Yokogawa UM330 Data sheet

Page 1
<<Contents>> <<Index>>
General Specifications
MODEL UM330 Digital Indicator with Alarms
GS 05F01D02-02E
General
Model UM330 Digital Indicator with Alarms is a precision alarm instrument with universal input 1/8DIN. For excellent monitoring operability, it displays process variables on a large display. It is also provided with four alarm setting points (or setting outputs; one is optional). A retransmission output and 15 V DC loop power supply are provided as standard. A communication fanction or 24 V DC loop power supply is available optionally.
Main Features
• Extra-large digital display allows the indicated values to be read even from a long distance. LEDs of 20mm height are used for the process variable display.
• Universal input allows simple setting of the input types (TC, RTD, DCV) or input measuring range.
• Various communication function are provided. Communication is possible with personal computer and programable logic controller.
Function Specifications
Signal Computation Function
Measured input computation:
Contact input: Retains and displays maximum and
Bias addition (-100.0 to 100.0% of measured input range width.), first-order lag filter (time constant off, 1 to 120 s.)
minimum readings from measured variable. Resets the maximum and minimum readings.
UM330
UM330E
“E” indicates the model with expanded functions.
Alarm Function
Six different types of alarms are provided. If an alarm occurs, the alarm lamp indicates it. Four (one is optional) of the six can be used as relay contact outputs.
Alarm types:
PV high limit, PV low limit, Deenergized on PV high limit, Deenergized on PV low limit, Fault diagnosis, and FAIL output
Setting ranges for process variable alarms:
PV alarms; -100.0 to 100.0% of measured input range. Alarm hysteresis width; 0.0 to 100.0% of measured input
range width.
Delay timer:
0.00 to 99.59 (minute, second) An alarm is output when the delay timer expires after the alarm setpoint is reached. Setting for each alarm is possible.
Fault diagnosis alarm: Input burn out, A/D conversion
error, TC RJC error FAIL output: Software failure, hardware failure Stand-by action:
Stand-by action can be set to make PV alarm OFF during start-up.
Display and Operation function
PV display:
Parameter display:
Status display: 4 alarm LEDs (AL1, AL2, AL3, AL4) Operation keys: and keys: Increase/decrease
SET/ENT key: Sets setpoint data, calls or switches
4-digit digital display for engineering data
4-digit digital display for various data,
including parameters
setpoints or various parameters.
various parameters.
GS 05F01D02-02E
©Copyright Feb. 2000
Page 2
<<Contents>> <<Index>>
2
SELECT display:
Allows selection and registration of frequently changed parameters from the operation parameters during operation. For example, if the first alarm setpoint is registered in the SELECT display, the setpoint can easily be displayed during operation.
Security function:
An operation inhibiting mode using a password is provided.
Communication Functions (optional)
The communication function, provided with the instrument, allows connection to a personal computer, and programmable logic controller.
Communication protocol
Computer link communication:
Communication protocol with a personal computer
LED display unit (for PV)
Display PV, and error code when error is detected.
Ladder communication:
Communication protocol with program­mable logic controller.
MODBUS Communication:
Communication protocol with a personal computer or PLC.
Communication interface
Communication protocol:
Computer link, ladder communication or
MODBUS communication Standard: EIA RS485 Maximum number of connectable controllers:
31 GREEN series controllers Maximum communication distance: 1,200 m Communication method:
Two-wire half duplex, or four-wire half
duplex, start-stop synchronization system,
protocol free Communication rate: 600, 1200, 2400, 4800, 9600 bps
Status lamps
Indicate alarm status (AL1, 2, 3, 4).
Operational keys
LED display unit
Display setting item/value of parameters.
