RecoverXL™ and RecoverXLT™ Oil-Less
Universal Refrigerant Recovery Systems
Operation and Maintenance
Manual
Page 2
Table of Contents Page
General Safety Instructions 2-3
RecoverXL
RecoverXLT Operating
Restart Pr
Push
Recover
Care and Maintenance - Auto Purge Instructions 7
Recovery Tips & T
Component Location and List 8-9
roubleshooting
T
echnical Data
T
Suction
RecoverXL/XLT
Im
portant Notice to Purc
arranty Information
W
Operation
Dir
Dir
ocedure 5
-Pull Liquid Recovery
ing R-410A High Pressure Gas 6
Filter 10
Guide 3-4
ect Liquid/Vapor Recovery
Guide 4-5
ect Liquid/Vapor Recovery
echniques 7
Guide 9
Wiring Diagrams
haser 12
5
0
1
11
12
General Safety Instructions
1) Know your equipment. Read and understand the operation manual and the labels affixed to this unit. Learn the applications and limitations, as well as the specific potential hazards of RecoverXL/XLT.
Use the correct hoses. Use only hoses designed
2)
for handling of refrigerants. Th
minimum length required for each job and
the equipped with a shut-off device (s
mpact ball valve) at the
co likelihood o For best performance we recommend using 3/8” hoses. YELLOW JACKET hoses are made for
almost every type of refrigerant. See your local distributor for more information.
3) Ground
XLT into a properly grounded recepta the appr
4) If the detachable power cord is damaged, it must be replaced by a cord assembly available from the manufacturer or distributor wher purchased.
5) If the must be replaced by the manufacturer or authorized service
6) Do not pressure test with compressed air. Some mixtures of air and refrigerant have been shown to be combustible at elevated pressures.
7) Avoid dangerous environments. To keep
f refrigerant leaks to the atmosphere.
all equipment. Plug the RecoverXL/
opriate plug.
attached power socket is damaged, it
end to reduce the
center in order to avoid hazard.
the
e hose should be
uch as the
cle using
e
its
2
operator exposure to a minimum, use the RecoverXL/XLT only in areas with sufficient ventilation.
Recovery should always be performed in well ventilated areas. Use the RecoverXL/XLT only in locations where mechanical ventilation which provides at least four air changes per hour is present, or place the unit 18” above the floor during use.
The RecoverXL/XLT should not be used near open containers of gasoline or any other flammable liquid. Do not allow refrigerants to come in contact with open flame. Refrigerant decomposition in flame results in phosgene gas. Breathing phosgene gas can be fatal.
8) Always wear safety goggles and gloves sonal protective equipment should be worn to
Per protect operator from frostbite.
9) Use caution when connecting or disconnect-
ing. Improper usage may result in refrigerant
burns (frostbite). If a major leak occurs, proceed immediately to a well ventilated area.
Disconnect recovery machine from pow
10)
before servicing.
present when the unit is disassembled.
11)
damaged parts. Do not operate the
Repair
RecoverXL/XLT if there is a defective part. Repair the unit to proper operating conditions before further use.
An electrical shock hazard is
.
er
Page 3
12) Use recommended accessories. Follow the
instructions that accompany all accessories. Improper use may damage equipment or cr a hazard.
Use
13)
14) Operate the RecoverXL/XLT within the
Caution: All refrigerant hoses, recovery tanks,
refrigerant lines, other vessels containing refrigerants
the RecoverXL/XLT only with the proper
refrigerants. (See specifications for a complete
list of compatible refrigerants.)
design parameters only. The RecoverXL/XLT was designed to operate within a temperature range of 40 operate in a w
o (4o
C) to 120oF (49oC). Do not
cation.
et lo
and the RecoverXL/XLT should be handled as if under high pressure. When opening a tank containing refrigerant, open valves slowly to prevent release of
eate
refrigerant, especially if the valves might be damaged.
To prevent the risk of fire DO NOT use an extension cord longer than 25’ (7.6 m) and a minimum of 16
AWG (1.276 mm
RecoverXL Operating Guide
Direct Liquid/Vapor Recovery
The RecoverXL is used to pull liquid or vapor refrigerant out of the system and transfer it into a recovery cylinder.
