Yellow Jacket Yellow Jacket 95764 Manual

Page 1
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
RecoverXLT2-AP™ Oil-Less Universal
Refrigerant Recovery System
Operation and Maintenance
Manual
(English)
Page 2
Table of Contents Page
General Safety Instructions 2-3 RecoverXLT2-AP
S
ystem Purge Instructions
Restart
Pr
Push-
Pull Liquid Recovery
ing R-410A High Pressure Gas 6
Recover Suction
Filter 7 y Tips & T
Recover T
roubleshooting
L
ED Light Me
T
echnical Data
Calculated RecoverXLT2-AP
portant Notice to Purc
Im
arranty Information
W
Operation
Dir
ect Liquid Recovery
Recovery
Vapor
ocedure 5
echniques 7
Guide 8
aning 8
Recovery Ra
Wiring Diagram
Guide
3-4 4 5
5-6
9
tings 9
9
haser 10
10
General Safety Instructions
1) Know your equipment. Read and understand the
operation manual and the labels affixed to this unit. Learn the applications and limitations, as well as the specific potential hazards of the
RecoverXLT2-AP .
2) Use the correct hoses. Use only hoses designed
for handling of refrigerants. Th the
minimum length required for each job and equipped with a shut-off device (s co
mpact ball valve) at the likelihood o For best performance we recommend using 3/8” hoses. YELLOW JACKET hoses are made for
almost every type of refrigerant. See your local distributor for more information.
3) Ground
RecoverXLT2-AP tacle using the appropriate plug.
4) If the detachable power cord is damaged, it
must be replaced by a cord assembly available from the manufacturer or distributor wher purchased.
5) If the
must be replaced by the manufacturer or authorized service
6) Do not pressure test with compressed air. Some
mixtures of air and refrigerant have been shown to
f refrigerant leaks to the atmosphere.
all equipment. Plug th
into a properly grounded recep-
attached power socket is damaged, it
center in order to avoid hazard.
e hose should be
uch as the
end to reduce the
e
e
its
2
be combustible at elevated pressures.
7) Avoid dangerous environments. To keep
operator exposure to a minimum, RecoverXLT2-AP ventilation.
8) Recovery should always be performed in well ventilated areas. Use the RecoverXLT2-AP only in locations where mechanical ventilation which provides at least four air changes per hour
esent, or place the unit 18” above the floor
pr during use.
9)The RecoverXLT2-AP should not be used near open containers of gasoline or any other flamma­ble liquid. Do not allow refrigerants to come in contact with open flame. Refrigerant decomposi­tion in flame results in phosgene gas. Br
ne gas can be fatal.
phosge
10) Always wear safety goggles and gloves. Person­al protective equipment should be worn to protect operator from frostbite.
11) Use caution when connecting or disconnecting.
Improper usage may result in refrigerant bur (f
rostbite). If a major leak occurs, proceed imme-
diately to a well ventilated area.
12)
Disconnect recovery machine from pow before servicing.
present when the unit is disassembled.
only in areas with sufficient
An electrical shock hazard is
use the
is
eathing
ns
er
Page 3
13. Repair damaged parts. Do not operate the
RecoverXLT2-AP if there is a defective part. Repair the unit to proper operating conditions before further use.
14. Use recommended accessories. Follow the
instructions that accompany all accessories. Improper use may damage equipment or cr a hazard.
the RecoverXLT2-AP only with the prop-
Use
15. er refrigerants. (See specifications for a com-
plete list of compatible refrigerants.)
16. Operate the RecoverXLT2-AP within the design parameters only. The RecoverXLT2-AP was designed to operate within a temperature range of 40
o
120
F (49oC). Do not operate in a wet location.
17. To minimize sparking potential, it is recom­mended that electrical equipment startup by fi tur
ning on switch then plug power cord into an
outlet at least three meters away.
o (4o
C) to
18. Use an area fan to vent/diffuse any leakage during service.
19. Evacuate all air from system/recovery cylinder prior to use.
20. Fill tank to no more than 45% of HFC safe fill
eate
rst
weight. L
abel all recovery cylinders appropriately.
21.