Increase/Decrease the setting data (, ) Select parameter/Enter the setting data (SET/ENT)
Sample Structures of Communication Systems Configuration Diagram
(1) Computer link communication/MODBUS communication (2) Ladder communication
Personal computer
PV
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
UM350/UM330 Digital indicator with Alarms
PV
PV2
PV2
AL
AL
1
1
2
2
3
3
REM
REM
4
4
MAN1
MAN1
MAN2
MAN2
STP
STP
CAS
CAS
A/M
A/M
DISP
DISP
SET/ENT
SET/ENT
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
MELSEC-A
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
SET/ENT
UM350/UM330 Digital indicator with Alarms
PLC
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
DISP
SET/ENT
PV
PV2
AL
1 2 3
REM
4
MAN1 MAN2 STP CAS
A/M
DISP
SET/ENT
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation
GS 05F01D02-02E 1st Edition Mar.31,2000-00
Page 3
<<Contents>> <<Index>>
3
Hardware Specifications
Measured input signal
Number of inputs: 1 Input type, measurement range, and measurement
accuracy: The type of input and measurement range can be specified using the input range code shown in the table below by front key operation or
communication. Sampling period: 250ms Burnout detection:
Available with TC, RTD, standard signal, 0.4
to 2V DC and 1 to 5V DC.
Up-scale, down-scale, and off can be set.
For standard signal, an input of 0.1V or less is
regarded as burnout. Input bias current: 0.05 µA (for TC and RTD b-terminal) Measuring current(RTD): about 0.13mA Input resistance:
TC/mV: 1 M or more DC voltage input: Approximately 1 M
Allowable signal source resistance:
Allowable leadwire resistance:
Allowable input voltage:
Noise rejection ratio:
Reference-junction compensation error:
Applicable standard: For TC and RTD, JIS, IEC, DIN(ITS-
Effect from allowable signal source resistance:0.1 µV/ or less DC voltage input: 2 k or less Effect from allowable signal source resistance:
0.01%/100 or less
RTD 150/wire or less (provided that there is no variation between the three wires.) For the range of -150.0 to 150.0, 10Ω/wire Effect from allowable leadwire resistance: ±0.1°C/10 or less
TC/mV/RTD ±10V DC DC voltage ±20V DC
Normal mode 40dB (50/60Hz) or more Common mode 120dB (50/60Hz) or more
±1.0°C (15 to 35 °C), ±1.5°C (0 to 15°C, 35 to 50°C)
90)
TC/mV input: 250Ω or less
Input Type
Unspecified(when shipped from the factory) Thermocouple
RTD
Standard signal
DC voltage
K
J
T
B
S R N
E L (DIN)
U (DIN)
W (DIN) Platinel 2 PR20-40
W97Re3-W75Re25 JPt100
Pt100
0.4 to 2V 1 to 5V 0 to 2V 0 to 10V
-10 to 20mV 0 to 100mV
Input range
code
OFF
1 2 3 4 5 6 7
8 9
10
11 12 13 14 15 16 17
18 30 31 35 36 37 40 41 50 51 55 56
Note 1 : The accuracy is ±0.3°C of instrument range ± 1 digit for a temperature range from 0 to 100°C Note 2 : The accuracy is ±0.5°C of instrument range ±1 digit for a temperature range from -100 to 200°C. *1 Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/60 Hz power frequency)
Instrument
range (˚C)
Set the data item PV input Type "IN" to the OFF option to leave the PV input type undefined.
-200 to 1370˚C
-199.9 to 999.9˚C
-199.9 to 500.0˚C
-199.9 to 999.9˚C
-199.9 to 400.0˚C
0.0 to 400.0˚C 0 to 1800˚C
0 to 1700˚C 0 to 1700˚C
-200 to 1300˚C
-199.9 to 999.9˚C
-199.9 to 900.0˚C
-199.9 to 400.0˚C
0.0 to 400.0˚C 0 to 2300˚C 0 to 1390˚C 0 to 1900˚C
0 to 2000˚C
-199.9 to 500.0˚C
-150.0 to 150.0˚C
-199.9 to 850.0˚C
-199.9 to 500.0˚C
-150.0 to 150.0˚C
0.400 to 2.000
1.000 to 5.000
0.000 to 2.000
0.00 to 10.00
-10.00 to 20.00
0.0 to 100.0
Instrument
range (˚F)
-300 to 2500˚F 0 to 2300˚F
-199.9 to 999.9˚F
-300 to 2300˚F
-300 to 750˚F
-199.9 to 750.0˚F 32 to 3300˚F
32 to 3100˚F 32 to 3100˚F
-300 to 2400˚F
-300 to 1800˚F
-300 to 1300˚F
-300 to 750˚F
-199.9 to 750.0˚F 32 to 4200˚F 32 to 2500˚F 32 to 3400˚F
32 to 3600˚F
-199.9 to 999.9˚F
-199.9 to 300.0˚F
-300 to 1560˚F
-199.9 to 999.9˚F
-199.9 to 300.0˚F
Scaling is enable in the following 4 range.
