YOKOGAWA UD350 User's Manual

User’ s Manual
GREEN Series User ’s Manual
- Detailed Instruction -
IM 05J01B02-01E
IM 05J01B02-01E
5th Edition
GREEN Series User’s Manual
- Detailed Instruction -
IM 05J01B02-01E 5th Edition

CONTENTS

Ref.1.1: References Related to PV Input ...................................................Ref. 1-1
Ref.1.1(1) Correcting the PV (1. Using PV input filter and PV input bias)............ Ref. 1-1
Ref.1.1(2) Correcting the PV (2.Using ten-segment linearizer biasing or
approximation)....................................................................................Ref. 1-4
Ref.1.1(3) Square-root extraction of PV ................................................................ Ref. 1-9
Ref.1.1(4) Changing the PV sampling period...................................................... Ref. 1-1 1
Ref.1.1(5) Checking that the changed PV sampling period is appropriate ....... Ref. 1-14
Ref.1.1(6) Correcting the input value from a sensor .......................................... Ref. 1-16
Ref.1.1(7) Using PV tracking function (UT only) .................................................Ref. 1-18
Ref.1.1(8) PV input range adjustment (When the UT/UP mode No. is 6, 7 or
12 only) ..............................................................................................Ref. 1-21
Ref.1.2: References Related to Remote Input......................................... Ref. 1-22
Ref.1.2(1) Setting remote input units, range and scaling................................... Ref. 1-23
Ref.1.2(2) Using square root extraction during remote input ............................ Ref. 1-27
Ref.1.2(3) Using remote setpoint filtering and ratio bias computing ................ Ref. 1-28
Ref.1.2(4)
Tracking target setpoint when switching from remote to local control .
Ref. 1-30
Ref.2.1: References Related to Control Output ........................................Ref. 2-1
Ref.2.1(1) Switching between Direct and Reverse Actions.................................. Ref. 2-2
Ref.2.1(2) Selecting PID Control Mode According to the Operating Condition ..Ref. 2-4
Ref.2.1(3) Using Control Output Limiter ...............................................................Ref. 2-8
Ref.2.1(4) Using Anti-reset Windup (Over-integration Prevention) Function ..... Ref. 2-9
Ref.2.1(5) Using “Super” (Overshoot Prevention) Function..............................Ref. 2-10
Ref.2.1(6) Using “Super2” (Hunting Prevention) Function ................................ Ref. 2-11
Ref.2.1(7) Using Split-signal Computation / Output Function ........................... Ref. 2-13
Ref.2.1(8) Setting Preset Output Values.............................................................. Ref. 2-16
Ref.2.1(9) Placing Control Output in Tracking Mode (for Cascade
Primary-loop Control or Loop Control for Backup) ........................ Ref. 2-18
Ref.2.1(10) Using Shutdown Function ................................................................ Ref. 2-19
Ref.2.2: References Related to Retransmission Output ........................ Ref. 2-20
Ref.2.2(1) Changing the type of retransmission output signal .......................... Ref. 2-21
Ref.2.2(2) Retransmitting Program Pattern 2 (for UP750/UP550 only) .............. Ref. 2-23
Ref.2.2(3) Using the Loop Power Supply Function ............................................ Ref. 2-24
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
Toc-ii
Ref.3.1: References Related to Contact Input........................................... Ref. 3-1
Ref.3.1(1) Changing contact input functions for the UT35h/UT32h.................... Ref. 3-2
Ref.3.1(2) Changing contact input functions for the UT450/UT420 .................... Ref. 3-5
Ref.3.1(3) Changing contact input functions for the UT550/UT551/UT520 ......... Ref. 3-9
Ref.3.1(4) Changing contact input functions for the UT750.............................. Ref. 3-14
(4-1): Changing contact input terminal assignments of the UT750 ............ Ref. 3-14
(4-2): Using contact I/O expansion module with the UT750 ...................... Ref. 3-18
(4-3): Using Interrupt-message functions with the UT750 ......................... Ref. 3-20
(4-4): Using Interrupt-operating display functions with the UT750............. Ref. 3-22
Ref.3.1(5) Changing contact input functions for the UP35h ............................. Ref. 3-24
Ref.3.1(6) Changing contact input functions for the UP550 ..............................Ref. 3-26
Ref.3.1(7) Changing contact input functions for the UP750 .............................Ref. 3-29
(7-1): Changing contact input functions for the UP750.............................. Ref. 3-29
(7-2): Using contact I/O expansion module with the UP750 ...................... Ref. 3-34
(7-3): Using Interrupt-message functions with the UP750......................... Ref. 3-36
(7-4): Using Interrupt-operating display functions with the UP750............. Ref. 3-39
Ref.3.2: References Related to Contact Output...................................... Ref. 3-40
Ref.3.2(1) Changing Contact Output Functions for the UT750, UT550, UT551
and UT520 .........................................................................................Ref. 3-41
(1) Single-loop control (UT mode 1).......................................................... Ref. 3-44
(2) Cascade, primary-loop control (UT mode 2)........................................ Ref. 3-45
(3) Cascade, secondary-loop control (UT mode 3) ................................... Ref. 3-45
(4) Cascade control (UT mode 4) ............................................................. Ref. 3-46
(5) Loop control for backup (UT mode 5) .................................................. Ref. 3-46
(6) Loop control with PV switching (UT mode 6) ....................................... Ref. 3-47
(7) Loop control with PV auto-selector (UT mode 7) ................................. Ref. 3-47
(8) Loop control with PV-hold function (UT mode 8).................................. Ref. 3-48
(9) Dual-loop control (UT mode 1 1 ) .......................................................... Ref. 3-48
(10) Temperature and humidity control (UT mode 12)............................... Ref. 3-48
(1 1) Cascade control with two universal inputs (UT mode 13)................... Ref. 3-49
Loop control with PV switching and two universal inputs (UT mode 14) ..
(12)
Loop control with PV auto-selector and two universal inputs (UT mode 15).
(13)
(14) Custom computation control (UT mode 21) ....................................... Ref. 3-49
Ref.3.2(2) Changing Contact Output Functions in the UP750 and UP550 ........Ref. 3-50
(1) Single-loop control (UP mode 1) ......................................................... Ref. 3-51
(2) Cascade, primary-loop control (UP mode 2)........................................ Ref. 3-52
(3) Cascade control (UP mode 4) ............................................................. Ref. 3-53
(4) Loop control with PV switching (UT mode 6) ....................................... Ref. 3-53
(5) Loop control with PV auto-selector (UP mode 7) ................................. Ref. 3-54
(6) Dual-loop control (UP mode 1 1) This function is for the UP750 only..... Ref. 3-55
(7) Temperature and humidity control (UP mode 12)
This function is for the UP750 only . .......................................... Ref. 3-55
Ref. 3-49 Ref. 3-49
IM 05J01B02-01E
5th Edition : Mar.25,2005-00
Toc-iii
(8) Cascade control with two universal inputs (UP mode 13) .................... Ref. 3-56
Loop control with PV switching and two universal inputs (UP mode 14) ....
(9) (10)
Loop control with PV auto-selector and two universal inputs (UP mode 15).
(1 1) Custom computation control (UP mode 21) ....................................... Ref. 3-56
Ref.3.2(3) Using the I/O Expansion Module with UT750 and UP750 .................. Ref. 3-57
Ref.3.3: References Related to Alarms ................................................... Ref. 3-62
Ref.3.3(1) Setting Alarm T rigger Conditions....................................................... Ref. 3-63
Ref.3.3(2) Setting Alarm hysteresis ON/OFF range............................................ Ref. 3-65
Ref.3.3(3) Using the alarm timer (Control stable signal event) .......................... Ref. 3-67
Ref.3.3(4) Using the sensor ground alarm .......................................................... Ref. 3-70
Ref.3.3(5) Using the heater burnout alarm (UT35u and UT32u only)................. Ref. 3-75
Ref.3.4: References Related to Instrument Alarms and Events............. Ref. 3-77
Ref.3.4(1) Using Instrument Alarms .................................................................... Ref. 3-78
Ref.3.4(2) Setting the Operating Conditions of Instrument Alarms................... Ref. 3-83
Ref.3.4(3) Setting Hysteresis (On-off Bandwidth) of an Instrument Alarm ....... Ref. 3-84
Ref.3.4(4) Using the Sensor Ground Alarm.........................................................Ref. 3-86
Ref.3.4(5) Using PV Events ..................................................................................Ref. 3-90
Ref.3.4(6) Using Time Events ..............................................................................Ref. 3-97
Ref.3.4(7) Using Local Events ...........................................................................Ref. 3-101
Ref. 3-56 Ref. 3-56
Ref.4.1: References Related to T arget Setpoints...................................... Ref. 4-1
Ref.4.1(1) Using Multiple T arget Setpoints (8 Max.).............................................. Ref. 4-2
Ref.4.1(2) Selecting PID selection method (T arget SP selection, Zone PID or
Selection by specified PID number)................................................. Ref. 4-10
Ref.4.1(3) Limiting Changes in T arget Setpoints................................................ Ref. 4-17
Ref.4.1(4) Setting ramp grades when switching between target setpoints ......Ref. 4-18
Ref.5.1: References Related to Segment Operation................................. Ref. 5-1
Ref.5.1(1) Selecting Segment time between Time and Ramp time ...................... Ref. 5-1
Ref.5.1(2) Selecting PID control between Zone and Segment .............................Ref. 5-7
Ref.5.2: References Related to Program Setup ...................................... Ref. 5-10
Ref.5.2(1) Selecting Program Start Condition ....................................................Ref. 5-10
Ref.5.2(2) Using the Delayed Start Timer for Programmed Operation .............. Ref. 5-17
Ref.5.2(3) Selecting Segment-end Condition .....................................................Ref. 5-18
Ref.5.2(4) Using the Wait Function......................................................................Ref. 5-24
Ref.5.2(5)
Ref.5.2(6) Using the Repeat Functions ...............................................................Ref. 5-34
Ref.5.2(7) Using the Advance Functions.............................................................Ref. 5-37
Ref.5.2(8) Signal Output at Program end ............................................................Ref. 5-39
Ref.5.2(9) Operation in Local Mode (with Constant T arget Setpoint) ................ Ref. 5-41
Ref.5.2(10) Starting the Program Operation at Any Segment ............................ Ref. 5-44
Ref.5.2(11) Operation with Linked Program Patterns (Pattern-link) .................. Ref. 5-46
Using the Hold Functions (Changing Segment Setpoint in Hold Status)
Ref. 5-30
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
Toc-iv
Ref.5.3: Handy Features for Creating and Editing Programs................. Ref. 5-48
Ref.5.3(1) Checking the T otal Number of Unused Segments.............................Ref. 5-48
Ref.5.3(2) Checking the number of segments in a specific Program Pattern ... Ref. 5-50
Ref.5.3(3) Checking the number of all unused events ....................................... Ref. 5-51
Ref.5.3(4) Copying Program Patterns ................................................................. Ref. 5-53
Ref.5.3(5) Deleting Program Patterns .................................................................Ref. 5-55
Ref.5.3(6) Adding (Inserting)/Deleting segments in Program Patterns............. Ref. 5-57
Ref.6.1: References Related to Displays................................................... Ref. 6-1
Ref.6.1(1) Using SELECT Displays........................................................................ Ref. 6-2
Ref.6.1(2) Changing Contents of Deviation Trend Display (for UP750, UP550
and UT750 only) .................................................................................. Ref. 6-5
Ref.6.1(3) Changing Deviation Display Range of Deviation Monitor
(for UT750, UT550, UT551 and UT450 only) .......................................Ref. 6-7
Ref.7.1: References Related to Security ...................................................Ref. 7-1
Ref.7.1(1) Setting a password to prevent unauthorized changes to
setup parameters................................................................................ Ref. 7-1
Ref.7.1(2) Using the keylock function to prevent unauthorized key operation... Ref. 7-2
Ref.8.1: Outline of Registers and I - relays................................................Ref. 8-1
Ref.8.1(1) Outline of Registers and I - relays ........................................................Ref. 8-2
Ref.8.1(2) D-register Outline and D-register Map .................................................Ref. 8-3
UP750,UP550 D-register Map.................................................................... Ref. 8-4
UP35 D-register Map .............................................................................. Ref. 8-8
UT750, UT55, UT520 D-register Map.................................................... Ref. 8-12
UT450,UT420 D-register Map .................................................................. Ref. 8-16
UT35, UT32 D-register Map .............................................................. Ref. 8-19
Ref.8.1(3) B-register Outline and B-register Map ...............................................Ref. 8-23
UP750,UP550 B-register Map.................................................................. Ref. 8-24
Ref.8.1(4) I-relay Outline and I-relay Map ............................................................ Ref. 8-26
UP750, UP550 I-relay Map...................................................................... Ref. 8-28
Ref.8.1(5) I-relay Timer setting............................................................................. Ref. 8-33
Revision Information ............................................................................................ i
IM 05J01B02-01E
5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>