22. To minimize sparking potential, locate vacuum pump outside of building.
Caution: All refrigerant hoses, recovery tanks, refrigerant lines, other vessels containing refrigerants and the RecoverXLT2-AP should be handled as if under high pressure. When opening a tank containing refrigerant, open valves slowly to prevent release of refrigerant, especially if the valves might be damaged.
To prevent the risk of fire DO NOT use an extension cord longer than 25’ (7.6 m) and a minimum of 16
AWG (1.276 mm
RecoverXLT2-AP Operating Guide
Direct Liquid/Vapor Recovery
2
).
The RecoverXLT2-AP is used to pull liquid or vapor refrigerant out of the system and transfer it into a recovery cylinder.
Liquid recovery is accomplished by connecting to the high pressure system discharge service port (liquid port) side of the system being serviced with a manifold (to regulate refrigerant flow).
Vapor recovery can be done by connecting to the system suction service port (low pressure) side of the system.
Because the RecoverXLT2-AP is capable of recov- ering liquid, it is more efficient to recover all of the liquid, followed by the vapor.
Ensure you have the capacity to recover all the re­frigerant in the system. In the USA the recovery cylinders can only be filled to 80% capacity and in the EU it is only 60% capacity and 45% for HFCs.
Refer to the following instructions and the diagram on page 4:
Liquid Recovery
1. Know the type and quantity of refrigerant pre­sent before servicing any system.
2. Turn off power to the system being serviced. Turn the selector knob to off.
3. Connect your manifold to the system ser
viced. High Side to liquid port and Low Side
to vapor port as shown in diagram on page 4.
4. Connect the Utility port of your manifold to the 1/4” SUCTION port of the RecoverXLT2-AP
Connect one hose from the recovery cylinder
5. (liquid side) to the 1/4” DISCHARGE port of the RecoverXLT2-AP
Note: Be
sure to connect hose ends with shut­off to suction and discharge ports of recovery machine. (For best performance us hoses.)
6. Purge all hoses of non-
recovering refrigerant into recovery cylinder.
7. Open the liquid valve on the recovery tank.
8. Turn the selector VALVE on th
RecoverXLT2-AP to LIQUID RECOVERY position.
9. Open the High Side and Utility valves on your manifold and use them to regulate the refriger­ant pressure to 80 psi maximum.
10. Ensure ambient pressure by
rect position based on if this feature is being
cor used.
.
condensables before
pass switch is in the
being
e 3/8”
e
.
3
Page 4
11. Turn the RecoverXLT2-AP on. Note: The RecoverXLT2-AP will turn
r
un for approx. six seconds before the compres­sor will start. This is to ventilate the enclosure and prevent potentially dangerous mixtures of gasses building up inside the unit.
12.
T
he RecoverXLT2-AP will recover the liquid
refrigerant. When you have removed all liquid in the sy procedure step 9 to reduce your recovery time
Vapor Recovery
1.
Know the type and quantity of refrigerant pre­sent before servicing any system.
2. Turn off power to the system being serviced. Turn the selector knob to off.
3. Connect your manifold to the system serviced. High Side to liquid port and Low Side to vapor port as shown in diagram on page 4.
4. Connect the Utility port of your manifold to the
1/4” SUCTION port of the RecoverXLT2-AP
Connect one hose from the recovery cylinder
5. (liquid side) to the 1/4” DISCHARGE port of the RecoverXLT2-AP
Note: Be off to suction and discharge ports of recovery machine. (For best performance us hoses.)
stem switch to vapor recovery
.
sure to connect hose ends with shut-
on and
the
being
e 3/8”
6. Purge all hoses of non-
recovering refrigerant into recovery cylinder.
7. Open the liquid valve on the recovery tank.
8. Turn the selector VALVE on the RecoverXLT2- AP to VAPOR RE
Slowly open the valves on your ma
9. use the
m to regulate the refrigerant pressure to
80 psi maximum.
.
.
T
urn the RecoverXLT2-AP on.
10. Note: The RecoverXLT2-AP will turn on and
run for approximately six seconds before co
mpressor will start. This is the ventilate the enclosure and prevent potentially danger m
ixture of gasses from building up inside the
unit.
he RecoverXLT2-AP will recover the vapor
11. T refrigerant. When the suction gauge indicates the appropriate vacuum, turn the selector valve OFF.
Turn selector valve to PURGE position.
