press the SET/ENT key for more than 3 seconds to show the password check display.)
1 to 9999
1
100.0% of PV input range
0.0% of PV input range
OFF (0)
OFF (0)
0
User Setting
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
List of Alarm Types
The table below shows the alarm types and alarm actions. In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with stand-by actions.
5-6
Alarm action
Alarm type
Open/close shows status of relay contact, and lit and unlit shows status of lamp
No alarm OFF
Hysteresis
PV high limit
PV low limit
Fault diagnosis output (Note 1) FAIL output (Note 2)
Open (unlit)
Closed (lit)
Alarm setpoint
PV
Hysteresis
Alarm setpoint PV
Closed (lit)
Open (unlit)
Contact
closes
if alarm
occurs
1
11
2
12
Contact
opens
if alarm
occurs
Alarm type
Open/close shows status of relay contact, and lit and unlit shows status of lamp
De-energized
on PV high limit
De-energized
on PV low limit
Note 1: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
Note 2: FAIL output
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
Stand-by Action
C
Treated
Normal Abnormal
as normal
It is effective in the following cases where;
- the power is turned on
- the alarm type is changed
The alarm output does not turn on in this region even if the PV value is below the low limit of the alarm setpoint.
Closed
(unlit)
Hysteresis
Open (lit)
Alarm setpoint
The alarm
output turns on.
Alarm action
Hysteresis
PV
Alarm setpoint
Open (lit)
Closed
(unlit)
PV
Low limit of alarm setpoint
Alarm type codeAlarm type code
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
9
19
10
20
2221
Power-on
Time
Behavior of the PV High-limit Alarm Parameter (Alarm Type Code: 1)
PV value
Alarm
setpoint
Alarm
contact output
OffOff On
Alarm hysteresis
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
Functions of Active Color PV Display
This part describes the functions of Active Color PV Display. PV display color is changed by the following four actions.
PV display is selectable from red-to-green or green-to-red changing action, or fixed color. Link to alarm 1 mode (when PCMD = 2, 3) (Setting example-1) Link to alarm 1 and 2 mode (when PCMD = 4, 5) is the same. When either of the alarms
occurs, the display color is changed. PV limit mode (when PCMD = 6, 7) (Setting example-2) Fixed color mode (when PCMD = 0, 1) (Setting example-3)
Setting Example-1 : Link to Alarm
Works linked to alarm 1. Set PV high limit alarm for alarm 1 type, and 80°C for alarm 1 setpoint. If PCMD (PV color mode parameter) = 2, PV display color is changed from green to red when PV input value exceeds alarm 1 setpoint. The red-to-green changing action is selectable. Setting parameters PCMD (PV color mode parameter) = 2 AL1 (Alarm 1 type parameter) = 1 A1 (Alarm 1 setpoint parameter) = 80°C HY1 (Alarm 1 hysteresis parameter) = 5°C
°C
5-7
Alarm 1 setpoint A1=80°C
75°C
PV
PV : green PV : green
PV : red
Setting Example-2 : Link to PV
Set high limit 70°C for PCCH, and low limit 20°C for PCCL. PV display color is changed from green to red when PV input value is out of the range. The red-to-green changing action is selectable. Setting parameters PCMD (PV color mode parameter) = 6 PCCH (High limit for PV color change parameter) = 70°C PCCL (Low limit for PV color change parameter) = 20°C Hysteresis fixed to 0.25% is inserted where PV display color is changed. In the example blow, where changed from red to green.
°C
High limit for PV color change parameter PCCH = 70°C
70°C
Low limit for PV color change parameter PCCL = 20°C
20°C
PV
Alarm 1 hysteresis
Time
PV : red
PV : green
PV : red
Time
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
Setting Example-3 : Fixed in Red or Green
Set the PV display color or Fixed in green mode, Setting of Fixed to red mode is also possible. Setting parameter PCMD (PV color mode parameter) = 0
PV : green
External RJC
External RJC is not a compensation function built in a indicator but a compensation func­tion working outside the indicator.
External RJC is used when input is thermocouple, and RJC=OFF. Using External RJC makes the accuracy of RJC higher and shortens the compensating
wire.
5-8
Parameter
Symbol
(ERJC)
Furnace
Furnace
Name of Parameter Setting Range Initial Value
External RJC setpoint
-50.0 to 50.0°C, -58.0 to 122.0°F For thermocouple input, temperature compensation value outside the indicator can be set. Available only when RJC=OFF.