-1999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999
At or above 0˚C ±0.1% ±1 digit of F.S. Below 0˚C, ±0.2% ±1 digit of F.S.
At or above 400˚C ±0.15% ±1 digit of F.S. Below 400˚C ±5% ±1 digit of F.S.
±0.15% ±1 digit of F.S.
±0.1% ±1 digit of F.S.
Below 0˚C ±0.25% ±1 digit of F.S. At or above 0˚C ±0.1% ±1 digit of F.S. Below 0˚C ±0.2% ±1 digit of F.S.
±0.2% ±1 digit of F.S. ±0.1% ±1 digit of F.S.
At or above 800˚C ±0.5% ±1 digit of F.S. Below 800˚C, not guaranteed
±0.2% ±1 digit of F.S. (Note1) (Note2) ±0.1% ±1 digit of F.S. (Note1) ±0.2% ±1 digit of F.S. (Note1) (Note2) ±0.1% ±1 digit of F.S. (Note1)
±0.2% ±1 digit of F.S. ±0.1% ±1 digit of F.S.
Measurement accuracy
*1
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation GS 05F01D02-02E 1st Edition Mar.31,2000-00
Page 4
<<Contents>> <<Index>>
4
24V DC Loop Power Supply for Sensor
Supplies power to the 2-wire transmitter. A resister (10 to 250) is to be placed between the alarm unit and transmitter. Current signals are converted into voltage signals, and read through the process input.
Supply voltage is 21.6 to 28.0V DC, maximum supply current is about 30mA (only for models with 24V DC loop power supply).
24 V DC Power Supply Wiring to Two-wire Sensor
250
12
PV input
1 to 5 V DC signal
13
21
Loop power
28.0 V DC
22
supply
21.6 to
External resistor (Note)
Two-wire transmitter
4-20mADC
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Retransmission Output
Either PV or target set point is output. Either this or the 15V DC loop power supply is available.
Number of output point: 1 Output signal: 4 to 20mA DC On-load resistance: 600 or less Output accuracy: ±0.3% of the span
Performance in the standard operating conditions (at 23±2°C, 55±10% RH, and 50/
60 Hz power frequency) 15V DC loop power supply: Power supply voltage 14.5 to 18.0V DC; maximum
supply current approximately 21mA. (Safety
circuit against short-circuiting in the field)
Contact Input
Usage: Resets the displayed maximum and minimum Number of inputs: 1 point
Input type: Non-voltage contact input or transistor open Input contact capacity: 12V DC, 10mA or more (for non­On/off determination:
Minimum retention time for status detection: about 1 s.
process variables.
collector input
voltage contact input)
For non-voltage contact input,
ON = contact resistance of 1k or less,
OFF = contact resistance of 20k or more.
For transistor contact input,
ON = 2V or less,
OFF = leak current of 100µA or less.
