Wolf Pro Wall Hood Installation Guide

I NSTALLATION I NSTRUCTIONS
P RO W ALL V ENTILATION H OODS
As you follow these instructions, you will notice WARNING and CAUTION symbols. This blocked information is important for the safe and efficient installation of Wolf equip­ment. There are two types of potential hazards that may occur during installation.
signals a situation where minor injury or product damage may occur if you do not follow instructions.
states a hazard that may cause serious injury or death if precautions are not followed.
WOLF®is a registered trademark of Wolf Appliance, Inc.
CONTACT INFORMATION
Wolf Customer Service: 800-332-9513
Website: wolfappliance.com
3
WOLF PRO WALL VENTILATION HOODS
Dimensions in parentheses are in millimeters unless otherwise specified.
INSTALLATION REQUIREMENTS
IMPORTANT NOTE:
This installation must be completed by a qualified installer or Wolf authorized service center technician.
Installer:
Please read the entire Installation Instructions prior to installation. Save these instructions for the local inspector’s refer­ence, then leave them with the homeowner.
Homeowner:
Please read and keep these instructions for future reference and be sure to read the entire Use & Care Information prior to use.
Any questions or problems about the installa­tion should be directed to your Wolf dealer or Wolf Appliance, Inc. at 800-332-9513. You can also visit our website at wolfappliance.com.
IMPORTANT NOTE:
This appliance must be installed in accordance with National Electrical Codes, as well as all state, municipal and local codes. The correct voltage, frequency and amperage must be supplied to the appliance from a dedicated, grounded circuit which is protected by a properly sized circuit breaker or time delay fuse. The proper voltage, frequency, and amperage ratings are listed on the product rating plate.
Record the model and serial numbers before installing the wall hood. Both numbers are listed on the rating plate, located inside the left wall of the hood shell. Refer to the illustration below.
A)
Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
B)
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
C)
Ducted fans must always be vented to the outdoors.
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
RATING PLATE INFORMATION
Model Number
Serial Number
Rating plate location
Rating plate located
inside hood shell
To reduce the risk of fire and to properly exhaust air, be sure to duct air outside. Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
4
WOLF PRO WALL VENTILATION HOODS
LIST OF MATERIALS
The following is a list of materials shipped with the Wolf Pro wall ventilation hood.
Stainless steel wall hood
Transition with backdraft damper— 24" (610) and 27" (686) deep hoods: attached inside hood (needs to be removed prior to installation)
Decorative stainless steel rail and installa­tion components—(R) model hoods only
Control knobs—two for low-profile and 24" (610) deep hoods, three for 27" (686) deep hoods
Filters (installed in hood)
Grease cups—24" (610) and 27" (686) deep hoods only (shipped loose in carton)
Halogen lamps for lighting—heat lamps for 27" (686) deep hoods are not included
Wood mounting support—24" (610) and 27" (686) deep hoods only
Installation package (part #810555) mounting hardware included:
(10) #8 x 3" (76) Phillips drywall screws, (12) #10 x 1
1
/2" (38) pan head wood screws, (12) #12 flat washers (4) #8 x 3" (76) Phillips sheet metal screws
Installation Instructions
Use & Care Information and product registration card
Wolf logo nameplate
Bottle of Signature stainless steel cleaner
INSTALLATION CONSIDERATIONS
Wolf Pro wall ventilation hoods are recommended for use with all Wolf cooking appliances.
IMPORTANT NOTE:
For optimal performance, a Pro 27" (686) deep wall hood is recom­mended for use with ranges and rangetops that contain a charbroiler or griddle.
Proper installation is the responsibility of the installer. Product failure due to improper installation is not covered under the Wolf Warranty. Refer to the Wolf Pro Ventilation Hoods Use & Care Information for warranty details, or visit our website, wolfappliance.com.
Make sure you have the tools and materials necessary for proper installation.
Warranty service must be performed by a Wolf authorized service center. Wolf is not responsible for service required to correct a faulty installation.
IMPORTANT NOTE:
Wolf Pro ventilation hoods are shipped without the blower assembly. Wolf internal, in-line and remote blower assemblies are available, refer to page
24. Use only a Wolf blower with the Pro wall ventilation hood.
Low-Profile Wall Hood
Low-Profile Wall Hood (R) Rail Option
24" (610) Wall Hood
24" (610) Wall Hood (R) Rail Option
27" (686) Wall Hood
27" (686) Wall Hood (R) Rail Option
5
Dimensions in parentheses are in millimeters unless otherwise specified.
INSTALLATION INSTRUCTIONS
ACCESSORIES
Optional acces­sories are available through your Wolf dealer. To obtain local dealer information, visit the Showroom Locator section of our website, wolfappliance.com.
RECIRCULATING KIT
If you are installing the accessory recirculating kit, refer to the instructions included with the kit before installing the hood. Accessory kits are available through your Wolf dealer.