Ref.1.1: References Related to PV Input

Ref. 1-1
IMPORTANT
UP750 UP750-
Note: The functions discussed in this section apply to all the models of UT and UP series.
UP550 UP550-
However, some of the functions are unavailable with certain models. Such models, if any, will be clearly noted in each of the following items from (1) to (8).
UP35 UP35-
: Applicable models of this section
UT750 UT750-
UT5 UT55-
UT520-
UT40 UT450-
UT420-
UT3 UT35-
UT32-
These sections provide references related to PV input, such as PV correction, listed below. Only read the following descriptions if necessary and carry out the required operation.
(1) Correcting the PV (1. Using PV input filter and PV input bias) (2) Correcting the PV (2. Using ten-segment linearizer biasing or approximation) (3) Square-root extraction of PV (4) Changing the PV sampling period (5) Checking that the changed PV sampling period is appropriate (6) Correcting the input value from a sensor (7) Using PV tracking function (UT only) (8) PV input range adjustment (when the UT/UP mode No. is 6, 7 or 12 only)
UM3 None
<<Ref.1.1: References Related to PV Input>>

Ref.1.1(1) Correcting the PV (1. Using PV input filter and PV input bias)

Filtering and biasing functions are available with all the UT/UP series models.
PV input filtering can be used to remove noise from a PV input that contains high frequency noise,
such as flow rate and pressure signals.
The PV input filter provides first-order-lag computation. Setting a larger time constant (as a parameter value) can increase the amount of noise removed. This filtering is also used to improve controllability and for phase compensation. The time constant of the PV filter is offered as an operating parameter and can be changed during operation.
Actual input With a small time constant With a large time constant
Fig. 1-1-1
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-2
PV input biasing adds a constant bias value to the PV input value, and the result is used for the
controller display and control computation.
PV input value PV value inside the controllerPV input bias
+
=
In some cases, the measured value is smaller than the actual value by a constant amount due to the physical circumstances at the sensor point. For example, the ambient temperature inside a furnace is often measured instead of the material’s temperature. In such cases, add a constant value for biasing. When the PV value is within the allowable accuracy range but there is a dispersion in PV readings between other equipment, it is possible to use this function for fine adjustment.
The following parameters are used.
• Operating parameters (Operation-related parameters): BS and FL
UP750 UP550 UT750
Code
BS
FL
UT5 UT40
Code
(BS) (BS)
(FL) (FL)
UP35 UT3
Code
Description
PV input bias
PV input filter
Setting range
-100.0 to 100.0% of input range span
OFF or 1 to 120 s
Default
0.0% of input range span
OFF (No filtering)
D-register No.
243, 273(Note1)
244, 274(Note2)
Note1: For dual-loop control of UP750 and UT750, the D-register number of loop-2 BS is 273. Note2: For dual-loop control of UP750 and UT750, the D-register number of loop-2 FL is 274.
T o set the parameters, carry out the following steps.
For UP750, UP550, UT750, UT550, UT551, and UT520
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter.
1: Referring to the User’s Manual above, display
the operating parameter main menu [LP1] (Note1). Then, display the submenu [P AR].
Note1: If the UP/UT mode has been set for using loop-2 or the
secondary loop, also set the corresponding parameters under the main menu [LP2] in the same way.
2: Press the
SET/ENT
key 3 times* to display the PV input bias parameter BS. * Depends on the controller mode. Pressing the
SET/ENT
key one more time displays
the PV input filter parameter FL.
3: In each of these parameter setting displays,
adjust the parameter value using the
keys, then press the
SET/ENT
key to register it.
/
Parameter map (UT550/UT520)
Operating display
Main
SET3S
menu
MODE
SET
MOD
(C.A.M)
MOD (R/L) MOD (S/R)
SPN
“BS”
SET3S
or +
LP1 LP2 USR
1.SP
1.A1
1.A2
1.A3
1.A4
1.P
1.D
1.OH
1.OL
1.MR
1.H
1.DR
1.Pc
1.Ic
1.Dc
1.Hc
1.DB
1.RP
1.PO
1.Oc
Sub menu
+
SET
1.I
7.SP
7.A1
7.A2
7.A3
7.A4
7.P
7.D
7.OH
7.OL
7.MR
7.H
7.DR
7.Pc
7.Ic
7.Dc
7.Hc
7.DB RHY
7.PO
7.Oc
SET
SET
8.SP
8.A1
8.A2
8.A3
8.A4
8.P
7.I
8.I
8.D
Same
8.OH
8.OL
8.MR
8.H
8.DR
8.Pc
8.Ic
8.Dc
8.Hc
8.DB RDV
8.PO
8.Oc
as
LP1
SET
PAR 1.PID 7.PID 8.PID
SET
AT SC
BS
FL
UPR DNR
RT RBS RFL ORB ORH ORL
SET
U1 U2 U3
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
For UP35, UT450, UT420, UT35, and UT32
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller.
Parameter map (UT350/UT320/UT351/UT321)
Operating display
SET
3S
The parameter map is very helpful in finding the path to the setting display for a particular parameter.
1: With the operating display shown, press and
hold down the
SET/ENT
key for 3 seconds or
longer to call up [oP.P A]. Then press the
SET/ENT
SET/ENTSET/ENT
key repeatedly (Note) until the PV filter parameter FL appears. Pressing the the PV input bias parameter BS.
Note: The number of times a
depending on the model of the controller. See the parameter map of your controller.
SET/ENT
key one more time displays
SET/ENT
key is pressed differs
PID = 0
“FL”
PID = 1
2: In each of these parameter setting displays,
adjust the parameter value using the
keys, then press the
SET/ENT
key to register
/
it.
Ref. 1-3
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-4
<<Ref.1.1: References Related to PV Input>>

Ref.1.1(2) Correcting the PV (2.Using ten-segment linearizer biasing or approximation)