Liquid recovery is accomplished by connecting to the high pressure system discharge service port (liquid port) side of the system being serviced with a manifold (to regulate refrigerant flow).
Vapor recovery can be done by connecting to the system suction service port (low pressure) side of the system.
Because the RecoverXL is capable of recovering liquid, it is more efficient to recover all of the liquid, followed by the vapor.
Ensure you have the capacity to recover all the re­frigerant in the system. In the USA the recovery cylinders can only be filled to 80% capacity and in the EU it is only 60% capacity.
Refer to the following instructions and the diagram on page 4:
Liquid Recovery
1. Know the type and quantity of refrigerant pre­sent before servicing any system.
2. Turn off power to the system being serviced. Turn the selector knob to off.
3. Connect your manifold to the system
viced. High Side to liquid port and Low Side
ser to vapor port as shown in diagram on page 4.
4. Connect the Utility port of your manifold to the 1/4” SUCTION port of the RecoverXL
Connect one hose from the recovery cylinder
5. (liquid side) to the 1/4” DISCHARGE port of the RecoverXL
.
being
.
2
).
sure to connect hose ends with shut-
Note: Be off to suction and discharge ports of recovery machine. (For best performance use 3/8” hoses.)
6. Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
7. Open the liquid valve on the recovery tank.
8.
T
urn the RecoverXL on.
9. Turn the selector VALVE on the RecoverXL to LIQUID RECOVERY position.
10. Open the High Side and Utility valves on your manifold and use them to regulate the refriger­ant pressure to 80 psi maximum.
he RecoverXL will recover the liquid refriger-
T
11. ant. When you have removed all the liquid in the system switch to vapor recovery procedure step 9 to reduce your recovery time.
Vapor Recovery
1. Know the type and quantity of refrigerant pre­sent before servicing any system.
2. Turn off power to the system being serviced. Turn the selector knob to off.
3. Connect your manifold to the system
viced. High Side to liquid port and Low Side
ser to vapor port as shown in diagram on page 4.
4. Connect the Utility port of your manifold to the
1/4” SUCTION port of the RecoverXL
5.
Connect one hose from the recovery cylinder
(liquid side) to the 1/4” DISCHARGE port of the RecoverXL.
Note: Be
sure to connect hose ends with shut-
being
.
3
Page 4
off to suction and discharge ports of recovery machine. (For best performance use 3/8” hoses.)
6. Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
7. Open the liquid valve on the recovery tank.
urn the RecoverXL on.
8.
T
9. Turn the selector VALVE on the RecoverXL to VAPOR RECOVERY position.
10. Slowly open the valves on your manifold and
11.
m to regulate the refrigerant pressure to
use the 80 psi maximum.
he RecoverXL will recover the vapor
T refrigerant. When the suction gauge indicates
Liquid or Vapor Recovery Diagram
the appropriate vacuum, turn the selector valve OFF.
12. Turn selector valve to PURGE position.
13. When the suction gauge again indicates the appropriate vacuum the recovery and pur
are complete. Turn the selector valve to
cycles OFF and turn the RecoverXL off.
Note: If the machine is not recovering, refer to
the troubleshooting guide on page 9. Restart procedures are on the side of the machine and on page 5.
ge
RecoverXLT Operating Guide
Direct Liquid/Vapor Recovery
The RecoverXLT is used to pull liquid or vapor refrigerant directly out of the system and transfer it into a recovery cylinder.
Liquid recovery is accomplished by connecting to the high pressure system discharge service port (Liquid Port) side of the system being serviced.
Vapor recovery can be done by connecting to the system suction service port (low pressure) side of the system.
Because the RecoverXLT is capable of recovering
4
direct liquid, it is best to first recover all of the liquid, followed by the vapor. This will make your job easier and faster. Refer to the following instructions and the above diagram:
1. Know the type and quantity of refrigerant present
before servicing any system.
2. Turn off power to the system being serviced. Turn the selector knob to off.
3. Connect your manifold to the system
viced. High Side to liquid port and Low Side
ser
being
Page 5
to vapor port as shown in diagram on page 4.
