Xantrex Technology ACCB-L, ACCB-L-L1 User Manual

Sine Wave Plus Long AC Conduit Box Owner’s Guide
ACCB-L ACCB-L-L1
Owner’s Guide
Sine Wave Plus Long AC Conduit Box
About Xantrex
Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical power.
Trademarks
Sine Wave Plus Long AC Conduit Box is a trademark of Xantrex International. Xantrex is a registered trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Notice of Copyright
Sine Wave Plus AC Conduit Box Long Owner’s Guide © June 2004 Xantrex International. All rights reserved.
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
June 2004 Revision A
Part Number
973-0031-01-01 Rev A
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax: 1 800 994 7828 (toll free North America)
1 360 925 5143 (direct)
Email: customerservice@xantrex.com
Web: www.xantrex.com
About This Guide
Purpose
The purpose of this Owner’s Guide is to provide explanations and procedures for installing, operating, maintaining, and troubleshooting the Sine Wave Plus Long AC Conduit Box.
Scope
The Guide provides safety guidelines, and procedures for installing and operating the Sine Wave Plus Long AC Conduit Box.
Audience
The Guide is intended for a skilled electrician or technician who needs to install and operate the Sine Wave Plus Long AC Conduit Box. Installers should be certified and familiar with all local and national codes regarding electrical installations of this nature.
Organization
This Guide is organized into three chapters.
Chapter 1, “Introduction” provides a basic introduction to the design and purpose of the Sine Wave Plus Long AC Conduit Box (ACCB-L).
Chapter 2, “Installation” provides installation and wiring instructions for the Sine Wave Plus Long AC Conduit Box.
Chapter 3, “Operation” describes the different modes and operation of the AC Bypass Switch(es) on the ACCB-L-L1, or for the second AC Bypass Switch (ACCB-L-L2) if installed.
Warranty and product information is provided at the end of the guide.
Product Naming Conventions
ACCB-L refers to the Long AC Conduit Box without AC Bypass Switch.
ACCB-L-L1 refers to the Long AC Conduit Box with AC Bypass Switch.
ACCB-L-L2 refers to the ACCB-L-L1 with the field-installed ACCB-L2-PCK (AC Bypass Switch assembly, with wiring, and an AC Bus Bar for Hot L2 connections) and is usually configured for dual operation.
Long AC Conduit Box refers to all products and is used in situations where all three products are treated the same.
973-0031-01-01 Rev A iii
About This Guide
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other equipment.
Important:
serious as a caution or warning.
These notes describe things which are important for you to know, but not as
Abbreviations and Acronyms
AC Alternating Current
ACCB-L AC Conduit Box Long (with ground bar only)
ACCB-L-L1 AC Conduit Box Long (adds internal components for wiring)
ACCB-L-L2 AC Conduit Box Long (built on ACCB-L-L1 for dual configuration)
ACCB-L2-PCK AC Bypass Switch Assembly only (includes wiring)
ALM Auxiliary Load Module
AHJ Authority Having Jurisdiction
ASC Authorized Service Center
AWG American Wire Gauge
CEC Canadian Electrical Code
CSA Canadian Standards Association
DC Direct Current
EPO Emergency Power Off
GSM Generator Start Module
ICA Inverter Communications Adapter
ICM Inverter Control Module
ISC-S Inverter Stacking Control – Series
NEC National Electrical Code
RMA Return Material Authorization
UL Underwriters Laboratory
Related Information
You can find more information about Xantrex Technology Inc. as well as its products and services at www.xantrex.com.
iv 973-0031-01-01 Rev A
Important Safety Instructions
WARNING
This chapter contains important safety and operating instructions for the Sine Wave Plus Long AC Conduit Box (ACCB-L and ACCB-L-L1) and the ACCB-L-L2 (ACCB-L2-PCK add-on package). Read and keep this Sine Wave Plus AC Conduit Box Long Owner’s Guide for future reference.