Ten-segment linearizer biasing and approximation are available with UP750, UP550, UT750, UT550, UT551, and UT520.
Whether to use the biasing or approximation function is specified by the parameter 1.PMD (Note), which is set to specify
As shown in the following “Operating parameters (Ten-segment linearizer input parameters)” table, the setting display of parameter 1.PMD is located after the ten-segment linearizer input 1 to 1 1 and ten-segment linearizer output 1 to 1 1.
Note: •“1.PMD” is the parameter for UP750, UP550, and UT750.
For how to set the parameters required for the functions discussed here, see “ Setting the Required Param-
ten-segment linearizer biasing at the time of shipping.
•“1.MD” is the parameter for UT550, UT551 and UT520.
•“2.PMD” can also be used if the UP/UT mode is set for using loop-2 or the secondary loop.
eters” in the end of this subsection.
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ten-segment Linearizer Biasing
This function is used to correct an input signal affected by sensor deterioration. The corrected values (b) are obtained by adding the corresponding bias values to each of the 1 1 points of optionally set input values (a). The input values used to configure the ten-segment linearizer are set with parameters 1.a1 to 1.a1 1 (Note). The bias values (b-axis) for each of the input values (a) are set with parameters 1.b1 to 1.b1 1 (Note).
Note: • 1.a1 to 1.a11 and 1.b1 to 1.b1 1 are the parameters for UP750, UP550, and UT750.
• 1.A1 to 1.AB and 1.B1 to 1.BB are the parameters for UT550, UT551 and UT520.
• If the UP/UT mode is set for using loop-2 or the secondary loop, “2.a1 to 2.a11 and 2.b1 to 2.b11,” and “2.A1 to 2.AB and 2.B1 to
2.BB” can also be used.
Output (b)
Corrected value (the sum of actual input and bias values)
n.b4
Actual input
Ten-segment linearizer bias
Ref. 1-5
n.a2 n.a4 Input
(a)
Fig. 1-1-2 T en-segment Linearizer Biasing
Ten-segment Linearizer Approximation
This function is used when the input signal and the required measurement signal have a non-linear relationship. For example, when trying to obtain the volume from a sphere tank level. As shown in the figure below, the output values (b) can be optionally set to 11 points of the optionally set input values (a). The input values used to configure the ten-segment linearizer are set with parameters 1.a1 to 1.a1 1 (Note). The corrective values (b-axis) of ten-segment linearizer approximation for each of the input values (a) are set with parameters 1.b1 to 1.b1 1 (Note).
Note: • 1.a1 to 1.a11 and 1.b1 to 1.b1 1 are the parameters for UP750, UP550, and UT750.
• 1.A1 to 1.AB and 1.B1 to 1.BB are the parameters for UT550, UT551 and UT520.
• If the UP/UT mode is set for using loop-2 or the secondary loop, “2.a1 to 2.a11 and 2.b1 to 2.b11” and “2.A1 to 2.AB and 2.B1 to 2.BB” can also be used.
Output (b)
Ten-segment linearizer approximation
Input (a)
Fig. 1-1-3 T en-segment Linearizer Approximation
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
The following parameters are used.
• Operating parameters (T en-segment Linealizer Parameters)
UP750 UP550 UT750 Code
1.a1
2.a1
1.b1
2.b1
1.a2
2.a2
1.b2
2.b2
1.a3
2.a3
1.b3
2.b3
1.a4
2.a4
1.b4
2.b4
1.a5
2.a5
1.b5
2.b5
1.a6
2.a6
1.b6
2.b6
1.a7
2.a7
1.b7
2.b7
UT5
Code
(1.A1)
2.A1 (for 2nd loop)
(1.B1)
2.B1 (for 2nd loop)
(1.A2)
2.A2 (for 2nd loop)
(1.B2)
2.B2 (for 2nd loop)
(1.A3)
2.A3 (for 2nd loop)
(1.B3)
2.B3 (for 2nd loop)
(1.A4)
2.A4 (for 2nd loop)
(1.B4)
2.B4 (for 2nd loop)
(1.A5)
2.A5 (for 2nd loop)
(1.B5)
2.B5 (for 2nd loop)
(1.A6)
2.A6 (for 2nd loop)
(1.B6)
2.B6 (for 2nd loop)
(1.A7)
2.A1 (for 2nd loop)
(1.B7)
2.B7 (for 2nd loop)
Description Setting range
Ten-segment linearizer 1 input-1
(Note 1)
Ten-segment linearizer 1 output-1
(Note 1)
Ten-segment linearizer 1 input-2
(Note 1)
Ten-segment linearizer 1 output-2
(Note 1)
Ten-segment linearizer 1 input-3
(Note 1)
Ten-segment linearizer 1 output-3
(Note 1)
Ten-segment linearizer 1 input-4
(Note 1)
Ten-segment linearizer 1 output-4
(Note 1)
Ten-segment linearizer 1 input-5
(Note 1)
Ten-segment linearizer 1 output-5
(Note 1)
Ten-segment linearizer 1 input-6
(Note 1)
Ten-segment linearizer 1 output-6
(Note 1)
Ten-segment linearizer 1 input-7
(Note 1)
Ten-segment linearizer 1 output-7
(Note 1)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
Default D-register
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
Ref. 1-6
No. 726
751 727
752 728
753 729
754 730
755 731
756 732
757 733
758 734
759 735
760 736
761 737
762 738
763 739
764
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-7
UP750 UP550 UT750 Code
1.a8
2.a8
1.b8
2.b8
1.a9
2.a9
1.b9
2.b9
1.a10
2.a10
1.b10
2.b10
1.a11
2.a11
1.b11
2.b11
1.PMD
2.PMD
Note1: These parameters are used for loop-2 when the UP/UT mode is set for using loop-2 or the secondary loop. Note2: As shown in the table,
UT5
Description Setting range
Code
Ten-segment
(1.A8)
2.A8 (for 2nd loop)
(1.B8)
2.B8 (for 2nd loop)
(1.A9)
2.A9 (for 2nd loop)
(1.B9)
2.B9 (for 2nd loop)
(1.AA)
2.AA (for 2nd loop)
(1.BA)
2.BA (for 2nd loop)
(1.AB)
2.AB (for 2nd loop)
(1.BB)
2.BB (for 2nd loop)
(1.MD)
2.MD (for 2nd loop)
biasing. In this mode, the ten-segment linearizer output parameters are bias values; therefore, their setting ranges at the time of shipping are -66.7 to 105.0% of measurement range span. If the ten-segment linearizer mode is parameters will be -66.7 to 105.0% of the PV input range (corrective values for approximation).
linearizer 1 input-8 (Note 1)
Ten-segment linearizer 1 output-8
(Note 1) Ten-segment
linearizer 1 input-9 (Note 1)
Ten-segment linearizer 1 output-9
(Note 1) Ten-segment
linearizer 1 input-10 (Note 1) Ten-segment
linearizer 1 output-10 (Note 1)