HORIZONTAL DISCHARGE KIT
Pro low-profile wall hoods come standard from the factory with horizontal or vertical discharge. If a horizontal discharge is needed for installation of a 24" (610) or 27" (686) deep wall hood, an accessory horizontal discharge kit is required. Refer to the instructions included in the kit for complete mounting and blower options. Accessory kits are available through your Wolf dealer.
INSTALLATION CONSIDERATIONS
IMPORTANT NOTE:
Wolf recommends that the Pro wall ventilation hood be installed 30" (762) to 36" (914) above the countertop.
Rail option (R) wall hoods come with a classic stainless steel decorative rail and stand-offs. Optional platinum or brass rails are available to match Wolf dual fuel range bezels. Contact your Wolf dealer for details.
ELECTRICAL REQUIREMENTS
Wolf Pro wall ventilation hoods require a separate, grounded 110/120 V AC, 60 Hz power supply. The service should have its own 15 amp circuit breaker. Locate the electrical supply within the shaded area shown in the Installation Specifications illustration on page 7.
You must follow all National Electrical Code regulations. In addition, be aware of local codes and ordinances when installing your service.
DUCT COVER
If you are installing a Wolf duct cover with the Pro wall hood, refer to instructions on page 18 before installing the hood.
Dimensions in parentheses are in millimeters unless otherwise specified.6
WOLF PRO WALL VENTILATION HOODS
10" (254)
OVERALL
HEIGHT
OVERALL WIDTH
4" (102)
22" (559)
OVERALL DEPTH
12"
(305)
2"
(51)
3
/4" (19)
DIAMETER
OF RAIL
OVERALL WIDTH
4" (102)
24" (610)
OVERALL DEPTH
12"
(305)
18" (457)
OVERALL
HEIGHT
2"
(51)
3
/4" (19)
DIAMETER
OF RAIL
OVERALL WIDTH
27" (686)
OVERALL DEPTH
12"
(305)
18" (457)
OVERALL
HEIGHT
2"
(51)
4" (102)
3
/4" (19)
DIAMETER
OF RAIL
OVERALL DIMENSIONS
LOW-PROFILE WALL HOODS
Overall Widths 30" (762), 36" (914),
42" (1067) and 48" (1219)
Overall Height
10" (254)
Overall Depth (
excluding
rail) 22" (559)
Shipping Weight (shell only) 39–55 lbs
(18–25 kg)
Unit dimensions may vary to ±1/8" (3).
24" (610) DEEP WALL HOODS
Overall Widths 30" (762), 36" (914),
42" (1067), 48" (1219), 54" (1372),
60" (1524) and 66" (1676)
Overall Height
18" (457)
Overall Depth (
excluding
rail) 24" (610)
Shipping Weight (shell only) 67–126 lbs
(30–57 kg)
Unit dimensions may vary to ±1/8" (3).
27" (686) DEEP WALL HOODS
Overall Widths 30" (762), 36" (914),
42" (1067), 48" (1219), 54" (1372),
60" (1524) and 66" (1676)
Overall Height
18" (457)
Overall Depth (
excluding
rail) 27" (686)
Shipping Weight (shell only) 92–163 lbs
(42–74 kg)
Unit dimensions may vary to ±1/8" (3).
Low-Profile Wall Hood
shown with (R) rail option
24" (610) Deep Wall Hood
shown with (R) rail option
27" (686) Deep Wall Hood
shown with (R) rail option
7
INSTALLATION INSTRUCTIONS
E
6"
(152)
5"
(127)
LOCATION OF ELECTRICAL
30" TO 36"
(762–914)
TO COUNTERTOP
10" (254)
HEIGHT
OF HOOD
22" (559)
DEPTH OF HOOD
WIDTH OF HOOD
30" TO 36"
(762–914)
TO COUNTERTOP
NOTE: Pro low-profile wall hoods have an adjustable discharge.
30" TO 36"
(762–914)
TO COUNTERTOP
30" TO 36"
(762–914)
TO COUNTERTOP
18" (457)
HEIGHT
OF HOOD
24" (610) 27" (686)
DEPTH OF HOOD
WIDTH OF HOOD
NOTE: 24" (610) and 27" (686) deep wall hoods have a vertical discharge. A horizontal discharge kit is available as a sales accessory.
E
6"
(152)
5"
(127)
LOCATION OF ELECTRICAL
INSTALLATION SPECIFICATIONS
Low-Profile Wall Hoods
24" (610) and 27" (686) Deep Wall Hoods
8
WOLF PRO WALL VENTILATION HOODS
TRANSITION SPECIFICATIONS
The illustrations and chart provide dimensions specific to Pro low-profile wall hood models with different transition applications. These dimensions are critical for proper installation.