12.
13. When the suction gauge again indicates the appropriate vacuum the recovery and pur cycles
are complete. Turn the selector valve to
OFF and turn the RecoverXLT2-AP off.
Note: If the machine is not recovering, refer to the troubleshooting guide on page 9. Restart procedures are on the side of the machine and on page 5.
condensables before
COVERY position.
nifold and
the
ous
ge
Liquid or Vapor Recovery Diagram
4
Page 5
System Purge Instructions
Purging or evacuating the RecoverXLT2-AP is one
of the simplest and most important functions. Re­duce the risk of cross contamination and prolong the life of the RecoverXLT2-AP by purging after every service.
Note: The purge process must be done before disconnecting the discharge hose from the
RecoverXLT2-AP.
1. Once the unit reaches appropriate vacuum level, either at just above ambient pressure with the ambient pressure switch or user defined vacuum
Restart Procedure
If the recovery unit was stopped during operation, it may be necessary to balance the internal pressures before the unit will start.
To balance the internal pressure:
1) Turn the system switch off.
Push-Pull Liquid Recovery
level, turn the system switch to OFF, then rotate the selector valve clockwise first to OFF the equalize then to PURGE. Turn the system switch ON.
Note: The low side gauge should read an increase in suction pressure, indicating the refrigerant that was trapped in the machine. Wait until the low side gauge reaches an appropriate vacuum.
2. Close the valve to the recovery tank and shut the
RecoverXLT2-AP off.
2) Rotate selector clockwise to the OFF position. Allow pressures to balance.
3) Turn the selector valve counter-clockwise to the previous RECOVER position.
4) Turn the recovery machine ON.
The Push-Pull Liquid Recovery mode is used for transferring large volumes of liquid refrigerant. The RecoverXLT2-AP “pulls” vapor from the recovery cylinder and produces high pressure discharge gas that “pushes” liquid out of the HVAC system and into the recovery cylinder. The auto purge feature makes the reconfiguration to vapor recovery easier and faster to do.
Some HVAC systems will not allow for the push­pull recovery method. If any of the following conditions apply, do not use push-pull method, but follow the instructions on page 3.
• System contains less than 10 pounds of
rigerant.
ref
• System is a heat pump or other unit with a
reversing valve.
• System has an accumulator between the
service ports used in liquid recovery.
• The refrigerant system does not allow for the
formation of a solid column of liquid.
For push-pull recovery, a sight glass is monitored during recovery. When liquid is no longer visible, stop recovery and finish recovering using the VAPOR recovery process for RecoverXLT2-AP as described on page 4.
When push-pull recovery is complete, a small amount of refrigerant remains in the system. For
complete recovery, the system must be pulled into a vacuum as required by EPA standards. This process requires:
1) An extra hose for the push-pull recovery.
2) A recovery cylinder with about 5 lbs. ref
rigerant.
3) A sight glass (Note: Make sure sight
rated for being recovered)
Follow these steps:
Turn off power to the system to be serviced.
1)
2) Hook up the RecoverXLT2-AP, the system to be recovered, and the recovery tank as shown in the diagram on the next page.
3) Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
4) Open valves on the recovery tank.
5) Turn the selector valve to VAPOR position. Turn the RecoverXLT2-AP on.
6) Note: The RecoverXLT2-AP will turn on and
run for approximately six seconds before co enclosure and prevent potentially danger m unit.
the pressure of the refrigerant
.
mpressor will start. This is the ventilate the
ixture of gasses from building up inside the
of
glass is
the
ous
5
Page 6
7) Monitor the sight glass. When the passing liquid in no longer visible through the sight glass, the push-pull method of recovery is
.
complete
8)
Close the VAPOR valve on the recovery tank
and let the recovery continue.
9) Turn the selector valve clockwise to the PURGE position and follow procedures for purging the RecoverXLT2-AP
urn the RecoverXLT2-AP off.
10) T
.
Push-Pull Recovery Diagram
11) Close LIQUID valve on recovery tank.