Ten-segment linearizer 1 input-11
(Note 1) Ten-segment
linearizer 1 output-11 (Note 1)
Ten-segment linearizer 1 mode
(Note 1)
at the time of shipping, the ten-segment linearizer mode parameter (1.PMD and others) is set to 0, which selects
changed to 1, which selects approximation, the setting ranges of ten-segment linearizer output
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
-66.7% to 105.0% of PV input range
-66.7% to 105.0% of PV input range span (Note 2)
0:Ten-segment linearizer biasing 1:Ten-segment linearizer approximation (Note 2)
Default D-register
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0.0% of PV input range
0.0% of PV input range span (Note 2)
0:Ten-segment linearizer biasing
No. 740
765 741
766 742
767 743
768 744
769 745
770 746
771 747
772 748
773
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-8
Setting the Required Parameters
T o set the parameters, carry out the following steps.
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter .
1: Referring to the User’s Manuals above, display
the operating parameter main menu [PSY1] (Note 1).
Note1: If the UP/UT mode has been set for using loop-2 or the
secondary loop, also set the corresponding parameters under the main menu [PYS2] in the same way .
SET/ENT
2: Press the
key 23 times to display the
UT750's Parameter Map
Operation dilplay
Main
SET3S
menu
PYS1
LP1MODE
USRLP2 PYS2PYS1 STUP
SETSET
parameter “1.PMD”. (Note2) And adjust the parameter value(0 or 1) using the
/ keys, then press the
register it.
Note2: “1.PMD” is the parameter for UP750, UP550 and UT750.
“1.MD” is the parameter for UT550, UT551 and UT520.
SET/ENT
3: Press the
eter main menu [PYS1], and then
SET/ENT
press
key once to display the param-
key again to display the parameter
“1.a1” (Note3).
Note3: “1.a1” is the parameter for UP750,UP550 and UT750.
“1.A1” is the parameter for UT550, UT551 and UT520.
4: Thereafter, adjust the display value for each
parameter in the order shown in the parameter table above, using the press the
SET/ENT
key to register them.
/ keys then
SET/ENT
key to
“1.a1”
“1.PMD”
1.a1
1.b1
1.a2
1.b2
1.a3
1.b3
1.a4
1.b4
1.a5
1.b5
1.a6
1.b6
1.a7
1.b7
1.a8
1.b8
1.a9
1.b9
1.a10
1.b10
1.a11
1.b11
1.PMD
2.a1
2.b1
2.a2
2.b2
2.a3
2.b3
2.a4
2.b4
2.a5
2.b5
2.a6
2.b6
2.a7
2.b7
2.a8
2.b8
2.a9
2.b9
2.a10
2.b10
2.a11
2.b11
2.PMD
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-9
<<Ref.1.1: Reference Related to PV Input>>

Ref.1.1(3) Square-root extraction of PV

Square-root extraction is available with UP750, UP550, UT750, UT550, UT551 and UT520. This calculation is used to convert, for example, a differential pressure signal from a throttling flow meter such as
an orifice and nozzle into a flow-rate signal. A low signal cut off point can also be set.
100.0%
Slope = 1
Input 100.0%0.0%
Low signal cut off point (0.0 - 5.0%)
The low signal cut off point is set using parameter A.LC1 or other (see table below).
Fig. 1-1-4 Square-root Extraction
The following parameters are used.
• Setup parameters (Analog Input Computation Parameters)
UP750 UP550 UT750 Code
A.SR1
A.LC1
A.SR2
(Note 1)
A.LC2
(Note 1)
A.SR3
(Note 2)
A.LC3
(Note 2)
Note 1: These parameters are used for 2-loop type of UP750 or UT750. Not displayed for UP550, UT550, UT551 and UT520. Note 2: These parameters can be used when the controller has Remote input function.
UT5
Description Setting range
Code
Analog input-1
(SR1)
(LC1) no function OFF or ON
no function 0.0 to 5.0% of PV input range
(SR3)
(LC3)
spuare-root computation
Analog input-1 low signal cutoff
Analog input-2 spuare-root computation
Analog input-2 low signal cutoff
Analog input-3 spuare-root computation
Analog input-3 low signal cutoff
OFF or ON (ON: Compute the square root)
0.0 to 5.0% of PV input range
(ON: Compute the square root)
OFF or ON (ON: Compute the square root)
0.0 to 5.0% of PV input range
Default
D-register No.
1003OFF
10041.0%
1007OFF
10081.0%
1011OFF
10121.0%
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-10
Setting the Required Parameters
T o set the parameters, carry out the following steps.
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter .
1: Referring to the User’s Manuals above, display
the Setup parameter main menu [CMLP]. Then, display the submenu [AIN].
SET/ENT
2: Press the
key 3 times to display the param-
Main
menu
Parametre Map
Password
OK
(UT750)
Operation parameters
display
DISP
eter “A.SR1”. (Note1) When you use the “Spuare-root extraction of PV”, set the parameter value to “ON” using the
/ keys, then press the
SET/ENT
key to
register it.
Note1: “A.SR1” is the parameter for UP750, UP550 and UT750.
“SR1” is the parameter for UT550, UT551 and UT520.
SET/ENT
3: Press the
key once to display the parameter “A.LC1”. (Note2) Set the “Analog input-1 low signal cutoff” if necessary .
Note2: “A.LC1” is the parameter for UP750, UP550 and UT750.
“LC1” is the parameter for UT550, UT551 and UT520.
Sub menu
LOOP2LOOP1 CMLP
“A.SR1”
A.BS1
A.FL1
A.SR1
A.LC1 A.BS2
A.FL2 A.SR2 A.LC2 A.BS3
A.FL3 A.SR3 A.LC3
CONF UTMD
SET DISP
AIN RET TRND LOCK
SETSETSET SET
RET1
DVB1 DVB2 TSC1 TSC2
TTM
/
A/M
MODE
LP1 LP2
PID USR PYS1 PYS2 PWD
RTH1 RTL1 RET2 RTH2 RTL2
4: After the above operation, repeat the following
operation if necessary .
• Display the parameter setting display which you want to set the value. (ex.“A.LC2”)
• Adjust the parameter value using the
keys, then press the
SET/ENT
key to register
/
it.
TIP
Descriptions of other parameters that belong to submenu AIN, such as parameter A.FL1, are given in “Ref. 1.1 (6) Correcting the Input V alue from a Sensor” of this section. Refer to it as necessary.
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
<<Ref. 1.1: References Related to PV Input>>