Low-Profile Wall Hoods – 10" (254) Round Accessory Transition (for use with in-line or remote blower)
Model (A) (B) (C) (D)
PW302210(R) 30" (762) 9" (229) 143/4" (375) 55/8" (143)
PW362210(R) 36" (914) 9" (229) 173/4" (451) 55/8" (143)
PW422210(R) 42" (1067) 9" (229) 203/4" (527) 55/8" (143)
PW482210(R) 48" (1219) 9" (229) 233/4" (603) 55/8" (143)
Low-Profile Wall Hoods – 500 CFM Internal Blower (vertical discharge)
Model (A) (B) (C) (D)
PW302210(R) 30" (762) 11/2" (38) 143/4" (375) 25/8" (60)
PW362210(R) 36" (914) 11/2" (38) 173/4" (451) 25/8" (60)
PW422210(R) 42" (1067) 11/2" (38) 203/4" (527) 25/8" (60)
PW482210(R) 48" (1219) 11/2" (38) 233/4" (603) 25/8" (60)
Low-Profile Wall Hoods – 500 CFM Internal Blower (horizontal discharge)
Model (A) (B) (C) (D)
PW302210(R) 30" (762) 11/2" (38) 143/4" (375) 2" (51)
PW362210(R) 36" (914) 11/2" (38) 173/4" (451) 2" (51)
PW422210(R) 42" (1067) 11/2" (38) 203/4" (527) 2" (51)
PW482210(R) 48" (1219) 11/2" (38) 233/4" (603) 2" (51)
Letters correspond to those in the illustrations.
Low-Profile Wall Hoods – 10" (254) Round Accessory Transition
Low-Profile Wall Hoods – 500 CFM Internal Blower (vertical discharge)
Low-Profile Wall Hoods – 500 CFM Internal Blower (horizontal discharge)
IMPORTANT NOTE:
The transition included with the 500 CFM internal blower accommo­dates 3
1
/4" (83) x 10" (254) ductwork. An
optional 3
1
/4" (83) x 10" (254) to 8" (203) round transition is available as a sales accessory. Contact your Wolf dealer for details.
Low-Profile Wall Hoods –
No Transition
B
HEIGHT OF
TRANSITION
TO CENTER
OF TRANSITION
D
D
TO CENTER
OF TRANSITION
C
TO CENTER
OF TRANSITION
WIDTH
OF HOOD
B
HEIGHT OF
TRANSITION
A
C
TO CENTER
OF TRANSITION
A
WIDTH
OF HOOD
RECTANGULAR
CUT-OUT
14"
(356)
1
3
"
/4
(83)
D
TO CENTER
OF
TRANSITION
A
WIDTH
B
HEIGHT OF
TRANSITION
C
TO CENTER
OF TRANSITION
OF HOOD
9
Dimensions in parentheses are in millimeters unless otherwise specified.
INSTALLATION INSTRUCTIONS
24" (610) and 27" (686) Deep Wall Hoods –
Transition Included
24" (610) Deep Wall Hoods
Model (A) (B) (C) (D)
PW302418(R) 30" (762) 9" (229) 143/4" (375) 55/8" (143)
PW362418(R) 36" (914) 9" (229) 173/4" (451) 55/8" (143)
PW422418(R) 42" (1067) 9" (229) 203/4" (527) 55/8" (143)
PW482418(R) 48" (1219) 9" (229) 233/4" (603) 55/8" (143)
PW542418(R) 54" (1372) 9" (229) 263/4" (679) 55/8" (143)
PW602418(R) 60" (1524) 9" (229) 293/4" (756) 55/8" (143)
PW662418(R) 66" (1676) 9" (229) 323/4" (832) 55/8" (143)
27" (686) Deep Wall Hoods
Model (A) (B) (C) (D)
PW302718(R) 30" (762) 9" (229) 143/4" (375) 55/8" (143)
PW362718(R) 36" (914) 9" (229) 173/4" (451) 55/8" (143)
PW422718(R) 42" (1067) 9" (229) 203/4" (527) 55/8" (143)
PW482718(R) 48" (1219) 9" (229) 233/4" (603) 55/8" (143)
PW542718(R) 54" (1372) 9" (229) 263/4" (679) 55/8" (143)
PW602718(R) 60" (1524) 9" (229) 293/4" (756) 55/8" (143)
PW662718(R) 66" (1676) 9" (229) 323/4" (832) 55/8" (143)
Letters correspond to those in the illustrations.
TRANSITION SPECIFICATIONS
The illustration and chart provide dimensions specific to Pro 24" (610) and 27" (686) deep wall hood models. These dimensions are critical for proper installation.
B
HEIGHT OF
TRANSITION
TO CENTER
OF TRANSITION
D
C
TO CENTER
OF TRANSITION
A
WIDTH
OF HOOD