0.0°C
32.0°F
UM351/UM331
Terminal block
Thermocouple
Compensating wire
UM351/UM331
Terminal block
Thermocouple
Compensating wire
Normal wiring
Example : Setting parameters RJC = OFF ERJC = 25.0°C
Installed in an area where ambient temperature is fixed.
Set the temperature in the area using ERJC parameter.
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Toc> <5. Parameters>
Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to change settings easily. A maximum of four displays can be regis­tered.
Useful
operating display
(SELECT display)
Ordinary operating
displays (example)
5-9
PV
AL1234
SET/ENT
PV display
SET/ENT
PV
AL1234
key
SET/ENT
Alarm-1 setting
display (example)
SET/ENT
key
<Setting Method>
Set the parameter numbers (D register numbers) you wish to register for setup parameters C.S1 to C.S4.
Numbers for Registration with SELECT Display
Operating Parameter Registration Number Alarm-1 setpoint (A1) Alarm-2 setpoint (A2) Alarm-3 setpoint (A3) Alarm-4 setpoint (A4) Bias (BS) 243 Filter (FL) 244
231 232 233 234
Setup Parameter Registration Number Alarm-1 hysteresis Alarm-2 hysteresis Alarm-3 hysteresis Alarm-4 hysteresis
919 920 921 922
For any registration number other than those above, see Users Manual (Reference) (CD­ROM version).
IM 05F01D12-41E 4th Edition: May 31, 2006-00
<Int> <Toc>

Revision Information

Title : Models UM351/UM331 Digital Indicator with Alarms Users Manual
Manual No. : IM 05F01D12-41E
May 2003/1st Edition
Newly published
Sep 2003/2nd Edition
Complies with safety and EMC standards.
Jul 2004/3rd Edition
Change of the company name
May 2006/4th Edition
Revision by the change of safety standard description
i
Written by Yokogawa Electric Corporation
Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN
IM 05F01D12-41E 4th Edition: May 31, 2006-00
YOKOGAWA ELECTRIC CORPORATION Network Solutions Business Division
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN Phone: +81-422-52-7179 Facsimile: +81-422-52-6793
Sales Branch Offices
Tokyo, Nagoya, Osaka, Hiroshima, Fukuoka
YOKOGAWA CORPORATION OF AMERICA Headquaters
2 Dart Road, Newnan, GA. 30265-1094 U.S.A. Phone: +1-770-253-7000 Facsimile: +1-770-251-0928
Sales Branch Offices / Texas, Chicago, Detroit, San Jose
YOKOGAWA EUROPE B. V. Headquaters
Databankweg 20, 3821 AL Amersfoort THE NETHERLANDS Phone: +31-334-64-1611 Facsimile: +31-334-64-1610 Sales Branch Offices / Houten (The Netherlands), Wien (Austria), Zaventem (Belgium), Ratingen (Germany), Madrid (Spain), Bratislava (Slovakia), Runcorn (United Kingdom), Milano (Italy), Velizy villacoublay(France), Johannesburg(Republic of South Africa)
YOKOGAWA AMERICA DO SUL S.A. Headquarters & Plant
Praca Acapulco, 31-Santo Amaro, Sao Paulo/SP, BRAZIL CEP-04675-190 Phone: +55-11-5681-2400 Facsimile: +55-11-5681-4434
YOKOGAWA ENGINEERING ASIA PTE. LTD. Head office
5 Bedok South Road, Singapore 469270 SINGAPORE Phone: +65-6241-9933 Facsimile: +65-6241-2606
YOKOGAWA ELECTRIC KOREA CO., LTD. Seoul Sales office
395-70, Shindaebang-dong, Dongjak-gu, Seoul,156-010, KOREA Phone: +82-2-3284-3000 Facsimile: +82-2-3284-3019
YOKOGAWA TAIWAN CORPORATION Head office
17F, No.39, Sec. 1, Chung Hwa Road Taipei, 100 TAIWAN Phone: +886-2-2314-9166 Facsimile: +886-2-2314-9918
YOKOGAWA AUSTRALIA PTY. LTD. Head office
Centrecourt D1, 25-27 Paul Street North, North Ryde, N. S. W. 2113, AUSTRALIA Phone: +61-2-9805-0699 Facsimile: +61-2-9888-1844
YOKOGAWA INDIA LTD. Head office
40/4 Lavelle Road, Bangalore, 560 001, INDIA Phone: +91-80-227-1513 Facsimile: +91-80-227-4270
LTD. YOKOGAWA ELECTRIC
Grokholskiy per. 13, Build. 2, 4th Floor, 129010, Moscow, RUSSIA FEDERATION Phone: +7-095-737-7868 Facsimile: +7-095-737-7869
Loading...