Ref.1.1(4) Changing the PV sampling period

CAUTION
When the controller is shipped, the PV sampling period is already set to values suitable for implementing the model’s functions and specifications. Therefore, under normal conditions, the default sampling period should be used with the controller and changing it to a shorter one may disable some of the controller’s functions. The sampling period should only be changed if you fully understand the procedures described in the following section.
CAUTION
The response time in communication may be longer when change the PV sampling period shorter. In this case, reset the PV sampling period longer.
The PV sampling period can be changed with UP750, UP550, UT750, UT550, UT551 and UT520.
Ref. 1-11
For UP750 and UP550 (Program Controllers)
The PV sampling period can be selected from 100 ms (the fastest), 200 ms, and 500 ms. (The factory-set default is 200 ms.)
For UT750, UT550, UT551 and UT520 (Digital Indicating Controllers)
The PV sampling period can be selected from 50 ms (the fastest), 100 ms, 200 ms, and 500 ms. (The factory-set default is 200 ms.)
The following tables show the limitations of controller functions for each value of the PV sampling period.
(1) UP750 (Program controller)
PV sampling period Limitations of controller functions 100 ms (the fastest) Possible with single-loop models (UP750-0) when neither cascade control (UP mode = 4)
200 ms (factory-set default) Possible with single-loop models (UP750-0) when cascade control is used.
500 ms
Note: • To check that the selected PV sampling period is appropriate, use the setup parameter SMEC described later.
• Set the PV sampling period as 200ms when the “SUPER 2” function is used. Set the PV sampling period as 500ms when the “SUPER 2” function is used in Cascade control, dual loop control or Temperature and Humidity control mode.
nor custom computation function is used.
Possible with single-loop models (UP750-0) and dual-loop models (UP750-5) when about less than 50 custom computation modules are used. “50” is given as a rough guide (Note).
When 50 or more custom computation modules are used. “50” is given as a rough guide (Note).
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-12
(2) UP550 (Program controller)
PV sampling period Limitations of controller functions 100 ms (the fastest) Possible when cascade control (UP mode = 4) is not used and also none of the following
200 ms (factory-set default) When any of the functions prohibited (listed above) with a 100 ms sampling period are used.
500 ms Note
Note: • To check that the selected PV sampling period is appropriate, use the setup parameter SMEC described later.
• Set the PV sampling period as 200ms when the “SUPER 2” function is used. Set the PV sampling period as 500ms when the “SUPER 2” function is used in Cascade control, dual loop control or Temperature and Humidity control mode.
functions are used. This is given as a rough guide (Note).
• SUPER function • Heating/cooling control • PV input computation
• Deviation alarm • Sensor grounding alarm • Self-diagnostic alarm
• FAIL output • SP rate-of-change limiter • Output rate-of-change limiter
When Cascade control mode is used.
(3) UT750 (Digital indicating controller)
PV sampling period Limitations of controller functions 50 ms (the fastest) Possible with UT750-00 (single-loop model with no optional specification) when single-loop
100 ms
200 ms (factory-set default) Possible with single-loop models (UT750-0) when cascade control is used.
500 ms
Note: • To check that the selected PV sampling period is appropriate, use the setup parameter SMEC described later.
• Set the PV sampling period as 200ms when the “SUPER 2” function is used. Set the PV sampling period as 500ms when the “SUPER 2” function is used in Cascade control, dual loop control or Temperature and Humidity control mode.
control (UT mode = 1) is used and none of the following functions are used. This is given as a rough guide (Note).
• SUPER function • Heating/cooling control • PV input computation
• Deviation alarm • Sensor grounding alarm • Self-diagnostic alarm
• FAIL output • SP rate-of-change limiter • Output rate-of-change limiter Possible with single-loop models (UT750-0) when cascade control (UP mode = 4) is not used.
Possible with position-proportional models (UT750-1).
Possible with single-loop models (UT750-0) and dual-loop models (UT750-5) when about less than 50 custom computation modules are used. ← “50” is given as a rough guide (Note).
When 50 or more custom computation modules are used. “50” is given as a rough guide (Note).
This is given as a rough guide (Note).
(4) UT550, UT551, UT520 (Digital indicating controller)
PV sampling period Limitations of controller functions

50 ms (the fastest) Possible with UT5
100 ms
200 ms (factory-set default) When cascade control mode is used. 500 ms
Note: • To check that the selected PV sampling period is appropriate, use the setup parameter SMC described later.
• Set the PV sampling period as 100ms when the “SUPER 2” function is used. Set the PV sampling period as 200ms when the “SUPER 2” function is used in Cascade control.
control (UT mode = 1) is used and none of the following functions are used. This is given as a rough guide (Note).
• SUPER function • Heating/cooling control • PV input computation
• Deviation alarm • Sensor grounding alarm • Self-diagnostic alarm
• FAIL output • SP rate-of-change limiter • Output rate-of-change limiter Possible when cascade control (UP mode = 4) is not used and any of the fumctions prohibited
(listed above) with a 100ms sampling period are used.
Note
(single-loop model with no optional specification) when single-loop
The following parameters are used
• Setup parameters (UP Mode/UT Mode parameters):SMP
UP750 UP550 UT750 Code
SMP
Note 1: Only UT750, UT550, UT551 and UT520 can select “50ms”. Note 2: The D-register No. of UP750, UP550 (UP mode) is 1281 and the No. of UT750, UT5 is 1181.
UT5
Code
(SMP)
Description Setting range
PV sampling period settig
50 (Note1), 100, 200 or 500
Default
200
D-register No.
1281(UP mode) 1181(UT mode)
(Note 2) (Note 2)
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-13
Setting the Required Parameters
T o set the parameters, carry out the following steps.
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter.
1: Referring to the User’s Manual above,
display the setup parameter main menu [UTMD].
Parameter map
Password
(UT750)
Then, display the submenu [MD].
SET/ENT
2: Press the
parameter “SMP”.
3: In the parameter setting displays, adjust
the parameter value using the
keys, then press the
register it.
key 2 times to display the
SET/ENT
/
key to
LOOP1
CONF UTMDLOOP2 CMLP
“SMP”
TEST
SET DISP
MD IN OUT VALV
SET
UTM
IN1
SMP
UNI1
SMEC
RH1 RL1
SDP1
SH1
SL1
IN3
BSL1
UNI3
RJC1
IN2
RH3
UNI2
RL3
RH2
SDP3
RL2
SH3
SDP2
SL3
SH2
BSL3
SL2
P.UN1
BSL2
P.DP1
RJC2
P.RH1 P.RL1 P.UN2 P.DP2 P.RH2 P.RL2
OT1 OT2 CT1
CT2 CTc1 CTc2
AO1
AO2
AO3
A1H
A1L
A2H
A2L
A3H
A3L
PSL1 BPS1 PRI1 STP1
DLN1 ADR1 RP.T1
PSL2
BPS2
PRI2
STP2
DLN2 ADR2 RP.T2
R485
SETSET
INI
V.RS
V.L V.H
TR.T
V.MOD
INIT
SET
SETSET
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-14
<<Ref. 1.1: References Related to PV Input>>