12) Reconnect the hoses per the procedure for the
RecoverXLT2-AP
Rotate the selector valve to the VAPOR
13) position.
14) Continue reaches the appropriate level of vacuum.
Note: See pages 3-4 for a detailed set of instructions on Vapor Recovery.
instructions.
recovery until the unit shuts off or
Recovering R-410A High Pressure Gas
IMPORTANT!!! Some equipment should not be used with this refrigerant. Take time to read the safety instructions that came with the device you are servicing as well as any material that came with your refrigerant.
WARNING!!! USE ONLY D.O.T. RECOVERY CYLINDERS APPROVED FOR R-410A.
Overfilling the tank may cause it to rupture!
The RecoverXLT2-AP will recover R-410A provided the following instructions are followed:
1) Set-up for recovery as per diagram on page 4 for normal recovery or page 5 for push­r
ecovery.
pull
6
2) Follow the operating procedures for y our model.
3) Continue cates the appropriate level of vacuum or Ambient Pressure Switch has shut the unit off and LEDs indicate Recovery Complete
Turn system switch off.
4)
5) Purge the machine (see page 5 for more details).
recovery until suction gauge indi-
.
Page 7
Suction Filter
The RecoverXLT2-AP is equipped with a built-in particulate strainer located behind the suction port. Unscrew the suction port by using a 11/16 wrench to unscrew the hex head port to remove. This prevents contaminants, copper shavings, carbon, and other foreign objects from making their way to the RecoverXLT2-AP compressor and causing permanent damage.
Like a filter drier, this strainer MUST be cleaned or replaced often. Failure to do this can cause the strainer to become too clogged for refrigerant to
RECOVERY TIPS AND TECHNIQUES
1) To assure the fastest and quickest recovery possible, use the shortest hoses possible and avoid hoses with Schrader depressors.
2) Know what kind and the am refrigerant that is g is critical to avoid contamination and how m
uch refrigerant will be recovered.
st job of the day usually means a fresh,
fir empty tank and no cause for worry about over
-filling. However, the last job of the day means there is already liquid in the tank and over-filling can be a concern. Over-filling a recovery cylinder can have disastrous results.
3) Always try to recover liquid first. This is the preferred method of recovery for
RecoverXLT2-AP
tim
es faster in standard liquid mode than
vapor.
4) If recovering large amounts of refrigerant (
more), the push-pull method is recom-
lbs or mended. (Note: This process requires the
hoses to be switched before recovery of the remaining vapor.)
, which pump
ount of
oing to be recovered. This
know
The
the
s liquid 5 to 7
20
flow freely. A sure sign that the straining device is clogged is the freezing of the suction port and the filter cover.
Before replacing, check the condition of the o-ring. Replace if necessary.
Note: Make sure to use a strainer in the
RecoverXLT2-AP for every job! Filter strainers
and o-rings are available from your supplier.
Filter Strainer and O-Ring - Part #95457
5) Recovery can often be speeded up by simultaneous recovery from low side of the sy both the high and low side of the system and join them with a BRUTE™ II Manifold or Y connector to the hose going to the Suction Port of the RecoverXLT2-AP.
6) Protect
7) Recovery machines are not vacuum pumps.
the RecoverXLT2-AP by keeping the
built-in suction filter IN THE MACHINE. Failure to use the suction RecoverXLT2-AP
For proper evacuation, use a YELLOW JACKET SuperEvac™ vacuum pump. To speed up the evacuation process, use the SuperEvac vacuum pump and a core removal tool (Part #18975). For more inform contact your Y
stem. Attach short hoses to
ELLOW JACKET wholesaler.
both the high and
filter in the
will void the warranty.
ation
7
Page 8
Troubleshooting Guide
Condition
No power to unit
Compressor will not start
Unit runs but shuts off after short time
Unit trips breaker upon start up Unit runs but does not recover refrigerant
Unit will not pull a vacuum
Unit running sluggish Low voltage to unit Check power supply Vacuum switch won’t
reset
Power cord not plugged in Plug power cord in Outlet not energized Reset breaker Compressor under unequalled conditions See restart procedure Compressor thermal overload is tripped Thermal overload will reset in approx.