Contact Outputs
Usage: Alarm output, FAIL output Number of relay contact outputs:
Alarm -1 to -3 relay contact rating: Alarm -4 relay contact rating:
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation
4 points (The alarm -4 is optional)
240V AC 1A, or 30V DC 1 A, make contact
250V AC 3 A, or 30V DC 3 A (load resis-
tance)
Output signal: 3 terminals (NC, NO,
Common), transfer contact
Display Unit Specifications
Process variable display unit:
Parameter display:
Status indicating lamps: LEDs
4-digit 7-segment red LED, each digit 20 mm in height
4-digit 7-segment red LED, each digit 9.3 mm in height
Conformance to Safety and EMC standards
Safety standard:
EMC standards:
Conforms to IEC1010-1: 1990 and EN61010-1: 1992. Certified for CSA1010, The overvoltage category of each input is CAT II (IEC1010-1) Certified for UL 508
Conforms to the following EMC standards. During evaluation, the instrument operates with the measuring accuracy within ±20% of the range. EMI (Emission) EN61326-1: 1997+Am1:1998 EMS (immunity) EN61326-1: 1997+Am1:1998
Construction/Installation/Wiring
Structure: Dust-proof and Drip-proof front panel Body construction: ABS resin and polycarbonate
Case color: Black Weight: Approximately 1 kg or less Dimensions: 96W × 48H × 100D (from the front panel)
Mounting: Direct panel mounting; mounting bracket, one Panel cutout dimensions:
Mounting attitude: Up to 30 degrees above the horizontal. Wiring: M3.5 screw terminal (signals, power supply/
conforming to IP55.
(mm) each for right and left mounting.
92
+0.8
0
(W) ×
45
+0.6
0
No downward tilting allowed. ground)
(H) mm
Power supply / Isolation
Power supply: Voltage rating at 100 to 240V AC (±10%), Power consumption: MAX. 20VA (MAX. 8.0W)
Memory backup: Non-volatile memory (Service life Withstanding voltage:
Between primary terminal and secondary terminal: Between primary terminal and ground terminal: Between ground terminal and secondary terminal: Between two secondary terminal:
Note. The withstanding voltage is specified as 2300V AC
Isolation resistance: Between power supply terminal and Ground: Class 3 grounding (grounding resistance of Isolation specifications
Measured input terminal:
24V DC loop power supply terminals for sensor:
50/60 Hz
approx. 1000,000 times of writings)
1500V AC for 1 min. (Note) 1500V AC for 1 min. (Note) 1500V AC for 1 min.
500V AC for 1min
Primary terminal:
Power supply, relay output
Secondary terminal:
Analog input/output signal terminals, contact input terminal
perminute to provide amargin of safety .
ground terminal, 500V DC 20M or more 100 or less)
Isolated from other input/output terminals. Not isolated from the internal circuit.
Isolated from other input/output terminals and internal circuit.
GS 05F01D02-02E 1st Edition Mar.31,2000-00
Page 5
<<Contents>> <<Index>>
5
Retransmission output terminal:
Contact input terminal:
Relay contact output terminal:
RS-485 communication terminals:
Power supply terminal:
Ground terminal:
Isolated from other input/output terminals and internal circuit.
Not isolated from communication terminals. Isolated from other input/output terminals and internal circuit.
Isolated from other input/output terminals and internal circuit.
Not isolated from contact input terminals. Isolated from other I/O terminals and internal circuit.
Isolated from other input/output terminals, and internal circuit.
Isolated from other input/output terminals, and internal circuit.
Environmental conditions
Normal operating conditions:
Ambient temperature: 0 to 50°C
Ambient temperature change limit: 10°C /h or less Ambient humidity: 20 to 90% RH (non-condensing) Magnetic field: 400 A/m or less Continuous vibration (5 to 14 Hz):
Continuous vibration (14 to 150 Hz): Short-period vibration: 14.7 m/s2, 15 s. or less
Shock: 147 m/s2 or less, 11 ms. Installation altitude:
Warm-up time: 30minutes or more
Transit/storage conditions
Temperature: -25° to 70°C Temperature change limit: 20°C /h or less Humidity: 5 to 95% RH (non-condensing)
Effects on operating conditions
Effect of ambient temperature:
Effect on power supply flactuation (within rated voltage
0 to 40°C when using 24V DC loop power supply for sensor
Amplitude of 1.2 mm or less
4.9 m/s2 or less
2,000 m above sea level maximum
For voltage/TC input, within ±1µV/°C and ±0.01% of F.S./°C, whichever is greater. For RTD input, within ±0.05 °C/°C (ambient temperature) For analog output, ±0.05% of F.S./°C or less
range): For analog input, within ±1 µV/10V and ±0.01% of F.S./10V, whichever is greater. For analog output, within ±0.05% of F.S./ 10V
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation GS 05F01D02-02E 1st Edition Mar.31,2000-00
Page 6
<<Contents>> <<Index>>
24 V DC Power Supply Wiring to Two-wire Sensor
15 V DC Power Supply Wiring to Two-wire Sensor
12
13
+
-
Note: Connecting a 250 resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on
terminal lugs)
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint 41).