Ref.1.1(5) Checking that the changed PV sampling period is appropriate

CAUTION
When you have changed the PV sampling period according to “Ref. 1.1 (4) Changing the PV sampling period” in this section, be sure to check that the new period is appropriate by referring to the following descriptions.
It is necessary to check the new period with UP750, UP550, UT750, UT550, UT551 and UT520 after the PV sampling period has been changed.
It is possible to check whether or not the currently set PV sampling period is appropriate for the controller to perform its required functions. For example, with UT550, the PV sampling period can be selected from 4 periods as shown in Table 1-1-1. However, some of the controller functions will be restricted under the use of each period. Although these limitations are given as “Limitations of controller functions” in “Ref. 1.1 (4) Changing the PV sampling period”, they should be taken only as rough guides. Therefore, you must check whether or not the period is appropriate before you use the controller.Carry out this check at the time of the operation test of the system that uses the controller.
This check is performed by monitoring the sampling error counter. The counter value shows how many times the controller failed to process its operation at the current PV sampling period.(The controller increments the counter value by 1 per 10 ms of control period delay when it cannot execute all the processing within the specified period.)
PV sampling period
Processing
This chart shows that processing cannot be executed within the specified sampling period. In this example, the processing is delayed by 30 ms so the sampling error counter is incremented by 3.
Fig. 1-1-5 PV Sampling Period
Processing Processing
30ms
If the counter value is not “0,” it means that some of the processing of the controller remains unprocessed. For this reason, if an exact control is required, set the sampling period so that the counter value will not increase unless a long time has elapsed. If the counter value increases in a short period of time, change the sampling period to a larger value. Y ou can monitor the counter value through the display of setup parameter SMEC (or SMC for UT5) as shown in the following.
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-15
Table 1-1-1
PV sampling period Limitations of UT750 functions 50 ms (the fastest) Possible with UT750-00 (single-loop model with no optional specification) when single-loop
control (UT mode = 1) is used and none of the following functions are used. This is given as a rough guide (Note).
• SUPER function • Heating/cooling control • PV input computation
• Deviation alarm • Sensor grounding alarm • Self-diagnostic alarm
• FAIL output • SP rate-of-change limiter • Output rate-of-change limiter
100 ms
Possible with single-loop models (UT750-0) when cascade control (UP mode = 4) is not used.
Possible with position-proportional models (UT750-1).
This is given as a rough guide (Note).
200 ms (factory-set default) Possible with single-loop models (UT750-0) when cascade control is used.
Possible with single-loop models (UT750-0) and dual-loop models (UT750-5) when about less than 50 custom computation modules are used. ← “50” is given as a rough guide (Note).
500 ms
When 50 or more custom computation modules are used. “50” is given as a rough guide (Note).
Note: • To check that the selected PV sampling period is appropriate, use the setup parameter SMEC described later.
• Set the PV sampling period as 200ms when the “SUPER 2” function is used. Set the PV sampling period as 500ms when the “SUPER 2” function is used in Cascade control, dual loop control or Temperature and Humidity control mode.
The following parameters are used.
• Setup parameters (UP Mode / UT Mode Parameters): SMEC (SMC)
UP750 UP550 UT750 Code
SMEC
Note: Since parameter SMEC is display only, it has no setting range.
UT5
Description Setting range
Default
D-register No.
Code
320 (Note)
(SMC)
Sampling period error counter
0 to 30000 (Note)
When the controller is powered on for the first time, the error counter value is 0. The counter value displayed can increase up to 30000 as errors occur. T urning the power of f resets the counter value to 0.
Setting the Required Parameters
T o check that the selected PV sampling period is appropriate.
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter.
1: Referring to the User’s Manual above,
display the setup parameter main menu [UTMD].
Parameter map
Password
(UT750)
Then, display the submenu [MD].
2: Press the
parameter “SMEC”, and check the counter value.
Note1: “SMC” is the parameter for UT550, UT551 and UT520.
SET/ENT
key 3 times to display the
LOOP1
CONF UTMDLOOP2 CMLP
“SMEC”
TEST
SET DISP
MD IN OUT VALV
SET
UTM
IN1
SMP
UNI1
SMEC
RH1 RL1
SDP1
SH1 SL1
IN3
BSL1
UNI3
RJC1
IN2
RH3
UNI2
RL3
RH2
SDP3
RL2
SH3
SDP2
SL3
SH2
BSL3
SL2
P.UN1
BSL2
P.DP1
RJC2
P.RH1 P.RL1 P.UN2 P.DP2 P.RH2 P.RL2
OT1 OT2 CT1 CT2 CTc1 CTc2 AO1 AO2 AO3 A1H
A1L
A2H
A2L
A3H
A3L
PSL1 BPS1
PRI1 STP1 DLN1 ADR1 RP.T1 PSL2 BPS2
PRI2 STP2 DLN2 ADR2 RP.T2
R485
SETSET
INI
V.RS
V.L V.H TR.T
V.MOD
INIT
SET
SETSET
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
<<Ref. 1.1: References Related to PV Input>>
Ref. 1-16