1. Before installing the Long AC Conduit Box, read all instructions and cautionary markings on the Long AC Conduit Box and all appropriate sections of this guide.
2. Do not expose the Long AC Conduit Box to rain, snow, or spray.
3. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings.
4. Do not install the Long AC Conduit Box in a zero-clearance compartment. Overheating may result. Minimum clearance for ventilation around the unit
must be twelve inches above and around the sides of the unit. See “Ventilation Requirements” on page 2–5 for additional information.
5. Do not store anything flammable near the unit. Relocate anything flammable to another location.
6. Xantrex offers CSA “approved” parts for installation into this product. Parts purchased elsewhere are subject to approval by the local electrical authority. See Figure 2-11 on page 2–16 for details.
7. The Long AC Conduit Box is designed to be permanently connected to your Sine Wave Plus inverter. Xantrex recommends that all wiring be done by a certified technician or electrician to ensure adherence to the local and national electrical codes applicable in your application.
8. To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the Long AC Conduit Box, or inverter, with damaged or substandard wiring.
9. To reduce the risk of electrical shock, disconnect all power to the Long AC Conduit Box and the Sine Wave Plus Inverter/Charger before attempting any maintenance or cleaning or working on the Long AC Conduit Box.
Safety
10. The Long AC Conduit Box is provided with an equipment-grounding bar which must be connected to the inverter/system equipment ground.
973-0031-01-01 Rev A v
Safety
Explosive gas precautions
1. Working in the vicinity of lead-acid batteries is dangerous. Batteries generate explosive gases during normal operation. Therefore, you must read this guide and follow the instructions exactly before installing the Long AC Conduit Box.
2. To reduce the risk of battery explosion, follow these instructions and those published by the battery manufacturer and the manufacturer of the equipment in which the battery is installed.
Certifications
CSA certified to the following standards:
UL 1741-2001 (First Edition), and
CSA C22.2 No. 107.1-01
vi 973-0031-01-01 Rev A
Contents
Important Safety Instructions
1
Introduction
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 AC Bypass Switch Assembly - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6 Blockoff Plates - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–7
2
Installation
Preparing for the Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Code Compliance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2 Installation Tools and Materials - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Configuration Planning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3
Off-Grid Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3 On-Grid Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3
Pre-Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Service Planning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Ventilation Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5 Removing and Replacing the Cover - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6 Installing or Removing the Blockoff Plates - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7 Knockout Preparation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–8 Installing Additional Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Mounting on the Xantrex Back Plate (XBP) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11 Mounting on Plywood - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
Wiring - General - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14
Accessing the AC Input/Output Terminal Block in the ACCB-L-L1 - - - - - - - - - - - - - - - - - 2–14 Wire Sizes and Disconnect Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–15
Wiring for Off-Grid Applications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19
Single Inverter Configurations (120 Vac) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19 Step-down Configurations (240 Vac to 120 Vac) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21 Step-up Configuration (Deep Well Pump) (120 Vac to 240 Vac) - - - - - - - - - - - - - - - - - - - 2–23 Dual Inverter Configurations (120 Vac and 240 Vac) - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24
Wiring for On-Grid Applications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25
Single Inverter Configurations (120 Vac) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25 Step-up Configurations (Utility Backup) (120 Vac to 240 Vac) - - - - - - - - - - - - - - - - - - - - 2–27 Dual Inverter Configurations (120 Vac and 240 Vac) - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–28
Additional Accessory Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–29