Receiving 4-20 mA DC Current
Signals with the Indicator
250
4-20 mA
Installation category (overvoltage category): II (IEC1010-1)
NOTE
12
13
11
12
13
12
13
A
b
B
-
+
-
+
TC input
RTD input
mV/V input
6
5
4
7
AL1
AL2
AL3
COM
UM
16
17
Retransmission output
4-20 mA DC
16
17
15 V DC loop power supply
14.5-18.0 V DC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
Load resistance: 600
or less
* If 15 V DC loop power supply is used,
retransmission output cannot be used.
-
+
-
+
11
21
13
23
3
15
25
5
19
29
9
1
17
27
7
12
22
14
24
4
16
26
6
20
30
10
2
18
28
8
8
9
Power supply
10
L
N
Power supply
23
24
RS-485 communication
* Wiring can only be carried out
for indicators with communication
functions.
Maximum baud rate: 9600 bps
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
19
20
DI1
COM
Resets the PV
peak and bottom values
when DI1 is changed
from OFF to ON
.
Common
1
2
Relay contact output
3
Alarm-4 output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
* Wiring can only be carried out for
UM330-01 or UM330-02.
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
UM
* Wiring can only be carried out for indicators with 24 V DC
loop power supply.
12
13
14
15
Two-wire transmitter
PV input
0.4 to 2.0 V DC signal
Loop power
supply
14.5 to
18.0 V DC
External
resistor
(Note)
4-20 mA DC
Note: Connecting a 100 resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
100
12
13
21
22
Two-wire transmitter
PV input
1 to 5 V DC signal
Loop power
supply
21.6 to
28.0 V
DC
External
resistor
(Note)
4-20 mA DC
Note: Connecting a 250 resistor to the terminals is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
250 V
Contact input
Contact
Contact rating: 12 V DC, 10 mA Min.
DI1
COM
+5V
Transistor contact
19
20
* Wiring can only be carried out
for indicators with 24 V DC
loop power supply.
21
22
21.6-28.0 V DC
(30 mA DC max.)
+
-
24 V DC loop
power supply
Alarm output
Relay
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Allowable range: 100 to 240 V AC (10%)
(free voltage)
50/60 Hz shared
PV input
* Not configured at factory before shipment
6
Standard Type, Terminal Arrangements
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation
GS 05F01D02-02E 1st Edition Mar.31,2000-00
Page 7
<<Contents>> <<Index>>
External Dimensions and Panel Cutout Dimensions
7
45
(25)
+0.6
112
Unit: mm
Small bracket
91.8 Small bracket
96
48
10011
1 to 10 mm (Panel thickness)
Front of indicator
General installation
145 min.
70 min.
0
92
+0.8
0
(53)
Model and Suffix Codes
Model Suffix Code Description
UM330
Type
Optional functions
-0 Standard type with three alarms
-3
Digital indicator with Alarms (provided with retransmission output and 15 V DC loop power supply as standard)
Standard type with three alarms (with a 24 V DC loop power supply)
0 None 1 Communication and additional alarm-4 2 Additional alarm-4
Standard accessories: Brackets (mounting hardware), unit label, and Users Manuals,
Items to be Specified When Ordering
Model and suffix codes, necessary/unnecessary of Users Manual or QIC.
All Rights Reserved. Copyright © 2000, Yokogawa M&C Corporation GS 05F01D02-02E 1st Edition Mar.31,2000-00