Ref.1.1(6) Correcting the input value from a sensor

CAUTION
The “analog input bias” and “analog input filter” described here are similar to the functions described in “Ref.
1.1 (1) Correcting the PV (1. Using PV filter and PV bias)” of this section. To use the PV filter and PV bias, operating parameters FL and BS are used. As they are operating param­eters, their settings can be changed during operation. Therefore, it is recommended that under normal circumstances you use FL and BS. As for “analog input bias” and “analog input filter ,” read the following description and only set them if neces­sary .
Sensor input value correction is available with UP750, UP550, UT750, UT550, UT551 and UT520. Analog input bias is used to correct sensor-input characteristics, compensating lead wire errors, and so on.
Normally , the PV biasing (BS) is convenient as mentioned in the CAUTION above, however, use the analog input bias (A.BS) in cases where a constant correction is required due to sensor deterioration or for other reasons. Since this biasing is set using a setup parameter , it is suitable for input correction where once the parameter is set, it will not be changed for a long time.
The analog input filter is used to remove noise from a PV input signal that contains high frequency noise such as flow rate and pressure signals. This filter provides a first-order-lag calculation, which can remove more noise the larger the time constant be­comes (see the figure below). However, an excessively large time constant will distort the waveform. (See the figure below) As mentioned in the CAUTION above, a similar effect can be obtained by using the PV filter (FL). However, an analog input filter should be used in the cases where a constant level of correction is required, such as in an environment that contains a lot of noise.
Actual input With a small time constant With an excessively
Fig. 1-1-6 Image of PV Input Correction by Analog Input Filter
large time constant
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
The following parameters are used.
• Setup parameters (Analog Input Computation Parameters) : A.BS1, A.FL1, etc.
UP750 UP550 UT750 Code
A.BS1
A.FL1
A.BS2
(Note1)
A.FL2
(Note1)
A.BS3
(Note2)
A.FL3
(Note2)
Note 1: These parameters are used for 2-loop type of UP750 or UT750. Not displayed for UP550, UT550, UT551 and UT520. Note 2: These parameters can be used when the controller has Remote input function.
UT5
Description Setting range
Code
Analog input 1
(BS1)
bias Analog input 1
(FL1) no function -100.0% to 100.0% of
filter Analog input 2
bias
no function OFF or 1 to 120 (sec)
Analog input 2
-100.0% to 100.0% of input range span
OFF or 1 to 120 (sec)
input range span
filter
(BS3)
(FL3)
Analog input 3 bias
Analog input 3 filter
-100.0% to 100.0% of input range span
OFF or 1 to 120 (sec)
Default
input range span
(no filter)
input range span
(no filter)
input range span
(no filter)
Setting the Required Parameters
T o set the parameters, carry out the following steps.
Ref. 1-17
D-register No.
10010.0% of
1002OFF
10050.0% of
1006OFF
10090.0% of
1010OFF
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter.
1: Referring to the User’s Manual above,
display the setup parameter main menu [CMLP]. Then, display the submenu [AIN].
2: Press the
SET/ENT
key once to display the
parameter “A.BS1”. (Note1) Adjust the parameter value using the /
keys, then press the
SET/ENT
key to
register it.
Note1: “A.BS1” is the parameter for UP750,UP550 and UT750.
“BS1” is the parameter for UT550, UT551 and UT520.
SET/ENT
3 : Press the
key once to display the parameter “A.FL1”. (Note2) Set the “Analog input-1 filter” if necessary .
Note2: “A.FL1” is the parameter for UP750,UP550 and UT750.
“FL1” is the parameter for UT550, UT551 and UT520.
Main
menu
Sub menu
Parameter map
Password
OK
“A.BS1”
(UT750)
Operation parameter's
Setting display
DISP
LOOP2LOOP1 CMLP
A.BS1
A.FL1 A.SR1 A.LC1 A.BS2
A.FL2 A.SR2 A.LC2 A.BS3
A.FL3 A.SR3 A.LC3
CONF UTMD
SET DISP
AIN RET TRND LOCK
SETSETSET SET
RET1
DVB1 DVB2 TSC1 TSC2
TTM
/ A/M
MODE
LP1 LP2 PID
USR PYS1 PYS2 PWD
RTH1 RTL1 RET2 RTH2 RTL2
4: After the above operation, repeat the
following operation if necessary .
• Display the parameter setting display which you want to set the value. (ex.“A.BS2”)
• Adjust the parameter value using the
/ keys, then press the
SET/ENT
key
to register it.
TIP
Descriptions of other parameters that belong to submenu AIN, such as parameter A.SR1, are given in “Ref.
1.1 (3) Square-root extraction of PV” of this section. Refer to it as necessary .
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
<<Ref. 1.1: References Related to PV Input>>
Ref. 1-18

Ref.1.1(7) Using PV tracking function (UT only)

The PV tracking function is available with UT750, UT550, UT551. UT520, UT450, and UT420. PV tracking is used to prevent a sudden change in PV .
Note: As shown below, PV tracking is turned OFF at the time of shipment. T urn it ON if necessary.
When PV tracking is ON, the controller sets the SP equal to PV temporarily in the event of the following:
• Power-on
• Switching from MAN to AUTO mode
• Switching from STOP to RUN
• Switching the number of setpoint (SP No.)
After SP is equalized to PV, the SP is gradually changed toward the original SP value at a constant rate-of-change (for ramp rate; see the CAUTION below and the following Fig. 1-1-7).
CAUTION
The SP rate-of-change (ramp rate) is set using parameter UPR and/or DNR, which is set to OFF at the time of shipment. To use PV tracking, you must set parameter UPR and/or DNR to a desired ramp rate value. See “Ref.4.1(4) Changing SP at a ramp rate when SP is switched” in Ref. 4-1: References Related to Target Setpoint (SP). With these parameters OFF, which specifies no ramp rate (ramp rate = 0), PV tracking will not operate.
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-19
PV tracking enabled
SP
PV
SP ramp-rate
(UPR or DNR)
MAN AUTO MAN AUTO
mode change mode change
Time Time
PV tracking disabled
SP
PV
Fig. 1-1-7 PV tracking function
The following parameters are used.
• Setup parameters (Target Setpoint-related Parameters) : PVT
UP750 UP550 UT750 Code
PVT
Note 1: This parameter is used for loop-2 when the UP/UT mode is set for using loop-2 or secondary loop.
UT5 UT40
Code
(PVT)
Description Setting range
PV tracking selection OFF or ON
Default
OFF
D-register No.
903(for loop-1) 943(for loop-2)
(Note1)
Setting the Required Parameters
T o use the PV tracking function (to turn ON/OFF the PV tracking function), carry out the operation shown below. Since the operation differs between UT750/UT550/UT551/UT520 and UT450/UT420, instructions will be given
separately in [1] and [2]. Follow either of them according to your controller’s model.
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.1: References Related to PV Input>
Ref. 1-20
[1] UT750, UT550, UT551, UT520
T o set the parameters, carry out the following steps.
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter .
1: Referring to the User’s Manual above,
display the setup parameter main menu [LOOP1] (Note1). Then, display the submenu [SP].
Note 1: To set PVT for loop-2, go to the main menu [LOOP2],
then the submenu [SP] and carry out the same proce­dure.
SET/ENT
2: Press the
key 3 times (Note 2) to display the parameter “PVT”. And adjust the parameter value (OFF or ON) using the
SET/ENT
the
key to register it. (When “ON” is
/ keys, then press
set, PV tracking operate.)
Note 2: The times of key operation may change by the condition
of controller’s setting.
“PVT”
Main menu
Sub menu
Parameters map
Password
OK
LOOP1
LOOP2 CMLP
SET DISP
SP ALM CTL
RMS
AL1
SPT
AL2
PVT
AL3
TMU
AL4
SPH
HY1 HY2
SPL
HY3 HY4 DY1 DY2 DY3 DY4 AMD
OPR MOD
AR ZON R.MD R.TM
1.RP
2.RP
3.RP
4.RP
5.RP
6.RP RHY RDU
(UT750)
DISP
CONF UTMD
SETSET SET
[2] UT450, UT420
Here we explain how to display the parameter setting display and to change the parameter values. Before carrying out these operations be sure to refer to the User’s Manuals Initial Settings and Parameter Map of the controller. The parameter map is very helpful in finding the path to the setting display for a particular parameter .
1: With the operating display shown, press
and hold down the
SET/ENT
key for 3 seconds or
longer to call up [oP.PA].
2: Press the
/ key one time to call up
[STUP].
3: Press the
SET/ENT
key 5 times (Note) to display the parameter “PVT”. And adjust the parameter value (OFF or ON) using the
/ keys, then press the
SET/ENT
key to
Parameters map
Operating display
SET
3 sec or more
/
SET
SET
SET
Setup parameters
/
register it. (When “ON” is set, PV tracking operate.)
Note: The times of key operation may change by the condition
of controller’s setting.
“PVT”
SET
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.1: References Related to PV Input>
Ref. 1-21
<<Ref. 1.1: References Related to PV Input>>

Ref.1.1(8) PV input range adjustment (When the UT/UP mode No. is 6, 7 or 12 only)