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -v
973-0031-01-01 Rev A vii
Contents
3
Operation
The AC Bypass Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Operating the AC Bypass Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Normal Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Bypass Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 AC Input/Output Off - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Dual Inverters: 240 Vac Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Warranty and Return Information
Index
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - IX–1
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - WA–1
viii 973-0031-01-01 Rev A
Figures
Figure 1-1 The Sine Wave Plus ACCB-L Basic- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Figure 1-2 The Sine Wave Plus Long AC Conduit Box (ACCB-L-L1, and ACCB-L-L2)- - - - - - - - 1–3 Figure 1-3 ACCB-L Dimensions (not to scale) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5 Figure 1-4 Bypass Switch Assembly in the ACCB-L-L1- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6 Figure 1-5 Blockoff Plates - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–7 Figure 2-1 Shock Hazard Warning Label - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Figure 2-2 Clearance Requirements for Ventilation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5 Figure 2-3 Cover Removal and Replacement - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6 Figure 2-4 The Blockoff Plate on the Long AC Conduit Box- - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7 Figure 2-5 SW Plus Inverter, AC Side Showing Knockout Location - - - - - - - - - - - - - - - - - - - - - - 2–8 Figure 2-6 Knockouts Locations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–9 Figure 2-7 Installing Additional Breakers on the DIN Rail - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Figure 2-8 The Xantrex Back Plate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11 Figure 2-9 Installing the ACCB-L on the Backplate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12 Figure 2-10 Installing the ACCB-L to the SW Plus Inverter on Plywood- - - - - - - - - - - - - - - - - - - 2–13 Figure 2-11 ACCB-L Approved Internal Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16 Figure 2-12 ACCB-L-L1 Internal Components (Factory installed) - - - - - - - - - - - - - - - - - - - - - - - 2–17 Figure 2-13 ACCB-L-L1 Internal Components with the Optional ACCB-L2-PKG Installed - - - - - 2–18 Figure 2-14 Wiring an Off-grid Application Using a Single Inverter - - - - - - - - - - - - - - - - - - - - - 2–19 Figure 2-15 Wiring an Off-grid Application Using a Single Inverter (No Sub Panel) - - - - - - - - - - 2–20 Figure 2-16 Wiring an Off-grid Application Using a Single Inverter and TX Autotransformer
in a Step-Down Configuration- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21
Figure 2-17 Wiring an Off-grid Application Using a Single Inverter and TX Autotransformer
for a Step-Down Configuration (No Sub Panel) - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–22
Figure 2-18 Wiring an Off-grid Application Using a Single Inverter and TX Autotransformer
for a Step-Up Configuration for a Deep Well Pump Application- - - - - - - - - - - - - - - - 2–23 Figure 2-19 Wiring an Off-grid Application Using Dual Inverters (ACCB-L-L2)- - - - - - - - - - - - - 2–24 Figure 2-20 Wiring an On-grid Application Using a Single Inverter - - - - - - - - - - - - - - - - - - - - - - 2–25 Figure 2-21 Wiring an On-grid Application Using a Single Inverter (No Sub Panel) - - - - - - - - - - - 2–26 Figure 2-22 Wiring an On-grid Application Using a Single Inverter and TX Autotransformer
for a Step-Up Configuration for Utility Backup - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27 Figure 2-23 Wiring an On-grid Application Using Dual Inverters (ACCB-L-L2) - - - - - - - - - - - - - 2–28 Figure 2-24 Accessory Wiring for Single-Inverter Configurations - - - - - - - - - - - - - - - - - - - - - - - 2–29 Figure 2-25 Accessory Wiring for Dual-Inverter Configurations - - - - - - - - - - - - - - - - - - - - - - - - 2–30 Figure 3-1 AC Bypass Switch Mode Summary - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Figure 3-2 Normal Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Figure 3-3 Bypass Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Figure 3-4 AC Output OFF - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
973-0031-01-01 Rev A ix
x
Tables
Table 1-1 Operational and Environmental Specifications for the ACCB-L, ACCB-L-L1,
and ACCB-L-L2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Table 2-1 Torque Values for Wiring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–15
973-0031-01-01 Rev A xi
xii
1
Introduction
Chapter 1, “Introduction” provides a basic introduction to the design and purpose of the Sine Wave Plus Long AC Conduit Box (ACCB-L).
The following topics are covered in this chapter.