4. Connect the Utility port of your manifold to the 1/4” SUCTION port of the RecoverXLT.
5.
Connect one hose from the recovery cylinder
(liquid side) to the 1/4” DISCHARGE port of the RecoverXLT.
Note: Be sure to connect hose ends with shut-off to suction and discharge ports of recovery machine (for best performance use 3/8” hoses.)
6. Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
7. Open the liquid valve on the recovery tank.
T
8.
urn the RecoverXLT on.
9. Turn the selector VALVE on the RecoverXLT to either the LIQUID or VAP
Open the Utility and either High Side or Low
10. Side valves on the manifold. Remember it is more efficient to recover the liquid refrigerant
OR position.
Restart Procedure
If the recovery unit was stopped during operation, it may be necessary to balance the internal pressures before the unit will start.
To balance the internal pressure:
1) Turn the system switch off.
first. Caution: do not over-pressure low side gauge.
11.
T
he RecoverXLT will continue to recover until it reaches and sustains the appropriate vacuum at which point the LOW PRESSURE SWITCH shuts down the unit and the lamp
Recovery Co
Turn the system switch off. Turn the selector
12. valve clockwise to OFF. Turn the system switch on. Turn selector valve to PURGE position.
13. When the unit again shuts down and the lamp indicates Recovery Complete, the recovery and purge cycles are complete.
Note: If the machine is not recovering, refer to the troubleshooting guide on page 9. Restart procedures are on the side of the machine and below.
2) Rotate selector clockwise to the OFF position. Allow pressures to balance.
3) Turn the recovery machine ON.
4) Turn the selector valve counter-clockwise to the previous RECOVER position.
mplete
.
indicates
Push-Pull Liquid Recovery
The Push-Pull Liquid Recovery mode is used for transferring large volumes of liquid refrigerant. The RecoverXL/XLT “pulls” vapor from the recovery cylinder and produces high pressure discharge gas that “pushes” liquid out of the HVAC system and into the recovery cylinder. The auto purge feature makes the reconfiguration to vapor recovery easier and faster to do.
Some HVAC systems will not allow for the push­pull recovery method. If any of the following conditions apply, do not use push-pull method, but follow the instructions on page 3 for the RecoverXL and page 4 for RecoverXLT.
 System contains less than 10 pounds of
rigerant.
ref
 System is a heat pump or other unit with a
reversing valve.
 System has an accumulator between the
service ports used in liquid recovery.
 The refrigerant system does not allow for the
formation of a solid column of liquid.
For push-pull recovery, a sight glass is monitored during recovery. When liquid is no longer visible, stop recovery and finish recovering using the VAPOR recovery process for RecoverXL or RecoverXLT as described on page 3 or 4.
When push-pull recovery is complete, a small amount of refrigerant remains in the system. For complete recovery, the system must be pulled into a vacuum as required by EPA standards. This process requires:
1) An extra hose for the push-pull recovery.
2) A recovery cylinder with about 5 lbs. rigerant.
ref
3) A sight glass (Note: Make sure sight
rated for being recovered)
the pressure of the refrigerant
.
of
glass is
5
Page 6
Follow these steps:
1) Turn off power to the system to be serviced.
2) Hook up the RecoverXL/XLT, the system to be recovered, and the recovery tank as shown in the diagram below.
3) Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
4) Open valves on the recovery tank.
5) Turn the selector valve to VAPOR position.
T
urn the RecoverXL/XLT on.
6)
7) Monitor the sight glass. When the passing liquid is no longer visible through the sight glass, the push-pull method of recovery is complete
.
8)
Close the VAPOR valve on the recovery tank
Push-Pull Recovery Diagram
and let the recovery continue.
9) Turn the selector valve clockwise to the PURGE position and follow procedures for purging the RecoverXL/XLT
10) Turn the RecoverXL/XLT off.
11) Close LIQUID valve on recovery tank.
12) Reconnect the hoses per the procedure for the RecoverXL/XLT instructions.
13) Rotate the selector valve to the VAPOR position.
14) Continue reaches the appropriate level of vacuum.