Unit is shut down on Recovery Complete.
Ambient Pressure Switch tripped Pressurize inlet port before power up.
Unit has not ventilated the cabinet yet The RecoverXLT2-AP fan will run for
Unit is shut down on tank full or high pressure.
Restriction on discharge side tripping the high pressure switch
Compressor is under unequalled conditions Suction filter clogged
Selector valve in wrong position Put selector valve in liquid or vapor
Hoses are not tight Tighten hoses Ambient Pressure Switch turned off The RecoverXLT2-AP is equipped
Leak in HVAC/R system Find and repair leak in system
Switch needs to reset Pressurize inlet port
Possible Problem Possible Solution
15-30 minutes
Low pressure switch resets at atmospheric pressure, rotate selector valve to either the Vapor or Liquid Recovery position.
approximately six seconds before the compressor starts up to prevent un­wanted mixtures of gas from building up inside the unit.
Check tank pressure, check for restrictions, check shorting cap or umbilical connection, and check high gauge pressure to see if unit is under high pressure.
Check for restrictions
1) Tank valves 2
) Schrader cores Selector valve in correct position See restart procedure
Clean or replace suction filter
recovery position
with an Ambient Pressure Switch that will prevent the unit from recovering below ambient pressure so as not to pull air into the recovery cylinder from a potentially leaking system.
LED LIGHT MEANINGS
Green Light Flashing System startup ventilation. Solid Green Light System Recovering Solid Yellow Light System loss in airflow detected. Check system fan. Alternating Red and Yellow Lights Ambient Pressure reached. Solid Red Light High pressure cutout reached.
8
Page 9
Technical Data
Compressor: Power Source: Size:
Vapor Push/Pull Liquid Vapor Push/Pull Liquid
R-22 R-32 R-134a R-404A
0.17 4.16 3.10 10 250 186 .011 3.41 2.53 7 205 152
0.20 4.20 3.14 12 252 188
0.30 3.66 2.73 18 220 164
1/2 HP Reciprocating Oil-Less
230V AC 50/60 H
Height: 12.50”
i
dth: 12.50”
W Depth: 19.25”
Weight: 29.90”
z 1 Phase
Calculated Recovery Ratings
Kg./minute Kg./hour
R-410A R-1234yf R-407C
0.18 3.70 2.77 11 222 166
0.17 3.83 2.86 10 230 171
0.18 3.99 2.98 11 240 179
Wiring Diagram
9
Page 10
IMPORTANT NOTICE TO PURCHASER
Check for damage immediately. Prior to shipment, all YELLOW JACKET RecoverXLT2-AP Refrigerant Recovery Systems are completely tested and inspected to assure compliance with Ritchie Engineering facto­ry specifications.
If the recovery system carton is damaged, check contents immediately. Note damage on shipper’s Bill of Lading and have shipper sign statement. Notify carrier immediately of the damage to arrange inspection of the recovery system and packaging. The CARRIER ALONE is responsible for handling and settling your claim. Ritchie Engineering will cooperate in assessing damage if the recovery system is returned to the factory prepaid.
WARRANTY INFORMATION
Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which it was designed. Warranty does not cover items that have been altered, abused or returned solely in need of field service maintenance.
YELLOW JACKET recovery products (UPC 957xx) are covered by a one year warranty for parts and labor.
The following exceptions will not be covered under this warranty: Recovery products that have been altered, misused, or improperly maintained.
Carton contents include:
• RecoverXLT2-AP Refrigerant Recovery
System
• Owner’s manual
• Warranty registration card
To validate warranty, mail registration card within 10 days.
The following must be done before returning unit:
1) Call our technical service pers (
800) 769-8370 to assess if the problem esolved over the phone.
be r
2) Obtain an RGA number from Ritchie Engineering for the return of the product.
3) Fax a copy of the or (
800) 322-8684.
If at any time after the warranty period you have problems with your YELLOW JACKET recovery unit, call our technical service depart­ment for help in selecting the correct replace­ment parts, or to arrange for its repair at reason­able costs.
iginal invoice to
onnel at
can
10
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Loading...