For this topic: See:
“Introduction” page 1–2
“Specifications” page 1–4
“AC Bypass Switch Assembly” page 1–6
Introduction
Introduction
The Sine Wave Plus Long AC Conduit Box (ACCB-L and ACCB-L-L1) connects to the AC side of a Sine Wave Plus inverter and accepts AC conduit runs. It is designed to protect the wiring connections to the inverter and provides room for up to nine additional AC disconnect breakers (Square D, Type QOU, DIN rail mounted) to protect user-specified loads.
There are three models of ACCB-L:
the ACCB-L Basic,
the ACCB-L-L1, and
the ACCB-L-L2.
The ACCB-L contains a ground bar only and provides no wiring.
The ACCB-L-L1 includes a ground wire attached to the ground bar, an AC bypass switch (for a single AC input source) and input/output wiring attached to the AC Input/output Terminals, a Neutral bar with neutral wire installed, and an isolated H
OT bar.
The ACCB-L-L2 configuration is created by field-intalling an ACCB-L2-PCK into an ACCB-L-L1. The ACCB-L2-PCK consists of another field-installable AC Bypass Switch with wiring and an isolated AC Bus Bar.
Knockout panels for additional Bypass Switch Assembly for additional circuit breakers
This guide provides instructions for connecting the Long AC Conduit Box to the inverter and other system components (i.e., utility panel, AC distribution panel, grounding, and generator). It also provides instructions for installing additional Square D™, Type QOU, DIN rail-mounted circuit breakers.
ACCB-L includes:
A
Front Cover
B
Blockoff PlatesGround Bar
B
A
Blockoff
Plates
B
Cover Base
C
D
C D
Din Rail
Figure 1-1
1–2 973-0031-01-01 Rev A
The Sine Wave Plus ACCB-L Basic
Introduction
ACCB-L-L1
G
J
I
F
K
E
H
ACCB-L-L2
L
N
M
K
ACCB-L-L1 includes the components of the ACCB-L and adds the following:
E
One AC Bypass Switch Assembly
F
AC Bus Bar (Neutral)
G
AC Bus Bar (HOT L1)
H
AC Input/output Terminal Block
I
One length white NEUTRAL wire
J
One length green GROUND wire
Figure 1-2
(including wiring)
The Sine Wave Plus Long AC Conduit Box (ACCB-L-L1, and ACCB-L-L2)
ACCB-L-L2 is created by installing the ACCB-L2-PCK to the ACCB-L-L1. ACCB-L2-PCK consists of the following:
Second AC Bypass Switch Assembly
K
Only (including wiring)
L
AC Bus Bar (HOT L2)
M
One length white NEUTRAL wire
N
One length green GROUND wire
*This package is field-installed. The illustration above shows where it would be located when installed in the ACCB-L-L1.
973-0031-01-01 Rev A 1–3
Introduction
Specifications
The following table contains the specifications for the ACCB-L, the ACCB-L-L1, and the ACCB-L-L2. The ACCB-L-L2 is not available pre-built from the factory, but is created by field-installing an ACCB-L2-PCK into a ACCB-L-L1 model.
Table 1-1
Operational and Environmental Specifications for the ACCB-L, ACCB-L-L1, and ACCB-L-L2
ACCB-L ACCB-L-L1 ACCB-L-L2
Dimensions 33" (H) x 11" (W) x 8 3/4" (D)
(84 cm x 28 cm x 23 cm)
33" (H) x 11" (W) x 8 3/4" (D) (84 cm x 28 cm x 23 cm)
This configuration is created by field-installing an ACCB­L2-PCK into an ACCB-L­L1.