Note: See pages 3-4 for a detailed set of instructions on Vapor Recovery.
recovery until the unit shuts off or
.
Recovering R-410A High Pressure Gas
IMPORTANT!!! Some equipment should not be used with this refrigerant. Take time to read the safety instructions that came with the device you are servicing as well as any material that came with your refrigerant.
WARNING!!! USE ONLY D.O.T. RECOVERY CYLINDERS APPROVED FOR R-410A.
Overfilling the tank may cause it to rupture!
The RecoverXL/XLT will recover R-410A provided the following instructions are followed:
1) Set-up for recovery as per diagram on page 4 for normal recovery or page 6 for push­r
.
ecovery
Follow the operating procedures for your
2)
6
pull
model.
3) Continue recovery RecoverXL appropriate level of vacuum. RecoverXLT - Low Pressure Switch shut the unit off and lamp indicates Recovery
Co
4)
Turn system switch off.
5) Purge the machine (see page 7 for more details).
Technical Support: Call 800-769-8370 for additional information.
mplete
.
until:
- suction gauge indicates the
has
Page 7
Care and Maintenance
Auto Purge Instructions
Purging or evacuating the RecoverXL/XLT is one of the simplest and most important functions. Reduce the risk of cross contamination and prolong the life of the RecoverXL/XLT by purging after every service.
Note: The purge process must be done before disconnecting the discharge hose from the
RecoverXL/XLT.
For RecoverXLT Models
T
he Low Pressure Switch will shut the unit
1) off and the lamp will indicate Recovery
mplete when the unit reaches appropr
Co
m levels. After the unit shuts down, turn
vacuu the system switch to off, then rotate th selector valve cloc then to PURGE. Turn the system switch on.
Note: The low side gauge should read an increase in suction pressure, indicating the refrigerant that was trapped in the machine.
Wait until the Low Pressure Switch again shuts the unit off at the appropriate vacuum.
2) Close the valve to the recovery tank and shut
kwise to OFF to equalize
iate
e
the RecoverXLT off.
For RecoverXL Models
1) Monitor the recovery of the system until the suction gauge indicates the appropriate level of vacuum. Turn off and rotate selector valve to OFF to equalize then to PURGE. After the unit shuts down, turn the system switch to off, then rotate the selector valve clockwise to OFF to equalize then to PURGE. Turn the system switch on.
2) Turn the system switch on.
Note: The low side gauge should read an increase in suction pressure, indicating the refrigerant that was trapped in the machine.
Wait until the suction gauge indicates the appropriate vacuum.
3) Turn the selector system
Close the valve to the recovery tank and shut
4)
the RecoverXL off.
RECOVERY TIPS AND TECHNIQUES
1) To assure the fastest and quickest recovery possible, use the shortest hoses possible and avoid hoses with Schrader depressors.
2) Know what kind and the am refrigerant that is g is critical to avoid contamination and
uch refrigerant will be recovered.
how m
st job of the day usually means a fresh,
fir empty tank and no cause for worry about over
-filling. However, the last job of the day means there is already liquid in the tank and over-filling can be a concern. Over-filling a recovery cylinder can have disastrous results.
3) Refrigerant responds to heat. Therefore, a significant increase in the speed of the recovery process will be obtained if a heat gun is used, specifically to any spots where liquid may have accumulated.
4) Always try to recover liquid first. This is the preferred method of recovery for RecoverXL/XLT , which pumps liquid 5 to 7
es faster in standard liquid mode than
tim vapor.
5) If recovering large amounts of refrigerant (
more), the push-pull method is recom-
lbs or
ount of
oing to be recovered. This
know
The
the
20
mended. (Note: This process requires the
hoses to be switched before recovery of the remaining vapor.)
6) Recovery can often be speeded up by simultaneous recovery from low side of the sy both the high and low side of the system and join them with a BRUTE™ II Manifold or Y connector to the hose going to the Suction Port of the RecoverXL/XLT.