Parameters RH1 to RL3 are used to set the range used for control within the instrument range. Parameters P.RH1 to P.RL2 (PV range) are used to set the PV ranges used for the controller’s internal computa­tion when the controller performs loop control with PV switching or loop control with PV auto-selector which receives two inputs of different measurement ranges (see Fig. 1-1-8). The parameters are also used to set the PV range for relative humidity data obtained from dry- and wet- bulb calculations in temperature and humidity control. The decimal point position of the PV range can be set with parameters P.DP1 and P.DP2.
P.RL1 P.RH1
RL2 or 3
RL1 RH1
Range of analog input 1
0 300 500 1000C
PV range
Range of analog input 2 or 3
Fig. 1-1-8 PV Range for a Control Having More than One Input
Dry bulb (Input 1)
-50 to 100C
Dry- and wet-bulb
PV1
-50 to 100C
Wet bulb (Input 2)
-50 to 100C
calculation
PV range convention
30.0 to 100.0%
<Example>
Sets
• _ _ _ _. _ for P.DP2,
• 100.0 for P.RH2, and
• 30.0 for P.RL2.
PV2
Fig. 1-1-9 PV Range for T emperature and Humidity Control
• Setup parameters (Input-related Parameters): P.UNn, P.RLn, etc
UP750 UP550 UT750
Code
P.UNn
(Note1)
P.DPn
P.RHn
UT55 UT520
Code
(P.Un)
(P.D1)
(P.H1)
Description
n
n
n
PVn Unit C : Degree Celsius
PVn decimal
Maximum value of PVn range
Setting range
% : Percent
C : Degree CelsiusF : Fahrenheit
– : No unit 0 to 4 (Note2)
-19999 to 30000 (Note3)
RH2 or 3
Default
Maximum value of PVn range or scale
D-register No.
1230 (for loop-1) 1234 (for loop-2)
1231 (for loop-1) 1235 (for loop-2)
1232 (for loop-1) 1236 (for loop-2)
P.RLn
Note1: The “n” in the table is 1 or 2. The number 1 or 2 indicates the number of loop. Note2: The number 0 to 4 of setting range means that: 0: no decimal point, 1: one digit below decimal point, 2: two digits below decimal point, 3: three digits below decimal point, 4: four digits below decimal point Note3: Under normal operation, keep the value of these parameters between the maximum and minimum values of the PV range.
n
(P.L1)
• When UP750,UP550 or UT750, P .RL1< P.RH1, where (P.H1-P.RL1)30000
• When UT550, UT551 or UT520, P .L1< P.H1, where (P.H1-P.RL1)30000
Minimum value of PVn range
-19999 to 30000 (Note3)
Minimum value of PVn range or scale
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
1233 (for loop-1) 1237 (for loop-2)
<T oc> <Ref. 1.2: References Related to Remote Input>

Ref.1.2: References Related to Remote Input

Ref. 1-22
IMPORTANT
UP750 UP550 UP35 UT750 UT5 UT40 UT3 None None None UT750-1 UT450-1
Note: Some of the functions below are not available on certain models. For more information, see those sections.
: Applicable models of this section
UT55-1 UT55-2 UT55-4 UT551-B UT551-D UT52-7 UT52-8
UT450-2 UT450-4 UT420-7 UT420-8
None
This section contains reference information on the following aspects of remote input. Refer to this information and change parameters only if necessary .
(1) Setting remote input units, range and scaling (2) Using square root extraction during remote input (3) Using remote setpoint filtering and ratio bias computing (4) Tracking target setpoint when switching from remote to local control
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<Toc> <Ref. 1.2: References Related to Remote Input>
<<Ref.1.2: Reference Related to Remote Input>>

Ref.1.2(1) Setting remote input units, range and scaling

T o use these remote input functions, the controller must have auxiliary analog input capabilities. Auxiliary analog input is indicated as “input-3” in the parameter table below.
The following parameters are used.
Setup parameters (Input-related Parameters) : IN3, UN3, RH3, RL3, SDP3, SH3, SL3
UT750
Code
UT5
Code
IN3
(IN3)
UNI3
(UN3)
RH3
(RH3)
RL3
(RL3)
SDP3
(DP3)
SH3
(SH3)
SL3
(SL3)
Note 1: UT450/UT420 do not have these parameters.
For UT450/UT420, use “DPC”, “RSH” and “RSL” parameters for the settings. For UT551, revers range can be set.
UT40
Code
(RSP)
(RSH)
(RSL)
Description Setting range
Remote Input type (Input-3 type)
Remote Input unit (Note 1)
Maximum value of remote input range (Note 1)
Minimum value of remote input range (Note 1)
Remote input decimal point position (Note 1)
Max. value of remote input scale
Min. value of remote input scale
0.4 to 2V (40) 1 to 5V (41) 0 to 2V (50) 0 to 10V (51)
% C
– (no unit)
F
Within the PV input range
0: 99999 (no decimal point) 1: 9999.9 2: 999.99 3: 99.999 4: 9.9999
-19999 to 30000 However, SL1<SH, SH1-SL130000
Default
UT5: 41 UT40 : 41
%
5.000
1.000
1
Maximum value of remote input range
Minimum value of remote input range
Ref. 1-23
D-register No.
1221UT750 : 1 to 5V
1222
1224
1225
1226
1227
1228
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
<T oc> <Ref. 1.2: References Related to Remote Input>
Ref. 1-24
Setting Example (1) For UT750 and UT5
The example below shows signal type, units, range and scaling setpoints used for remote input with the UT750, UT550, UT551 and UT520. For example, with analog input-3 (IN3) = 41, the remote input range is 1.000 to 5.000 for standard signals (1 to 5 V). Here, for an input range of 2 to 4 V , set as follows.
Maximum value of analog input-3 range (RH3) = 4,000 (Ref.: “3,500” means 3.5 V.) Minimum value of analog input-3 range (RL3) = 2,000
1V 2V 5V4V
Input range of analog input-3
Remote input range
EU (100)%EU (0)%
4.000 (RH3)2.000 (RL3)
Fig. 1-2-1
In the above example, remote input range was set to 2 to 4 V . To change the input voltage signal to the physical unit of the actual controlled condition (hereinafter, “ scaling”), see the Setting Scaling Procedure.
Setting Scaling Procedure
(1) For UT750 and UT5
The following procedure shows how to change setpoints from the factory-set defaults.
1V 2V 5V4V
EU (0) %
Input range of analog input-3
(IN=41)
EU (100) %
Step1
Minimum value of PV input range or PV input scale (i.e.:-270.0)(SL3)
10.00 (SL3)
Remote input range
Physical quantity range
Remote input range
after scaling
4.000V (RH3)2.000V (RL3)
For UT551, reverse range can be set. RL3=4.000V, RH3=2.000V
Maximum value of PV input range or PV input scale (i.e.:1370.0)(SH3)
50.00 (SH3)
Fig. 1-2-2
Step1: This example shows a remote input range of 1.000 to 5.000 for standard signals
(1 to 5 V) for an analog input -3 type (IN3) = 41.
Step2: In this example, the remote input range is set as 2.000 to 4.000V using the parameters
RL3 and RH3.
Step3: With the UT750/UT5 the same units and decimal point position set for the PV
input range are used for the remote input range. For this reason, if the PV input range is set to a thermocouple type K ( -270.0 to 1370.0 C) the initial value of SL3 is set to “-270.0” and that of SH3 is set to “1370.0” .
Step4: Change the initial settings of SDP3,SL3 and SH3 to the actual values for the remote
Input range. In this example, the SDP3 is set to “2” and SL3 is set to “10.00” and the SH3 is set to “50.00”.
Step2
Step3
Step4
IM 05J01B02-01E 5th Edition : Mar.25,2005-00
Loading...
+ 272 hidden pages