Weight 19 pounds (8.6 kg) 24 pounds (10.9 kg) ~2 pounds
Shipping Weight 23 pounds (10.4 kg) 27 pounds (12.2 kg) ~2 pounds
Operating Voltage 120/240 Vac,
60 Hz split-phase
Factory-installed hardware
• Din Rail
• Ground Bar
120/240 Vac, 60 Hz split-phase
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output Terminals
• AC Bypass Breaker
120/240 Vac, 60 Hz split-phase
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output Terminals
• AC Bypass Breaker
Factory-installed wiring
None #6 THHN AWG, rated to
105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - H
• One - H
OT IN OT OUT
#6 THHN AWG, rated to 105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - H
• One - H
a
OT IN OT OUT
Field-installed hardware
N/A ACCB-L2-PCK (needed to
create ACCB-L-L2)
• AC Bypass Breaker (Din Rail-mountable) (w/H and H
OT Out wiring)
• AC Bus Bar (H
OT In
OT L2)
AC Bypass Switch
Bypass None 60 Amp (SPST) 60 Amp (SPST)
Inverter
None 60 Amp (DPST) 60 Amp (DPST)
Input/Output
Rated Temperature 0 to 25 °C
(32 to 77 °F)
Storage Temperature
-55 to +100 °C (-67 to 212 °F)
Enclosure Indoor rated, White,
Powdercoat Finish
0 to 25 °C (32 to 77 °F)
-55 to +100 °C (-67 to 212 °F)
Indoor rated, White, Powdercoat Finish
0 to 25 °C (32 to 77 °F)
-55 to +100 °C (-67 to 212 °F)
Indoor rated, White, Powdercoat Finish
1–4 973-0031-01-01 Rev A
Specifications
Table 1-1
Ratings 120/240 Vac/60 hz., split-
Regulatory Certified by CSA to UL 1741-
Operational and Environmental Specifications for the ACCB-L, ACCB-L-L1, and ACCB-L-L2
ACCB-L ACCB-L-L1 ACCB-L-L2
phase, 60 Amp pass-thru
2001 (First Edition) and CSA C22.2 No. 107.1-01
120/240 Vac/60 hz., split­phase, 60 Amp pass-thru
Certified by CSA to UL 1741­2001 (First Edition) and CSA C22.2 No. 107.1-01
120/240 Vac/60 hz., split­phase, 60 Amp pass-thru
Certified by CSA to UL 1741-2001 (First Edition) and CSA C22.2 No. 107.1-
a
01
a.The ACCB-L-L2 is not available pre-built from the factory, but is created by field-installing an ACCB-L2-PCK into a ACCB-L-L1 model.
Mounting Hole Size =
.265 x 1" (Obround)
Figure 1-3
Slot Size = .188"
(fits up to #8 screw)
ACCB-L Base
Outside
Inverter Side
Slot Size = .188"
(fits up to #8 screw)
Mounting Hole Size =
.265 x 1" (Obround)
ACCB-L Dimensions (not to scale)
973-0031-01-01 Rev A 1–5
Introduction
AC Bypass Switch Assembly
The AC bypass switch assembly in the ACCB-L-L1 is designed for 120 Vac applications and comes with two 60-amp circuit breakers (one SPST and one DPST). The breaker pair is equipped with a lockout rocker that allows only one breaker to be ON at any given time.
The AC bypass switch allows the generator or grid to provide power to the inverter loads in the event that the inverter is disabled for battery maintenance or removed for service.
Factory-installed AC Bypass Breaker
Figure 1-4
Bypass Switch Assembly in the ACCB-L-L1
A second AC bypass switch assembly (ACCB-L2-PCK) is available for dual­inverter installations (ACCB-L-L2 configuration). This field-installed, add-on package includes pre-cut wires for wiring a second inverter in the lower position and provides an additional Isolated Hot Bar for optional installation.
CAUTION: Equipment Damage
Although it is possible to use the second AC Bypass Switch for a second AC input (i.e., generator and grid) to the same inverter, using the AC Bypass Switch for this purpose is not recommended. Switching ON both Bypass switches can cause the two AC sources to short each other out.
For more information see Chapter 3, “Operation” in this guide.
WARNING: Electrical Hazard
If the inverter is removed from service while the bypass is used, live circuits inside the Long AC Conduit Box will not be guarded from accidental contact. Be sure to install the Blockoff Plates to prevent accidental electrocution if the inverter is removed from the system.
1–6 973-0031-01-01 Rev A