7) Protect
8) Recovery machines are not vacuum pumps.
the RecoverXL/XLT by keeping the built-in suction filter IN THE MACHINE. Failure to use the suction
RecoverXL/XLT
For proper evacuation, use a YELLOW JACKET SuperEvac™ vacuum pump. To speed up the evacuation process, use the SuperEvac vacuum pump and a core removal tool (Part #18975). For more inform contact your Y
switch off
both the high and
stem. Attach short hoses to
filter in the
will void the warranty.
ation
ELLOW JACKET wholesaler.
7
Page 8
Components
RecoverXL/XLT Parts
Part# Description Part# Description
95444
95445
95446
95447
95448
95449
95450
95325
95547
95338
Case, Front
Case, Rear
Case Half (both halves)
Case, Cord Wrap
Aluminum Frame
Compressor Bracket Grommet
Condenser Coil
High Pressure Switch (XLT w/ TOS)
High Pressure Switch (XL/XLT w/o TOS)
Low Pressure Switch (XLT Only)
95216
95453
95228
95455
95294
95451
95452
95210
95190
95457
Rocker Switch
Manifold Assembly
CPR Valve
Fan Blade
Fan Clip
High Pressure Gauge
Low Pressure Gauge
Large Cord Strain Relief Bushing
Capacitor
Replacement Filter Screen
8
RecoverXLT w/TOS Parts Only
Part# Description
95477
TOS LED Strip Assembly
95478
TOS LED Connection Cable
95527
TOS Board for RecoverXLT (board, LED strip and cable)
95248
Umbilical Cord Overfill Sensor
95188
Shorting Cap for Umbilical Cord
Page 9
Troubleshooting Guide
Condition
No power to unit
Compressor will not start
Unit runs but shuts off after short time
Unit trips breaker upon start up
Unit runs but does not recover refrigerant
Unit will not pull a vacuum
Unit running sluggish Low voltage to unit Check power supply
Vacuum switch won’t reset
Power cord not plugged in Plug power cord in
Outlet not energized Reset breaker Compressor under unequalled conditions See restart procedure
Compressor thermal overload is tripped Thermal overload will reset in approx.
Unit is shut down on Recovery Complete.
Unit is shut down on tank full or high pressure.
Restriction on discharge side tripping the high pressure switch
Compressor is under unequalled conditions
Suction filter clogged
Selector valve in wrong position Put selector valve in liquid or vapor
Hoses are not tight Tighten hoses
Leak in HVAC/R system Find and repair leak in system
Switch needs to reset Pressurize inlet port
Possible Problem Possible Solution
15-30 minutes
Low pressure switch resets at atmospheric pressure, rotate selector valve to either the Vapor or Liquid Recovery position.
Check tank pressure, check for restrictions, check shorting cap or umbilical connection, and check high gauge pressure to see if unit is under high pressure.
Check for restrictions
1) Tank valves ) Schrader cores
2
Selector valve in correct position See restart procedure
Clean or replace suction filter
recovery position
Components, cont.
Domestic Models 115 V International Models 230 V
Part# Description Part# Description
95218
95156
95215
95456
95187
*If the detachable power cord is damaged (95431 or 95432), it must be replaced by a cord assembly available from the manufacturer or distributor where purchased.
**If the attached power cord or socket is damaged (95215 or 95459), it must be replaced by the
manufacturer or its authorized service center in order to avoid hazard.
Oil-less Compressor 115V, 60Hz
Circuit Breaker - 12 AMP
Power Cord, Domestic**
Neon Lamp, 115V (RecoverXLT only)
Compressor Relay, 115V
95264
95429
95430
95266
95459
95431
95432
Oil-less Compressor 230V, 50Hz
Circuit Breaker - 6 AMP
230V Amber Lamp (RecoverXLT only)
Compressor Relay, 230V
IEC 320 Power Socket **
Power Cord, 230V CE*
Power Cord, 230V UK*
9
Page 10
TECHNICAL DATA
Compressor:
Power Source: 115V AC 60 Hz 1 Phase 230V AC 50 Hz 1 Phase
Amperage: Run Load Amps: 9.3 3.7
Full Load Amps: 11.0 11.0
Locked Rotor Amps: 30.0 18.0
Size:
Height: 12.50”
Weight: 29.90”
*UL Certified Rates to ARI Standard 740-98
1/2 HP Reciprocating Oil-Less
Width: 12.50”
Depth: 19.25”
RecoverXL
Vapor lbs./min
Liquid lbs./min
Push-Pull lbs./min
Vacuum Level
RecoverXLT
Vapor lbs./min
Liquid lbs./min
Push-Pull lbs./min
Vacuum Level
Other Refrigerants - The RecoverXL/XLT is approved for use with the following refrigerants which have not been certified for a particular recovery rate: R401B, R-402A, R-402B, R-404A, R-406A, R-407A, R-407B, R-407C, R-407D, R-408A, R-409A, R-411A, R-411B, R-500 and R-502.
R-12 R-134a R-22 R-500 R-502 R-410A
.31 .31 .31 .31 .55 .42
1.68 1.68 1.68 1.68 2.29 1.41
13.12 13.12 13.12 13.12 13.18 11.6
15 inHg 15 inHg 15 inHg 15 inHg 15 inHg 15 inHg
R-12 R-134a R-22 R-500 R-502 R-410A
.37 .37 .37 .37 .66 .42
1.98 1.98 1.98 1.98 2.65 1.68
12.81 12.81 12.81 12.81 12.9 11.6
15 inHg 15 inHg 15 inHg 15 inHg 15 inHg 15 inHg
Suction Filter
The RecoverXL/XLT is equipped with a built-in particulate strainer located behind the suction port. Unscrew the suction port by using a 11/16 wrench to unscrew the hex head port to remove. This prevents contaminants, copper shavings, carbon, and other foreign objects from making their way to the RecoverXL/XLT compressor and causing permanent damage.
Like a filter drier, this strainer MUST be cleaned or replaced often. Failure to do this can cause the strainer to become too clogged for refrigerant to flow freely. A sure sign that the straining device is
clogged is the freezing of the suction port and the filter cover.
Before replacing, check the condition of the o-ring. Replace if necessary.
Note: Make sure to use a strainer in the RecoverXL/XLT for every job! Filter strainers and o-rings are available from your supplier.
Filter Strainer and O-Ring - Part #95457
10
Page 11
Wiring Diagrams
11
Page 12
IMPORTANT NOTICE TO PURCHASER
Check for damage immediately. Prior to shipment, all YELLOW JACKET RecoverXL/ XLT Refrigerant Recovery Systems are completely tested and inspected to assure compliance with Ritchie Engineering factory specifications.
If the recovery system carton is damaged, check contents immediately. Note damage on shipper’s Bill of Lading and have shipper sign statement. Notify carrier immediately of the damage to arrange inspection of the recovery system and packaging. The CARRIER ALONE is responsible for handling and settling your claim. Ritchie Engineering will cooperate in assessing damage if
WARRANTY INFORMATION
Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which it was designed. Warranty does not cover items that have been altered, abused or returned solely in need of field service maintenance.
YELLOW JACKET recovery products (UPC 957xx) are covered by a one year warranty for parts and labor. The 115V recovery products (UPC 95760 and 95762) have an extended three year compressor warranty if the warranty card is returned and on file. The warranty also allows for a one year over-the-counter exchange, when applicable. To receive this over-the-counter exchange, call Ritchie Engineering Customer Service at (800)769-8370 and get the required authorization number. Failure to get the required authorization number could result in a denial of the over-the-counter exchange.
the recovery system is returned to the factory prepaid.
Carton contents include:
 RecoverXL or RecoverXLT Refrigerant
y System
Recover
 Owner’s manual
 Warranty registration card
To validate warranty, mail registration card within 10 days.
The following exceptions will not be covered under this warranty: Recovery products that have been altered, misused, or improperly maintained.
The following must be done before returning unit:
1) Call our technical service pers
800) 769-8370 to assess if the problem can
( be resolved over the phone.
2) Obtain an RGA number from Ritchie Engineering for the return of the product.
3) Fax a copy of the or
800) 322-8684.
(
iginal invoice to
onnel at
Note: All units must be shipped to the Bloomington, MN plant for repair. If at any
time after the warranty period you have problems with your YELLOW JACKET recovery unit, call
Printed in U.S.A.